space heating load

Upload: asp9924

Post on 03-Jun-2018

230 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 Space Heating Load

    1/33

    Chapter 6. Space Heating Lo

  • 8/13/2019 Space Heating Load

    2/33

    Heating Load:

    1- Heat loss through walls, windows,etc

    2- Heat to warm outside air (1) desired (2) infiltration

    The ideal heating system would provide just enough heat to m

    loss from structure.

    Load is not a constant

    Outdoor temp changes as well as wind velocity, sunlight (sola

    heat gains, appliances, people.

    Heating system must handle the coldest outside average tem

    the year.

    Most equipment operate at partial load most of the time

    Unheated Rooms: To< Tu< Ti Assume steady state heat transfer

    )( oi TTUAq =&

  • 8/13/2019 Space Heating Load

    3/33

    The following Factors should be considered

    performing heat load calculations:1. Is the heat capacity of the structure high or low ?

    2. Is the structure insulated ?

    3. Is the structure exposed to high wind ?

    4. Is the ventilation or infiltration load high ?

    5. Is there more glass area than normal in the structure ?

    6. During what part of the day will the structure be used ?

    7. What is the nature of occupancy ?

    8. Will there be long periods of operation at reduced indoor tempe

    9. What is the amplitude between maximum and minimtemperature in the locality ?

    10. Are there local conditions that cause significant variattemperatures listed ?

    11. What auxiliary heating devices will be in the building ?

    12. What is the expected cost of fuel or energy ?

  • 8/13/2019 Space Heating Load

    4/33

  • 8/13/2019 Space Heating Load

    5/33

    Chapter 4 Design Temp for inside. Low end (70F at = 30%) of

  • 8/13/2019 Space Heating Load

    6/33

    Representative inside air design tempera

  • 8/13/2019 Space Heating Load

    7/33

  • 8/13/2019 Space Heating Load

    8/33

  • 8/13/2019 Space Heating Load

    9/33

  • 8/13/2019 Space Heating Load

    10/33

  • 8/13/2019 Space Heating Load

    11/33

  • 8/13/2019 Space Heating Load

    12/33

  • 8/13/2019 Space Heating Load

    13/33

    Air change method, ACH Air Chang

    0aslowasbecanand0.25.0

    hourperchangeairofnumberACH

    ))((

    Re =

    =

    sidential

    T

    ACH

    C

    VACHQ&

    Experience shows nominal values for air changes per h

  • 8/13/2019 Space Heating Load

    14/33

    Experience shows nominal values for air changes per h

  • 8/13/2019 Space Heating Load

    15/33

    Crack Method

    Q=AC Pn

    A= effective leakage area of the cracks

    C= flow coefficients, which depends on the type of crack

    of flow in the crackP=outside - inside pressure difference, Po-Pin=exponent that depends on the nature of the flow crack

  • 8/13/2019 Space Heating Load

    16/33

    Crack method is complex but in general more accurat

    We need to be able to calculate P to put in the equa

    essureBuildingSw PPPP Pr++=

    Pw=Pressure difference due to wind

    Cp= function of angle of wind, Height and length to width ratio of bu

    Ps=Pressure difference stack effect

    Cd range from 1 for buildings with no doors in the stairways to abou

    for modern office buildings

    Pp=Pressure difference due to building pressurization

    wwindPP =

    cgaR

    ghoPdC

    sP =

  • 8/13/2019 Space Heating Load

    17/33

    Figure 6.1 Windows and door infiltration Characteristic

    Figure 6.2 Variation of wall averaged pressure coefficierise buildings

    Figure 6.3 Variation of wall averaged pressure coefficiebuildings

    Figure 6.4 Average roof pressure coefficients for a tall b

    Figure 6.5 Pressure difference due to stack effect. Figure 6.6 Curtain wall infiltration for one room or one

    Figure 6.7 Infiltration through cracks around a closed sw

    Figure 6.8 Swinging door infiltration characteristics wit

    Figure 6.9 Flow coefficient dependence on traffic rate

    Supply Air for Space Heating Source Media for space heating

  • 8/13/2019 Space Heating Load

    18/33

    Figure 6.1 Windows and doo

    infiltration Characteristic

  • 8/13/2019 Space Heating Load

    19/33

  • 8/13/2019 Space Heating Load

    20/33

    Fig. 6.2 Variation of wall averaged pre

    coefficients for low rise buildings

  • 8/13/2019 Space Heating Load

    21/33

    Fig. 6.3 Variation of wall averaged pre

    coefficients for tall buildings

  • 8/13/2019 Space Heating Load

    22/33

    Fig. 6. 4 Average roof pressure

    coefficients for a tall building

    Fig. 6. 5 Pressure differe

    stack effect.

  • 8/13/2019 Space Heating Load

    23/33

    Fig.6.6 Curtain wall infiltration for

    one room or one room floor

    Fig. 6.7 Infiltration throug

    around a closed swingin

  • 8/13/2019 Space Heating Load

    24/33

  • 8/13/2019 Space Heating Load

    25/33

    Fig. 6.8 Swinging door infiltration

    characteristics with traffic

    Figure 6.9 Flow coeff

    dependence on traffic

  • 8/13/2019 Space Heating Load

    26/33

    Procedure for calculating heat losses from a s

    1. Select the design outdoor weather conditions: temperature, hum

    direction, and speed.

    2. Select the design indoor air temperature to be maintained

    space when outside design conditions exist.

    3. Estimate temperatures in adjacent un-heated spaces.

    4. Select or compute the heat transmission coefficient (U fbuilding components through which heat losses are to be calcu

    5. Determine all surface areas through which the heat is lost.

    6. Compute heat transmission losses for each kind of wall, glass

    and roof in the building by multiplying the heat transmission

    each case by the area of the surface and the temperature diffe

    indoor and outdoor air, or adjacent unheated space.

    7. Compute heat losses from basement or grade-level slab floo

    presented in Chapter 5.

  • 8/13/2019 Space Heating Load

    27/33

    8. Select infiltration air quantities and compute the heat loinfiltration around doors and windows.

    9. When positive ventilation using outdoor air is provided by an

    air-conditioning unit, the energy required to warm the outdootemperature must be provided by the unit. The principle for calload component is identical to that for infiltration. If mechanicathe room is provided in an amount equal to the out-door air drunit, the unit must also provide for the natural infiltrationmechanical exhaust is used, and the outdoor ventilation air sup-exceeds the natural infiltration that would occur without vent

    infiltration may be neglected.10. The sum of the transmission losses or heat transmitted through

    walls, floors, ceiling, glass, and other surfaces, plus the energy athe cold entering air by infiltration or required to replace mechrepresents the total heating load.

    11. In buildings that have a reasonably steady internal heat releasemagnitude from sources other than the heating system, a comp

    heat release under design conditions should be made and dedtotal of the heat losses computed above.

    12. Additional heating capacity may be required for intermibuildings to bring the temperature of the air, confining surfacecontents to the design indoor temperature within a specified tim

  • 8/13/2019 Space Heating Load

    28/33

  • 8/13/2019 Space Heating Load

    29/33

  • 8/13/2019 Space Heating Load

    30/33

    Source Media for space heating

    Hot water as heating media

    q = mwcp (t2 t1)

    where:

    q = heating required, Btu/hr or W

    mw = mass flow rate of hot water, lbm/hr or kg/s

    cp = specific heat of water, Btu/lbm or kJ/(kg-C

    t2 = water temperature leaving coil, F or C

    t1 = water temperature entering coil, F or C

    Assuming that cp is constantq = 500 Qgpm(t2 t1) English Units

    q = 4.2 QL/s(t2 t1) SI units

  • 8/13/2019 Space Heating Load

    31/33

    Source Media for space heating

    Steam as heating fluid

    q = mv (i2 i1)

    where:

    q= heating required, Btu/hr or Wmv = mass flow rate of the vapor, lbm/hr or kg/s

    i2 = enthalpy of the vapor leaving the coil, Btu/lbm o

    i1 = enthalpy of the vapor entering the coil, Btu/lbm

    If saturated vapor is the heating medium,

    i2 i1 = the enthalpy of vaporization, i fg.

  • 8/13/2019 Space Heating Load

    32/33

    Source Media for space heating

    Furnace Heating

    In the case of a furnace where combustion gases

    air directly, the heating value of the fuel and a fu

    efficiency must be known. A general relation from

    mfor Qfcan be found is

    qf= mf(HV)= Qf(HV)where:

    qf = heating required, Btu/hr or W

    mf = rate at which fuel is used, lbm/hr or kg

    Qf = Volume flow rate ft3/min or m3/s

    HV = heating value of the fuel, Btu/lbm or kJ

    = furnace efficiency

  • 8/13/2019 Space Heating Load

    33/33