Page 1: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

Solutions for Utility-Scale, Power Management and Grid Integration

Page 2: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

2

Ready for the Energy Challenges

Joinning technology and expertise we offer the most advanced energy integration solutions

Page 3: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

3

Dear friends,

Javier Landero Cruz CEO of GPTech

After more than a decade of dedication, GPTech continues growing upon its base, built on a solid and singular knowledge on energy integration, ready to overcome every new barrier that our customers could find in the development of new projects within the energetic revolution in which we are immersed. In recent years we have participated in many relevant projects, achieving new and innovative ways to solve the hardest technological and operational challenges- This makes our company a reference in the renewable energy sector, especially when environmental and grid stability conditions aren’t favorable to the use of new renewable energy sources.

Analyzing the sector’s evolution, we detect a strong trend to choose the renewable way to solve the lack of energy in regions with high difficulty of access to conventional sources. Furthermore, if we take into account the strong commitment of major and emerging economies with the development of dis-tributed generation. We believe that now it is the time of making possi-ble the smart use of new solutions based on the in-formation technology joined with a solid knowledge of grid management and especially in power elec-tronic applications.

In order to face these challenges, GPTech has developed a range of solutions and products looking for reliability, efficiency and specially flexibility to give an early answer to our customers. With the release of the family WD3.0 of power converters, we are giving response to the market trend of raising voltage level of the power source in both the field of photovoltaic panels and in battery groups. Along with this hardware development, we offer the most advanced control algorithms allowing our systems to give integrated solutions to the key technological challenges of Grid Operation and Power Quality.

Obviously, difficulties will always remain... a continuous improvement through innovation combined with a strong investment in the research and development of new products is key to further enhance our capabilities, always thinking in our vision of “Being a Model in the Energetic Revolution”, to continue supporting our clients with the best solutions.

Joinning technology and expertise we offer the most advanced energy integration solutions

Page 4: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA
Page 5: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

5

Technologies that add value ...

PROFITTo achieve the maximum bene-fit and increase profitability, it is necessary to obtain the best performance in all situations.

The success of a sustainable in-crease of renewable generation into national transmission grid is based on its stable behavior.

Our solutions are the key to de-liver the highest quality power signal with the best performance.

We are pioneers in developing solutions for utility-scale with great complexity in grid inte-gration, operating since 2002 in places like Vietnam, Galapagos (Ecuador), Puerto Rico, Jamaica, South Africa or Maldives Islands.

RELIANCEBecause we offer a contrasted experience in grid integration under the hardest ambient condition and most demanded technical requirements. Today, GPTech is a leader com-pany in the development of power electronic devices all over the world, which uses the state of the art technology to provide new solutions for the Energy Sector.

GPTech is a consolidated tech-nological reference in the major markets, as well as those who are increasing their energy capa-city as South Africa, Chile or Peru.

The expertise of our team allows to adjust the timing of network integration and to overcome the most demanding requirements, adding robustness to the grid.

CAPACITYIn a field where technology ad-vances so fast, it is critical to select partners with the neces-sary experience and confiden-ce to overcome every techno-logical and financial barriers. We offers advanced manage-ment systems that allow a more agile, predictable and contro-llable way to meet the needs of the network operators, re-gardless of the energy sources.

This capability has allowed us to collaborate with different or-ganisms in the development of grid connection requirements, which have become an inter-national reference for the sus-tainable growth of renewables.

Page 6: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

6

In GPTech we are committed to society in all aspects, and we are con-

vinced that the sum of little gestures can make great changes.

The environment is our natural allied, so we take care of it every day

and demanding to the ones around us doing the same. We boost our

innovation in electronics technology towards achieving social and en-

vironmental improvements.

The company is always involved in different social causes, trying to

maximize the benefit for our clients, suppliers, and the society as a

whole, promoting a culture of continuous improvement in the mana-

gement of all processes and activities.

We also care about a healthy life for our crew, promoting sport com-

petitions and other social activities that foster their companionship.

Corporate Social Responsability

Page 7: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

7

Our activity is developed following a ethical code which cornersto-

ne are our commitment to employees’ rights and the respect for

the environment.

Because we only understand a way to work where responsability

and honesty, fairness, accuracy and transparency are essentials

the points...

A real sustainable future depends on ethical commitments

Page 8: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

8

Our main objective is to enable the emergence of new opportunities for the development of clean and sustainable energy even under the hardest conditions.

With this philosophy we have developed and provided the power plant control for Mount Sig-nal, one of the biggest PV Plant operating in USA with 256 MW.

Moreover, this ability is what has made us the leaders in complex enviroments, providing our solutions in the first utility scale plants in diffe-rent locations as Chile, Argentina, Perú, Ecuador, Puerto Rico, Guatemala or Honduras.

We are ready to successfully face the new tech-nological challenges of the energy industry, to ensure that energy arrives in the best conditions of stability for more people every day and elimi-

nate all barriers in his way.

Technologies that go beyond the boundaries...

Desierto de Atacama, Chile (100 MW)

Marcovia, Honduras (35MW)

Creating new opportunities for energy development...

Page 9: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

9

Technologies that go beyond the boundaries...

Horus, Guatemala (80MW)

Illumina, Puerto Rico (20MW)Cañada Honda, Argentina (5MW)

Majes-Repartición, Perú (80MW)

Creating new opportunities for energy development...

Page 10: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

10

Page 11: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

11

Contents

SmartPV

EnergyReserve

GridCapabilities

EMSystems

Page 12: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

12

Global vision to solve the renewable integration into the Electric Grids

For over a decade, our experts develop innovative solutions to solve the new challenges emerging from the world growth of renewable energy sector.

GPTech develops technology and products for power conversion and management achieving total control of the generation chain to obtain the best performance in utility-scale projects.

For every new stage, we enrich our vision with the contribution of key industry players, so that our products and services provide a comprehensive response to the real needs of each project.

Complete Inverter Stage Solutions for PV Large-Scale Plants with advanced control

and power regulation capacities to meet any technical requirement.

Storage turnkey products which solves all the technological aspects with a contrasted set of solutions for the

complete range of applications

GPTECH APIS INVERTER STATIONS

BATTERIES AND APCS FOR POWER CONDITIONING SYSTEMS FROM 1 TO 3.3 MW

DIESEL GENSET CONTROL FOR HYBRID POWER PLANTS

Page 13: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

13

Leaders in STATCOMs solutions for renewable signal enhacement and ancillary services. Our power electronics solutions provide to the utility plants the key to reach the best power estability and superior performance.

Optimised designs for Hybrid Renewable & Fuel to reduce the fuel compsumption and saving money while the facility is enhanced with our high performance management and control products

A new level in grid stability. GPTech Energy Management Systems have been created to obtain a complete control of the power to be delivered, configured for each individual case with our strong expertise.

CONTAINERISED STATCOMS FOR LARGE SCALE PLANTS

DIESEL GENSET CONTROL FOR HYBRID POWER PLANTS

UTILITY-SCALE SOLUTIONS

Page 14: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

14

Advanced Solutions for PV Management and Control

Page 15: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

15

GPtech SmartPV brings you the most advanced set of products to deliver the power generated with top efficiency and stability, under all conditions.

Technology created for Large-Scale Plants, with additional features to ensures a total control of the power signal.

Because we know that every project is unique, we design flexible solutions to cover all the requirements. .

Page 16: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

16

SmartPV Power InvertersBreakthrough technology designed for the utility-scale

ADVANCED POWER CONTROL

• Remotecontrolofactiveandreactivepower.

• Ramp rate response of programmable power in order to

guaranteethegridbalance.

• DifferentmodesofoperationforVoltageRideThrough

1.Maximumreactivepowerinjection

2.Constantpowerfactor

3.Nocurrentinjection

4.Voltagedroopcompensation

• Instantpowerregulationaccordingtofrequencyvariations.

HIGHEST FLEXIBILITY IN INVERTER PERFORMANCE• Flexible power operation range based on the required

powerfactor.

•WideDCoperationrange.

• Maintainsmaximumpoweratextremeambientconditions.

• Redundantaircoolingsystemforbestperformanceinex-

tremeclimates.

Page 17: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

17

BEST EXPERTISE IN POWER ELECTRONICS

• Outdoorandindoormodels

• Compact,reliableandrobustdesignforallclimateconditions

• Convenientfrontaccessforserviceandmaintenance

• Bestpeakefficiencyofover98%

•Widethermaloperationrange4oF/140oF(-20oC/60oC)

New PVWD family ready for 1100-1500v input level

Page 18: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

18

ABOVE THE STANDARDS

Ourequipmentoperatesalwaysathigherlevelsthanindustry

standards.

Thisfactdoesnotonlyreflectsourphilosophybasedonoffe-

ringthehighestquality toourcustomers. Italsoassuresa

innovationvaluetoourtechnologyforfacingthenextchallen-

gesonthesector.

.

SmartPV Power InvertersReliability guaranteed from the design stage

A DEEPER INSIGHT TO ACHIEVE THE BEST PERFORMANCE

Withadvancedwarrantyplanstomeeteveryneed,theGP-

Techqualityassuranceplansaredesignedtooffersupport

fortherealneeds,basedonourexperienceintheentireva-

luechainofoursolutions, fromthedesigningstageto the

estimadedend-of-lifeoftheprojects.

READY FOR THE LATEST GRID CODES

GPTechSmartPVInverterscomplywiththemostdemanding

gridcodesintheworld.

Theyadapttothenecessitiesofanymarketduetoaflexible

poweroperationrangedependingonthepowerfactor,with

aneasyintegrationtothegridandlowpowerconsumption,

Thesedevicesofferremotecontrolofactiveandreactive

power,aswellasramprateresponseguaranteeingthegrid

stability.

Hence,wehaveachievedtosupplyandinstallthefirstUtility

Scalewithinvertersover2400m.abovesealevel,orbeingthe

firstcompanyinmeetingthemostdemandinggridcodere-

quirementsprevailingindifferentcountries.

Page 19: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

19

Page 20: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

20

SmartPV Central Inverters UL

PV500WD1-I / PV630WD1-I / PV750WD1-I / PV900WD1-I

SmartPV-WD UL

Optimised Designs for the USA Market

Voltage Regulation System (VRS)

Frequency Response and Advanced Regulation Ramp-Rate Control Better Reactive Power

Capacity

PV500WD1-O / PV630WD1-O / PV750WD1-O / PV900WD1-O

Page 21: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

21

Notes1. At 100% U AC, nom and cos ϕ = 1 2. Further AC voltages can be configured 3. At rated AC power @PF=1 @ 25ºC (77 ºF). Self-consumption is not considered in the efficiency measurement4. Self-consumption at rated operation

PV500WD1 PV630WD1 PV750WD1 PV900WD1DC Input Voltage range (MPPT) (1) 395 - 825 Vdc 495 - 825 Vdc 585 - 825 Vdc 705 - 825 Vdc

Maximum DC voltage 1000 Vdc

Maximum input current 1530 A

DC inputs (optional external box) 10 - 20. Protected by fuses

AC Output

Rated AC voltage 3 x 240 Vac 3 x 300 Vac 3 x 355 Vac 3 x 430 Vac

AC voltage range (2) 216 - 264 Vac 270 - 330 Vac 319 - 391 Vac 387 - 473 Vac

Frequency rated 50/60 Hz

Frequency operation range 47 - 63 Hz

Rated AC power @ 50oC 560 kVA 700 kVA 830 kVA 1000 kVA

Rated AC power @ 25oC 600 kVA 750 kVA 890 kVA 1080 kVA

Rated AC power @ 50oC and PF of 0,9 500 kW 630 kW 750 kW 900 kW

Maximum output current 1450 A

Total Harmonic Distortion (THD) <3%

Power Factor at rated power adjustable (0.9 inductive ... 0.9 capacitive)

Galvanic insulation No

Efficiency

Maximum European efficiency (3) 98,00% 98,30% 98,49% 98,68%

Maximum CEC effienciy (3) 97,99% 98,29% 98,48% 98,67%

Self-consumption at night <= 200 W

Self-consumption in operation (4) <= 3 kW

Ambient conditions

Operation temperature -4oF/140oF (-20oC/60oC)

Operation ambient temperature (without derating) -4oF/122oF (-20oC/50oC)

Storage and transport temperature -22oF/149oF (-30oC/65oC)

Maximum relative humidity 95% without condensation

Maximum fresh air consumption 4000 m3/h

Maximum altitude above the sea level 3000 m

Mechanical characteristics

Dimensions (H / W / D) INDOOR: 2100 x 2000 x 780 mm / 82,67 x 78,74 x 30,70 inOUTDOOR: 2300 x 2000 x 845 mm / 90,55 x 78,74 x 33,26 in

Weight INDOOR: 1870 kg (4122 Ibs)OUTDOOR: 2100 kg (4629 Ibs)

Environment rating INDOOR: NEMA 2, IP20OUTDOOR: NEMA 3R, IP54

AC Protections

AC over voltage protection Class II

Anti-islanding Yes

Grid voltage variations Yes

Frequency failures Yes

Asymmetric currents Yes

Low Voltage Ride Through (LVRT) Capability Yes

DC Protections

DC overvoltage protection Class II

Inverter shutting down on overload error Yes

PV-field isolation detector Yes

Panel Disconnnection Capability Yes. Contactor

Other Protections

Breaker protections of auxiliary systems Yes

Auxiliary systems overvoltage protection Yes

Power Control Features

Reactive control by external signal Yes

Reactive control by internal configuration Yes. Timetable PF configuration or voltage dependent function

Reactive injection in LVRT Yes. Configurable Operation Mode

Over frequency active power response Yes. Configurable droop

Ramp rate control Yes. Under irradiance value restriction

External power limitation Yes. Control allows continuous limit values

STATCOM mode for night compensation Optional (additional elements required)

Interfaces

Touch-HMI Optional

MODBUS RTU/TCP communication protocol Yes/ Yes

Luminous indicator, start/stop control and emergency stop Yes

Master / Slave Mode Optional (additional elements required)

Legal standards

UL1741 Yes

United States - UL Listing Mark Yes

Canada - cUL Listing Mark Yes

IEEE 1547 Yes

CSI/CEC Performance Testing (California) Yes

IEC 62109-1, IEC 62109-2 Yes

Page 22: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

22

SmartPV Central Inverters International

SmartPV-WD International

Extended Range to meet all the requirements

Extreme Robustness

Frequency Response and Advanced Regulation

Voltage Regulation System (VRS)

Ramp-Rate Control Flexibility and wide range of features

PV500 FAMILY: PV500WD2-I / PV540WD2-I / PV500WD2-O / PV540WD2-O PV630 FAMILY: PV630WD2-I / PV675WD2-I / PV630WD2-O / PV675WD2-OPV750 FAMILY: PV750WD2-I / PV800WD2-I / PV750WD2-O / PV800WD2-OPV900 FAMILY: PV900WD2-I / PV950WD2-I / PV975WD2-I / PV900WD2-O / PV950W2-O / PV975WD2-O

PV950WD2 efficiency curve

@ Rated AC power @PF=1 @ 35ºC (95ºF). Self-consumption is not considered in the efficiency measurement

Page 23: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

23

Notes1. At 100% U AC, nom and cos ϕ = 1 2. Further AC voltages can be configured 3. Self-consumption at rated operation

FAMILY PV500 FAMILY PV630 FAMILY PV750 FAMILY PV900PV500WD2 PV540WD2 PV630WD2 PV675WD2 PV750WD2 PV800WD2 PV900WD2 PV950WD2 PV975WD2

DC Input Voltage range (MPPT)(1) 375 – 825Vdc 455 – 825Vdc 525 – 825Vdc 580 – 825Vdc 608 – 825Vdc 620 – 825Vdc

Max. input voltage 1000Vdc

Max. DC Input Current 1800A 1900A 1800A 1900A 1800A 1900A 1900A 1900A 1900A

2200A 2300A 2200A 2300A 2200A 2300A 2300A 2300A 2300A

AC Output

Nominal AC Voltage 3 x 240Vac 3 x 300Vac 3 x 355Vac 3 x 400Vac 3 x 420Vac 3 x 430Vac

AC voltage range(2) 216 – 264Vac 270 – 330Vac 319 – 391Vac 360 – 440Vac 378 – 462Vac 387 – 473Vac

Frequency 50/60Hz

Frequency operation range 47 – 63Hz

Rated AC power @ 50ºC (122 ºF) 560kVA 600kVA 700kVA 750kVA 830kVA 890kVA 1005kVA 1055kVA 1080kVA

Rated AC power @ 35ºC (95 ºF) 600kVA 645kVA 750kVA 805kVA 890kVA 950kVA 1075kVA 1125kVA 1155kVA

Rated AC power @ 50ºC (122 ºF) and PF of 0.9 500kW 540kW 630kW 675kW 750kW 800kW 900kW 950kW 975kW

Maximum output current 1450A 1600A 1450A 1600A 1450A 1600A 1600A 1600A 1600A

Total Harmonic Distortion (THD) < 3%

Power factor Adjustable

Galvanic Isolation No

Efficiency

European efficiency 98.11% 98.11% 98.35% 98.35% 98.45% 98.45% 98.55% 98.57% 98.59%

CEC efficiency 98.10% 98.10% 98.37% 98.37% 98.50% 98.50% 98.61% 98.64% 98.66%

Self-consumption in standby <= 240W

Self-consumption in operation (3) <= 2kW

Ambient Conditions

Operation ambient temperature 14ºF / 140ºF (-10ºC / 60ºC)

Operation ambient temp. without derating 14ºF / 95ºF (-10ºC / 35ºC)

Storage and transport temperature -22ºF / 149ºF (-30ºC / 65ºC)

Maximum relative humidity 95% without condensation

Fresh air consumption 3500m3/h

Max. altitude above sea level 3000m

Mechanical characteristics

Dimensions (H / W / D) INDOOR: 2100 x 2000 x 780 mm / 82,67 x 78,74 x 30,70 inOUTDOOR: 2300 x 2000 x 845 mm / 90,55 x 78,74 x 33,26 in

Weight INDOOR: 1870kg (4122lbs)OUTDOOR: 2100kg (4629lbs)

Environment rating INDOOR: NEMA 2, IP20OUTDOOR: NEMA 3R, IP54

AC Protections

AC overvoltage protection Yes

Anti-islanding Yes

Grid voltage variations Yes

Frequency failures Yes

Asymmetric currents Yes

Low Voltage Ride Through (LVRT) capability Yes

DC Protections

DC overvoltage protection Yes

Inverter shutting down on overload error Yes

PV-field isolation detector Yes

Panel disconnection capability Yes. DC Contactor

Other Protections

Breaker protections of auxiliary systems Yes

Auxiliary systems overvoltage protection Yes

Power Control Features

Reactive control by external signal Yes

Reactive control by internal configuration Yes. Timetable PF configuration or voltage dependent function

Reactive injection for LVRT Yes. Configurable operation mode

Over frequency active power response Yes. Configurable droop

Ramp rate control Yes. Under irradiance value restriction

Reactive power or active power priority Configurable

External power limitation Yes

STATCOM mode: Reactive injection at night Optional (requires additional elements)

Interfaces

Touch-HMI Optional

MODBUS ommunication protocol Optional

Luminous indicator, start/stop control and Emergency Stop Yes

Legal standards

IEC 62109-1, IEC 62109-2 Yes

NEC Compliance Yes

Page 24: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

24

SmartPV High-Capacity Modular Inverter - 1000Vdc Input Voltage Level

PV940WD3LV450 / PV1880WD3LV450 /PV2820WD3LV450

SmartPV-WD3 1100V

Highest Power Capacity and Scalable Integration

Easy Direct IntegrationPower Control and Grid

Stability advanced features

Optimized cost solution for Large-Scale

InstallationsOutdoor scalable

Solutions up to 3MW

PVWD3 family is intended to be coupled to a distribution substation through a MV trans-former for galvanic isolation.

With an easy integration to the grid and low power consumption, these devices allows remote control of active and reactive power, as well as ramp rate response guaranteeing grid stability.

Efficiency curve for maximum, rated and minimal DC-link voltage of the PV-WD3LV450 models (self-consumption is not considered)

PV-WD3 1100V efficiency curve

Page 25: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

25

PV940WD3LV450 PV1880WD3LV450 PV2820WD3LV450

DC Input

Voltage range (1) 670 – 950Vdc

Max. input voltage 1100Vdc

Rated input current @ 670Vdc, Tamb=35ºC 1590A 3180A 4770A

Max. short circuit input current 1925A 3850A 5775A

Max. Number of DC Inputs (2) Up to 12 Up to 24 Up to 36

DC Cabinet Integrated

AC Output

Frequency 50/60Hz

Frequency operation range 47 – 63Hz

Rated AC power @ 95ºF/35ºC 1045 kVA 2090 kVA 3135 kVA

Rated AC power @ 122ºF/50ºC 940 kVA 1880 kVA 2820 kVA

Rated voltage (3) 450 Vac

Total Harmonic Distortion (THD) < 3%

Power factor (PF) Adjustable

Efficiency

Efficiency(4) >98%

Self-consumption in standby < 250W < 400W < 550W

Self-consumption in operation(5) < 3kW < 5.5kW < 8kW

Ambient Conditions

Operation ambient temperature 14ºF / 140ºF (-10ºC / 60ºC)

Operation ambient temperature (without de-rating) 14ºF / 122ºF (-10ºC / 50ºC)

Storage and transport temperature -40ºF / 149ºF (-40ºC / 65ºC)

Maximum relative humidity 100%

Fresh air consumption 5750 m3/h 11500 m3/h 16500 m3/h

Max. altitude above sea level without derating 1000m

Max. altitude above sea level allowed 4000m

Mechanical characteristics

Dimensions (W x D x H) 1710 x1000 x2200mm 3420 x1000 x2200mm 4630 x1000 x2200mm

Protection degree NEMA 3R, IP54

Power control features

Anti-islanding protection Yes

Active power curtailment Yes

Active power ramp rate constraint Yes

Reactive power closed-loop control Yes

Power factor closed-loop control Yes

Frequency Ride Through (FRT) capability Yes

Voltage Ride Through (VRT) capability Yes

Over frequency active power response Yes

Reactive power injection for VRT Yes

STATCOM mode: Reactive injection at night Optional

Interfaces

Touch-HMI Optional

Communications Channel 2 x Ethernet ports: 10 or 100 Mbps (no switched) for externalcommunications (SCADA or Energy Management System)

Communications Ports Connectors RJ45 Female or Fiber (optional)

Communication Protocols Modbus TCP and NTP

Luminous indicator, start/stop control and emergency stop Yes

Legal standards

Legal standards Designed and manufactured according to IEC62019-1, IEC62109-2, IEC61000-3-4, IEEE1547, UL840

Notes1. At 100% U AC, nom and cos ϕ = 1 2. Different DC fuse sizes are available under request.3. Other voltage configurations are possible under request4. At rated AC power @PF=1 @ 35ºC (95 ºF). Self-consumption is not considered in the efficiency measurement5. Self-consumption at rated operation

Page 26: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

26

SmartPV High-Capacity Modular Inverters - 1500Vdc Input Voltage Level

PV1000WD3HV550 / PV2000WD3HV550 /PV3000WD3HV550

SmartPV-WD3 1500V

Extreme Power Capacity at 1500Vdc and Scalable Integration

1500V DC Voltage Input capacity

Power Control and Grid Stability advanced featu-

res

Optimized cost solution for Large-Scale Installations

The next step in PV Energy Integration

GPTech SmartPV High DC Voltage Inverters have been specially designed for PV plants development operating with the new gene-ration of 1500Vdc solar modules, offering the best way to solve the challenges of Utility-Sca-le projects.

SmartPV High DC Voltage family complies with the most demanding grid codes around the world, offering higher power management ca-pacity joined with an easy integration with the LV/MV Transformer.

1500VREADY

Efficiency curve for maximum, rated and minimal DC-link voltage of the PV-WD3HV550 models (self-consumption is not considered)

PV-WD3 1500V efficiency curve

Page 27: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

27

PV1000WD3HV550 PV2000WD3HV550 PV3000WD3HV550

DC Input

Voltage range (1) 820 – 1250Vdc

Max. input voltage 1500Vdc

Rated input current @ 820Vdc, Tamb=35ºC 1380A 2760A 4140A

Max. short circuit input current 1700A 3400A 5100A

Max. Number of DC Inputs (2) Up to 12 Up to 24 Up to 36

DC Cabinet Integrated

AC Output

Frequency 50/60Hz

Frequency operation range 47 – 63Hz

Rated AC power @ 95ºF/35ºC, 1111 kVA 2222 kVA 3333 kVA

Rated AC power @ 122ºF/50ºC 1000 kVA 2000 kVA 3000 kVA

Rated voltage (3) 550 Vac

Total Harmonic Distortion (THD) < 3%

Power factor (PF) Adjustable

Efficiency

Efficiency(4) >98%

Self-consumption in standby < 250W < 400W < 550W

Self-consumption in operation(5) < 3kW < 5.5kW < 8kW

Ambient Conditions

Operation ambient temperature 14ºF / 140ºF (-10ºC / 60ºC)

Operation ambient temperature (without de-rating) 14ºF / 122ºF (-10ºC / 50ºC)

Storage and transport temperature -40ºF / 149ºF (-40ºC / 65ºC)

Maximum relative humidity 100%

Fresh air consumption 5750 m3/h 11500 m3/h 16500 m3/h

Max. altitude above sea level without derating 1000m

Max. altitude above sea level allowed 4000m

Mechanical characteristics

Dimensions (W x D x H) 1710 x1000 x2200mm 3420 x1000 x2200mm 4630 x1000 x2200mm

Protection degree NEMA 3R, IP54

Power control features

Anti-islanding protection Yes

Active power curtailment Yes

Active power ramp rate constraint Yes

Reactive power closed-loop control Yes

Power factor closed-loop control Yes

Frequency Ride Through (FRT) capability Yes

Voltage Ride Through (VRT) capability Yes

Over frequency active power response Yes

Reactive power injection for VRT Yes

STATCOM mode: Reactive injection at night Optional

Interfaces

Touch-HMI Optional

Communications Channel 2 x Ethernet ports: 10 or 100 Mbps (no switched) for externalcommunications (SCADA or Energy Management System)

Communications Ports Connectors RJ45 Female or Fiber (optional)

Communication Protocols Modbus TCP and NTP

Luminous indicator, start/stop control and emergency stop Yes

Legal standards

Legal standards Designed and manufactured according to IEC62019-1, IEC62109-2, IEC61000-3-4, IEEE1547, UL840

Notes1. At 100% U AC, nom and cos ϕ = 1 2. Different DC fuse sizes are available under request.3. Other voltage configurations are possible under request4. At rated AC power @PF=1 @ 35ºC (95 ºF). Self-consumption is not considered in the efficiency measurement5. Self-consumption at rated operation

Turnkey solutions specially designed to offer complete conversion stations with an extended DC input voltage range and power range up to 3MW.

Page 28: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

28

SmartPV Advanced Power Integrated StationsA complete set of integration possibilities for your project’s needs wherever it is placed.

Page 29: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

29

SmartPV Advanced Power Integrated StationsA complete set of integration possibilities for your project’s needs wherever it is placed.

80 MW Horus I+II Plants in Guatemala with APIS 2200 The biggest operating in Central America

THE QUICKEST OPTION TO INTEGRATE ENERGY INTO THE GRID

Page 30: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

30

Complete solutions designed for utility-scale plants that operate under extreme conditions.

They integrate all needed to plug and play the entire conversion stage from Pv Panels to the MV grid. each project.

TURNKEY SOLUTIONS TO MEET THE THE MOST DEMANDING GRID CODE REQUIREMENTS

Page 31: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

31

FLEXIBLE PHILOSOPHY FOR SOLID SOLUTIONS

Depending on the integration, tthe SmartPV APIS include GPTech inverters of the SmartPV inverters serie, Low and Medium Voltage Protections and auxiliary, Medium Voltage Transformer with protection cells and fence, fulfilling all legal requirements and optimised to the technical needs. These devices offer remote control of active and reactive power, as well as ramp rate response guaranteeing the grid stability

Page 32: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

32

SmartPV APIS ULAPIS1200-UL / APIS1500-UL / APIS1750-UL

Mechanical characteristicsInverter Power Module dimensions (H / W / D) 2100 x 2000 x 780 mm / 82,67 x 78,74 x 30,70 in

Inverter Disconnection Module dimensions (H / W / D) 2100 x 1100 x 750 mm / 82,67 x 43,3 x 29,52 in

Container dimensions (H / W / D) 2900 x 6000 X 2440 mm / 20’ x 8’ x 9’6”

Weight (5) 8396 kg / 18510 Ibs

Maximum fresh air consumption 8000 (2 x 4000) m3/h

Environment rating NEMA 3R, IP54

Medium Voltage StageTransformer Pad Mounted

Protections 2 x GPTech GPDM -I

APIS UL-i20

APIS UL-skd

Optimised Designs for the USA Market

Mechanical characteristicsInverter Power Module dimensions (H / W / D) 2300 x 2000 x 845 mm / 90,55 x 78,74 x 30,70 in

Inverter Disconnection Module dimensions (H / W / D) 2162 x 1100 x 750 mm / 85,12 x 43,3 x 29,52 in

Skid dimensions (H / W / D) 2522 X 9000 x 2100 mm / 99,3 x 354,4 x 82,7 in

Weight (5) 12000 kg / 26455 Ibs

Maximum fresh air consumption 12000 (2 x 6000) m3/h

Environment rating NEMA 3R, IP54

Medium Voltage StageTransformer Pad Mounted

Protections 2 x GPTech GPDM -O

Page 33: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

33

APIS 1200-UL APIS 1500-UL APIS 1750-ULDC Input Voltage range (MPPT) (1) 395 - 825 Vdc 495 - 825 Vdc 585 - 825 Vdc

MPPT Inputs 2

Maximum DC voltage 1000 Vdc

Maximum input current 3060 A

DC inputs (optional external box) 2 0-40 (2x10 - 2x20). Protected by fuses

AC OutputTransformer output. Medium AC voltage(5) 24 kV

Frequency rated 50/60 Hz

Frequency operation range 47 - 63 Hz

Rated AC power @ 50oC 1,12 (2 x 0,56) MVA 1,4 (2 x 07) MVA 1,66 (2 x 0,83) MVA

Rated AC power @ 25oC 1,2 (2 x 0,6) MVA 1,5 (2 x 0,75) MVA 1,78 (2 x 0,89) MVA

Rated AC power @ 50oC and PF of 0,9 1,0 (1 x 0,5) MW 1,26 (2 x 0,63) MW 1,5 (2 x 0,75) MW

Inverter output. Maximum output current 2900 (2 x 1450) A

Total Harmonic Distortion (THD) <3%

Power Factor at rated power adjustable (0.9 inductive ... 0.9 capacitive)

Galvanic insulation Yes

EfficiencyMaximum European efficiency (2) 97,29% 97,72% 98,00%

Maximum CEC effienciy (3) 97,18% 97,63% 97,92%

Inverter self-consumption at night <=400 (2 x 200) W

Inverter self-consumption in operation (4) <= 6 (2 x 3) kVA

Ambient conditionsOperation temperature -4oF/140oF (-20oC/60oC)

Operation ambient temperature (without derating) -4oF/122oF (-20oC/50oC)

Storage and transport temperature -22oF/149oF (-30oC/65oC)

Maximum relative humidity 95% without condensation

Maximum altitude above the sea level 3000 m

AC ProtectionsInverter output AC overvoltage protection Class II

Anti-islanding Yes

Grid voltage variations Yes

Frequency failures Yes

Asymmetric currents Yes

Low Voltage Ride Through (LVRT) Capability Yes

DC ProtectionsDC overvoltage protection Class II

Inverter shutting down on overload error Yes

PV-field isolation detector Yes

Panel Disconnnection Capability Yes. Contactor

Other ProtectionsBreaker protections of auxiliary systems Yes

Auxiliary systems overvoltage protection Yes

Power Control FeaturesReactive control by external signal Yes

Reactive control by internal configuration Yes. Timetable PF configuration or voltage dependent function

Reactive injection in LVRT Yes. Three different operation modes

Over frequency active power response Yes. Configurable droop

Ramp rate control Yes. Under irradiance value restriction

External power limitation Yes. Control allows continuous limit values

InterfacesTouch-HMI Yes

MODBUS RTU communication protocol Yes

Field bus connection with RS485 Yes

Luminous indicator, start/stop control and emergency stop Yes

Remote monitoring system, with GSM/GPRS modem Optional

Legal standardsUL1741 (6) Yes

United States - UL Listing Mark Yes

Canada - cUL Listing Mark Yes

IEEE 1547 Yes

CSI/CEC Performance Testing (California) Yes

IEC 62109-1, IEC 62109-2 Yes

Notes1. At VAC, nom and cosφ= 1 2. Inverter self-consumption is not considered in the efficiency measurement. Medium voltage transformer is not considered in the efficiency measurement (Typical transformer efficiency > 99%) 3. Self-consumption at rated operation4. Self-consumption in inverters is not considered in the efficiency measurement. A 33kV/240-300-355-430V transformer is considered5. Estimated. Customized MV transformer configuration6. For UL certification, please, consult special sales conditions

Page 34: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

34

SmartPV APIS InternationalAPIS1200-INT / APIS1500-INT / APIS1750-INT

APIS INT-i20

APIS INT-skd

Extended Range to meet all the requirements

Mechanical characteristicsInverter Power Module dimensions (H / W / D) 2100 x 2000 x 780 mm / 82,67 x 78,74 x 30,70 in

Container dimensions (H / W / D) 2900 x 6000 X 2440 mm / 8’ x 20’ x 9’6”

Weight 8396 kg / 18510 Ibs

Maximum fresh air consumption 8000 (2 x 4000) m3/h

Environment rating NEMA 3R, IP54

Medium Voltage StageTransformer Pad Mounted / Oil -Outdoor

Protections 2 x GPTech GPDM -I

Mechanical characteristicsInverter Power Module dimensions (H / W / D) 2300 x 2000 x 845 mm / 90,55 x 78,74 x 30,70 in

Inverter Disconnection Module dimensions (H / W / D) 2162 x 1100 x 750 mm / 85,12 x 43,3 x 29,52 in

Skid dimensions (H / W / D) 2522 X 9000 x 2100 mm / 99,3 x 354,4 x 82,7 in

Weight 12000 kg / 26455 Ibs

Maximum fresh air consumption 12000 (2 x 6000) m3/h

Environment rating NEMA 3R, IP54

Medium Voltage StageTransformer Pad Mounted / Oil -Outdoor

Protections 2 x GPTech GPDM -O

Page 35: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

35

APIS INT-i40

A complete set of integration options

Mechanical characteristicsInverter Power Module dimensions (H / W / D) 2100 x 2000 x 780 mm / 82,67 x 78,74 x 30,70 in

Container dimensions (H / W / D) 2900 x 12000 X 2440 mm / 8’ x 40’ x 9’6”

Weight 17530 kg / 38647 Ibs

Maximum fresh air consumption 8000 (2 x 4000) m3/h

Environment rating NEMA 3R, IP54

Medium Voltage StageTransformer Pad Mounted / Oil -Outdoor

Protections up to 4 x GPTech GPDM -I

Page 36: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

36

APIS 1200-INT APIS 1500-INT APIS 1700-INTDC Input Voltage range (MPPT) 375 - 825 Vdc 455 - 825 525 – 825 Vdc

Maximum DC voltage 1000 Vdc

Maximum input current 3800 A

Fused DC inputs (optional external box) 2 0-40 (2x10 - 2x20)

Number of MPPT inputs 2

AC OutputRated AC power @ 50oC2 1120 kVA 1400 kVA 1660 kVA

Rated AC power @ 35oC2 1200 kVA 1500 kVA 1780 kVA

Nominal AC voltage Customizable. Standard voltages. 11kV; 13. kV; 15 kV; 20 kV; 22.9 kV;33 kV;34.5 kV

Transformers taps Customizable. Standards ±2.5%,±5%

Transformer Vector Group Customizable. Standards. Ynd11d11; Dy11y11

Frequency rated 50/60 Hz

Frequency operation range 47 - 63 Hz

Power Factor at rated power Full range adjustable

Cooling type ONAN/KNAN

Output MV Maneuver T-Blade. Bayonet fuses.

EfficiencyMaximum European efficiency3 97.01% 97.16% 97,23%

Maximum CEC effienciy3 97.14% 97.30% 97,38%

Internal consumption at nigh (Inv. / MV transformer) (W)4 <=400 (2 x 200) W / <2400 W <=400 (2 x 200) W / <3000 W <=400 (2 x 200) W / <3400 W

Internal consumption in operation (Inv. / APIS Aux. services) (W)5 <= 6000 (2 x 3000) W / <2100 W

Ambient ConditionsOperation temperature -4oF/140oF (-20oC/55oC)

Operation ambient temperature (without derating) -4oF/113oF (-20oC/45oC)

Storage and transport temperature -22oF/149oF (-30oC/65oC)

Maximum relative humidity 95% without condensation

Maximum altitude above the sea level 3000 m

AC ProtectionsInverter output AC overvoltage protection Yes

Anti-islanding Yes

Grid voltage variations Yes

Frequency failures Yes

Asymmetric currents Yes

Low Voltage Ride Through (LVRT) Capability Yes

DC ProtectionsDC overvoltage protection Yes

Inverter shutting down on overload error Yes

PV-field isolation detector Yes

Panel Disconnnection Capability Yes. DC Contactor

Other ProtectionsBreaker protections of auxiliary systems Yes

Auxiliary systems overvoltage protection Yes

Power Control FeaturesReactive control by external signal Yes

Reactive control by internal configuration Yes. Timetable PF configuration or voltage dependent function

Reactive injection in LVRT Yes. Three different operation modes

Over frequency active power response Yes

Ramp rate control Yes. Under irradiance value restriction

External power limitation Yes. Control allows continuous limit values

APIS Controller Optional. See specifications

InterfacesTouch-HMI Yes

MODBUS RTU communication protocol Yes

Field bus connection with RS485 Yes

Remote monitoring system, with GSM/GPRS modem Optional

Legal standardsNEC 2011 Yes

United States - UL 1741 Listing Mark6 Yes, Certification in process

Canada - cUL Listing Mark6 Yes, Certification in process

IEEE 15476 Yes, Certification in process

CSI/CEC Performance Testing (California)6 Yes, Certification in process

IEC 62109-1, IEC 62109-2 Yes

Notes1. Estimated. Customized MV transformer configuration2. At VAC, nom and cosφ= 1 3. Inverter self-consumption is not considered in the efficiency measurement. Medium voltage transformer is not considered in the efficiency measurement (Typical transformer efficiency > 99%) 4. Self-consumption at rated operation5. Self-consumption in inverters is not considered in the efficiency measurement. reference transformer values: 33kV/240-300-355-430V6. For UL certification, please, consult special sales conditions

Page 37: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

37

APIS 1900-INT APIS 2200-INT APIS 3300-INT APIS 4400-INTDC Input Voltage range (MPPT) 525 – 825 Vdc 580 – 825 Vdc 580 – 825 Vdc 580 – 825 Vdc

Maximum DC voltage 1000 Vdc 1000 Vdc 1000 Vdc

Maximum input current 3800 A 5700 A 7600 A

Fused DC inputs (optional external box) 2 0-40 (2x10 - 2x20) 30-60 (3x10 - 3x20) 40-80 (4x10 - 4x20)

Number of MPPT inputs 2 3 4

AC OutputRated AC power @ 50oC2 1780 kVA 2010 kVA 3015 kVA 4020 kVA

Rated AC power @ 35oC2 1900 kVA 2150 kVA 3225 kVA 4300 kVA

Nominal AC voltage Customizable. Standard voltages. 11kV; 13. kV; 15 kV; 20 kV; 22.9 kV;33 kV;34.5 kV

Transformers taps Customizable. Standards ±2.5%,±5%

Transformer Vector Group Customizable. Standards. Ynd11d11; Dy11y11

Frequency rated 50/60 Hz

Frequency operation range 47 - 63 Hz

Power Factor at rated power Full range adjustable

Cooling type ONAN/KNAN

Output MV Maneuver T-Blade. Bayonet fuses.

EfficiencyMaximum European efficiency3 97,23% 97.30% 98.45% 98.45%

Maximum CEC effienciy3 97,38% 97.50% 98.49 98.49

Internal consumption at nigh (Inv. / MV transformer) (W)4 <=400 (2 x 200) W / <3800 W <=400 (2 x 200) W / <4400W <=600 (3 x 200) W / <5000W <=800 (4 x 200) W / <5600W

Internal consumption in operation (Inv. / APIS Aux. services) (W)5 <= 6000 (2 x 3000) W / <2100 W <= 9000 (3 x 3000) W/<2100W <= 12000 (4 x 3000)W/<2100W

Ambient ConditionsOperation temperature -4oF/140oF (-20oC/55oC)

Operation ambient temperature (without derating) -4oF/113oF (-20oC/45oC)

Storage and transport temperature -22oF/149oF (-30oC/65oC)

Maximum relative humidity 95% without condensation

Maximum altitude above the sea level 3000 m

AC ProtectionsInverter output AC overvoltage protection Yes

Anti-islanding Yes

Grid voltage variations Yes

Frequency failures Yes

Asymmetric currents Yes

Low Voltage Ride Through (LVRT) Capability Yes

DC ProtectionsDC overvoltage protection Yes

Inverter shutting down on overload error Yes

PV-field isolation detector Yes

Panel Disconnnection Capability Yes. DC Contactor

Other ProtectionsBreaker protections of auxiliary systems Yes

Auxiliary systems overvoltage protection Yes

Power Control FeaturesReactive control by external signal Yes

Reactive control by internal configuration Yes. Timetable PF configuration or voltage dependent function

Reactive injection in LVRT Yes. Three different operation modes

Over frequency active power response Yes

Ramp rate control Yes. Under irradiance value restriction

External power limitation Yes. Control allows continuous limit values

APIS Controller Optional. See specifications

InterfacesTouch-HMI Yes

MODBUS RTU communication protocol Yes

Field bus connection with RS485 Yes

Remote monitoring system, with GSM/GPRS modem Optional

Legal standardsNEC 2011 Yes

United States - UL 1741 Listing Mark6 Yes

Canada - cUL Listing Mark6 Yes, Certification in process

IEEE 15476 Yes, Certification in process

CSI/CEC Performance Testing (California)6 Yes, Certification in process

IEC 62109-1, IEC 62109-2 Yes

Notes1. Estimated. Customized MV transformer configuration2. At VAC, nom and cosφ= 1 3. Inverter self-consumption is not considered in the efficiency measurement. Medium voltage transformer is not considered in the efficiency measurement (Typical transformer efficiency > 99%) 4. Self-consumption at rated operation5. Self-consumption in inverters is not considered in the efficiency measurement. reference transformer values: 33kV/240-300-355-430V6. For UL certification, please, consult special sales conditions

Page 38: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

38

Some Available Control Features

Dynamic closed-loop System

Soft start

Soft shutdown

Error/Alarm Handling

Power Transformer

MV Swtichgear

Converters

Communications Error

Auxiliaty Systems

Temperature Control

APIS Fan Control

Power Transformer Derating

Converter Derating

Humidity Control

Solar Inverter Controls

Energy efficiency strategies

Round-Robin Scheduling

Temperature Derating

BPCS+ESS Controls

SOC Management

Dinamic Active Power Limits

Energy efficiency strategies

Round-Robin Scheduling

STATCOM Controls

Energy efficiency strategies

Round-Robin Scheduling

MODULAR DESIGNED WITH ADVANCE COMMUNICATION AND CONTROL FEATURES ADAPTED TO EACH FACILITY

APIS CONTROLLER

APIS CONTROLLER

GPTech APIS Controller has become a key solu-tion for the generation units integration for any modern renewable and hybrid power plant.

The solution is based on open standards:

• Preventing the lock in by a specific technology and/or vendor

• Enabling an easy integration of the solution with third-party applications

Customized features to fully reach customer’s re-quirements in the most effective and reliable way.

Page 39: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

39

PV-GPDM

DC Swith

Maximum input voltage 1000 Vdc

Maximum input current 1800 A

Switch type Switch disconnector

Maximum short-circuit current Up to 100 kA

Maximum DC inputs 20

Number of handling switches 1

AC Switch

Maximum voltage range 690 V

Frequency 50/60 Hz

Maximum output current 2000 A

Switch type Circuit breaker

Max. short-circuit current (1s) Up to 40 kA

Numer of handlers 1

General Characteristics

Dimensions (H x W x D) 2162 x 1100 x 750 mm / 85,12 x 43,3 x 29,52 inches

Environmental rating NEMA 3R

Weight 605 Kg / 1331 Ib

Operation temperature -4oF / 140oF (-20oC / 60oC)

Storage and transport temperature 22oF / 149oF (-30oC / 65oC)

Maximum relative humidity 95%

Maximum altitude above sea level 3000 m

Legal Standards

UL1741 Yes

United States - UL Listing Mark Yes

Canada - UL Listing Mark Yes

IEEE 1547 Yes

IEC 62109-1, IEC 62109-2 Yes

PVWD -GPDM-I / PVWD-GPDM-O

PVWD DC/AC Disconnection Module

PV-GPDM Indoor/Outdoor

• The PVWD DC/AC Disconnection Module con-nects all Smart PV Inverters of the PVWD series to the DC and AC side of the PV facility.

• The disconnection module contains AC and DC switches in a compact single enclosure sepa-rated from inverters and compatible for the whole PVWD familly and the Advanced Power Integrated Stations (APIS). It allows up to 20 DC inputs, guarantying safe emergency disconnec-tion and/or maintenance in compliance with NEC.

Page 40: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

40

Page 41: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

41

GPTech EnergyReserve solutions for high capacity energy storage and control provides new and unlimited possibilities in the energy management .

Ready for the entire range of indus-try needs: from residential to utility applications, enhancing grid stabi-lity, fitting production and comp-sumption hours, and defining new strategies in the power control.

Designed and built Plug and Play Integrated Storage Systems, fo-cused on strategic markets in the most demanding network environ-ments: Chile, Mexico, Brazil, USA ...

Solutions for a new era in the energy industry

Page 42: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

42

EnergyReserve: Storage and Control Solutions Whatever you need about energy storage…

GPTechEnergyReserveisthecompletefully-functionalstoragesolutionforallthetodayandtomorrowneeds,basedonourpowercontroltechnologyintegratedwithselectedenergystoragesystemsfromtheleaderbrands,carefullystudiedforeverynewwork.

TheyarecomposedbyanESS(energyStorageSystem)andtheAPCS(AdvancedPowerConditioningSystem)forthePowerRegulationandcontrol.ThecompletesolutionismanagedwithourGPTechEMSystemstechnology.

EachprojectisevaluatedusingthemostadvancedcalculationtoolstoobtaintheexactlyEnergyReserveSolutionneededforthefacility,tomeetthelatestTechnicalRequirements.

• Agreementswiththemainbatteriesmanufactures

• Opentodifferentstoragetechnologies

• EnergyShifting

• RampRate

• AdvancedPowerCurtailment

• VoltageRegulation

• FrequencyControl

• PowerQuality

GPTech APCS: Advanced Power Conditioning Station

ESS: Energy Storage System

Page 43: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

43

Grid support services

• Frequency regulation.

• Spinning reserve

• Peak shifting

• Black start

• VAR support

• Voltage regulation

• Load leveling

Renewables Integration

• Grid code compliance

• Ramp rate control

• Contribution to frequency regulation

• Voltage regulation

• VAR support

• Capacity firming

Hybrid Systems

• Grid stability during fluctuations of renewable systems.

• Backup power during genset starting transients.

• Backup energy for stand-alone operation.

• Optimization of diesel spinning reserve

• Energy shifting for on-grid and off-grid operation

• Capacity firming

A new era for advanced energy management and new ancillary services possibilities.

Page 44: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

44

EnergyReserve HP

Specially configured to meet the har-dest grid codes to be acomplished by renewable installations (as Puerto Rico, South Africa, Mexico...)

Capable of providing ancillary services to improve the management of key net-work aspects such as frequency respon-se and voltage regulation.

EnergyReserve P

Designed as high capacity source of power over an approximate average time of 15 to 45 minutes

• Ramp rate control

• Spinning reserve

• Frequency regulation

• VAR support

• Voltage regulation

• Power Quality

EnergyReserve S

EnergyReserve S is desgined for the sto-rage of energy during low-demand pe-riods and low-rate hours.

• Energy Shifting

• VAR support

• Voltage regulation

Time (minutes)

Power (KW)

1min 10min 100min

100 KW

1000 KW

Time (minutes)

Power (KW)

1min 10min 100min

100 KW

1000 KW

Time (minutes)

Power (KW)

1min 10min 100min

100 KW

1000 KW

S PHP

EnergyReserve: Storage and Control Solutions

Modular designs custo-mized to you needs

Functional Block ready to be integrated

obtaining a tailored design to the pro-

ject requirements

Complete storage functional solutions

Completely functional storage and con-

trol solutions ready to be connected to

the facility

Robustness and best performance

Ensuring the best robustness with project

life warranty plans, which includes advanced

maintenance and spare part services

...with the background of a leader in energy integration

GPTech EneryReserve profiles for all requirements...

Page 45: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

45

The up and down ramps regulation approximates the behavior of generators to conventional systems, but the way to solve is different in the two cases:The rise requires applying a power limitation

For supporting a controlled descent, the system needs to provide an injection of extra power to support the slope requiring a storage system for this purpose.

GPTech has developed success comercial solutions to add ramp rate capabillity to Utility PV Plants, achieving a stable performance as never seen before.

State of the art technology to open new paths for the renewable energy development in a larger range of applications.

RAMP RATE AVAILABILITY AND CONTROL

GPTech EneryReserve profiles for all requirements...

Page 46: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

46

EnergyReserve APCS ULAPCS1200-UL / APCS1500-UL / APCS1750-UL

Mechanical characteristicsInverter Power Module dimensions (H / W / D) 2100 x 2000 x 780 mm / 82,67 x 78,74 x 30,70 in

Inverter Disconnection Module dimensions (H / W / D) 2100 x 1100 x 750 mm / 82,67 x 43,3 x 29,52 in

Container dimensions (H / W / D) 2900 x 6000 X 2440 mm / 8’ x 20’ x 9’6”

Weight (5) 8396 kg / 18510 Ibs

Maximum fresh air consumption 8000 (2 x 4000) m3/h

Environment rating NEMA 3R, IP54

Medium Voltage StageTransformer Pad Mounted with double secondary windings

Protections 2 x GPTech GPDM -I

APCS UL-i20

APCS UL-skd

Optimised Designs for the USA Market

Mechanical characteristicsInverter Power Module dimensions (H / W / D) 2300 x 2000 x 845 mm / 90,55 x 78,74 x 30,70 in

Inverter Disconnection Module dimensions (H / W / D) 2162 x 1100 x 750 mm / 85,12 x 43,3 x 29,52 in

Skid dimensions (H / W / D) 2522 X 9000 x 2100 mm / 99,3 x 354,4 x 82,7 in

Weight (5) 12000 kg / 26455 Ibs

Maximum fresh air consumption 12000 (2 x 6000) m3/h

Environment rating NEMA 3R, IP54

Medium Voltage StageTransformer Pad Mounted with double secondary windings

Protections 2 x GPTech GPDM -O

Page 47: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

47

APCS 1200-UL APCS 1500-UL APCS 1750-ULDC Input SOC voltage range (max. power)1 395 - 825 Vdc 495 - 825 Vdc 585 - 825 Vdc

Max. input voltage 1000 Vdc

Max. Input current 3060 A

AC OutputNominal AC Voltage 50/60 Hz

AC voltage range2 47 - 63 Hz

Frequency 1,12 (2 x 0,56) MVA 1,4 (2 x 07) MVA 1,66 (2 x 0,83) MVA

Rated AC power @ 50ºC (122 ºF) 1,2 (2 x 0,6) MVA 1,5 (2 x 0,75) MVA 1,78 (2 x 0,89) MVA

Rated AC power @ 25ºC (77 ºF) 1,0 (1 x 0,5) MW 1,26 (2 x 0,63) MW 1,5 (2 x 0,75) MW

Maximum output current 2900 (2 x 1450) A

Total Harmonic Distortion (THD) <3%

Power Factor at rated power adjustable (0.9 inductive ... 0.9 capacitive)

Galvanic Isolation Yes

EfficiencyEuropean efficiency3 97,29% 97,72% 98,00%

CEC efficiency3 97,18% 97,63% 97,92%

Self-consumption in standby <=400 (2 x 200) W

Self-consumption in operation4 <= 6 (2 x 3) kVA

Ambient conditionsOperation temperature -4oF/140oF (-20oC/60oC)

Operation ambient temperature (without derating) -4oF/122oF (-20oC/50oC)

Storage and transport temperature -22oF/149oF (-30oC/65oC)

Maximum relative humidity 95% without condensation

Maximum altitude above the sea level 3000 m

AC ProtectionsAC overvoltage protection: Class II Class II

EMI-filter Yes

Anti-islanding Yes

Grid voltage variations Yes

Frequency failures Yes

Asymmetric currents Yes

Low voltage ride through (LVRT) capability Yes

DC ProtectionsDC overvoltage protection: Class II Class II

Inverter shutting down on overload error Yes

Battery system isolation detector Yes

Other ProtectionsBreaker protections of auxiliary systems Yes

Auxiliary systems overvoltage protection Yes

InterfacesTouch-HMI Yes

MODBUS RTU communication protocol Yes

Field bus connection with RS485 Yes

Luminous indicator, start/stop control and emergency stop Yes

Remote monitoring system, with GSM/GPRS modem Optional

Legal standardsUL1741 Yes

United States - UL Listing Mark Yes

Canada - cUL Listing Mark Yes

IEEE 1547 Yes

CSI/CEC Performance Testing (California) Yes

IEC 62109-1, IEC 62109-2 Yes

Notes1. At VAC, nom and cosφ= 1 2. Inverter self-consumption is not considered in the efficiency measurement. Medium voltage transformer is not considered in the efficiency measurement (Typical transformer efficiency > 99%) 3. Self-consumption at rated operation4. Self-consumption in inverters is not considered in the efficiency measurement. A 33kV/240-300-355-430V transformer is considered5. Estimated. Customized MV transformer configuration6. For UL certification, please, consult special sales conditions

Page 48: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

48

EnergyReserve APCS ULAPCS2400-UL / APCS3000-UL / APCS3500-UL

Mechanical characteristicsInverter Power Module dimensions (H / W / D) 2100 x 2000 x 780 mm / 82,67 x 78,74 x 30,70 in

Inverter Disconnection Module dimensions (H / W / D) 2100 x 1100 x 750 mm / 82,67 x 43,3 x 29,52 in

Container dimensions (H / W / D) 2900 x 12000 X 2440 mm / 8’ x 40’ x 9’6”

Weight (5) 19000 kg / 41888 Ibs

Maximum fresh air consumption 16000 (4 x 4000) m3/h

Environment rating NEMA 3R, IP54

Medium Voltage StageTransformer 2 X Pad Mounted with double secondary windings

Protections 2 x GPTech GPDM -I

APCS UL-i40

Optimised Designs for the USA Market

BPCS Battery Power Conditioning System

BPCS500WD efficiency curve 600 kW @PF=1.0 @25ºC (77 ºF

Page 49: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

49

Notes1. At VAC, nom and cosφ= 1 2. Inverter self-consumption is not considered in the efficiency measurement. Medium voltage transformer is not considered in the efficiency measurement (Typical transformer efficiency > 99%) 3. Self-consumption at rated operation4. Self-consumption in inverters is not considered in the efficiency measurement. A 33kV/240-300-355-430V transformer is considered5. Estimated. Customized MV transformer configuration6. For UL certification, please, consult special sales conditions

APCS 2400-UL APCS 3000-UL APCS 3500-ULDC Input SOC voltage range (max. power)1 395 - 825 Vdc 495 - 825 Vdc 585 - 825 Vdc

Max. input voltage 1000 Vdc

Max. Input current 6120 A

AC OutputNominal AC Voltage 50/60 Hz

AC voltage range2 47 - 63 Hz

Frequency 2,24 (4 x 0,56) MVA 2,8 (4 x 0,7) MVA 3,32 (4 x 0,83) MVA

Rated AC power @ 50ºC (122 ºF) 2,4 (4 x 0,6) MVA 3,0 (4 x 0,75) MVA 3,56 (4 x 0,89) MVA

Rated AC power @ 25ºC (77 ºF) 2,0 (4 x 0,5) MW 2,52 (2 x 0,63) MW 3,00 (4 x 0,75) MW

Maximum output current 5800 (4 x 1450) A

Total Harmonic Distortion (THD) <3%

Power Factor at rated power adjustable (0.9 inductive ... 0.9 capacitive)

Galvanic Isolation Yes

EfficiencyEuropean efficiency3 97,29% 97,72% 98,00%

CEC efficiency3 97,18% 97,63% 97,92%

Self-consumption in standby <=400 (2 x 200) W

Self-consumption in operation4 <= 6 (2 x 3) kVA

Ambient conditionsOperation temperature -4oF/140oF (-20oC/60oC)

Operation ambient temperature (without derating) -4oF/122oF (-20oC/50oC)

Storage and transport temperature -22oF/149oF (-30oC/65oC)

Maximum relative humidity 95% without condensation

Maximum altitude above the sea level 3000 m

AC ProtectionsAC overvoltage protection: Class II Class II

EMI-filter Yes

Anti-islanding Yes

Grid voltage variations Yes

Frequency failures Yes

Asymmetric currents Yes

Low voltage ride through (LVRT) capability Yes

DC ProtectionsDC overvoltage protection: Class II Class II

Inverter shutting down on overload error Yes

Battery system isolation detector Yes

Other ProtectionsBreaker protections of auxiliary systems Yes

Auxiliary systems overvoltage protection Yes

InterfacesTouch-HMI Yes

MODBUS RTU communication protocol Yes

Field bus connection with RS485 Yes

Luminous indicator, start/stop control and emergency stop Yes

Remote monitoring system, with GSM/GPRS modem Optional

Legal standardsUL1741 Yes

United States - UL Listing Mark Yes

Canada - cUL Listing Mark Yes

IEEE 1547 Yes

CSI/CEC Performance Testing (California) Yes

IEC 62109-1, IEC 62109-2 Yes

Page 50: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

50

Salinas, Puerto Rico (13MW)

Ancillary Services Real Case Puerto Rico for a 10 MW PV Plant

3 x Enerrgy Reserve Solutions 2 x AVCS4000

1 x EMSystem PPC Utility Scale

Page 51: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

51

Page 52: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

52

Page 53: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

53

The electrical authorities demand control requirements that plants must meet to guarantee system stability.

Some are of special relevance as the Limitation of Power (Power Cur-tailment) to adjust available produc-tion to real demand, and the Ramp Rate Control which softens the impact caused by sudden changes in environmental conditions that may affect the instantaneous capacity to generate renewable energy.

.

Advanced Ancillary Services to meet the most demanding grid requirements

Page 54: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

54

Technology for the Power StabilityBreakthrough technology designed for the utility-scale

STABILISATION SYSTEMS

The STATCOM solutions provide a source of reactive power control with the finest response to meet the grid requirements all time.

Since 2006, GPTech STATCOMs are installed in energy plants with a total capacity which currently exceeds 1GW.

Voltage control is performed by the reactive capacity of installed systems. These are managed by the Power Plant Controller based on the grid operator references.

The technology of GPTech offers added values of signal quality through its advanced function for generation and control of Reactive Power. Its PV conversion systems, the GPTech STATCOMs pro-ducts’ family of, as well the power plant controller GPTech EMS which include a reactive manager.

Page 55: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

55

FAST INTEGRATION AND SCALABILITY

The development of own monitoring tools, together with the possibility of integration with third party SCADA solutions ensure a rapid and flexible solution.In order to achieve optimum integration, we select the most widely accepted protocols adjusting the final features for each project.

Page 56: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

56

GridCapabilities STATCOMsSTATCOM1000

Voltage Regulation Sys-tem (VRS)

Frequency Response and Advanced Regulation

Voltage Regulation Sys-tem (VRS)

Robustness performance in weak electric grids

Better Reactive Power Capacity

Fast Dynamic Response

STATCOM1000

GridCapabilities-STATCOM1000

GPTech 4 MVA STATCOM containerised

Flexible Solutions to be integrated in High Ca-pacity Solutions, ready to be connected easily.

Page 57: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

57

Notes1. Further AC voltages can be configured2. Auxiliary-consumption is not considered in the losses measurement3. Auxiliary-consumption at rated operation

STATCOM1000AC Output

Nominal AC Voltage 480 V

AC voltage range1 432 … 528

Frequency 60 Hz

Rated AC power @ 50ºC (122 ºF) 1000 kVA

Rated AC power @ 25ºC (77 ºF) 1080 kVA

Maximum output current 1450 A

Total Harmonic Distortion (THD) < 3%

Galvanic Isolation No

Losses

Maximum losses2

Auxiliary consumption at stand-by

Auxiliary consumption in operation3 <= 100 W

Self-consumption in operation <= 3 kW

Ambient conditions

Operation temperature -4oF/140oF (-20oC/60oC)

Operation ambient temperature (without derating) -4oF/122oF (-20oC/50oC)

Storage and transport temperature -22oF/149oF (-30oC/65oC)

Maximum relative humidity 95% without condensation

Maximum fresh air consumption (Indoor/Outdoor) 4000 m3/h / 6000 m3/h

Maximum altitude above the sea level 3000 m

Mechanical characteristics

Dimensions (H / W / D) Indoor Aplication 2100 x 2000 x 780 mm / 82,67 x 78,74 x 30,70 in

Dimensions (H / W / D) Outdoor Aplication 300 x 2000 x 845 mm / 90,55 x 78,74 x 33,26 in

Weight (Indoor/Outdoor) 1870 kg (4122 Ibs) / 2100 kg (4629 Ibs)

Environment rating (Indoor/Outdoor) NEMA 2, IP20 / NEMA 3R, IP54

AC Protections

AC overvoltage protection: Class II Class II

EMI-filter Yes

Anti-islanding Yes

Grid voltage variations Yes

Frequency failures Yes

Asymmetric currents Yes

Voltage sag compensation Yes

Other protections

Breaker protections of auxiliary systems Yes

Output coil and IGBT over temperature (For each phase of converter) Yes

Power Control Features

Reactive control by external signal Yes

Reactive control by internal configuration Yes. Timetable PF configuration or voltage dependent function

Reactive injection in LVRT Yes. Three different operation modes

Over frequency active power response Yes. Configurable droop

Ramp rate control Yes. Under irradiance value restriction

External power limitation Yes. Control allows continuous limit values

STATCOM mode for night compensation Optional (additional elements required)

Interfaces

Touch-HMI Yes

MODBUS RTU communication protocol Yes

Field bus connection with RS485 Yes

Luminous indicator, start/stop control and emergency stop Yes

Remote monitoring system, with GSM/GPRS modem Optional

Master-Slave operation Optional

Legal standards

UL1741 Yes

United States - UL Listing Mark Yes

Canada - cUL Listing Mark Yes

IEEE 1547 Yes

CSI/CEC Performance Testing (California) Yes

IEC 62109-1, IEC 62109-2 Yes

GPTech APCS Controller

Page 58: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

58

Maan, Jordan

2 AVCS4000 have been installed to manage

around 9MAr in a 50MW PV installation in extreme electrical and enviromen-

tal conditons

Page 59: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

59

Page 60: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

60

Page 61: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

61

Renewable sources are a now a real energy alternative, increasing its presence every year exponentially

For a sustainable growth of the clean energy, it is critical to provide advanced energy management and control solutions to maximize them.

GPTech EMSystems are based on our strong experience as energy integrators, adding a new vision joinning specially created control al-gorithms and the lattest technology.

.

A new vision of the power plants control

Page 62: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

62

EMSystems Complete Control Solutions for PlantsLeveling up the plants to the next generation of stability and control possibilities

• Ancillary Services and Large-Scale Pv Plants are improved with new control options as the voltage and frequency regulation or distributed performance to obtain the best of each plant source.

• A correct combination of solar, wind and others with conventional sources represents an opportunity of saving money with fuel reduction and plant management, while a cleaner world is developed.

• GPtech EMSystems are the best answer to the new challenges in hybridation and renewable power control.

Page 63: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

63

GPTech EMSystems PPC Utility-Scale GPTech EMSystems HybridThe GPTech Solution for Utilities, full customised with the latest control and management system for voltage, frequency and reacti-ve power control.

The bridge to ensure the grid code acomplishement under best conditions of reliability

Solutions adapted for all the industry requirements from small industry and comercial facilities to com-plex hybrid installation.

EMsystem Hybrid Solutions are focused on saving fuel costs, optimise energy sources performance and enhancing the power quality.

Every project is analysed to select the best scaled confiiguration to meet the specific goals

63 MW CPV Plant in Touwsrivier - South Africa - with SmartPV Inverters and

EMSystems PPC Utility-Scale

Wide range of configuration options to suit all the facility requirements. EMSystems PPCs are ready to work with all project scales and complexity.

Page 64: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

64

Specially designed to implement hybrid generation and mixing renewable and conventional sources, with possibility of Energy Storage Integration.

GPTech EMSystems hybrid provides different direct benefits as:

– Fuel Save – Off-grid self-conpsumptiom optimisation – Energy Shifting – Monitoring and control of the sources – Grid Stability

A complete set of solutions configured with different functionalities to attent in the best way all the customer needs for every plant.

GPTech EMSystems is the perfect solution when integration renewable sources as principal generation with large stora-ge systems, and complementary ancillary services into the main grid.

The whole set of features offered by the system provides all the functionalities required for the facility:

• Complex Grid Codes accomplishment• Accurace management of Reactive Power• Voltage / Frequency advanced power• Power quality criteria control• Possibility of integrate the local benefit scheme if it exists.

A new world of possibilities for leveling up your projects to the new generation of large-scale renewable facilities.

Utility-Scale: Grid Stability and Control for Large-Scale Plants

Hybrid: Grid Stability and Control for Large-Scale Plants

EMSystems PPC for a complete range of applications

Page 65: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

65

EMSystems PPC Basic ConfigurationsHigher PPC features are available under request, please contact us for more information

PPC STANDARD PPC EXTENDEDPower Plant Characteristics

Maximum Number of Controllable Equipment Up to 20 devices or 10 MW Up to 60 devices or 50 MW

Compatible Controllable Equipment SmartPV Family Solar: SmartPV

Ancillary Services: Energy Reserve GridCapabilities

Compatible Power Analyzer PM130PLUS (SATEC) / ION 8600 (Schenider) / PAC4200 (Siemens)

Controls at the Point of Interconection

General Power plant soft start/stop

Active Power Control Active power curtailment / Active power ramp rate constraint

Reactive Power Control Reactive power closed-loop control / Fixed reactive power when null production

Frequency Stability Active power injection/absortion due to frequency variations

Voltage Control Voltage Reference closed-loop control / Characteristic curve V-Q

Power Factor Control Power factor closed-loop control

Error/Alarm Handling PPC monitors the control system and takes the plant to a safe state if errors are detected Errors and alarms are notified to the Plant supervision system"

Grid Code Autocheck functionallity In order to verify the Grid Code Compliance, the PPC implements automatic validation profiles that can be carried out during the Site Acceptance Test.

Communications

Communications Channel1 ethernet port 10 or 100 Mbps with internal mana-gement switch for external communications (SCADA,

RTU, PV Inverters, Power Analyzers…)

2 ethernet ports 10 or 100 Mbps (no switched) with internal management switch for external communi-cations (SCADA, RTU, PV Inverters, Statcoms, Storage

Systems, Power Analyzers…)

Communications Ports Connectors RJ45 Female / Fiber (optional) RJ45 Female / Fiber (optional)

Communication Protocols Modbus TCP and NTP Modbus TCP, Modbus RTU, NTP, DNP3 Serial, DNP3 TCP, IEC-61850 GOOSE and IEC-61850 MMS.

Additional Interfaces

Power Analyzer 1 Up to 3 (depending on plan scheme)

Digital I/O up to 16 up to 48

Analog I/O up to 2 up to 24

Power Supply

Power Consumption < 300W

DC input Voltage Range 80…370 Vdc

AC input Voltage Range 100...240 Vac

Frequency Range AC 47...63 Hz

Protections Fuses. 1P+N

Ambient Conditions

Operation ambient temperature 14ºF to 113ºF (-10 ºC to 45 ºC)

Storage and transport temperature -4ºF to 140ºF (-20ºC to 60ºC)

Max. altitude above sea level allowed 2,000 m.a.s.l.

Maximum relative humidity 95 % without condensation

Mechanical Characteristics

Dimensions (H x W x D) 1000 x 600 x 300 1400 x 1000 x 450 mm.

Fixation Wall-mounted Floor-mounted

IP Rating IP23

Service/Maintenance System

Remote access Yes Yes

Web Server for monitoring Yes Yes

Data Logging Yes Yes

Luminous indicator and on/off control Yes Yes

Legal standards

UL1741 IEC 60364-5-523 , EN 60950-1 IEC 60364-5-523 , EN 60950-1

24 MW PV Plant in Puerto Rico with EMSystems PPC Utility-Scale

Page 66: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

66

Page 67: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

67

Mount signal, 256 MW PV Plant operating with our EMSystem

PPC Utility-Scale

Page 68: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

68

With you along the whole lifetime of your projects

After Sales and Premium Support

Worldwide presence

Higher technical consultancy

Training seminars

Advanced warranty

Evaluation & repair

Spare parts

Maintenance

Up to 99% Availability (ask for O&M Plans)

We participate in the whole process of the PV power plant development and ac-company our clients along all the stages.

From the pre-sale to the end of the life of the faci-lity, we guarantee best performance up to 25 years.

Page 69: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

69

Renewable Energy plants require the total securi-ty on an optimal functioning to maximize the re-turn of investment. Top Quality Components, O&M and Availability services are key issues to guarantee maximum production and superior financial returns.

Page 70: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

70

PUERTO RICO

Centro de Negocios SAN JUANMetro Office Park (HQ)

Metro Office Park Metro Parque 7 Street 1 Suite 204 Guaynabo 00968

San Juan de Puerto Rico

SOUTH AFRICA

Floor Lancaster Gate, Hyde Park LaneCnr. William Nicol Dr. & Jan Smits Ave Hyde Park

Sandton 2196 Johannesburg

SPAIN

HeadquarterC/ Camino de los Descubrimientos 17

Isla de la Cartuja Seville

I+D CenterAvenida de Camas, 26-28

PIBO 41110 Bollullos de la Mitacion Seville

Page 71: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

71

USA

West4370 La Jolla Village Drive, Northern Trust Building Suite 00, San Diego, California

East1111 Lincoln Road 4th Floor (Regus) Miami Beach - Florida

BRAZIL

Edifício Candelária Corporate, Rua Candelária, 65, 16th FloorCentro, Rio de Janeiro, 20091-020

tel. (+55) 21 2172-5351

CHILE

Alonso de Cordova 5870 - Oficina 1810 Las CondesSantiago

Worldwide Presence

CGE1602 Publisher and Editor: Greenpower Technologies S.L.Copyright 2015 for the whole content by GPTech. All rights reserved. Subject to technical changes.

Page 72: Solutions for Utility-Scale, Power Management and Grid ... · PDF fileGPTECH APIS INVERTER STATIONS ... , based on our experience in the entire va- ... Rated AC power @ 25oC 600 kVA

[email protected]

BRAZILEdifício Candelária Corporate, Rua Candelária, 65, 16th Floor

Centro, Rio de Janeiro, 20091-020

tel. (+55) 21 2172-5351

USAWest

4370 La Jolla Village Drive, Northern Trust Building Suite 00, San Diego, California

East1111 Lincoln Road 4th Floor (Regus)

Miami Beach - Florida

CHILEAlonso de Cordova 5870 - Oficina 1810

Las CondesSantiago

PUERTO RICOCentro de Negocios SAN JUANMetro Office Park (HQ)Metro Office Park Metro Parque 7 Street 1 Suite 204 Guaynabo 00968 San Juan de Puerto Rico

SOUTH AFRICAFloor Lancaster Gate, Hyde Park LaneCnr. William Nicol Dr. & Jan Smits Ave Hyde Park Sandton 2196 Johannesburg

SPAINHeadquarterC/ Camino de los Descubrimientos 17 Isla de la Cartuja Seville

I+D CenterAvenida de Camas, 26-28 PIBO 41110 Bollullos de la Mitacion Seville