Protection, prevention and environmental impact of fire in a tire storage SNCP experience feedback report Recommendations on fire protection in tyre storage facilities using ESFR sprinkler system ESFR sprinkler system 06 60, RUE AUBER – 94408 VITRY SUR SEINE CEDEX – TEL : 01 49 60 57 57 – FAX : 01 45 21 03 50 N° SIRET : 78435748500035 – APE : 911 A – SYNDICAT PROFESSIONNEL 53394 LOI DU 21 MARS 1884 Mél : [email protected] - Internet : www.lecaoutchouc.com Centre Français du Caoutchouc et des Polymères industriels

Upload: truongduong

Post on 28-Mar-2018

234 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Protection, prevention and environmental impact of fire

in a tire storage SNCP experience feedback report

Recommendations on fire protection in tyre storage facilities using ESFR sprinkler system

ESFR sprinkler system

06

6 0 , R U E A U B E R – 9 4 4 0 8 V I T R Y S U R S E I N E C E D E X – T E L : 0 1 4 9 6 0 5 7 5 7 – F A X : 0 1 4 5 2 1 0 3 5 0

N° SIRET : 78435748500035 – APE : 911 A – SYNDICAT PROFESSIONNEL 53394 LOI DU 21 MARS 1884

M é l : i n f o @ l e c a o u t c h o u c . c o m - I n t e r n e t : w w w . l e c a o u t c h o u c . c o m

Centre Français du Caoutchouc e t des Polymères indust r ie ls

Page 2: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 2

Summary sheet

Automatic fire ignition and extinguishing tests in tyre storage facilities.

on-tread and laced configurations

storage height up to 8.75 m

ceiling height up to 12 m

fire protection system using K25 ESFR sprinklers

Lessons learnt from the tests

tyres do not ignite easily without an accelerating agent

pyrolysis is slow to set in

the heat release rate is low for the first 3 minutes, then increases rapidly

the fire's kinetics, development and heat release rate are similar for both

types of storage configurations: on tread and laced

the automatic extinguishing system acts in the same way on both types of

storage

the first ESFR sprinkler head opens before the flames emerge from the stock

clearance, between 1.25 m and 4.25 m, has no measurable effect

the fire does not spread to another island 2.4 m away with the sprinklers operating

Page 3: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 3

K25 ESFR sprinkler heads protect:

a storage height of 7.45 m in control mode, with a density of

52 l/min/m2 at ground level (head pressure of 1.7 bar)

a storage height of 7.45 m in suppression mode, with a density of

67 l/min/m2 at ground level (head pressure of 2.8 bar)

a storage height of 8.75 m in suppression mode, with a density of

91 l/min/m2 at ground level (head pressure of 5.2 bar)

the quantity of burnt tyres is low, around 600 kg in control mode, less than

150 kg in suppression mode

the quantity of smoke emitted is low, visibility in the building remains

sufficient for fire-fighting operations

Since the quantity of burnt tyres is small, the potential impact is limited to the

inside of the building. Atmospheric emissions have no impact on the

environment or the population.

Similarly, pollutants in the extinguishing water are negligible and below the

daily limits authorised for industrial facilities.

the temperature of framework elements is under 100°C and does not exceed

31°C in suppression mode

Recommendations

For new warehouses with up to 12 m of storage height, with K25 ESFR sprinkler

systems:

both types of storage can be used: on tread and laced

a density of 67 l/min/m2 at ground level (head pressure of 2.8 bar) protects

a tyre storage configuration up to 7.45 m high, in suppression mode

a density of 91 l/min/m2 at ground level (head pressure of 5.2 bar) protects

a tyre storage configuration up to 8.75 m high, in suppression mode

Page 4: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 4

Experience feedback report Réf : SNCP/REX-INC/06-2007

Automatic fire ignition and extinguishing tests in tyre storage facilities.

1. Introduction

Under the auspices of SNCP, a study group of tyre manufacturing, logistics and

protection professionals met to further industry knowledge of fire hazard management in tyre storage facilities, specifically the performance of automatic

water-based sprinkler systems.

The members of this partnership – the SNCP, Bridgestone, Goodyear-Dunlop,

Hankook and Michelin, the logistic groups Afilog and Aliapur, and the manufacturer Tyco Fire & Building Products – have put together ambitious

specifications for significant extinguishing tests. These tests cover various configurations for storing tyres and various sprinkler types and characteristics.

The Centre National de Prévention et Protection (CNPP Entreprise) in Vernon then performed the tests.

The purpose of this experience feedback report is to present the main lessons

learnt from analyses of the test results.

Page 5: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 5

2. Test facilities

2.1 Test hall

The tests were conducted at the CNPP in test hall no. 3, measuring 30 m

long, 20 m wide and 24 m high.

The test hall has metal walls and structural elements. Each of the hall's

4 facades is equipped with a rolling shutter (width: 4 m/height: 4.5 m) generally kept open at 40–50 cm from the ground to simulate air intake in a

warehouse configuration.

The roof of the test hall is equipped with a smoke extraction system:

four 5.2 m² louvered lateral openings, kept closed for the tests

1 central 25 m² opening, kept 50–100% open depending on the test

Test hall ground is equipped with a 64m² fire resistant material platform

located in the middle of the hall.

2.2 Extinguishing system

A moveable 18 m x 15 m metal ceiling with an adjustable height of 9–12 m

was installed in the centre of the test hall.

The ceiling was equipped with a 3 m x 3 m main pipework grid fitted with

20 pendant DN65 drops on which model TY 9226 ESFR, K25, RTI 26, 74°C, sprinklers were installed.

Main pipework is completed at its end with a 4 pendant antenna for warning sprinklers installation (same sprinklers used in test with reduced

opening).

2.3 Tyre storage configurations

There were 4 to 5 levels of tyre storage (7.45 m or 8.75 m high), covering a

floor area of 12 to 14 pallets depending on the test. The tyres were arranged on tread and/or laced.

Page 6: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 6

Two pallet designs was used, depending on the test:

Monoblock pallet E4 folding pallet

Outside width between tyres 1.30 m to 1.43 m 1.20 m to 1.35 m

Inside width between uprights 1.24 m 1.05 m

Outside length 1.93 m 2.35 m

Inside length between uprights 1.74 m 2.20 m

Height 1.55 m 2.20 m

Spacing between pallets, measured at the

base in both directions, varies from 1 to 27 cm depending on the tests (x in the

diagram).

2.4 Ignition system

The fire ignition system consisted of cotton pellets, each soaked in 320 ml

of fuel and enclosed in a plastic film bag (L = 15 cm, ∅ = 8 cm). Two igniters, each consisting of two pellets, were arranged at ground level at the intersection between pallets A20, A30, B20 and B30, in the free space

between the pallets and positioned against the tyres.

Stockage témoin

2,4 m

1 2 3 4

A

B

C

D

2.5 Instrumentation

1 thermocouple per sprinkler head to detect its operating temperature

14 thermocouples in the storage

1 thermocouple at the top of the control storage area

2 thermocouples above the ignition point, close to the ceiling

5 thermocouples in a control angle iron placed against the ceiling above

the ignition point

5 thermocouples in the roof’s structural elements above the ceiling

Water flow rate and pressure

2.6 Video monitoring

Each test was filmed by video cameras installed around the storage area.

x

Page 7: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 7

Appendices 1 to 5:

The appendices contain additional data for each of the five ESFR sprinkler tests:

tables of parameters and results

diagrams of open sprinkler heads and their opening times relative to ignition

time 0

superimposed curves for temperature and water discharge

Appendix 1 – Test CNPP21 (VG7)

Tyre storage

Tyre configuration On tread Number of tyres per pallet 36

Nominal storage height 7.45 m Monoblock pallet levels 5

Nb of pallets on the ground 14 Total number of pallets 70

Spacing between pallets x = 5 cm Number of tyres stored 2 520

Storage configuration below ceiling Ignition point between heads 13 and 14

Extinguishing system configuration

Ceiling height 9 m Sprinkler head height (deflectors)

8.7 m

Clearance between deflectors

and top of storage

1.25 m Head (deflector) to ceiling

clearance

0.3 m

Sprinkler type K25 ESFR Sprinkler K-factor K = 363

Sprinkler RTI 26 Operating temperature 74 °C

Sprinkler spacing 3 m x 3 m Sprinkler SIN TY 9226

Nominal sprinkler density 42 l.m-2.min

-1 Sprinkler pressure 1.1 bar

Nominal flow per sprinkler 378 l/min Extinguishing agent Water only

Test conditions

Test date 21/06/2005 Outside temperature 18 °C

Air intake Natural; only north door open to 3 m from ground

Smoke extraction Natural, central vent 100% open

Conditions for ending test Avg temp at angle iron exceeds 638 °C

One of the ceiling structure temperatures exceeds 350°C

Test results

First sprinkler opened 2 min 38 s Total no. of sprinklers open 7

Last sprinkler opened 29 min 20 s Max temp 5 cm under ceiling 230 °C

Damage to test tyres No Max temp 30 cm under ceiling 83 °C

Avg max angle iron temp 95 °C Time max temp attained 21 min 25 s

Max ceiling framework temp 41 °C Time max temp attained 22 min 05 s

Total no. of pallets damaged 22 --- ---

Equivalent no. of tyres burnt 61 tyres or 2.5 % of test stock

Extinguishing efficiency Control mode achieved

Page 8: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 8

Max=50°CMax =38°C Max=65°C Max=57°C Max=57°C Max=36°C

Max=63°CMax =45°C Max=77°C Max=63°C Max=93°C Max=96°C

2 1 4 3 5b 5

76 10b 10

12 11 14 13 15b 15

17 16 19 18 20b 20

98

3 min 50 s

Nord

2 min 38 s

3 min 10 s 3 min 14 s

4 min 30 s 29 min 20 s

12 min 25 s

Sprinkler non ouvert Sprinkler ouvert

Max=46°CMax =39°C Max=55°C Max=57°C Max=91°C Max=66°C

Max=43°CMax =42°C Max=67°C Max=60°C Max=78°C Max=69°C

(1) North - (2) Unopened sprinklers – (3) Open sprinklers

Temperatures / Open sprinkler heads

Températures / Têtes sprinkler ouvertes

0

50

100

150

200

250

0 5 10 15 20 25 30 35 40 45

Temps (min)

Tem

péra

ture

(°C

)

0

1

2

3

4

5

6

7

8

9

10

Cornière moyenne

30 cm sous plafond

5 cm sous plafond

Nbre total têtes ouvertes

Nbre têtes ouvertes débitant

30 min : Pompiers en intervention

(1) 30 min : Operation by fire fighters - (2) Time (min)

(2) (3)

(1)

Avg angle iron temp

30 cm below ceiling .

5 cm below ceiling

Total no. open heads

No. open discharging

(1)

(2)

Page 9: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 9

Appendix 2 – Test CNPP22 (VG10)

Tyre storage

Tyre configuration Laced Number of tyres per pallet 40 to 48

Nominal storage height 7.45 m Monoblock pallet levels 5

Nb of pallets on the ground 14 Total number of pallets 70

Spacing between pallets x = 5 cm Number of tyres stored 2 952

Storage configuration below ceiling Ignition point between heads 13 and 14

Extinguishing system configuration

Ceiling height 9 m Sprinkler head height (deflectors)

8.7 m

Clearance between deflectors

and top of storage

1.25 m Head (deflector) to ceiling

clearance

0.3 m

Sprinkler type K25 ESFR Sprinkler K-factor K = 363

Sprinkler RTI 26 Operating temperature 74 °C

Sprinkler spacing 3 m x 3 m Sprinkler SIN TY 9226

Nominal sprinkler density 52 l.m-2.min

-1

then 67

Sprinkler pressure 1.7 bar

then 2.8

Nominal flow per sprinkler 468 l/min Extinguishing agent Water only

Test conditions

Test date 29/06/2005 Outside temperature 19 °C

Air intake Natural; 4 facade doors open to 40 cm above ground

Smoke extraction Natural, central vent 100% open

Conditions for ending test Avg temp at angle iron exceeds 638 °C

One of the ceiling structure temperatures exceeds 350°C

Test results

First sprinkler opened 3 min 54 s Total no. of sprinklers open 6

Last sprinkler opened 6 min 24 s Max temp 5 cm under ceiling 193 °C

Damage to test tyres No Max temp 30 cm under ceiling 227 °C

Avg max angle iron temp 73 °C Time max temp attained 7 min 15 s

Max ceiling framework temp 30 °C Time max temp attained 14 min 20 s

Total no. of pallets damaged 22 --- ---

Equivalent no. of tyres burnt 57 tyres or 2 % of test stock

Extinguishing efficiency Control mode achieved with 52 l/min/m

2

Suppression mode achieved with 67 l/min/m2

Page 10: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 10

Max=47°CMax =40°C Max=58°C Max=43°C Max=62°C Max=70°C

Max=49°CMax =39°C Max=39°C Max=49°C Max=54°C Max=55°C

2 1 4 3 5b 5

76 10b 10

12 11 14 13 15b 15

17 16 19 18 20b 20

98

4 min 00 s

Nord

4 min 00 s

Max=60°CMax =40°C Max=42°C Max=40°C Max=74°C Max=69°C

Max=42°CMax =46°C Max=47°C Max=38°C Max=40°C Max=66°C

3 min 54 s 3 min 58 s

6 min 24 s

6 min 19 s

Sprinkler non ouvert Sprinkler ouvert

(1) North - (2) Unopened sprinklers – (3) Open sprinklers

Temperatures / Open sprinkler heads

Températures / Têtes sprinkler ouvertes

0

20

40

60

80

100

120

140

160

180

200

0 5 10 15 20 25 30 35 40 45 50 55 60

Temps (min)

Tem

péra

ture

(°C

)

0

1

2

3

4

5

6

7

8

9

10

Cornière moyenne

30 cm sous plafond

5 cm sous plafond

Nbre total têtes ouvertes

Nbre têtes ouvertes débitant

Taux d'application initial + 30 % : 69 l.m-2.min-1

Réseau secours

pour exercice

(1) Initial sprinkler density + 30 % : 69 l.m

-2.min

-1 - (2)Emergency supply for test

(3) Time (min)

Avg angle iron temp

30 cm below ceiling .

5 cm below ceiling

Total no. open heads

No. open discharging heads

(1)

(2) (3)

(2) (1)

(3)

Page 11: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 11

Appendix 3 – Test CNPP23 (VG7-0)

Tyre storage

Tyre configuration On tread Number of tyres per pallet 32 to 36

Nominal storage height 7.45 m Monoblock pallet levels 5

Nb of pallets on the ground 14 Total number of pallets 70

Spacing between pallets x = 5 cm Number of tyres stored 2 280

Storage configuration below ceiling Ignition point between heads 13 and 14

Extinguishing system configuration

Ceiling height 10.5 m Sprinkler head height (deflectors)

10.2 m

Clearance between deflectors

and top of storage

2.75 m Head (deflector) to ceiling

clearance

0.3 m

Sprinkler type K25 ESFR Sprinkler K-factor K = 363

Sprinkler RTI 26 Operating temperature 74 °C

Sprinkler spacing 3 m x 3 m Sprinkler SIN TY 9226

Nominal sprinkler density 67 l.m-2.min

-1 Sprinkler pressure 2.8 bar

Nominal flow per sprinkler 603 l/min Extinguishing agent Water only

Test conditions

Test date 06/10/2005 Outside temperature 13 °C

Air intake Natural; 4 facade doors open to 50 cm above ground

Smoke extraction Natural, central vent 50 % open

Conditions for ending test Avg temp at angle iron exceeds 400°C

One of the ceiling structure temperatures exceeds 350°C

Test results

First sprinkler opened 4 min 27 s Total no. of sprinklers open 2

Last sprinkler opened 40 min 20 s Max temp 5 cm under ceiling 87 °C

Damage to test tyres No Max temp 30 cm under ceiling 65 °C

Avg max angle iron temp 31 °C Time max temp attained 40 min 25 s

Max ceiling framework temp 24 °C Time max temp attained ---

Total no. of pallets damaged 10 --- ---

Equivalent no. of tyres burnt 14 tyres or 0.7 % of test stock

Extinguishing efficiency Suppression mode achieved

Page 12: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 12

Max=40°CMax =39°C Max=38°C Max=29°C Max=47°C Max=50°C

Max=55°CMax =50°C Max=38°C Max=42°C Max=49°C Max=32°C

2 1 4 3 5b 5

76 10b 10

12 11 14 13 15b 15

17 16 19 18 20b 20

98

4 min 27 s

Nord

40 min 20 s

Max=44°CMax =41°C Max=38°C Max=30°C Max=58°C Max=62°C

Max=73°CMax =49°C Max=49°C Max=35°C Max=67°C Max=60°C

Sprinkler non ouvert Sprinkler ouvert

(1) North - (2) Unopened sprinklers – (3) Open sprinklers

Temperatures / Open sprinkler heads

Températures / Têtes sprinkler ouvertes

0

10

20

30

40

50

60

70

80

90

100

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90

Temps (min)

Tem

péra

ture

(°C

)

0

1

2

3

4

5

Cornière moyenne

30 cm sous plafond

5 cm sous plafond

Nbre total têtes ouvertes

Nbre têtes ouvertes débitant

(1) Time (min)

Avg angle iron temp

30 cm below ceiling .

5 cm below ceiling

Total no. open heads

No. open discharging

(1)

(2) (3)

(1)

Page 13: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 13

Appendix 4 – Test CNPP24 (VG8)

Tyre storage

Tyre configuration Mixed Number of tyres per pallet 32 to 40

Nominal storage height 7.45 m Monoblock pallet levels 5

Nb of pallets on the ground 14 Total number of pallets 70

Spacing between pallets x = 5 cm Number of tyres stored 2 444

Storage configuration below ceiling Ignition point under head 13

Extinguishing system configuration

Ceiling height 12 m Sprinkler head height (deflectors)

11.7 m

Clearance between deflectors

and top of storage

4.25 m Head (deflector) to ceiling

clearance

0.3 m

Sprinkler type K25 ESFR Sprinkler K-factor K = 363

Sprinkler RTI 26 Operating temperature 74 °C

Sprinkler spacing 3 m x 3 m Sprinkler SIN TY 9226

Nominal sprinkler density 67 l.m-2.min

-1 Sprinkler pressure 2.8 bar

Nominal flow per sprinkler 603 l/min Extinguishing agent Water only

Test conditions

Test date 13/10/2005 Outside temperature 21 °C

Air intake Natural; 4 facade doors open to 50 cm above ground

Smoke extraction Natural, central vent 50 % open

Conditions for ending test Avg temp at angle iron exceeds 400°C

One of the ceiling structure temperatures exceeds 350°C

Test results

First sprinkler opened 3 min 07 s Total no. of sprinklers open 1

Last sprinkler opened 3 min 07 s Max temp 5 cm under ceiling 83 °C

Damage to test tyres No Max temp 30 cm under ceiling 73 °C

Avg max angle iron temp 26 °C Time max temp attained 3 min 30 s

Max ceiling framework temp 22 °C Time max temp attained ---

Total no. of pallets damaged 7 --- ---

Equivalent no. of tyres burnt 6 tyres or 0.3 % of test stock

Extinguishing efficiency Suppression mode achieved

Page 14: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 14

Nord

Max=34°CMax =30°C Max=30°C Max=28°C Max=37°C Max=28°C

21 43 5b 5

76 10b 10

12 11 14 13 15b 15

17 16 19 18 20b 20

98

3 min 07 s

Max=35°CMax =29°C Max=30°C Max=28°C Max=41°C Max=41°C

Max=35°CMax =29°C Max=28°C Max=25°C Max=70°C Max=34°C

Max=31°CMax =28°C Max=28°C Max=27°C Max=55°C Max=35°C

Sprinklers non ouverts Sprinklers ouverts

(1) North - (2) Unopened sprinklers – (3) Open sprinklers

Temperatures / Open sprinkler heads

Températures / Têtes sprinkler ouvertes

0

10

20

30

40

50

60

70

80

90

100

0 5 10 15 20 25 30 35 40 45 50 55 60

Temps (min)

Tem

péra

ture

(°C

)

0

1

2

3

4

5

Cornière moyenne

30 cm sous le plafond

5 cm sous le plafond

Nbre total têtes ouvertes

Nbre têtes ouvertes débitant

(1) Time (min)

Avg angle iron temp

30 cm below ceiling .

5 cm below ceiling

Total no. open heads

No. open discharging heads

(1)

(2) (3)

(1)

Page 15: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 15

Appendix 5 – Test CNPP25 (VG11)

Tyre storage

Tyre configuration Laced Number of tyres per pallet 56 to 96

Nominal storage height 8.75 m E4 pallet levels 4

Nb of pallets on the ground 12 Total number of pallets 48

Spacing between pallets x = 1–27 cm Number of tyres stored 3 799

Storage configuration below ceiling Ignition point under head 13

Extinguishing system configuration

Ceiling height 12 m Sprinkler head height (deflectors)

11.7 m

Clearance between deflectors

and top of storage

2.95 m Head (deflector) to ceiling

clearance

0.3 m

Sprinkler type K25 ESFR Sprinkler K-factor K = 363

Sprinkler RTI 26 Operating temperature 74 °C

Sprinkler spacing 3 m x 3 m Sprinkler SIN TY 9226

Nominal sprinkler density 91 l.m-2.min

-1 Sprinkler pressure 5.2 bar

Nominal flow per sprinkler 819 l/min Extinguishing agent Water only

Test conditions

Test date 20/10/2005 Outside temperature 17 °C

Air intake Natural; 4 facade doors open to 50 cm above ground

Smoke extraction Natural, central vent 50 % open

Conditions for ending test Avg temp at angle iron exceeds 400°C

One of the ceiling structure temperatures exceeds 350°C

Test results

First sprinkler opened 2 min 59 s Total no. of sprinklers open 1

Last sprinkler opened 2 min 59 s Max temp 5 cm under ceiling 87 °C

Damage to test tyres No Max temp 30 cm under ceiling 82 °C

Avg max angle iron temp 23 °C Time max temp attained 3 min 20 s

Max ceiling framework temp 19 °C Time max temp attained ---

Total no. of pallets damaged 6 --- ---

Equivalent no. of tyres burnt 7 tyres or 0.2% of test stock

Extinguishing efficiency Suppression mode achieved

Page 16: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Copyright SNCP december 2007 Page 16

Nord

Max=28°CMax =26°C Max=21°C Max=22°C Max=31°C Max=29°C

Max=24°CMax =25°C Max=24°C Max=22°C Max=23°C Max=24°C

Stockage témoin

21 43 5b 5

76 10b 10

12 11 14 13 15b 15

17 16 19 18 20b 20

98

2 min 59 s

Max=29°CMax =25°C Max=22°C Max=22°C Max=38°C Max=28°C

Max=29°CMax =26°C Max=23°C Max=27°C Max=34°C Max=25°C

Sprinkler non ouvert Sprinkler ouvert

(1) North - (2) Unopened sprinklers – (3) Open sprinklers – (4) Control storage

Temperatures / Open sprinkler heads

Température / Têtes sprinkler ouvertes

0

10

20

30

40

50

60

70

80

90

100

0 5 10 15 20 25 30 35 40 45 50 55 60

Temps (min)

Tem

péra

ture

(°C

)

0

1

2

3

4

5

Cornière moyenne

30 cm sous plafond

5 cm sous plafond

Nbre total têtes ouvertes

Nbre têtes ouvertes débitant

(1) Time (min)

Avg angle iron temp

30 cm below ceiling .

5 cm below ceiling

Total no. open heads

No. open discharging heads

(1)

(2) (3)

(1)

(4)

Page 17: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Appendix 6 : Summary table of CNPP full-scale tests using K25 ESFR sprinklers (to optimise new warehouses)

Test series to define protection characteristics for future warehouses:

with K25 ESFR sprinklers

for building heights up to 12 m

for all types of tyre arrangement (on side, on tread and laced)

for storage heights up to 8.75 m

Page 18: SNCP experience feedback report - Accueil prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler Recommendations on fire protection

Syndicat National du Caoutchouc et des Polymères - Comité de Prévention et Protection Incendie

Summary table of CNPP full-scale tests using K25 ESFR sprinklers (to optimise new warehouses)

Test series to define protection characteristics for future warehouses:

¤ with K25 ESFR sprinklers

¤ for building heights up to 12 m

¤ for all types of tyre arrangement (on side, on tread and laced)

¤ for storage heights up to 8.75 m

CNPP 21 (VG 7)

21/6/05

CNPP 22 (VG 10)

29/6/05

CNPP 23 (VG 7-0)

6/10/05

CNPP 24 (VG 8)

13/10/05

CNPP 25 (VG 11)

20/10/05

Confirm NFPA Rule 13 on tread tyres Confirm NFPA Rule 13 for laced tyres,

using K25 heads.

Test whether suppression mode is

achievable with water density of 67

l/min/m2.

Test whether suppression mode is

achievable with water density of 67

l/min/m2 and a ceiling height

of 10.5 m

Test whether suppression mode is

achievable with a density of 67

l/min/m2 and a ceiling height of 12 m

for both laced and on tread storage.

Test whether suppression mode is

achievable with a density of 91

l/min/m2 and a ceiling height of 12 m

for laced storage 8.75m high.

Storage Type of storage on tread laced on tread laced and on tread laced

Storage height (m) 7,45 7,45 7,45 7,45 8,75

Ceiling height (m) 9 9 10,5 12 12

Clearance (m) 1.25 1,25 2,75 4,25 2,95

Number of pallets on floor 3x4 + 2 3x4 + 2 3x4 +2 3x4 +2 3x4

Number of pallet levels 5 5 5 5 4

Number of tyres 2520 2952 2280 2444 3799

Sprinkler Sprinkler type ESFR ESFR ESFR ESFR ESFR

SIN number TY 9226 TY 9226 TY 9226 TY 9226 TY 9226

K-factor 25.2 / 363 25.2 / 363 25.2 / 363 25.2 / 363 25.2 / 363

Operating temperature (°C) 74 74 74 74 74

RTI 26 26 26 26 26

Water Actual head pressure (bar) 1,1 1.7 then 2.8 2,8 2,8 5,2

(only) Flow per head (l/min) 378 468 then 600 603 603 819

Water density at floor (l/min/m2) 42 52 then 67 67 67 91

Fire Location of ignition below heads between 2 heads between 2 heads between 2 heads beneath 1 head beneath 1 head

Overall assessment of• test resultsControlled

controlled with 52 l/min/m2

Suppressed with 67 l/min/m2 Suppressed Suppressed Suppressed

Findings Opening time 1st head 2'38" 3'54" 4'27" 3'07" 2'59"

main Number of heads open 7 6 2 1 1

Time to open, heads 2 to n 3'10"/3'14"/3'50"/4'30"/12'25"/29'2

0"

3'58"/4'/4'/6'19"/6'24" 40'20"

Max. angle iron temp (°C) 95 73 31 26 23

Max ceiling gas temperature (°C) 230 223 87 83 87

Mass burned (kg,% test storage) 600 kg/2% 570 kg/2% 140 kg/0.6% 60 kg/0.3% 60 kg/0.2%

Lessons learned from test With 7 heads open, only control mode

is achieved.

Head 7 opens belatedly at 29'20", with

the fire well-contained and with little

strength.

The suppression mode established by

the rule cannot be confirmed with

certainty.

With 52 l/min/m2:

Control mode is achieved (visual

observation, low corner temperature,

ceiling gas temperature greatly

reduced).

With 67 l/min/m2, suppression mode

is achieved.

The fire’s kinetic energy is similar for

both types of storage, laced and on

tread.

The rule is confirmed using K25 heads.

Suppression mode is achieved.

Clearance has no visible or measurable

effect.

The fire is shielded within the rolls of

tyres until the top of the tyre is

destroyed and water can get through.

The fire does not travel to adjacent tyre

rolls (top, bottom, left right), but can

propagate through the ends of the

rolls.

Suppression mode is achieved.

Clearance has no visible or measurable

effect.

The fire’s kinetic energy is the same for

both types of storage, laced and on

tread. The effectiveness of fire

containment is the same in both cases.

Suppression mode is achieved.

Tests

date

Test objectives

Controlled with 52 l/min/m2