Building Smoke Management
March 2010By: Felipe Agustin
-
8/12/2019 Smoke Management Control
2/17
-
8/12/2019 Smoke Management Control
3/17
Toxic Gas; CO; Narcotic gas
Hydrogen Cyanide; Acidic halides; and Acrolein
Reduced oxygen level; High Temperatures; Reduced Visibility.
-
8/12/2019 Smoke Management Control
4/17
Hinder escape;
Hinder Rescue
-
8/12/2019 Smoke Management Control
5/17
Contain the smoke within the source of fireand avoid spreading out to other rooms;
Minimize the production of smoke;
Maintain tenable environment within all exit
access and area of refuge access path forthe time necessary to allow occupants toreach an exit or area of refuge.
-
8/12/2019 Smoke Management Control
6/17
Atriums;
Large Void Spaces;
Areas of Refuge;
Corridors;
Lift lobbies; Fire compartment
Stairwell Pressurization
-
8/12/2019 Smoke Management Control
7/17
Smoke Production; Type, location and quantity of fuel;
Height cross sectional area and area (volume) of the area to be protected;
Volume of unseparated space that communicates with another large volumearea;
Type & location of occupancies;
Barriers separating adjacent spaces from a large volume space; Egress routes from large volume space and any communicating space;
Areas of refuge.
-
8/12/2019 Smoke Management Control
8/17
Standard Fire Exhaust system Stop air supply to fire effected floors; Supply air to all fire unaffected floors; Extract from fire effected floors;
Stop all extract from fire effected floors; Maintain 20 Pa Pressure differentialbetween fire effected and unaffectedfloors.
*Uses Larger riser sizes.
-
8/12/2019 Smoke Management Control
9/17
Alternative Fire Exhaust system: Stop air supply to fire affected floors; Supply air to immediate (one only) floor
above and below fire affected floors;
Extract from fire affected floor; Stop all extract from immediate (oneonly) floor above and below fire affectedfloors;
All other floors, stop supply and extract.
-
8/12/2019 Smoke Management Control
10/17
Central VAV system: Stop air supply to all floors; Extract air from fire affected floor; Stop all extract from all unaffected
floors; Use fire rated exhaust fan.
-
8/12/2019 Smoke Management Control
11/17
Floor by Floor VAV system: Supply & Exhaust air shafts sized for
minimum outside air only; Fire rated exhaust fan to be fitted with
VSD or 2 speed motor control; Supply air fan to be fitted with VScontroller;
During fire mode: both supply andextract fan to enable at high speed;
Air exhaust from fire affected floor; Supply to immediate floor above and
below.
-
8/12/2019 Smoke Management Control
12/17
Tempered Outside Air Supplied with ChilledBeams:
Supply & Exhaust air shafts sized forminimum outside air only;
Fire rated exhaust fan; During fire mode MO1 to close MO2 toopen;
Outside air fan supply air to affectedfloor above & below fire affected floor forpressurization;
Return air fan fitted with VS Controller; Fan to run high speed for exhaust from
fire affected floor.
-
8/12/2019 Smoke Management Control
13/17
Design Limitations (NFPA 92B): Smoke Layer depth = 20% of floor to ceiling
height (rule of thumb not to exceed 1meter; Based on Engineering Analysis; Make-up air velocity not to exceed 1.02 m/s to
avoid smoke disruption and spreading; Door opening shall not force door opening to
pressure limit (max 50 Pa).
-
8/12/2019 Smoke Management Control
14/17
Minimum Design Pressure Difference AcrossBarriers as per NFPA 92A:
Building Type Ceiling Height Design Pressure
Difference (in w.g.)
AS Any 0.05 or (12.5 Pa)
NS 9 ft or 2.7 meter 0.10 or (25 Pa)
NS 15 ft or 4.6 meters 0.14 or (35 Pa)
NS 21 ft or 6.4 meters 0.18 or (45 Pa)
Note: AS Sprinklered; NS Non Sprinklered
-
8/12/2019 Smoke Management Control
15/17
-
8/12/2019 Smoke Management Control
16/17
Smoke Dampers Shall be listed in accordance with ANSI/UL 555S;
Control System shall be listed in accordance with ANSI/UL 864Standard for Control Units and Accessories for Fire Alarm Systems;
Smoke Detectors Conventional type Beam type:
Projected; and Optical;
Fire Curtains - Shall be listed in accordance with ANSI/UL 268;
Fans
-
8/12/2019 Smoke Management Control
17/17
SAVES LIFE;
CAN BE INTEGRATED WITH MECHANICALVENTILATION SYSTEMS;
CAN BE DESIGNED TO ASSISTEMERGENCY RESPONSE PERSONNEL;
CAN BE USED AS POST FIRE SMOKEREMOVAL