  • 8/12/2019 Smoke Management Control

    1/17

    Building Smoke Management

    March 2010By: Felipe Agustin

  • 8/12/2019 Smoke Management Control

    2/17

  • 8/12/2019 Smoke Management Control

    3/17

    Toxic Gas; CO; Narcotic gas

    Hydrogen Cyanide; Acidic halides; and Acrolein

    Reduced oxygen level; High Temperatures; Reduced Visibility.

  • 8/12/2019 Smoke Management Control

    4/17

    Hinder escape;

    Hinder Rescue

  • 8/12/2019 Smoke Management Control

    5/17

    Contain the smoke within the source of fireand avoid spreading out to other rooms;

    Minimize the production of smoke;

    Maintain tenable environment within all exit

    access and area of refuge access path forthe time necessary to allow occupants toreach an exit or area of refuge.

  • 8/12/2019 Smoke Management Control

    6/17

    Atriums;

    Large Void Spaces;

    Areas of Refuge;

    Corridors;

    Lift lobbies; Fire compartment

    Stairwell Pressurization

  • 8/12/2019 Smoke Management Control

    7/17

    Smoke Production; Type, location and quantity of fuel;

    Height cross sectional area and area (volume) of the area to be protected;

    Volume of unseparated space that communicates with another large volumearea;

    Type & location of occupancies;

    Barriers separating adjacent spaces from a large volume space; Egress routes from large volume space and any communicating space;

    Areas of refuge.

  • 8/12/2019 Smoke Management Control

    8/17

    Standard Fire Exhaust system Stop air supply to fire effected floors; Supply air to all fire unaffected floors; Extract from fire effected floors;

    Stop all extract from fire effected floors; Maintain 20 Pa Pressure differentialbetween fire effected and unaffectedfloors.

    *Uses Larger riser sizes.

  • 8/12/2019 Smoke Management Control

    9/17

    Alternative Fire Exhaust system: Stop air supply to fire affected floors; Supply air to immediate (one only) floor

    above and below fire affected floors;

    Extract from fire affected floor; Stop all extract from immediate (oneonly) floor above and below fire affectedfloors;

    All other floors, stop supply and extract.

  • 8/12/2019 Smoke Management Control

    10/17

    Central VAV system: Stop air supply to all floors; Extract air from fire affected floor; Stop all extract from all unaffected

    floors; Use fire rated exhaust fan.

  • 8/12/2019 Smoke Management Control

    11/17

    Floor by Floor VAV system: Supply & Exhaust air shafts sized for

    minimum outside air only; Fire rated exhaust fan to be fitted with

    VSD or 2 speed motor control; Supply air fan to be fitted with VScontroller;

    During fire mode: both supply andextract fan to enable at high speed;

    Air exhaust from fire affected floor; Supply to immediate floor above and

    below.

  • 8/12/2019 Smoke Management Control

    12/17

    Tempered Outside Air Supplied with ChilledBeams:

    Supply & Exhaust air shafts sized forminimum outside air only;

    Fire rated exhaust fan; During fire mode MO1 to close MO2 toopen;

    Outside air fan supply air to affectedfloor above & below fire affected floor forpressurization;

    Return air fan fitted with VS Controller; Fan to run high speed for exhaust from

    fire affected floor.

  • 8/12/2019 Smoke Management Control

    13/17

    Design Limitations (NFPA 92B): Smoke Layer depth = 20% of floor to ceiling

    height (rule of thumb not to exceed 1meter; Based on Engineering Analysis; Make-up air velocity not to exceed 1.02 m/s to

    avoid smoke disruption and spreading; Door opening shall not force door opening to

    pressure limit (max 50 Pa).

  • 8/12/2019 Smoke Management Control

    14/17

    Minimum Design Pressure Difference AcrossBarriers as per NFPA 92A:

    Building Type Ceiling Height Design Pressure

    Difference (in w.g.)

    AS Any 0.05 or (12.5 Pa)

    NS 9 ft or 2.7 meter 0.10 or (25 Pa)

    NS 15 ft or 4.6 meters 0.14 or (35 Pa)

    NS 21 ft or 6.4 meters 0.18 or (45 Pa)

    Note: AS Sprinklered; NS Non Sprinklered

  • 8/12/2019 Smoke Management Control

    15/17

  • 8/12/2019 Smoke Management Control

    16/17

    Smoke Dampers Shall be listed in accordance with ANSI/UL 555S;

    Control System shall be listed in accordance with ANSI/UL 864Standard for Control Units and Accessories for Fire Alarm Systems;

    Smoke Detectors Conventional type Beam type:

    Projected; and Optical;

    Fire Curtains - Shall be listed in accordance with ANSI/UL 268;

    Fans

  • 8/12/2019 Smoke Management Control

    17/17

    SAVES LIFE;

    CAN BE INTEGRATED WITH MECHANICALVENTILATION SYSTEMS;

    CAN BE DESIGNED TO ASSISTEMERGENCY RESPONSE PERSONNEL;

    CAN BE USED AS POST FIRE SMOKEREMOVAL