smart pressure transmitters - autekautek.no/datasheets/smar/ld291e.pdf · 0 to 85 °c (-32 to 185...
TRANSCRIPT
-
SMART PRESSURE TRANSMITTERS4 to 20 mA + HART® Digital Communication
smarB27
-
B28smar
DESCRIPTION
0 ~ 1.25 kPa to 0 ~ 25 MPa (0 ~ 5 inH20 to 0 ~ 3600 psi) ±0.1% accuracy of the calibrated range Accepts calibration from URL to URL/40 Wetted parts in 316 SST or Hastelloy Digital display (optional) Zero, span and damping adjustment through HART® local switches(only if fitted with display)
Digital electronics, sensor and communication Self diagnostics Weather proof, explosion proof and intrinsically safe
The series LD29X is the economical alternative in rou-tine gage pressure measurement. This lightweight de-sign eliminates the need for mounting brackets andtransmitter supports in many applications.
The model LD291 offers digital HART® based commu-nication simplifying calibration and providing remotediagnostics.
Its microprocessor-based electronics allow for total in-terchangeability with SMAR capacitive sensors. It au-tomatically corrects sensor characteristic changescaused by temperature fluctuations.
All members of the LD29X series use SMAR’s fieldproven capacitive sensors. Also, an optional LCD indi-cator can be added to provide additional operationsand local indication.
NEW
-
B29 smar
TECHNICAL CHARACTERISTICS
Functional Specifications
ServiceLiquid, gas or vapor application
OutputTwo wire, 4-20 mA with HART® superimposed digital commu-nication signal.
Power Supply12 - 45 Vdc
Load LimitationMax. Impedance (VPOWER SUPPLY - 12 Vdc)/0.02Min. 250 required for communication
IndicatorOptional 4½-digit numerical and 5-character alphanumericalLCD indicator.
Hazardous Area CertificationsExplosion proof, weather proof and intrinsically safe(CENELEC and FM standards).
Zero and Span AdjustmentBy Local Adjustment from 0 to 0.975 URL, URL = UpperRange Limit.
Temperature LimitsAmbient: -40 to 85 °C (-40 to 185 °F).Process: -40 to 100 °C (-40 to 212 °F) (Silicone Oil).
0 to 85 °C (-32 to 185 °F) (Fluorolube Oil).Storage: -40 to 100 °C (-40 to 212 °F).Display: -10 to 60 °C (14 to 140 °F) operation.
-40 to 85 °C (-40 to 185 °F) without damage.
Failure AlarmIn case of sensor or circuit failure, the self diagnostics drivesthe output to 3.9 or 21.0 mA and according to user’s choice.
Turn-on TimePerforms within specifications in less than 10 seconds afterpower is applied to the transmitter.
Overpressure Limits14 MPa (2000 psi) for ranges 2, 3, 431 MPa (4500 psi) for range 5
These overpressures will not damage the transmitter, but anew calibration may be necessary.
Humidity Limits0 to 100% RH.
Damping AdjustmentBy Hand-Held Terminator Local adjustment: 0 ~ 32 secondsplus intrinsic sensor response time (0.2s).
ConfigurationBy Digital Communication HART® or partially by local adjust-ment.
Performance Specifications
Accuracy± 0.1% of span (for span 0.1 URL).± 0.05 (1 +(0.1 URL/span))% of span (for span < 0.1 URL).
For Ranges 5:± 0.2% of span (for span 0.1 URL).± 0.1 (1 +(0.1 URL/span))% of span (for span < 0.1 URL).
Stability±0.2% of URL for 1 year.
Temperature Effect±(0.18% URL + 0.18% span) per 20 °C (36 °F).
Power Supply Effect0.005% of calibrated span per volt.
Mounting Position EffectZero shift of up to 250 Pa (1 inH20) which can be calibratedout. No span effect.
Electro-Magnetic EffectDesigned to comply with IEC 801 and European standardsEN50081 and EN50082.
Physical Specifications
Electrical Connection½ -14 NPT, Pg 13,5 or M20 x 1,5
Process Connection½ -14 NPT (Female or Male), G ½ A DIN 16288 (Male).
Wetted Parts• Isolating Diaphragms and Process Connection
316L SST, Hastelloy C276.
Nonwetted Parts• Electronic Housing
Injected aluminum with polyester painting or 316 SST(NEMA 4X, IP67).
• Fill FluidSilicone or Fluorolube Oil.
• Cover O-RingsBuna N.
• Mounting BracketOptional universal mounting bracket for surface or vertical/horizontal 2"-pipe (DN 50) carbon steel with polyesterpainting or 316 SST. Accessories (bolts, nuts, washersand U-clamp) in carbon steel or 316 SST.
• Identification Plate316 SST.....
Approximate Weights< 2.0 kg (4lb): aluminum housing without mounting bracket.
NEW
-
B30smar
ORDERING CODE
Hastelloy is a trademark of the Cabot Corp.Fluorolube is a trademark of Hooker Chemical Corp.HART is a trademark of Hart Communication Foundation.
* Meets NACE material recommendations per MR-01-75.** Leave it blank for no optional items.
MODELLD291
SMART PRESSURE TRANSMITTERS - 4 to 20 mA + HART Digital Communication
Diaphragm Material
GageGageGageGage
316L SST316L SSTHastelloy C276Hastelloy C276Others - Specify
TYPICAL MODEL NUMBER
Without IndicatorWith Digital Indicator
Local Indicator
½ - 14 NPT- FemaleG ½ A DIN 16288 Form B - MaleG ½ A DIN 16288 Form D - Male½ - 14 NPT - MaleOthers - Specify
Process Connections
Electrical Connections
½ - 14 NPTM20 x 1,5Pg 13,5 DIN
Without Mounting BracketCarbon Steel Mounting Bracket with Carbon Steel accessories316 SST Mounting Bracket with 316 SST accessoriesCarbon Steel Mounting Bracket with 316 SST accessoriesOthers - Specify
316 SST HousingSpecial Options - Specify
Optional Items **
CODE
M2M3M4M5
Range
1.256.25
62.500.625
totototo
50250
250025
kPakPakPaMPa
525
990
totototo
2001000
3603600
inH2OinH2Opsipsi
CODE
1I2I3H4HZ
Silicone OilFluorolube OilSilicone Oil*Fluorolube Oil*
316L SST316L SSTHastelloy C276*Hastelloy C276*
Fill Fluid (Low Side) Process Connection Material
CODE
01
CODE
1GHMZ
0AB
CODE
Mounting Bracket
0127Z
CODE
CODE
H1ZZ
LD291 M2 1I 0 1 A 0- - / **-
-
B31 smar
DIMENSIONS
Dimensions are mm (in)
ElectricalConnection(Both Sides)
113(4.44)
83(3
.26)
Allow 150 mm minimum for local zero and spanadjustment with magnetic tools
DN
50(2
” P
IPE
)
101(3,98)
165,4(6.48)
X
143.7(5,66)
62,1(2.44)
T
Z
113(4.44)
83(3
.26)
Allow 150 mm minimum for local zero and spanadjustment with magnetic tools
T
DN
50(2
” P
IPE
)
101(3.98)
165,4(6.48)
X97
(3.8
1)
83(3.26)
143,7(5.66)
62,1(2.44)
FEMALE
MALE
Z
83(3.26)
Y97
(3.8
1)
31,7(1.25)
Process ConnectionTheared NPT 1/2”
14 NPT Male
Y
Process ConnectionTheared NPT 1/2”14 NPT Female
ElectricalConnection(Both Sides)
M2/M3M4M5
41,14345,6
172,1174176,6
208,3210,2212,8
297,6299,5302,1
X Y TRange
Dimensions
Z
M2/M3M4M5
41,14345,6
202,7204,6207,2
208,3210,2212,8
297,6299,5302,1
X Y TRange
Dimensions
Z
-
B32smar
DIMENSIONS
Dimensions are mm (in)
ElectricalConnection(Both Sides)
113(4.44)
83(3
.26)
Allow 150 mm minimum for local zero and spanadjustment with magnetic tools
DN
50(2
” P
IPE
)
101(3,98)
165,4(6.48)
X
143.7(5,66)
62,1(2.44)
T
Z
113(4.44)
83(3
.26)
Allow 150 mm minimum for local zero and spanadjustment with magnetic tools
T
DN
50(2
” P
IPE
)
101(3.98)
165,4(6.48)
X97
(3.8
1)
83(3.26)
143,7(5.66)
62,1(2.44)
MALE
MALE
Z
83(3.26)
Y97
(3.8
1)
–
Process ConnectionTheared DIN G 1/2”
A Form D
ElectricalConnection(Both Sides)
Y
M2/M3M4M5
41,14345,6
208,6210,5213,1
208,3210,2212,8
297,6299,5302,1
X Y TRange
Dimensions
Z
M2/M3M4M5
41,14345,6
211,7213,6216,2
208,3210,2212,8
297,6299,5302,1
X Y TRange
Dimensions
Z