![Page 1: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/1.jpg)
SMART DISTRIBUTION APPLICATIONS &THEIRINTEGRATION IN A SMART GRID ENVIRONMENT
Presented By:Bob Uluski
Electric Power Research Institute
July, 2011
![Page 2: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/2.jpg)
![Page 3: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/3.jpg)
Key Smart Distribution Applications
• What are the major trends of the day?
• What issues need to be resolved?
• Where should the industry go from here?
![Page 4: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/4.jpg)
Distribution Voltage Optimization
• ANSI standards have some flexibility in the allowable delivery voltage
• Distribution utilities typically have delivery voltage in upper portion of the range
• Concept of CVR: Maintain voltage delivered to the customer in the lower portion of the acceptable range
Major Trend: Many electrical utilities are implementing Conservation Voltage Reduction for demand and energy reduction
![Page 5: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/5.jpg)
CVR Benefits Achieved• CVR factor for voltage reduction ranges from 0.65 to 0.7• Reduction of electrical demand ranges from 1.5% to 2.1%
– Cheap alternative to conventional generation– Reduction of total demand by 310 MW (eliminate need for
two peak shaving CTs)– No carbon or emission offsets needed
• Reduction of energy consumption ranges from 1.3% - 2%• Near unity power factor• Provide demand response capabilities• Decrease sub/feeder overloading• Reduced High and Low voltage complaints• Improve Customer voltage quality (less flicker).• Increase customer end-use appliance life by 15%.• Lower Customer Bills $16.50/yr
![Page 6: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/6.jpg)
Distribution Voltage Optimization Key issues and challenges
Major Issue: Not all feeders are created equal from a CVR perspective – Benefit varies with load type and feeder characteristics
CVR Factors for various Substations
0.0 2.0 4.0 6.0
1
3
5
7
9
11
13
15
17
19
21
23
25
27• Effectiveness measured by CVR factor:
• Average of these results: CVFf = 1.2
• CVRf usually ranges between 0.7 and 0.8
CVR factor = % change in load % change in voltage
Need ability to determine benefits in advance
![Page 7: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/7.jpg)
Distribution Voltage Optimization Key issues and challenges
Major Issue: Will the CVR benefit last long into the future? Or, will the benefits diminish in just a few years?
• Some emerging load characteristics don’t favor CVR
• Need better understanding of “up and coming” appliances to determine if CVR will provide lasting effects
![Page 8: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/8.jpg)
Distribution Voltage Optimization Key issues and challenges
Major Issue: What general approach to CVR works best?
• Standalone Voltage regulator and LTC controls with line drop compensation set to “end-of-line” voltage for CVR
• On-Site Voltage Regulator (OVR) for single location voltage regulation
• “Rule-based” DA control of capacitor banks and voltage regulators for CVR with/without voltage measurement feedback from end of line
• “Auto-Adaptive” voltage regulation (e.g. PCS Utilidata“AdatiVolt”, Cooper Power Systems IVVC)
• “Distribution model based” Volt-VAR Optimization
![Page 9: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/9.jpg)
Distribution Voltage Optimization Key issues and challenges
Major Issue: What general approach to CVR works best?
![Page 10: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/10.jpg)
• Feeder conditioning needed to “flatten” voltage profile to maximize CVR benefits
• Addition of fixed and switched capacitor banks
• Feeder re-configuration
• Feeder phase balancing
• Reconductoring
• Replacement of electromechanical volt-VAR controllers with Intelligent Electronic Devices (IEDs)
• Addition of two way communication facilities
• Addition of end-of-line (EOL) metering
Distribution Voltage OptimizationMajor issue: What infrastructure improvements are needed to effectively implement CVR? Are these infrastructure improvements economically justified
![Page 11: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/11.jpg)
Distribution Voltage OptimizationMajor issue: How can AMI assist with effective deployment of CVR? What critical measurements are needed for effective CVR deployment?
• Need to determine critical voltage measurements for CVR
• Many utilities currently use AMI or bell weather meters for voltage feedback – i.e. where are the lowest voltage points at any given time?
– AMI appears to be an ideal source for providing voltage feedback• How many measurements are needed?
• What locations should be monitored?
• How often should measurements be taken?
• Do natural fluctuations in individual measurements affect usability of AMI data
![Page 12: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/12.jpg)
Distribution Voltage OptimizationWhere should industry go from here?
• Need ability to predict CVR benefits– Excellent work going on at PNNL, NEETRAC, EPRI and other
organizations to model CVR behavior– Work being coordinated through IEEE volt-VAR task force
• Must include distribution voltage optimization (CVR) in distribution planning process– Impact on capacity planning process– Design necessary infrastructure improvements
• Vendors and utilities alike need to gain practical experience with the concept (demonstrations and full-scale deployments)
![Page 13: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/13.jpg)
Dynamic Volt-VAR ControlMajor Trend: Growing need for dynamic voltage control due to variable output from renewable energy resources.
![Page 14: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/14.jpg)
Dynamic Volt-VAR ControlMajor Trend: Growing need for dynamic voltage control due to variable output from renewable energy resources.
![Page 15: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/15.jpg)
Dynamic Volt/Var Control
• Solar PV inverters typically operate at unity power factor
• Var control is possible in most applications
– Inverters have inherent ability to control vars
– No hardware change required
– Firmware upgrade only
• VA “Headroom”
– Data mining of over 40,000 PV installations in CA
– PV inverters typically sized greater than solar panel
– 20% margin or “headroom” available in inverters to provide var control
• Some form of communication is needed
– Vars could be controlled by utility via “broadcast” commands
Key issue: Need to deal with fluctuations associated with variable power output to prevent customer complaints, excess wear and tear on voltage regulators (LTCs), and other anomolies.
![Page 16: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/16.jpg)
Dynamic Volt/Var ControlKey issue: Need to deal with fluctuations associated with variable power output to prevent customer complaints, excess wear and tear on voltage regulators (LTCs), and other anomalies.
VA
Rs
Gen
erat
ed Capacitive
Inductive
System Voltage
V1 V2 V3V4
Q1
Q4
Q3Q2
Volt/VarMode 1 –Normal
Regulation
VA
Rs
Gen
erat
ed Capacitive
Inductive
System Voltage
V1V2
Q2
Q1
Volt/VarMode 2 –VAR
Support
Utility-Defined Curve Shapes
Simple Broadcast
![Page 17: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/17.jpg)
Dynamic Volt/Var ControlKey issue: Need to deal with fluctuations associated with variable power output to prevent customer complaints, excess wear and tear on voltage regulators (LTCs), and other anomalies.
12 kV Voltage
0.9
0.925
0.95
0.975
1
1.025
1.05
0 4 8 12 16 20
Hour
V (p
u)
Baseline – No PV
20% PV
20% PV w/ volt-var control
Feeder Medium Voltage Response
![Page 18: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/18.jpg)
Dynamic Volt/Var ControlKey issue: Restrictive Clause 4.1.1 in IEEE 1547-2003
“The Distributed Energy Resource (DR) shall not actively regulate the voltage at the Point of Common Connection (PCC). The DR shall not cause the Area Electric Power System (EPS) service voltage at other Local EPSs to go outside the requirements of ANSI C84.1-1995, Range A.”
addresses the possible impacts of the DR:– Impact of DR operations on voltage-regulating devices, which may
create either a too low, or a too high voltage.– Voltage imbalance due to single-phase DR– Intermittent operations of DR, which may result in unacceptable
voltage fluctuations and excessive operations of voltage-regulating devices in the Area EPS
– Improper regulation during reverse power flow conditions, which may result in either a too high, or a too low voltage
![Page 19: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/19.jpg)
Dynamic Volt-VAR ControlWhere should industry go from here?
• Continue IEEE 1547.8 WG activities to develop “Recommended Practice for Establishing Methods and Procedures that Provide Supplemental Support for Implementation Strategies For Expanded Use of IEEE Standard 1547”
• Enhance standard communication protocols (e.g., DNP3) to support broadcast commands to smart inverters.
• Add support for smart inverter controls to DMS suite of applications
![Page 20: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/20.jpg)
Fault Location Isolation & Service Restoration (FLISR)Major Trend: Many electrical utilities are implementing FLISR as a means of implementing a “self-healing” grid
Nature of the Problem
• When a permanent fault occurs, customers on “healthy” sections of the feeder may experience a lengthy outage
• FLISR provides the means to restore service to some customers before field crews arrive on the scene
FAULTOCCURS
CustomerReportsOutage
FieldCrews
On-Scene
Travel Time
FaultLocated
Fault Investigation& Patrol Time
POWER RESTOREDTO CUSTOMERS ON HEALTHY SECTIONS
OF FEEDERTime to Perform
Manual Switching Repair Time
FeederBack toNormal
5 – 10 minutes
15 – 30 minutes
15 – 20 minutes
10- 15 minutes
45 – 75 minutes
![Page 21: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/21.jpg)
Normal Configuration
![Page 22: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/22.jpg)
A Fault Occurs
![Page 23: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/23.jpg)
Flow of Fault Current TriggersFaulted Circuit Indicators (FCIs)
![Page 24: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/24.jpg)
…and trips again (lockout)
![Page 25: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/25.jpg)
FLISR identifies faulted section by comparing FCIs
![Page 26: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/26.jpg)
FLISR opens switches to isolatethe faulted feeder section
![Page 27: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/27.jpg)
FLISR Triggers Upstream Restoration
![Page 28: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/28.jpg)
Downstream restoration of blinking sectionCompare load with available capacity
![Page 29: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/29.jpg)
Downstream restoration of blinking sectionCompare load with available capacity
Pre-fault load = 1 MW
Available Capacity = 2 MW
![Page 30: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/30.jpg)
Capability exists, so…
Pre-fault load = 1 MW
Available Capacity = 2 MW
![Page 31: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/31.jpg)
FLISR closes switch to restore serviceVia alternate supply line
![Page 32: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/32.jpg)
Now FLISR checks for capacity to Transfer last downstream section
Pre-fault load = 2 MW
Available Capacity = 1.5 MW
![Page 33: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/33.jpg)
In this case capacity does not exist so downstream section is not restored
Pre-fault load = 2 MW
Available Capacity = 1.5 MW
Major Issue: Lack of capacity on backup supply circuits
![Page 34: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/34.jpg)
Pre-fault load = 2 MW
Available Capacity = 2.5 MW
Can offload red substation by transferring load to another substation, applying demand response, using CVR, discharging energy storage, reduce amount of fast charging, etc
FLISR: Key issues and challengesMajor Issue: Lack of capacity on backup supply circuits
![Page 35: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/35.jpg)
These actions free enough capacity to pick up last remaining section, so…
Pre-fault load = 2 MW
Available Capacity = 2.5 MW
Can offload red substation by transferring load to another substation, applying demand response, using CVR, discharging energy storage, reduce amount of fast charging, etc
![Page 36: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/36.jpg)
Can pick up the last downstream section
Can offload red substation by transferring load to another substation, applying demand response, using CVR, discharging energy storage, reduce amount of fast charging, etc
![Page 37: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/37.jpg)
Time Line Without and With FLISR
FaultOccurs
memberReportsOutage
FieldCrews
On-Scene
Travel Time
FaultLocated
Fault Investigation& Patrol Time
POWER RESTOREDON
HEALTHY SECTIONSOF FEEDER
Time to PerformManual Switching Repair Time
FeederBack toNormal
5 – 10 minutes
15 – 30 minutes
15 – 20 minutes
10 - 15 minutes
45 – 75 minutes
FAULTOCCURS
FeederBack toNormal
POWER RESTOREDON
HEALTHY SECTIONSOF FEEDER
Travel Time
15 – 30 minutes
1 - 4 Hours
Repair Time
1 - 4 Hours
1 to 5 minutes
5 - 10 minutes
PatrolTime
memberReportsOutage
5 – 10 minutes
Without FLISR
With FLISR
![Page 38: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/38.jpg)
FLISR with large distributed generation presentMajor Issue: Impact of high DG presence on FLISR Operation
![Page 39: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/39.jpg)
Same fault occurs
FLISR with large distributed generation presentMajor Issue: Impact of high DG presence on FLISR Operation
![Page 40: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/40.jpg)
Flow of Fault Current TriggersFaulted Circuit Indicators (FCIs)
![Page 41: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/41.jpg)
Circuit breaker opens
![Page 42: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/42.jpg)
FLISR analyzes FCIs – incorrectly identifies faulted segment
Need directional FCI or short circuit model to avoid this
situation
![Page 43: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/43.jpg)
Fault Location Isolation & Service RestorationWhere should industry go from here?
• Incorporate energy storage and possible microgrid in FLISR operation
• Develop planning & design criteria for effective FLISR implementation– Availability of backup sources with sufficient capacity
– Protection system that adapts to feeder reconfiguration
– Design necessary infrastructure improvements
![Page 44: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/44.jpg)
Optimal Network Reconfiguration
• Goal: Identify changes in feeder configuration that would improve overall distribution feeder performance and reliability– optimize topology for steady state
operations…
• Selectable Operating Objective– Minimal power and energy losses
– Maximum reliability
– Best load balance
– Best voltage profiles
– Weighted combination of the above
![Page 45: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/45.jpg)
Optimal Network Reconfiguration
• Goal: Identify changes in feeder configuration that would improve overall distribution feeder performance and reliability– optimize topology for steady state
operations…
• Selectable Operating Objective– Minimal power and energy losses
– Maximum reliability
– Best load balance
– Best voltage profiles
– Weighted combination of the above
Load Transfer Occurs
![Page 46: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/46.jpg)
Conclusions• Advanced distribution applications will play a growing role in managing
distribution system operation for improved efficiency, reliability, and performance
• Utilities must have the necessary skills to deal with these new systems:– Training/certification of operators– New procedures and business processes– Maintenance of hi tech systems– Growing engineering support in the DSO
• New planning tools and capabilities are needed for smart distribution systems– Account for advanced control capabilities, – Model impact of DER– Real and reactive power forecasting – Make sure software supplier vendors are in sync with the needs of planning engineers
• AMI will certainly play a key role in maximizing the benefits – improved accuracy and lower operating margins– Still some significant issues that need to be addressed such as data throughput and
security
![Page 47: SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN · PDF file• ANSI standards have some flexibility in the allowable delivery voltage • Distribution utilities ... the requirements](https://reader031.vdocuments.site/reader031/viewer/2022030418/5aa44e417f8b9a1d728bb2d8/html5/thumbnails/47.jpg)
Questions and Discussion
Bob Uluski
Electric Power Research Institute
102 Stevens Drive
Fort Washington, PA 19034
(215) 317-9105