smart airflow™ - purdue engineeringsmart airflow concept • ventilation – develop a low cost...

15
SMART AIRFLOW™ A ventilation airflow virtual sensor Jon Douglas Applied Research

Upload: others

Post on 24-Apr-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

SMART AIRFLOW™A ventilation airflow virtual sensor

Jon Douglas Applied Research

Page 2: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Outline

• Background– Ventilation rules as applied to RTUs– Setting ventilation rates with economizers

• Describe the Smart Airflow concept• Engineering behind it• Summarize benefits of virtual sensors

2

Page 3: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Factors Impacting Ventilation Rate 

• Damper position• Return duct design• Supply airflow rate 3

• Damper position• Return duct design• Supply airflow rate

Page 4: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Ventilation Background

• Building codes require ventilation in commercial buildings.• Amount required based on:

• Floor Area• Number of occupants

• Typically 10 – 30% of supply airflow

– Two common implementations– Fixed ventilation – Demand control ventilation

Page 5: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Controls Configuration for Ventilation

– Single speed fan– Min damper position

– Variable speed fan– Min damper position at low airflow– Min damper position at high airflow

– Demand control ventilation– Min damper position min CO2 & low airflow– Min damper position at max CO2 & high airflow

5

Page 6: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Setting Minimum Damper Positions

• Test and Balance Contractor– Iterative– Low velocity potentially inaccurate

15% OD air = 61 fpm = 0.7mph

• Guess– 15% open = 15% outdoor – Function of damper design– Very inaccurate

• Average error 46%• Max error 127%

6

0

100

200

300

400

500

600

700

800

900

1000

0 100 200 300 400 500 600 700

Actual Ven

tilation Ra

te (C

FM)

Desired Ventilation Rate (CFM)

Ventilation ERROR when Using Percent Open = Percent OD air

DESIGN A DESIGN B

Average Error +86 CFM

Average Error ‐71

Page 7: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Smart Airflow Concept

• Ventilation– Develop a low cost virtual ventilation airflow sensor– Installer to configure system based on ventilation airflow– Add economizer diagnostics

• Supply Airflow– Same features, but out of scope

7

Page 8: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Lab Setup

8

T

Airflow measurementplenum

Return Duct Supply Duct

Rooftop Unit

TransitionDuct

Page 9: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Development Methodology

9

Supply Airflow

Return Duct DP

Damper Position Ventilation Airflow Rate

Inlet filter DP

Wind

Barometric Relief

Wind

Outdoor Damper DP

Page 10: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Damper Calibration Curve

0% 5% 10% 15% 20% 25% 30% 35% 40% 45% 50%

Outdoor Damper Position  (% open)

IC29310

IC29307

IC29309 #2 Refit

IC29308 

Fit

Error Plus

Error Minus

air

ODVent

PCAQ

1096

Average Error 16%

Dam

per E

ffect

ive

Are

a (C

A)

Page 11: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Feedback Control Loop

• Control design challenges– Slow actuator:  30‐90 seconds between closed to open– Actuator resolution: Typically 1‐2%– Actuator life:  Move actuator every 10 minutes

11

Desired Ventilation

Controller

DamperCommand

Actual Position

Damper DP

VirtualSensorRTU

Measured Ventilation

Page 12: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Solid Control Design = Good Fault Detection

• Properly handle “Edge Conditions”– Bad inputs

• Out of range DP = Bad pressure sensor• No feedback signal = Bad cable or failed actuator

– Controller output at limit• 100% open = Over ventilation• 0% open = Under ventilation

• FMEA on system– Pressure sensor tube falls off.– Actuator disconnects from damper

12

Page 13: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Damper Diagnostic Using Differential Pressure

13

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Pressure Differen

ce (in h2

o)

Damper Position (% open)

Return Duct Restriction

DamperError

Pressure Too Low, Sensor Error

Page 14: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Benefits of Control with Virtual Sensors

• Customer– Interact with systems in engineering units.– Better performance– Natural diagnostics

• Company– Better understanding of products– Improved consistency of products

14

Page 15: SMART AIRFLOW™ - Purdue EngineeringSmart Airflow Concept • Ventilation – Develop a low cost virtual ventilation airflow sensor – Installer to configure system based on ventilation

Questions?

Jon DouglasApplied Research Lennox Industries

[email protected]

15