AIR CONDITIONER (MULTI TYPE) SERVICE MANUAL FILE No. A10-033 This service manual provides relevant explanations about new indoor unit (4 series). Please refer to the following service manuals for each indoor units. Indoor unit Indoor unit Model name: 4-way Cassette Type (MMU-AP∗∗∗2H) A08-004 2-way Cassette Type (2 series) (MMU-AP∗∗∗2WH) A10-007 Fresh Air Intake Indoor Unit Type (MMD-AP∗∗∗1HFE) A06-016 High-wall Type (2 series) (MMK-AP∗∗∗2H) SVM-05052-1 High-wall Type (3 series) (MMK-AP∗∗∗3H) SVM-09059 Other indoor units (1 series) A03-009, A03-010, A05-006, A05-007, A06-002 <1-way Cassette Type (YH, SH)> MMU-AP0074YH-E(-TR) MMU-AP0094YH-E(-TR) MMU-AP0124YH-E(-TR) MMU-AP0154SH-E(-TR) MMU-AP0184SH-E(-TR) MMU-AP0244SH-E(-TR) <Concealed Duct High Static Pressure Type> MMD-AP0184H-E(-TR) MMD-AP0244H-E(-TR) MMD-AP0274H-E(-TR) MMD-AP0364H-E(-TR) MMD-AP0484H-E(-TR) MMD-AP0724H-E(-TR) MMD-AP0964H-E(-TR) <Floor Standing Concealed Type> MML-AP0074BH-E(-TR) MML-AP0094BH-E(-TR) MML-AP0124BH-E(-TR) MML-AP0154BH-E(-TR) MML-AP0184BH-E(-TR) MML-AP0244BH-E(-TR) <Compact 4-way Cassette Type> MMU-AP0074MH-E(-TR) MMU-AP0094MH-E(-TR) MMU-AP0124MH-E(-TR) MMU-AP0154MH-E(-TR) MMU-AP0184MH-E(-TR) <Ceiling Type> MMC-AP0154H-E(-TR) MMC-AP0184H-E(-TR) MMC-AP0244H-E(-TR) MMC-AP0274H-E(-TR) MMC-AP0364H-E(-TR) MMC-AP0484H-E(-TR) <Floor Standing Cabinet Type> MML-AP0074H-E(-TR) MML-AP0094H-E(-TR) MML-AP0124H-E(-TR) MML-AP0154H-E(-TR) MML-AP0184H-E(-TR) MML-AP0244H-E(-TR) <Slim Duct Type> MMD-AP0074SPH-E(-TR) MMD-AP0094SPH-E(-TR) MMD-AP0124SPH-E(-TR) MMD-AP0154SPH-E(-TR) MMD-AP0184SPH-E(-TR) <Floor Standing Type> MMF-AP0154H-E(-TR) MMF-AP0184H-E(-TR) MMF-AP0244H-E(-TR) MMF-AP0274H-E(-TR) MMF-AP0364H-E(-TR) MMF-AP0484H-E(-TR) MMF-AP0564H-E(-TR) <Concealed Duct Standard Type> MMD-AP0074BH-E(-TR), MMD-AP0094BH-E(-TR), MMD-AP0124BH-E(-TR), MMD-AP0154BH-E(-TR) MMD-AP0184BH-E(-TR), MMD-AP0244BH-E(-TR), MMD-AP0274BH-E(-TR), MMD-AP0304BH-E(-TR) MMD-AP0364BH-E(-TR), MMD-AP0484BH-E(-TR), MMD-AP0564BH-E(-TR) PRINTED IN JAPAN, Apr, 2011, TDOC

Upload: cong-viet

Post on 28-Oct-2015

300 views

Category:

Documents


7 download

DESCRIPTION

Toshiba SMMS VRF Indoor units

TRANSCRIPT

Page 1: SM_4 Sereis VRF Indoor Units

Toshiba

AIR CONDITIONER (MULTI TYPE)

SERVICE MANUAL

FILE No. A10-033

This service manual provides relevant explanations about new indoor unit (4 series). Please refer to the following service manuals for each indoor units.

Indoor unit

Indoor unitModel name:4-way Cassette Type(MMU-AP∗∗∗2H)

A08-004

2-way Cassette Type (2 series)(MMU-AP∗∗∗2WH)

A10-007

Fresh Air Intake Indoor Unit Type(MMD-AP∗∗∗1HFE)

A06-016

High-wall Type (2 series)(MMK-AP∗∗∗2H)

SVM-05052-1

High-wall Type (3 series)(MMK-AP∗∗∗3H)

SVM-09059

Other indoor units (1 series) A03-009, A03-010, A05-006, A05-007, A06-002

<1-way Cassette Type (YH, SH)>MMU-AP0074YH-E(-TR)MMU-AP0094YH-E(-TR)MMU-AP0124YH-E(-TR)MMU-AP0154SH-E(-TR)MMU-AP0184SH-E(-TR)MMU-AP0244SH-E(-TR)

<Concealed Duct High Static Pressure Type>MMD-AP0184H-E(-TR)MMD-AP0244H-E(-TR)MMD-AP0274H-E(-TR)MMD-AP0364H-E(-TR)MMD-AP0484H-E(-TR)MMD-AP0724H-E(-TR)MMD-AP0964H-E(-TR)

<Floor Standing Concealed Type>MML-AP0074BH-E(-TR)MML-AP0094BH-E(-TR)MML-AP0124BH-E(-TR)MML-AP0154BH-E(-TR)MML-AP0184BH-E(-TR)MML-AP0244BH-E(-TR)

<Compact 4-way Cassette Type>MMU-AP0074MH-E(-TR)MMU-AP0094MH-E(-TR)MMU-AP0124MH-E(-TR)MMU-AP0154MH-E(-TR)MMU-AP0184MH-E(-TR)

<Ceiling Type>MMC-AP0154H-E(-TR)MMC-AP0184H-E(-TR)MMC-AP0244H-E(-TR)MMC-AP0274H-E(-TR)MMC-AP0364H-E(-TR)MMC-AP0484H-E(-TR)

<Floor Standing Cabinet Type>MML-AP0074H-E(-TR)MML-AP0094H-E(-TR)MML-AP0124H-E(-TR)MML-AP0154H-E(-TR)MML-AP0184H-E(-TR)MML-AP0244H-E(-TR)

<Slim Duct Type>MMD-AP0074SPH-E(-TR)MMD-AP0094SPH-E(-TR)MMD-AP0124SPH-E(-TR)MMD-AP0154SPH-E(-TR)MMD-AP0184SPH-E(-TR)

<Floor Standing Type>MMF-AP0154H-E(-TR)MMF-AP0184H-E(-TR)MMF-AP0244H-E(-TR)MMF-AP0274H-E(-TR)MMF-AP0364H-E(-TR)MMF-AP0484H-E(-TR)MMF-AP0564H-E(-TR)

<Concealed Duct Standard Type>MMD-AP0074BH-E(-TR), MMD-AP0094BH-E(-TR), MMD-AP0124BH-E(-TR), MMD-AP0154BH-E(-TR)MMD-AP0184BH-E(-TR), MMD-AP0244BH-E(-TR), MMD-AP0274BH-E(-TR), MMD-AP0304BH-E(-TR)MMD-AP0364BH-E(-TR), MMD-AP0484BH-E(-TR), MMD-AP0564BH-E(-TR)

PRINTED IN JAPAN, Apr, 2011, TDOC

+00A10-033_01EN.book Page 1 Tuesday, June 21, 2011 10:41 AM

Page 2: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 1 Tuesday, June 21, 2011 10:41 AM

ContentsPrecautions for Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

1 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141-1. Compact 4-way cassette type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

1-2. 1-way cassette type (compact type YH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

1-3. 1-way cassette type (SH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

1-4. Concealed duct standard type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

1-5. Concealed duct high static pressure type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

1-6. Slim duct type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

1-7. Ceiling type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

1-8. Floor standing cabinet type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

1-9. Floor standing concealed type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

1-10. Floor standing type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

2 Parts Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252-1. Indoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

3 Refrigerant Cycle Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

4 Control Outline. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

5 Applied Control and Functions (Including Circuit Configuration) . . . . . . . . . . . . . 375-1. Indoor controller block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

5-1-1. When main (sub) remote controller connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

5-1-2. When wireless remote controller kit connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

5-1-3. When both main (sub) remote controller and wireless remote controller kit connected. 41

5-2. Indoor printed circuit board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

5-3. Optional connector specifications of indoor P.C. board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

5-4. Test operation of indoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

5-5. Method to set indoor unit function DN code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

5-6. Applied control of indoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

6 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 676-1. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

6-2. Troubleshooting method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

6-3. Troubleshooting based on information displayed on remote controller . . . . . . . . . . . . . . . . . . . . 74

6-4. Check codes displayed on remote controller and SMMS outdoor unit (7-segment display on I/F board) and locations to be checked. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

6-5. Sensor characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

1

Toshiba

Page 3: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 2 Tuesday, June 21, 2011 10:41 AM

7 P.C. Board Exchange Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 987-1. Replacement of indoor P.C. boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

8 Detachments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1058-1. 1-way cassette (SH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105

8-2. Compact 4-way cassette . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

8-3. Slim duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124

8-4. Concealed duct standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129

8-5. Concealed duct high static pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132

8-6. Ceiling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133

8-7. Floor standing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141

8-8. Floor standing cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144

9 Exploded Diagram / Service Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1479-1. 1-way cassette type (YH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147

9-2. 1-Way cassette type (SH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152

9-3. Compact 4-way cassette type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156

9-4. Slim duct type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160

9-5. Concealed duct standard type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164

9-6. Concealed duct high static pressure type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178

9-7. Ceiling type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186

9-8. Floor standing type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193

9-9. Floor standing concealed type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202

9-10. Floor standing cabinet type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208

2

Toshiba

Page 4: SM_4 Sereis VRF Indoor Units

Original instruction

+00A10-033_01EN.book Page 3 Tuesday, June 21, 2011 10:41 AM

Please read carefully through these instructions that contain important information which complies with the “Machinery” Directive (Directive 2006/42/EC), and ensure that you understand them.

Generic Denomination: Air Conditioner

Definition of Qualified Installer or Qualified Service PersonThe air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you.A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below.

Agent Qualifications and knowledge which the agent must have

Qualified installer

• The qualified installer is a person who installs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.

• The qualified installer who is allowed to do the electrical work involved in installation, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.

• The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.

• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.

Qualified service person

• The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.

• The qualified service person who is allowed to do the electrical work involved in installation, repair, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.

• The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation, repair, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.

• The qualified service person who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.

3

Toshiba

Page 5: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 4 Tuesday, June 21, 2011 10:41 AM

Definition of Protective Gear When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing.In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.

The important contents concerned to the safety are described on the product itself and on this Service Manual.Please read this Service Manual after understanding the described items thoroughly in the following contents(Indications / Illustrated marks), and keep them.

[Explanation of indications]

* Property damage: Enlarged damage concerned to property, furniture, and domestic animal / pet

[Explanation of illustrated marks]

Work undertaken Protective gear worn

All types of work Protective gloves ‘Safety’ working clothing

Electrical-related workGloves to provide protection for electricians and from heat Insulating shoes Clothing to provide protection from electric shock

Work done at heights(50 cm or more) Helmets for use in industry

Transportation of heavy objects Shoes with additional protective toe cap

Repair of outdoor unit Gloves to provide protection for electricians and from heat

Indication Explanation

DANGER Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.

WARNINGIndicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.

CAUTIONIndicates contents assumed that an injury or property damage (*) may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.

Mark Explanation

Indicates prohibited items (Forbidden items to do)The sentences near an illustrated mark describe the concrete prohibited contents.

Indicates mandatory items (Compulsory items to do)The sentences near an illustrated mark describe the concrete mandatory contents.

Indicates cautions (Including danger / warning)The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.

4

Toshiba

Page 6: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 5 Tuesday, June 21, 2011 10:41 AM

Warning Indications on the Air Conditioner Unit[Confirmation of warning label on the main unit]Confirm that labels are indicated on the specified positionsIf removing the label during parts replace, stick it as the original.

Warning indication Description

WARNING

ELECTRICAL SHOCK HAZARDDisconnect all remote electric power supplies before servicing.

WARNING

Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.

CAUTION

High temperature parts. You might get burned when removing this panel.

CAUTION

Do not touch the aluminium fins of the unit. Doing so may result in injury.

CAUTION

BURST HAZARDOpen the service valves before the operation, otherwise there might be the burst.

CAUTION

Do not climb onto the fan guard.Doing so may result in injury.

5

Toshiba

Page 7: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 6 Tuesday, June 21, 2011 10:41 AM

Precautions for SafetyThe manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.

DANGER

Turn off breaker.

Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker for both the indoor and outdoor units to the OFF position. Otherwise, electric shocks may result.

Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the OFF position.Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts.Only a qualified installer (*1) or qualified service person (*1) is allowed to remove the intake grille of the indoor unit or service panel of the outdoor unit and do the work required.

Before starting to repair the outdoor unit fan or fan guard, be absolutely sure to set the circuit breaker to the OFF position, and place a “Work in progress” sign on the circuit breaker.

When cleaning the filter or other parts of the indoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.

When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning, abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure.

Electric shock hazard

When you access inside of the service panel to repair electric parts, wait for about five minutes after turning off the breaker. Do not start repairing immediately.Otherwise you may get electric shock by touching terminals of high-voltage capacitors. Natural discharge of the capacitor takes about five minutes.

Prohibition

Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out.There is a danger of electric shocks if the circuit breaker is set to ON by mistake.

Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an electric shock if the power is turned on without first conducting these checks.

Stay on protection

If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical parts box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, wear insulated heat-resistant gloves, insulated boots and insulated work overalls, and take care to avoid touching any live parts.You may receive an electric shock if you fail to heed this warning. Only qualified service person (*1) is allowed to do this kind of work.

6

Toshiba

Page 8: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 7 Tuesday, June 21, 2011 10:41 AM

WARNING

General

Before starting to repair the air conditioner, read carefully through the Service Manual, and repair the air conditioner by following its instructions.

Only qualified service person (*1) is allowed to repair the air conditioner.Repair of the air conditioner by unqualified person may give rise to a fire, electric shocks, injury, water leaks and / or other problems.

Do not use any refrigerant different from the one specified for complement or replacement.Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.

Only a qualified installer (*1) or qualified service person (*1) is allowed to carry out the electrical work of the air conditioner.Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and / or electrical leaks.

When transporting the air conditioner, wear shoes with protective toe caps, protective gloves and other protective clothing.

When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks.Failure to wear this protective gear may result in electric shocks.

Electrical wiring work shall be conducted according to law and regulation in the community and installation manual. Failure to do so may result in electrocution or short circuit.

Only a qualified installer (*1) or qualified service person (*1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.

When working at heights, use a ladder which complies with the ISO 14122 standard, and follow the procedure in the ladder’s instructions.Also wear a helmet for use in industry as protective gear to undertake the work.

When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work.Parts and other objects may fall from above, possibly injuring a person below.

When executing address setting, test run, or troubleshooting through the checking window on the electric parts box, put on insulated gloves to provide protection from electric shock. Otherwise you may receive an electric shock.

Do not touch the aluminum fin of the outdoor unit.You may injure yourself if you do so. If the fin must be touched for some reason, first put on protective gloves and safety work clothing, and then proceed.

Do not climb onto or place objects on top of the outdoor unit.You may fall or the objects may fall off of the outdoor unit and result in injury.

When transporting the air conditioner, wear shoes with additional protective toe caps.

When transporting the air conditioner, do not take hold of the bands around the packing carton.You may injure yourself if the bands should break.

Be sure that a heavy unit (10 kg or heavier) such as a compressor is carried by two persons.

This air conditioner has passed the pressure test as specified in IEC 60335-2-40 Annex EE.

Check earth wires.

Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs.If the earth wire is not correctly connected, contact an electric engineer for rework.

After completing the repair or relocation work, check that the ground wires are connected properly.

Be sure to connect earth wire. (Grounding work) Incomplete grounding causes an electric shock.Do not connect ground wires to gas pipes, water pipes, and lightning rods or ground wires for telephone wires.

Prohibition of modification.

Do not modify the products.Do not also disassemble or modify the parts.It may cause a fire, electric shock or injury.

Use specified parts.

When any of the electrical parts are to be replaced, ensure that the replacement parts satisfy the specifications given in the Service Manual (or use the parts contained on the parts list in the Service Manual).Use of any parts which do not satisfy the required specifications may give rise to electric shocks, smoking and / or a fire.

7

Toshiba

Page 9: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 8 Tuesday, June 21, 2011 10:41 AM

Do not bring a child close to

the equipment.

If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical parts box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, put a sign in place so that no-one will approach the work location before proceeding with the work. Third-party individuals may enter the work site and receive electric shocks if this warning is not heeded.

Insulating measures

Connect the cut-off lead wires with crimp contact, etc., put the closed end side upward and then apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.

No fire

When performing repairs using a gas burner, replace the refrigerant with nitrogen gas because the oil that coats the pipes may otherwise burn.When repairing the refrigerating cycle, take the following measures.1) Be attentive to fire around the cycle. When using a gas stove, etc., be sure to put out fire before work;

otherwise the oil mixed with refrigerant gas may catch fire.2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may

be caused.3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the

inflammables.

Refrigerant

The refrigerant used by this air conditioner is the R410A.

Check the used refrigerant name and use tools and materials of the parts which match with it.For the products which use R410A refrigerant, the refrigerant name is indicated at a position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the service port is changed from one of the former R22.

For an air conditioner which uses R410A, never use other refrigerant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused.

When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air completely may cause the air conditioner to malfunction.

Do not charge refrigerant additionally. If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant.In this time, never charge the refrigerant over the specified amount.

When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R410A into the specified refrigerant. If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.

After installation work, check the refrigerant gas does not leak. If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.

Never recover the refrigerant into the outdoor unit. When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device.The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.

Assembly / Wiring

After repair work, surely assemble the disassembled parts, and connect and lead the removed wires as before.Perform the work so that the cabinet or panel does not catch the inner wires.If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is caused at user’s side.

Insulator check

After the work has finished, be sure to use an insulation tester set (500 V Megger) to check the resistance is 1 MΩ or more between the charge section and the non-charge metal section (Earth position).If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.

Ventilation

When the refrigerant gas leaks during work, execute ventilation.If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation.

8

Toshiba

Page 10: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 9 Tuesday, June 21, 2011 10:41 AM

Compulsion

When the refrigerant gas leaks, find up the leaked position and repair it surely.If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room.The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks.If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.

Tighten the flare nut with a torque wrench in the specified manner.Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.

Nitrogen gas must be used for the airtight test.

The charge hose must be connected in such a way that it is not slack.

For the installation / moving / reinstallation work, follow to the Installation Manual.If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused.

Check after repair

Once the repair work has been completed, check for refrigerant leaks, and check the insulation resistance and water drainage.Then perform a trial run to check that the air conditioner is running properly.

After repair work has finished, check there is no trouble. If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.

After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound.If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet.

Be sure to fix the screws back which have been removed for installation or other purposes.

Do not operate the unit with the valve closed.

Check the following matters before a test run after repairing piping.• Connect the pipes surely and there is no leak of refrigerant.• The valve is opened.Running the compressor under condition that the valve closes causes an abnormal high pressure resulted in damage of the parts of the compressor and etc. and moreover if there is leak of refrigerant at connecting section of pipes, the air is sucked and causes further abnormal high pressure resulted in burst or injury.

Check after reinstallation

Only a qualified installer (*1) or qualified service person (*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and / or vibration may result.

Check the following items after reinstallation.1) The earth wire is correctly connected.2) The power cord is not caught in the product.3) There is no inclination or unsteadiness and the installation is stable.If check is not executed, a fire, an electric shock or an injury is caused.

When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe.Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.

Cooling check

When the service panel of the outdoor unit is to be opened in order for the compressor or the area around this part to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel.If you fail to heed this warning, you will run the risk of burning yourself because the compressor pipes and other parts will be very hot to the touch. In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.

Take care not to get burned by compressor pipes or other parts when checking the cooling cycle while running the unit as they get heated while running. Be sure to put on gloves providing protection for electric shock and heat.

When the service panel of the outdoor unit is to be opened in order for the fan motor, reactor, inverter or the areas around these parts to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel.If you fail to heed this warning, you will run the risk of burning yourself because the fan motor, reactor, inverter heat sink and other parts will be very hot to the touch.In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.

9

Toshiba

Page 11: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 10 Tuesday, June 21, 2011 10:41 AM

Explanations given to userIf you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person to have the repairs done.Do not set the circuit breaker to the ON position until the repairs are completed.

Relocation• Only a qualified installer (*1) or qualified service person (*1) is allowed to relocate the air conditioner.

It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and / or vibration may result.

• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe.Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.

(*1) Refer to the “Definition of Qualified Installer or Qualified Service Person”

Installation

Only a qualified installer (*1) or qualified service person (*1) is allowed to install the air conditioner. If the air conditioner is installed by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and / or vibration may result.

Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner.

Be sure to use the company-specified products for the separately purchased parts. Use of non-specified products may result in fire, electric shock, water leakage or other failure. Have the installation performed by a qualified installer.

Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit. Capacity overflow may occur on the terminal block and may result in fire.

Do not install the air conditioner in a location that may be subject to a risk of expire to a combustible gas.If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.

Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.

Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws.

Install the circuit breaker where it can be easily accessed by the qualified service person (*1).

If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.

Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.

10

Toshiba

Page 12: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 11 Tuesday, June 21, 2011 10:41 AM

Declaration of Conformity

NOTEThis declaration becomes invalid if technical or operational modifications are introduced without the manufacturer’s consent.

Manufacturer: Toshiba Carrier Corporation336 Tadehara, Fuji-shi, Shizuoka-ken 416-8521 JAPAN

Authorized Representative / TCF holder:

Nick BallToshiba EMEA Engineering DirectorToshiba Carrier UK Ltd.Porsham Close, Belliver Industrial Estate, PLYMOUTH, Devon, PL6 7DB. United Kingdom

Hereby declares that the machinery described below:

Generic Denomination: Air Conditioner

Model / type: Indoor unit<1-way Cassette Type (YH, SH)>MMU-AP0074YH-E(TR), MMU-AP0094YH-E(TR), MMU-AP0124YH-E(TR), MMU-AP0154SH-E(TR), MMU-AP0184SH-E(TR), MMU-AP0244SH-E(TR)

<Compact 4-way Cassette Type>MMU-AP0074MH-E(TR), MMU-AP0094MH-E(TR), MMU-AP0124MH-E(TR), MMU-AP0154MH-E(TR), MMU-AP0184MH-E(TR)

<Slim Duct Type>MMD-AP0074SPH-E(TR), MMD-AP0094SPH-E(TR), MMD-AP0124SPH-E(TR), MMD-AP0154SPH-E(TR), MMD-AP0184SPH-E(TR)

<Concealed Duct Standard Type>MMD-AP0074BH-E(TR), MMD-AP0094BH-E(TR), MMD-AP0124BH-E(TR), MMD-AP0154BH-E(TR), MMD-AP0184BH-E(TR), MMD-AP0244BH-E(TR), MMD-AP0274BH-E(TR), MMD-AP0304BH-E(TR), MMD-AP0364BH-E(TR), MMD-AP0484BH-E(TR), MMD-AP0564BH-E(TR)

<Concealed Duct High Static Pressure Type>MMD-AP0184H-E(TR), MMD-AP0244H-E(TR), MMD-AP0274H-E(TR), MMD-AP0364H-E(TR), MMD-AP0484H-E(TR), MMD-AP0724H-E(TR), MMD-AP0964H-E(TR)

<Ceiling Type>MMC-AP0154H-E(TR), MMC-AP0184H-E(TR), MMC-AP0244H-E(TR), MMC-AP0274H-E(TR), MMC-AP0364H-E(TR), MMC-AP0484H-E(TR)

<Floor Standing Type>MMF-AP0154H-E(TR), MMF-AP0184H-E(TR), MMF-AP0244H-E(TR), MMF-AP0274H-E(TR), MMF-AP0364H-E(TR), MMF-AP0484H-E(TR), MMF-AP0564H-E(TR)

<Floor Standing Concealed Type>MML-AP0074BH-E(TR), MML-AP0094BH-E(TR), MML-AP0124BH-E(TR), MML-AP0154BH-E(TR), MML-AP0184BH-E(TR), MML-AP0244BH-E(TR)

<Floor Standing Cabinet Type>MML-AP0074H-E(TR), MML-AP0094H-E(TR), MML-AP0124H-E(TR), MML-AP0154H-E(TR), MML-AP0184H-E(TR), MML-AP0244H-E(TR)

Commercial name: Super Modular Multi System Air ConditionerSuper Heat Recovery Multi System Air ConditionerMiNi-Super Modular Multi System Air Conditioner (MiNi-SMMS series)

Complies with the provisions of the “Machinery” Directive (Directive 2006/42/EC) and the regulations transposing into national law

Complies with the provisions of the following harmonized standard:

EN 378-2: 2008+A1:2009

11

Toshiba

Page 13: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 12 Tuesday, June 21, 2011 10:41 AM

SpecificationsModel Sound power level (dBA) Weight (kg)

Cooling Heating Main unit (Ceiling panel)MMU-AP0074MH-E * * 17 (3)MMU-AP0094MH-E * * 17 (3)MMU-AP0124MH-E * * 17 (3)MMU-AP0154MH-E * * 17 (3)MMU-AP0184MH-E * * 17 (3)MMU-AP0074YH-E * * 22 (3.5)MMU-AP0094YH-E * * 22 (3.5)MMU-AP0124YH-E * * 22 (3.5)MMU-AP0154SH-E * * 21 (5.5)MMU-AP0184SH-E * * 21 (5.5)MMU-AP0244SH-E * * 22 (5.5)MMD-AP0074BH-E * * 28MMD-AP0094BH-E * * 28MMD-AP0124BH-E * * 28MMD-AP0154BH-E * * 32MMD-AP0184BH-E * * 32MMD-AP0244BH-E * * 43MMD-AP0274BH-E * * 43MMD-AP0304BH-E * * 43MMD-AP0364BH-E * * 55MMD-AP0484BH-E * * 55MMD-AP0564BH-E * * 55MMD-AP0184H-E * * 50MMD-AP0244H-E * * 52MMD-AP0274H-E * * 52MMD-AP0364H-E * * 56MMD-AP0484H-E * * 67MMD-AP0724H-E * * 160MMD-AP0964H-E 70 70 160MMD-AP0074SPH-E * * 22MMD-AP0094SPH-E * * 22MMD-AP0124SPH-E * * 22MMD-AP0154SPH-E * * 23MMD-AP0184SPH-E * * 23MMC-AP0154H-E * * 22MMC-AP0184H-E * * 22MMC-AP0244H-E * * 26MMC-AP0274H-E * * 26MMC-AP0364H-E * * 34MMC-AP0484H-E * * 34MML-AP0074H-E * * 37MML-AP0094H-E * * 37MML-AP0124H-E * * 37MML-AP0154H-E * * 37MML-AP0184H-E * * 40MML-AP0244H-E * * 40MML-AP0074BH-E * * 21MML-AP0094BH-E * * 21MML-AP0124BH-E * * 21MML-AP0154BH-E * * 29MML-AP0184BH-E * * 29MML-AP0244BH-E * * 29MMF-AP0154H-E * * 48MMF-AP0184H-E * * 48MMF-AP0244H-E * * 49MMF-AP0274H-E * * 49MMF-AP0364H-E * * 65MMF-AP0484H-E 72 72 65MMF-AP0564H-E 72 72 65

12

Toshiba

Page 14: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 13 Tuesday, June 21, 2011 10:41 AM

Model Sound power level (dBA) Weight (kg)

Cooling Heating Main unit (Ceiling panel)MMU-AP0074MH-TR * * 17 (3)MMU-AP0094MH-TR * * 17 (3)MMU-AP0124MH-TR * * 17 (3)MMU-AP0154MH-TR * * 17 (3)MMU-AP0184MH-TR * * 17 (3)MMU-AP0074YH-TR * * 22 (3.5)MMU-AP0094YH-TR * * 22 (3.5)MMU-AP0124YH-TR * * 22 (3.5)MMU-AP0154SH-TR * * 21 (5.5)MMU-AP0184SH-TR * * 21 (5.5)MMU-AP0244SH-TR * * 22 (5.5)MMD-AP0074BH-TR * * 28MMD-AP0094BH-TR * * 28MMD-AP0124BH-TR * * 28MMD-AP0154BH-TR * * 32MMD-AP0184BH-TR * * 32MMD-AP0244BH-TR * * 43MMD-AP0274BH-TR * * 43MMD-AP0304BH-TR * * 43MMD-AP0364BH-TR * * 55MMD-AP0484BH-TR * * 55MMD-AP0564BH-TR * * 55MMD-AP0184H-TR * * 50MMD-AP0244H-TR * * 52MMD-AP0274H-TR * * 52MMD-AP0364H-TR * * 56MMD-AP0484H-TR * * 67MMD-AP0724H-TR * * 160MMD-AP0964H-TR 70 70 160MMD-AP0074SPH-TR * * 22MMD-AP0094SPH-TR * * 22MMD-AP0124SPH-TR * * 22MMD-AP0154SPH-TR * * 23MMD-AP0184SPH-TR * * 23MMC-AP0154H-TR * * 22MMC-AP0184H-TR * * 22MMC-AP0244H-TR * * 26MMC-AP0274H-TR * * 26MMC-AP0364H-TR * * 34MMC-AP0484H-TR * * 34MML-AP0074H-TR * * 37MML-AP0094H-TR * * 37MML-AP0124H-TR * * 37MML-AP0154H-TR * * 37MML-AP0184H-TR * * 40MML-AP0244H-TR * * 40MML-AP0074BH-TR * * 21MML-AP0094BH-TR * * 21MML-AP0124BH-TR * * 21MML-AP0154BH-TR * * 29MML-AP0184BH-TR * * 29MML-AP0244BH-TR * * 29MMF-AP0154H-TR * * 48MMF-AP0184H-TR * * 48MMF-AP0244H-TR * * 49MMF-AP0274H-TR * * 49MMF-AP0364H-TR * * 65MMF-AP0484H-TR 72 72 65MMF-AP0564H-TR 72 72 65

13

Toshiba

Page 15: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 14 Tuesday, June 21, 2011 10:41 AM

1 Wiring Diagrams1-1. Compact 4-way cassette typeModels: MMU-AP0074MH-E(TR), AP0094MH-E(TR), AP0124MH-E(TR), AP0154MH-E(TR), AP0184MH-E(TR)

Indo

or u

nit

Ear

th s

crew

Pow

er s

uppl

y1~

50H

z 22

0-24

0V1~

60H

z 22

0V

Flow

sel

ecto

r uni

t Ea

rth s

crew

(Hig

h ce

iling

resh

uffli

ng)

Con

trol P

.C. B

oard

fo

r Ind

oor U

nit

1.Br

oken

line

indi

cate

the

wiri

ng a

t site

.Lo

ng d

ashe

d sh

ort d

ashe

d lin

e in

dica

te th

e ac

cess

orie

s.2.

indi

cate

s th

e te

rmin

al b

lock

. in

dica

tes

the

conn

ectio

n te

rmin

al.

indi

cate

s th

e co

nnec

tor o

n th

e co

ntro

l P.C

. boa

rd.

3. in

dica

tes

the

prot

ectio

n gr

ound

.4.

indi

cate

s th

e co

ntro

l P.C

. boa

rd.

RE

D :

RE

DW

HI :

WH

ITE

YE

L : Y

ELL

OW

BLU

: B

LUE

BLK

: B

LAC

KG

RY

: G

RA

YP

NK

: PI

NK

OR

N :

OR

AN

GE

BR

W :

BR

OW

NG

RN

: G

RE

EN

Sym

bol

Parts

Nam

eC

N**

Con

nect

orD

MD

rain

Pum

p M

otor

F301

,302

Fuse

FMFa

n M

otor

FSFl

oat S

witc

hLM

1,2

Louv

er M

otor

PMV

Pul

se M

otor

Val

veR

Y30

2D

rain

Con

trol R

elay

TAIn

door

tem

p se

nsor

TB01

,02

Term

inal

Blo

ckTC

1,2,

TCJ

Tem

p se

nsor

Wire

d R

emot

e C

ontro

ller

Ada

pter

for

Wire

less

R

emot

e C

ontro

ller

Out

door

uni

t

Pow

er

supp

ly

circ

uit

CO

LOR

ID

EN

TIFI

CA

TIO

N

14

Toshiba

Page 16: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 15 Tuesday, June 21, 2011 10:41 AM

1-2. 1-way cassette type (compact type YH)Models: MMU-AP0074YH-E(TR), AP0094YH-E(TR), AP0124YH-E(TR)

Pow

er s

uppl

y1~

50H

z 22

0-24

0V1~

60H

z 22

0V

Flow

sel

ecto

r uni

t E

arth

scr

ew

Con

trol P

.C. B

oard

fo

r Ind

oor U

nit

1.Br

oken

line

indi

cate

the

wiri

ng a

t site

.Lo

ng d

ashe

d sh

ort d

ashe

d lin

e in

dica

te th

e ac

cess

orie

s.2.

indi

cate

s th

e te

rmin

al b

lock

. in

dica

tes

the

conn

ectio

n te

rmin

al.

indi

cate

s th

e co

nnec

tor o

n th

e co

ntro

l P.C

. boa

rd.

3. in

dica

tes

the

prot

ectio

n gr

ound

.4.

indi

cate

s th

e co

ntro

l P.C

. boa

rd.

RED

: R

EDW

HI :

WH

ITE

YEL

: YEL

LOW

BLU

: B

LUE

BLK

: B

LAC

KG

RY

: G

RA

YPN

K :

PIN

KO

RN

: O

RA

NG

EBR

W :

BR

OW

NG

RN

: G

RE

EN

Rem

ote

Con

trolle

r

Sub

P.C

. Boa

rd

Out

door

uni

t

Pow

er

supp

ly

circ

uit

CO

LOR

ID

EN

TIFI

CA

TIO

N

Sym

bol

Par

ts N

ame

CN

**C

onne

ctor

DM

Dra

in P

ump

Mot

orF3

01,3

02Fu

seFM

Fan

Mot

orFS

Floa

t Sw

itch

LMLo

uver

Mot

orPM

VP

ulse

Mot

or V

alve

RY

001

Louv

er C

ontro

l Rel

ayR

Y00

2D

rain

Con

trol R

elay

RY00

5,006

,007

Fan

Mot

or C

ontro

l Rela

yTA

Indo

or te

mp

sens

orTB

01,0

2Te

rmin

al B

lock

TC,T

CJ

Tem

p se

nsor

TRTr

ansf

orm

er

Indo

or u

nit

Ear

th s

crew

Line

Filt

er

15

Toshiba

Page 17: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 16 Tuesday, June 21, 2011 10:41 AM

1-3. 1-way cassette type (SH)Models: MMU-AP0154SH-E(TR), AP0184SH-E(TR), AP0244SH-E(TR)

Pow

er s

uppl

y1~

50H

z 22

0-24

0V1~

60H

z 22

0V

Flow

sel

ecto

r uni

t Ea

rth s

crew

Con

trol P

.C. B

oard

fo

r Ind

oor U

nit

1.Br

oken

line

indi

cate

the

wiri

ng a

t site

.Lo

ng d

ashe

d sh

ort d

ashe

d lin

e in

dica

te th

e ac

cess

orie

s.2.

indi

cate

s th

e te

rmin

al b

lock

. in

dica

tes

the

conn

ectio

n te

rmin

al.

indi

cate

s th

e co

nnec

tor o

n th

e co

ntro

l P.C

. boa

rd.

3. in

dica

tes

the

prot

ectio

n gr

ound

.4.

indi

cate

s th

e co

ntro

l P.C

. boa

rd.

RE

D :

RE

DW

HI :

WH

ITE

YEL

: Y

ELL

OW

BLU

: BL

UE

BLK

: B

LAC

KG

RY

: GR

AY

PN

K : P

INK

OR

N :

OR

ANG

EB

RW

: B

RO

WN

GR

N :

GR

EEN

Out

door

uni

t

Pow

er

supp

ly

circ

uit

CO

LOR

ID

EN

TIFI

CA

TIO

N

Sym

bol

Parts

Nam

eC

N**

Con

nect

orD

MD

rain

Pum

p M

otor

F301

,302

Fuse

FMFa

n M

otor

FSFl

oat S

witc

hLM

Louv

er M

otor

PM

VPu

lse

Mot

or V

alve

RY

302

Dra

in C

ontro

l Rel

ayTA

Indo

or te

mp

sens

orTB

01,0

2Te

rmin

al B

lock

TC1,

2,TC

JTe

mp

sens

or

Indo

or u

nit

Earth

scr

ew

Wire

d R

emot

e C

ontro

ller

Ada

pter

for

Wire

less

Rem

ote

Con

trolle

r

(Hig

h ce

iling

re

shuf

fling

)

16

Toshiba

Page 18: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 17 Tuesday, June 21, 2011 10:41 AM

1-4. Concealed duct standard typeModels: MMD-AP0074BH-E(TR), AP0094BH-E(TR), AP0124BH-E(TR), AP0154BH-E(TR), AP0184BH-E(TR), AP0244BH-E(TR), AP0274BH-E(TR), AP0304BH-E(TR), AP0364BH-E(TR), AP0484BH-E(TR), AP0564BH-E(TR)

Pow

er s

uppl

y1~

50H

z 22

0-24

0V1~

60H

z 22

0V

Flow

sel

ecto

r uni

t E

arth

scr

ewC

ontro

l P.C

. Boa

rd

for I

ndoo

r Uni

t

1.Br

oken

line

indi

cate

the

wiri

ng a

t site

.Lo

ng d

ashe

d sh

ort d

ashe

d lin

e in

dica

te th

e ac

cess

orie

s.2.

indi

cate

s th

e te

rmin

al b

lock

. in

dica

tes

the

conn

ectio

n te

rmin

al.

indi

cate

s th

e co

nnec

tor o

n th

e co

ntro

l P.C

. boa

rd.

3. in

dica

tes

the

prot

ectio

n gr

ound

.4.

indi

cate

s th

e co

ntro

l P.C

. boa

rd.

RED

: R

EDW

HI :

WH

ITE

YEL

: YEL

LOW

BLU

: B

LUE

BLK

: B

LAC

KG

RY

: G

RA

YPN

K :

PIN

KO

RN

: O

RA

NG

EBR

W :

BR

OW

NG

RN

: G

RE

EN

Out

door

uni

t

Pow

er

supp

ly

circ

uit

CO

LOR

ID

EN

TIFI

CA

TIO

N

Sym

bol

Par

ts N

ame

CN

**C

onne

ctor

DM

Dra

in P

ump

Mot

orF3

01,3

02Fu

seFM

Fan

Mot

orFS

Floa

t Sw

itch

PMV

Pul

se M

otor

Val

veR

Y30

2D

rain

Con

trol R

elay

TAIn

door

tem

p se

nsor

TB01

,02

Term

inal

Blo

ckTC

1,2,

TCJ

Tem

p se

nsor

Indo

or u

nit

Ear

th s

crew

Wire

d R

emot

e C

ontro

ller

Adap

ter f

or

Wire

less

Rem

ote

Con

trolle

r

Rea

ctor

(Hig

h ce

iling

re

shuf

fling

)

17

Toshiba

Page 19: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 18 Tuesday, June 21, 2011 10:41 AM

1-5. Concealed duct high static pressure typeModels: MMD-AP0184H-E(TR), AP0244H-E(TR), AP0274H-E(TR), AP0364H-E(TR), AP0484H-E(TR)

Pow

er s

uppl

y1~

50H

z 22

0-24

0V1~

60H

z 22

0VLine

Filt

er

Con

trol P

.C. B

oard

fo

r Ind

oor U

nit

RE

D :

RE

DW

HI :

WH

ITE

YEL

: Y

ELLO

WB

LU :

BLU

EB

LK :

BLA

CK

GR

Y : G

RA

YP

NK

: PIN

KO

RN

: O

RA

NG

EB

RW

: BR

OW

NG

RN

: G

RE

EN

Out

door

un

it

Pow

er

supp

ly

circ

uit

CO

LOR

ID

EN

TIFI

CA

TIO

N

Indo

or u

nit

Ear

th s

crew

Rem

ote

Con

trolle

r

(Ref

er th

a st

atic

pre

ssur

e sp

ecifi

catio

ns fo

r eac

h ta

p.)

Term

inal

N

o.Fa

n m

otor

wiri

ng(M

MD

-)S

tatic

pr

essu

re ta

pAP

0484

AP

0184

~AP

0364

F1B

LU(5

0/60

Hz)

Low

tap

F2O

RN

(50/

60H

z)M

iddl

e ta

pF3

BLK

(60H

z)B

LK(5

0/60

Hz)

Hig

h ta

pF4

BR

W(5

0Hz)

—H

igh

tap

Fan

mot

or in

side

wiri

ng d

iagr

am (e

xp.)

Mot

or o

ver h

eatin

g pr

otec

tion

switc

h

Wire

d fo

r MM

D-A

P048

4H-E

onl

y B

row

n co

lor w

ire.

Whe

n dr

ain

pum

p is

inst

alle

dSy

mbo

lP

arts

Nam

e43

F1,F

2Fa

n m

otor

Con

trol R

elay

CN

**C

onne

ctor

FFu

seF3

01Fu

seFM

Fan

Mot

orPM

VP

ulse

Mot

or V

alve

RC

Run

ning

Cap

acito

rR

Y002

Dra

in C

ontro

l Rel

ayRY

005,0

06,00

7Fa

n M

otor

Con

trol R

elay

TAIn

door

tem

p se

nsor

TB01

,02,

03Te

rmin

al B

lock

TC1,

2,TC

JTe

mp

sens

orTR

Tran

sfor

mer

Sold

Se

para

tely

DM

Dra

in P

ump

Mot

orFS

Floa

t Sw

itch

1.Br

oken

line

indi

cate

the

wiri

ng a

t site

.Lo

ng d

ashe

d sh

ort d

ashe

d lin

e in

dica

te

the

acce

ssor

ies.

2. in

dica

tes

the

term

inal

blo

ck.

indi

cate

s th

e co

nnec

tion

term

inal

. in

dica

tes

the

conn

ecto

r on

the

cont

rol P

.C. b

oard

.3.

indi

cate

s th

e pr

otec

tion

grou

nd.

4. in

dica

tes

the

cont

rol P

.C. b

oard

.5.

Whe

n in

stal

ling

the

drai

n pu

mp

conn

ect

the

froat

sw

itch

conn

ecto

r to

CN

30

conn

ecto

r.6.

pos

ition

is c

onne

cted

to te

rmin

al

bloc

k w

hen

chan

ge to

sta

tic p

ress

ure.

Exch

ange

the

lead

wire

of a

rrow

()

posi

tion

afte

r che

ck th

e te

rmin

al

num

ber a

s fig

ure

and

lead

wire

's c

olor

of

fan

mot

or.

7.Be

car

eful

whe

n m

odify

the

stat

ic

pres

sure

, the

sta

tic p

ress

ure

of h

igh

tap

is d

iffer

ent b

y 50

Hz

or 6

0Hz.

Flow

sel

ecto

r uni

t Ea

rth s

crew

Sub

P.C.

Boa

rd

18

Toshiba

Page 20: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 19 Tuesday, June 21, 2011 10:41 AM

Models: MMD-AP0724H-E(TR), AP0964H-E(TR)

Sym

bol

Parts

Nam

e43

F1,F

2Fa

n m

otor

Con

trol R

elay

CN

**C

onne

ctor

F1,2

,3Fu

se fo

r Fan

Mot

orF3

01Fu

seFM

Fan

Mot

orP

MV

Puls

e M

otor

Val

veR

CR

unni

ng C

apac

itor

RY

002

Dra

in C

ontro

l Rel

ayRY

005,0

06,00

7Fa

n M

otor

Con

trol R

elay

TAIn

door

tem

p se

nsor

TB01

,02,

03,

04,0

5,06

Term

inal

Blo

ck

TC1,

2,TC

JTe

mp

sens

orTR

Tran

sfor

mer

Sol

d S

epar

atel

yD

MD

rain

Pum

p M

otor

FSFl

oat S

witc

h

1.Br

oken

line

indi

cate

the

wiri

ng a

t site

.Lo

ng d

ashe

d sh

ort d

ashe

d lin

e in

dica

te

the

acce

ssor

ies.

2. in

dica

tes

the

term

inal

blo

ck.

indi

cate

s th

e co

nnec

tion

term

inal

. in

dica

tes

the

conn

ecto

r on

the

cont

rol P

.C. b

oard

.3.

indi

cate

s th

e pr

otec

tion

grou

nd.

4. in

dica

tes

the

cont

rol P

.C. b

oard

.5.

Whe

n in

stal

ling

the

drai

n pu

mp

conn

ect

the

froat

sw

itch

conn

ecto

r to

CN

30

conn

ecto

r.6.

pos

ition

is c

onne

cted

to te

rmin

al

bloc

k w

hen

chan

ge to

sta

tic p

ress

ure.

Exch

ange

the

lead

wire

of a

rrow

()

posi

tion

afte

r che

ck th

e te

rmin

al

num

ber a

s fig

ure

and

lead

wire

's c

olor

of

fan

mot

or.

7.Be

car

eful

whe

n m

odify

the

stat

ic

pres

sure

, the

sta

tic p

ress

ure

of h

igh

tap

is d

iffer

ent b

y 50

Hz

or 6

0Hz.

Term

inal

N

o.Fa

n m

otor

w

iring

Stat

ic p

ress

ure

Pa

(mm

Aq)

Not

e

F1Y

EL

69(7

)F2

BLU

137(

14)

Set

ting

from

fact

ory

F3O

RN

196(

20)

Pow

er s

uppl

y1~

50H

z 22

0-24

0V1~

60H

z 22

0V

Line

Filt

er

RE

D :

RE

DW

HI :

WH

ITE

YE

L : Y

ELL

OW

BLU

: B

LUE

BLK

: BL

AC

KG

RY

: G

RAY

PN

K :

PIN

KO

RN

: O

RA

NG

EB

RW

: B

RO

WN

GR

N :

GR

EEN

CO

LOR

ID

EN

TIFI

CAT

ION

Indo

or u

nit

Ear

th s

crew

Flow

sel

ecto

r uni

t E

arth

scr

ew

Out

door

un

it

Rem

ote

Con

trolle

r

Con

trol P

.C. B

oard

fo

r Ind

oor U

nit

Pow

er

supp

ly

circ

uit

Whe

n dr

ain

pum

p is

inst

alle

d

Sub

P.C.

Boa

rd

Fan

mot

or in

side

wiri

ng d

iagr

am

Mot

or o

ver h

eatin

g pr

otec

tion

switc

h

19

Toshiba

Page 21: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 20 Tuesday, June 21, 2011 10:41 AM

1-6. Slim duct typeModels: MMD-AP0074SPH-E(TR), AP0094SPH-E(TR), AP0124SPH-E(TR), AP0154SPH-E(TR), AP0184SPH-E(TR)

Pow

er s

uppl

y1~

50H

z 22

0-24

0V1~

60H

z 22

0V

Indo

or u

nit

Ear

th s

crew

Flow

sel

ecto

r uni

t E

arth

scr

ew

Wire

d R

emot

e C

ontro

ller

Sym

bol

Par

ts N

ame

CN

**C

onne

ctor

DM

Dra

in P

ump

Mot

orF3

01,3

02Fu

seFM

Fan

Mot

orFS

Floa

t Sw

itch

RY3

02D

rain

Con

trol R

elay

TAIn

door

tem

p se

nsor

TB01

,02

Term

inal

Blo

ckTC

1,2,T

CJTe

mp

sens

or

1.Br

oken

line

indi

cate

the

wiri

ng a

t site

.Lo

ng d

ashe

d sh

ort d

ashe

d lin

e in

dica

te th

e ac

cess

orie

s.2.

indi

cate

s th

e te

rmin

al b

lock

. in

dica

tes

the

conn

ectio

n te

rmin

al.

ind

icat

es th

e co

nnec

tor o

n th

e co

ntro

l P.C

. bo

ard.

3. in

dica

tes

the

prot

ectio

n gr

ound

.4.

indi

cate

s th

e co

ntro

l P.C

. boa

rd.

RED

: R

EDW

HI :

WH

ITE

YE

L : Y

ELL

OW

BLU

: B

LUE

BLK

: BL

AC

KG

RY

: G

RAY

PN

K :

PIN

KO

RN

: O

RA

NG

EB

RW

: B

RO

WN

GR

N :

GR

EE

N

CO

LOR

ID

ENTI

FIC

ATIO

N

Out

door

uni

t

Con

trol P

.C. B

oard

for

Indo

or U

nit

Pow

er

supp

ly

circ

uit

(Hig

h ce

iling

re

shuf

fling

)

20

Toshiba

Page 22: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 21 Tuesday, June 21, 2011 10:41 AM

1-7. Ceiling typeModels: MMC-AP0154H-E(TR), AP0184H-E(TR), AP0244H-E(TR), AP0274H-E(TR), AP0364H-E(TR), AP0484H-E(TR)

Rem

ote

Con

trolle

r

Out

door

uni

t

Con

trol P

.C. B

oard

for

Indo

or U

nit

Pow

er

supp

ly

circ

uit

Adap

ter f

or W

irele

ss

Rem

ote

Con

trolle

r

1.Br

oken

line

indi

cate

the

wiri

ng a

t site

.Lo

ng d

ashe

d sh

ort d

ashe

d lin

e in

dica

te th

e ac

cess

orie

s.2.

indi

cate

s th

e te

rmin

al b

lock

. in

dica

tes

the

conn

ectio

n te

rmin

al.

indi

cate

s th

e co

nnec

tor o

n th

e co

ntro

l P.C

. bo

ard.

3. in

dica

tes

the

prot

ectio

n gr

ound

.4.

indi

cate

s th

e co

ntro

l P.C

. boa

rd.

5.W

hen

inst

allin

g th

e dr

ain

pum

p co

nnec

t the

froa

t sw

itch

conn

ecto

r to

CN

34 c

onne

ctor

.

RED

: R

EDW

HI :

WH

ITE

YEL

: YEL

LOW

BLU

: B

LUE

BLK

: B

LAC

KG

RY

: G

RA

YPN

K :

PIN

KO

RN

: O

RA

NG

EBR

W :

BRO

WN

GR

N :

GR

EE

N

CO

LOR

ID

EN

TIFI

CA

TIO

N

Sym

bol

Parts

Nam

eC

N**

Con

nect

orF3

01,3

02Fu

seFM

Fan

Mot

orLM

Louv

er M

otor

PM

VPu

lse

Mot

or V

alve

RY

302

Dra

in C

ontro

l Rel

ayTA

Indo

or te

mp

sens

orTB

01,0

2Te

rmin

al B

lock

TC1,

2,TC

JTe

mp

sens

orS

old

Sep

arat

ely

DM

Dra

in P

ump

Mot

orFS

Floa

t Sw

itch

Pow

er s

uppl

y1~

50H

z 22

0-24

0V1~

60H

z 22

0V

Indo

or u

nit

Ear

th s

crew

Flow

sel

ecto

r uni

t Ea

rth s

crew

(Hig

h ce

iling

re

shuf

fling

)W

hen

drai

n pu

mp

is in

stal

led

21

Toshiba

Page 23: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 22 Tuesday, June 21, 2011 10:41 AM

1-8. Floor standing cabinet typeModels: MML-AP0074H-E(TR), AP0094H-E(TR), AP0124H-E(TR), AP0154H-E(TR), AP0184H-E(TR), AP0244H-E(TR)

1.Br

oken

line

indi

cate

the

wiri

ng a

t site

.Lo

ng d

ashe

d sh

ort d

ashe

d lin

e in

dica

te th

e ac

cess

orie

s.2.

indi

cate

s th

e te

rmin

al b

lock

. in

dica

tes

the

conn

ectio

n te

rmin

al.

indi

cate

s th

e co

nnec

tor o

n th

e co

ntro

l P.C

. bo

ard.

3. in

dica

tes

the

prot

ectio

n gr

ound

.4.

indi

cate

s th

e co

ntro

l P.C

. boa

rd.

RED

: R

EDW

HI :

WH

ITE

YE

L : Y

ELL

OW

BLU

: B

LUE

BLK

: BL

AC

KG

RY

: G

RAY

PN

K :

PIN

KO

RN

: O

RA

NG

EB

RW

: B

RO

WN

GR

N :

GR

EE

N

CO

LOR

ID

EN

TIFI

CA

TIO

N

Rem

ote

Con

trolle

r

Out

door

uni

t

Pow

er s

uppl

y1~

50H

z 22

0-24

0V1~

60H

z 22

0V

Indo

or u

nit

Earth

scr

ew

Flow

sel

ecto

r uni

t E

arth

scr

ew

Con

trol P

.C. B

oard

for

Indo

or U

nit

Pow

er

supp

ly

circ

uit

Line

Filt

er

Sub

P.C

. Boa

rd

Sym

bol

Par

ts N

ame

CN

**C

onne

ctor

F301

Fuse

FMFa

n M

otor

PMV

Pul

se M

otor

Val

veR

CR

unni

ng C

apac

itor

RY00

5,006

,007

Fan

Mot

or C

ontro

l Rela

yTA

Indo

or te

mp

sens

orTB

01,0

2Te

rmin

al B

lock

TC1,

2,TC

JTe

mp

sens

orTR

Tran

sfor

mer

22

Toshiba

Page 24: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 23 Tuesday, June 21, 2011 10:41 AM

1-9. Floor standing concealed typeModels: MML-AP0074BH-E(TR), AP0094BH-E(TR), AP0124BH-E(TR), AP0154BH-E(TR), AP0184BH-E(TR), AP0244BH-E(TR)

Rem

ote

Con

trolle

r

Out

door

uni

t

Pow

er s

uppl

y1~

50H

z 22

0-24

0V1~

60H

z 22

0V

Indo

or u

nit

Ear

th s

crew

Flow

sel

ecto

r uni

t E

arth

scr

ew

Line

Filt

er

1.Br

oken

line

indi

cate

the

wiri

ng a

t site

.Lo

ng d

ashe

d sh

ort d

ashe

d lin

e in

dica

te th

e ac

cess

orie

s.2.

indi

cate

s th

e te

rmin

al b

lock

. in

dica

tes

the

conn

ectio

n te

rmin

al.

indi

cate

s th

e co

nnec

tor o

n th

e co

ntro

l P.C

. bo

ard.

3. in

dica

tes

the

prot

ectio

n gr

ound

.4.

indi

cate

s th

e co

ntro

l P.C

. boa

rd.

RE

D :

RE

DW

HI :

WH

ITE

YE

L : Y

ELL

OW

BLU

: B

LUE

BLK

: B

LAC

KG

RY

: G

RA

YP

NK

: PI

NK

OR

N :

OR

AN

GE

BR

W :

BR

OW

NG

RN

: G

RE

EN

CO

LOR

ID

EN

TIFI

CA

TIO

N

Sym

bol

Parts

Nam

eC

N**

Con

nect

orF3

01Fu

seFM

Fan

Mot

orP

MV

Pul

se M

otor

Val

veR

CR

unni

ng C

apac

itor

RY00

5,006

,007

Fan

Mot

or C

ontro

l Rela

yTA

Indo

or te

mp

sens

orTB

01,0

2,03

Term

inal

Blo

ckTC

1,2,

TCJ

Tem

p se

nsor

TRTr

ansf

orm

er

Con

trol P

.C. B

oard

for

Indo

or U

nit

Pow

er

supp

ly

circ

uit

Sub

P.C

. Boa

rd

23

Toshiba

Page 25: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 24 Tuesday, June 21, 2011 10:41 AM

1-10.Floor standing typeModels: MMF-AP0154H-E(TR), AP0184H-E(TR), AP0244H-E(TR), AP0274H-E(TR), AP0364H-E(TR), AP0484H-E(TR), AP0564H-E(TR)

Rem

ote

Con

trolle

r

Out

door

uni

t

Pow

er s

uppl

y1~

50H

z 22

0-24

0V1~

60H

z 22

0V

Indo

or u

nit

Ear

th s

crew

Flow

sel

ecto

r un

it Ea

rth

scre

w

Line

Filt

er

RED

: R

ED

WH

I : W

HIT

EYE

L : Y

ELLO

WBL

U :

BLU

EBL

K :

BLA

CK

GR

Y :

GR

AY

PNK

: P

INK

OR

N :

OR

AN

GE

BRW

: BR

OW

NG

RN

: G

RE

EN

CO

LOR

ID

EN

TIFI

CA

TIO

N

Sym

bol

Par

ts N

ame

CN

**C

onne

ctor

LMLo

uver

Mot

orF3

01Fu

seFM

Fan

Mot

orP

MV

Pul

se M

otor

Val

veR

CR

unni

ng C

apac

itor

RY0

01Lo

uver

Con

trol R

elay

RY00

5,006

,007

Fan

Mot

or C

ontro

l Rela

yTA

Indo

or te

mp

sens

orTB

01,0

2,03

Term

inal

Blo

ckTC

1,2,

TCJ

Tem

p se

nsor

TRTr

ansf

orm

er

1.Br

oken

line

indi

cate

the

wiri

ng a

t site

.Lo

ng d

ashe

d sh

ort d

ashe

d lin

e in

dica

te th

e ac

cess

orie

s.2.

indi

cate

s th

e te

rmin

al b

lock

. in

dica

tes

the

conn

ectio

n te

rmin

al.

indi

cate

s th

e co

nnec

tor o

n th

e co

ntro

l P.C

. bo

ard.

3. in

dica

tes

the

prot

ectio

n gr

ound

.4.

indi

cate

s th

e co

ntro

l P.C

. boa

rd.

Con

trol P

.C. B

oard

for

Indo

or U

nit

Pow

er

supp

ly

circ

uit

Sub

P.C

. Boa

rd

24

Toshiba

Page 26: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 25 Tuesday, June 21, 2011 10:41 AM

2 Parts Rating2-1. Indoor unitCompact 4-way cassette type

1-way cassette type

Model MMU-AP 0074MH 0094MH 0124MH 0154MH 0184MHFan motor SWF-230-60-1R

Motor for horizontal grille MP24Z3N

Pulse motor EDM-MD12TF-3

Pulse motor valve EDM-B25YGTF-3 EDM-B40YGTF-3

TA sensor Lead wire length: 155 mm Vinyl tube

TC1 sensor Ø4 size lead wire length: 1400 mm Vinyl tube

TC2 sensor Ø6 size lead wire length: 1500 mm Vinyl tube (Black)

TCJ sensor Ø6 size lead wire length: 1400 mm Vinyl tube (Red)

Float switch FS-0218-103

Drain pump motor ADP-1409

Model MMU-AP 0074YH 0094YH 0124YHFan motor AF-200-22-4N-1

Running capacitor for fan motor AC 400 V, 1 µF

Drain pump motor PJD-05230TF-1

Float switch FS-0208-602

Control P.C. board transformer TT-13

Pulse motor EDM-MD12TF-3

Pulse motor valve EDM-B25YGTF

TA sensor Lead wire length: 818 mm

TC1 sensor Ø4 size lead wire length: 1200 mm Vinyl tube (Blue)

TCJ sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Red)

Model MMU-AP 0154SH 0184SH 0244SHFan motor SWF-280-60-1

Driving motor for horizontal grille MP24GA1

Pulse motor EDM-MD12TF-3

Pulse motor valve EDM-B40YGTF-3

TA sensor Lead wire length: 155 mm Vinyl tube

TC1 sensor Ø4 size lead wire length: 1100 mm Vinyl tube (Blue)

TC2 sensor Ø6 size lead wire length: 1100 mm Vinyl tube (Black)

TCJ sensor Ø6 size lead wire length: 1100 mm Vinyl tube (Red)

Float switch FS-0218-103

Drain pump motor ADP-1409

25

Toshiba

Page 27: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 26 Tuesday, June 21, 2011 10:41 AM

Concealed duct standard type

Concealed duct high static pressure type

Model MMD-AP 0074BH 0094BH 0124BH 0154BH 0184BHFan motor ICF-280-120-2

Drain pump motor ADP-1409

Float switch FS-0218-102

Pulse motor EDM-MD12TF-3

Pulse motor valve EDM-B25YGTF EDM-B40YGTF

TA sensor Lead wire length: 618 mm

TC1 sensor Ø4 size lead wire length: 1200 mm Vinyl tube (Blue)

TC2 sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Black)

TCJ sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Red)

Model MMD-AP 0244BH 0274BH 0304BH 0364BH 0484BH 0564BHFan motor ICF-280-120-1 ICF-280-120-2

Drain pump motor ADP-1409

Float switch FS-0218-102

Pulse motor EDM-MD12TF-3

Pulse motor valve EDM-B40YGTF EDM-B60YGTF-1

TA sensor Lead wire length: 618 mm

TC1 sensor Ø4 size lead wire length: 1200 mm Vinyl tube (Blue)

TC2 sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Black)

TCJ sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Red)

Model MMD-AP 0184H 0244H 0274H 0364H 0484HFan motor STF-200-160-4B STF-200-160-4A STF-200-260-4C STF-200-260-4B

Running condenser for fan motor AC 500 V, 4 µF AC 400 V, 8 µF AC 450 V, 6 µF AC 400 V, 8 µF

Drain pump motor ADP-1409

Float switch FS-0218-102-6

Pulse motor EDM-MD12TF-3

Pulse motor valve EDM-B40YGTF EDM-B60YGTF-1

TA sensor Lead wire length: 1200 mm

TC1 sensor Ø4 size lead wire length: 1200 mm Vinyl tube (Blue)

TC2 sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Black)

TCJ sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Red)

Model MMD-AP 0724H 0964HFan motor STF-200-370-4A

Running condenser for fan motor AC 450 V, 12 µF

Drain pump motor ADP-1409

Float switch FS-0218-102-6

Pulse motor EDM-MD12TF-3

Pulse motor valve EDM-BAOYGTF-1

TA sensor Lead wire length: 818 mm

TC1 sensor Ø4 size lead wire length: 2000 mm Vinyl tube (Blue)

TC2 sensor Ø6 size lead wire length: 2000 mm Vinyl tube (Black)

TCJ sensor Ø6 size lead wire length: 2000 mm Vinyl tube (Red)

26

Toshiba

Page 28: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 27 Tuesday, June 21, 2011 10:41 AM

Slim duct type

Ceiling type

Floor standing cabinet type

Floor standing concealed type

Model MMD-AP 0074SPH 0094SPH 0124SPH 0154SPH 0184SPHFan motor SWF-280-60-1

Pulse motor EDM-MD12TF-3

Pulse motor valve EDM-B25YGTF EDM-B40YGTF

Drain pump motor ADP-1409

Float switch FS-0218-102

TA sensor Lead wire length: 1558 mm Vinyl tube

TC1 sensor Ø4 size lead wire length: 1200 mm Vinyl tube (Blue)

TC2 sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Black)

TCJ sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Red)

Model MMC-AP 0154H 0184H 0244H 0274H 0364H 0484HFan motor SWF-280-60-1 SWF-280-60-2 SWF-280-120-2

Driving motor for horizontal grille MP24GA1

Pulse motor EDM-MD12TF-3

Pulse motor valve EDM-B40YGTF EDM-B60YGTF-1

TA sensor Lead wire length: 155 mm Vinyl tube

TC1 sensor Ø4 size lead wire length: 1200 mm Vinyl tube (Blue)

TC2 sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Black)

TCJ sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Red)

Model MML-AP 0074H 0094H 0124H 0154H 0184H 0244HFan motor AF-200-19-4F AF-200-45-4F AF200-70-4K

Running condenser for fan motor AC450 V, 1.2 µF AC400 V, 1.8 µF AC450 V, 2 µF

Transformer TT13

Pulse motor EDM-MD12TF-3

Pulse motor valve EDM-B25YGTF EDM-B40YGTF

TA sensor Lead wire length: 818 mm Vinyl tube

TC1 sensor Ø4 size lead wire length: 1200 mm Vinyl tube (Blue)

TC2 sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Black)

TCJ sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Red)

Model MML-AP 0074BH 0094BH 0124BH 0154BH 0184BH 0244BHFan motor AF-200-19-4G AF-200-70-4K

Running condenser for fan motor AC450 V, 1.5 µF AC450 V, 1 µF AC450 V, 2 µF

Transformer TT-13

Pulse motor EDM-MD12TF-3

Pulse motor valve EDM-B25YGTF EDM-B40YGTF

TA sensor Lead wire length: 818 mm Vinyl tube

TC1 sensor Ø4 size lead wire length: 2000 mm Vinyl tube (Blue)

TC2 sensor Ø6 size lead wire length: 2000 mm Vinyl tube (Black)

TCJ sensor Ø6 size lead wire length: 2000 mm Vinyl tube (Red)

27

Toshiba

Page 29: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 28 Tuesday, June 21, 2011 10:41 AM

Floor standing typeModel MMF-AP 0154H 0184H 0244H 0274H 0364H 0484H 0564H

Fan motor AF-200-37R AF-200-63T AF-200-110M-1 AF-200-160H-1

Running condenser for fan motor AC500 V, 3 µF AC500 V, 3.5 µF AC500 V, 4 µF

Transformer TT-13

Pulse motor EDM-MD12TF-3

Pulse motor valve EDM-B40YGTF EDM-B60YGTF-1

Driving motor for vertical louver MT8-3-9

TA sensor Lead wire length: 1200 mm Vinyl tube

TC1 sensor Ø4 size lead wire length: 1200 mm Vinyl tube (Blue)

TC2 sensor Ø6 size lead wire length: 2000 mm Vinyl tube (Black)

TCJ sensor Ø6 size lead wire length: 1200 mm Vinyl tube (Red)

28

Toshiba

Page 30: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 29 Tuesday, June 21, 2011 10:41 AM

3 Refrigerant Cycle DiagramIndoor unit

CAUTIONMMU-AP0074YH, AP0094YH, AP0124YH type air conditioners have no TC2 sensor.

Explanation of functional parts in indoor unit

Functional part name Functional outlinePulse Motor Valve

PMV

(Connector CN082 (6P): Blue)1) Controls super heat in cooling operation2) Controls under cool in heating operation3) Recovers refrigerant oil in cooling operation4) Recovers refrigerant oil in heating operation

Temp. Sensor 1.TA (Connector CN104 (2P): Yellow)1) Detects indoor suction temperature

2.TC1 (Connector CN100 (3P): Brown)1) Controls PMV super heat in cooling operation

3.TC2 (Connector CN101 (2P): Black)1) Controls PMV under cool in heating operation

4.TCJ(Connector CN102 (2P): Red)1) Controls PMV super heat in cooling operation2) [MMU-AP0074YH to AP0124YH only] Controls PMV under cool in heating operation

Capillary tube

Gas side

Heat exchanger at indoor side

Pulse Motor Valve (PMV)

Sensor (TC2)

Liquid side

Strainer

Sensor (TCJ)

Sensor (TA)

Fan

Fan motor

Sensor (TC1)

29

Toshiba

Page 31: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 30 Tuesday, June 21, 2011 10:41 AM

4 Control Outline

Indoor unitControl specificationsNO. Item Specification outline Remarks

1

Upon power supply reset

1. Identification of outdoor unitWhen the power supply is reset, the outdoor unit is identified, and control is redirected according to the identification result.

2. Indoor fan speed and air flow direction control availability settingsSettings such as indoor fan speed and air flow direction control availability are replaced on the basis of EEPROM data.

3. If power supply reset is performed in the wake of a fault, the check code is cleared. If the abnormality persists after the Start / Stop button on the remote controller is pressed to resume operation, the check code is redisplayed on the remote controller.

2

Operation selection

1. The operation mode changes in response to an operation selection command issued via the remote controller.

Ts: Temperature settingTa: Room temperature

3

Room temp. control

1. Adjustment range - remote controller temperature setting (°C)

2. In heating operation, the temperature setting may be fine-tuned via the DN code “06”.

Factory default

Shift in heating suction temperature(not applicable to remote controller thermo operation)

4

Automatic capacity control

1. The outdoor unit determines the operational capacities of indoor units according to the difference between Ta and Ts.

Ts: Temperature settingTa: Room temperature

Remote controller command Control outline

STOP Air conditioner shutdown

FAN Fan operation

COOL Cooling operation

DRY Drying operation

HEAT Heating operation

COOL / DRY HEATWired type 18~29 18~29

Wireless type 18~30 16~30

SET DATA 0 2 4 6Temperature setting adjustment +0 °C +2 °C +4 °C +6 °C

Model type SET DATAFloor standing (standard, concealed, cabinet) 0

Other model 2

Cooling Heating

30

Toshiba

Page 32: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 31 Tuesday, June 21, 2011 10:41 AM

5

Fan speed control

1. The fan operates in one of the four speed modes of “HIGH (HH)”, “MED (H)”, “LOW (L)” and “AUTO” on the basis of a command issued via the remote controller. (Concealed duct high static pressure type: HH only)

2. In AUTO fan speed mode, the air speed changes according to the difference between Ta and Ts.

<Cooling>

HH > H+ > H >L+ > L > ULor LL

• Control is identical in remote controller thermo and body thermo operation.Speed modes shown in < > apply to cooling operation under AUTO air conditioner operation mode.

• In AUTO fan speed mode, the fan speed remains the same for 3 minutes each time a speed change occurs.However, a speed change command issued via the remote controller can override this, and the fan speed changes accordingly.

• At the beginning of cooling operation, a higher speed (steeper downward temperature gradient) is chosen.

• As long as the temperature difference remains on a boundary line, the fan speed stays the same.<Heating>

Figures inside ( ) applies to remote controller thermo operation.Figures outside ( ) applies to body thermo operation.Speed modes shown in < > apply to heating operation under AUTO air conditioner operation mode.

DN code “32”“0000”: Body thermo“0001”: Remote controller thermo

• In AUTO fan speed mode, the fan speed remains the same for 1 minute each time a speed change occurs.However, a speed change command issued via the remote controller can override this, and the fan speed changes accordingly.

• At the beginning of heating operation, a higher speed (steeper upward temperature gradient) is chosen.

• As long as the temperature difference remains on a boundary line, the fan speed stays the same.

• When TC2 60 °C, the fan speed is raised by one step.

TC2: Indoor heat exchanger sensor temperature

3. If the air conditioner goes thermo OFF during heating operation, the fan speed drops down to LL (breeze).

“HEATING STANDBY ” displayed

NO. Item Specification outline Remarks

31

Toshiba

Page 33: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 32 Tuesday, June 21, 2011 10:41 AM

6

Cold air discharge prevention control

1. In heating operation, the upper limit of the fan tap is set according to the lower of whichever is the higher between TC2 sensor and TCJ sensor temperatures, on the one hand, and TC1 sensor temperature, on the other.• If the fan continuously operates in zone B for 6 minutes, it automatically moves

into zone C.• During defrosting, the control point is shifted by +6 °C.

TCJ: Indoor heat exchanger sensor temperature• In zones D and E,

priority is given to the remote controller fan speed setting.

• In zone A, “HEATING STANDBY ” is displayed.

7

Freeze prevention control (low temp. release)

1. During cooling, the air conditioner is operated in the manner described below according to the temperature readings of the TC1, TC2 and TCJ sensors.• If zone J operation is detected for 5 minutes, the air conditioner is forced into

thermo OFF.• In zone K, the timer is put on pause, with the current timer count retained.• If zone I operation is detected, the timer count is cleared, and the air conditioner

returns to normal operation.• If continuous zone J operation forces the air conditioner into thermo OFF, the

indoor fan is operated in breeze mode until it moves into zone I.The control is terminated under the following conditions:

Termination conditions1)TC1 12 °C, TC2 12 °C, and TCJ 12 °C2)Passage of 20 minutes after stoppage

2. During cooling, the air conditioner is operated in the manner described below according to the temperature readings of the TC2 and TCJ sensors.• If zone M operation is detected for 45 minutes, the air conditioner is forced into

thermo OFF.• In zone N, the timer is put on pause, with the current timer count retained.• When the air conditioner goes back into zone M, timer count is resumed from

the retained value.• If zone L operation is detected, the timer count is cleared, and the air conditioner

returns to normal operation.

TC1: Indoor heat exchanger sensor temperature

Reset conditions1)TC1 12 °C, TC2 12 °C and TCJ 12 °C2)Passage of 20 minutes after stoppage

* With models without TC2, TC2 is not part of the control parameters.

NO. Item Specification outline Remarks

Zone A:OFFZone B:26 °C or above and

below 28 °CBreeze

Zone C:28 °C or above and below 30 °CLow

Zone D:30 °C or above and below 32 °CMedium

Zone E:High

Temperature in ( ): If the temperature is below this value when the power is turned on, the air conditioner is forced into thermo OFF.

TC1 TC2, TCJ

P1 10 °C (5 °C) -10 °C

Q1 0 °C -14 °C

TC2, TCJ

P2 5

Q2 -2.0

32

Toshiba

Page 34: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 33 Tuesday, June 21, 2011 10:41 AM

8

Cooling oil (refrigerant) recovery control

While the outdoor unit is recovering cooling oil (refrigerant), the indoor units perform the following control tasks: [common for operational (cooling thermo ON / thermo OFF / FAN), as well as non-operational indoor units]

1)Open the indoor PMV to a certain degree.2)Engage in recovery control for a specified period of time and return to normal

cooling operation at the end of this period upon terminating the control.3)Operate the drain pump throughout the recovery control period and for about 1

minute after it.

• Recovery operation normally takes place roughly every 2 hours.

• The opening position of the indoor PMV depending on the type and capacity of the indoor unit.

9

Heating refrigerant (oil) recovery control

While the outdoor unit is recovering heating refrigerant (oil), the indoor units perform the following control tasks:

1)Open the indoor PMV to a certain degree.2)Control the indoor fan according to the operation mode.

[Indoor units operating in heating thermo ON / OFF state]Let the indoor fan continue operating, but turn it off if the temperature of the indoor heat exchanger drops.

[Indoor units operating in FAN mode]Turn off the indoor fan and display “HEATING STANDBY ” on the remote controller.

[Non-operational indoor units]Keep the indoor fan turned off.3)Terminate the recovery operation depending on the TC2 temperature reading.

The timing of termination is determined by each indoor unit.4)Operate the indoor fan and drain pump for about 1 minute after the termination

of the recovery operation. (Applicable to compact 4-way cassette type and 1-way cassette type)

• Recovery operation normally takes place roughly every hour.

• The opening position of the indoor PMV depending on the type and capacity of the indoor unit.

10

Defrosting control

While the outdoor unit is engaged in defrosting control, the indoor units perform the following control tasks:

1)Open the indoor PMV to a certain degree.2)Control the indoor fan according to the operation mode.

[Indoor units operating in heating thermo ON / OFF state]Let the indoor fan continue operating for a while, but turn it off as the temperature of the indoor heat exchanger drops.

[Indoor units operating in FAN mode]Let the indoor fan continue operating.

[Non-operational indoor units]Keep the indoor fan turned off.3)As defrosting control comes to an end, it gives way to heating refrigerant (oil)

recovery control.(For control details, see “9. Heating refrigerant (oil) recovery control” above.)

• For defrosting commencement conditions, see 5 Control Outline “7. Defrosting control (reverse defrosting method)” in SMMS-i Outdoor Unit Service Manual A10-005 above.

• The opening position of the indoor PMV depending on the type and capacity of the indoor unit.

11

Short intermittent operation compensation control

1. For 5 minutes after startup, the system is forced to continue operating even if it reaches the thermo OFF region.

2. However, priority is given to cooling / heating selection, operation standby, and protective control, so that there is no overriding of thermo OFF in these cases.

12

Drain pump control

1. During cooling (including DRY operation), the drain pump is operated at all times.2. If the float switch is activated while the drain pump is in operation, the drain pump

continues operating, with the relevant check code displayed.3. If the float switch is activated while the drain pump is turned off, thermo OFF is

forced on the air conditioner, with the drain pump put into operation. If the float switch continues to be activated for about 5 minutes, the drain pump is turned off, with the relevant check code displayed.

Check code [P10]

13 Elimination of residual heat

1. When the air conditioner is turned off after engaging in heating operation, the indoor fan is operated for about 30 seconds in “breeze” mode.

NO. Item Specification outline Remarks

33

Toshiba

Page 35: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 34 Tuesday, June 21, 2011 10:41 AM

14

Filter sign display(not applicable to wireless type)* Provided in

the separately mounted type, TCB-AX21E.

1. The indoor fan’s cumulative hours of operation are counted, and when these exceed the prescribed value (150H / 2500H), a filter replacement signal is sent to the remote controller to display a filter sign on it.

2. When a filter reset signal is received from the remote controller, the timer measuring cumulative hours is cleared. If the prescribed hours have been exceeded, the hours count is reset, with the sign on the remote controller display erased.

“FILTER ” displayed

15

Operation standbyHeating standby

<Operation standby> .......... Displayed on remote controller1. When any of the DN codes listed below is displayed

• “P05” - Detection of an open phase in the power supply wiring• “P10” - Detection of indoor flooding in at least one indoor unit• “L30” - Detection of an interlock alarm in at least one indoor unit

2. Forced thermo OFF• “COOL / DRY” operation is unavailable because at least one indoor unit is

operating in “HEAT” mode.• “HEAT” operation is unavailable because at least one indoor unit is operating in

“COOL / DRY” mode under priority cooling setting (bit 1 of SW11 on outdoor I/F P.C. board ON).

3. All indoor units not able to engage in any of the above operations stand by in thermo OFF state.

4. The indoor fan has been turned off because the system is engaged in a heat refrigerant (oil) recovery operation.

• “OPERATION STANDBY ” displayed

No display provided on wireless remote controller

<Heating standby> .......... Displayed on remote controller1. Normal thermo OFF

• During heating, the indoor unit goes thermo OFF as the heating temperature setting is reached.

2. During heating, the fan rotates at a breeze speed (UL or lower) or remains stationary to prevent cold air from being discharged (including defrosting operation).

3. Forced thermo OFF• “HEAT” operation is unavailable because at least one indoor unit is operating in

“COOL / DRY” mode under priority cooling setting (bit 1 of SW11 on outdoor I/F P.C. board ON).

• “HEATING STANDBY ” displayed

NO. Item Specification outline Remarks

Filter service life 2500H 150H

Type

4-way cassette type1-way cassette type(SH, YH)2-way cassette typeCeiling typeConcealed duct standard typeConcealed duct high static pressure typeSlim duct type

High wall typeFloor standing typeFloor standing concealed typeFloor standing cabinet type

34

Toshiba

Page 36: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 35 Tuesday, June 21, 2011 10:41 AM

16

Selection of central control mode

1. The range of operations that can be performed via an indoor unit remote controller can be determined through the setting of the central controller.

2. Setting details

• In the case of a wired remote controller, “CENTRAL CONTROL IN PROGRESS ” is displayed (lit up) while in central control mode.

• The display blinks when a control function inaccessible to a remote controller is chosen.

• A wireless remote controller has the same set of control functions, although there is no display. When a control operation is performed via a wireless remote controller while in central control mode, a peep sound alert (5 times) is provided.

17

Louver control 1. Louver position setting• When the louver position is changed, the louver turns all the way down before

settling in the set position.• Louver position is adjustable in the range shown in the diagrams below.

• During group operation, position setting can be performed individually or collectively.

2. Swing setting• The “SWING” sign is displayed, along with alternating images as shown below.

• During group operation, swing setting can be performed individually or collectively.

3. Set louver positions

18

DC motor 1. When the fan is turned on, the positions of the stator and rotor are determined.(The motor turns in incremental steps.)

2. The fan operates in accordance with commands issued by the indoor controller.

Note: If the fan is rotating while the air conditioner is turned off due to an inflow of outside air or some other reason, the indoor unit may operate without turning on the fan motor.

Note: If fan motor lock is detected, the indoor unit is turned off, with an error display provided.

Check code “P12”

NO. Item Specification outline Remarks

TCC-Link central control

(O: Accessible ×: Inaccessible)

Operation via TCC-

Link central control

Operation via RBC-AMT32ERBC-

AMT32E displayStart / stop

selectionOperation

mode selection

Timer setting

Temperature setting

Fan speed setting

Air flow direction setting

Individual O O O O O O

“CENTRAL CONTROL

IN PROGRESS”

Central 1 × O × O O O

Central 2 × × × × O O

Central 3 O × O × O O

Central 4 O × O O O O

During cooling / drying During heating / fan-only operation

In all operation modes

(alternating)

4-way 1-way (SH) Ceiling

Normal stop Downward Closed Horizontal

Abnormal stop Downward No change Horizontal

Heating standby Upward Upward Horizontal

Oil / refrigerant recovery Upward Upward Horizontal

35

Toshiba

Page 37: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 36 Tuesday, June 21, 2011 10:41 AM

19

Power saving mode

1. Push the button on the remote controller2. The " " segment lights up on the wired remote controller display.3. The requirement capacity ratio is limited to approximately 75 %.4. If the power saving operation is enabled, the settings are retained when the

operation is stopped, when the mode is changed, or when the power is reset. The power saving operation will be enabled the next time the operation starts.

The power saving operation cannot be set by the wireless remote controller or wired remote controller of AMT31E or older.

NO. Item Specification outline Remarks

36

Toshiba

Page 38: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 37 Tuesday, June 21, 2011 10:41 AM

5 Applied Control and Functions (Including Circuit Configuration)

5-1. Indoor controller block diagram5-1-1. When main (sub) remote controller connected<Compact 4-way cassette type, 1-way cassette (SH) type, ceiling type, concealed duct standard type, slim duct type>

Mai

n (s

ub) r

emot

e co

ntro

ller (

up to

2 u

nits

)

Mai

n re

mot

e co

ntro

ller

:RB

C-A

MT3

2E

Sub

rem

ote

cont

rolle

r :R

BC

-AS2

1E2

Sche

dule

Tim

er (W

eekl

y tim

er m

ode)

Dis

play

LC

DD

ispl

ay

LED

EE

PRO

M

Rem

ote

cont

rolle

r co

mm

unic

atio

n ci

rcui

t

Func

tion s

etting

Pow

er

supp

ly

circ

uit

Rec

harg

eabl

e ba

ttery

Dis

play

LC

DLC

D

driv

er

Func

tion s

etting

Key

switc

hK

ey s

witc

h

CP

U

Pow

er

supp

ly

circ

uit

Indo

or u

nit

Cen

tral

rem

ote

cont

rolle

r (o

ptio

nal)

Net

wor

k ad

apto

r (op

tiona

l)

Indo

or c

ontro

l P.C

. boa

rd (M

CC

-140

2)

(In c

ase

of 1

:1

mod

el)

Net

wor

k ad

apto

r P.C

. bo

ard

(MC

C-1

401)

Remo

te cont

roller

commu

nicatio

n circ

uit

AI-NE

T com

munic

ation

circuit

Powe

r suppl

y circu

itSw

itch se

tting

Tran

sfor

mer

Louv

er

mot

or

Indo

or

fan

mot

or

*Not

appli

cable

to co

ncea

led du

ct sta

ndard

type

Slim

Duc

t Typ

eD

rain

pu

mp

Powe

r sup

ply ci

rcuit

Fan

mot

or

cont

rol c

ircui

t

In o

pera

tion

Ala

rmG

ettin

g re

ady

Ther

mos

tat O

NC

OO

LH

EA

TFA

N

AC

synch

roniza

tion

signa

l inpu

t circ

uit

BUS

comm

unica

tion

circu

it

Exte

rnal

out

put

Driver

TA s

enso

r

TCI s

enso

r

TC2

sens

or

TCJ

sens

or

Floa

t inp

ut

Remo

te co

ntrolle

r co

mmun

icatio

n cir

cuit

EEPR

OM

Net

wor

k ad

apto

r : "1

:1 m

odel

" con

nect

ion

inte

rface

TC

B-PC

NT3

0TLE

2

Indo

or /

outd

oor c

omm

unic

atio

n

Pow

er s

ourc

e 1Ø

220

-240

V, 5

0 H

z 1Ø

220

V, 6

0 H

z

Out

door

un

it

Sam

eas

left

*2S

amea

s lef

t *2

Pow

er

sour

ce

Up

to 8

uni

ts c

an b

e co

nnec

ted.

*1 *1

Onl

y up

to 7

uni

ts if

a n

etw

ork

adap

tor i

s in

stal

led

with

2

mai

n (s

ub) r

emot

e co

ntro

llers

co

nnec

ted.

*2Th

e ne

twor

k ad

apto

r can

onl

y be

inst

alle

d in

one

uni

t.

*3A

wee

kly

timer

can

not b

e co

nnec

ted

to a

sub

rem

ote

cont

rolle

r.

Pow

er

sour

ceO

utdo

or

unit

Out

door

un

it

37

Toshiba

Page 39: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 38 Tuesday, June 21, 2011 10:41 AM

<1-way cassette (YH) type, floor standing type, concealed duct high static pressure type, floor standing concealed type, floor standing cabinet type>

Mai

n (s

ub) r

emot

e co

ntro

ller (

up to

2 u

nits

)

Mai

n re

mot

e co

ntro

ller

:RB

C-A

MT3

2E

Sub

rem

ote

cont

rolle

r :R

BC

-AS2

1E2

Sche

dule

Tim

er (W

eekl

y tim

er m

ode)

Dis

play

LC

D

Dis

play

LE

D

EEP

RO

M

Rem

ote

cont

rolle

r co

mm

unic

atio

n ci

rcui

t

Func

tion s

etting

Pow

er

supp

ly

circ

uit

Rec

harg

eabl

e ba

ttery

Dis

play

LC

DLC

D

driv

er

Func

tion s

etting

Key

sw

itch

Key

sw

itch

Pow

er

supp

ly

circ

uit

Indo

or u

nit

Cen

tral

rem

ote

cont

rolle

r (o

ptio

nal)

Net

wor

k ad

apto

r (op

tiona

l)

Indo

or c

ontro

l P.C

. boa

rd (M

CC

-140

3)

(In c

ase

of 1

:1

mod

el)

Net

wor

k ad

apto

r P.C

. bo

ard

(MC

C-1

401)

Remo

te cont

roller

commu

nicatio

n circ

uit

AI-NE

T com

munic

ation

circuit

Powe

r sup

ply cir

cuit

Switch

settin

g

Tran

sfor

mer

Louv

er

mot

or

Indo

or

fan

mot

or

*Not

appli

cable

to

conc

ealed

duct

high

static

pres

sure

typeD

rain

pu

mp

Pow

er s

uppl

y ci

rcui

t

Fan

mot

or

rela

y ci

rcui

t

In o

pera

tion

Ala

rmGe

tting

read

yTh

ermo

stat O

NC

OO

LH

EA

TFA

N

AC

synch

roniza

tion

signa

l inpu

t circ

uit

BUS

comm

unica

tion

circu

it

Exte

rnal

ou

tput

Driver

TA s

enso

r

TCI s

enso

r

TC2

sens

or

TCJ

sens

or

Floa

t inp

ut

Remo

te co

ntrolle

r co

mmun

icatio

n cir

cuit

EEPR

OM

Net

wor

k ad

apto

r : "1

:1 m

odel

" con

nect

ion

inte

rface

TC

B-P

CN

T30T

LE2

Indo

or /

outd

oor c

omm

unic

atio

n

Pow

er s

ourc

e 1Ø

220

-240

V, 5

0 H

z 1Ø

220

V, 6

0 H

z

Out

door

un

it

Sam

eas

left

*2Sa

mea

s lef

t *2

Pow

er

sour

ce

Up

to 8

uni

ts c

an b

e co

nnec

ted.

*1

*1O

nly

up to

7 u

nits

if a

ne

twor

k ad

apto

r is

inst

alle

d w

ith 2

mai

n (s

ub) r

emot

e co

ntro

llers

co

nnec

ted.

*2Th

e ne

twor

k ad

apto

r can

on

ly b

e in

stal

led

in o

ne

unit.

*3A

wee

kly

timer

can

not b

e co

nnec

ted

to a

sub

re

mot

e co

ntro

ller.

Pow

er

sour

ceO

utdo

or

unit

Out

door

un

it

*1-w

ay T

ype

only

Tran

sfor

mer

*Not a

pplica

ble to

concea

led

duct h

igh sta

tic pre

ssure

type

*Not

appli

cable

to 1-

way

air di

scha

rge c

asse

tte

type (

comp

act)

38

Toshiba

Page 40: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 39 Tuesday, June 21, 2011 10:41 AM

5-1-2. When wireless remote controller kit connected<Compact 4-way cassette type, 1-way cassette (SH) type, ceiling type, concealed duct standard type, slim duct type>

Sens

or P

.C. b

oard

Powe

r sup

ply

circu

it

Sam

eas l

eft

*2Sa

mea

s lef

t *2

Pow

er

sour

ce

Up

to 8

uni

ts c

an b

e co

nnec

ted.

*1

*1O

nly

up to

7 u

nits

if a

ne

twor

k ad

apto

r is

inst

alle

d w

ith 2

w

irele

ss re

mot

e co

ntro

ller k

its

conn

ecte

d.

*2Th

e ne

twor

k ad

apto

r ca

n on

ly b

e in

stal

led

in

one

unit.

Pow

er

sour

ceO

utdo

or

unit

Out

door

un

it

In o

pera

tion

Ala

rmGe

tting

read

yTh

ermo

stat O

NC

OO

LH

EA

TFA

N

AC

synch

roniza

tion

signa

l inpu

t circ

uit

BUS

comm

unica

tion

circu

it

Exte

rnal

ou

tput

Driver

TA s

enso

r

TCI s

enso

r

TC2

sens

or

TCJ

sens

or

Floa

t inp

ut

Remo

te co

ntrolle

r co

mmun

icatio

n cir

cuit

EEPR

OM

*Not

applica

ble to

conce

aled

duct h

igh sta

tic pre

ssure

type

Indo

or c

ontro

l P.C

. boa

rd (M

CC

-140

2)

Powe

r sup

ply ci

rcuit

Fan

mot

or

rela

y ci

rcui

t

Tran

sfor

mer

Net

wor

k ad

apto

r : "1

:1 m

odel

" con

nect

ion

inte

rface

TC

B-PC

NT3

0TLE

2In

door

/ ou

tdoo

r com

mun

icat

ion

Pow

er s

ourc

e 1Ø

220

-240

V, 5

0 H

z 1Ø

220

V, 6

0 H

z

Out

door

un

it

Louv

er

mot

or

Indo

or

fan

mot

or

*Not

appli

cable

to co

ncea

led du

ct sta

ndard

type

Slim

Duc

t Typ

e

Dra

in

pum

p

Indo

or u

nit

Cen

tral

rem

ote

cont

rolle

r (o

ptio

nal)

Net

wor

k ad

apto

r (op

tiona

l)

(In c

ase

of 1

:1

mod

el)

Net

wor

k ad

apto

r P.C

. bo

ard

(MC

C-1

401)

Remo

te cont

roller

commu

nicatio

n circ

uit

AI-NE

T com

munic

ation

circuit

Powe

r supp

ly circu

itSw

itch se

tting

Wire

less r

emot

e con

trolle

r kit

Remo

te co

ntrolle

r co

mmun

icatio

n cir

cuit

Emer

genc

y op

erat

ion S

W

Func

tion

setti

ng S

W

Disp

lay

LED

Sens

or c

ircui

t

Buzz

er

39

Toshiba

Page 41: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 40 Tuesday, June 21, 2011 10:41 AM

<1-way cassette (YH) type, floor standing type, concealed duct high static pressure type, floor standing concealed type, floor standing cabinet type>

Sam

eas l

eft

*2Sa

mea

s lef

t *2

Pow

er

sour

ce

Up

to 8

uni

ts c

an b

e co

nnec

ted.

*1

*1O

nly

up to

7 u

nits

if a

ne

twor

k ad

apto

r is

inst

alle

d w

ith 2

w

irele

ss re

mot

e co

ntro

ller k

its

conn

ecte

d.

*2Th

e ne

twor

k ad

apto

r ca

n on

ly b

e in

stal

led

in

one

unit.

Pow

er

sour

ceO

utdo

or

unit

Out

door

un

it

Wire

less r

emot

e co

ntro

ller k

it

Rem

ote

cont

rolle

r co

mm

unic

atio

n ci

rcui

t

Sens

or

circu

itD

ispl

ay

sect

ion

In o

pera

tion

Alar

mGe

tting

read

yTh

ermost

at ON

COO

LHE

ATFA

N

AC

synch

roniza

tion

signa

l inpu

t circ

uit

BUS

com

mun

icatio

n cir

cuit

Exte

rnal

ou

tput

Driver

TA s

enso

r

TCI s

enso

r

TC2

sens

or

TCJ

sens

or

Floa

t inp

ut

Remo

te co

ntrolle

r co

mmun

icatio

n cir

cuit

EEPR

OM

*Not

applica

ble to

conce

aled

duct h

igh sta

tic pre

ssure

type

Indo

or c

ontro

l P.C

. boa

rd (M

CC

-140

3)

Fan

mot

or

rela

y ci

rcui

t

Tran

sfor

mer

Tran

sfor

mer

Pow

er s

uppl

y ci

rcui

t

Net

wor

k ad

apto

r : "1

:1 m

odel

" con

nect

ion

inte

rface

TC

B-P

CN

T30T

LE2

Indo

or /

outd

oor c

omm

unic

atio

n

Pow

er s

ourc

e 1Ø

220

-240

V, 5

0 H

z 1Ø

220

V, 6

0 H

z

Out

door

un

it

Louv

er

mot

or

Indo

or

fan

mot

or

*Not

appli

cable

to

conc

ealed

duct

high s

tatic

press

ure t

ype

Dra

in

pum

p

Indo

or u

nit

Cen

tral

rem

ote

cont

rolle

r (o

ptio

nal)

Net

wor

k ad

apto

r (op

tiona

l)

(In c

ase

of 1

:1

mod

el)

Net

wor

k ad

apto

r P.C

. bo

ard

(MC

C-1

401)

Remo

te cont

roller

commu

nicatio

n circ

uit

AI-NE

T com

munic

ation

circuit

Powe

r supp

ly circu

itSw

itch se

tting

*1-w

ay T

ype

only

40

Toshiba

Page 42: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 41 Tuesday, June 21, 2011 10:41 AM

5-1-3. When both main (sub) remote controller and wireless remote controller kit connected

<Compact 4-way cassette type, 1-way cassette (SH) type, ceiling type, concealed duct standard type, slim duct type>

Mai

n (s

ub) r

emot

e co

ntro

ller (

up to

2 u

nits

)

Mai

n re

mot

e co

ntro

ller

:RB

C-A

MT3

2E

Sub

rem

ote

cont

rolle

r :R

BC

-AS2

1E2

Sche

dule

Tim

er (W

eekl

y tim

er m

ode)

Dis

play

LC

D

Dis

play

LE

D

EE

PRO

M

Rem

ote

cont

rolle

r co

mm

unica

tion

circu

it

Func

tion s

etting

Pow

er

supp

ly

circ

uit

Rec

harg

eabl

e ba

ttery

Dis

play

LC

DLC

D

driv

er

Func

tion

settin

g

Key

switc

hKe

y sw

itch

Pow

er

supp

ly

circ

uit

Indo

or u

nit

Cen

tral

rem

ote

cont

rolle

r (o

ptio

nal)

Net

wor

k ad

apto

r (op

tiona

l)

Indo

or c

ontro

l P.C

. boa

rd (M

CC

-140

2)

(In c

ase

of 1

:1

mod

el)

Net

wor

k ad

apto

r P.C

. bo

ard

(MC

C-1

401)

Remo

te cont

roller

commu

nicatio

n circ

uit

AI-NE

T com

munic

ation

circuit

Powe

r sup

ply cir

cuit

Switch

settin

g

Tran

sfor

mer

Louv

er

mot

or

Indo

or

fan

mot

or

*Not

appli

cable

to co

ncea

led du

ct sta

ndar

d typ

e Slim

Duc

t Typ

eD

rain

pu

mp

Powe

r sup

ply ci

rcuit

Fan

mot

or

cont

rol c

ircui

t

In o

pera

tion

Ala

rmG

ettin

g re

ady

Ther

mos

tat O

NC

OO

LH

EA

TFA

N

AC

synch

roniza

tion

signa

l inpu

t circ

uit

BUS

comm

unica

tion

circu

it

Exte

rnal

out

put

Driver

TA s

enso

r

TCI s

enso

r

TC2

sens

or

TCJ

sens

or

Floa

t inp

ut

Remo

te co

ntrolle

r co

mmun

icatio

n cir

cuit

EEPR

OM

Net

wor

k ad

apto

r : "1

:1 m

odel

" con

nect

ion

inte

rface

TC

B-P

CN

T30T

LE2

Indo

or /

outd

oor c

omm

unic

atio

n

Pow

er s

ourc

e 1Ø

220

-240

V, 5

0 H

z 1Ø

220

V, 6

0 H

z

Out

door

un

it

Sam

eas l

eft

*2S

amea

s lef

t *2

Pow

er

sour

ce

Up

to 8

uni

ts c

an b

e co

nnec

ted.

*1

*1O

nly

up to

7 u

nits

if

a ne

twor

k ad

apto

r is

inst

alle

d.

*2Th

e ne

twor

k ad

apto

r can

onl

y be

inst

alle

d in

on

e un

it.

*3A

wee

kly

timer

ca

nnot

be

conn

ecte

d to

a

sub

rem

ote

cont

rolle

r.

Pow

er

sour

ceO

utdo

or

unit

Out

door

un

it

Sens

or P

.C. b

oard

Powe

r sup

ply

circu

it

Wire

less r

emot

e con

trolle

r kit

Remo

te co

ntrolle

r co

mmun

icatio

n cir

cuit

Emer

genc

y op

erat

ion S

W

Func

tion

setti

ng S

W

Disp

lay

LED

Sens

or c

ircui

t

Buzz

er

*Not a

pplica

ble to

concea

led

duct h

igh sta

tic pre

ssure

type

41

Toshiba

Page 43: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 42 Tuesday, June 21, 2011 10:41 AM

<1-way cassette (YH) type, floor standing type, concealed duct high static pressure type, floor standing concealed type, floor standing cabinet type>

Mai

n (s

ub) r

emot

e co

ntro

ller (

up to

2 u

nits

)

Mai

n re

mot

e co

ntro

ller

:RB

C-A

MT3

2E

Sub

rem

ote

cont

rolle

r :R

BC

-AS2

1E2

Sche

dule

Tim

er (W

eekl

y tim

er m

ode)

Dis

play

LC

DD

ispl

ay

LED

EE

PRO

M

Rem

ote

cont

rolle

r co

mm

unica

tion

circu

it

Func

tion s

ettin

g

Pow

er

supp

ly

circ

uit

Rec

harg

eabl

e ba

ttery

Dis

play

LC

DLC

D

driv

er

Func

tion

settin

g

Key

switc

hKe

y sw

itch

Pow

er

supp

ly

circ

uit

Indo

or u

nit

Cen

tral

rem

ote

cont

rolle

r (o

ptio

nal)

Net

wor

k ad

apto

r (op

tiona

l)

Indo

or c

ontro

l P.C

. boa

rd (M

CC

-140

3)

(In c

ase

of 1

:1

mod

el)

Net

wor

k ad

apto

r P.C

. bo

ard

(MC

C-1

401)

Remo

te con

troller

com

munic

ation

circuit

AI-NE

T com

munic

ation

circuit

Powe

r sup

ply cir

cuit

Switch

settin

g

Tran

sfor

mer

Louv

er

mot

or

Indo

or

fan

mot

or

*Not

appli

cable

to

conc

ealed

duct

high s

tatic

press

ure t

ype

Dra

in

pum

p

Powe

r sup

ply ci

rcuit

Fan

mot

or

cont

rol c

ircui

t

In o

pera

tion

Ala

rmGe

tting

read

yTh

ermos

tat O

NC

OO

LH

EA

TFA

N

AC

synch

roniza

tion

signa

l inpu

t circ

uit

BUS

comm

unica

tion

circu

it

Exte

rnal

ou

tput

Driver

TA s

enso

r

TCI s

enso

r

TC2

sens

or

TCJ

sens

or

Floa

t inp

ut

Remo

te co

ntrolle

r co

mmun

icatio

n cir

cuit

EEPR

OM

Net

wor

k ad

apto

r : "1

:1 m

odel

" con

nect

ion

inte

rface

TC

B-PC

NT3

0TLE

2

Indo

or /

outd

oor c

omm

unic

atio

n

Pow

er s

ourc

e 1Ø

220

-240

V, 5

0 H

z 1Ø

220

V, 6

0 H

z

Out

door

un

it

Sam

eas l

eft

*2Sa

mea

s lef

t *2

Pow

er

sour

ce

Up

to 8

uni

ts c

an b

e co

nnec

ted.

*1

*1O

nly

up to

7 u

nits

if

a ne

twor

k ad

apto

r is

inst

alle

d.

*2Th

e ne

twor

k ad

apto

r can

onl

y be

inst

alle

d in

on

e un

it.

*3A

wee

kly

timer

ca

nnot

be

conn

ecte

d to

a

sub

rem

ote

cont

rolle

r.

Pow

er

sour

ceO

utdo

or

unit

Out

door

un

it

Wire

less r

emot

e co

ntro

ller k

it

*Not

applica

ble to

conce

aled

duct h

igh sta

tic pre

ssure

type

Tran

sfor

mer

Rem

ote

cont

rolle

r co

mm

unic

atio

n ci

rcui

t

Sens

or

circu

itD

ispl

ay

sect

ion

*1-w

ay T

ype

only

42

Toshiba

Page 44: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 43 Tuesday, June 21, 2011 10:41 AM

5-2. Indoor printed circuit boardMCC-1402 <compact 4-way cassette type, 1-way cassette (SH) type, ceiling type, concealed duct standard type, slim duct type>

Mic

roco

mpu

ter o

pera

tion

LED

Filte

r / o

ptio

nal e

rror

inpu

tE

EP

RO

MH

igh-

ceili

ng a

djus

tmen

t inp

ut

Pow

er s

uppl

y

Opt

iona

l pow

er s

uppl

y

Rem

ote

cont

rolle

r po

wer

sou

rce

LED

Dra

in p

ump

outp

ut

Rem

ote

cont

rolle

r jum

per

Indo

or /

outd

oor c

omm

unic

atio

n(d

oubl

ing

as c

entra

l con

trol c

omm

unic

atio

n)

Indo

or /

outd

oor c

omm

unic

atio

n (b

acku

p)

TCI s

enso

r

TC2

sens

or

Ext

erna

l err

or in

put

TCJ

sens

or

EX

CT

DIS

P(U

sed

for s

ervi

cing

)C

HK

(Use

d fo

r ser

vici

ng)

TA s

enso

r

HA

(T10

)

Opt

iona

l out

put

Fan

outp

ut

Louv

er

Floa

t SW

DC

fan

retu

rn

PM

V o

utpu

tD

C fa

n ou

tput

43

Toshiba

Page 45: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 44 Tuesday, June 21, 2011 10:41 AM

MCC-1403 <1-way cassette (YH) type, floor standing type, concealed duct high static pressure type, floor standing concealed type, floor standing cabinet type>

PM

V o

utpu

t EE

PR

OM

Indo

or /

outd

oor c

omm

unic

atio

n (b

acku

p)

Indo

or / o

utdo

or c

omm

unic

atio

n (d

oubl

ing

as c

entra

l co

ntro

l com

mun

icat

ion)

Rem

ote

cont

rolle

r pow

er

sour

ce L

ED

HA

(T10

)

Opt

iona

l out

put

Rem

ote

cont

rolle

r jum

per

Use

d fo

r se

rvic

ing

DIS

P

CH

K

TCI s

enso

r

TC2

sens

or

TCJ

sens

or

Ext

erna

l err

or

inpu

t

Floa

t SW

*S

hort

plug

inse

rted

in c

once

aled

duc

tTA

sen

sor

Filte

r / o

ptio

nal e

rror i

nput

EX

CT

AC

fan

outp

ut

Opt

iona

l po

wer

sup

ply

Louv

er

Pow

er

supp

ly

trans

form

er

(prim

ary

side

)

Pow

er s

uppl

y

Pow

er s

uppl

y tra

nsfo

rmer

(sec

onda

ry s

ide)

(A

C 1

1, 1

4, 2

0 V

)M

icro

com

pute

r op

erat

ion

LED

Dra

in p

ump

outp

ut

44

Toshiba

Page 46: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 45 Tuesday, June 21, 2011 10:41 AM

5-3. Optional connector specifications of indoor P.C. board

Function Connector No. Pin No. Specification RemarksFan output

CN32

1 DC12 V Factory default setting: ON when indoor unit in operation and OFF when indoor unit at rest* Fan can be operated on its own by pressing FAN

button on remote controller (DN = 31)2

Output

HA

CN61

1 Start / stop input Start / stop input for HA (J01: In place / Removed = Pulse input (factory default) / Step input)

2 0 V (COM)

3 Remote controller disabling input

Enables / disables start / stop control via remote controller

4 In-operation output ON during operation (HA answerback signal)

5 DC12 V (COM)

6 Alarm output ON while alarm ON

Optional output

CN60

1 DC12 V (COM)

2 Defrosting output ON while outdoor unit defrosted

3 Thermostat ON output ON while real thermostat ON (compressor ON)

4 Cooling output ON while air conditioner in cooling or related operation (COOL, DRY or cooling under AUTO mode)

5 Heating output ON while air conditioner in heating operation (HEAT or heating under AUTO mode)

6 Fan output ON while indoor fan ON (air cleaner in use or via interlock wiring)

External error input CN80

1 DC12 V (COM) Generates test code L30 and automatically shuts down air conditioner (only if condition persistsfor 1 minute)

2 DC12 V (COM)

3 External error input

CHKOperation check CN71

1 Check mode input Used for indoor operation check (prescribed operational status output, such as indoor fan "H" or drain pump ON, to be generated without communication with outdoor unit or remote controller)

20 V

DISPDisplay mode CN72

1 Display mode input Product display mode - Communication just between indoor unit and remote controller enabled (upon turning on of power) Timer short-circuited out (always)2 0 V

EXCTDemand CN73

1 Demand input Imposes thermostat OFF on indoor unit

2 0 V

45

Toshiba

Page 47: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 46 Tuesday, June 21, 2011 10:41 AM

5-4. Test operation of indoor unit▼ Check function for operation of indoor unit (Functions at indoor unit side)This function is provided to check the operation of the indoor unit singly without communication with the remote controller or the outdoor unit. This function can be used regardless of operation or stop of the system.However, if using this function for a long time, a trouble of the equipment may be caused. Limit using this function within several minutes.

[How to operate]1) Short-circuit CHK pin (CN71 on the indoor P.C. board).

The operation mode differs according to the indoor unit status in that time.Normal time: Both float SW and fan motor are normal.Abnormal time: Either one of float SW or fan motor is abnormal.

2) Restricted to the normal time, if short-circuiting DISP pin (CN72 on the indoor P.C. board) in addition to short-circuit of CHK pin (CN71 on the indoor P.C. board), the minimum opening degree (30 pls) can be set to the indoor PMV only.When open DISP pin, the maximum opening degree (1500 pls) can be obtained again.

[How to clear]Open CHK pin. While the system is operating, it stops once but automatically returns to operation after several minutes.

• To exchange the indoor PMV coil, set the indoor PMV to Max. opening degree.• For the detailed positions of CHK pin (CN71 on indoor P.C. board) and DISP pin (CN72 on indoor P.C. board),

refer to the indoor P.C. board MCC-1570.

Short-circuit of CHK pinNormal time

Abnormal timeDISP pin open DISP pin short circuit

Fan motor (H) (H) Stop

Indoor PMV (*) Max. opening degree (1500 pls) Min. opening degree (30 pls) Min. opening degree (30 pls)

Louver Horizontal Horizontal Immediate stop

Drain pump ON ON ON

Communication All ignored All ignored All ignored

P.C. board LED Lights Lights Flashes

46

Toshiba

Page 48: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 47 Tuesday, June 21, 2011 10:41 AM

5-5. Method to set indoor unit function DN code(When performing this task, be sure to use a wired remote controller.)

<Procedure> To be performed only when system at rest

1 Push the + + buttons simultaneously and hold for at least 4 seconds.The unit No. displayed first is the address of the header indoor unit in group control.Then the fan and louver of the selected indoor unit move.

2 Each time the “Select unit” side of the button is pressed, one of the indoor unit Nos. under group control is displayed in turn. Then the fan and louver of the selected indoor unit move.

3 Use the button to select the CODE No. (DN code) of the desired function.

4 Use the button to select the desired SET DATA associated with the selected function.

5 Push the button. (The display changes from flashing to steady.)• To change the selected indoor unit, go back to step 2.• To change the selected function, go back to step 3.

6 When the button is pushed, the system returns to normal off state.

47

Toshiba

Page 49: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 48 Tuesday, June 21, 2011 10:41 AM

Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)

DN Item Description At shipment

01Filter display delay timer 0000: None

0002: 2500H0004: 10000H

0001: 150H0003: 5000H

According to type

02 Dirty state of filter 0000: Standard0001: High degree of dirt (Half of standard time)

0000: Standard

03 Central control address 0001: No.1 unit0099: Unfixed

to 0064: No.64 unit 0099: Unfixed

04 Specific indoor unit priority

0000: No priority 0001: Priority 0000: No priority

06Heating temp shift 0000: No shift

0002: +2 °C to0001: +1 °C0010: +10 °C(Up to +6 recommended)

0002: +2 °C(Floor type 0000: 0 °C)

0d Existence of [AUTO] mode

0000: Provided0001: Not provided (Automatic selection from connected outdoor unit)

0001: Not provided

0F Cooling only 0000: Heat pump0001: Cooling only (No display of [AUTO] [HEAT])

0000: Heat pump

10 Type 0001: 4-way Cassette etc.* refer to 50 page Type CODE No. [10]

Depending on model type

11 Indoor unit capacity 0000: Unfixed 0001 to 0034 According to capacity type

12 Line address 0001: No.1 unit to 0030: No.30 unit 0099: Unfixed

13 Indoor unit address 0001: No.1 unit to 0064: No.64 unit 0099: Unfixed

14 Group address 0000: Individual0002: Follower unit of group

0001: Header unit of group 0099: Unfixed

19

Louver type(Air direction adjustment)

0000: No louver 0001: Swing only According to type

0002: (1-way Cassette type, Ceiling type)0003: (2-way Cassette type)0004: (4-way Cassette type)

1E

Temp difference of [AUTO] mode selection COOL → HEAT, HEAT → COOL

0000: 0 deg to 0010: 10 deg 0003: 3 deg(Ts±1.5)(For setup temperature, reversal of COOL / HEAT by ± (Data value) / 2)

28 Automatic restart of power failure

0000: None 0001: Restart 0000: None

2A Selection of option / error input (CN70)

0000: Filter input0002: None

0001: Alarm input (Air washer, etc.) 0002: None

2E HA terminal (CN61) select

0000: Usual0002: Fire alarm input

0001: Leaving-ON prevention control 0000: Usual(HA terminal)

31 Ventilating fan control 0000: Unavailable 0001: Available 0000: Unavailable

32 TA sensor selection 0000: Body TA sensor 0001: Remote controller sensor 0000: Body TA sensor

33 Temperature unit select 0000: °C (at factory shipment) 0001: °F 0000: °C

48

Toshiba

Page 50: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 49 Tuesday, June 21, 2011 10:41 AM

5d

High-ceiling adjustment(Air flow selection)

1-way cassette (SH)

Compact 4-way cassette

Ceiling

0000: Standard

Built-in filter 4-way cassette0000: Standard filter (factory default)Ceiling0000: Standard filter (factory default)Concealed duct standard0000: Standard filter (factory default)0001: High-performance filter (65 %, 90 %)

Static pressure selection Concealed duct standard0000: Standard (factory default)0001: High static pressure 10003: High static pressure 20006: Low static pressure

Slim Duct0000: Standard (factory default)0001: High static pressure 10003: High static pressure 20006: High static pressure 3

60 Timer setting(wired remote controller)

0000: Available (can be performed) 0001: Unavailable (cannot be performed)

0000: Available

92 External interlock release condition

0000: Operation stopped 0001: Release signal received 0000: Operation stopped

D0Whether the power saving mode can be set by the remote controller

0000: Invalid 0001: Valid 0001: Valid

DN Item Description At shipment

Value Type AP015, AP018 AP024

0000 Standard (factory default) 3.5 m or less 3.8 m or less

0001 High-ceiling (1) 4.0 m or less 4.0 m or less

0003 High-ceiling (3) 4.2 m or less 4.2 m or less

SET DATA Type AP007 to

AP012 AP015 AP018

0000 Standard (factory default) 2.7 m or less 2.9 m or less 3.2 m or less

0002 High-ceiling (2) — 3.2 m or less 3.4 m or less

0003 High-ceiling (3) — 3.5 m or less 3.5 m or less

Value Type AP015 to AP056

0000 Standard (factory default) 3.5 m or less

0001 High-ceiling (1) 4.0 m or less

49

Toshiba

Page 51: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 50 Tuesday, June 21, 2011 10:41 AM

TypeDN code “10”

*1 Default value stored in EEPROM mounted on service P.C. board

Indoor Unit CapacityDN code “11”

*1 Default value stored in EEPROM mounted on service P.C. board

Value Type Model0000 1-way Cassette MMU-AP∗∗∗SH

0001*1 4-way Cassette MMU-AP∗∗∗H

0002 2-way Cassette MMU-AP∗∗∗WH

0003 1-way Cassette (Compact) MMU-AP∗∗∗YH

0004 Concealed Duct Standard MMD-AP∗∗∗BH

0005 Slim Duct MMD-AP∗∗∗SPH (SH)

0006 Concealed Duct High Static Pressure MMD-AP∗∗∗H

0007 Ceiling MMC-AP∗∗∗H

0008 High Wall MMK-AP∗∗∗H

0010 Floor Standing Cabinet MML-AP∗∗∗H

0011 Floor Standing Concealed MML-AP∗∗∗BH

0013 Floor Standing MMF-AP∗∗∗H

0014 Compact 4-way Cassette MMU-AP∗∗∗MH

0016 Fresh Air Intake indoor unit (Duct type) MMD-AP∗∗∗HFE

Value Capacity0000* Invalid

0001 007 type

0003 009 type

0005 012 type

0007 015 type

0009 018 type

0011 024 type

0012 027 type

0013 030 type

0015 036 type

0017 048 type

0018 056 type

0021 072 type

0023 096 type

~ –

50

Toshiba

Page 52: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 51 Tuesday, June 21, 2011 10:41 AM

5-6. Applied control of indoor unit Control system using remote controller interface (TCB-IFCB4E2)Wiring and setting• In the case of group control, the control system functions as long as it is connected to one of the indoor units

(control P.C. board) in the group. If it is desired to access the operation and error statuses of other units, relevant signals must be brought to it from those units individually.

▼ Control items(1) Start / Stop input signal Start / stop of unit(2) In-operation signal Output present while unit in normal operation(3) Error signal Output present while alarm (e.g. serial communication error or operation of protective

device for indoor / outdoor unit) being activated

▼ Wiring diagram of control system using remote controller interface (TCB-IFCB4E2)Input IFCB4E2: No-voltage ON / OFF serial signalOutput No-voltage contact (in-operation and error indication)

Contact capacity: Max. AC 240 V, 0.5 A

ON side Start signal input

OFF side Stop signal input

COM

In-operation signal output

Error signal output

Power source 220-240 V

Indoor control P.C. board

Start / stop inputCOM (GND)

Remote controller disabling / enabling inputIn-operation signal output

COM (+12V)Error signal output

(yellow)

51

Toshiba

Page 53: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 52 Tuesday, June 21, 2011 10:41 AM

▼ Ventilating fan control from remote controller

[Function]• The start / stop operation can be operated from the wired remote controller when air to air heat exchanger

or ventilating fan is installed in the system.• The fan can be operated even if the indoor unit is not operating.• Use a fan which can receive the no-voltage A contact as an outside input signal.• In a group control, the units are collectively operated and they can not be individually operated.

1. OperationHandle a wired remote controller in the following procedure.* Use the wired remote controller during stop of the system.* Be sure to set up the wired remote controller to the header unit. (Same in group control)* In a group control, if the wired remote controller is set up to the header unit, both header and follower units

are simultaneously operable.

1 Push concurrently + + buttons for 4 seconds or more.The unit No. displayed firstly indicates the header indoor unit address in the group control.In this time, the fan of the selected indoor unit turns on.

2 Every pushing button, the indoor unit numbers in group control are displayed successively.In this time, the fan of the selected indoor unit only turns on.

3 Using the setup temp or button, specify the CODE No. 31.

4 Using the timer time or button, select the SET DATA. (At shipment: )The setup data are as follows:

5 Push button. (OK if display goes on.)• To change the selected indoor unit, go to the procedure 2 ).• To change the item to be set up, go to the procedure 3 ).

6 Pushing returns the status to the usual stop status.

2. Wiring

SET DATA Handling of operation of air to air heat exchanger or ventilating fanUnavailable (At shipment)

Available

Compact 4-way Cassette type1-way Cassette type (SH) Concealed Duct Standard typeSlim Duct typeCeiling typeCorresponds up to a relay in which rated current of the operation coil is approx. 75 mAOther type models: Correspond up to a relay in which rated current of the operation coil is approx. 16 mA (Does not correspond to a terminal block type relay on the market.)

Relay (DC12 V, procured locally) Corresponds to the relay up to one that the rated current of the operation coil is approx. 75 mA

Outside control input of fanTo terminal

Note) Determine the cable length between the indoor control P.C. board and the relay within 2 m.

model :

Indoor control P.C. board

52

Toshiba

Page 54: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 53 Tuesday, June 21, 2011 10:41 AM

▼ Leaving-ON prevention control

[Function]• This function controls the indoor units individually. It is connected with cable to the control P.C. board of the

indoor unit.• In a group control, it is connected with cable to the indoor unit (Control P.C. board), and the CODE No. 2E

is set to the connected indoor unit.• It is used when the start operation from outside if unnecessary but the stop operation is necessary.• Using a card switch box, card lock, etc, the forgotten-OFF of the indoor unit can be protected.• When inserting a card, start / stop operation from the remote controller is allowed.• When taking out a card, the system stops if the indoor unit is operating and start / stop operation from the

remote controller is forbidden.

1. Control items1) Outside contact ON: The start / stop operation from the remote controller is allowed.

(Status that card is inserted in the card switch box)2) Outside contact OFF: If the indoor unit is operating, it is stopped forcedly.

(Start / Stop prohibited to remote controller)(Status that card is taken out from the card switch box)

* When the card switch box does not perform the above contact operation, convert it using a relay with b contact.

2. OperationHandle the wired remote controller switch in the following procedure.* Use the wired remote controller switch during stop of the system.

1 Push concurrently + + buttons for 4 seconds or more.

2 Using the setup temp or button, specify the CODE No. .

3 Using the timer time or button, set to the SET DATA.

4 Push button.

5 Push button. (The status returns to the usual stop status.)

3. Wiring

▼ Power peak-cut from indoor unitWhen the relay is turned on, a forced thermostat-OFF operation starts.

Relay (procured locally)

Power supply

Note) Determine the cable length between the indoor control P.C. board and the relay within 2 m.Outside contact (Card switch box, etc: Procured locally)

* In the figure, the contact indicates a status that the card is taken out.

Indoor control P.C. board

Note) Determine the cable length between the indoor or outdoor control P.C. board and the relay within 2 m.

Relay (procured locally)

Relay coil signal

Indoor control P.C. board

(2P plug: RED)

• Wiring example

53

Toshiba

Page 55: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 54 Tuesday, June 21, 2011 10:41 AM

Manual address setting using the remote controllerProcedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed and outdoor wiring has not been started (manual setting using the remote controller)

▼ Wiring example of 2 refrigerant lines

In the example above, disconnect the remote controller connections between the indoor units and connect a wired remote controller to the target unit directly before address setting.

Pair the indoor unit to set and the remote controller one-to-one.

Turn on the power.

1 Push and hold the , , and buttons at the same time for more than 4 seconds.LCD starts flashing.

Line (system) address 1 1 1 2 2

Indoor unit address 1 2 3 1 2

Group address 1Header unit

2Follower unit

2Follower unit

2Follower unit

2Follower unit

Outdoor unit

Outdoor unit

Remote controller

Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 1 Indoor unit 2

Refrigerant line 1 Refrigerant line 2

SET DATA CODE No.

54

Toshiba

Page 56: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 55 Tuesday, June 21, 2011 10:41 AM

<Line (system) address>

2 Push the TEMP. / buttons repeatedly to set the CODE No. to .

3 Push the TIME / buttons repeatedly to set a system address.(Match the address with the address on the interface P.C. board of the header outdoor unit in the same refrigerant line.)

4 Push button.(It is OK if the display turns on.)

<Indoor unit address>

5 Push the TEMP. / buttons repeatedly to set the CODE No. to .

6 Push the TIME / buttons repeatedly to set an indoor unit address.

7 Push the button.(It is OK if the display turns on.)

<Group address>

8 Push the TEMP. / buttons repeatedly to set the CODE No. to .

9 Push the TIME / buttons repeatedly to set a group address. If the indoor unit is individual, set the address to ; header unit, ; follower unit, .

10 Push the button.(It is OK if the display turns on.)

11 Push the button.The address setting is complete.( flashes. You can control the unit after has disappeared.)

NOTE

1. Do not use address numbers 29 or 30 when setting system addresses using the remote controller.These 2 address numbers cannot be used on outdoor units and the CODE No. [E04] (Indoor / outdoor communication error) will appear if they are mistakenly used.

2. If you set addresses to indoor units in 2 or more refrigerate lines manually using the remote controller and will control them centrally, set the header outdoor unit of each line as below.• Set a system address for the header outdoor unit of each line with SW13 and 14 of their interface P.C. boards.• Turn off dip switch 2 of SW30 on the interface P.C. boards of all the header outdoor units connected to the

same central control, except the unit that has the lowest address. (For unifying the termination of the wiring for the central control of indoor and outdoor units)

• Connect the relay connectors between the [U1, U2] and [U3, U4] terminals on the header outdoor unit of each refrigerate line.

• After finishing all the settings above, set the address of the central control devices. (For the setting of the central control address, refer to the installation manuals of the central control devices.)

Individual : 0000Header unit : 0001 In case of group

controlFollower unit : 0002

55

Toshiba

Page 57: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 56 Tuesday, June 21, 2011 10:41 AM

Confirming the indoor unit addresses and the position of an indoor unit using the remote controller

◆Confirming the numbers and positions of indoor units

To see the indoor unit address of an indoor unit which you know the position of

▼ When the unit is individual (the indoor unit is paired with a wired remote controller one-to-one), or it is a group-controlled one.

(Execute it while the units are running.)

1 Push the button if the units stop.

2 Push the button (left side of the button).A unit numbers is indicated on the LCD (it will disappear after a few seconds). The indicated number shows the system address and indoor unit address of the unit. When 2 or more indoor units are connected to the remote controller (group-controlled units), a number of other connected units appears each time you push the button (left side of the button).

Starts running

56

Toshiba

Page 58: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 57 Tuesday, June 21, 2011 10:41 AM

To find an indoor unit’s position from its address

▼ When checking unit numbers controlled as a group

(Execute it while the units are stopped.)The indoor unit numbers in a group are indicated one after another. The fan and louvers of the indicated units are activated.

1 Push and hold the and buttons at the same time for more than 4 seconds.• appears on UNIT No. on the LCD display.• The fans and louvers of all the indoor units in the group are activated.

2 Push the button (left side of the button). Each time you push the button, the indoor unit numbers are indicated one after another.• The first-indicated unit number is the address of the header unit.• Only the fan and louvers of the indicated indoor unit are activated.

3 Push the button to finish the procedure.All the indoor units in the group stop.

Stop

57

Toshiba

Page 59: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 58 Tuesday, June 21, 2011 10:41 AM

▼ To check all the indoor unit addresses using an arbitrary wired remote controller.(When communication wirings of 2 or more refrigerant lines are interconnected for central control)

(Execute it while the units are stopped.)You can check indoor unit addresses and positions of the indoor units in a single refrigerant line.When an outdoor unit is selected, the indoor unit numbers of the refrigerant line of the selected unit are indicated one after another and the fan and louvers of the indicated indoor units are activated.

1 Push and hold the TIME and buttons at the same time for more than 4 seconds.At first, the line 1 and CODE No. (Address Change) are indicated on the LCD display. (Select an outdoor unit.)

2 Push the (left side of the button) and buttons repeatedly to select a system address.

3 Push the button to confirm the system address selection.• The address of an indoor unit connected to the selected refrigerant line is indicated on the LCD display and

its fan and louvers are activated.

4 Push the button (left side of the button). Each time you push the button, the indoor unit numbers of the selected refrigerant line are indicated one after another.• Only the fan and louvers of the indicated indoor unit are activated.

◆To select another system address5 Push the CL button to return to step 2.

• After returning to step 2, select another system address and check the indoor unit addresses of the line.

6 Push the button to finish the procedure.

58

Toshiba

Page 60: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 59 Tuesday, June 21, 2011 10:41 AM

◆Changing the indoor unit address using a remote controller

To change an indoor unit address using a wired remote controller.

▼ The method to change the address of an individual indoor unit (the indoor unit is paired with a wired remote controller one-to-one), or an indoor unit in a group.(The method is available when the addresses have already been set automatically.)

(Execute it while the units are stopped.)

1 Push and hold the , , and buttons at the same time for more than 4 seconds.(If 2 or more indoor units are controlled in a group, the first indicated UNIT No. is that of the head unit.)

2 Push the button (left side of the button) repeatedly to select an indoor unit number to change if 2 or more units are controlled in a group. (The fan and louvers of the selected indoor unit are activated.)(The fan of the selected indoor unit is turned on.)

3 Push the TEMP. / buttons repeatedly to select for CODE No..

4 Push the TIME / buttons repeatedly to change the value indicated in the SET DATA section to that you want.

5 Push the button.

6 Push the button (left side of the button) repeatedly to select another indoor UNIT No. to change.Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.

7 Push the button (left side of the button) to check the changed addresses.

8 If the addresses have been changed correctly, push the button to finish the procedure.

Finish

59

Toshiba

Page 61: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 60 Tuesday, June 21, 2011 10:41 AM

▼ To change all the indoor unit addresses using an arbitrary wired remote controller.(The method is available when the addresses have already been set automatically.)

(When communication wirings of 2 or more refrigerant lines are interconnected for central control)

NOTEYou can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.

* Enter the address check / change mode and change the addresses.

If no number appears on UNIT No., no outdoor unit exists on the line. Push button and select another line following step 2.

(Execute it while the units are stopped.)

1 Push and hold the TIME / buttons at the same time for more than 4 seconds.At first, the line 1 and CODE No. (Address Change) are indicated on the LCD display.

2 Push (left side of the button) and buttons repeatedly to select a system address.

3 Push the button.• The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD

display and the fan and louvers of the unit are activated.At first, the current indoor unit address is displayed in SET DATA.(No system address is indicated.)

Cancels the line selection

Press to finish setting.

Finish

60

Toshiba

Page 62: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 61 Tuesday, June 21, 2011 10:41 AM

4 Push the TIME / buttons repeatedly to change the value of the indoor unit address in SET DATA.Change the value in SET DATA to that of a new address.

5 Push the button to confirm the new address on SET DATA.

6 Push the button (left side of the button) repeatedly to select another address to change. Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one after another. Only the fan and louvers of the selected indoor unit are activated. Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.

7 Push the button.(All the segments on the LCD display light up.)

8 Push the button to finish the procedure.

61

Toshiba

Page 63: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 62 Tuesday, June 21, 2011 10:41 AM

◆Error clearing function

How to clear the error using the wired remote controller

▼ Clearing an error of the outdoor unitClear the currently detected outdoor unit for each refrigerant line to which the indoor unit controlled by the remote controller is connected. (The indoor unit error is not cleared.)Use the service monitoring function of the remote controller.

1 Push and hold the , and for 4 seconds or longer to enter the service monitoring mode.

2 Push the button to set CODE No. to “ ”.

3 The display in A of the following figure counts down as follows at 5-second intervals: “ ” “ ” “ ” “ ” “ ” “ ”.The error is cleared when “ ” appears.However, the display counts down from “ ” again.

4 Push the to return the display to normal.

▼ Clearing an error of the indoor unitPush the button on the remote controller.(Only the error of the indoor unit controlled by the remote controller will be cleared.)

62

Toshiba

Page 64: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 63 Tuesday, June 21, 2011 10:41 AM

◆Monitoring function of wired remote controller

The following monitoring function is available if the remote controller of RBC-ATM32E is used.

▼ ContentEnter the service monitoring mode using the remote controller to check the sensor temperature or operation status of the remote controller, indoor unit, and outdoor unit.

1 Push and hold the , and for 4 seconds or longer to enter the service monitoring mode. The service monitor lights up. The temperature of CODE No. appears at first.

2 Push the button to change to CODE No. of the item to monitor. Refer to the following table for CODE No.

3 Push the left part of the button to change to the item to monitor. Monitor the sensor temperature or operation status of the indoor unit and outdoor unit in the refrigerant line

4 Push the to return the display to normal.

63

Toshiba

Page 65: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 64 Tuesday, June 21, 2011 10:41 AM

◆Target outdoor unit (SMMS, SHRM, Mini-SMMS – Series 1 – 2)

*1 In the case of group connection, only the header indoor unit data can be displayed.*2 01 ... Only compressor 1 is on

10 ... Only compressor 2 is on11 ... Both compressor 1 and 2 are on

*3 The upper digit of CODE No. indicates the outdoor unit No.U1 outdoor unit (Header unit)U2 outdoor unit (follower unit 1)U3 outdoor unit (follower unit 2)U4 outdoor unit (follower unit 3)

CODE No. Data Format Unit Remote controller display exampleIndoor unit data

00 Room temperature (in control) *1 ×1 °C

[0024]=24 °C

01 Room temperature (Remote controller) ×1 °C02 Air Temperature (TA) ×1 °C03 Coil Temperature (TCJ) ×1 °C04 Coil Temperature (TC2) ×1 °C05 Coil Temperature (TC1) ×1 °C08 PMV ×1 pls [0050]=500 pls

System data

0A Number of connected indoor units ×1 – [0048]=480B Total horse power of connected indoor units ×1 HP [0415]=41.5 HP0C Number of connected outdoor units ×1 – [0004]=40D Total horse power of outdoor units ×1 HP [0420]=42 HP

CODE No.Data Format Unit Remote controller display example

U1 U2 U3 U4Individual data 1 of outdoor unit *3

10 20 30 40 Discharge temperature of compressor 1 (Td1) ×1 °C

[0024]=24 °C11 21 31 41 Discharge temperature of compressor 2

(Td2) ×1 °C

12 22 32 42 Detection pressure of high-pressure sensor (Pd) ×1 MPa

[0123]=1.23 MPa13 23 33 43 Detection pressure of low-pressure sensor

(Ps) ×1 MPa

14 24 34 44 Suction Temperature (TS) ×1 °C

[0024]=24 °C15 25 35 45 Coil Temperature 1 (TE) ×1 °C16 26 36 46 Liquid Temperature (TL) ×1 °C17 27 37 47 Outdoor Temperature (TO) ×1 °C18 28 38 48 Low-pressure saturation temperature (TU) ×1 °C19 29 39 49 Current of compressor 1 (I1) ×1 A

[0135]=13.5 A1A 2A 3A 4A Current of compressor 2 (I2) ×1 A1B 2B 3B 4B PMV1 + 2 ×1 pls [0050]=500 pls1C 2C 3C 4C PMV3 ×1 pls [0050]=500 pls1D 2D 3D 4D Compressor 1, 2 ON/OFF *2 –1E 2E 3E 4E Outdoor fan mode ×1 – [0031]=Mode 311F 2F 3F 4F Horse power of outdoor unit ×1 HP [0016]=16HP

64

Toshiba

Page 66: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 65 Tuesday, June 21, 2011 10:41 AM

◆Target outdoor unit (SMMS-i – Series 4)

*1 The TF/TSA/TOA sensors are equipped only with some types of indoor units. The data does not appear for other types.*2 In the case of group connection, only the header indoor unit data can be displayed.*3 The upper digit of CODE No. indicates the outdoor unit No.*4 [(The upper digit of CODE No.) – 4] indicates the outdoor unit No.

1✽, 5✽ ... U1 outdoor unit (Header unit)2✽, 6✽ ... U2 outdoor unit (follower unit 1)3✽, 7✽ ... U3 outdoor unit (follower unit 2)4✽, 8✽ ... U4 outdoor unit (follower unit 3)

*5 Only CODE No. 5✽ of U1 outdoor unit (Header unit) is displayed.

CODE No. Data Format Unit Remote controller display exampleIndoor unit data *2

00 Room temperature (in control) ×1 °C

[0024]=24 °C

01 Room temperature (Remote controller) ×1 °C02 Air Temperature (TA) ×1 °C03 Coil Temperature (TCJ) ×1 °C04 Coil Temperature (TC2) ×1 °C05 Coil Temperature (TC1) ×1 °C06 Discharge temperature (TF) *1 ×1 °C08 PMV ×1/10 pls [0150]=1500 pls

F9 Air Suction Temperature of direct expansion coil (TSA) *1 ×1 °C

[0024]=24 °CFA Outdoor Air Temperature (TOA) *1 ×1 °C

System data

0A Number of connected indoor units ×1 – [0048]=480B Total horse power of connected indoor units ×10 HP [0415]=41.5HP0C Number of connected outdoor units ×1 – [0004]=40D Total horse power of outdoor units ×10 HP [0420]=42HP

CODE No.Data Format Unit Remote controller display example

U1 U2 U3 U4Individual data 1 of outdoor unit *3

10 20 30 40 Detection pressure of high-pressure sensor (Pd) ×100 MPa

[0123]=1.23 MPa11 21 31 41 Detection pressure of low-pressure sensor

(Ps) ×100 MPa

12 22 32 42 Discharge temperature of compressor 1 (Td1) ×1 °C

[0024]=24 °C

13 23 33 43 Discharge temperature of compressor 2 (Td2) ×1 °C

14 24 34 – Discharge temperature of compressor 3 (Td3) ×1 °C

15 25 35 45 Suction Temperature (TS) ×1 °C16 26 36 46 Coil Temperature 1 (TE1) ×1 °C17 27 37 – Coil Temperature 2 (TE2) ×1 °C18 28 38 48 Liquid Temperature (TL) ×1 °C19 29 39 49 Outdoor Temperature (TO) ×1 °C1A 2A 3A 4A PMV1 + 2 ×1 pls

[0050]=500 pls1B 2B 3B – PMV4 ×1 pls1C 2C 3C 4C Current of compressor 1 (I1) ×10 A

[0135]=13.5 A1D 2D 3D 4D Current of compressor 2 (I2) ×10 A1E 2E 3E – Current of compressor 3 (I3) ×10 A1F 2F 3F 4F Outdoor fan current (IFan) ×10 A

65

Toshiba

Page 67: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 66 Tuesday, June 21, 2011 10:41 AM

*1 The TF / TSA / TOA sensors are equipped only with some types of indoor units. The data does not appear for other types.*2 In the case of group connection, only the header indoor unit data can be displayed.*3 The upper digit of CODE No. indicates the outdoor unit No.*4 [(The upper digit of CODE No.) – 4] indicates the outdoor unit No.

1✽, 5✽ ... U1 outdoor unit (Center unit)2✽, 6✽ ... U2 outdoor unit (terminal unit 1)3✽, 7✽ ... U3 outdoor unit (terminal unit 2)4✽, 8✽ ... U4 outdoor unit (terminal unit 3)

*5 Only CODE No. 5✽ of U1 outdoor unit (Center unit) is displayed.

◆LED display of circuit board1.D501 (Red)

• Lights up when the power is turned on (Microcomputer works)• Blinks at 1-second intervals (0.5-second): No EEPROM, or writing error• Blinks at 10-second intervals (5-second): No DISP mode• Blinks at 2-second intervals (1-second): Function change being set (EEPROM)

2.D403 (Red)• Lights up (on hardware) when the power is supplied to the remote controller

3.D503 (Yellow): Indoor/Outdoor central control• Lights up for the first half 5 seconds while communicating with a central control device• Blinks for the second half 5 seconds at 0.2-second intervals (0.1-second) while communicating with

the outdoor unit4.D504 (Green): Remote controller communication

• The group header unit lights up for the first half 5 seconds while communicating with the remote controller

• Blinks for the second half 5 seconds at 0.2-second intervals (0.1-second) during communication between group indoor header and follower

CODE No.Data Format Unit Remote controller display example

U1 U2 U3 U4Individual data 2 of outdoor unit *4

50 60 70 80 Rotation of compressor 1 ×10 rps[0642]=64.2 rps51 61 71 81 Rotation of compressor 2 ×10 rps

52 62 72 – Rotation of compressor 3 ×10 rps53 63 73 83 Outdoor fan mode ×1 Mode [0058]=Mode 58

54 64 74 84 Heat sink temperature of compressor IPDU1 ×1 °C

[0024]=24 °C55 65 75 85 Heat sink temperature of compressor

IPDU2 ×1 °C

56 66 76 – Heat sink temperature of compressor IPDU3 ×1 °C

57 67 77 87 Heat sink temperature of outdoor fan IPDU ×1 °C

58 – – – In heat/cool collecting control *5 0: Normal1: In collecting control

[0010] = In heat collecting control[0001] = In cool collecting control

59 – – – Pressure release *5

0: Normal1: In release control

[0010] = In pressure release control

5A – – – Discharge temperature release *5 [0001] = In discharge temperature release control

5B – – –

Terminal unit release (U2 / U3 / U4 outdoor unit) *5

[0100] = In U2 outdoor unit release control[0010] = In U3 outdoor unit release control[0001] = In U4 outdoor unit release control

5F 6F 7F 8F Horse power of outdoor unit ×1 HP [0016]=16HP

66

Toshiba

Page 68: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 67 Tuesday, June 21, 2011 10:41 AM

6 Troubleshooting6-1. Overview(1) Before engaging in troubleshooting

(a) Applicable modelsAll Super Module Multi (SMMS, SHRM, Mini-SMMS, SMMS-i) models.(Indoor units: MMO-APOOO, Outdoor units: MMY-MAPOOOO∗, MCY-MAPOOOHT∗)

(b) Tools and measuring devices required• Screwdrivers (Philips, flat head), spanners, long-nose pliers, nipper, pin to push reset switch, etc.• Multimeter, thermometer, pressure gauge, etc.

(c) Things to check prior to troubleshooting (behaviors listed below are normal)

(2) Troubleshooting procedureWhen a fault occurs, proceed with troubleshooting in accordance with the procedure shown below.

NOTERather than a genuine fault (see the List of Check Codes below), the problem could have been caused by a microprocessor malfunction attributable to a poor quality of the power source or an external noise. Check for possible noise sources, and shield the remote controller wiring and signal wires as necessary.

NO. Behavior Possible cause

1

A compressor would not start • Could it just be the 3-minute delay period (3 minutes after compressor shutdown)?

• Could it just be the air conditioner having gone thermo OFF?• Could it just be the air conditioner operating in fan mode or put on the timer?• Could it just be the system going through initial communication?

2 An indoor fan would not start • Could it just be cold air discharge prevention control, which is part of heating?

3An outdoor fan would not start or would change speed for no reason

• Could it just be cooling operation under low outside temperature conditions?

• Could it just be defrosting operation?

4 An indoor fan would not stop • Could it just be the elimination of residual heat being performed as part of the air conditioner shutdown process after heating operation?

5 The air conditioner would not respond to a start / stop command from a remote controller

• Could it just be the air conditioner operation under external or remote controller?

Investigate check code displayed on interface P.C. board of header unit

Investigate check code displayed on interface P.C. board of relevant follower unit

Check fault site or faulty part

Fault

"E28" error

Any other fault

67

Toshiba

Page 69: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 68 Tuesday, June 21, 2011 10:41 AM

6-2. Troubleshooting methodThe remote controllers (main remote controller and central control remote controller) and the interface P.C. board of an outdoor unit are provided with an LCD display (remote controller) or a 7-segment display (outdoor interface P.C. board) to display operational status. Using this self-diagnosis feature, the fault site / faulty part may be identified in the event of a fault by following the method described below.

The list below summarizes check codes detected by various devices. Analyze the check code according to where it is displayed and work out the nature of the fault in consultation with the list.• When investigating a fault on the basis of a display provided on the indoor remote controller or TCC-LINK central control remote controller -

See the “TCC-LINK remote controller or main remote controller display” section of the list.• When investigating a fault on the basis of a display provided on an outdoor unit - See the “Outdoor 7-segment display” section of the list.• When investigating a fault on the basis of a display provided on the AI-NET central control remote controller - See the “AI-NET central control

display” section of the list.• When investigating a fault on the basis of a wireless remote controller-controlled indoor unit - See the “Light sensor indicator light block”

section of the list.

List of check codes (indoor unit)(Error detected by indoor unit)

Check code Display of receiving unit

Typical fault site Description of errorTCC-LINK

central control or main remote

controller display

Outdoor 7-segment display Indicator light block

Sub-code Flash

E03 – – Indoor-remote controller periodic communication error

Communication from remote controller or network adaptor has been lost (so has central control communication).

E04 – – Indoor-outdoor periodic communication error Signals are not being received from outdoor unit.

E08 E08 Duplicated indoor address Duplicated indoor address Indoor unit detects address identical to its own.

E10 – – Indoor inter-MCU communication error

MCU communication between main controller and motor microcontroller is faulty.

E18 – –Error in periodic communication between indoor header and follower unit

Periodic communication between indoor header and follower units cannot be maintained.

F01 – – ALT Indoor heat exchanger temperature sensor (TCJ) error

Heat exchanger temperature sensor (TCJ) has been open / short-circuited.

F02 – – ALT Indoor heat exchanger temperature sensor (TC2) error

Heat exchanger temperature sensor (TC2) has been open / short-circuited.

F03 – – ALT Indoor heat exchanger temperature sensor (TC1) error

Heat exchanger temperature sensor (TC1) has been open / short-circuited.

F10 – – ALT Ambient temperature sensor (TA) error Ambient temperature sensor (TA) has been open / short-circuited.

F11 – – ALT Discharge temperature sensor (TF) error

Discharge temperature sensor (TF) has been open / short-circuited.

F29 – – SIM P.C. board or other indoor error Indoor EEPROM is abnormal (some other error may be detected).

L03 – – SIM Duplicated indoor group header unit There is more than one header unit in group.

L07 – – SIM Connection of group control cable to stand-alone indoor unit

There is at least one stand-alone indoor unit to which group control cable is connected.

L08 L08 – SIM Indoor group address not set Address setting has not been performed for one or more indoor units (also detected at outdoor unit end).

L09 – – SIM Indoor capacity not set Capacity setting has not been performed for indoor unit.

L20 – – SIM Duplicated central control address There is duplication in central control address setting.

L30 L30 Detected indoor unit No. SIM Indoor external error input (interlock) Unit shutdown has been caused by external error input (CN80).

P01 – – ALT Indoor AC fan error Indoor AC fan error is detected (activation of fan motor thermal relay).

P10 P10 Detected indoor unit No. ALT Indoor overflow error Float switch has been activated.

P12 – – ALT Indoor DC fan error Indoor DC fan error (e.g. overcurrent or lock-up) is detected.

P31 – – ALT Other indoor unit error Follower unit cannot be operated due to header unit alarm (E03 / L03 / L07 / L08).

IPDU: Intelligent Power Drive Unit (Inverter P.C. board): Lighting, : Flashing, : Goes off

ALT.: Flashing is alternately when there are two flashing LEDSIM: Simultaneous flashing when there are two flashing LED

68

Toshiba

Page 70: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 69 Tuesday, June 21, 2011 10:41 AM

(Error detected by main remote controller)

(Error detected by central control device)

Note: The same error, e.g. a communication error, may result in the display of different check codes depending on the device that detects it. Moreover, check codes detected by the main remote controller / central control device do not necessarily have a direct impact on air conditioner operation.

Check code Display of receiving unit

Typical fault site Description of errorMain remote

controller

Outdoor 7-segment display Indicator light block

Sub-code Flash

E01 – –No master remote controller, faulty remote controller communication (reception)

Signals cannot be received from indoor unit; master remote controller has not been set (including two remote controller control).

E02 – – Faulty remote controller communication (transmission) Signals cannot be transmitted to indoor unit.

E09 – – Duplicated master remote controller

Both remote controllers have been set as master remote controller in two remote controller control (alarm and shutdown for header unit and continued operation for follower unit)

Check code Display of receiving unit

Typical fault site Description of errorTCC-LINK central control

Outdoor 7-segment display Indicator light block

Sub-code Flash

C05 – –

No indication (when main remote controller also in use)

Faulty central control communication (transmission)

Central control device is unable to transmit signal due to duplication of central control device (AI-NET).

C06 – – Faulty central control communication (reception) Central control device is unable to receive signal.

– – – Multiple network adapters Multiple network adapters are connected to remote controller communication line (AI-NET).

C12 – – –Blanket alarm for general-purpose device control interface

Device connected to general-purpose device control interface for TCC-LINK / AI-NET is faulty.

P30 – – As per alarm unit (see above)

Group control follower unit error

Group follower unit is faulty (unit No. and above detail [∗∗∗] displayed on main remote controller)

69

Toshiba

Page 71: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 70 Tuesday, June 21, 2011 10:41 AM

List of check codes (outdoor unit)(Errors detected by SMMS outdoor interface - typical examples)

Check code Display of receiving unit

Typical fault site Description of errorOutdoor 7-segment display TCC-LINK

central control or main remote

controller display

Indicator light block

Sub-code Flash

E06 Number of indoor units from which signal is received normally E06 Dropping out of indoor unit

Indoor unit initially communicating normally fails to return signal (reduction in number of indoor units connected).

E07 – (E04)Indoor-outdoor communication circuit error

Signal cannot be transmitted to indoor units (➝ indoor units left without communication from outdoor unit).

E08 Duplicated indoor address (E08) Duplicated indoor address More than one indoor unit is assigned same address (also detected at indoor unit end).

E1201: Indoor-outdoor communication02: Outdoor-outdoor communication

E12 Automatic address starting error

• Indoor automatic address setting is started while automatic address setting for equipment in other refrigerant line is in progress.

• Outdoor automatic address setting is started while automatic address setting for indoor units is in progress.

E15 – E15Indoor unit not found during automatic address setting

Indoor unit fails to communicate while automatic address setting for indoor units is in progress.

E16 00: Overloading01: Number of units connected E16 Too many indoor units

connected / overloading

Combined capacity of indoor units is too large (more than 135 % of combined capacity of outdoor units).

E19 00: No header unit02: Two or more header units E19 Error in number of outdoor

header unitsThere is no or more than one outdoor header unit in one refrigerant line.

E20

01: Connection of outdoor unit from other refrigerant line02: Connection of indoor unit from other refrigerant line

E20

Connection to other refrigerant line found during automatic address setting

Indoor unit from other refrigerant line is detected while indoor automatic address setting is in progress.

E23 – E23Outdoor-outdoor communication transmission error

Signal cannot be transmitted to other outdoor units.

E25 – E25 Duplicated follower outdoor address

There is duplication in outdoor addresses set manually.

E26 Address of outdoor unit from which signal is not received normally E26 Dropping out of outdoor

unit

Follower outdoor unit initially communicating normally fails to do so (reduction in number of follower outdoor units connected).

E28 Detected outdoor unit No. E28 Outdoor follower unit errorOutdoor header unit detects fault relating to follower outdoor unit (detail displayed on follower outdoor unit).

E31 E31 IPDU communication error There is no communication between IPDUs (P.C. boards) in inverter box.

F04 – F04 ALTOutdoor discharge temperature sensor (TD1) error

Outdoor discharge temperature sensor (TD1) has been open / short-circuited.

F05 – F05 ALTOutdoor discharge temperature sensor (TD2) error

Outdoor discharge temperature sensor (TD2) has been open / short-circuited.

F06 01: TE102: TE2 F06 ALT

Outdoor heat exchanger temperature sensor (TE1, TE2) error

Outdoor heat exchanger temperature sensors (TE1, TE2) have been open / short-circuited.

F07 – F07 ALT Outdoor liquid temperature sensor (TL) error

Outdoor liquid temperature sensor (TL) has been open / short-circuited.

F08 – F08 ALTOutdoor outside air temperature sensor (TO) error

Outdoor outside air temperature sensor (TO) has been open / short-circuited.

F11 – F11

IPDU: Intelligent Power Drive Unit (Inverter P.C. board): Lighting, : Flashing, : Goes off

ALT.: Flashing is alternately when there are two flashing LEDSIM: Simultaneous flashing when there are two flashing LED

70

Toshiba

Page 72: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 71 Tuesday, June 21, 2011 10:41 AM

F12 – F12 ALTOutdoor suction temperature sensor (TS1) error

Outdoor suction temperature sensor (TS1) has been open / short-circuited.

F1301: Compressor 102: Compressor 203: Compressor 3

F13 ALTOutdoor IGBT built-in temperature sensor (TH) error

Open-circuit or short-circuit of the outdoor IGBT built-in temperature sensor (TH) was detected.

F15 – F15 ALTOutdoor temperature sensor (TE1, TL) wiring error

Wiring error in outdoor temperature sensors (TE1, TL) has been detected.

F16 – F16 ALT Outdoor pressure sensor (Pd, Ps) wiring error

Wiring error in outdoor pressure sensors (Pd, Ps) has been detected.

F22 – F22 ALTOutdoor discharge temperature sensor (TD3) error

Outdoor discharge temperature sensor (TD3) has been open / short-circuited.

F23 – F23 ALT Low pressure sensor (Ps) error Output voltage of low pressure sensor (Ps) is zero.

F24 – F24 ALT High pressure sensor (Pd) error

Output voltage of high pressure sensor (Pd) is zero or provides abnormal readings when compressors have been turned off.

F31 – F31 SIM Outdoor EEPROM errorOutdoor EEPROM is faulty (alarm and shutdown for header unit and continued operation for follower unit)

H0101: Compressor 102: Compressor 203: Compressor 3

H01 Compressor breakdown Overcurrent of the inverter current (Idc) detection circuit was detected.

H0201: Compressor 102: Compressor 203: Compressor 3

H02 Compressor error (Lock) Compressor lock was detected.

H0301: Compressor 102: Compressor 203: Compressor 3

H03 Current detection circuit error

Current error was detected while the compressor was stopped.

H04 – H04 Compressor 1 case thermo activation

Compressor 1 case thermo was activated for protection.

H05 – H05Outdoor discharge temperature sensor (TD1) wiring error

Wiring / installation error or detachment of outdoor discharge temperature sensor (TD1) has been detected.

H06 – H06 Activation of low-pressure protection

Low pressure (Ps) sensor detects abnormally low operating pressure.

H07 – H07 Low oil level protection Temperature sensor for oil level detection (TK1-5) detects abnormally low oil level.

H08

01: TK1 sensor error02: TK2 sensor error03: TK3 sensor error04: TK4 sensor error05: TK5 sensor error

H08Error in temperature sensor for oil level detection (TK1-5)

Temperature sensor for oil level detection (TK1-5) has been open / short-circuited.

H14 – H14 Compressor 2 case thermo activation

Compressor 2 case thermo was activated for protection.

H15 – H15Outdoor discharge temperature sensor (TD2) wiring error

Wiring / installation error or detachment of outdoor discharge temperature sensor (TD2) has been detected.

H16

01: TK1 oil circuit error02: TK2 oil circuit error03: TK3 oil circuit error04: TK4 oil circuit error05: TK5 oil circuit error

H16 Oil level detection circuit error

No temperature change is detected by temperature sensor for oil level detection (TK1-5) despite compressor having been started.

H25 – H25Outdoor discharge temperature sensor (TD3) wiring error

Wiring / installation error or detachment of outdoor discharge temperature sensor (TD3) has been detected.

L04 – L04 SIM Duplicated outdoor refrigerant line address

Identical refrigerant line address has been assigned to outdoor units belonging to different refrigerant piping systems.

L06Number of priority indoor units(check code L05 or L06 depending on individual unit)

L05 SIMDuplicated priority indoor unit (as displayed on priority indoor unit)

More than one indoor unit has been set up as priority indoor unit.

L06 SIM

Duplicated priority indoor unit (as displayed on indoor unit other than priority indoor unit)

More than one indoor unit has been set up as priority indoor unit.

Check code Display of receiving unit

Typical fault site Description of errorOutdoor 7-segment display TCC-LINK

central control or main remote

controller display

Indicator light block

Sub-code Flash

71

Toshiba

Page 73: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 72 Tuesday, June 21, 2011 10:41 AM

MG-CTT: Magnet contactor

L08 – (L08) SIM Indoor group address not set

Address setting has not been performed for one or more indoor units (also detected at indoor end).

L10 – L10 SIM Outdoor capacity not set Outdoor unit capacity has not been set (after P.C. board replacement).

L17 – L17 SIM Outdoor model incompatibility error

Old model outdoor unit (prior to 3 series) has been connected.

L18 – L18 SIM FS (Flow Selector) unit error

Cooling / heating cycle error resulting from piping error is detected.

L28 – L28 SIM Too many outdoor units connected

More than four outdoor units have been connected.

L29

SMMS (Series 1)01: A3-IPDU1 error02: A3-IPDU2 error03: A3-IPDU1/A3-IPDU2 error04: Fan IPDU error05: A3-IPDU1

+ Fan IPDU error06: A3-IPDU2

+ Fan IPDU error07: All IPDU error

SMMS-i (Series 4)L29 SIM Error in number of IPDUs There are insufficient number of IPDUs (P.C.

boards) in inverter box.

L30 Detected indoor unit No. (L30) SIM Indoor external error input (interlock)

Indoor unit has been shut down for external error input in one refrigerant line (detected by indoor unit).

P03 – P03 ALT Outdoor discharge (TD1) temperature error

Outdoor discharge temperature sensor (TD1) has detected abnormally high temperature.

P0401: Compressor 102: Compressor 203: Compressor 3

P04 ALT High-pressure SW activation High-pressure SW was activated.

P05

00: Open phase detected

P05 ALT

Open phase / power failureOpen phase is detected when power is turned on.Inverter DC voltage is too high (overvoltage) or too low (undervoltage).

01: Compressor 102: Compressor 203: Compressor 3

Inverter DC voltage (Vdc) errorMG-CTT error

P0701: Compressor 102: Compressor 203: Compressor 3

P07 ALT Heat sink overheating error

Temperature sensor built into IGBT (TH) detects overheating.

P10 Indoor unit No. detected (P10) ALT Indoor unit overflowIndoor unit has been shutdown in one refrigerant line due to detection of overflow (detected by indoor unit).

P13 – P13 ALT Outdoor liquid backflow detection error

State of refrigerant cycle circuit indicates liquid backflow operation.

P15 01: TS condition02: TD condition P15 ALT Gas leak detection

Outdoor suction temperature sensor (TS1) detects sustained and repeated high temperatures that exceed standard value.

P17 – P17 ALT Outdoor discharge (TD2) temperature error

Outdoor discharge temperature sensor (TD2) detects abnormally high temperature.

P18 – P18 ALT Outdoor discharge (TD3) temperature error

Outdoor discharge temperature sensor (TD3) detects abnormally high temperature.

P19 Outdoor unit No. detected P19 ALT 4-way valve reversing error

Abnormality in refrigerating cycle is detected during heating operation.

P20 – P20 ALT Activation of high-pressure protection

High pressure (Pd) sensor detects high pressure that exceeds standard value.

Check code Display of receiving unit

Typical fault site Description of errorOutdoor 7-segment display TCC-LINK

central control or main remote

controller display

Indicator light block

Sub-code Flash

72

Toshiba

Page 74: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 73 Tuesday, June 21, 2011 10:41 AM

(Errors detected by IPDU featuring in SMMS standard outdoor unit - typical examples)

Note: The above check codes are examples only, and different check codes may be displayed depending on the outdoor unit configuration (e.g. a Super heat recovery multi system). For details, see the service manual for the outdoor unit.

Check code Display of receiving unit

Typical fault site Description of errorOutdoor 7-segment display TCC-LINK

central control or main remote

controller display

Indicator light block

Sub-code Flash

F1301: Compressor 102: Compressor 203: Compressor 3

F13 ALTError in temperature sensor built into indoor IGBT (TH)

Temperature sensor built into indoor IGBT (TH) has been open / short-circuited.

H0101: Compressor 102: Compressor 203: Compressor 3

H01 Compressor breakdown Inverter current (Idc) detection circuit detects overcurrent.

H0201: Compressor 102: Compressor 203: Compressor 3

H02 Compressor error (lockup) Compressor lockup is detected

H0301: Compressor 102: Compressor 203: Compressor 3

H03 Current detection circuit error

Abnormal current is detected while inverter compressor is turned off.

P0401: Compressor 102: Compressor 203: Compressor 3

P04 ALT Activation of high-pressure SW High-pressure SW is activated.

P0701: Compressor 102: Compressor 203: Compressor 3

P07 ALT Heat sink overheating error

Temperature sensor built into IGBT (TH) detects overheating.

P20 – P20 ALT High-pressure protection activation

High-pressure (Pd) sensor detected a value over the criteria.

P22

SMMS (Series 1)04: Rotation difference error06: Maximum rotation exceeded08: Out of step0A: Idc activation0C: Fan lock0d: Lock0E: Sync error0F: Control error

SMMS-i (Series 4)0∗: IGBT circuit1∗: Position detection circuit error3∗: Motor lockup error4∗: Motor current detectionC∗: TH sensor errorD∗: TH sensor errorE∗: Inverter DC voltage error (outdoor fan)

Note: Although letters 0 to F appear at locations indicated by “∗”, please ignore them.

P22 ALT Outdoor fan IPDU error Outdoor fan IPDU detects error.

P2601: Compressor 102: Compressor 203: Compressor 3

P26 ALT Activation of G-Tr (IGBT) short-circuit protection

Short-circuit protection for compressor motor driver circuit components is activated (momentary overcurrent).

P2901: Compressor 102: Compressor 203: Compressor 3

P29 ALT Compressor position detection circuit error

Compressor motor position detection error is detected.

73

Toshiba

Page 75: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 74 Tuesday, June 21, 2011 10:41 AM

6-3. Troubleshooting based on information displayed on remote controller

Using main remote controller (RBC-AMT32E)(1) Checking and testingWhen a fault occurs to an air conditioner, a check code and indoor unit No. are displayed on the display window of the remote controller.Check codes are only displayed while the air conditioner is in operation.If the display has already disappeared, access error history by following the procedure described below.

(2) Error historyThe error history access procedure is described below (up to four errors stored in memory). Error history can be accessed regardless of whether the air conditioner is in operation or shut down.

<Procedure> To be performed when system at rest

1 Invoke the SERVICE CHECK mode by pressing the + buttons simultaneously and holding for at least 4

seconds.The letters “ SERVICE CHECK” light up, and the check code “01” is displayed, indicating the error history. This is accompanied by the indoor unit No. to which the error history is related and a check code.

2 To check other error history items, press the button to select another check code.Check code “01” (latest) ➝ Check code “04” (oldest)Note: Error history contains four items.

3 When the button is pushed, normal display is restored.

REQUIREMENTDo not push the button as it would erase the whole error history of the indoor unit.

How to read displayed information

Check code Indoor unit No. in which fault has occurred

Normal display is restored.

Steps to follow

<7-segment display symbols>

<Corresponding alphanumerical letters>

74

Toshiba

Page 76: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 75 Tuesday, June 21, 2011 10:41 AM

Using TCC-LINK central control remote controller (TCB-SC642TLE2)(1) Checking and testingWhen a fault occurs to an air conditioner, a check code and indoor unit No. are displayed on the display window of the remote controller.Check codes are only displayed while the air conditioner is in operation.If the display has already disappeared, access error history by following the procedure described below.

(2) Error historyThe error history access procedure is described below (up to four errors stored in memory). Error history can be accessed regardless of whether the air conditioner is in operation or shut down.

1 Push the + buttons simultaneously and hold for at least 4 seconds.

2 The letters “ SERVICE CHECK” light up, and the check code “01” is displayed.

3 When a group No. is selected (blinking), if there is an error history, the UNIT No. and the latest error history information are displayed alternately.*During this procedure, the temperature setting feature is unavailable.

4 To check other error history items, push the button to select another check code (01-04.).

5 To check check code relating to another group, push (ZONE) and (GROUP) buttons to select a group No.Do not push the button as it would erase the whole error history of the selected group.

6 To finish off the service check, push the button.

Alternate blinking

Display of check codeDisplay of Unit No.

Alternate blinking

Display of check codeDisplay of Unit No.

75

Toshiba

Page 77: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 76 Tuesday, June 21, 2011 10:41 AM

Using indoor unit indicators (receiving unit light block) (wireless type)To identify the check code, check the 7-segment display on the header unit. To check for check codes not displayed on the 7-segment display, consult the “List of Check Codes (Indoor Unit)” in “6-2. Troubleshooting method”.

: Goes off : Lighting : Blinking (0.5 seconds)

Light block Check code Cause of fault

– Power turned off or error in wiring between receiving and indoor units

E01 Faulty receptionReceiving unit Error or poor contact in wiring

between receiving and indoor units

E02 Faulty transmission

E03 Loss of communication

E08 Duplicated indoor unit No. (address)Setting error

E09 Duplicated master remote controller

E10 Indoor unit inter-MCU communication error

E12 Automatic address starting error

E18 Error or poor contact in wiring between indoor units, indoor power turned off

E04 Error or poor contact in wiring between indoor and outdoor units(loss of indoor-outdoor communication)

E06 Faulty reception in indoor-outdoor communication (dropping out of indoor unit)

E07 Faulty transmission in indoor-outdoor communication

E15 Indoor unit not found during automatic address setting

E16 Too many indoor units connected / overloading

E19 Error in number of outdoor header units

E20 Detection of refrigerant piping communication error during automatic address setting

E23 Faulty transmission in outdoor-outdoor communication

E25 Duplicated follower outdoor address

E26 Faulty reception in outdoor-outdoor communication, dropping out of outdoor unit

E28 Outdoor follower unit error

E31 IPDU communication error

P01 Indoor AC fan error

P10 Indoor overflow error

P12 Indoor DC fan error

P13 Outdoor liquid backflow detection error

P03 Outdoor discharge (TD1) temperature error

P04 Activation of outdoor high-pressure SW

P05Open phase / power failureInverter DC voltage (Vdc) errorMG-CTT error

P07 Outdoor heat sink overheating error - Poor cooling of electrical component (IGBT) of outdoor unit

P15 Gas leak detection - insufficient refrigerant charging

P17 Outdoor discharge (TD2) temperature error

P18 Outdoor discharge (TD3) temperature error

P19 Outdoor 4-way valve reversing error

P20 Activation of high-pressure protection

P22 Outdoor fan IPDU error

P26 Outdoor G-Tr short-circuit error

P29 Compressor position detection circuit error

P31 Shutdown of other indoor unit in group due to fault (group follower unit error)

Operation Timer Ready

All lights out

Operation Timer Ready

Blinking

Operation Timer Ready

Blinking

Operation Timer Ready

Alternate blinking

Operation Timer Ready

Alternate blinking

MG-CTT: Magnet contactor

76

Toshiba

Page 78: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 77 Tuesday, June 21, 2011 10:41 AM

F01 Heat exchanger temperature sensor (TCJ) error

Indoor unit temperature sensor errors

F02 Heat exchanger temperature sensor (TC2) error

F03 Heat exchanger temperature sensor (TC1) error

F10 Ambient temperature sensor (TA) error

F11 Discharge temperature sensor (TF) error

F04 Discharge temperature sensor (TD1) error

Outdoor unit temperature sensor errors

F05 Discharge temperature sensor (TD2) error

F06 Heat exchanger temperature sensor (TE1, TE2) error

F07 Liquid temperature sensor (TL) error

F08 Outside air temperature sensor (TO) error

F12 Suction temperature sensor (TS1) error

F13 Heat sink sensor (TH) error

F15 Wiring error in heat exchanger sensor (TE1) and liquid temperature sensor (TL) Outdoor unit temperature sensor wiring / installation error

F16 Wiring error in outdoor high pressure sensor (Pd) and low pressure sensor (Ps)Outdoor pressure sensor wiring error

F22 Outdoor discharge temperature sensor (TD3) error

F23 Low pressure sensor (Ps) error Outdoor unit pressure sensor errorsF24 High pressure sensor (Pd) error

F29 Fault in indoor EEPROM

H01 Compressor breakdownOutdoor unit compressor-related errorsH02 Compressor lockup

H03 Current detection circuit error

H05 Wiring / installation error or detachment of outdoor discharge temperature sensor (TD1)

H06 Abnormal drop in low-pressure sensor (Ps) reading Protective shutdown of outdoor unitH07 Abnormal drop in oil level

H08 Error in temperature sensor for oil level detection circuit (TK1, TK2, TK3, TK4 or TK5)

H15 Wiring / installation error or detachment of outdoor discharge temperature sensor (TD2)

H16 Oil level detection circuit error - Error in outdoor unit TK1, TK2, TK3, TK4 or TK5 circuit

H25 Wiring / installation error or detachment of outdoor discharge temperature sensor (TD3)

L03 Duplicated indoor group header unit

L05 Duplicated priority indoor unit (as displayed on priority indoor unit)

L06 Duplicated priority indoor unit (as displayed on indoor unit other than priority indoor unit)

L07 Connection of group control cable to stand-alone indoor unit

L08 Indoor group address not set

L09 Indoor capacity not set

L04 Duplicated outdoor refrigerant line address

L10 Outdoor capacity not set

L17 Outdoor model incompatibility error

L18 Flow selector units error

L20 Duplicated central control address

L28 Too many outdoor units connected

L29 Error in number of IPDUs

L30 Indoor external interlock error

Light block Check code Cause of fault

Operation Timer Ready

Alternate blinking

Operation Timer Ready

Alternate blinking

Operation Timer Ready

Synchronized blinking

Operation Timer Ready

Blinking

Operation Timer Ready

Synchronized blinking

Operation Timer Ready

Synchronized blinking

77

Toshiba

Page 79: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 78 Tuesday, June 21, 2011 10:41 AM

Other (indications not involving check code)

F31 Outdoor EEPROM error

Light block Check code Cause of fault

– Test run in progress

–Setting incompatibility(automatic cooling / heating setting for model incapable of it and heating setting for cooling-only model)

Light block Check code Cause of fault

Operation Timer Ready

Synchronized blinking

Operation Timer Ready

Synchronized blinking

Operation Timer Ready

Alternate blinking

78

Toshiba

Page 80: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 79 Tuesday, June 21, 2011 10:41 AM

6-4. Check codes displayed on remote controller and SMMS outdoor unit (7-segment display on I/F board) and locations to be checked

For other types of outdoor units, refer to their own service manuals.

Check codeLocation

of detection

Description System status Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

E01 – – –

Remote controller

Indoor-remote controller communication error(detected at remote controller end)

Stop of corresponding unit

Communication between indoor P.C. board and remote controller is disrupted.

• Check remote controller inter-unit tie cable (A / B).

• Check for broken wire or connector bad contact.

• Check indoor power supply.

• Check for defect in indoor P.C. board.

• Check remote controller address settings(when two remote controllers are in use).

• Check remote controller P.C. board.

E02 – – –

Remote controller

Remote controller transmission error

Stop of corresponding unit

Signal cannot be transmitted from remote controller to indoor unit.

• Check internal transmission circuit of remote controller.--- Replace remote controller as necessary.

E03 – – 97

Indoor unit

Indoor-remote controller communication error(detected at indoor end)

Stop of corresponding unit

There is no communication from remote controller (including wireless) or network adaptor.

• Check remote controller and network adaptor wiring.

E04 – – 04

Indoor unit

Indoor-outdoor communication circuit error(detected at indoor end)

Stop of corresponding unit

Indoor unit is not receiving signal from outdoor unit.

• Check order in which power was turned on for indoor and outdoor units.

• Check indoor address setting.

• Check indoor-outdoor tie cable.

• Check outdoor termination resistance setting (SW30, Bit 2).

E06 E06

No. of indoor units from which signal is received normally

04

I/F Dropping out of indoor unit

All stop Indoor unit initially communicating normally fails to return signal for specified length of time.

• Check power supply to indoor unit.(Is power turned on?)

• Check connection of indoor-outdoor communication cable.

• Check connection of communication connectors on indoor P.C. board.

• Check connection of communication connectors on outdoor P.C. board.

• Check for defect in indoor P.C. board.

• Check for defect in outdoor P.C. board (I/F).

– E07 – –

I/F Indoor-outdoor communication circuit error(detected at outdoor end)

All stop Signal cannot be transmitted from outdoor to indoor units for 30 seconds continuously.

• Check outdoor termination resistance setting (SW30, Bit 2).

• Check connection of indoor-outdoor communication circuit.

79

Toshiba

Page 81: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 80 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

E08 E08

Duplicated indoor address

96

Indoor unitI/F

Duplicated indoor address

All stop More than one indoor unit is assigned same address.

• Check indoor addresses.• Check for any change

made to remote controller connection (group / individual) since indoor address setting.

E09 – – 99

Remote controller

Duplicated master remote controller

Stop of corresponding unit

In two remote controller configuration (including wireless), both controllers are set up as master. (Header indoor unit is shut down with alarm, while follower indoor units continue operating.)

• Check remote controller settings.

• Check remote controller P.C. boards.

E10 – – CF

Indoor unit

Indoor inter-MCU communication error

Stop of corresponding unit

Communication cannot be established / maintained upon turning on of power or during communication.

• Check for defect in indoor P.C. board

E12 E12

01: Indoor-outdoor communication02: Outdoor-outdoor communication

42

I/F Automatic address starting error

All stop • Indoor automatic address setting is started while automatic address setting for equipment in other refrigerant line is in progress.

• Outdoor automatic address setting is started while automatic address setting for indoor units is in progress.

• Perform automatic address setting again after disconnecting communication cable to that refrigerant line.

E15 E15 – 42

I/F Indoor unit not found during automatic address setting

All stop Indoor unit cannot be detected after indoor automatic address setting is started.

• Check connection of indoor-outdoor communication line.

• Check for error in indoor power supply system.

• Check for noise from other devices.

• Check for power failure.• Check for defect in indoor

P.C. board.

E16 E16

00: Overloading01-: No. of units connected

89

I/F Too many indoor units connected

All stop • Combined capacity of indoor units exceeds 135 % of combined capacity of outdoor units.

Note: If this code comes up after backup setting for outdoor unit failure is performed, perform “No overloading detected” setting.

<“No overloading detected” setting method> Turn on SW09/Bit 2 on I/F P.C. board of outdoor header unit.• More than 48 indoor units

are connected.

• Check capacities of indoor units connected.

• Check combined HP capacities of indoor units.

• Check HP capacity settings of outdoor units.

• Check No. of indoor units connected.

• Check for defect in outdoor P.C. board (I/F).

80

Toshiba

Page 82: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 81 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

E18 – – 97·99

Indoor unit

Error in communication between indoor header and follower units

Stop of corresponding unit

Periodic communication between indoor header and follower units cannot be maintained.

• Check remote controller wiring.

• Check indoor power supply wiring.

• Check P.C. boards of indoor units.

E19 E19

00: No header unit02: Two or more header units 96

I/F Error in number of outdoor header units

All stop • There is more than one outdoor header unit in one line.

• There is no outdoor header unit in one line.

Outdoor header unit is outdoor unit to which indoor-outdoor tie cable (U1,U2) is connected.• Check connection of

indoor-outdoor communication line.

• Check for defect in outdoor P.C. board (I/F).

E20 E20

01: Connection of outdoor unit from other line02: Connection of indoor unit from other line

42

I/F Connection to other line found during automatic address setting

All stop Equipment from other line is found to have been connected when indoor automatic address setting is in progress.

Disconnect inter-line tie cable in accordance with automatic address setting method explained in “Address setting” section.

E23 E23 – 15

I/F Outdoor-outdoor communication transmission error

All stop Signal cannot be transmitted to other outdoor units for at least 30 seconds continuously.

• Check power supply to outdoor units. (Is power turned on?)

• Check connection of tie cables between outdoor units for bad contact or broken wire.

• Check communication connectors on outdoor P.C. boards.

• Check for defect in outdoor P.C. board (I/F).

• Check termination resistance setting for communication between outdoor units.

E25 E25 – 15I/F Duplicated

follower outdoor address

All stop There is duplication in outdoor addresses set manually.

Note: Do not set outdoor addresses manually.

E26 E26

Address of outdoor unit from which signal is not received normally

15

I/F Dropping out of outdoor unit

All stop Outdoor unit initially communicating normally fails to return signal for specified length of time.

• Backup setting is being used for outdoor units.

• Check power supply to outdoor unit. (Is power turned on?)

• Check connection of tie cables between outdoor units for bad contact or broken wire.

• Check communication connectors on outdoor P.C. boards.

• Check for defect in outdoor P.C. board (I/F).

E28 E28

Detected outdoor unit No.

d2

I/F Outdoor follower unit error

All stop Outdoor header unit receives error code from outdoor follower unit.

• Check check code displayed on outdoor follower unit.

<Convenient functions>If SW04 is pressed and held for at least 1 second while [E28] is displayed on the 7-segmentdisplay of outdoor header unit, the fan of the outdoor unit that has been shut down due to an error comes on.If SW04 and SW05 are pressed simultaneously, the fans of normal outdoor units come on.To stop the fan or fans, press SW05 on its own.

81

Toshiba

Page 83: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 82 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

E31 E31

SMMS (Series 1)01: A3-IPDU1 error02: A3-IPDU2 error03: A3-IPDU1/A3-IPDU2 error04: Fan IPDU error05: A3-IPDU1 + Fan IPDU error06: A3-IPDU2 + Fan IPDU error07: All IPDU error or Communication error between IPDU and I/F circuit board or Outdoor I/F circuit board error

SMMS-i (Series 4)

Symbol O signifies site of IPDU error.

CF

I/F IPDU communication error

All stop Communication is disrupted between IPDUs (P.C. boards) in inverter box.

• Check wiring and connectors involved in communication between IPDU-I/F P.C. board for bad contact or broken wire.

• Check for defect in outdoor P.C. board (I/F, A3-IPDU or Fan IPDU).

• Check for external noise.

F01 – – 0F

Indoor unit

Indoor TCJ sensor error

Stop of corresponding unit

Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TCJ sensor connector and wiring.

• Check resistance characteristics of TCJ sensor.

• Check for defect in indoor P.C. board.

F02 – – 0d

Indoor unit

Indoor TC2 sensor error

Stop of corresponding unit

Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TC2 sensor connector and wiring.

• Check resistance characteristics of TC2 sensor.

• Check for defect in indoor P.C. board.

F03 – – 93

Indoor unit

Indoor TC1 sensor error

Stop of corresponding unit

Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TC1 sensor connector and wiring.

• Check resistance characteristics of TC1 sensor.

• Check for defect in indoor P.C. board.

F04 F04 – 19

I/F TD1 sensor error

All stop Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TD1 sensor connector.

• Check resistance characteristics of TD1 sensor.

• Check for defect in outdoor P.C. board (I/F).

F05 F05 – A1

I/F TD2 sensor error

All stop Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TD2 sensor connector.

• Check resistance characteristics of TD2 sensor.

• Check for defect in outdoor P.C. board (I/F).

F06 F06

01: TE1 sensor error02: TE2 sensor error 18

I/F TE1/TE2 sensor error

All stop Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TE1/TE2 sensor connectors.

• Check resistance characteristics of TE1/TE2 sensors.

• Check for defect in outdoor P.C. board (I/F).

82

Toshiba

Page 84: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 83 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status

Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

F07 F07 – 18

I/F TL sensor error

All stop Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TL sensor connector.

• Check resistance characteristics of TL sensor.

• Check for defect in outdoor P.C. board (I/F).

F08 F08 – 1b

I/F TO sensor error

All stop Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TO sensor connector.

• Check resistance characteristics of TO sensor.

• Check for defect in outdoor P.C. board (I/F).

F10 – – 0C

Indoor unit

Indoor TA sensor error

Stop of corresponding unit

Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TA sensor connector and wiring.

• Check resistance characteristics of TA sensor.

• Check for defect in indoor P.C. board.

F11 – –

Indoor unit

Indoor TF sensor error

Stop of corresponding unit

Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TF sensor connector and wiring.

• Check resistance characteristics of TF sensor.

• Check for defect in indoor P.C. board.

F12 F12 – A2

I/F TS1 sensor error

All stop Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TS1 sensor connector.

• Check resistance characteristics of TS1 sensor.

• Check for defect in outdoor P.C. board (I/F).

F13 F13

01: Compressor 1 side02: Compressor 2 side03: Compressor 3 side

43

IPDU TH sensor error

All stop Sensor resistance is infinity or zero (open / short circuit).

• Defect in IGBT built-in temperature sensor➝ Replace A3-IPDU P.C. board.

F15 F15 – 18

I/F Outdoor temperature sensor wiring error (TE1, TL)

All stop During compressor operation in HEAT mode, TE1 continuously provides temperature reading higher than indicated by TL by at least specified margin for 3 minutes or more.

• Check installation of TE1 and TL sensors.

• Check resistance characteristics of TE1 and TL sensors.

• Check for outdoor P.C. board (I/F) error.

F16 F16 – 43

I/F Outdoor pressure sensor wiring error (Pd, Ps)

All stop Readings of high-pressure Pd sensor and low-pressure Ps sensor are switched.Output voltages of both sensors are zero.

• Check connection of high-pressure Pd sensor connector.

• Check connection of low-pressure Ps sensor connector.

• Check for defect in pressure sensors Pd and Ps.

• Check for error in outdoor P.C. board (I/F).

• Check for deficiency in compressive output of compressor.

F22 F22 –

I/F TD3 sensor error

All stop Sensor resistance is infinity or zero. (open / short circuit)

• Check connection of TD3 sensor connector.

• Check resistance characteristics of TD3 sensor.

• Check for defect in outdoor P.C. board (I/F).

F23 F23 – 43

I/F Ps sensor error

All stop Output voltage of Ps sensor is zero.

• Check for connection error involving Ps sensor and Pd sensor connectors.

• Check connection of Ps sensor connector.

• Check for defect in Ps sensor.• Check for deficiency in

compressive output of compressor.

• Check for defect in 4-way valve.

• Check for defect in outdoor P.C. board (I/F).

• Check for defect in SV4 circuit.

83

Toshiba

Page 85: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 84 Tuesday, June 21, 2011 10:41 AM

MG-CTT: Magnet contactor*1 Total shutdown in case of header unit

Continued operation in case of follower unit

Check codeLocation

of detection

Description System status

Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerF24 –

F24 F24 – 43

I/F Pd sensor error

All stop Output voltage of Pd sensor is zero (sensor open-circuited). Pd > 4.15 MPa despite compressor having been turned off.

• Check connection of Pd sensor connector.

• Check for defect in Pd sensor.• Check for defect in outdoor

P.C. board (I/F).

F29 – – 12Indoor unit

Other indoor error

Stop of corresponding unit

Indoor P.C. board does not operate normally.

• Check for defect in indoor P.C. board (faulty EEPROM)

F31 F31 – 1C

I/F Outdoor EEPROM error

All stop *1 Outdoor P.C. board (I/F) does not operate normally.

• Check power supply voltage.• Check power supply noise.• Check for defect in outdoor

P.C. board (I/F).

H01 H01

01: Compressor 1 side02: Compressor 2 side03: Compressor 3 side

1F

IPDU Compressor breakdown

All stop Inverter current detection circuit detects overcurrent and shuts system down.

• Check power supply voltage. (AC200 V ± 10 %).

• Check for defect in compressor.

• Check for possible cause of abnormal overloading.

• Check for defect in outdoor P.C. board (A3-IPDU).

H02 H02

01: Compressor 1 side02: Compressor 2 side03: Compressor 3 side

1d

IPDU Compressor error (lockup)MG-CTT error

All stop Overcurrent is detected several seconds after startup of inverter compressor.

• Check for defect in compressor.

• Check power supply voltage. (AC200 V ± 10 %).

• Check compressor system wiring, particularly for open phase.

• Check connection of connectors / terminals on A3-IPDU P.C. board.

• Check conductivity of case heater.(Check for refrigerant entrapment inside compressor.)

• Check for defect in outdoor P.C. board (A3-IPDU).

• Check outdoor MG-CTT.

H03 H03

01: Compressor 1 side02: Compressor 2 side03: Compressor 3 side

17

IPDU Current detection circuit error

All stop Current flow of at least specified magnitude is detected despite inverter compressor having been shut turned off.

• Check current detection circuit wiring.

• Check defect in outdoor P.C. board (A3-IPDU).

H05 H05 –

I/F TD1 sensor miswiring (incomplete insertion)

All stop Discharge temperature of compressor 1 (TD1) does not increase despite compressor being in operation.

• Check installation of TD1 sensor.

• Check connection of TD1 sensor connector and wiring.

• Check resistance characteristics of TD1 sensor.

• Check for defect in outdoor P.C. board (I/F).

H06 H06 – 20

I/F Activation of low-pressure protection

All stop Low-pressure Ps sensor detects operating pressure lower than 0.02 MPa.

• Check service valves to confirm full opening(both gas and liquid sides).

• Check outdoor PMVs for clogging (PMV1, 2).

• Check for defect in SV2 or SV4 circuits.

• Check for defect in low-pressure Ps sensor.

• Check indoor filter for clogging.• Check valve opening status of

indoor PMV.• Check refrigerant piping for

clogging.• Check operation of outdoor fan

(during heating).• Check for insufficiency in

refrigerant quantity.

84

Toshiba

Page 86: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 85 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

H07 H07 – d7

I/F Low oil level protection

All stop Operating compressor detects continuous state of low oil level for about 2 hours.

<All outdoor units in corresponding line to be checked>• Check balance pipe

service valve to confirm full opening.

• Check connection and installation of TK1, TK2, TK3, TK4, and TK5 sensors.

• Check resistance characteristics of TK1, TK2, TK3, TK4, and TK5 sensors.

• Check for gas or oil leak in same line.

• Check for refrigerant entrapment inside compressor casing.

• Check SV3A, SV3B, SV3C, SV3D, SV3E, and SV3F valves for defect.

• Check oil return circuit of oil separator for clogging.

• Check oil equalizing circuit for clogging.

H08 H08

01: TK1 sensor error02: TK2 sensor error03: TK3 sensor error04: TK4 sensor error05: TK5 sensor error

d4

I/F Error in temperature sensor for oil level detection

All stop Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TK1 sensor connector.

• Check resistance characteristics of TK1 sensor.

• Check for defect in outdoor P.C. board (I/F).

All stop Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TK2 sensor connector.

• Check resistance characteristics of TK2 sensor.

• Check for defect in outdoor P.C. board (I/F).

All stop Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TK3 sensor connector.

• Check resistance characteristics of TK3 sensor.

• Check for defect in outdoor P.C. board (I/F).

All stop Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TK4 sensor connector.

• Check resistance characteristics of TK4 sensor.

• Check for defect in outdoor P.C. board (I/F).

All stop Sensor resistance is infinity or zero (open / short circuit).

• Check connection of TK5 sensor connector.

• Check resistance characteristics of TK5 sensor.

• Check for defect in outdoor P.C. board (I/F).

85

Toshiba

Page 87: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 86 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status

Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

H14 H14 –

I/F Compressor 2 case thermo activation

All stop Compressor 2 case thermo was activated.

• Check Compressor 2 case thermo circuit.(Connector, Wiring, Circuit board)

• Open and check the service valve.(Gas side, Liquid side)

• Check the outdoor PMV clogging (PMV1, 2).

• Check the SV42 circuit.• Check the SV4 circuit (SV41 / 42

miswiring).• Check the opening status of indoor

PMV.• Check the four-way valve error.• Check the refrigerant shortage.

H15 H15 –

I/F TD2 sensor miswiring (incomplete insertion)

All stop Air discharge temperature of (TD2) does not increase despite compressor 2 being in operation.

• Check installation of TD2 sensor.• Check connection of TD2 sensor connector

and wiring.• Check resistance characteristics of TD2

sensor.• Check for defect in outdoor P.C. board (I/F).

86

Toshiba

Page 88: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 87 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status

Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

H16 H16

SMMS (1 series)01: TK1 oil circuit error02: TK2 oil circuit error03: TK3 oil circuit error04: TK4 oil circuit error

I/F Oil detection circuit error

All stop The temperature change of TK1 cannot be detected even after Compressor 1 starts operating.

• Check the TK1 sensor installation.• Check the TK1 sensor resistant

characteristics.• Check the misconnection of TK1, TK2,

TK3, or TK4.• Check the SV3E valve error.• Check the oil circuit capillary clogging

and non-return valve error.• Check the hibernating refrigerant in

compressor.

SMMS (1 series)01: TK1 oil circuit error02: TK2 oil circuit error03: TK3 oil circuit error04: TK4 oil circuit error

I/F Oil detection circuit error

All stop The temperature change of TK2 cannot be detected even after Compressor 2 starts operating.

• Check the TK2 sensor installation.• Check the TK2 sensor resistant

characteristics.• Check the misconnection of TK1, TK2,

TK3, or TK4.• Check the SV3E valve error.• Check the oil circuit capillary clogging

and non-return valve error.• Check the hibernating refrigerant in

compressor.

The temperature change of TK3 cannot be detected even after Compressor 3 starts operating.

• Check the TK3 sensor installation.• Check the TK3 sensor resistant

characteristics.• Check the misconnection of TK1, TK2,

TK3, or TK4.• Check the SV3E valve error.• Check the oil circuit capillary clogging

and non-return valve error.• Check the hibernating refrigerant in

compressor.

The temperature change of TK4 cannot be detected even after Compressor 4 starts operating, or the temperature difference from that of the other TK sensor changes only in the specified range for a given time or longer.

• Check the TK4 sensor installation.• Check the TK4 sensor resistant

characteristics.• Check the misconnection of TK1, TK2,

TK3, or TK4.• Check the SV3E valve error.• Check the oil circuit capillary clogging

and non-return valve error.• Check the hibernating refrigerant in

compressor.

SMMS-i (4 series)01: TK1 oil circuit error02: TK2 oil circuit error03: TK3 oil circuit error04: TK4 oil circuit error05: TK5 oil circuit error

d7

I/F Oil level detection circuit error

All stop No temperature change is detected by TK1 despite compressor 1 having been started.

• Check for disconnection of TK1 sensor.• Check resistance characteristics of

TK1 sensor.• Check for connection error involving

TK1, TK2, TK3, TK4, and TK5 sensors• Check for faulty operation in SV3E or

SV3F valve.• Check for clogging in oil equalizing

circuit capillary and faulty operation in check valve.

• Check for refrigerant entrapment inside compressor.

No temperature change is detected by TK2 despite compressor 2 having been started.

• Check for disconnection of TK2 sensor.• Check resistance characteristics of

TK2 sensor.• Check for connection error involving

TK1, TK2, TK3, TK4, and TK5 sensors• Check for faulty operation in SV3E or

SV3F valve.• Check for clogging in oil equalizing

circuit capillary and faulty operation in check valve.

• Check for refrigerant entrapment inside compressor.

No temperature change is detected by TK3 despite compressor 3 having been started.

• Check for disconnection of TK3 sensor.• Check resistance characteristics of

TK3 sensor.• Check for connection error involving

TK1, TK2, TK3, TK4, and TK5 sensors• Check for faulty operation in SV3E or

SV3F valve.• Check for clogging in oil equalizing

circuit capillary and faulty operation in check valve.

• Check for refrigerant entrapment inside compressor.

87

Toshiba

Page 89: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 88 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status

Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

H16 H16

SMMS-i (4 series)01: TK1 oil circuit error02: TK2 oil circuit error03: TK3 oil circuit error04: TK4 oil circuit error05: TK5 oil circuit error d7

I/F Oil level detection circuit error

All stop No temperature change is detected by TK4 despite compressor having been started.

• Check for disconnection of TK4 sensor.• Check resistance characteristics of

TK4 sensor.• Check for connection error involving

TK1, TK2, TK3, TK4, and TK5 sensors• Check for faulty operation in SV3E or

SV3F valve.• Check for clogging in oil equalizing

circuit capillary and faulty operation in check valve.

• Check for refrigerant entrapment inside compressor.

No temperature change is detected by TK5 despite compressor having been started.

• Check for disconnection of TK5 sensor.• Check resistance characteristics of

TK5 sensor.• Check for connection error involving

TK1, TK2, TK3, TK4, and TK5 sensors• Check for faulty operation in SV3E

valve.• Check for clogging in oil equalizing

circuit capillary and faulty operation in check valve.

• Check for refrigerant entrapment inside compressor.

H25 H25 –

I/F TD3 sensor miswiring (incomplete insertion)

All stop Air discharge temperature (TD3) does not increase despite compressor 3 being in operation.

• Check installation of TD3 sensor.• Check connection of TD3 sensor

connector and wiring.• Check resistance characteristics of

TD3 sensor.• Check for defect in outdoor P.C. board

(I/F).

L02 L02 –

Indoor unit

Outdoor unit model mismatch error

Only the target unit stopped

An error was found on the outdoor unit model.

• Check the model name of the outdoor unit.

• Check the miswiring of the communication line between indoor and outdoor.

L03 – – 96

Indoor unit

Duplicated indoor header unit

Stop of corresponding unit

There is more than one header unit in group.

• Check indoor addresses.• Check for any change made to remote

controller connection (group / individual) since indoor address setting.

L04 L04 – 96

I/F Duplicated outdoor line address

All stop There is duplication in line address setting for outdoor units belonging to different refrigerant piping systems.

• Check line addresses.

L05 – – 96

I/F Duplicated priority indoor unit (as displayed on priority indoor unit)

All stop More than one indoor unit has been set up as priority indoor unit.

• Check display on priority indoor unit.

L06 L06

No. of priority indoor units

96

I/F Duplicated priority indoor unit (as displayed on indoor unit other than priority indoor unit)

All stop More than one indoor unit have been set up as priority indoor unit.

• Check displays on priority indoor unit and outdoor unit.

L07 – – 99

Indoor unit

Connection of group control cable to stand-alone indoor unit

Stop of corresponding unit

There is at least one stand-alone indoor unit to which group control cable is connected.

• Check indoor addresses.

L08 L08 – 99

Indoor unit

Indoor group / addresses not set

Stop of corresponding unit

Address setting has not been performed for indoor units.

• Check indoor addresses.Note:

This code is displayed when power is turned on for the first time after installation.

L09 – – 46Indoor unit

Indoor capacity not set

Stop of corresponding unit

Capacity setting has not been performed for indoor unit.

Set indoor capacity. (DN = 11)

88

Toshiba

Page 90: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 89 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

L10 L10 – 88

I/F Outdoor capacity not set

All stop Jumper wire provided on P.C. board for servicing I/F P.C. board has not been removed as required for given model.

Check model setting of P.C. board for servicing outdoor I/F P.C. board.

L17 L17Target indoor address

I/F Outdoor unit model mismatch error

The outdoor unit model is duplicate. The Cool/Heat Flex series 1/2 are duplicate.

• Check the outdoor unit model.

L18 L18 –

I/F Cool / heat switch unit error

Only the target unit stopped

The heating operation was performed without the cool-only setting configured in a cool-only room where a cool/heat switch unit is not connected.

• Check the remote controller setting. (DN="0F")

• Check the cool / heat switching unit.Check the piping connection of the switching unit.(Miswiring of discharge gas / suction gas)Check the SVS / SVD valve miswiring / misinstallation.

L20 – – 98

AI-NETIndoor unit

Duplicated central control address

All stop There is duplication in central control address setting.

• Check central control addresses.

• Check network adaptor P.C. board (applicable to AI-NET).

L28 L28 – 46

I/F Too many outdoor units connected

All stop There are more than four outdoor units.

• Check No. of outdoor units connected (Only up to 4 units per system allowed).

• Check communication lines between outdoor units.

• Check for defect in outdoor P.C. board (I/F).

L29 L29

SMMS (Series 1)01: A3-IPDU1 error02: A3-IPDU2 error03: A3-IPDU1/A3-IPDU2 error04: Fan IPDU error05: A3-IPDU1 + Fan IPDU error06: A3-IPDU2 + Fan IPDU error07: All IPDU error or Communication error between IPDU and I/F circuit board or Outdoor I/F circuit board error

SMMS-i (Series 4)

Symbol O signifies site of IPDU error.

CF

I/F Error in No. of IPDUs

All stop Insufficient number of IPDUs are detected when power is turned on.

• Check model setting of P.C. board for servicing outdoor I/F P.C. board.

• Check connection of UART communication connector.

• Check A3-IPDU, fan IPDU, and I/F P.C. board for defect.

89

Toshiba

Page 91: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 90 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

L30 L30

Detected indoor address

b6

Indoor unit

External interlock of indoor unit

Stop of corresponding unit

• Signal is present at external error input terminal (CN80) for 1 minute.

When external device is connected to CN80 connector:1) Check for defect in

external device.2) Check for defect in indoor

P.C. board.When external device is not connected to CN80 connector:1) Check for defect in indoor

P.C. board.

– L31 – – I/F Extended IC error

Continued operation

There is part failure in P.C. board (I/F).

Check outdoor P.C. board (I/F).

P01 – – 11Indoor unit

Indoor fan motor error

Stop of corresponding unit

• Check the lock of fan motor (AC fan).

• Check wiring.

P03 P03 – 1E

I/F Discharge temperature TD1 error

All stop Discharge temperature (TD1) exceeds 115 °C.

• Check outdoor service valves (gas side, liquid side) to confirm full opening.

• Check outdoor PMVs (PMV1, 2, 4) for clogging.

• Check resistance characteristics of TD1 sensor.

• Check for insufficiency in refrigerant quantity.

• Check for defect in 4-way valve.

• Check for leakage of SV4 circuit.

• Check SV4 circuit (wiring or installation error in SV41, SV42 or SV43).

P04 P04

01: Compressor 1 side02: Compressor 2 side03: Compressor 3 side

21

IPDU Activation of high-pressure SW

All stop High-pressure SW is activated.

• Check connection of high-pressure SW connector.

• Check for defect in Pd pressure sensor.

• Check outdoor service valves (gas side, liquid side) to confirm full opening.

• Check for defect in outdoor fan.

• Check for defect in outdoor fan motor.

• Check outdoor PMVs (PMV1, 2) for clogging.

• Check indoor / outdoor heat exchangers for clogging.

• Check for short-circuiting of outdoor suction / discharge air flows.

• Check SV2 circuit for clogging.

• Check for defect in outdoor P.C. board (I/F).

• Check for error in indoor fan system (possible cause of air flow reduction).

• Check opening status of indoor PMV.

• Check indoor-outdoor communication line for wiring error.

• Check for faulty operation of check valve in discharge pipe convergent section.

• Check gas balancing SV4 valve circuit.

• Check SV5 valve circuit.• Check for refrigerant

overcharging.

90

Toshiba

Page 92: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 91 Tuesday, June 21, 2011 10:41 AM

MG-CTT: Magnet contactor

Check codeLocation

of detection

Description System status

Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

P05 P05

SMMS (Series 1)01: Open phase detected02: Phase sequence error

I/F Open phase detected, Phase sequence error

All stop • Phase sequence error was detected when the power is turned on.

• Open phase error was detected when the power is turned on.

• Check the phase sequence of outdoor power wiring.

• Check the outdoor PC board (I/F) error.

SMMS-i (Series 4)00:

AF

I/F Detection of open phase / phase sequence

All stop • Open phase is detected when power is turned on.

• Inverter DC voltage is too high (overvoltage) or too low (undervoltage).

• Check for defect in outdoor P.C. board (I/F).

01: Compressor 1 side02: Compressor 2 side03: Compressor 3 side

Inverter DC voltage (Vdc) error (compressor)MG-CTT error

P07 P07

01: Compressor 1 side02: Compressor 2 side03: Compressor 3 side

1C

IPDUI/F

Heat sink overheating error

All stop Temperature sensor built into IGBT (TH) is overheated.

• Check power supply voltage.• Check outdoor fan system

error.• Check heat sink cooling duct

for clogging.• Check IGBT and heat sink for

thermal performance for faulty installation.(e.g. mounting screws and thermal conductivity)

• Check for defect in A3-IPDU.(faulty IGBT built-in temperature sensor (TH))

P10 P10

Detected indoor address

0b

Indoor unit

Indoor overflow error All stop • Float switch operates.

• Float switch circuit is open-circuited or disconnected at connector.

• Check float switch connector.• Check operation of drain

pump.• Check drain pump circuit.• Check drain pipe for clogging.• Check for defect in indoor

P.C. board.

P12 – – 11

Indoor unit

Indoor fan motor error Stop of corresponding unit

• Motor speed measurements continuously deviate from target value.

• Overcurrent protection is activated.

• Check connection of fan connector and wiring.

• Check for defect in fan motor.• Check for defect in indoor

P.C. board.• Check impact of outside air

treatment (OA).

91

Toshiba

Page 93: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 92 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

P13 P13 – 47

I/F Outdoor liquid backflow detection error

All stop <During cooling operation>When system is in cooling operation, high pressure is detected in follower unit that has been turned off.<During heating operation>When system is in heating operation, outdoor PMV 1 or 2 continuously registers opening of 100p or less while under SH control.

• Check full-close operation of outdoor PMV (1, 2, 4).

• Check for defect in Pd or Ps sensor.

• Check gas balancing circuit (SV2) for clogging.

• Check balance pipe.• Check SV3B circuit for

clogging.• Check defect in outdoor

P.C. board (I/F).• Check capillary of oil

separator oil return circuit for clogging.

• Check for leakage of check valve in discharge pipe convergent section.

P15 P15

01: TS condition

AE

I/F Gas leakdetection(TS1 condition)

All stop Protective shutdown due to sustained suction temperature at or above judgment criterionfor at least 10 minutes is repeated four times or more.<TS error judgment criterion>In cooling operation: 60 °CIn heating operation: 40 °C

• Check for insufficiency in refrigerant quantity.

• Check outdoor service valves (gas side, liquid side) to confirm full opening.

• Check PMVs (PMV1, 2) for clogging.

• Check resistance characteristics of TS1 sensor.

• Check for defect in 4-way valve.

• Check SV4 circuit for leakage

02: TD condition

AE

I/F Gas leak detection(TD condition)

All stop Protective shutdown due to sustained discharge temperature (TD1, TD2 or TD3) at or above 108 °C for at least 10 minutes is repeated four times or more.

• Check for insufficiency in refrigerant quantity.

• Check PMVs (PMV 1, 2) for clogging.

• Check resistance characteristics of TD1, TD2 and TD3 sensors.

• Check indoor filter for clogging.

• Check piping for clogging.• Check SV4 circuit (for

leakage or coil installation error).

P17 P17 – bb

I/F Discharge temperature TD2 error

All stop Discharge temperature (TD2) exceeds 115 °C.

• Check outdoor service valves (gas side, liquid side) to confirm full opening.

• Check outdoor PMVs (PMV1, 2, 4) for clogging.

• Check resistance characteristics of TD2 sensor.

• Check for defect in 4-way valve.

• Check SV4 circuit for leakage.

• Check SV4 circuit (for wiring or installation error involving SV41, SV42 and SV43).

P18 P18 –

I/F Discharge temperature TD3 error

All stop Discharge temperature (TD3) exceeds 115 °C.

• Check outdoor service valves (gas side, liquid side) to confirm full opening.

• Check outdoor PMVs (PMV1, 2, 4) for clogging.

• Check resistance characteristics of TD3 sensor.

• Check for defect in 4-way valve.

• Check SV43 circuit for leakage.

• Check SV4 circuit (for wiring or installation error involving SV41, SV42 and SV43).

92

Toshiba

Page 94: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 93 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

P19 P19

Detected outdoor unit No.

8

I/F 4-way valve reversing error

All stop Abnormal refrigerating cycle data is collected during heating operation.

• Check for defect in main body of 4-way valve.

• Check for coil defect in 4-way valve and loose connection of its connector.

• Check resistance characteristics of TS1 and TE1 sensors.

• Check output voltage characteristics of Pd and Ps pressure sensors.

• Check for wiring error involving TE1 and TL sensors.

P20 P20 – 22

I/F Activation of high-pressure protection

All stop Pd sensor detects pressure equal to or greater than 3.6 MPa.

• Check for defect in Pd pressure sensor.

• Check service valves (gas side, liquid side) to confirm full opening.

• Check for defect in outdoor fan.

• Check for defect in outdoor fan motor.

• Check outdoor PMVs (PMV1, 2, 4) for clogging.

• Check indoor / outdoor heat exchangers for clogging.

• Check for short-circuiting of outdoor suction / discharge air flows.

• Check SV2 circuit for clogging.

• Check for defect in outdoor P.C. board (I/F).

• Check for defect in indoor fan system (possible cause of air flow reduction).

• Check opening status of indoor PMV.

• Check indoor-outdoor communication line for wiring error.

• Check for faulty operation of check valve in discharge pipe convergent section.

• Check gas balancing SV4 valve circuit.

• Check SV5 valve circuit.• Check for refrigerant

overcharging.

93

Toshiba

Page 95: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 94 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

P22 P22

SMMS (Series 1)08: Out of step0A: IDC activation0E: Sync error0F: Control error06: Maximum rotation exceeded04: Rotation difference error0D: Lock0C: Fan lock

IPDU Outdoor fan IPDU error

All stop (Sub code: 08)FAN IPDU position detection circuitPosition detection is not performed properly.

• Check the fan motor.• Check the connector

connection for fan motor.• Check the error of IPDU

board for fan.

All stop (Sub code: 0A)FAN IPDU overcurrent protection circuitOvercurrent was detected when the fan started running or during operation.

• Check the fan motor.• Check the error of IPDU

board for fan.

All stop (Sub code: 0E)FAN IPDU position detection circuitPosition detection is not performed properly.

• Check the fan motor.• Check the connector

connection for fan motor.• Check the error of IPDU

board for fan.

All stop (Sub code: 0F)FAN IPDU position detection circuitPosition detection is not performed properly.

• Check the fan motor.• Check the connector

connection for fan motor.• Check the error of IPDU

board for fan.

All stop (Sub code: 06)External factors such as blastPosition detection is not performed properly. (Restarted in 6 seconds)

• Check the fan motor.• Check the error of IPDU

board for fan.

All stop (Sub code: 04)External factors such as blastThe difference between targeted rotation and actual rotation is 25% or more. (Restarted in 6 seconds)

• Check the fan motor.• Check the error of IPDU

board for fan.

All stop (Sub code: 0D)FAN IPDU position detection circuitPosition detection is not performed properly. (No wind)

• Check the fan motor.• Check the connector

connection for fan motor.• Check the error of IPDU

board for fan.

All stop (Sub code: 0C)External factors such as blastPosition detection is not performed properly. (Wind blows) (Restarted in 6 seconds)

• Check the fan motor.• Check the error of IPDU

board for fan.

94

Toshiba

Page 96: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 95 Tuesday, June 21, 2011 10:41 AM

Check codeLocation

of detection

Description System status Error detection condition(s) Check items (locations)Main

remote controller

Outdoor 7-segment display AI-NET central control remote

controllerCheck code Sub-code

P22 P22

SMMS-i (Series 4)0∗: IGBT circuit1∗: Position detection circuit error3∗: Motor lockup error4∗: Motor current detectionC∗: TH sensor temperature errorD∗: TH sensor errorE∗: Inverter DC voltage error (outdoor fan)Note:

Although letters 0 to F appear at locations indicated by “∗”, please ignore them.

1A

IPDU Outdoor fan IPDU error

All stop (Sub code: 0∗)Fan IPDU over current protection circuit Flow of current equal to or greater than the specified value is detected during startup of the fan.

• Check fan motor.• Check for defect in fan

IPDU P.C. board.

All stop (Sub code: 1∗)Fan IPDU position detection circuitPosition detection is not going on normally.

• Check fan motor.• Check connection of fan

motor connector.• Check for defect in fan

IPDU P.C. board.

All stop (Sub code: 3∗)Gusty wind, an obstruction, or another external factorSpeed estimation is not going on normally.

• Check fan motor.• Check for defect in fan

IPDU P.C. board.

All stop (Sub code: 4∗)Fan IPDU over current protection circuit Flow of current equal to or greater than the specified value is detected during operation of the fan.

• Check fan motor.• Check connection of fan

motor connector.• Check for defect in fan

IPDU P.C. board.

All stop (Sub code: C∗)Higher temperature than the specified value is detected during operation of the fan.

• Check fan motor.• Check for defect in fan

IPDU P.C. board.

All stop (Sub code: D∗)The resistance value of the sensor is infinite or zero (open or short circuit).

• Check for defect in fan IPDU P.C. board.

All stop (Sub code: E∗)Fan IPDU DC voltage protection circuit The DC voltage higher or lower than the specified value is detected.

• Check power voltage of the main power supply.

• Check for defect in fan IPDU P.C. board.

• Check connection of fan IPDU P.C. board.

P26 P26

01: Compressor 1 side02: Compressor 2 side03: Compressor 3 side

14

IPDU G-TR short-circuit protection error

All stop Overcurrent is momentarily detected during startup of compressor.

• Check connector connection and wiring on A3-IPDU P.C. board.

• Check for defect in compressor (layer short-circuit).

• Check for defect in outdoor P.C. board (A3-IPDU).

P29 P29

01: Compressor 1 side02: Compressor 2 side03: Compressor 3 side

16

IPDU Compressor position detection circuit error

All stop Position detection is not going on normally.

• Check wiring and connector connection.

• Check for compressor layer short-circuit.

• Check for defect in A3-IPDU P.C. board.

P31 – – 47

Indoor unit

Other indoor error(group follower unit error)

Stop of corresponding unit

There is error in other indoor unit in group, resulting in detection of E07/L07/L03/L08.

• Check indoor P.C. board.

95

Toshiba

Page 97: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 96 Tuesday, June 21, 2011 10:41 AM

Errors detected by TCC-LINK central control deviceCheck code

Location of

detectionDescription System status Error detection

condition(s) Check items (locations)Main remote

controller

Outdoor 7-segment display AI-NET central control remote

controllerSub-code

C05 – –

TCC-LINK TCC-LINK central control device transmission error

Continued operation

Central control device is unable to transmit signal.

• Check for defect in central control device.

• Check for defect in central control communication line.

• Check termination resistance setting.

C06 – –

TCC-LINK central control device reception error

Continued operation

Central control device is unable to receive signal.

• Check for defect in central control device.

• Check for defect in central control communication line.

• Check termination resistance setting.

• Check power supply for devices at other end of central control communication line.

• Check defect in P.C. boards of devices at other end of central control communication line.

C12 – –

General-purpose deviceI/F

Blanket alarm for general-purpose device control interface

Continued operation

Error signal is input to control interface for general-purpose devices.

• Check error input.

P30

Differs according to nature of alarm-causing error

TCC-LINK Group control follower unit error

Continued operation

Error occurs in follower unit under group control.([P30] is displayed on central control remote controller.)

• Check check code of unit that has generated alarm.

(L20 displayed.)Duplicated central control address

Continued operation

There is duplication in central control addresses.

• Check address settings.

96

Toshiba

Page 98: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 97 Tuesday, June 21, 2011 10:41 AM

6-5. Sensor characteristicsIndoor unit

▼ Temperature sensor characteristicsIndoor TA sensor

Resistance [kΩ]

Temperature [°C]

Temperature [°C] Resistance [kΩ]

Temperature [°C] Resistance [kΩ]

Resistance [kΩ](10 °C or below)

Temperature [°C]

Resistance [kΩ](10 °C or above)

Indoor TC1 sensor

Resistance [kΩ](10 °C or below)

Temperature [°C]

Resistance [kΩ](10 °C or above)

Indoor TC2 and TCJ sensors Temperature [°C] Resistance [kΩ]

97

Toshiba

Page 99: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 98 Tuesday, June 21, 2011 10:41 AM

7 P.C. Board Exchange Procedures

Indoor unit

7-1. Replacement of indoor P.C. boards

Points to note when replacing indoor P.C. board assemblyThe electrically erasable programmable read-only memory (hereinafter EEPROM, IC10) mounted on an indoor P.C. board holds important setting data, including the type and capacity codes intrinsic to the model (set at the factory), as well as the line / indoor / group addresses, high ceiling adjustment setting and the like (during installation, either automatically or manually). Proceed with the replacement of an indoor P.C. board assembly in accordance with the procedure described below.After completion of the work, check the settings again, including the indoor unit No. and group header / follower designation, and confirm the integrity of the refrigerating cycle by conducting a test operation, etc.

<Replacement procedure>

Method 1If it is possible to turn on the indoor unit and read the setting data from the P.C. board to be replaced via a wired remote controller -

Reading EEPROM data: Procedure 1

Replacing P.C. board and turning on power: Procedure 2

Writing EEPROM data in new EEPROM: Procedure 3

Resetting power supply (applicable to all indoor units connected to remote controller in case of group operation)

Part code Model type P.C. board type

431-6V-437

MMU-AP∗∗4MH seriesMMU-AP∗∗4SH seriesMMC-AP∗∗4H seriesMMD-AP∗∗4SPH series

MCC-1402

431-6V-438 MMD-AP∗∗4BH series MCC-1402

431-6V-444

MMU-AP∗∗4YH seriesMMD-AP∗∗4H seriesMMF-AP∗∗4H seriesMML-AP∗∗4BH series

MCC-1403

431-6V-469 MML-AP∗∗4H series MCC-1403

98

Toshiba

Page 100: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 99 Tuesday, June 21, 2011 10:41 AM

Method 2If it is not possible to turn on the indoor unit or read the setting data from the P.C. board to be replaced via a wired remote controller or operate the remote controller due to the failure of its power supply circuit -

Replacing EEPROM (IC10) (For the location of this component and the method to replace it, see the “ EEPROM location diagram” section.)• The EEPROM on the P.C. board to be replaced needs to be removed and mounted on the service P.C. board.

Replacing P.C. board and turning on power: Procedure 2

Reading EEPROM data: Procedure 1• If data cannot be read, go to Method 3.

Replacing EEPROM (IC10) again (For the location of this component and the method to replace it, see the “ EEPROM location diagram” section.)• The old EEPROM, supplied with the P.C. board to be replaced and now mounted on the service P.C. board,

needs to be replaced with the new EEPROM, supplied with the service P.C. board.

Replacing P.C. board and turning on power: Procedure 2

Writing EEPROM data in new EEPROM: Procedure 3

Resetting power supply (applicable to all indoor units connected to remote controller in case of group operation)

Method 3If it is not possible to read the setting data due to the failure of the EEPROM itself -Replacing P.C. board and turning on power: Procedure 2

Writing EEPROM data on basis of information supplied by customer (e.g. high ceiling adjustment setting and optional connection setting): Procedure 3

Resetting power supply (applicable to all indoor units connected to remote controller in case of group operation)

99

Toshiba

Page 101: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 100 Tuesday, June 21, 2011 10:41 AM

Procedure 1: reading setting data from EEPROM(Read the setting data from EEPROM, including both the factory settings and any modifications made to them on site.)

1 Push the + + buttons simultaneously and hold for at least 4 seconds. (This number corresponds to the same number shown on the Remote Controller Operation Diagram.)* In the case of group control, the unit No. displayed first is the indoor unit No. of the header unit.

At the same time, the CODE No. (DN code) 10 is displayed, and the fan of the selected indoor unit comes on, with the louver swinging, depending on the model.

2 Each time the button is pushed, one of the indoor unit No. under group control is displayed in turn.* The fan of the selected indoor unit comes on, with the louvers swinging, depending on the model.

3 The button allows you to move the CODE No. (DN code) up / down by one place.

4 First, change the CODE No. (DN code) from 10 to 01. (To set filter sign lighting time)Jot down the setting data displayed.

5 Change the CODE No. (DN code) using the button.Again, jot down the setting data displayed.

6 Repeat step 5 until all the setting data has been jotted down. (See the CODE No. list.)* CODE No. (DN code) go from 01 to FF with a few gaps along the way.

7 When finished, push the button to bring the system back to normal off state.(It takes the system about 1 minute to become responsive to remote controller operation.)

CODE No. (DN code) necessary at minimum

The type and capacity of the indoor unit are necessary for fan speed setting.

DN Contents10 Type

11 Indoor unit capacity

12 Line address

13 Indoor address

14 Group address

Remote controller operation diagram

100

Toshiba

Page 102: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 101 Tuesday, June 21, 2011 10:41 AM

Procedure 2: replacing P.C. board1 Replace the faulty P.C. board with a service P.C. board.

Be sure to replicate the old jumper setting (removal), switch setting (SW501), and connector short-circuit setting (e.g. CN34) on the service P.C. board. (See the diagram at below.)

2 It is necessary to establish a one-to-one correspondence between the indoor unit being serviced and the remote controller.Turn on the indoor unit using one of the methods described below according to the system configuration.

(1) Single (stand-alone) operationTurn on the indoor unit and proceed to Procedure 3.

(2) Group operationA) If it is possible to selectively turn on the indoor unit being serviced

Turn on the indoor unit being serviced and proceed to Procedure 3.B) If it is not possible to selectively turn on the indoor unit being serviced (Case 1)

a) Temporarily disconnect the group control wiring from terminals A and B of the indoor unit being serviced.b) Connect the remote controller wiring to the terminals, turn on the indoor unit, and proceed to Procedure 3.* If this method cannot be used, proceed to the alternative method described below (Case 2).

C) If it is not possible to selectively turn on the indoor unit being serviced (Case 2)a) Remove the CN41 connectors of all other indoor units in the same group.b) Turn on the indoor unit and proceed to Procedure 3.

* Be sure to restore the temporarily removed group control wiring and CN41 connectors to their initial states after Procedure 3 has been completed.

If a short-circuiting plug had been used on the replaced P.C. board, reuse it on the service P.C. board.

If a short-circuiting plug had been used on the replaced P.C. board, reuse it on the service P.C. board.

From left: CN112, 111 and 110

Remove group control wiring from terminals A and B of indoor unit being serviced, and connect remote controller wiring.

Indoor unit (one being serviced)Service P.C. boardP.C. board

Indoor unitIndoor unitP.C. board

Remote controllerGroup control wiring

Remove CN41 connectors of all other indoor units in same group.

Case 1

Case 2 Indoor unit (one being serviced)Service P.C. boardP.C. board

Indoor unitIndoor unitP.C. board

Remote controllerGroup control wiring

101

Toshiba

Page 103: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 102 Tuesday, June 21, 2011 10:41 AM

Procedure 3: writing setting data in EEPROM(The EEPROM of the service P.C. board has been set to the factory default values.)

1 Push the + + buttons simultaneously and hold for at least 4 seconds. (This number corresponds to the same number shown on the Remote Controller Operation Diagram.)(Under UNIT No., ALL is displayed.)At the same time, the CODE No. (DN code) 10 is displayed, and the fan of the indoor unit comes on, with the louver swinging, depending on the model.

2 Push the left part of the button to display the indoor unit No. one by one in the group control. Specify the indoor unit No. whose service PC board was replaced.(This operation is not available if the UNIT No. shows

.)

3 The button allows you to moved the CODE No. (DN code) up / down by one place.

4 First, set the type and capacity codes of the indoor unit.(Changing the type and capacity codes in EEPROM overwrites the factory default settings.)

(1) Set the CODE No. (DN code) to 10 (no change)(2) Use the button to select the type.

(For example, 0001 is for the 4-way cassette type.) - See the CODE No. list.(3) Push the button. (The display should change from flashing to steady.)(4) Use the button to set the CODE No. (DN code) to 11.(5) Use the button to set the capacity code.

(For example, 0012 is for the 027 type.) - See the CODE No. list.(6) Push the button. (The display should change from flashing to steady.)(7) Push the button to bring the system back to normal off state.

5 Next, write any setting changes made on-site after installation, such as address settings, in the EEPROM. Perform the tasks specified in step 1 again.

6 Use the button to set the CODE No. (DN code) to 01 (To set filter sign lighting time)

7 Check the value displayed with the value jotted down in Procedure 1 and information proved by the customer.

(1) If there is a discrepancy, change the setting in accordance with the jotted-down value, and push the button. (The display should change from flashing to steady.)

(2) If there is no discrepancy, do nothing.

8 Use the button to change the CODE No. (DN code).Again, check the value, and change the setting if necessary.

9 Repeat steps 6 and 7 until all the settings are checked.

10 When finished, push the button to bring the system back to normal off state.In the case of group operation, turn the unit off, reconnect the indoor-indoor group control wiring and CN41 connectors, and turn on all the indoor units.(It takes the system about 1 minute to become responsive to remote controller operation.)

* CODE No. (DN code) go from 01 to FF with a few gaps along the way.If you realize you have wrongly corrected a certain setting after pushing the button, you can recover the initial value by pushing the button, provided that the CODE No. (DN code) is yet to be changed.

102

Toshiba

Page 104: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 103 Tuesday, June 21, 2011 10:41 AM

EEPROM location diagramThe EEPROM (IC10) is mounted on an IC socket. Use a pair of tweezers, etc. to remove it. When installing it, adjust its orientation as shown in the diagram below.During EEPROM removal / installation, take care not to bend IC leads.

P.C. board (MCC-1402) P.C. board (MCC-1403) EEPROM(IC10) When installing the EEPROM, align its notch with that of the IC socket.

EEPROM(IC10)

IC socket Notch EEPROM

Notch

103

Toshiba

Page 105: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 104 Tuesday, June 21, 2011 10:41 AM

CODE No. list (Example)

*1 The initial setup value of EEPROM installed on the service P.C. board*2 <Model Name: MMU-AP ∗∗∗ 2H>

For the above models, set CODE No. to “ ” and the setting data 0000 (initial) to “0001”.

CODE No. (DN) Item Setting data Factory-set value

01 Filter sign lighting time Depending on Type

02 Filter pollution leve 0000: standard

03 Central control address 0099: Not determined

06 Heating suction temperature shift 0002: +2 °C (Floor standing type: 0)

0d Existence of automatic COOL/HEAT mode 0001: No auto mode cooling / heating * Automatically selection by connected outdoor unit0F Cooling only 0000: Heat pump

10 Type Depending on model type

11 Indoor unit capacity Depending on capacity type

12 System address 0099: Not determined

13 Indoor unit address 0099: Not determined

14 Group address 0099: Not determined

19 Louver type (wind direction adjustment) Depending on Type.

1E Temperature range of cooling / heating automatic SW control point

0003: 3 deg (Ts ± 1.5)

28 Power failure automatic recovery 0000: None

31 Vent Fan (Single operation) 0000: Not possible

32 Sensor SW (Selection of static pressure) 0000: Body sensor

5d High ceiling select 0000: Standard

60 Timer setting (wired remote controller) 0000: Available

F0 Swing mode 0001: Standard

D0 Power save operation 0001: Standard

TypeCode No. [10]

Setup data Type Model abb. name

0000 1-way Cassette MMU-AP∗∗∗SH

0001 *1, *2 4-way Cassette MMU-AP∗∗∗2H

0002 2-way Cassette MMU-AP∗∗∗WH

0003 1-way Cassette(Compact type)

MMU-AP∗∗∗YH

0004 Concealed Duct Standard MMD-AP∗∗∗BH

0005 Slim Duct MMD-AP∗∗∗SPHMMD-AP∗∗∗SH

0006 Concealed Duct High Static Pressure MMD-AP∗∗∗H

0007 Ceiling MMC-AP∗∗∗H

0008 High Wall MMK-AP∗∗∗H

0009 — —

0010 Floor Standing Cabinet MML-AP∗∗∗H

0011 Floor Standing Concealed MML-AP∗∗∗BH

0012 — —

0013 Floor Standing MMF-AP∗∗∗H

0014 Compact 4-way Cassette MMU-AP∗∗∗MH

0016 Fresh air intake unit (Duct type) MMD-AP∗∗∗HFE

Indoor unit capacityCODE No. [11]

Setup data Model Setup data Model0000* Invalid 0016 —

0001 007 type 0017 048 type

0002 — 0018 056 type

0003 009 type 0019 —

0004 — 0020 —

0005 012 type 0021 072 type

0006 — 0022 —

0007 015 type 0023 096 type

0008 — 0024 —

0009 018 type 0025 —

0010 — 0026 —

0011 024 type 0027 —

0012 027 type 0028 —

0013 030 type ~ —

0014 — 0034 —

0015 036 type

104

Toshiba

Page 106: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 105 Tuesday, June 21, 2011 10:41 AM

8 Detachments8-1. 1-way cassette (SH)MMU-AP0154SH✽, AP0184SH✽, AP0244SH✽

Ceiling panel: RBC-US21PGE

No. Part name Procedure Remarks1 Air intake

grille REQUIREMENTBe sure to put on gloves when working; otherwise an injury may be caused.

1. Detachment1) Stop operation of the air conditioner, and then turn off switch

of the breaker.2) Remove the screws of air intake grille fixing knob on a side

of each filter.

3) Open the grilles by sliding knobs toward suction side. (Both 2 pieces at left and right sides)

4) Pull out the grille by pushing claws at rear hinge (2 positions) with (-) screwdriver.

2. Attachment1) Insert the rear hinge (2 positions) into square holes of the

panel. (Insert it surely up to the end.)

NOTEAfter inserting the hinge, check the grille does not fall out even if pulling the grilles.

2) Close the grilles and slide the hooks (2 positions) toward discharge side to fix them.

3) Remove the screws of air intake grille fixing knob on a side of each filter.

Knobs of air intake grilleAir intake grilleAir filter

SlideRear hinge

Knob

105

Toshiba

Page 107: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 106 Tuesday, June 21, 2011 10:41 AM

2 Electric parts cover

1. Detachment1) Perform work of procedure 1. of 1.2) Loosen fixing screws. (Ø4 ×8, 2 pcs)3) Pull down the cover and shift it to the fan motor side to

remove it.2. Attachment

1) Insert the cover along edge of the electrical control box and match the projection inside of the fixing screw with hole of the cover.

2) Tighten the fixing screws. (Ø4 × 8, 2 pcs)

3 Adjust cap 1. Detachment1) Perform work of procedure 1. of 1.2) Take off fixing screws. (Ø4 × 12, 2 pcs)3) Hold handle of the cap, and then slide it toward suction side

to remove cap.2. Attachment

1) Catch on the top claw and slide it toward discharge side for attachment.

2) Fit the fixing screws. (Ø4 × 12, 2 pcs)

No. Part name Procedure Remarks

Screws (2 positions)

Projection

Screw

Sliding direction

Handle

106

Toshiba

Page 108: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 107 Tuesday, June 21, 2011 10:41 AM

4 Ceiling panel 1. Detachment1) Perform works of procedures 1. of 2 and 1. of 3.2) Remove louver connector (CN33 White, 5P) connected to

the control P.C. board, and then take off the lead wire from the clamp.

NOTEWhen removing the connector, unlock the lock of the housing.

3) Take off screws fixing the ceiling panel. (M5 × 4 pcs, M4 × 2 pcs)

NOTEBe sure to open the screw cap before taking off the fixing screw (M4) at the center of the discharge port.

4) While pulling down the ceiling panel by pushing the knob of hook (movable) at right side of the panel toward inner side, remove the hook (movable) and also the hook (movable) at left side to pull down the ceiling panel by lifting the left side of the panel and sliding toward outside.

2. Attachment1) Hook the hooks at both sides of the ceiling panel to the

indoor unit.2) Fit the fixing screws. (M5 × 4 pcs, M4 × 2 pcs)

NOTEBe sure to close the screw cap after screwing the fixing screw (M4) at the center of the discharge port.

3) Connect the louver connector of the ceiling panel to the connector (CN33 White, 5P) of the control P.C. board.

No. Part name Procedure Remarks

Remove louver connector.

Fixing screw M5

Fixing screw M4

Fixing screw M4 for screw cap

Hook knob

107

Toshiba

Page 109: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 108 Tuesday, June 21, 2011 10:41 AM

5 Electrical control box

1. Detachment1) Perform work of procedure 1. of 2.2) Take off the fixing screws. (Ø4 × 8, 4 pcs)3) Remove the cord clamp on the ceiling surface, pull the

electrical control box downward, and then hook the hooking claw at the rear side to square hole of the panel.

2. Attachment1) Take off the hook at the rear side of the electrical control box.2) Return the electrical control box at the original position, ant

then fit the fixing screws. (Ø4 × 8, 4 pcs)3) Using cord clamp at the ceiling surface, fix the lead wires as

before.

No. Part name Procedure Remarks

Square hole for hooking electrical control box

Hooking section

Fixing screw

Fixing screw

Cord clamp

108

Toshiba

Page 110: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 109 Tuesday, June 21, 2011 10:41 AM

6 Control P.C. board

1. Detachment1) Perform work of procedure 1. of 5.2) Remove connectors connected from the control P.C. board

to other parts.

NOTEBe sure to unlock the lock of the housing before removing the connector.

CN33: Louver motor (5P: White)CH34: Float switch (3P: Red)CN41: Remote controller terminal block

(3P: Blue)(Screws of terminal block: 4P)

CN67: Power supply terminal block(2P: Black)(Screws of terminal block: 2P)

CN68: Drain pump (2P: Blue)CN82: PMV (6P: Blue)CN100: TC1 sensor (3P: Brown)CN101: TC2 sensor (2P: Black)CN102: TCJ sensor (2P: Red)CN104: Room temp. Sensor (2P: Orange)CN333: Fan motor power supply (5P: White)CN334: Fan motor position detection (5P: White)

3) Unlock the locks of the card edge spacers (7 positions), and then remove the control P.C. board.

2. Attachment1) Fix the control P.C. board to the card edge spacers (7

positions).2) Connect the connectors disconnected in item 1 as before.

NOTEFor connectors, check there is no missing or contact failure.

No. Part name Procedure Remarks

Card edge spacer

Power supply terminal block 2P

Remote controller terminal block 4P

109

Toshiba

Page 111: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 110 Tuesday, June 21, 2011 10:41 AM

7 Fan motor fan 1. Detachment1) Perform work of procedure 1. of 2.2) Remove clamps of the lead wires which are connected to the

following connectors of the control P.C. board.

NOTEBe sure to unlock the lock of the housing before removing the connector.

CN333: Fan motor power supply (5P: White)CN334: Fan motor position detection (5P: White)3) Remove the hooking claws at both sides of the fan case

(lower) and remove the fan by pulling out it from the partition board.

4) Loosen hexagon socket head screw of the fan.5) Remove screws of the fixing bracket while holding the fan

motor, and then remove the fan and the fan motor. Earth wires of the motor are tightened together.

2. Attachment1) Insert the fan into the shaft of the motor and screw the fan

motor with the fixing bracket. (Tighten earth lead wires of the motor together as before.) For the boss of the fan, attach hexagon socket head screw to shaft of the motor matching the marked position of the shaft with groove of the fan.

NOTEMatch the rotation direction of the motor with that of the fan, and fix the fan motor so that the motor lead section comes to the piping side referring to the right photo.

2) Determine the position so that the fan locates at the center against the fan case (upper), and then fix the fan with hexagon socket head screw.

NOTEFor fixation, use a torque wrench and tighten with 4.9 N•m or more.

3) Mount the fan case (lower) as before, and check the fan smoothly rotates without contacting with fan case.

4) Connect the connectors disconnected in procedure 1.5) Fix parts as before in order of Electric parts cover ➝ Air

intake grille.

No. Part name Procedure Remarks

Hooking claw

Relief groove

Earth wires (Tightening together)

Motor lead section

Fixing bracket

Pipe side

Fan case (Upper)

110

Toshiba

Page 112: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 111 Tuesday, June 21, 2011 10:41 AM

8 Drain pan 1. Detachment1) Perform work of procedure 1. of 4.2) Remove the drain cap, and then drain the drain water

accumulated in the drain pan.

NOTEWhen removing the drain cap, be sure to catch drain water using bucket, etc.

3) Take off screws fixing the drain pan. (Ø4 × 8, 2 pcs)4) Remove the drain pan while lowering the discharge side.

2. Attachment1) Fix parts as before in order of Drain cap ➝ Drain pan ➝

Ceiling panel ➝ Electric parts cover ➝ Adjust cover ➝ Air intake grille.

No. Part name Procedure Remarks

Fixing screw

Drain cap

Pull down the discharge side

And remove the drain pan.

111

Toshiba

Page 113: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 112 Tuesday, June 21, 2011 10:41 AM

9 Drain pump 1. Detachment1) Perform work of procedure 1. of 8.2) Remove clamps of the lead wires connected to the following

connectors of the control P.C. board.

NOTEBe sure to unlock the lock of the housing before removing the connector.

CN34: Float switch (3P: Red)CN68: Drain pump (3P: Blue)3) Pick the hose band and shift band from pump connecting

part to remove the drain hose.4) Take off screws fixing the drain pump assembly. (Ø4 × 8, 3

pcs)5) Pull out the drain pump assembly toward discharge side to

remove it.

2. Attachment1) Fix the drain pump assembly as before.2) Connect the drain hose and attach the hose band.

NOTEInsert the drain hose completely up to the end of the pump connecting part, and then attach band at the white mark position of the hose.

3) Insert the connectors to the control P.C. board as before.4) Fix parts as before in order of Drain cap ➝ Drain pan ➝

Ceiling panel ➝ Electric parts cover ➝ Adjust cover ➝ Air intake grille.

No. Part name Procedure Remarks

CN68CN34

Shift the band toward hose side.

Hose band

Fixing screw

Pull out toward discharge side.

112

Toshiba

Page 114: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 113 Tuesday, June 21, 2011 10:41 AM

10 PMV motor 1. Detachment1) Perform work of procedure 1. of 8.2) Remove the relay connector of PMV motor. (As the relay

connectors are connected in the vinyl tube, cut off the banding band fixing the both ends of the tube and shift the tube to remove relay connector.)

3) Peel off the butyl rubber adhered to the pulse motor valve (PMV) body until PMV body appears, and remove PMV motor after loosening the nut fixing PMV motor with double spanners.

2. Attachment1) Mount PMV motor and the relay connector as before.

NOTEControl tightening torque of PMV body and PMV motor with 7.84 ± 0.98 N•m.

11 Heat exchanger

1. Detachment1) Recover the refrigerant gas.2) Remove the refrigerant pipe of the indoor unit.3) Perform work of procedure 1. of 8.4) Remove the pipe cover by taking off fixing screws of the

cover. (Ø4 × 8, 2 pcs)5) Remove the clamp which fixes TC1 sensor, TC2 sensor and

TCJ sensor, and then pull out the sensors from the holder.6) Remove the heat exchanger by taking off fixing screws of the

partition board while holding the heat exchanger. (Ø4 × 8, 4 pcs)

2. Attachment1) Fix parts as before in order of Heat exchanger ➝ Sensors ➝

Pipe cover ➝ Drain cap ➝ Drain pan ➝ Ceiling panel ➝ Electric parts cover ➝ Adjust cover ➝ Air intake grille.

2) Connect the refrigerant pipe as before, and then perform vacuuming.

No. Part name Procedure Remarks

Relay connector (In vinyl tube (Black)) Banding band

PMV motor PMV body

Fixing screw Pipe cover

Partition board (Pipe drawing port side)

Fixing screw

Partition board

Fixing screw

113

Toshiba

Page 115: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 114 Tuesday, June 21, 2011 10:41 AM

8-2. Compact 4-way cassetteMMU-AP0074MH✽, AP0094MH✽, AP0124MH✽, AP0154MH✽, AP0184MH✽

Ceiling panel: RBC-UM11PG(W)E

Preparing work:1. Before work, be sure to stop the power supply of the air conditioner and turn off switch of the

power supply breaker. (Otherwise an electric shock may be caused.)2. Be sure to put on the gloves when working; otherwise an injury may be caused with parts sharp

edges etc.No. Part name Procedure Remarks1 Air intake

grille1. Detachment

1) Loosen the fixing screw.

2) Slide the fixing bracket toward the outside.

3) Slide the air intake grille buttons to detach the air intake grille from the ceiling panel. Lower the grille slowly whilst holding.

4) Slide hooks (2 positions) of the air intake grille to inner side, and then hang down the air intake grille.

5) Take off the strap that connects the panel and the air intake grille, and then lift up shaft of the air intake grille to remove the air intake grille.

2. Attachment1) Hook shaft of the air intake grille to the panel.2) Hook strap of the air intake grille to the original position of the panel.3) Close the air intake grille and slide the hooks outward to fix it.4) Slide the fixing bracket and fixing screw.

Air intake grille Ceiling panel

Hook of air intake grille

Hook of fall-preventive strap

Hook hole of ceiling panel

114

Toshiba

Page 116: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 115 Tuesday, June 21, 2011 10:41 AM

2 Electric parts cover

1. Detachment1) Perform work of procedure 1-1.2) Take off screws (Ø4 × 10, 3 pcs.) fixing the electric parts

cover.3) Remove the electric parts cover from the temporary hanging

hook of the electric parts cover, and then open the cover.

2. Attachment1) Close the electric parts cover and hook the cover hole to the

temporary hanging hook.2) Tighten the fixing screws. (Ø4 × 10, 3 pcs.)

3 Adjust corner cover

1. Detachment1) Perform work of procedure of 1-1.2) Turn clockwise screws (4 positions) at the suction port

corner until adjust corner cover rises up.

NOTEWhen you work, keep the torque at below 12N•m. Do not use an electric screwdriver; otherwise the mechanism of adjust corner cover may be damaged and not be removed.

3) Pull downward the risen-up part of adjust corner cover and remove it.

4) Remove the strap of adjust corner cover.

2. Attachment1) Attach the strap of adjust corner cover to the panel, hook

claws of adjust corner cover to the panel corner, and then push the opposite side into the panel.

2) Turn screws (4 positions) of the suction port corner counterclockwise until bump between adjust corner cover and panel disappears.

NOTEWhen you work, keep the torque at below 12N•m. Do not use an electric screwdriver; otherwise the mechanism of adjust corner cover may be damaged and not be removed.

No. Part name Procedure Remarks

Screw Temporary hanging hook

ScrewUnnecessary to remove this hook.

Torque~12N•m

Torque~12N•m

115

Toshiba

Page 117: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 116 Tuesday, June 21, 2011 10:41 AM

4 Ceiling panel 1. Detachment1) Perform works of procedure 1-1-, 2-1, and 3-1.2) Remove the louver connector (CN33, White, 5P) connected

to the control P.C. board and then take off the lead wire from the clamp.

NOTERemove the connectors after unlocking the lock of the housing.

3) Take off screws (M5, 4 pcs.) fixing the ceiling panel.4) Push the temporary bracket to inner side to remove the

ceiling panel.

2. Attachment1) Hook the panel to the temporary bracket of the drain pan of

the main body.

NOTEThe panel has directionality. Therefore mount the panel according to the temporary bracket and the bracket mounting position.

2) Tighten the fixing screws. (M5, 4 pcs.)3) Connect louver connector of the ceiling panel to the

connector (CN33, White, 5P) of the control P.C. board.

No. Part name Procedure Remarks

Temporary bracket

Hanging section of tentative hook of ceiling panel

Push to remove

Drain piping corner

Temporary bracketCeiling panel

Hanging section of temporary bracketWasher

based screw

Cable clamp

CN33

116

Toshiba

Page 118: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 117 Tuesday, June 21, 2011 10:41 AM

5 Control P.C. board

1. Detachment1) Perform works of procedure 1-1- and 2-1.2) Remove the connectors connected from the control P.C. board to other parts.CN33: Louver motor (5P, White)CN34: Float switch (3P, Red)CN41: Terminal block of remote controller (3P, Blue)CN40: Terminal block of crossover between inside and outside (2P, Blue)CN68: Drain pump (3P, Blue)CN67: Terminal block of power supply (3P, Black)CN100: TC1 sensor (3P, Brown)CN101: TC2 sensor (2P, Black)CN102: TCJ sensor (2P, Red)CN104: Room temp sensor (2P, Yellow)CN82: PMV (6P, Blue)CN333: Fan motor power supply (5P, White)CN334: Fan motor position detection (5P, White)

NOTERemove the connectors after unlocking the lock of the housing.

3) Unlock the lock of the card edge spacer (6 positions) and then remove the control P.C. board.

2. Attachment1) Fix the control P.C. board to the card edge spacer. (6 positions)2) Connect the connectors as original before being removed in item 1.

NOTEFor drawing of each wire and position of ferrite core, perform wiring same as those before removing. If there is incomplete drawing of wire, short or water leakage of the parts may be caused.

No. Part name Procedure Remarks

Ferrite core for sensor lead

Ferrite core for fan motorDrawing-out port of lead wire

Card edge spacer

Enlarged drawingFix the lead wires with cord clamp so that the lead wires do not slacken at P.C board side. (2 positions)

Cord clamp

As shown in the figure, store PMV lead wire connected with connector assembly so that the connector positions under wire of the terminal.

Details of PMV lead wire drawing

Fix the sensor lead wires firmly with the cord clamp so that they do not touch with the caution plate of the terminal block and they do not slacken at P.C. board side. (3 positions)Arrange the clamp at the position as shown in the figure.

Cord clamp

Fold back the sensor lead wire and fix it surely with the cord clamp.Adhere on the transformer.

Arrow view

Details of sensor lead wire drawing

Be sure that the float switch lead wire positions at inner side of the fan motor lead wire.Cord clampFold back the float switch lead wire and fix surely with cord clamp. (There is no catching-in of P.C. board and lead wire.)

Arrange at position as shown in the figure.Details of fan motor lead wire drawing

117

Toshiba

Page 119: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 118 Tuesday, June 21, 2011 10:41 AM

6 Electrical control box

1. Detachment1) Perform works of procedure 1-1- and 2-1.2) Remove connectors of the lead wire connected to the following connectors of the control P.C. board.CN33: Louver motor (5P, White)CN34: Float switch (3P, Red)CN68: Drain pump (3P, Blue)CN100: TC1 sensor (3P, Brown)CN101: TC2 sensor (2P, Black)CN102: TCJ sensor (2P, Red)CN82: PMV (6P, Blue)CN333: Fan motor power supply (5P, White)CN334: Fan motor position detection (5P, White)

NOTERemove the connectors after unlocking the lock of the housing.

3) Remove each lead wire from cord clamps in the electrical control box.

4) Remove the power supply wiring, remote controller wiring, and crossover wiring.

5) Take off screws (Ø4 × 10, 2 pcs.)

2. Attachment1) Tighten screws (Ø4 × 10, 2 pcs.) fixing the electrical control box.2) Connect the connectors as original before being removed in item 1.3) Perform power supply wiring, remote controller wiring, and crossover wiring between inside and outside.

NOTEFor drawing of each wire and position of ferrite core, perform wiring same as those before removing. If there is incomplete drawing of wire, short or water leakage of the parts may be caused.

No. Part name Procedure Remarks

Ferrite core for sensor lead

Ferrite core for fan motorDrawing-out port of lead wire

Card edge spacer

Enlarged drawingFix the lead wires with cord clamp so that the lead wires do not slacken at P.C board side. (2 positions)

Cord clamp

As shown in the figure, store PMV lead wire connected with connector assembly so that the connector positions under wire of the terminal.

Details of PMV lead wire drawing

Fix the sensor lead wires firmly with the cord clamp so that they do not touch with the caution plate of the terminal block and they do not slacken at P.C. board side. (3 positions)Arrange the clamp at the position as shown in the figure.

Cord clamp

Fold back the sensor lead wire and fix it surely with the cord clamp.Adhere on the transformer.

Arrow view

Details of sensor lead wire drawing

Be sure that the float switch lead wire positions at inner side of the fan motor lead wire.Cord clampFold back the float switch lead wire and fix surely with cord clamp. (There is no catching-in of P.C. board and lead wire.)

Arrange at position as shown in the figure.Details of fan motor lead wire drawing

118

Toshiba

Page 120: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 119 Tuesday, June 21, 2011 10:41 AM

7 Fan guard 1. Detachment1) Perform work of procedure 1-1.2) Take off screws fixing the fan guard. (Ø4 × 10, [Screws for

plastic molding] 4 pcs.)

NOTEThe specification of fixing screws for the fan guard differs from those of other fixing screws.Therefore keep them separately from other screws.

2. Attachment1) Attach screws for fixing the fan guard. (Ø4 × 10, [Screws for

plastic molding] 4 pcs.)

8 Bell mouth 1. Detachment1) Perform work of procedure 6-1.2) Take off the lead wires of the drain pump, float switch, and

fan motor from the bell mouth.3) Take off fixing screws of the bell mouth. (Ø4 × 10, 4 pcs.)

2. Attachment1) Mount the bell mouth with screws. (Ø4 × 10, 4 pcs.)2) Perform wiring as original before being removed.

NOTEPinch lead wire of the drain pump and float switch with lead wire fixing claws of the bell mouth and perform wiring along the guide.

9 Turbo fan 1. Detachment1) Perform work of procedure 8-1.2) Take off the nut (M6 nut 1 pc.) of the turbo fan.

NOTEUse a box wrench for attachment and detachment of the turbo fan. If using a monkey wrench etc, the other parts may be damaged in work.

2. Attachment1) Insert the turbo fan into the fan motor so that boss of the

turbo fan matches with cut surface of the fan motor, and then tighten it with nut.

NOTETightening torque of turbo fan: 5.9 ± 0.6N•mApply looseness-preventing agent to the nut after tightening.

No. Part name Procedure Remarks

Fan guard

4 screws

Fixing claws for lead wires Bell mouth

Fixing claws for lead wires4 screws

Fan motor fixing M6 nut

Drawing-out port of fan motor lead wire

Turbo fan

119

Toshiba

Page 121: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 120 Tuesday, June 21, 2011 10:41 AM

10 Fan motor 1. Detachment1) Perform work of procedure 9.2) Take off screws fixed with lead holding bracket of the fan

motor. (Ø4 × 10, 2 pcs.)3) Open wiring holding part of the fan motor lead holding

bracket and then take off the fan motor lead wire from the bracket.

4) Take off fixing nuts for the fan motor to remove the fan motor. (M 3 pcs.)

NOTEUse a box wrench for attachment and detachment of the fan motor fixing nuts; otherwise contact or damage for other parts may be caused.

2. Attachment1) Mount the fan motor with the fixing nuts.

NOTE

Tightening torque of turbo fan: 5.9 ± 0.6 N•mApply looseness-preventing agent (as paints) to the nut after tightening.

2) Attach the fan motor lead wire holder.

NOTE• For the fan motor lead wire, fix the lead wire holding bracket

along concave part of the ceiling panel. (There is no catch-in of lead wire and ceiling panel.)

• When fixing the lead wire bracket, tighten fan motor earth together with the lead wire.

• For this work, do not use an electric screwdriver.• Take note the damage of earth terminal.

3) Bend the lead wire holding part and fix the fan motor lead wire.

NOTEBe sure that the lead wire does not come to contact with the heat exchanger.

No. Part name Procedure Remarks

Fixing nut for fan motor

Fixing screw Holding metal fitting for fan motor lead wire

Wiring holding bracket

Fan motor lead wire Concave part of ceiling panel

Fan motor

Fan motor earth wire

120

Toshiba

Page 122: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 121 Tuesday, June 21, 2011 10:41 AM

11 Drain pan 1. Detachment1) Perform works of procedure 4-1 and 8-1.2) Remove the drain cap and extract drain water accumulated

in the drain pan.

NOTEWhen removing the drain cap, be sure to receive drain water with a bucket, etc.

3) Take off screws fixing the drain pan to remove the drain pan. (Ø4×10, 4 pcs.)

2. Attachment1) Insert the drain cap into the drain pan.

NOTEPut a stick or others into hole at center of the drain cap, and then insert the drain cap until it strikes on the socket of the drain pan.

2) Draw each lead wire to the correct positions, and then insert the drain pan into the main unit.

NOTEDraw lead wires of the drain pump and the float switch along the guide of the cabinet. Insert the drain pan along the guides of sensors (TC1, TC2, TCJ) and PMV lead wire.The drain pan and each lead wire are not caught in; otherwise water leakage may be caused.

3) Fix the drain pan with screws. (Ø4 × 10, 4 pcs.)

12 Drain pump assembly

1. Detachment1) Perform work of procedure 11-1.2) Pick up the hose band and slide it from the pump connecting

part to remove the drain hose.3) Take off screws (Ø4 × 10, 3 pcs.) fixing the drain pump

assembly, and then move hooking claw (1 position) of the main body from the drain pump assembly to remove the drain pump assembly.

2. Attachment1) Fix the drain pump assembly as original.

NOTEFor fixing, use a hooking claw (1 position) and screws (3 positions).When screwing, be sure not to run on the hooking claw at main body side.

2) Mount the drain hose and the hose band as original.

NOTEInsert the drain hose up to the end of pump connecting part, and then put the band at white marked position of the hose.

No. Part name Procedure Remarks

2 screws

2 screws

Piping holder Lead wire

Socket of drain pan

Drain pan

Piping holder rib

Drain pump assembly

Hose band

White marked position

Drain hose

Hooking claw for drain pump

Fixing screw for drain pump

121

Toshiba

Page 123: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 122 Tuesday, June 21, 2011 10:41 AM

13 PMV (Pulse Motor Valve)

1. Detachment1) Perform work of procedure 11-1.2) Take off screws (Ø4 × 10, 3 pcs.) fixing the piping cover to

remove the piping cover.3) Cut off binding band that binds the PMV lead wires.4) Peel butyl rubber of PMV a little and remove PMV motor with

a spanner wrench.

NOTEFor attachment and detachment of PMV motor, use a 14 mm or 19 mm spanner wrench.

2. Attachment1) Mount PMV motor with a spanner wrench.

NOTEPMV motor tightening torque: 7.84 ± 0.78N•m

2) Perform wiring of PMV and sensor lead as original.

NOTEArrange each wire as original.

3) Fix the piping cover with screws.

No. Part name Procedure Remarks

3 screws

Piping cover

PMV body PMV nut

<Details of sensor lead wire drawing>As shown in the figure, make draining shape on the lead wire (Black) once, and then fix it with bind band.

Fix the head of bind band and lead wire at inner side of the position in the figure so that they do not stick out to outside.

Insert the sensor lead wires (Red), (Blue), (Black) from the positions in the figure.

Sensor lead (Black)

PMV motor

Details of A part

Heat-insulation pipe (Gas pipe)

Sensor lead (Blue)

Sensor lead (Red)

Heat-insulation pipe (Liquid pipe)

Sensor lead wire (Black)

Do not turn the head of bind band upward.

Sensor lead wire (Red)

Sensor lead wire (Blue)

As shown in the figure, hook the sensor and PMV lead wires to the claw of the No.13 piping cover, and then pass them so that they are stored in this groove.When mounting the piping cover, check each lead wire does not hit PMV motor.

Sensor lead wires (Red) (Blue)

Sensor lead wire (Black)

PMV lead wire

(PMV lead from foot)

(Inner sparkle side)

Bind band

Arrow view B

Bundle each sensor lead wire (Red), (Blue), (Black), and PMV lead wire, fold back toward you at position in the figure, and then fix them with bind band.

122

Toshiba

Page 124: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 123 Tuesday, June 21, 2011 10:41 AM

14 Heat exchanger

1. Detachment1) Recover refrigerant gas.2) Remove the refrigerant pipe at indoor unit side.3) Perform work of procedure 11-1.4) Take off screws (Ø4 × 10, 3 pcs.) fixing the piping cover to

remove the piping cover.5) While holding the heat exchanger, remove fixing band and

fixing screws (Ø4 × 10, 3 pcs.) and then remove the heat exchanger.

2. Attachment1) Mount parts in order, heat exchanger ➝ fixing band ➝

piping cover ➝ drain pan ➝ bell mouth ➝ electrical control box as original.

NOTEArrange wires as original.

2) Attach the removed connectors and wires as original.3) Connect the refrigerant pipe as original, and then perform

vacuuming.

No. Part name Procedure Remarks

Fixing band Fixing band for heat exchanger

2 fixing screws for heat exchange

123

Toshiba

Page 125: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 124 Tuesday, June 21, 2011 10:41 AM

8-3. Slim ductMMD-AP0074SPH✽, AP0094SPH✽, AP0124SPH✽, AP0154SPH✽, AP0184SPH✽

No. Part name Procedure Remarks

REQUIREMENTBe sure to put on gloves at working; otherwise an injury may be caused by parts, etc.

• Before replacement of the parts, be sure to stop operation of the air conditioner and turn off switch of the breaker.

1 1. Detachment1) Push knobs (3 positions) of the air filter hooks toward the

arrow direction to remove the air filter.

2. Attachment1) Insert the air filter surely into the hooking grooves (4

positions) at the opposite side of the hooks, and then fix it to the original position.

NOTEIn case of sucking system from bottom side, installation direction is determined. Install the air filter so that hooks are aligned at discharge side.

2 Plate inlet-APlate inlet-B

1. Detachment1) Take off fixing screws while holding the plate inlet-A with

hands to remove it. (Sucking system from rear side: Ø4 × 10, 8 pcs)(Sucking system from bottom side: Ø4 × 10, 11 pcs)

2) Take off fixing screws while holding the plate inlet-B with hands to remove it. (Ø4 × 10, 6 pcs)

NOTEBe careful that sheeting metal does not fall when removing the plate inlet.

2. Attachment1) Using the screws taken off in procedure 1. 2) of 2, attach

the plate inlets in order of B ➝ A while holding them not to fall down.

[In case of sucking system from rear side]

[In case of sucking system from bottom side]

Air filterPush

Hook

Air filter

Hook Push

[In case of sucking system from rear side]

[In case of sucking system from bottom side]

Plate inlet-A: 11 screws

Plate inlet-B: 6 screws

Plate inlet-B: 6 screws

Plate inlet-A: 8 screws

124

Toshiba

Page 126: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 125 Tuesday, June 21, 2011 10:41 AM

3 E-cover 1. Detachment1) Perform work 1. of 2.2) Take off screws fixing E-cover, and then remove hooks of

the hooking part by lifting up. (Ø4 × 10, 2 pcs)

2. Attachment1) Hang on E-cover to hooks of the hooking part so that it does

not fall down.

NOTEBe sure not to catch TA sensor in the E-cover; otherwise the equipment cannot operate correctly.

2) Using the screws taken off in procedure 1. 2) of 3, attach E-cover while holding it with hands without clearance.

NOTEIf there is clearance, dust may enter in the electrical control box.

4 E-box 1. Detachment1) Perform works 1. of 2 and 1. of 3.2) Remove clamps and tie wrap at upper part of the photo.

(Drain pump incorporated model: 3 positions)(Natural drain model: 2 positions)

3) Take off screws fixing E-box. (Ø4 × 10, 2 pcs)E-box does not fall down under condition that screws are taken off.

4) Remove the E-box over sheeting metal which was fixed with screws.

2. Attachment1) Insert hooks of E-box into the hooking part of the main

body.2) Store E-box as before, and then attach it by using screws

taken off in procedure 1. 3) of 4.

NOTEBe sure to fix surely as before the lead wires of which clamps and tie wrap were taken off.

NOTECheck that lead wires of the drain pump do not reach the fan so that they are not caught in the fan, and then fix them.(In case of drain pump incorporated model)

No. Part name Procedure Remarks

2 screws

TA sensor Hooking part

E-cover

E-cover

Clamp Clamp

2 screwsDrain pumpLead wire:For only drain pump incorporated model

Tie wrap

125

Toshiba

Page 127: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 126 Tuesday, June 21, 2011 10:41 AM

5 P.C. board assembly

1. Detachment1) Perform works 1. of 2, 1. of 3, and 1. of 4.2) Disconnect connectors which are connected from P.C.

board assembly to other parts.

NOTEUnlock the lock of the housing to disconnect the connectors.

CN40: Indoor / Outdoor communication (3P: Blue)Communication terminal block: 2P

CN41: Remote controller terminal (3P: Blue)Remote controller terminal block: 2P

CN67: Power supply terminal (3P: Black)CN100: TC1 sensor (3P: Brown)CN101: TC2 sensor (2P: Black)CN102: TCJ sensor (2P: Red)CN333: Fan motor power supply (5P: White)CN334: Detection of fan motor position (5P: White)Relay connector (CN82): PMV lead (6P: Blue)

(In case of drain pump incorporated model)CN34: Float SW (3P: Red)CN68: Drain pump lead (3P: Blue)3) Unlock the lock of the card edge spacer, and then remove P.C. board assembly.

2. Attachment1) Attach P.C. board assembly to the card edge spacer.2) Using wires connect connectors as before, which were disconnected in procedure 1. 2) of 5.

NOTECheck there is no missing or poor contact of the connectors.

6 Multi blade fan case, fan lower case, fan upper case

1. Detachment1) Perform work 1. of 2.2) Take off hanging hooks at both sides of the lower fan case

to remove fan lower case.3) Remove the upper fan case while taking off hooks of fan

upper case which are hooked to the partition board.4) Loosen hexagonal hole screw of the multi blade fan to

remove multi blade fan from the shaft.If necessary, remove multi blade fan and then remove fan upper case.

2. Attachment1) Determine the position so that multi blade fan positions at

the center of the fan upper case, and then fix it with hexagonal hole screw.

NOTEArrange the multi blade fan so that screws position at the right side against the drain pan assembly.

NOTEFix multi blade fan with torque wrench 4.9 N•m or more.

2) Hook the lower fan case as before and attach it with hooks.

NOTEFinally check whether the multi blade fan turns surely and smoothly or not.

No. Part name Procedure Remarks

P.C. board assembly

Terminal block

Hanging hook

Fan lower caseMulti blade fan

Arrange the multi blade fan so that screws position at the right side against the drain pan assembly.

Drain pan assembly side

126

Toshiba

Page 128: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 127 Tuesday, June 21, 2011 10:41 AM

7 Fan motor 1. Detachment1) Perform works 1. of 2, 1. of 3, 1. of 6.2) Remove lead wires which are connected to the following

connectors of P.C. board assembly.

NOTEUnlock locks of the housing, and then remove the connectors.

CN333: Fan motor power supply (5P: White)CN334: Detection of fan motor (5P: White)Remove tie wrap which fixes lead wires.3) Remove the noise filter from lead wire to detect fan motor

position.4) Take off screws of fan motor fixing bracket.

Earth wires of the motor are tightened together.(Ø5 × 10, 2 pcs)Remove tie wrap which fixes the lead wires.

5) Remove fixing bracket of the fan motor by holding it with hands so that the fan motor does not fall down.

2. Attachment1) Mount the fan motor as before in order, Fan motor ➝ Fixing

bracket of fan motor ➝ Noise filter ➝ Lead wire process ➝ E-cover.

NOTECheck there is no missing or poor contact of the connectors.Check also that the multi blade fan turns surely and smoothly, and check togethertightening of motor earth.

8 Under panel Drain pan assembly

1. Detachment1) Take off the drain cap and drain the drain water

accumulated in the drain pan assembly.In case of natural drain model, drain the drain water by taking off hose band and drain hose.

NOTEWhen taking off drain cap and drain hose, be sure receive drain water in a bucket, etc.

2) Take off screws fixing the under panel while holding it to remove. (Ø4 × 10, 8 pcs)

NOTEBe careful that sheeting metal does not fall when removing the under panel.

3) Pull out the drain pan assy. by holding handle at lower part.

NOTEWhen pulling out the drain pan assy., never pull out the drain socket by drawing it with hands. If doing so, water leak may be caused.

4) Pull out it to some extent, lay hand on the bump at suction side, and then remove the drain pan assembly.

2. Attachment1) Hook and attach the drain pan assy. to the flange at

discharge side, and then push in.2) Using screws taken off in procedure 1. 2) of 8, attach under

panel by holding with hands.3) Attach drain cap, hose band, and drain hose as before,

which were taken off in procedure 1. 1) of 8.

NOTEFinally, be sure to check there is no water leakage from each attached part.

No. Part name Procedure Remarks

Noise filter

Earth lead

Drain cap or drain hose

Never hold and pull the drain socket.

Under panel

Drain pan assembly

127

Toshiba

Page 129: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 128 Tuesday, June 21, 2011 10:41 AM

9 Drain pump, Float switch, Drain hoseOnly for MMD-AP0071SPH to AP0181SPH MMD-0071SPH-C to AP0181SPH-C MMD-0071SPH-K to AP0181SPH-K

1. Detachment1) Perform works in procedures 1. of 2, 1. of 3, 1. of 8.2) Disconnect lead wires which are connected to the following

connectors of P.C. board assembly.

NOTEUnlock locks of the housing to remove the connectors.

CN34: Float SW (3P: Red)CN68: Drain pump lead (3P: Blue)3) Loosen hose band, remove cap of the drain hose, and take

off screws while holding the sheeting metal on which float switch and drain pump are put on. Remove them with care that pipes are not damaged. (Ø4× 10, 2 pcs)

NOTEIf the pipes are damaged, refrigerant leak may be caused.Take out them with great care.

2. Attachment1) Attach ASSY sheeting metal which was removed in procedure 1. 3) of 9 with care that pipes are not

damaged, and then fix it with screws.2) Insert the drain hose into the inlet of drain pump, and then fix it with hose band.

Arrange handle of the hose band at contrary side of heat exchanger side and at direction remote from drain pan assembly.

3) Carry out wiring as before, and then perform work of procedure 2. of 8.

NOTEFinally check whether they correctly operate or not.

10 Evaporator assembly

1. Detachment1) Recover refrigerant, and then remove refrigerant pipes at

indoor unit side.2) Perform works of procedures 1. of 2, 1. of 3, 1. of 8.

Remove sensors.3) Take off screws of the pipe holder, and remove the pipe

holder. (Ø4 × 10, 2 pcs)4) Take off screws of the heat exchanger support board (Pipe

side), and remove the heat exchanger support board (Pipe side). (Ø4 × 10, 4 pcs)

5) Take off screws of the heat exchanger support board (Opposite side) which fixes terminal block of the evaporator assembly. (Ø4 × 10, 2 pcs)

6) Remove the evaporator assembly.

2. Attachment1) Fasten the parts as before in order, Evaporator assembly

➝ Pipe holder ➝ Set sensors ➝ Drain pan assembly ➝ Under panel.

2) Connect the refrigerant pipe as before, and then perform vacuuming.

No. Part name Procedure Remarks

Drain hose

Drain pumpHose band

Float switch

Pipe holder

Heat exchanger support board (Pipe side)

128

Toshiba

Page 130: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 129 Tuesday, June 21, 2011 10:41 AM

8-4. Concealed duct standardMMD-AP0074BH✽, AP0094BH✽, AP0124BH✽, AP0154BH✽, AP0184BH✽, AP0244BH✽, AP0274BH✽, AP0304BH✽, AP0364BH✽, AP0484BH✽, AP0564BH✽

No. Component Procedure Remarks1 Electrical control box 1. Remove the air filter.

2. Remove the two screws of the electrical control box cover.

3. Remove the electrical control box cover.

4. Remove the two screws of the electrical control box.

5. Remove the electrical control box.As the electrical control box is fixed by the hook on the right of the main unit, pull it up once and then toward you to release the hook.

If necessary, remove the TA / TC / TCJ sensors.

2 Sirocco fan 1. Remove the air filter.2. Remove the fan motor

connector.3. Remove the hexagon screws

fixing the fan assembly and main unit.

4. Remove the fan assembly from the main unit. The fan assembly is fixed by three hooks on the upper part of the main unit. Pull it up once and then backward to remove the hooks.

5. Remove the four screws fixing the fan case and cover.

6. Remove the fan cover.7. Loosen the screws fixing the fan

with a hexagon wrench.8. Pull the fan toward the fan case

to remove the fan.

Screws (For fixing the electrical control box and cover)

Electrical control box cover

Screws (For fixing the electrical control box and main unit)

Electrical control box

Hook (both sides)

Hexagon screws (For fixing the fan assembly and main unit)

Hook (On the main unit)

Hook (On the fan assembly)

Fan case Fan fixing screw

FanFan case cover

Fan case cover fixing screw

129

Toshiba

Page 131: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 130 Tuesday, June 21, 2011 10:41 AM

3 Fan motor 1. Remove the fan.2. Remove the hexagon screws of

the fan motor attachment board.3. Remove the fan motor

attachment board. (2 positions)

4 Drain pan 1. Lift down the indoor unit.2. Remove the bottom board fixing

screws.3. Remove the bottom board from

the main unit.4. Remove the screws of the main

unit and drain pan fixing board.5. Remove the drain pan fixing

board from the main unit.6. Pull up and remove the drain

pan.

5 Float switch 1. Remove the drain pan.2. Remove the screw of the float

switch fixing board.3. Remove the plastic nut fixing the

float switch.4. Remove the float switch.

No. Component Procedure Remarks

Fan motor attachment board Fan motor

Fan motor attachment board fixing screw

Bottom board fixing screws

Bottom boardDrain pan fixing board screws

Drain pan fixing board screws

Drain pan fixing board Drain pan

Float switch Float switch fixing board

Float switch fixing screw

Float switch (seen from the opposite side)

Float switch fixing board

Plastic nut

130

Toshiba

Page 132: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 131 Tuesday, June 21, 2011 10:41 AM

6 Drain pump 1. Remove the float switch and drain pan.

2. Remove the screws of the main unit and drain pump fixing board. (3 positions)

3. Remove the three screws of the drain pump and its fixing board.

7 TC / TCJ sensor 1. Remove the five screws fixing the check port cover on the right.

2. Pull and remove the sensor from the sensor holder of the pipe.

8 Heat exchanger 1. Lift down the indoor unit.2. Remove the drain pan.3. Remove the check port cover on

the right.4. Remove the six screws fixing the

check port cover on the left.5. Remove the two screws fixing

the main unit and heat exchanger.

6. Remove the screws on the front and right, fixing the main unit and heat exchanger.

No. Component Procedure Remarks

Drain pump Drain pump holder

Drain pump holder fixing board screws

Screws for drain pump and fixing board

Drain pump holder

Check port cover (Right)

Check port cover fixing screw (Right)

Check port cover (Left)

Check port cover fixing screws (Left)

Heat exchanger fixing screws (Left)

Main unit (Left)

131

Toshiba

Page 133: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 132 Tuesday, June 21, 2011 10:41 AM

8-5. Concealed duct high static pressureMMD-AP0724H✽, AP0964H✽

▼ Replacing the fan motor1 Remove the electrical control cover.

(2 screws)

2 Remove the fan motor lead.(1)Remove the fan motor lead

connector. (3 positions)(2)Remove the fan motor lead from the

terminal board (terminal No. F1 – F3). (3 positions)

3 Remove the TC1 / TC2 / TA / TCJ sensor leads and PMV coil lead from the control circuit board connector.

4 Remove the electrical control box from the side board. (2 screws)

5 Remove the side board from the main unit. (M5 screws, 8 pcs)

6 Remove the three screws fixing the fan assembly, and slide the assembly along the guide rail to pull it out. (3 M5 tap tight screws)

7 Loosen the screws fixing the fan. (M8)

8 Remove the two screws fixing the motor band.

9 Replace the motor.

TC1 / TC2 / TCJ sensor leads

PMV coil lead

TA sensor lead

Electrical control box

Side board

Electrical control box cover

Fan motor lead connector

Fan motor lead

Electrical control box

Terminal board

Screws

Motor band

Fan case

Fan motor

M5 screws, 3 pcsFixing screw

Fan

Guide rail

Motor band

Fan case

Fan motor

M5 screws, 3 pcsFixing screw

Fan

Guide rail

132

Toshiba

Page 134: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 133 Tuesday, June 21, 2011 10:41 AM

8-6. CeilingMMC-AP0154H✽, AP0184H✽, AP0244H✽, AP0274H✽, AP0364H✽, AP0484H✽

No. Component Procedure Remarks1 Intake grille

REQUIREMENTWear gloves when working on it.Failure to observe this precaution may cause injury due to components, etc.

1. Removing1) Turn off the air conditioner and the breaker switch.2) Slide the air intake grille fixing knobs (two

positions) toward the arrow direction, and then open the air intake grille.

3) Slide the knob toward the intake grille to hang the grille.

4) Remove the hinge of the air intake grille.When removing the hinge, push the center hook with a flat-head driver or the like.

2. Attaching1) Hook the hinge of the air intake grille into the hole

of the main unit.Make sure that the hook is hooked firmly.

2) Fix the screws of air intake grille fixing knob on a side of each filter.

2 Electrical control cover 1. Removing

1) Perform Step 1 of 1.2) Loosen the screws fixing the electrical control

cover.(Ø4 X 10, 2)

3) The screw fixing part of the electrical control cover is a U-shaped groove.Slide the electrical control cover toward the fan motor.

2. Attaching1) Insert and close the electrical control cover into

the back of the electrical control box.2) Insert the fixing screws into the U-shaped groove

of the electrical control cover, and tighten the screws.(Ø4 X 10, 2)

Air intake grille fixing knob

Air intake grilleAir filterSlide

Model Knob HingeAP015 – AP027 4 positions 4 positionsAP036 – AP048 6 positions 6 positions

Sliding direction

Knob

Hinge

Screws (2 positions)

133

Toshiba

Page 135: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 134 Tuesday, June 21, 2011 10:41 AM

3 Electrical control box

1. Removing1) Perform Step 1 of 1 and Step 1 of 2.2) Remove the screws of the electrical control box.

(Ø4 X 10, 2)3) Pull down the electrical control box, and hook the

back.

2. Attaching1) Insert the hook of the electrical control box into the

hook part of the main unit.2) Fix the electrical control box with the screws.

(Ø4 X 10, 2)

4 Control circuit board

1. Removing1) Perform Step 1 of 1, Step 1 of 2, and Step 1 of 3.2) Remove the connector connected between the

control circuit board and another component.

NOTEUnlock the housing part before removing the connector.

CN33: Louver motor (5P: White)CN41: Remote controller terminal 2P (3P: Blue)CN67: Power terminal 3P (3P: Black)CN82: PMV (6P: Blue)CN100: TC1 sensor (3P: Brown)CN101: TC2 sensor (2P: Black)CN102: TCJ sensor (2P: Red)CN104: Room temperature sensor (2P: Orange)CN333: Fan motor power (5P: White)CN334: Fan motor position detection (5P: White)

3) Unlock the card edge spacer (6 positions) to remove the control circuit board.

2. Attaching1) Fax the control circuit board onto the card edge

spacer (6 positions).2) Reconnect the connector removed in Step 1.

NOTEMake sure that the connector is securely and firmly connected.

No. Component Procedure Remarks

Screws

134

Toshiba

Page 136: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 135 Tuesday, June 21, 2011 10:41 AM

5 FanShaftBearingCouplingFan case

Number of fans and attachment structure

1. RemovingNOTE

AP036 – AP048 is taken as an example.

1) Perform Step 1 of 1.2) Remove the screw fixing the drain pan to remove

the drain pan.(One drain pan is attached on the pipe removal side.)

3) Remove the hooks on both sides of the fan case (lower).

4) Remove the fan case (lower) from the separation board.

5) Remove the bolts (2 positions) fixing the bearing to remove the bearing from the main unit. (Ø8 X 12, 2).

NOTEThere are two bearing spacers between the cover and base fixing the bearing. Be careful not to lose them.

6) Loosen the screws with square holes of the coupling, and then remove the fan and shaft.

7) Loosen the screws with square holes of the coupling, and then remove the fan and shaft. If necessary, loosen the screws with square holes of the bearing, and then remove the bearing from the shaft.

No. Component Procedure Remarks

Model No. Attachment

AP015 – AP018 2 Attach both sides of the fan motor directly.

AP024 – AP027 3 Use the shaft. Support one side of the shaft with the bearing.

AP036 – AP048 4 Use the shaft. Support the middle part of the shaft with the bearing.

Fan case

Banding band

Drain pan board

Drain pan board fixing screw

Hook

Fan case (lower)

Bearing cover

Bolt

Bearing spacer

135

Toshiba

Page 137: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 136 Tuesday, June 21, 2011 10:41 AM

5 FanShaftBearingCouplingFan case(Continued)

2. Attaching1) Attach the fan to the shaft.

Place the tightening screw on the right side of the fan against the lower panel. (See the picture on the right.)

On the boss of the fan, there is undercut for scratch made when the screw with square hole is attached to the shaft.Fit the shaft scratch to the fan groove.Tighten later.For the fan attaching direction, see the picture on the right.

2) Attach the bearing to the shaft in Step 1 if necessary.On the shaft, there is a groove to fit the attaching position for the bearing. Fit a single face of the coupling to the groove, and then fix with the screw with square hole.

NOTETighten with torque wrench by 2.5 – 3.4 N•m.

3) Insert the shaft with fan into the coupling. Tighten later.

4) Reattach the bearing to the main unit.

NOTEInsert the bearing spacer between the base and cover, and tighten with a bolt.(Ø8 X 12, 2)

5) Tighten the coupling.On the shaft, there is a groove to fit the attaching position for the coupling.Fit a single face of the coupling to the groove, and then fix with the screw with square hole

NOTETighten with torque wrench by 4.9 N•m or more.

6) Position the fan so that the fan is placed on the center against the fan case (upper), and fix with the screw with square hole.

NOTETighten with torque wrench by 4.9 N•m or more.

7) Reattach the fan case (lower).Make sure that the fan rotates smoothly.

No. Component Procedure Remarks

Place the screw part on the right side against the lower panel.

Lower panel

Screw undercut

Shaft

Shaft grooveShaft groove

Coupling

Fan case (upper)

Place the fan on the center of the fan case.

136

Toshiba

Page 138: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 137 Tuesday, June 21, 2011 10:41 AM

6 Fan motor 1. Removing1) Perform Step 1 of 1, Step 1 of 2, and Step 1 of 5.2) Remove the clamp of the lead wire connected to

the following connectors of the control circuit board.

NOTEUnlock the housing part before removing the connector.

CN333: Fan motor power (5P: White)CN334: Fan motor position detection (5P: White)

3) Remove the screw of the metal fitting fixing the fan motor. The earth screws are tightened together. (Ø5 X 10, 2)

4) Hold and remove the fan motor in order not to drop it.

2. Attaching1) Fix the components again in the following order:

Fan motor ➝ Motor fixing metal fittings ➝ Electrical control box cover. Reconnect the connector and earth lead removed in Step 1.

7 Side cover 1. Removing1) Perform Step 1 of 1.2) Remove the screw of the side cover.

(One side: Ø4 X 12 With washer: 1)3) Slide the side cover in the discharge direction to

remove it.

2. Attaching1) Insert the hook of the side cover into the square

hole of the side of the main unit, and slide the cover in the intake direction to attach it.

2) Insert the screw into the side cover. (One side: Ø4 X 12 With washer: 1)

No. Component Procedure Remarks

Fixing metal fittings

Screw

Sliding direction

137

Toshiba

Page 139: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 138 Tuesday, June 21, 2011 10:41 AM

8 Lower panel 1. Removing1) Perform Step 1 of 1 and Step 1 of 7.2) For AP024 – AP048, remove the strengthening

metal fittings. (Ø4 X 12, 1)Remove the screw on the front, and thread it through the square hole of the side. For AP015 – AP018, there is no strengthening metal fitting.

3) Remove the screws from both sides.(One side: Ø4 X 8, 3)

4) Remove the screw of the fan.(Ø4 X 8, 3)

5) Slide the lower panel in the discharge direction to remove it.

NOTESlide it horizontally from the drain pan of the discharge. Applying excessive force may cause breakage.

6) When removing the sensor base, wrap vinyl tape on the tip of a flat-head driver as shown in the following picture, and then insert it into the groove of the side below the sign of the cover.

2. Attaching1) Slide along the drain pan from the discharge to

attach it.2) Insert the screws (strengthening metal fittings for

AP024 – AP048) removed in 1.

No. Component Procedure Remarks

Flat-head driver (Wrap vinyl tape)

Insert into the groove of the side below the

sign

Vinyl tape

Front: Screw endBack: Insert into square hole

Strengthening metal fitting

Screw

138

Toshiba

Page 140: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 139 Tuesday, June 21, 2011 10:41 AM

9 Drain pan 1. Removing1) Perform Step 1 of 1, Step 1 of 7, and Step 1 of 8.2) Remove the drain cap, and then drain water from

the drain pan.

NOTEWhen removing the drain cap, put a bucket or the like for drain water.

3) Pick the hose band, slide from the drain pan connection part, and then remove the drain hose.

4) Remove the thermal insulator attached on the discharge of the drain pan, and then remove the stepped screw.AP015 – AP027 One stepped screwAP036 – AP048 Two stepped screwsThe removed thermal insulator is used when attaching.

5) Slide the drain pan toward the discharge to remove it.

2. Attaching1) Insert the drain cap deep into the drain pan.2) Slide from the discharge, and then hook firmly on

the hook part of the board metal on the fan.3) Insert the stepped screw removed in 1, and attach

the thermal insulator on it.4) Use the hose band to attach the drain hose

removed in 1.

No. Component Procedure Remarks

Drain hose

Hose band

Stepped screw

Thermal insulator

139

Toshiba

Page 141: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 140 Tuesday, June 21, 2011 10:41 AM

10 Heat exchanger PMV motor

1. Removing1) Collect the refrigerant gas.2) Remove the refrigerant pipe from the indoor unit.3) Perform Step 1 of 1, Step 1 of 7, Step 1 of 8 and

Step 1 of 9.Also remove the sensors.

4) Remove the screws fixing the pipe fixing to remove it. (Ø4 X 8, 2)

5) When replacing the PMV motor, peel off the butyl rubber put on the PMV itself until the PMV appears, and loosen the nut fixing the PMV motor with a double spanner to remove it.

6) Hold the heat exchanger and remove the screws fixing the heat exchange separation board to remove it.(Ø4 X 8, 4)

7) Hold the heat exchanger and remove the screws fixing the heat exchanger on the opposite side of the heat exchange separation board to remove the heat exchanger. (Ø4 X 8, 2)

2. Attaching1) Fix the components together with the sensors in

the following order: Heat exchanger ➝ Pipe fixing ➝ Drain pan ➝ Lower panel.

2) Reconnect the refrigerant pipe and purge air.

No. Component Procedure Remarks

Pipe fixing

PMV motorPMV itself

PMV itself

Nut

Heat exchange separation board

140

Toshiba

Page 142: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 141 Tuesday, June 21, 2011 10:41 AM

8-7. Floor standingMMF-AP0154H✽, AP0184H✽, AP0244H✽, AP0274H✽, AP0364H✽, AP0484H✽, AP0564H✽

1. Electrical component assembly

1. Stop the air conditioner and turn off the main power.2. Pull the upper part of the intake grille toward you. Remove the two strings connecting the intake

grille and main unit, and then pull up the intake grille to remove it.3. Follow the procedure below to remove the electrical control box put on the bottom board:

AP015 – AP0271) Remove the screws 1 and 2 on the electrical control box to remove the drip-proof cover.2) Remove the screws 3 and 4 on the front of the electrical control box to remove the electrical control box cover.3) Remove the fan motor connector (9P) from CN083 (White).4) Remove the louver motor connector (3P) from CN033 (Green).5) Remove the remote controller connector (3P) from CN041 (Blue).6) Remove the PMV connector (6P) from CN082 (Blue).7) Remove the three temperature sensors from CN101 (Black), CN102 (Red), and CN104 (Yellow).8) Remove the indoor and outdoor connectors.9) Remove the two screws fixing the electrical control box to the lower cabinet, slide the box to the right, and pull it out toward you.

AP036 – AP0481) Remove the screws 3 and 4 on the front of the electrical control box to remove the electrical control box cover.2) Remove the fan motor connector (9P) from CN083 (White).3) Remove the louver motor connector (3P) from CN033 (Green).4) Remove the remote controller connector (3P) from CN041 (Blue).5) Remove the PMV connector (6P) from CN082 (Blue).6) Remove the three temperature sensors from CN101 (Black), CN102 (Red), and CN104 (Yellow).7) Remove the indoor and outdoor connectors.8) Remove the screws 1 and 2 on the electrical control box.9) Remove the two screws fixing the electrical control box to the lower cabinet, slide the box to the right, and pull it out toward you.* Only AP015 – AP027 models are equipped with a drip-proof cover.

Drip-proof cover

Electrical control box cover

Intake grille

Electrical control box

1

2

141

Toshiba

Page 143: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 142 Tuesday, June 21, 2011 10:41 AM

2. Heat exchanger

1. Perform Step 1 and 2 of Electrical component assembly.2. Remove the two screws fixing the upper cabinet, slide the cabinet upward by approximately 30

mm, and pull it out toward you.3. Follow the procedure below to remove the heat exchanger assembly:

AP015 – AP0271) Remove the relay connector of the PMV lead wire.2) Remove the screws 1 (4 positions) fixing the upper shield and box, and pull the heat exchange assembly out toward you.3) Remove the screws 2 (2 positions) of the heat exchange assembly pulled out, and then remove the upper shield.4) Remove the screws 3 (4 positions) of the heat exchange assembly pulled out, and then remove the evaporator shield.5) Remove the three temperature sensors from the heat exchange assembly, and then the heat exchange assembly itself.

AP036 – AP0481) Remove the relay connector of the PMV lead wire.2) Remove the screws 1 (3 positions) fixing the upper shield and box, and pull the heat exchange assembly out toward you.3) Remove the screws 2 (2 positions) of the heat exchange assembly pulled out, and then remove the upper shield.4) Remove the screws 3 (5 positions) of the heat exchange assembly pulled out, and then remove the evaporator shield.5) Remove the three temperature sensors from the heat exchange assembly, and then the heat exchange assembly itself.* Wear the protective gloves when removing.

Failure to observe this precaution may cause injury

Upper cabinet

1

2

To PMV coilUpper shield

Relay connector

Evaporator shield

Banding band (2 positions)

PMV lead wire

To circuit board CN082 (Blue)

Tube (for waterproof)

Upper shield

To PMV coil

Relay connector

Banding band (2 positions)

PMV lead wire

Evaporator shieldTo circuit board CN082 (Blue)

Tube (for waterproof)

<AP015 – AP027> <AP036 – AP056>

142

Toshiba

Page 144: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 143 Tuesday, June 21, 2011 10:41 AM

3. Fan assembly

1. Perform Step 1 and 2 of Electrical component assembly.2. Perform Step 2 of Heat exchanger.3. Follow the procedure below to remove the fan:

AP015 – AP0271) Cut the banding band fixing the fan motor lead wires, and remove the relay connector in the electrical control box.2) Remove the motor base fixing screws 1 (5 positions).3) Remove the fan (with one screw) of the fan assembly.4) Remove the motor base fixing screws 2 (3 positions), and then the fan motor.

AP036 – AP0561) Cut the banding band fixing the fan motor lead wires, and remove the relay connector in the electrical control box.2) Remove the fixing screws 1 (3 positions) of the shield to remove it.3) Remove the fan ceiling fixing screws 2 (4 positions), and then put out the fan assembly toward you.4) Remove the screws 3 (4 positions) fixing the motor fixing board and reception board.5) Remove the screws (4 per side) fixing the left and right of the bell mouth on the motor, and then remove the fan case (4 screws per

side).6) Remove the fan (with one screw per side) from the fan motor.7) Remove the motor band, and then the fan motor.* Wear the protective gloves when removing.

Failure to observe this precaution may cause injury

<AP015 – AP027> <AP015 – AP027> Fan assembly components

<AP036 – AP056> <AP036 – AP056> Fan assembly components

Fan

Fan motor

Motor base

Fan motor lead wire

Fan motor Motor base Fan

Fan case

Fan ceilingMotor fixing board

Fan (2)

Bell mouth (4)

Fan motor

Motor band

Motor reception boardShield

Fan motor lead wire

143

Toshiba

Page 145: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 144 Tuesday, June 21, 2011 10:41 AM

8-8. Floor standing cabinetMML-AP0074H✽, AP0094H✽, AP0124H✽, AP0154H✽, AP0184H✽, AP0244H✽

1. Removing the electrical control assembly

CAUTIONWear the protective gloves when removing.Failure to observe this precaution may cause injury.

1) Stop the air conditioner and turn off the main power.2) Remove the two intake grilles. (No fixing screw)3) Remove the front panel. (2 M4 screws)4) Remove the discharge grille. (M4 X 20L: 2)5) Remove the control assembly. (3 M4 screws)6) Remove the screw fixing the electrical control assembly to the box, and pull it out toward you.

Discharge grille

Front panel

Control assembly (Remote controller assembly)

Electrical component assembly

M4 screw

Intake grille

144

Toshiba

Page 146: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 145 Tuesday, June 21, 2011 10:41 AM

2. Removing the heat exchanger1) Follow "1. Removing the electrical control assembly" to remove the electrical control assembly.2) Remove the connecting pipes. (Liquid and gas pipes)3) Remove the strengthening board. (2 M4 screws)4) Remove the upper panel.5) Remove the vertical grille. (4 M4 screws)6) Remove the heat exchange shield (front). (3 M4 screws)7) Remove the heat exchange shield (right). (2 M4 screws)8) Remove the screws fixing the heat exchanger. (4 M4 screws)9) Remove the shield on the side of the heat exchanger. (2 M4 screws)10) Slide the heat exchanger to the right, keep the connecting pipe away from the drain pan, and then pull the exchanger upward.

Upper panel

Heat exchange shield (right)

ScrewsStrengthening board

Vertical grille

ScrewsShield

(Remove this before sliding the heat exchanger to the right)

Heat exchange shield (front)

Slide to the right

145

Toshiba

Page 147: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 146 Tuesday, June 21, 2011 10:41 AM

3. Removing the fan assembly1) Follow "2. Removing the heat exchanger" to remove the heat exchanger.2) Remove the nut in the deep right corner of the fan assembly. (M6 nut: 1 position)3) Remove the two screws in the left of the fan assembly. (M4 screw)4) Pull out the fan assembly toward you.

Pull out toward you

Fan assembly

146

Toshiba

Page 148: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 147 Tuesday, June 21, 2011 10:41 AM

9 Exploded Diagram / Service Parts List9-1. 1-way cassette type (YH)MMU-AP0074YH✽, AP0094YH✽, AP0124YH✽

147

Toshiba

Page 149: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 148 Tuesday, June 21, 2011 10:41 AM

148

Toshiba

Page 150: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 149 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMU-AP0074YH-E AP0094YH-E AP0124YH-E

201 43039234 CASE, FAN, UP SIDE 2 2 2202 43039235 CASE, FAN, LOWER 2 2 2203 43151292 SWITCH, FLOAT 1 1 1204 43155178 CAPACITOR 1 1 1205 4312C022 MOTOR, FAN 1 1 1206 43146707 MOTOR, PMV 1 1 1207 43146713 VALVE, PMV 1 1 1208 43120236 FAN, MULTI BLADE 2 2 2209 4314J421 EVAPORATOR ASSY 1 1 1210 4314Q075 DISTRIBUTOR ASSY 1 1 1211 43179117 BAND, HOSE 1 1 1212 43047685 NUT, FLARE, 1/4 IN 1 1 1213 43149355 NUT, FLARE, 3/8, IN 1 1 1214 43049776 SOCKET 1 1 1215 43194077 SOCKET, 1/8 IN 1 1 1216 43070146 HOSE, DRAIN 1 1 1217 43122082 CASING, ASSY 1 1 1218 43172143 DRAIN PAN, INST, ASSY 1 1 1219 43121731 PUMP ASSY 1 1 1220 43109369 GRILLE ASSY, P 1 1 1221 43170211 HOSE, DRAIN 1 1 1222 43107215 HOLDER, SENSOR 1 1 1223 43047609 BONNET 1 1 1224 43049697 BONNET 1 1 1225 43139154 BAND, MOTOR, LEFT 1 1 1226 43139155 BAND, MOTOR, RIGHT 1 1 1227 43139161 BAND, MOTOR, LEFT 1 1 1228 43139162 BAND, MOTOR, RIGHT 1 1 1229 43019904 HOLDER, SENSOR (TS) 2 2 2230 43149314 SHEET, PMV 1 1 1231 43147664 STRAINER 1 1 1232 43147665 STRAINER 1 1 1233 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1234 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1235 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1236 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1237 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1 1

149

Toshiba

Page 151: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 150 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMU-AP0074YH-TR AP0094YH-TR AP0124YH-TR

201 43039234 CASE, FAN, UP SIDE 2 2 2202 43039235 CASE, FAN, LOWER 2 2 2203 43151292 SWITCH, FLOAT 1 1 1204 43155178 CAPACITOR 1 1 1205 4312C022 MOTOR, FAN 1 1 1206 43146707 MOTOR, PMV 1 1 1207 43146713 VALVE, PMV 1 1 1208 43120236 FAN, MULTI BLADE 2 2 2209 4314J421 EVAPORATOR ASSY 1 1 1210 4314Q075 DISTRIBUTOR ASSY 1 1 1211 43179117 BAND, HOSE 1 1 1212 43047685 NUT, FLARE, 1/4 IN 1 1 1213 43149355 NUT, FLARE, 3/8, IN 1 1 1214 43049776 SOCKET 1 1 1215 43194077 SOCKET, 1/8 IN 1 1 1216 43070146 HOSE, DRAIN 1 1 1217 43122082 CASING, ASSY 1 1 1218 43172143 DRAIN PAN, INST, ASSY 1 1 1219 43121731 PUMP ASSY 1 1 1220 43109369 GRILLE ASSY, P 1 1 1221 43170211 HOSE, DRAIN 1 1 1222 43107215 HOLDER, SENSOR 1 1 1223 43047609 BONNET 1 1 1224 43049697 BONNET 1 1 1225 43139154 BAND, MOTOR, LEFT 1 1 1226 43139155 BAND, MOTOR, RIGHT 1 1 1227 43139161 BAND, MOTOR, LEFT 1 1 1228 43139162 BAND, MOTOR, RIGHT 1 1 1229 43019904 HOLDER, SENSOR (TS) 2 2 2230 43149314 SHEET, PMV 1 1 1231 43147664 STRAINER 1 1 1232 43147665 STRAINER 1 1 1233 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1234 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1235 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1236 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1238 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1 1

150

Toshiba

Page 152: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 151 Tuesday, June 21, 2011 10:41 AM

E-Parts

Location No. Part No. Description MMU-AP0074YH-E(TR) AP0094YH-E(TR) AP0124YH-E(TR)

401 43050425 SENSOR ASSY, SERVICE, TC 2 2 2402 43050426 SENSOR, SERVICE, TA 1 1 1403 43150320 SENSOR ASSY, SERVICE, TG 1 1 1404 43158204 TRANSFORMER, TT-13 1 1 1405 43160575 TERMINAL BLOCK, 2P, 20A 1 1 1406 43160583 TERMINAL, 6P 1 1 1407 4316V444 P.C. BOARD ASSY, MCC-1403 1 1 1408 4316V345 P.C. BOARD ASSY, MCC-1520 1 1 1

151

Toshiba

Page 153: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 152 Tuesday, June 21, 2011 10:41 AM

9-2. 1-Way cassette type (SH)

AP015, AP018 AP024

152

Toshiba

Page 154: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 153 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMU-AP0154SH-E AP0184SH-E AP0244SH-E

201 43121736 PUMP, DRAIN, ADP-1409 1 1 1202 43172195 PAN ASSY, DRAIN 1 1 1203 4314J370 REFRIGERATION CYCLE ASSY 1 1204 4314J371 REFRIGERATION CYCLE ASSY 1205 43121742 MOTOR, FAN 1 1 1206 43146707 MOTOR, PMV 1 1 1207 43146714 VALVE, PMV 1 1 1208 43120227 FAN, MULTI BLADE 2 2 2209 43170244 HOSE, DRAIN 1 1 1210 43122084 CASE, FAN, LOWER 2 2 2211 43122085 CASE, FAN, UPPER 2 2 2212 43079249 BAND, HOSE 1 1 1213 43047685 NUT, FLARE, 1/4 IN 1 1214 43049776 SOCKET 1215 43149351 SOCKET 1 1216 43047688 NUT, FLARE, 1/2, IN 1 1217 43149352 NUT, FLARE, 5/8, IN 1218 43149353 SOCKET 1 1219 43149354 SOCKET 1220 43151284 SWITCH, FLOAT 1 1 1221 43139152 BAND, MOTOR 2 2 2222 43179129 CAP DRAIN 1 1 1223 43119481 NUT, PLATE 2 2 2224 43170240 HOSE, DRAIN 1 1 1225 43107215 HOLDER, SENSOR 1 1 1226 43047609 BONNET 1227 43147195 BONNET, 1/2 IN 1 1228 43194029 BONNET 1229 43149355 NUT, FLARE, 3/8, IN 1230 43049697 BONNET 1 1231 43019904 HOLDER, SENSOR (TS) 2 2 2232 43149314 SHEET, PMV 1 1 1233 43179126 RUBBER, PUMP DRAIN 3 3 3234 43162051 BUSHING 1 1 1235 43179149 BAND, HOSE 1 1 1236 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1237 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1238 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1239 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1240 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1 1

153

Toshiba

Page 155: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 154 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMU-AP0154SH-TR AP0184SH-TR AP0244SH-TR

201 43121736 PUMP, DRAIN, ADP-1409 1 1 1202 43172195 PAN ASSY, DRAIN 1 1 1203 4314J370 REFRIGERATION CYCLE ASSY 1 1204 4314J371 REFRIGERATION CYCLE ASSY 1205 43121742 MOTOR, FAN 1 1 1206 43146707 MOTOR, PMV 1 1 1207 43146714 VALVE, PMV 1 1 1208 43120227 FAN, MULTI BLADE 2 2 2209 43170244 HOSE, DRAIN 1 1 1210 43122084 CASE, FAN, LOWER 2 2 2211 43122085 CASE, FAN, UPPER 2 2 2212 43079249 BAND, HOSE 1 1 1213 43047685 NUT, FLARE, 1/4 IN 1 1214 43049776 SOCKET 1215 43149351 SOCKET 1 1216 43047688 NUT, FLARE, 1/2, IN 1 1217 43149352 NUT, FLARE, 5/8, IN 1218 43149353 SOCKET 1 1219 43149354 SOCKET 1220 43151284 SWITCH, FLOAT 1 1 1221 43139152 BAND, MOTOR 2 2 2222 43179129 CAP DRAIN 1 1 1223 43119481 NUT, PLATE 2 2 2224 43170240 HOSE, DRAIN 1 1 1225 43107215 HOLDER, SENSOR 1 1 1226 43047609 BONNET 1227 43147195 BONNET, 1/2 IN 1 1228 43194029 BONNET 1229 43149355 NUT, FLARE, 3/8, IN 1230 43049697 BONNET 1 1231 43019904 HOLDER, SENSOR (TS) 2 2 2232 43149314 SHEET, PMV 1 1 1233 43179126 RUBBER, PUMP DRAIN 3 3 3234 43162051 BUSHING 1 1 1235 43179149 BAND, HOSE 1 1 1236 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1237 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1238 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1239 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1241 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1 1

154

Toshiba

Page 156: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 155 Tuesday, June 21, 2011 10:41 AM

E-Parts

Location No. Part No. Description MMU-AP0154SH-E(TR) AP0184SH-E(TR) AP0244SH-E(TR)

401 43050425 SENSOR ASSY, SERVICE, TC 2 2 2402 43050426 SENSOR, SERVICE, TA 1 1 1403 43150320 SENSOR ASSY, SERVICE, TG 1 1 1404 43160582 TERMINAL, 4P 1 1 1405 43160575 TERMINAL BLOCK, 2P, 20A 1 1 1406 4316V437 P.C. BOARD ASSY, MCC-1402 1 1 1

155

Toshiba

Page 157: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 156 Tuesday, June 21, 2011 10:41 AM

9-3. Compact 4-way cassette typeMMU-AP0074MH✽, AP0094MH✽, AP0124MH✽, AP0154MH✽, AP0184MH✽

AP015, AP018 AP007, AP009, AP012

AP015, AP018AP007, AP009, AP012

AP015, AP018AP007, AP009, AP012

156

Toshiba

Page 158: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 157 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMU-AP0074MH-E AP0094MH-E AP0124MH-E AP0154MH-E AP0184MH-E

201 43120225 FAN, ASSY TURBO 1 1 1 1 1202 43122094 BELLMOUTH 1 1 1 1 1203 43172185 PAN ASSY, DRAIN 1 1204 43172216 PAN ASSY, DRAIN 1 1 1205 43121738 MOTOR, FAN 1 1 1 1 1206 43146707 MOTOR, PMV 1 1 1 1 1207 43146713 VALVE, PMV 1 1 1208 43146714 VALVE, PMV 1 1209 4314J263 REFRIGERATION CYCLE ASSY 1 1210 4314J264 REFRIGERATION CYCLE ASSY 1 1 1211 4314Q006 DISTRIBUTOR ASSY 1 1212 4314Q007 DISTRIBUTOR ASSY 1 1 1213 43047685 NUT, FLARE, 1/4 IN 1 1 1 1 1214 43049776 SOCKET 1 1 1215 43149351 SOCKET 1 1 1 1 1216 43047688 NUT, FLARE, 1/2, IN 1 1217 43149353 SOCKET 1 1218 43047609 BONNET 1 1 1219 43147195 BONNET, 1/2 IN 1 1220 43049697 BONNET 1 1 1 1 1221 43170244 HOSE, DRAIN 1 1 1 1 1222 43079249 BAND, HOSE 1 1 1 1 1223 43060029 FILTER,NOISE 2 2 2 2 2224 43163052 HOLDER, LEAD, FAN MOTOR 1 1 1 1 1225 43119482 COVER, ASSY BODY 1 1 1 1 1226 43170248 HOSE, DRAIN 1 1 1 1 1227 43119483 COVER, PIPE 1 1 1 1 1228 43097212 NUT 1 1 1 1 1229 43107215 HOLDER, SENSOR 1 1 1 1 1230 43019904 HOLDER, SENSOR (TS) 2 2 2 2 2231 43179135 BAND, HOSE 1 1 1 1 1232 43149314 SHEET, PMV 1 1 1 1 1233 43139137 RUBBER, CUSHION 3 3 3 3 3234 43162056 COVER, E-BOX 1 1 1 1 1235 43177001 PUMP, DRAIN 1 1 1 1 1236 43151289 SWITCH, FLOAT 1 1 1 1 1237 43179126 RUBBER, PUMP DRAIN 3 3 3 3 3238 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1 1 1239 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1240 43166004 REMOTE CONTROLLER, SX-

A11JE2 1 1 1 1 1

241 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1 1

242 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1 1 1 1

245 43119475 GUARD FAN 1 1 1 1 1246 43149355 NUT, FLARE, 3/8, IN 1 1 1247 43197155 WASHER 3 3 3 3 3

157

Toshiba

Page 159: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 158 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMU-AP0074MH-TR AP0094MH-TR AP0124MH-TR AP0154MH-TR AP0184MH-TR

201 43120225 FAN, ASSY TURBO 1 1 1 1 1202 43122094 BELLMOUTH 1 1 1 1 1203 43172185 PAN ASSY, DRAIN 1 1204 43172216 PAN ASSY, DRAIN 1 1 1205 43121738 MOTOR, FAN 1 1 1 1 1206 43146707 MOTOR, PMV 1 1 1 1 1207 43146713 VALVE, PMV 1 1 1208 43146714 VALVE, PMV 1 1209 4314J263 REFRIGERATION CYCLE

ASSY 1 1

210 4314J264 REFRIGERATION CYCLE ASSY 1 1 1

211 4314Q006 DISTRIBUTOR ASSY 1 1212 4314Q007 DISTRIBUTOR ASSY 1 1 1213 43047685 NUT, FLARE, 1/4 IN 1 1 1 1 1214 43049776 SOCKET 1 1 1215 43149351 SOCKET 1 1 1 1 1216 43047688 NUT, FLARE, 1/2, IN 1 1217 43149353 SOCKET 1 1218 43047609 BONNET 1 1 1219 43147195 BONNET, 1/2 IN 1 1220 43049697 BONNET 1 1 1 1 1221 43170244 HOSE, DRAIN 1 1 1 1 1222 43079249 BAND, HOSE 1 1 1 1 1223 43060029 FILTER,NOISE 2 2 2 2 2224 43163052 HOLDER, LEAD, FAN

MOTOR 1 1 1 1 1

225 43119482 COVER, ASSY BODY 1 1 1 1 1226 43170248 HOSE, DRAIN 1 1 1 1 1227 43119483 COVER, PIPE 1 1 1 1 1228 43097212 NUT 1 1 1 1 1229 43107215 HOLDER, SENSOR 1 1 1 1 1230 43019904 HOLDER, SENSOR (TS) 2 2 2 2 2231 43179135 BAND, HOSE 1 1 1 1 1232 43149314 SHEET, PMV 1 1 1 1 1233 43139137 RUBBER, CUSHION 3 3 3 3 3234 43162056 COVER, E-BOX 1 1 1 1 1235 43177001 PUMP, DRAIN 1 1 1 1 1236 43151289 SWITCH, FLOAT 1 1 1 1 1237 43179126 RUBBER, PUMP DRAIN 3 3 3 3 3238 43166011 REMOTE CONTROLLER,

SX-A4EE 1 1 1 1 1

239 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1

240 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1

241 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1 1

243 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1 1 1 1

245 43119475 GUARD FAN 1 1 1 1 1246 43149355 NUT, FLARE, 3/8, IN 1 1 1247 43197155 WASHER 3 3 3 3 3

158

Toshiba

Page 160: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 159 Tuesday, June 21, 2011 10:41 AM

E-Parts

Location No. Part No. Description MMU-

AP0074MH-E(TR) AP0094MH-E(TR) AP0124MH-E(TR) AP0154MH-E(TR) AP0184MH-E(TR)401 43050425 SENSOR ASSY,

SERVICE, TA 2 2 2 2 2

402 43050426 SENS0R, SERVICE, TC 1 1 1 1 1

403 43150320 SENSOR ASSY, SERVICE, TG 1 1 1 1 1

404 43160582 TERMINAL, 4P 1 1 1 1 1405 43160575 TERMINAL

BLOCK, 2P, 20A 1 1 1 1 1

406 4316V437 P.C. BOARD ASSY, MCC-1402 1 1 1 1 1

159

Toshiba

Page 161: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 160 Tuesday, June 21, 2011 10:41 AM

9-4. Slim duct typeMMD-AP0074SPH✽, AP0094SPH✽, AP0124SPH✽, AP0154SPH✽, AP0184SPH✽

160

Toshiba

Page 162: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 161 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMD-AP0074SPH-E AP0094SPH-E AP0124SPH-E AP0154SPH-E AP0184SPH-E

201 43121742 MOTOR, FAN 1 1 1 1 1202 43146707 MOTOR, PMV 1 1 1 1 1203 43146713 VALVE, PMV 1 1 1204 43120227 FAN, MULTI BLADE 2 2 2 2 2205 43170244 HOSE, DRAIN 1 1 1 1 1206 4314J426 EVAPORATOR ASSY 1 1207 43122084 CASE, FAN, LOWER 2 2 2 2 2208 43122085 CASE, FAN, UPPER 2 2 2 2 2209 4314J432 EVAPORATOR ASSY 1 1 1210 4314Q082 DISTRIBUTOR ASSY 1 1 1211 4314Q083 DISTRIBUTOR ASSY 1 1212 43100319 PLATE, INLET-B 1 1 1 1 1213 43172183 PAN ASSY, DRAIN 1 1 1 1 1214 43149351 SOCKET 1 1 1 1 1215 43179129 CAP DRAIN 2 2 2 2 2216 43170240 HOSE, DRAIN 1 1 1 1 1217 43100321 FLANGE 1 1 1 1 1218 43049697 BONNET 1 1 1 1 1219 43179135 BAND, HOSE 1 1 1 1 1220 43149314 SHEET, PMV 1 1 1 1 1221 43146714 VALVE, PMV 1 1222 43196109 BUSHING 1 1 1 1 1223 43049776 SOCKET 1 1 1224 43149353 SOCKET 1 1225 43047688 NUT, FLARE, 1/2, IN 1 1226 43149355 NUT, FLARE, 3/8, IN 1 1 1227 43047685 NUT, FLARE, 1/4 IN 1 1 1 1 1228 43147662 STRAINER 1 1 1 1 1229 43047609 BONNET 1 1 1230 43047692 BONNET 1 1231 43100320 PLATE, INLET-A 1 1 1 1 1232 43121735 PUMP, DRAIN, ADP-1409 1 1 1 1 1233 43151302 SWITCH, FLOAT 1 1 1 1 1234 43179126 RUBBER, PUMP DRAIN 3 3 3 3 3235 43060029 FILTER,NOISE 1 1 1 1 1236 43079249 BAND, HOSE 1 1 1 1 1239 43180327 AIR FILTER 1 1 1 1 1241 43166011 REMOTE CONTROLLER,

SX-A4EE 1 1 1 1 1

242 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1

243 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1

244 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1 1

245 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1 1 1 1

161

Toshiba

Page 163: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 162 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMD-

AP0074SPH-TR AP0094SPH-TR AP0124SPH-TR AP0154SPH-TR AP0184SPH-TR201 43121742 MOTOR, FAN 1 1 1 1 1202 43146707 MOTOR, PMV 1 1 1 1 1203 43146713 VALVE, PMV 1 1 1204 43120227 FAN, MULTI BLADE 2 2 2 2 2205 43170244 HOSE, DRAIN 1 1 1 1 1206 4314J426 EVAPORATOR ASSY 1 1207 43122084 CASE, FAN, LOWER 2 2 2 2 2208 43122085 CASE, FAN, UPPER 2 2 2 2 2209 4314J432 EVAPORATOR ASSY 1 1 1210 4314Q082 DISTRIBUTOR ASSY 1 1 1211 4314Q083 DISTRIBUTOR ASSY 1 1212 43100319 PLATE, INLET-B 1 1 1 1 1213 43172183 PAN ASSY, DRAIN 1 1 1 1 1214 43149351 SOCKET 1 1 1 1 1215 43179129 CAP DRAIN 2 2 2 2 2216 43170240 HOSE, DRAIN 1 1 1 1 1217 43100321 FLANGE 1 1 1 1 1218 43049697 BONNET 1 1 1 1 1219 43179135 BAND, HOSE 1 1 1 1 1220 43149314 SHEET, PMV 1 1 1 1 1221 43146714 VALVE, PMV 1 1222 43196109 BUSHING 1 1 1 1 1223 43049776 SOCKET 1 1 1224 43149353 SOCKET 1 1225 43047688 NUT, FLARE, 1/2, IN 1 1226 43149355 NUT, FLARE, 3/8, IN 1 1 1227 43047685 NUT, FLARE, 1/4 IN 1 1 1 1 1228 43147662 STRAINER 1 1 1 1 1229 43047609 BONNET 1 1 1230 43047692 BONNET 1 1231 43100320 PLATE, INLET-A 1 1 1 1 1232 43121735 PUMP, DRAIN, ADP-1409 1 1 1 1 1233 43151302 SWITCH, FLOAT 1 1 1 1 1234 43179126 RUBBER, PUMP DRAIN 3 3 3 3 3235 43060029 FILTER,NOISE 1 1 1 1 1236 43079249 BAND, HOSE 1 1 1 1 1239 43180327 AIR FILTER 1 1 1 1 1241 43166011 REMOTE CONTROLLER,

SX-A4EE 1 1 1 1 1

242 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1

243 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1

244 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1 1

246 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1 1 1 1

162

Toshiba

Page 164: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 163 Tuesday, June 21, 2011 10:41 AM

E-Parts

Location No. Part No. DescriptionMMD-

AP0074SPH-E(TR)

AP0094SPH-E(TR)

AP0124SPH-E(TR)

AP0154SPH-E(TR)

AP0184SPH-E(TR)

401 43050425 SENSOR ASSY, SERVICE, TC 2 2 2 2 2

402 43050426 SENSOR, SERVICE, TA 1 1 1 1 1403 43150320 SENSOR ASSY,

SERVICE, TG 1 1 1 1 1

404 43160575 TERMINAL BLOCK, 2P, 20A 1 1 1 1 1

405 43163057 CLAMP, DOWN 1 1 1 1 1406 43163058 CLAMP, UP 1 1 1 1 1407 4316V437 P.C. BOARD ASSY,

MCC-1402 1 1 1 1 1

408 43160582 TERMINAL, 4P 1 1 1 1 1

163

Toshiba

Page 165: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 164 Tuesday, June 21, 2011 10:41 AM

9-5. Concealed duct standard typeMMD-AP0074BH✽, AP0094BH✽, AP0124BH✽, AP0154BH✽, AP0184BH✽

164

Toshiba

Page 166: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 165 Tuesday, June 21, 2011 10:41 AM

165

Toshiba

Page 167: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 166 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMD-AP0074BH-E AP0094BH-E AP0124BH-E AP0154BH-E AP0184BH-E

201 43120239 FAN, MULTI BLADE 1 1 1 1 1203 4312C021 MOTOR, FAN 1 1 1 1 1204 43096078 BUSHING 1 1 1 1 1205 43196012 BUSHING 2 2 2 2 2206 43146707 MOTOR, PMV 1 1 1 1 1208 43146713 VALVE, PMV 1 1 1209 43146714 VALVE, PMV 1 1212 43180321 AIR FILTER 1 1213 43180322 AIR FILTER 1 1 1214 4314J422 EVAPORATOR ASSY 1 1 1215 4314J423 EVAPORATOR ASSY 1 1218 43079249 BAND, HOSE 1 1 1 1 1221 43047685 NUT, FLARE, 1/4 IN 1 1 1 1 1222 43049776 SOCKET 1 1 1223 43149351 SOCKET 1 1 1 1 1224 43047688 NUT, FLARE, 1/2, IN 1 1226 43149353 SOCKET 1 1228 43070146 HOSE, DRAIN 1 1 1 1 1229 43121747 PUMP ASSY, WIRING 1 1 1 1 1230 43151294 SWITCH, FLOAT 1 1 1 1 1231 43160553 LEAD, MOTOR, FAN 1 1 1 1 1232 43100284 PLATE ASSY, A 1 1 1233 43100285 PLATE ASSY, A 1 1236 43100288 PLATE, B 1 1 1 1 1239 43100291 FLANGE 1 1240 43100292 FLANGE 1 1 1244 43172168 PAN ASSY, DRAIN 1 1245 43172169 PAN ASSY, DRAIN 1 1 1246 4314Q039 DISTRIBUTOR ASSY 1 1 1247 4314Q040 DISTRIBUTOR ASSY 1 1250 43107215 HOLDER, SENSOR 1 1 1 1 1251 43047609 BONNET 1 1 1252 43047692 BONNET 1 1254 43047686 NUT, FLARE, 3/8 IN 1 1 1255 43049697 BONNET 1 1 1 1 1256 43019904 HOLDER, SENSOR (TS) 2 2 2 2 2257 43179110 PLUG 1 1 1 1 1258 43149314 SHEET, PMV 1 1 1 1 1259 43179126 RUBBER, PUMP DRAIN 3 3 3 3 3260 43119468 PLATE ASSY 1 1 1 1 1261 43170233 HOSE, DRAIN 1 1 1 1 1262 43147664 STRAINER 2 2 2 1 1263 43166011 REMOTE CONTROLLER,

SX-A4EE 1 1 1 1 1

264 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1

265 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1

266 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1 1

267 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1 1 1 1

166

Toshiba

Page 168: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 167 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMD-AP0074BH-TR AP0094BH-TR AP0124BH-TR AP0154BH-TR AP0184BH-TR

201 43120239 FAN, MULTI BLADE 1 1 1 1 1203 4312C021 MOTOR, FAN 1 1 1 1 1204 43096078 BUSHING 1 1 1 1 1205 43196012 BUSHING 2 2 2 2 2206 43146707 MOTOR, PMV 1 1 1 1 1208 43146713 VALVE, PMV 1 1 1209 43146714 VALVE, PMV 1 1212 43180321 AIR FILTER 1 1213 43180322 AIR FILTER 1 1 1214 4314J422 EVAPORATOR ASSY 1 1 1215 4314J423 EVAPORATOR ASSY 1 1218 43079249 BAND, HOSE 1 1 1 1 1221 43047685 NUT, FLARE, 1/4 IN 1 1 1 1 1222 43049776 SOCKET 1 1 1223 43149351 SOCKET 1 1 1 1 1224 43047688 NUT, FLARE, 1/2, IN 1 1226 43149353 SOCKET 1 1228 43070146 HOSE, DRAIN 1 1 1 1 1229 43121747 PUMP ASSY, WIRING 1 1 1 1 1230 43151294 SWITCH, FLOAT 1 1 1 1 1231 43160553 LEAD, MOTOR, FAN 1 1 1 1 1232 43100284 PLATE ASSY, A 1 1 1233 43100285 PLATE ASSY, A 1 1236 43100288 PLATE, B 1 1 1 1 1239 43100291 FLANGE 1 1240 43100292 FLANGE 1 1 1244 43172168 PAN ASSY, DRAIN 1 1245 43172169 PAN ASSY, DRAIN 1 1 1246 4314Q039 DISTRIBUTOR ASSY 1 1 1247 4314Q040 DISTRIBUTOR ASSY 1 1250 43107215 HOLDER, SENSOR 1 1 1 1 1251 43047609 BONNET 1 1 1252 43047692 BONNET 1 1254 43047686 NUT, FLARE, 3/8 IN 1 1 1255 43049697 BONNET 1 1 1 1 1256 43019904 HOLDER, SENSOR (TS) 2 2 2 2 2257 43179110 PLUG 1 1 1 1 1258 43149314 SHEET, PMV 1 1 1 1 1259 43179126 RUBBER, PUMP DRAIN 3 3 3 3 3260 43119468 PLATE ASSY 1 1 1 1 1261 43170233 HOSE, DRAIN 1 1 1 1 1262 43147664 STRAINER 2 2 2 1 1263 43166011 REMOTE CONTROLLER,

SX-A4EE 1 1 1 1 1

264 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1

265 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1

266 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1 1

268 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1 1 1 1

167

Toshiba

Page 169: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 168 Tuesday, June 21, 2011 10:41 AM

MMD-AP0244BH✽, AP0274BH✽, AP0304BH✽, AP0364BH✽, AP0484BH✽

168

Toshiba

Page 170: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 169 Tuesday, June 21, 2011 10:41 AM

169

Toshiba

Page 171: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 170 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMD-

AP0244BH-E AP0274BH-E AP0304BH-E AP0364BH-E AP0484BH-E201 43120239 FAN, MULTI BLADE 2 2 2 3 3202 4312C020 MOTOR, FAN 1 1 1203 4312C021 MOTOR, FAN 1 1204 43096078 BUSHING 1 1 1 1 1205 43196012 BUSHING 2 2 2 2 2206 43146707 MOTOR, PMV 1 1 1 1 1207 43146723 BODY, PMV 1 1209 43146714 VALVE, PMV 1 1 1210 43180319 AIR FILTER 2 2211 43180320 AIR FILTER 2 2 2216 4314J424 EVAPORATOR ASSY 1 1 1217 4314J425 EVAPORATOR ASSY 1 1218 43079249 BAND, HOSE 1 1 1 1 1219 43125131 BEARING, SHAFT 1 1220 43125162 COUPLING 1 1222 43049776 SOCKET 1 1 1 1 1225 43149352 NUT, FLARE, 5/8, IN 1 1 1 1 1227 43149354 SOCKET 1 1 1 1 1228 43070146 HOSE, DRAIN 1 1 1 1 1229 43121747 PUMP ASSY, WIRING 1 1 1 1 1230 43151294 SWITCH, FLOAT 1 1 1 1 1231 43160553 LEAD, MOTOR, FAN 1 1 1 1 1234 43100286 PLATE ASSY, A 1 1 1235 43100287 PLATE ASSY, A 1 1236 43100288 PLATE, B 1 1 1 1 1237 43100289 FLANGE 1 1238 43100290 FLANGE 1 1 1241 43125163 SHAFT 1 1242 43172166 PAN ASSY, DRAIN 1 1243 43172167 PAN ASSY, DRAIN 1 1 1248 4314Q041 DISTRIBUTOR ASSY 1 1 1249 4314Q042 DISTRIBUTOR ASSY 1 1250 43107215 HOLDER, SENSOR 1 1 1 1 1251 43047609 BONNET 1 1 1 1 1253 43194029 BONNET 1 1 1 1 1254 43047686 NUT, FLARE, 3/8 IN 1 1 1 1 1256 43019904 HOLDER, SENSOR (TS) 2 2 2 2 2257 43179110 PLUG 1 1 1 1 1258 43149314 SHEET, PMV 1 1 1259 43179126 RUBBER, PUMP DRAIN 3 3 3 3 3260 43119468 PLATE ASSY 1 1 1 1 1261 43170233 HOSE, DRAIN 1 1 1 1 1262 43147664 STRAINER 1 1 1 1 1263 43166011 REMOTE CONTROLLER,

SX-A4EE 1 1 1 1 1

264 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1

265 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1

266 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1 1

267 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1 1 1 1

170

Toshiba

Page 172: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 171 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMD-

AP0244BH-TR AP0274BH-TR AP0304BH-TR AP0364BH-TR AP0484BH-TR201 43120239 FAN, MULTI BLADE 2 2 2 3 3202 4312C020 MOTOR, FAN 1 1 1203 4312C021 MOTOR, FAN 1 1204 43096078 BUSHING 1 1 1 1 1205 43196012 BUSHING 2 2 2 2 2206 43146707 MOTOR, PMV 1 1 1 1 1207 43146723 BODY, PMV 1 1209 43146714 VALVE, PMV 1 1 1210 43180319 AIR FILTER 2 2211 43180320 AIR FILTER 2 2 2216 4314J424 EVAPORATOR ASSY 1 1 1217 4314J425 EVAPORATOR ASSY 1 1218 43079249 BAND, HOSE 1 1 1 1 1219 43125131 BEARING, SHAFT 1 1220 43125162 COUPLING 1 1222 43049776 SOCKET 1 1 1 1 1225 43149352 NUT, FLARE, 5/8, IN 1 1 1 1 1227 43149354 SOCKET 1 1 1 1 1228 43070146 HOSE, DRAIN 1 1 1 1 1229 43121747 PUMP ASSY, WIRING 1 1 1 1 1230 43151294 SWITCH, FLOAT 1 1 1 1 1231 43160553 LEAD, MOTOR, FAN 1 1 1 1 1234 43100286 PLATE ASSY, A 1 1 1235 43100287 PLATE ASSY, A 1 1236 43100288 PLATE, B 1 1 1 1 1237 43100289 FLANGE 1 1238 43100290 FLANGE 1 1 1241 43125163 SHAFT 1 1242 43172166 PAN ASSY, DRAIN 1 1243 43172167 PAN ASSY, DRAIN 1 1 1248 4314Q041 DISTRIBUTOR ASSY 1 1 1249 4314Q042 DISTRIBUTOR ASSY 1 1250 43107215 HOLDER, SENSOR 1 1 1 1 1251 43047609 BONNET 1 1 1 1 1253 43194029 BONNET 1 1 1 1 1254 43047686 NUT, FLARE, 3/8 IN 1 1 1 1 1256 43019904 HOLDER, SENSOR (TS) 2 2 2 2 2257 43179110 PLUG 1 1 1 1 1258 43149314 SHEET, PMV 1 1 1259 43179126 RUBBER, PUMP DRAIN 3 3 3 3 3260 43119468 PLATE ASSY 1 1 1 1 1261 43170233 HOSE, DRAIN 1 1 1 1 1262 43147664 STRAINER 1 1 1 1 1263 43166011 REMOTE CONTROLLER,

SX-A4EE 1 1 1 1 1

264 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1

265 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1

266 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1 1

268 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1 1 1 1

171

Toshiba

Page 173: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 172 Tuesday, June 21, 2011 10:41 AM

MMD-AP0564BH✽

172

Toshiba

Page 174: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 173 Tuesday, June 21, 2011 10:41 AM

173

Toshiba

Page 175: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 174 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMD-AP0564BH-E201 43120239 FAN, MULTI BLADE 3203 4312C021 MOTOR, FAN 1204 43096078 BUSHING 1205 43196012 BUSHING 2206 43146707 MOTOR, PMV 1207 43146723 BODY, PMV 1210 43180319 AIR FILTER 2217 4314J425 EVAPORATOR ASSY 1218 43079249 BAND, HOSE 1219 43125131 BEARING, SHAFT 1220 43125162 COUPLING 1222 43049776 SOCKET 1225 43149352 NUT, FLARE, 5/8, IN 1227 43149354 SOCKET 1228 43070146 HOSE, DRAIN 1229 43121747 PUMP ASSY, WIRING 1230 43151294 SWITCH, FLOAT 1231 43160553 LEAD, MOTOR, FAN 1235 43100287 PLATE ASSY, A 1236 43100288 PLATE, B 1237 43100289 FLANGE 1241 43125163 SHAFT 1242 43172166 PAN ASSY, DRAIN 1249 4314Q042 DISTRIBUTOR ASSY 1250 43107215 HOLDER, SENSOR 1251 43047609 BONNET 1253 43194029 BONNET 1254 43047686 NUT, FLARE, 3/8 IN 1256 43019904 HOLDER, SENSOR (TS) 2257 43179110 PLUG 1259 43179126 RUBBER, PUMP DRAIN 3260 43119468 PLATE ASSY 1261 43170233 HOSE, DRAIN 1262 43147664 STRAINER 1263 43166011 REMOTE CONTROLLER, SX-A4EE 1264 43166012 REMOTE CONTROLLER, SX-A5EE 1265 43166004 REMOTE CONTROLLER, SX-A11JE2 1266 43166006 REMOTE CONTROLLER, WH-H1JE2 1267 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1

174

Toshiba

Page 176: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 175 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMD-AP0564BH-TR201 43120239 FAN, MULTI BLADE 3203 4312C021 MOTOR, FAN 1204 43096078 BUSHING 1205 43196012 BUSHING 2206 43146707 MOTOR, PMV 1207 43146723 BODY, PMV 1210 43180319 AIR FILTER 2217 4314J425 EVAPORATOR ASSY 1218 43079249 BAND, HOSE 1219 43125131 BEARING, SHAFT 1220 43125162 COUPLING 1222 43049776 SOCKET 1225 43149352 NUT, FLARE, 5/8, IN 1227 43149354 SOCKET 1228 43070146 HOSE, DRAIN 1229 43121747 PUMP ASSY, WIRING 1230 43151294 SWITCH, FLOAT 1231 43160553 LEAD, MOTOR, FAN 1235 43100287 PLATE ASSY, A 1236 43100288 PLATE, B 1237 43100289 FLANGE 1241 43125163 SHAFT 1242 43172166 PAN ASSY, DRAIN 1249 4314Q042 DISTRIBUTOR ASSY 1250 43107215 HOLDER, SENSOR 1251 43047609 BONNET 1253 43194029 BONNET 1254 43047686 NUT, FLARE, 3/8 IN 1256 43019904 HOLDER, SENSOR (TS) 2257 43179110 PLUG 1259 43179126 RUBBER, PUMP DRAIN 3260 43119468 PLATE ASSY 1261 43170233 HOSE, DRAIN 1262 43147664 STRAINER 1263 43166011 REMOTE CONTROLLER, SX-A4EE 1264 43166012 REMOTE CONTROLLER, SX-A5EE 1265 43166004 REMOTE CONTROLLER, SX-A11JE2 1266 43166006 REMOTE CONTROLLER, WH-H1JE2 1268 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1

175

Toshiba

Page 177: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 176 Tuesday, June 21, 2011 10:41 AM

E-Parts

176

Toshiba

Page 178: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 177 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. DescriptionMMD-

AP0074BH-E(TR)

AP0094BH-E(TR)

AP0124BH-E(TR)

AP0154BH-E(TR)

AP0184BH-E(TR)

401 43050425 SENSOR ASSY, SERVICE, TC 2 2 2 2 2402 43050426 SENSOR, SERVICE, TA 1 1 1 1 1403 43150320 SENSOR ASSY, SERVICE, TG 1 1 1 1 1404 43158193 REACTOR, CH-43-2Z-T 1 1 1 1 1405 43160575 TERMINAL BLOCK, 2P, 20A 1 1 1 1 1406 4316V438 P.C. BOARD ASSY, MCC-1402 1 1 1 1 1407 43160582 TERMINAL, 4P 1 1 1 1 1

Location No. Part No. DescriptionMMD-

AP0244BH-E(TR)

AP0274BH-E(TR)

AP0304BH-E(TR)

AP0364BH-E(TR)

AP0484BH-E(TR)

401 43050425 SENSOR ASSY, SERVICE, TC 2 2 2 2 2402 43050426 SENSOR, SERVICE, TA 1 1 1 1 1403 43150320 SENSOR ASSY, SERVICE, TG 1 1 1 1 1404 43158193 REACTOR, CH-43-2Z-T 1 1 1 1 1405 43160575 TERMINAL BLOCK, 2P, 20A 1 1 1 1 1406 4316V438 P.C. BOARD ASSY, MCC-1402 1 1 1 1 1407 43160582 TERMINAL, 4P 1 1 1 1 1

Location No. Part No. Description MMD-AP0564BH-E(TR)

401 43050425 SENSOR ASSY, SERVICE, TC 2402 43050426 SENSOR, SERVICE, TA 1403 43150320 SENSOR ASSY, SERVICE, TG 1404 43158193 REACTOR, CH-43-2Z-T 1405 43160575 TERMINAL BLOCK, 2P, 20A 1406 4316V438 P.C. BOARD ASSY, MCC-1402 1407 43160582 TERMINAL, 4P 1

177

Toshiba

Page 179: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 178 Tuesday, June 21, 2011 10:41 AM

9-6. Concealed duct high static pressure typeMMD-AP0184H✽, AP0244H✽, AP0274H✽, AP0364H✽, AP0484H✽

178

Toshiba

Page 180: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 179 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMD-

AP0184H-E AP0244H-E AP0274H-E AP0364H-E AP0484H-E201 4312C014 MOTOR, FAN 1 1202 4312C015 MOTOR, FAN 1203 4312C016 MOTOR, FAN 1204 4312C017 MOTOR, FAN 1205 43146707 MOTOR, PMV 1 1 1 1 1206 43146723 BODY, PMV 1 1207 43146714 VALVE, PMV 1 1 1208 43020352 FAN 1 1 1 1 1209 43020353 FAN 1 1210 4314J416 EVAPORATOR ASSY 1211 4314J417 EVAPORATOR ASSY 1 1 1212 4314J418 EVAPORATOR ASSY 1213 43147658 DISTRIBUTOR ASSY 1214 43147659 DISTRIBUTOR ASSY 1 1215 43147660 DISTRIBUTOR ASSY 1216 43147661 DISTRIBUTOR ASSY 1217 43047685 NUT, FLARE, 1/4 IN 1218 43149355 NUT, FLARE, 3/8, IN 1 1 1 1219 43049776 SOCKET 1 1 1 1220 43149351 SOCKET 1221 43047688 NUT, FLARE, 1/2, IN 1222 43149352 NUT, FLARE, 5/8, IN 1 1 1 1223 43149353 SOCKET 1224 43149354 SOCKET 1 1 1 1228 43107215 HOLDER, SENSOR 1 1 1 1 1229 43047609 BONNET 1 1 1 1230 43147195 BONNET, 1/2 IN 1231 43194029 BONNET 1 1 1 1232 43049697 BONNET 1233 43139154 BAND, MOTOR, LEFT 2 2 2 2 2234 43139155 BAND, MOTOR, RIGHT 2 2 2 2 2235 43019904 HOLDER, SENSOR (TS) 2 2 2 2 2236 43149314 SHEET, PMV 1 1 1237 43147664 STRAINER 1 1238 4314Q043 STRAINER 1 1 1239 43166011 REMOTE CONTROLLER,

SX-A4EE 1 1 1 1 1

240 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1

241 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1

242 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1 1 1 1

179

Toshiba

Page 181: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 180 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMD-

AP0184H-TR AP0244H-TR AP0274H-TR AP0364H-TR AP0484H-TR201 4312C014 MOTOR, FAN 1 1202 4312C015 MOTOR, FAN 1203 4312C016 MOTOR, FAN 1204 4312C017 MOTOR, FAN 1205 43146707 MOTOR, PMV 1 1 1 1 1206 43146723 BODY, PMV 1 1207 43146714 VALVE, PMV 1 1 1208 43020352 FAN 1 1 1 1 1209 43020353 FAN 1 1210 4314J416 EVAPORATOR ASSY 1211 4314J417 EVAPORATOR ASSY 1 1 1212 4314J418 EVAPORATOR ASSY 1213 43147658 DISTRIBUTOR ASSY 1214 43147659 DISTRIBUTOR ASSY 1 1215 43147660 DISTRIBUTOR ASSY 1216 43147661 DISTRIBUTOR ASSY 1217 43047685 NUT, FLARE, 1/4 IN 1218 43149355 NUT, FLARE, 3/8, IN 1 1 1 1219 43049776 SOCKET 1 1 1 1220 43149351 SOCKET 1221 43047688 NUT, FLARE, 1/2, IN 1222 43149352 NUT, FLARE, 5/8, IN 1 1 1 1223 43149353 SOCKET 1224 43149354 SOCKET 1 1 1 1228 43107215 HOLDER, SENSOR 1 1 1 1 1229 43047609 BONNET 1 1 1 1230 43147195 BONNET, 1/2 IN 1231 43194029 BONNET 1 1 1 1232 43049697 BONNET 1233 43139154 BAND, MOTOR, LEFT 2 2 2 2 2234 43139155 BAND, MOTOR, RIGHT 2 2 2 2 2235 43019904 HOLDER, SENSOR (TS) 2 2 2 2 2236 43149314 SHEET, PMV 1 1 1237 43147664 STRAINER 1 1238 4314Q043 STRAINER 1 1 1239 43166011 REMOTE CONTROLLER,

SX-A4EE 1 1 1 1 1

240 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1

241 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1

243 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1 1 1 1

180

Toshiba

Page 182: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 181 Tuesday, June 21, 2011 10:41 AM

E-Parts

Location No. Part No. Description MMD-

AP0184H-E(TR) AP0244H-E(TR) AP0274H-E(TR) AP0364H-E(TR) AP0484H-E(TR)401 43050425 SENSOR ASSY, SERVICE 2 2 2 2 2402 43050426 SENSOR, SERVICE 1 1 1 1 1403 43060859 FUSE BLOCK, 30A, 250V 1 1 1 1 1404 43150320 SENSOR ASSY, SERVICE 1 1 1 1 1405 43154173 RELAY, LY2F-L, AC230V 1 1 1 1 1406 43155206 CAPACITOR 1 1 1 1407 43155208 CAPACITOR 1409 43158204 TRANSFORMER 1 1 1 1 1410 43160575 TERMINAL BLOCK, 2P,

20A 1 1 1 1 1

411 43160576 TERMINAL BLOCK, 4P, 20A 1 1 1 1 1

412 43160577 FUSE, 10A 1 1 1 1 1413 43160582 TERMINAL, 4P 1 1 1 1 1414 4316V444 P.C. BOARD ASSY, MCC-

1403 1 1 1 1 1

415 4316V345 P.C. BOARD ASSY, MCC-1520 1 1 1 1 1

181

Toshiba

Page 183: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 182 Tuesday, June 21, 2011 10:41 AM

MMD-AP0724H✽, AP0964H✽

182

Toshiba

Page 184: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 183 Tuesday, June 21, 2011 10:41 AM

183

Toshiba

Page 185: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 184 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMD-AP0724H-E MMD-AP0964H-E201 4312C023 MOTOR, FAN 3 3202 43146707 MOTOR, PMV 1 1203 43146729 BODY, PMV 1 1204 4314J340 EVAPORATOR ASSY 1 1205 4314Q091 DISTRIBUTOR ASSY 1 1206 43122106 CASE, FAN 3 3207 43120237 FAN 3 3208 43047688 NUT, FLARE, 1/2, IN 1 1209 43149332 SOCKET 1 1210 43107215 HOLDER, SENSOR 1 1211 43147195 BONNET, 1/2 IN 1 1212 43147649 STRAINER 1 1213 43139154 BAND, MOTOR, LEFT 6 6214 43139155 BAND, MOTOR, RIGHT 6 6215 43019904 HOLDER, SENSOR (TS) 2 2216 43149314 SHEET, PMV 1 1217 43147726 STRAINER 1 1218 43166011 REMOTE CONTROLLER, SX-A4EE 1 1219 43166012 REMOTE CONTROLLER, SX-A5EE 1 1220 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1221 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1

Location No. Part No. Description MMD-AP0724H-TR MMD-AP0964H-TR201 4312C023 MOTOR, FAN 3 3202 43146707 MOTOR, PMV 1 1203 43146729 BODY, PMV 1 1204 4314J340 EVAPORATOR ASSY 1 1205 4314Q091 DISTRIBUTOR ASSY 1 1206 43122106 CASE, FAN 3 3207 43120237 FAN 3 3208 43047688 NUT, FLARE, 1/2, IN 1 1209 43149332 SOCKET 1 1210 43107215 HOLDER, SENSOR 1 1211 43147195 BONNET, 1/2 IN 1 1212 43147649 STRAINER 1 1213 43139154 BAND, MOTOR, LEFT 6 6214 43139155 BAND, MOTOR, RIGHT 6 6215 43019904 HOLDER, SENSOR (TS) 2 2216 43149314 SHEET, PMV 1 1217 43147726 STRAINER 1 1218 43166011 REMOTE CONTROLLER, SX-A4EE 1 1219 43166012 REMOTE CONTROLLER, SX-A5EE 1 1220 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1222 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1

184

Toshiba

Page 186: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 185 Tuesday, June 21, 2011 10:41 AM

E-Parts

Location No. Part No. Description MMD-AP0724H-E(TR) MMD-AP0964H-E(TR)401 43050425 SENSOR ASSY, SERVICE 2 2402 43050426 SENSOR, SERVICE 1 1403 43060859 FUSE BLOCK, 30A, 250V 3 3404 43150320 SENSOR ASSY, SERVICE 1 1405 43154173 RELAY, LY2F-L, AC230V 2 2406 43155219 CAPACITOR 3 3407 43158204 TRANSFORMER 1 1408 43160575 TERMINAL BLOCK, 2P, 20A 1 1409 43160576 TERMINAL BLOCK, 4P, 20A 3 3410 43160577 FUSE, 10A 3 3411 43160582 TERMINAL, 4P 1 1412 4316V444 P.C. BOARD ASSY, MCC-1403 1 1413 4316V345 P.C. BOARD ASSY, MCC-1520 1 1414 43060157 TERMINAL BLOCK, 4P 1 1

185

Toshiba

Page 187: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 186 Tuesday, June 21, 2011 10:41 AM

9-7. Ceiling typeMMC-AP0154H✽, AP0184H✽, AP0244H✽, AP0274H✽

186

Toshiba

Page 188: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 187 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMC-

AP0154H-E AP0184H-E AP0244H-E AP0274H-E201 43109407 GRILLE, INLET 2 2202 43109408 GRILLE, INLET 2 2204 43121742 MOTOR, FAN 1 1205 43121743 MOTOR, FAN 1 1206 43146707 MOTOR, PMV 1 1 1 1208 43146714 VALVE, PMV 1 1 1 1209 43120227 FAN, MULTI BLADE 2 2 3 3210 4314J426 EVAPORATOR ASSY 1 1211 4314J427 EVAPORATOR ASSY 1 1213 43122084 CASE, FAN, LOWER 2 2 3 3214 43122085 CASE, FAN, UPPER 2 2 3 3215 43121746 DRIVER A'SSY HORIZONTAL LOUVER 1 1 1 1216 43180314 AIR FILTER 2 2217 43180315 AIR FILTER 2 2218 43108014 BASE, RECEIVER 1 1 1 1219 4314Q079 DISTRIBUTOR ASSY 1 1220 4314Q080 DISTRIBUTOR ASSY 1 1222 43179136 BAND, HOSE 2 2 2 2224 43125162 COUPLING 1 1225 43047685 NUT, FLARE, 1/4 IN 1 1226 43047686 NUT, FLARE, 3/8 IN 1 1227 43049776 SOCKET 1 1228 43149351 SOCKET 1 1229 43047688 NUT, FLARE, 1/2, IN 1 1230 43149352 NUT, FLARE, 5/8, IN 1 1231 43149353 SOCKET 1 1232 43149354 SOCKET 1 1233 43060029 FILTER,NOISE 4 4 4 4235 43149326 COVER, BACK BASE 1 1 1 1236 43125164 SHAFT 1 1238 43125159 BEARING 1 1239 43160556 LEAD, LOUVER HORIZONTAL 1 1 1 1240 43109409 GRILLE A'SSY, HORIZONTAL 1 1241 43109410 GRILLE A'SSY, HORIZONTAL 1 1243 43107252 SHAFT, HOLIZONTAL LOUVER 1 1 1 1244 43107260 SUPPORT, GRILLE HORIZONTAL 1 1 1 1245 43122086 GRILLE A'SSY, VERTICAL 2 2 2 2246 43179129 CAP DRAIN 1 1 1 1247 43107254 H1NGE, GRILLE INLET 4 4 4 4248 43107255 HOOK, GRILLE INLET 2 2 2 2249 43108016 MARK TOSHIBA 1 1 1 1250 43170234 HOSE, DRAIN 1 1 1 1251 43102647 COVER, SIDE (RIGHT) 1 1 1 1252 43102648 COVER, SIDE (LEFT) 1 1 1 1256 43191663 PANEL, UNDER 1 1257 43191664 PANEL, UNDER 1 1259 43107215 HOLDER, SENSOR 1 1 1 1260 43047609 BONNET 1 1261 43147195 BONNET, 1/2 IN 1 1262 43194029 BONNET 1 1263 43049697 BONNET 1 1264 43019904 HOLDER, SENSOR (TS) 2 2 2 2265 43149314 SHEET, PMV 1 1 1 1266 43162049 BUSHING 50DIA 1 1 1 1267 43162050 BUSHING 56DIA 1 1 1 1269 43197189 SCREW, FIX DRAIN PAN 1 1 1 1270 43147664 STRAINER 1 1 1 1271 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1 1272 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1273 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1274 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1275 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1 1 1277 43107285 HOOK, GRILLE INLET 2 2 2 2278 43197202 NUT, FLANGE 2 2 2 2279 43197203 SCREW, PAINT, M3 2 2 2 2

187

Toshiba

Page 189: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 188 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMC-

AP0154H-TR AP0184H-TR AP0244H-TR AP0274H-TR201 43109407 GRILLE, INLET 2 2202 43109408 GRILLE, INLET 2 2204 43121742 MOTOR, FAN 1 1205 43121743 MOTOR, FAN 1 1206 43146707 MOTOR, PMV 1 1 1 1208 43146714 VALVE, PMV 1 1 1 1209 43120227 FAN, MULTI BLADE 2 2 3 3210 4314J426 EVAPORATOR ASSY 1 1211 4314J427 EVAPORATOR ASSY 1 1213 43122084 CASE, FAN, LOWER 2 2 3 3214 43122085 CASE, FAN, UPPER 2 2 3 3215 43121746 DRIVER A'SSY HORIZONTAL LOUVER 1 1 1 1216 43180314 AIR FILTER 2 2217 43180315 AIR FILTER 2 2218 43108014 BASE, RECEIVER 1 1 1 1219 4314Q079 DISTRIBUTOR ASSY 1 1220 4314Q080 DISTRIBUTOR ASSY 1 1222 43179136 BAND, HOSE 2 2 2 2224 43125162 COUPLING 1 1225 43047685 NUT, FLARE, 1/4 IN 1 1226 43047686 NUT, FLARE, 3/8 IN 1 1227 43049776 SOCKET 1 1228 43149351 SOCKET 1 1229 43047688 NUT, FLARE, 1/2, IN 1 1230 43149352 NUT, FLARE, 5/8, IN 1 1231 43149353 SOCKET 1 1232 43149354 SOCKET 1 1233 43060029 FILTER,NOISE 4 4 4 4235 43149326 COVER, BACK BASE 1 1 1 1236 43125164 SHAFT 1 1238 43125159 BEARING 1 1239 43160556 LEAD, LOUVER HORIZONTAL 1 1 1 1240 43109409 GRILLE A'SSY, HORIZONTAL 1 1241 43109410 GRILLE A'SSY, HORIZONTAL 1 1243 43107252 SHAFT, HOLIZONTAL LOUVER 1 1 1 1244 43107260 SUPPORT, GRILLE HORIZONTAL 1 1 1 1245 43122086 GRILLE A'SSY, VERTICAL 2 2 2 2246 43179129 CAP DRAIN 1 1 1 1247 43107254 H1NGE, GRILLE INLET 4 4 4 4248 43107255 HOOK, GRILLE INLET 2 2 2 2249 43108016 MARK TOSHIBA 1 1 1 1250 43170234 HOSE, DRAIN 1 1 1 1251 43102647 COVER, SIDE (RIGHT) 1 1 1 1252 43102648 COVER, SIDE (LEFT) 1 1 1 1256 43191663 PANEL, UNDER 1 1257 43191664 PANEL, UNDER 1 1259 43107215 HOLDER, SENSOR 1 1 1 1260 43047609 BONNET 1 1261 43147195 BONNET, 1/2 IN 1 1262 43194029 BONNET 1 1263 43049697 BONNET 1 1264 43019904 HOLDER, SENSOR (TS) 2 2 2 2265 43149314 SHEET, PMV 1 1 1 1266 43162049 BUSHING 50DIA 1 1 1 1267 43162050 BUSHING 56DIA 1 1 1 1269 43197189 SCREW, FIX DRAIN PAN 1 1 1 1270 43147664 STRAINER 1 1 1 1271 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1 1272 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1273 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1274 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1276 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1 1 1277 43107285 HOOK, GRILLE INLET 2 2 2 2278 43197202 NUT, FLANGE 2 2 2 2279 43197203 SCREW, PAINT, M3 2 2 2 2

188

Toshiba

Page 190: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 189 Tuesday, June 21, 2011 10:41 AM

MMC-AP0364H✽, AP0484H✽

189

Toshiba

Page 191: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 190 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMC-AP0364H-E MMC-AP0484H-E201 43109407 GRILLE, INLET 1 1202 43109408 GRILLE, INLET 2 2203 43121741 MOTOR, FAN 1 1206 43146707 MOTOR, PMV 1 1207 43146723 BODY, PMV 1 1209 43120227 FAN, MULTI BLADE 4 4212 4314J428 EVAPORATOR ASSY 1 1213 43122084 CASE, FAN, LOWER 4 4214 43122085 CASE, FAN, UPPER 4 4215 43121746 DRIVER A'SSY HORIZONTAL LOUVER 1 1216 43180314 AIR FILTER 1 1217 43180315 AIR FILTER 2 2218 43108014 BASE, RECEIVER 1 1221 4314Q081 DISTRIBUTOR ASSY 1 1222 43179136 BAND, HOSE 2 2223 43125131 BEARING, SHAFT 1 1224 43125162 COUPLING 1 1226 43047686 NUT, FLARE, 3/8 IN 1 1227 43049776 SOCKET 1 1230 43149352 NUT, FLARE, 5/8, IN 1 1232 43149354 SOCKET 1 1233 43060029 FILTER,NOISE 4 4235 43149326 COVER, BACK BASE 1 1237 43125165 SHAFT 1 1239 43160556 LEAD, LOUVER HORIZONTAL 1 1242 43109411 GRILLE A'SSY, HORIZONTAL 1 1243 43107252 SHAFT, HOLIZONTAL LOUVER 1 1244 43107260 SUPPORT, GRILLE HORIZONTAL 2 2245 43122086 GRILLE A'SSY, VERTICAL 3 3246 43179129 CAP DRAIN 1 1247 43107254 HINGE, GRILLE INLET 6 6248 43107255 HOOK, GRILLE INLET 3 3249 43108016 MARK TOSHIBA 1 1250 43170234 HOSE, DRAIN 1 1251 43102647 COVER, SIDE (RIGHT) 1 1252 43102648 COVER, SIDE (LEFT) 1 1258 43191665 PANEL, UNDER 1 1259 43107215 HOLDER, SENSOR 1 1260 43047609 BONNET 1 1262 43194029 BONNET 1 1264 43019904 HOLDER, SENSOR (TS) 2 2265 43149314 SHEET, PMV 1 1266 43162049 BUSHING 50DIA 1 1267 43162050 BUSHING 56DIA 1 1268 43139153 SPACER, BEARING 2 2269 43197189 SCREW, FIX DRAIN PAN 2 2270 43147664 STRAINER 1 1271 43166011 REMOTE CONTROLLER, SX-A4EE 1 1272 43166012 REMOTE CONTROLLER, SX-A5EE 1 1273 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1274 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1275 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1277 43107285 HOOK, GRILLE INLET 3 3278 43197202 NUT, FLANGE 3 3279 43197203 SCREW, PAINT, M3 3 3

190

Toshiba

Page 192: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 191 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMC-AP0364H-TR MMC-AP0484H-TR201 43109407 GRILLE, INLET 1 1202 43109408 GRILLE, INLET 2 2203 43121741 MOTOR, FAN 1 1206 43146707 MOTOR, PMV 1 1207 43146723 BODY, PMV 1 1209 43120227 FAN, MULTI BLADE 4 4212 4314J428 EVAPORATOR ASSY 1 1213 43122084 CASE, FAN, LOWER 4 4214 43122085 CASE, FAN, UPPER 4 4215 43121746 DRIVER A'SSY HORIZONTAL LOUVER 1 1216 43180314 AIR FILTER 1 1217 43180315 AIR FILTER 2 2218 43108014 BASE, RECEIVER 1 1221 4314Q081 DISTRIBUTOR ASSY 1 1222 43179136 BAND, HOSE 2 2223 43125131 BEARING, SHAFT 1 1224 43125162 COUPLING 1 1226 43047686 NUT, FLARE, 3/8 IN 1 1227 43049776 SOCKET 1 1230 43149352 NUT, FLARE, 5/8, IN 1 1232 43149354 SOCKET 1 1233 43060029 FILTER,NOISE 4 4235 43149326 COVER, BACK BASE 1 1237 43125165 SHAFT 1 1239 43160556 LEAD, LOUVER HORIZONTAL 1 1242 43109411 GRILLE A'SSY, HORIZONTAL 1 1243 43107252 SHAFT, HOLIZONTAL LOUVER 1 1244 43107260 SUPPORT, GRILLE HORIZONTAL 2 2245 43122086 GRILLE A'SSY, VERTICAL 3 3246 43179129 CAP DRAIN 1 1247 43107254 HINGE, GRILLE INLET 6 6248 43107255 HOOK, GRILLE INLET 3 3249 43108016 MARK TOSHIBA 1 1250 43170234 HOSE, DRAIN 1 1251 43102647 COVER, SIDE (RIGHT) 1 1252 43102648 COVER, SIDE (LEFT) 1 1258 43191665 PANEL, UNDER 1 1259 43107215 HOLDER, SENSOR 1 1260 43047609 BONNET 1 1262 43194029 BONNET 1 1264 43019904 HOLDER, SENSOR (TS) 2 2265 43149314 SHEET, PMV 1 1266 43162049 BUSHING 50DIA 1 1267 43162050 BUSHING 56DIA 1 1268 43139153 SPACER, BEARING 2 2269 43197189 SCREW, FIX DRAIN PAN 2 2270 43147664 STRAINER 1 1271 43166011 REMOTE CONTROLLER, SX-A4EE 1 1272 43166012 REMOTE CONTROLLER, SX-A5EE 1 1273 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1274 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1276 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1277 43107285 HOOK, GRILLE INLET 3 3278 43197202 NUT, FLANGE 3 3279 43197203 SCREW, PAINT, M3 3 3

191

Toshiba

Page 193: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 192 Tuesday, June 21, 2011 10:41 AM

E-Parts

Location No. Part No. Description MMC-

AP0154H-E(TR) AP0184H-E(TR) AP0244H-E(TR) AP0274H-E(TR)401 43050425 SENSOR ASSY, SERVICE, TC 2 2 2 2402 43050426 SENSOR, SERVICE, TA 1 1 1 1403 43150320 SENSOR ASSY, SERVICE, TG 1 1 1 1404 43160582 TERMINAL, 4P 1 1 1 1405 43160575 TERMINAL BLOCK, 2P, 20A 1 1 1 1406 4316V437 P.C. BOARD ASSY, MCC-1402 1 1 1 1

Location No. Part No. Description MMC-

AP0364H-E(TR) AP0484H-E(TR)401 43050425 SENSOR ASSY, SERVICE, TC 2 2402 43050426 SENSOR, SERVICE, TA 1 1403 43150320 SENSOR ASSY, SERVICE, TG 1 1404 43160582 TERMINAL, 4P 1 1405 43160575 TERMINAL BLOCK, 2P, 20A 1 1406 4316V437 P.C. BOARD ASSY, MCC-1402 1 1

192

Toshiba

Page 194: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 193 Tuesday, June 21, 2011 10:41 AM

9-8. Floor standing typeMMF-AP0154H✽, AP0184H✽, AP0244H✽, AP0274H✽

193

Toshiba

Page 195: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 194 Tuesday, June 21, 2011 10:41 AM

MMF-AP0154H✽, AP0184H✽, AP0244H✽, AP0274H✽

194

Toshiba

Page 196: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 195 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMF-

AP0154H-E AP0184H-E AP0244H-E AP0274H-E201 43109392 GRILLE, INLET 2 2 2 2202 43100388 CASE ASSY 1 1 1 1205 4312D004 MOTOR, GEARD 1 1 1 1206 4312C010 MOTOR, FAN 1 1207 4312C011 MOTOR, FAN 1 1210 43146707 MOTOR, PMV 1 1 1 1212 43146726 BODY, PMV 1 1 1 1213 43120229 FAN, MULTI BLADE 1 1 1 1215 43180238 AIR FILTER 1 1 1 1216 43139132 CLAMP, GRILLE 2 2 2 2217 43100389 CABINET ASSY 1 1 1 1219 43101357 PANEL, REMOTE CONTROLER 1 1 1 1220 43101345 COVER, REMOTE CONTROLER 1 1 1 1221 4314J410 EVAPORATOR ASSY 1 1222 4314J411 EVAPORATOR ASSY 1 1225 4300Q077 MAGNET, LOCK 2 2 2 2226 43047685 NUT, FLARE, 1/4 IN 1 1227 43149355 NUT, FLARE, 3/8, IN 1 1228 43049776 SOCKET 1 1229 43149351 SOCKET 1 1230 43047688 NUT, FLARE, 1/2, IN 1 1231 43149352 NUT, FLARE, 5/8, IN 1 1232 43149353 SOCKET 1 1233 43149354 SOCKET 1 1235 43139093 CONNECTION ROD 5 5 5 5236 3759V024 GRILLE ASSY 1 1 1 1237 43109207 GRILLE, OUTLET, VERTICAL 5 5 5 5238 43100373 CABINET, LOWER 1 1 1 1239 4314Q084 DISTRIBUTOR ASSY 1 1240 4314Q085 DISTRIBUTOR ASSY 1 1242 43107215 HOLDER, SENSOR 1 1 1 1243 43047609 BONNET 1 1244 43147195 BONNET, 1/2 IN 1 1245 43194029 BONNET 1 1246 43049697 BONNET 1 1249 43172090 PAN, DRAIN 1 1 1 1250 43197136 WASHER 1 1 1 1251 43109412 GRILLE, OUTLET, HORIZONTAL 5 5 5 5252 43019904 HOLDER, SENSOR (TS) 2 2 2 2253 43149314 SHEET, PMV 1 1 1 1254 43147664 STRAINER 1 1 1 1255 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1 1256 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1257 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1258 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1259 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1 1 1260 43155198 CAPACITOR 1 1261 43155199 CAPACITOR 1 1

195

Toshiba

Page 197: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 196 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMF-

AP0154H-TR AP0184H-TR AP0244H-TR AP0274H-TR201 43109392 GRILLE, INLET 2 2 2 2202 43100388 CASE ASSY 1 1 1 1205 4312D004 MOTOR, GEARD 1 1 1 1206 4312C010 MOTOR, FAN 1 1207 4312C011 MOTOR, FAN 1 1210 43146707 MOTOR, PMV 1 1 1 1212 43146726 BODY, PMV 1 1 1 1213 43120229 FAN, MULTI BLADE 1 1 1 1215 43180238 AIR FILTER 1 1 1 1216 43139132 CLAMP, GRILLE 2 2 2 2217 43100389 CABINET ASSY 1 1 1 1219 43101357 PANEL, REMOTE CONTROLER 1 1 1 1220 43101345 COVER, REMOTE CONTROLER 1 1 1 1221 4314J410 EVAPORATOR ASSY 1 1222 4314J411 EVAPORATOR ASSY 1 1225 4300Q077 MAGNET, LOCK 2 2 2 2226 43047685 NUT, FLARE, 1/4 IN 1 1227 43149355 NUT, FLARE, 3/8, IN 1 1228 43049776 SOCKET 1 1229 43149351 SOCKET 1 1230 43047688 NUT, FLARE, 1/2, IN 1 1231 43149352 NUT, FLARE, 5/8, IN 1 1232 43149353 SOCKET 1 1233 43149354 SOCKET 1 1235 43139093 CONNECTION ROD 5 5 5 5236 3759V024 GRILLE ASSY 1 1 1 1237 43109207 GRILLE, OUTLET, VERTICAL 5 5 5 5238 43100373 CABINET, LOWER 1 1 1 1239 4314Q084 DISTRIBUTOR ASSY 1 1240 4314Q085 DISTRIBUTOR ASSY 1 1242 43107215 HOLDER, SENSOR 1 1 1 1243 43047609 BONNET 1 1244 43147195 BONNET, 1/2 IN 1 1245 43194029 BONNET 1 1246 43049697 BONNET 1 1249 43172090 PAN, DRAIN 1 1 1 1250 43197136 WASHER 1 1 1 1251 43109412 GRILLE, OUTLET, HORIZONTAL 5 5 5 5252 43019904 HOLDER, SENSOR (TS) 2 2 2 2253 43149314 SHEET, PMV 1 1 1 1254 43147664 STRAINER 1 1 1 1255 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1 1256 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1257 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1258 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1260 43155198 CAPACITOR 1 1261 43155199 CAPACITOR 1 1262 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1 1 1

196

Toshiba

Page 198: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 197 Tuesday, June 21, 2011 10:41 AM

MMF-AP0364H✽, AP0484H✽, AP0564H✽

197

Toshiba

Page 199: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 198 Tuesday, June 21, 2011 10:41 AM

MMF-AP0364H✽, AP0484H✽, AP0564H✽

198

Toshiba

Page 200: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 199 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMF-AP0364H-E AP0484H-E AP0564H-E

201 43109392 GRILLE, INLET 2 2 2203 43102650 CASE ASSY 1 1 1204 43155180 CAPACITOR 1 1 1205 4312D004 MOTOR, GEARD 1 1 1208 4312C012 MOTOR, FAN 1209 4312C013 MOTOR, FAN 1 1210 43146707 MOTOR, PMV 1 1 1211 43146723 BODY, PMV 1 1 1214 43120230 FAN, MULTI BLADE 2 2 2215 43180238 AIR FILTER 1 1 1216 43139132 CLAMP, GRILLE 2 2 2218 43100390 CABINET ASSY 1 1 1219 43101357 PANEL, REMOTE CONTROLER 1 1 1220 43101345 COVER, REMOTE CONTROLER 1 1 1223 4314J412 EVAPORATOR ASSY 1 1 1225 4300Q077 MAGNET, LOCK 2 2 2227 43149355 NUT, FLARE, 3/8, IN 1 1 1228 43049776 SOCKET 1 1 1231 43149352 NUT, FLARE, 5/8, IN 1 1 1233 43149354 SOCKET 1 1 1235 43139093 CONNECTION ROD 5 5 5236 3759V024 GRILLE ASSY 1 1 1237 43109207 GRILLE, OUTLET, VERTICAL 5 5 5238 43100373 CABINET, LOWER 1 1 1241 4314Q086 DISTRIBUTOR ASSY 1 1 1242 43107215 HOLDER, SENSOR 1 1 1243 43047609 BONNET 1 1 1245 43194029 BONNET 1 1 1247 43139154 BAND, MOTOR, LEFT 2 2 2248 43139155 BAND, MOTOR, RIGHT 2 2 2249 43172090 PAN, DRAIN 1 1 1250 43197136 WASHER 1 1 1251 43109412 GRILLE, OUTLET, HORIZONTAL 5 5 5252 43019904 HOLDER, SENSOR (TS) 2 2 2253 43149314 SHEET, PMV 1 1 1254 43147664 STRAINER 1 1 1255 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1256 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1257 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1258 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1259 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1 1

199

Toshiba

Page 201: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 200 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MMF-AP0364H-TR AP0484H-TR AP0564H-TR

201 43109392 GRILLE, INLET 2 2 2203 43102650 CASE ASSY 1 1 1204 43155180 CAPACITOR 1 1 1205 4312D004 MOTOR, GEARD 1 1 1208 4312C012 MOTOR, FAN 1209 4312C013 MOTOR, FAN 1 1210 43146707 MOTOR, PMV 1 1 1211 43146723 BODY, PMV 1 1 1214 43120230 FAN, MULTI BLADE 2 2 2215 43180238 AIR FILTER 1 1 1216 43139132 CLAMP, GRILLE 2 2 2218 43100390 CABINET ASSY 1 1 1219 43101357 PANEL, REMOTE CONTROLER 1 1 1220 43101345 COVER, REMOTE CONTROLER 1 1 1223 4314J412 EVAPORATOR ASSY 1 1 1225 4300Q077 MAGNET, LOCK 2 2 2227 43149355 NUT, FLARE, 3/8, IN 1 1 1228 43049776 SOCKET 1 1 1231 43149352 NUT, FLARE, 5/8, IN 1 1 1233 43149354 SOCKET 1 1 1235 43139093 CONNECTION ROD 5 5 5236 3759V024 GRILLE ASSY 1 1 1237 43109207 GRILLE, OUTLET, VERTICAL 5 5 5238 43100373 CABINET, LOWER 1 1 1241 4314Q086 DISTRIBUTOR ASSY 1 1 1242 43107215 HOLDER, SENSOR 1 1 1243 43047609 BONNET 1 1 1245 43194029 BONNET 1 1 1247 43139154 BAND, MOTOR, LEFT 2 2 2248 43139155 BAND, MOTOR, RIGHT 2 2 2249 43172090 PAN, DRAIN 1 1 1250 43197136 WASHER 1 1 1251 43109412 GRILLE, OUTLET, HORIZONTAL 5 5 5252 43019904 HOLDER, SENSOR (TS) 2 2 2253 43149314 SHEET, PMV 1 1 1254 43147664 STRAINER 1 1 1255 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1256 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1257 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1258 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1262 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1 1

200

Toshiba

Page 202: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 201 Tuesday, June 21, 2011 10:41 AM

E-Parts

Location No. Part No. Description MMF-

AP0154H-E(TR) AP0184H-E(TR) AP0244H-E(TR) AP0274H-E(TR)401 43050425 SENSOR ASSY, SERVICE 2 2 2 2402 43050426 SENSOR, SERVICE 1 1 1 1403 43150320 SENSOR ASSY, SERVICE 1 1 1 1404 43158204 TRANSFORMER 1 1 1 1405 43160575 TERMINAL BLOCK, 2P, 20A 1 1 1 1406 43160582 TERMINAL, 4P 1 1 1 1407 4316V444 P.C. BOARD ASSY, MCC-1403 1 1 1 1408 4316V345 P.C. BOARD ASSY, MCC-1520 1 1 1 1

Location No. Part No. Description MMF-

AP0364H-E(TR) AP0484H-E(TR) AP0564H-E(TR)401 43050425 SENSOR ASSY, SERVICE 2 2 2402 43050426 SENSOR, SERVICE 1 1 1403 43150320 SENSOR ASSY, SERVICE 1 1 1404 43158204 TRANSFORMER 1 1 1405 43160575 TERMINAL BLOCK, 2P, 20A 1 1 1406 43160582 TERMINAL, 4P 1 1 1407 4316V444 P.C. BOARD ASSY, MCC-1403 1 1 1408 4316V345 P.C. BOARD ASSY, MCC-1520 1 1 1

201

Toshiba

Page 203: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 202 Tuesday, June 21, 2011 10:41 AM

9-9. Floor standing concealed typeMML-AP0074BH✽, AP0094BH✽, AP0124BH✽, AP0154BH✽, AP0184BH✽

202

Toshiba

Page 204: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 203 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MML-

AP0074BH-E AP0094BH-E AP0124BH-E AP0154BH-E AP0184BH-E201 43723020 CASE, FAN, LEFT 1 1 1 2 2202 43126119 CASE, FAN, RIGHT 1 1 1 2 2203 43155179 CAPACITOR 1 1 1205 43155191 CAPACITOR 1 1206 4312C008 MOTOR, FAN 1 1207 4312C024 MOTOR, FAN 1 1 1208 43146707 MOTOR, PMV 1 1 1 1 1209 43146713 VALVE, PMV 1 1 1210 43146726 BODY, PMV 1 1211 43120232 FAN, MULTI BLADE 1 1 1 2 2212 43180294 FILTER 1 1 1213 43180295 FILTER 1 1214 43170206 CATCH, DRAIN 1 1 1 1 1215 4314J429 EVAPORATOR ASSY 1 1 1216 4314J430 EVAPORATOR ASSY 1 1218 4314Q035 DISTRIBUTOR ASSY 1 1 1219 4314Q036 DISTRIBUTOR ASSY 1 1221 43047685 NUT, FLARE, 1/4 IN 1 1 1 1 1222 43149355 NUT, FLARE, 3/8, IN 1 1 1223 43049776 SOCKET 1 1 1224 43149351 SOCKET 1 1 1 1 1225 43047688 NUT, FLARE, 1/2, IN 1 1227 43149353 SOCKET 1 1229 43122046 PLATE-WIND 2 2 2230 43170197 HOSE ASSY 1 1 1 1 1231 43107215 HOLDER, SENSOR 1 1 1 1 1232 43047609 BONNET 1 1 1233 43147195 BONNET, 1/2 IN 1 1235 43049697 BONNET 1 1 1 1 1236 43139154 BAND, MOTOR, LEFT 2 2 2 2 2237 43139155 BAND, MOTOR, RIGHT 2 2 2 2 2238 43122104 BASE, MOTOR 1 1 1 1 1239 43019904 HOLDER, SENSOR (TS) 2 2 2 2 2240 43170207 STRAINER 1 1 1 1 1241 43111311 HINS 1 1 1 1 1242 43149314 SHEET, PMV 1 1 1 1 1243 43147664 STRAINER 1 1244 43147724 STRAINER 1 1 1245 43166011 REMOTE CONTROLLER, SX-

A4EE 1 1 1 1 1

246 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1

247 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1

248 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1 1

249 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1 1 1 1 1

251 4314Q043 STRAINER 1 1 1

203

Toshiba

Page 205: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 204 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MML-

AP0074BH-TR AP0094BH-TR AP0124BH-TR AP0154BH-TR AP0184BH-TR201 43723020 CASE, FAN, LEFT 1 1 1 2 2202 43126119 CASE, FAN, RIGHT 1 1 1 2 2203 43155179 CAPACITOR 1 1 1205 43155191 CAPACITOR 1 1206 4312C008 MOTOR, FAN 1 1207 4312C024 MOTOR, FAN 1 1 1208 43146707 MOTOR, PMV 1 1 1 1 1209 43146713 VALVE, PMV 1 1 1210 43146726 BODY, PMV 1 1211 43120232 FAN, MULTI BLADE 1 1 1 2 2212 43180294 FILTER 1 1 1213 43180295 FILTER 1 1214 43170206 CATCH, DRAIN 1 1 1 1 1215 4314J429 EVAPORATOR ASSY 1 1 1216 4314J430 EVAPORATOR ASSY 1 1218 4314Q035 DISTRIBUTOR ASSY 1 1 1219 4314Q036 DISTRIBUTOR ASSY 1 1221 43047685 NUT, FLARE, 1/4 IN 1 1 1 1 1222 43149355 NUT, FLARE, 3/8, IN 1 1 1223 43049776 SOCKET 1 1 1224 43149351 SOCKET 1 1 1 1 1225 43047688 NUT, FLARE, 1/2, IN 1 1227 43149353 SOCKET 1 1229 43122046 PLATE-WIND 2 2 2230 43170197 HOSE ASSY 1 1 1 1 1231 43107215 HOLDER, SENSOR 1 1 1 1 1232 43047609 BONNET 1 1 1233 43147195 BONNET, 1/2 IN 1 1235 43049697 BONNET 1 1 1 1 1236 43139154 BAND, MOTOR, LEFT 2 2 2 2 2237 43139155 BAND, MOTOR, RIGHT 2 2 2 2 2238 43122104 BASE, MOTOR 1 1 1 1 1239 43019904 HOLDER, SENSOR (TS) 2 2 2 2 2240 43170207 STRAINER 1 1 1 1 1241 43111311 HINS 1 1 1 1 1242 43149314 SHEET, PMV 1 1 1 1 1243 43147664 STRAINER 1 1244 43147724 STRAINER 1 1 1245 43166011 REMOTE CONTROLLER, SX-

A4EE 1 1 1 1 1

246 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1

247 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1

248 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1 1

250 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1 1 1 1 1

251 4314Q043 STRAINER 1 1 1

204

Toshiba

Page 206: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 205 Tuesday, June 21, 2011 10:41 AM

MML-AP0244BH✽

205

Toshiba

Page 207: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 206 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MML-AP0244BH-E201 43723020 CASE, FAN, LEFT 2202 43126119 CASE, FAN, RIGHT 2204 43155171 CAPACITOR 1206 4312C008 MOTOR, FAN 1208 43146707 MOTOR, PMV 1210 43146726 BODY, PMV 1211 43120232 FAN, MULTI BLADE 2213 43180295 FILTER 1214 43170206 CATCH, DRAIN 1217 4314J431 EVAPORATOR ASSY 1220 4314Q037 DISTRIBUTOR ASSY 1222 43149355 NUT, FLARE, 3/8, IN 1223 43049776 SOCKET 1226 43149352 NUT, FLARE, 5/8, IN 1228 43149354 SOCKET 1230 43170197 HOSE ASSY 1231 43107215 HOLDER, SENSOR 1232 43047609 BONNET 1234 43194029 BONNET 1236 43139154 BAND, MOTOR, LEFT 2237 43139155 BAND, MOTOR, RIGHT 2238 43122104 BASE, MOTOR 1239 43019904 HOLDER, SENSOR (TS) 2240 43170207 STRAINER 1241 43111311 HINS 1242 43149314 SHEET, PMV 1243 43147664 STRAINER 1245 43166011 REMOTE CONTROLLER, SX-A4EE 1246 43166012 REMOTE CONTROLLER, SX-A5EE 1247 43166004 REMOTE CONTROLLER, SX-A11JE2 1248 43166006 REMOTE CONTROLLER, WH-H1JE2 1249 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1

Location No. Part No. Description MML-AP0244BH-TR201 43723020 CASE, FAN, LEFT 2202 43126119 CASE, FAN, RIGHT 2204 43155171 CAPACITOR 1206 4312C008 MOTOR, FAN 1208 43146707 MOTOR, PMV 1210 43146726 BODY, PMV 1211 43120232 FAN, MULTI BLADE 2213 43180295 FILTER 1214 43170206 CATCH, DRAIN 1217 4314J431 EVAPORATOR ASSY 1220 4314Q037 DISTRIBUTOR ASSY 1222 43149355 NUT, FLARE, 3/8, IN 1223 43049776 SOCKET 1226 43149352 NUT, FLARE, 5/8, IN 1228 43149354 SOCKET 1230 43170197 HOSE ASSY 1231 43107215 HOLDER, SENSOR 1232 43047609 BONNET 1234 43194029 BONNET 1236 43139154 BAND, MOTOR, LEFT 2237 43139155 BAND, MOTOR, RIGHT 2238 43122104 BASE, MOTOR 1239 43019904 HOLDER, SENSOR (TS) 2240 43170207 STRAINER 1241 43111311 HINS 1242 43149314 SHEET, PMV 1243 43147664 STRAINER 1245 43166011 REMOTE CONTROLLER, SX-A4EE 1246 43166012 REMOTE CONTROLLER, SX-A5EE 1247 43166004 REMOTE CONTROLLER, SX-A11JE2 1248 43166006 REMOTE CONTROLLER, WH-H1JE2 1250 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1

206

Toshiba

Page 208: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 207 Tuesday, June 21, 2011 10:41 AM

E-Parts

Location No. Part No. DescriptionMML-

AP0074BH-E(TR)

AP0094BH-E(TR)

AP0124BH-E(TR)

AP0154BH-E(TR)

AP0184BH-E(TR)

401 43050425 SENSOR ASSY, SERVICE, TC 2 2 2 2 2402 43050426 SENSOR, SERVICE, TA 1 1 1 1 1403 43150320 SENSOR ASSY, SERVICE, TG 1 1 1 1 1404 43158204 TRANSFORMER 1 1 1 1 1405 43160575 TERMINAL BLOCK, 2P, 20A 1 1 1 1 1406 43160582 TERMINAL, 4P 1 1 1 1 1407 4316V444 P.C. BOARD ASSY, MCC-1403 1 1 1 1 1408 4316V345 P.C. BOARD ASSY, MCC-1520 1 1 1 1 1

Location No. Part No. Description MML-AP0244BH-E(TR)

401 43050425 SENSOR ASSY, SERVICE, TC 2402 43050426 SENSOR, SERVICE, TA 1403 43150320 SENSOR ASSY, SERVICE, TG 1404 43158204 TRANSFORMER 1405 43160575 TERMINAL BLOCK, 2P, 20A 1406 43160582 TERMINAL, 4P 1407 4316V444 P.C. BOARD ASSY, MCC-1403 1408 4316V345 P.C. BOARD ASSY, MCC-1520 1

207

Toshiba

Page 209: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 208 Tuesday, June 21, 2011 10:41 AM

9-10.Floor standing cabinet typeMML-AP0074H✽, AP0094H✽, AP0124H✽, AP0154H✽, AP0184H✽

208

Toshiba

Page 210: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 209 Tuesday, June 21, 2011 10:41 AM

MML-AP0074H✽, AP0094H✽, AP0124H✽, AP0154H✽, AP0184H✽

209

Toshiba

Page 211: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 210 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MML-

AP0074H-E AP0094H-E AP0124H-E AP0154H-E AP0184H-E201 43723020 CASE, FAN, LEFT 2 2 2 2 2202 43723019 CASE, FAN, RIGHT 2 2 2 2203 43126119 CASE, FAN, RIGHT 2204 43109394 GRILL, INLET, WHITE 2 2 2 2 2206 43155190 CAPACITOR 1 1207 43155171 CAPACITOR 1208 43155195 CAPACITOR 1 1209 4312C007 MOTOR, FAN 1 1210 4312C008 MOTOR, FAN 1211 4312C026 MOTOR, FAN 1 1212 43146707 MOTOR, PMV 1 1 1 1 1213 43146713 VALVE, PMV 1 1214 43146726 BODY, PMV 1 1 1215 43120228 FAN, MULTI BLADE 2 2 2 2216 43120232 FAN, MULTI BLADE 2217 43180280 AIR FILTER 2 2 2 2 2218 43101346 FRAME, WHITE 1 1 1 1 1219 43101347 COVER, CONTROL PANEL, WHITE 1 1 1 1 1220 43172101 PAN, DRAIN 1 1 1 1 1221 43100366 PANEL, FRONT 1 1 1 1 1222 4314J419 EVAPORATOR ASSY 1 1 1 1224 4314J420 EVAPORATOR ASSY 1225 4314Q044 DISTRIBUTOR ASSY 1 1226 4314Q045 DISTRIBUTOR ASSY 1 1228 4314Q074 DISTRIBUTOR ASSY 1229 43047685 NUT, FLARE, 1/4 IN 1 1 1 1 1230 43149355 NUT, FLARE, 3/8, IN 1 1 1231 43049776 SOCKET 1 1 1232 43149351 SOCKET 1 1 1 1 1233 43047688 NUT, FLARE, 1/2, IN 1 1235 43149353 SOCKET 1 1237 43100374 CABINET, UPPER, WHITE 1 1 1 1 1238 43100228 OUTLET, WHITE 1 1 1 1 1239 43109395 GRILLE, WHITE 3 3 3 3 3240 43109240 GRILLE 1 1 1 1 1241 43170201 HOSE, DRAIN 1 1 1 1 1242 43107215 HOLDER, SENSOR 1 1 1 1 1243 43047609 BONNET 1 1 1244 43047692 BONNET 1 1246 43049697 BONNET 1 1 1 1 1247 43196087 BUSHING, GRILLE 6 6 6 6 6248 43139154 BAND, MOTOR, LEFT 2 2 2 2 2249 43139155 BAND, MOTOR, RIGHT 2 2 2 2 2250 43122104 BASE, MOTOR 1 1 1 1 1251 43019904 HOLDER, SENSOR (TS) 2 2 2 2 2252 43149314 SHEET, PMV 1 1 1 1 1253 43147664 STRAINER 1 1 1 1 1254 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1 1 1255 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1256 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1257 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1 1258 431S8205 OWNER'S MANUAL, MMY-

MAP0804HT8-E 1 1 1 1 1

259 43147649 STRAINER 1 1 1

210

Toshiba

Page 212: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 211 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MML-

AP0074H-TR AP0094H-TR AP0124H-TR AP0154H-TR AP0184H-TR201 43723020 CASE, FAN, LEFT 2 2 2 2 2202 43723019 CASE, FAN, RIGHT 2 2 2 2203 43126119 CASE, FAN, RIGHT 2204 43109394 GRILL, INLET, WHITE 2 2 2 2 2206 43155190 CAPACITOR 1 1207 43155171 CAPACITOR 1208 43155195 CAPACITOR 1 1209 4312C007 MOTOR, FAN 1 1210 4312C008 MOTOR, FAN 1211 4312C026 MOTOR, FAN 1 1212 43146707 MOTOR, PMV 1 1 1 1 1213 43146713 VALVE, PMV 1 1214 43146726 BODY, PMV 1 1 1215 43120228 FAN, MULTI BLADE 2 2 2 2216 43120232 FAN, MULTI BLADE 2217 43180280 AIR FILTER 2 2 2 2 2218 43101346 FRAME, WHITE 1 1 1 1 1219 43101347 COVER, CONTROL PANEL, WHITE 1 1 1 1 1220 43172101 PAN, DRAIN 1 1 1 1 1221 43100366 PANEL, FRONT 1 1 1 1 1222 4314J419 EVAPORATOR ASSY 1 1 1 1224 4314J420 EVAPORATOR ASSY 1225 4314Q044 DISTRIBUTOR ASSY 1 1226 4314Q045 DISTRIBUTOR ASSY 1 1228 4314Q074 DISTRIBUTOR ASSY 1229 43047685 NUT, FLARE, 1/4 IN 1 1 1 1 1230 43149355 NUT, FLARE, 3/8, IN 1 1 1231 43049776 SOCKET 1 1 1232 43149351 SOCKET 1 1 1 1 1233 43047688 NUT, FLARE, 1/2, IN 1 1235 43149353 SOCKET 1 1237 43100374 CABINET, UPPER, WHITE 1 1 1 1 1238 43100228 OUTLET, WHITE 1 1 1 1 1239 43109395 GRILLE, WHITE 3 3 3 3 3240 43109240 GRILLE 1 1 1 1 1241 43170201 HOSE, DRAIN 1 1 1 1 1242 43107215 HOLDER, SENSOR 1 1 1 1 1243 43047609 BONNET 1 1 1244 43047692 BONNET 1 1246 43049697 BONNET 1 1 1 1 1247 43196087 BUSHING, GRILLE 6 6 6 6 6248 43139154 BAND, MOTOR, LEFT 2 2 2 2 2249 43139155 BAND, MOTOR, RIGHT 2 2 2 2 2250 43122104 BASE, MOTOR 1 1 1 1 1251 43019904 HOLDER, SENSOR (TS) 2 2 2 2 2252 43149314 SHEET, PMV 1 1 1 1 1253 43147664 STRAINER 1 1 1 1 1254 43166011 REMOTE CONTROLLER, SX-A4EE 1 1 1 1 1255 43166012 REMOTE CONTROLLER, SX-A5EE 1 1 1 1 1256 43166004 REMOTE CONTROLLER, SX-A11JE2 1 1 1 1 1257 43166006 REMOTE CONTROLLER, WH-H1JE2 1 1 1 1 1259 43147649 STRAINER 1 1 1260 431S8206 OWNER'S MANUAL, MMY-

MAP0804HT8-TR 1 1 1 1 1

211

Toshiba

Page 213: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 212 Tuesday, June 21, 2011 10:41 AM

MML-AP0244H✽

212

Toshiba

Page 214: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 213 Tuesday, June 21, 2011 10:41 AM

MML-AP0244H✽

213

Toshiba

Page 215: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 214 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MML-AP0244H-E201 43723020 CASE, FAN, LEFT 2203 43126119 CASE, FAN, RIGHT 2204 43109394 GRILL, INLET, WHITE 2207 43155171 CAPACITOR 1210 4312C008 MOTOR, FAN 1212 43146707 MOTOR, PMV 1214 43146726 BODY, PMV 1216 43120232 FAN, MULTI BLADE 2217 43180280 AIR FILTER 2218 43101346 FRAME, WHITE 1219 43101347 COVER, CONTROL PANEL, WHITE 1220 43172101 PAN, DRAIN 1221 43100366 PANEL, FRONT 1224 4314J420 EVAPORATOR ASSY 1227 4314Q046 DISTRIBUTOR ASSY 1230 43149355 NUT, FLARE, 3/8, IN 1231 43049776 SOCKET 1234 43149352 NUT, FLARE, 5/8, IN 1236 43149354 SOCKET 1237 43100374 CABINET, UPPER, WHITE 1238 43100228 OUTLET, WHITE 1239 43109395 GRILLE, WHITE 3240 43109240 GRILLE 1241 43170201 HOSE, DRAIN 1242 43107215 HOLDER, SENSOR 1243 43047609 BONNET 1245 43194029 BONNET 1247 43196087 BUSHING, GRILLE 6248 43139154 BAND, MOTOR, LEFT 2249 43139155 BAND, MOTOR, RIGHT 2250 43122104 BASE, MOTOR 1251 43019904 HOLDER, SENSOR (TS) 2252 43149314 SHEET, PMV 1253 43147664 STRAINER 1254 43166011 REMOTE CONTROLLER, SX-A4EE 1255 43166012 REMOTE CONTROLLER, SX-A5EE 1256 43166004 REMOTE CONTROLLER, SX-A11JE2 1257 43166006 REMOTE CONTROLLER, WH-H1JE2 1258 431S8205 OWNER'S MANUAL, MMY-MAP0804HT8-E 1

214

Toshiba

Page 216: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 215 Tuesday, June 21, 2011 10:41 AM

Location No. Part No. Description MML-AP0244H-TR201 43723020 CASE, FAN, LEFT 2203 43126119 CASE, FAN, RIGHT 2204 43109394 GRILL, INLET, WHITE 2207 43155171 CAPACITOR 1210 4312C008 MOTOR, FAN 1212 43146707 MOTOR, PMV 1214 43146726 BODY, PMV 1216 43120232 FAN, MULTI BLADE 2217 43180280 AIR FILTER 2218 43101346 FRAME, WHITE 1219 43101347 COVER, CONTROL PANEL, WHITE 1220 43172101 PAN, DRAIN 1221 43100366 PANEL, FRONT 1224 4314J420 EVAPORATOR ASSY 1227 4314Q046 DISTRIBUTOR ASSY 1230 43149355 NUT, FLARE, 3/8, IN 1231 43049776 SOCKET 1234 43149352 NUT, FLARE, 5/8, IN 1236 43149354 SOCKET 1237 43100374 CABINET, UPPER, WHITE 1238 43100228 OUTLET, WHITE 1239 43109395 GRILLE, WHITE 3240 43109240 GRILLE 1241 43170201 HOSE, DRAIN 1242 43107215 HOLDER, SENSOR 1243 43047609 BONNET 1245 43194029 BONNET 1247 43196087 BUSHING, GRILLE 6248 43139154 BAND, MOTOR, LEFT 2249 43139155 BAND, MOTOR, RIGHT 2250 43122104 BASE, MOTOR 1251 43019904 HOLDER, SENSOR (TS) 2252 43149314 SHEET, PMV 1253 43147664 STRAINER 1254 43166011 REMOTE CONTROLLER, SX-A4EE 1255 43166012 REMOTE CONTROLLER, SX-A5EE 1256 43166004 REMOTE CONTROLLER, SX-A11JE2 1257 43166006 REMOTE CONTROLLER, WH-H1JE2 1260 431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR 1

215

Toshiba

Page 217: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 216 Tuesday, June 21, 2011 10:41 AM

E-Parts

Location No. Part No. DescriptionMML-

AP0074H-E(TR)

AP0094H-E(TR)

AP0124H-E(TR)

AP0154H-E(TR)

AP0184H-E(TR)

401 43050425 SENSOR ASSY, SERVICE 2 2 2 2 2402 43050426 SENSOR, SERVICE 1 1 1 1 1403 43150320 SENSOR ASSY, SERVICE 1 1 1 1 1404 43158204 TRANSFORMER 1 1 1 1 1405 43160575 TERMINAL BLOCK, 2P, 20A 1 1 1 1 1406 43160582 TERMINAL, 4P 1 1 1 1 1407 4316V469 P.C. BOARD ASSY, MCC-1403 1 1 1 1 1408 4316V345 P.C. BOARD ASSY, MCC-1520 1 1 1 1 1

Location No. Part No. Description MML-AP0244H-E(TR)

401 43050425 SENSOR ASSY, SERVICE 2402 43050426 SENSOR, SERVICE 1403 43150320 SENSOR ASSY, SERVICE 1404 43158204 TRANSFORMER 1405 43160575 TERMINAL BLOCK, 2P, 20A 1406 43160582 TERMINAL, 4P 1407 4316V469 P.C. BOARD ASSY, MCC-1403 1408 4316V345 P.C. BOARD ASSY, MCC-1520 1

216

Toshiba

Page 218: SM_4 Sereis VRF Indoor Units

+00A10-033_01EN.book Page 217 Tuesday, June 21, 2011 10:41 AM

WARNINGS ON REFRIGERANT LEAKAGECheck of Concentration LimitThe room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc.Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device.The concentration is as given below.

The concentration limit of R410A which is used in multi air conditioners is 0.3 kg/m3.

NOTE 1 :If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.

For the amount of charge in this example:The possible amount of leaked refrigerant gas in rooms A, B and C is 10 kg.The possible amount of leaked refrigerant gas in rooms D, E and F is 15 kg.

NOTE 2 :The standards for minimum room volume are as follows.(1) No partition (shaded portion)

(2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15 % or larger than the respective floor spaces at the top or bottom of the door).

(3) If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.

NOTE 3 :The minimum indoor floor area compared with the amount of refrigerant is roughly as follows:(When the ceiling is 2.7 m high)

Total amount of refrigerant (kg)Min. volume of the indoor unit installed room (m3)

≤ Concentration limit (kg/m3)

e.g., charged amount (10 kg)

Outdoor unite.g.,charged amount (15 kg)

Indoor unit

Room A Room B Room C Room D Room E Room F

Important

Outdoor unitRefrigerant piping

Indoor unit

Refrigerant piping

Outdoor unit

Indoor unit

Mechanical ventilation device - Gas leak detector

Very small room

Small room

Medium room Large room

m2

Min

. ind

oor f

loor

are

a

Total amount of refrigerant kg

Range above the density limit of 0.3 kg/m3

(countermeasures needed)

Range below the density limit of 0.3 kg/m3

(countermeasures not needed)

217

Toshiba