Slow Coherency Based Controlled Islanding in Large

Power Systems Vijay Vittal

Ira A. Fulton Chair Professor Department of Electrical Engineering

Arizona State University

PSERC Webinar February 18, 2014

Page 2: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Acknowledgement

2

This presentation is based on research coordinated by the Consortium for Electric Reliability Technology Solutions (CERTS) with funding provided by the U.S. DOE.

Page 3: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Graduate students who worked on this project

• Guangyue Xu – PhD – Now works at Siemens Energy Systems, Plymouth, MN. Graduated from Xian Jiao Tong University

• Bo Yang – PhD – Now works at Siemens-PTI, Schenectady, NY. Graduated from Shanghai Jiao Tong University

• Xiaoming Wang – PhD – Now works at Midwest ISO Carmel, Indiana. Graduated from Tsinghua University

• Haibo You – PhD – Now works for Austin Electric, Austin, Texas. Graduated from Shanghai Jiao Tong University 3

Page 4: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Motivation

• Power systems are under increasing stress as restructuring introduces several new economic objectives for operation

• When a power system is subjected to large disturbances, and the designed remedial action or protection system does not work, the system approaches a potential catastrophic failure

• Appropriate mitigation actions need to be taken to steer the system away from severe consequences, to limit the extent of the disturbance, and to facilitate power system restoration

4

Page 5: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Mitigation Strategy

• In our approach, the system is first separated into several smaller islands at a slightly reduced capacity by a controlled islanding approach. Second, an adaptive load shedding scheme is deployed to bring back the frequency to an acceptable level

• The basis for forming the islands is to minimize the load-generation imbalance in each island, thereby facilitating the restoration process

5

Page 6: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Slow Coherency Grouping Based Islanding Using Minimal Cutsets

• Given a system operating condition we determine the slowly coherent groups of generators

• Depending on the disturbance location we then determine minimal cutsets using a graph theoretic approach which minimizes load generation imbalance in each island

• A graph theoretic method is applied to accurately determine the boundary of the island • A k-way partitioning technique is applied to

decide the boundary of the island

6

Page 7: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Why Do We Need Islanding? • Cascading outages that rapidly spread across

the power system could result in significant disruption and inconvenience to modern society, leaving millions of people in the dark West Coast outages in 1996 The Aug. 14, 2003 blackout in the Eastern Interconnection A recent massive power failure in Rio de Janeiro, Brazil

• Controlled islanding provides an option of last resort to prevent the spreading of cascading outages Intentionally separates a bulk power system into several self

sustaining electrically isolated parts after a severe contingency Loss of load and generation are limited in an acceptable range

7

Page 8: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

How Do We Do Islanding?

8

• Identify slowly coherent generators generators swinging together after a

disturbance are said to be coherent

• Determine a cutset involve the contingency lines generators being identified to be

slowly coherent are in isolated parts. the impact of the imbalance power of

each island is minimized.

• Build an islanding strategy cutset determination load shedding and generation tripping

plan when to island (another big problem)

Page 9: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Coherency Identification Matrix

9

Fn

Fr

F

F

Sn

Sr

S

S

v

v

vv

v

v

vv

2

1

2

1

==

+ ]~)1[(2

)~1(1

nrSS

rSS

vVvV

+

×

12

)(

SS

rr

VVI

SV FV

-------- states ---------

------ modes -------

s slow modes

(n-s) fast modes

SV ( ) 11111

−+ = TSS

TSS WVVWVV

slow coherency identification

matrix

row eigenvectors

If the (n-r) states are coherent with r reference states, then vS(r+1)~vSn will be duplications of vS1~vSr, and therefore every row eigenvector of VL will have only 1 non-zero entry 1.0.

pseudo-inverse weight

Page 10: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

How to Identify Coherent Machines?

10

• In power systems, when two machines are coherent exactly with r selected slow modes, the row eigenvectors related to the two machines of the r modes will be identical.

• In an actual power system, machines are nearly coherent.

25.03.013.01

3

2

1

xxx x1 and x2 are exactly

coherent to the two slow modes

25.035.013.01

3

2

1

xxx x1 and x2 are nearly

coherent to the two slow modes

Page 11: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

11

11

generator internal reactance x1 = x2 = x3 = 0.3 pu, x4 = 0.22 pu, inertia H1 = H2 = H3 = H4 = 6.5, machine base 900 MVA, system base 100 MVA.

Generators G1 and G2 in one group. Generators G3 and G4 in the other group. The result is in accordance with intuition.

9556.00444.00356.09644.01001

4231

GGGG

Grouping matrix of the four machine system

Page 12: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Determine Cutsets for Coherent Generators

12

• For small systems, cutsets can be determined manually.

• For large power systems that contain thousands of buses and branches, an automatic cutset searching program becomes necessary when coherent groups have been provided ???????

Page 13: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Steps to Perform Cutset Search

13

Input: Graph

Graph Simplification

Tree Collapse

K-way Partition by METIS

Refinement

Original Cutset Recovery Output: Cutset

Powerflow data

Dynamic data

Identify Slow Coherent Generators

Generator Grouping Results

Pre-Processing

Output: Graph

Page 14: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Graph Representation

14

Note that graph representation does not affect the cutset determination.

G G

63 MW-9 MVar

-62 MW15 MVar406 MW

123 MVar

200 MW100 MVar

100 MW-67 MVar

100 MW0 MVar

100 MW-50 MVar100 MW

0 MVar

143 MW-32 MVar

62 MW52 MVar

100 MW-10 MVar

-61 MW-47 MVar

-39 MW-3 MVar

BUS 2 BUS 1

BUS 3BUS 4

BUS 5

2 1

4 35

63

62143

39100

Power systems are represented as a directed graph to simplify analysis

Bus -> Node

Transmission Line/Transformer -> Branch

MW of Powerflow through TLs/TFs

-> Weight of Branch

Page 15: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Graph Simplification: 5 Steps

15

..

.I J

w1

wn

I J

wequ= w1+w2+…+wn

I J I

I J K

w1 w2

I K

w 25,26,27,3046,47,48,4950,51,52,53

54,55

20

Remove closed loop

Simplify 25,2627,30

48,4950,52

53

51,545546,47 A closed

loop

Major node

20

302625

27

4647

49

48 535250

5455

51

20

1. Equivalence of parallel lines 2. Removal of degree-one-nodes

3. Removal of degree-two-nodes

4. Removal of step-up transformers

5. Removal of closed loops

degree of graph: the degree of a node is

equal the number of branches connected

to that node.

Page 16: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Tree Collapse: Consolidate Coherent Machines

16

• Purpose: avoid generators in one coherent group being separated in different islands.

• Method: collapse generators in the same group into a large dummy node. Building a spanning tree Trim the spanning tree Collapse of the minimum spanning tree

Spanning Tree Building

Spanning Tree Trimming1

2 3

45

6

78

91011

12

13 14

1

2 5

3 4 6

7

8Irrelevant node5Generator node1

1

2 5

3 4 6

7 9

8

11 12 13

91011

12

13 14

dummy node

Page 17: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Graph Splitting and Island Merging

17

• After tree collapse, a graph partition program METIS (Developed by Prof. Karypis’ laboratory at the university of Minnesota) is employed to split the graph into specified number of parts

1:853 2:417

3:1062

33->36

32

4->31

• Some extra islands will be formed in the splitting process, and an island merging module is invoked to merge minor islands to their adjacent major islands.

merge islands

Page 18: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Cutset Recovery

18

• A partition result of the highly simplified graph is given at this time.

• In all the previous processes, actions are recorded. Final cutset can be recovered from the results of simplified graph.

Simplified system and cutset

Original system and cutset

Page 19: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Efficiency and Effectiveness of the Algorithm

19

• A software package is developed based on the algorithm. Test result:

• Bus: 15000 + • Branch: 18000 + • PC configuration: Intel Core2 6700 2.66 GHz CPU and 2 GB memory • Speed: less than 3 seconds

• Graph simplification efficiency

• Effectiveness of cutsets from the algorithm will be tested by time domain simulations

17%

Page 20: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Islanding Demonstrations on the WECC System

20

• Simulation tools: DSA Tools, especially PSAT and TSAT. • Simulation cases: the WECC system under two different operating

conditions: heavy summer (HS) case and light winter (LW) case • Contingencies: triple line outage (TLO) and severe double line

outage (SDLO) at California Oregon intertie (COI) and Path 15 (P15)

Simulation Cases

Operating Conditions

Contingency Locations Outages

Case #1 HS COI TLO

Case #2 HS COI SDLO

Case #3 LW P15 TLO

Case #4 LW P15 SDLO

COI: critical contingency to heavy summer case

P15: critical contingency to light winter case

Page 21: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Slowly Coherent Groups in the WECC

21

Page 22: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Candidate Cutsets

22

No. of Islands

Slow Coherency Groups Contained

Load/Generation Imbalance (MW)

No. of Lines in Cutsets

2 (1,2), (3,4,5) -5602/5602 15

3 (1,2), (3,4), (5) -5602/5903/-301 18

4 (1), (2), (3,4), (5) -4748/-907/5957/-301 21

5 (1), (2), (3), (4), (5) -4748/-907/ -487/6444/-301 34

Candidate cutsets for HS COI Case

No. of Islands

Slow Coherency Groups Contained

Load/Generation Imbalance (MW)

No. of Lines in Cutsets

2 (2), (1,3,4,5) 6028/-6028 15

3 (2), (1,3,4), (5) 6028/-6027/-1 18

4 (2), (1,4), (3), (5) 6028/-5886/-141/-1 34

Candidate cutsets for LW P15 Case

Page 23: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Locations of Contingencies and Cutsets

23

Two islanding strategies are built for the COI contingency and another two for the P15 contingency

For HS COI cases For LW P15 cases

Page 24: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Time Sequence of HS COI TLO

24

Time(Not scaled)

3-Φ fault at COI bus

1s

4 cycles

Clear fault, open three COI lines, RAS start1

1

30 cycles or more

Implement islanding(*)

50.4 cycles

2 3 4

0s 25s

23 4 RAS end

Start End

(*) Not employed in the uncontrolled islanding case

Note that RAS( remedial action schemes) are only employed in TLO cases.

Heavy Summer California Oregon Intertie

Triple Line Outage

Page 25: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

The HS COI TLO Case: generator variables

25 Uncontrolled Islanding Controlled Islanding

Relative rotor angle

gen speed (Hz)

S island

Page 26: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

HS COI SDLO

26 Only controlled islanding results are shown here

Time(Not scaled)

3-Φ fault at COI bus

1s

4 cycles

Clear fault, open two COI lines1

1

114 cycles

Open the 3rd COI line

20 cycles

2 3 4

0s 25s

23 4 Implement islanding (*)

Start End

(*) Not employed in the uncontrolled islanding case

Long Delay

Page 27: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

LW P15 TLO

27

Time(Not scaled)

3-Φ fault at COI bus

1s

4 cycles

Clear fault, open three P15 lines, RAS start1

1

22 cycles

RAS end

30 cycles

2 3 4

0s 25s

23 4 Implement islanding (*)

Start End

(*) Not employed in the uncontrolled islanding case

Only controlled islanding results are shown here

Page 28: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

LW P15 SDLO

28

Time(Not scaled)

3-Φ fault at COI bus

1s

4 cycles

Clear fault, open two P15 lines1

1

300 cycles

Open other six lines

396 cycles

2 3 4

0s 30s

23 4 Open the 3rd P15 line

Start End

(*) Not employed in the uncontrolled islanding case

20 cycles

5

5 Implement islanding (*)

Extreme Long Delay

Only controlled islanding results are shown here

Page 29: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Simulation Results

29

Features* Stable Islands Formed Load Shedding

(MW) Gen Tripping (MW)

HS COI

UI TLO No 3 7500 14420 SDLO No 4 6300 11290

CI TLO Yes 2 1530 2770 SDLO Yes 2 1220 480

LW P15

UI TLO No 3 14730 5310 SDLO No 3 15930 3790

CI TLO Yes 2 2970 1020 SDLO Yes 2 2840 260

* UI = uncontrolled islanding, CI = controlled islanding

Existing RAS without separation are NOT effective enough to prevent the WECC system from cascading outages when TLO or SDLO occurred at COI or P15.

Controlled islanding has a potential for preventing the formation of multiple asynchronous groups of generators and reducing load shedding and generation tripping after a severe contingency.

Present armed RASs in the WECC system are not designed for controlled islanding operation, therefore some unwanted load shedding or generation tripping may occur after islanding.

Page 30: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Simulation Results Analysis

30

Stable? Uncontrolled Islanding Controlled Islanding

HS COI TLO N Y

HS COI SDLO N Y

LW COI TLO N Y

LW COI SDLO N Y

HS COI TLO

HS COI

SDLO

LW P15 TLO

LW P15

SDLO MW

UI = uncontrolled islanding, CI = controlled islanding

Stability during

simulation

Page 31: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Conclusions

• Controlled islanding has proven to be effective in preventing system from losing synchronism after severe disturbances.

• In each island formed, frequencies and voltages in the transmission network are within an acceptable operating range, although services would be slightly degraded.

• Compared to uncontrolled islanding, controlled islanding results in less load shedding, in tripping of fewer generators, and in lower blackout probabilities.

• The algorithm works for large power system and is efficient.

• Several cutsets identified by the algorithm are effective in controlled islanding.

31

Page 32: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Application to the August 14, 2003 Northeast Blackout

• It is the 2004 Summer Peak Load Case for the Eastern Interconnection.

• It has nearly 38,000 buses and nearly 5000 generators.

• All the modeling detail provided in the base case was retained without any change.

• The proposed approach was applied to the August 14th, 2003 scenario.

32

Page 33: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Preparation of Case

• The conditions given in the joint US-Canadian final report were implemented in the base case obtained.

• The power flow was then obtained. • This shows the state of the system before

the final set of disturbances occurred. • The details of changes implemented are shown

in the next few slides.

33

Page 34: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Preparation of Case

• Adjust generation from AEP to compensate for this loss of generation in FE

• Remove Columbus-Bedford 345 kV Line • Remove Bloomington- Denois Creek 230 kV line • Trip Eastlake 5 generation • Remove Chamberlin – Harding 345 kV Line • Remove Stuart-Atlanta 345 kV Line • Remove Hanna- Juniper 345 kV Line • Remove Star-South Canton 345 kV Line

34

Page 35: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Preparation of Case

• Remove the following 138 kV lines • Cloverdale-Torrey • E. Lima – New Liberty • Babb – W. Akron • W. Akron – Pleasant Valley • Canton Central Transformer • Canton Central – Cloverdale • E. Lima – N. Findlay • Chamberlin- W. Akron • Dale – W. Akron • West Akron-Aetna • West Akron-Granger-Stoney-Brunswick-West Medina • West Akron-Pleasant Valley • West Akron-Rosemont-Pine-Wadsworth

35

Page 36: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Preparation of Case

• The slow coherency program was then run using the solved power flow case and the dynamic data provided to obtain the slowly coherent groups.

• All the modeling details provided in the data were included.

• No simplifications were made. • One of the slowly coherent groups identified

was the entire FE area.

36

Page 37: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Slowly Coherent Generator Groups

37

Page 38: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

38

Island created by automatic islanding program

Slowly coherent group in FE Area

Page 39: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

August 14, 2003 Scenario

• The Dale-West Canton 138 kV line sags into a tree and trips.

• In 2s this led to the overloading of Sammis-Star 345 kV line which then tripped.

• This tripped on Zone 3. • This was the start of the cascade.

39

Page 40: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Creation of Island

• At time t=0s a three phase fault occurs at Dale and the Dale-West Canton 138 kV line is tripped.

• We then create an island near the Cleveland area. • In order to create the island we have to trip 20 lines:

• 7 - 345 kV lines • 9 – 138 kV lines • 4 – 69 kV lines

• This island has: • Total generation = 6259.23 MW • Total load = 8309.07 MW

• The rate of frequency decline base load shedding sheds (23%) or 1911 MW of load in the island

40

Page 41: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Statement from Joint US-Canada Report

“The team found that 1,500 MW of load would have had to be dropped within the Cleveland-Akron area to restore voltage at the Star bus from 90.8%(at 120% of normal and emergency ampere rating) up to 95.9%(at 101% of normal and emergency ampere rating).”

41

Page 42: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

42

Line Flow Reduced on Sammis-Star

Page 43: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Bus Voltage Improved at Star

43

Page 44: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

August 14, 2003 Analysis

• With the flow reduced on the Sammis – Star line and the voltage at start maintained at nominal values the line did not trip

• As a result the cascading outages did not occur • The system remained intact and by shedding

around 1900 MW of load in Cleveland and creating an island the rest of the system remained intact

44

Page 45: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

Publications • You, H.,V. Vittal, and Z. Yang, "Self-healing in power systems: an approach

using islanding and rate of frequency decline based load shedding," IEEE Trans. Power Systems, Vol. 18, no. 1, pp.174-181, February 2003.

• You, H., V. Vittal, X. Wang, “Slow Coherency Based Islanding,” IEEE Transactions on Power Systems, Vol. 19, no. 1, pp 483-491, February 2004.

• Wang, X. , V. Vittal, G.T. Heydt, " Tracing Generator Coherency Indices Using the Continuation Method: A Novel Approach," IEEE Transactions on Power Systems, Vol. 20, No. 3, pp 1510-1518, August 2005.

• Yang, B., V. Vittal, G.T. Heydt, “Slow Coherency Based Controlled Islanding – A Demonstration of the Approach on the August 14, 2003 Blackout Scenario,” IEEE Transaction on Power Systems, Vol. 21, No. 4, pp. 1840-1847, November 2006.

• Xu, G., V. Vittal, “Slow Coherency based Cutset Determination Algorithm for Large Power Systems,” IEEE Transactions on Power Systems, Vol. 25, No. 2, pp.877-884, May 2010.

• Xu, G., V. Vittal, A. Meklin, J.E. Thalman, “Controlled Islanding Demonstrations on the WECC System,” IEEE Transactions on Power Systems, Vol. 26, No.3, pp.1426-1433, August, 2011.

45

Page 46: Slow Coherency Based Controlled Islanding in Large Power ... · Slow Coherency Based Controlled Islanding in Large Power Systems Vijay Vittal . ... Power systems are represented as

46

Thanks!