sitron-conductive catalog

12
Models: Controllers: BS/16 CN/16D Introduction Sitron´s line of Conductive Level Switches offer a wide range of customized options to meet any application's need. CL models are designed to control the level of all conductive mediums with up to 5 different points of level detection. Models are available with Fixed rigid rods, Removable rigid rods, or with Pendular electrodes attached to the housing with cables. Applications involve both alarm point level detection as well as on/off pump valve control. Like all of Sitron's products, the series of Conductive Level Switches feature easy installation and maintenance free reliability. Technology The probes work through the variation of the electrical resistance between the reference electrode and the level control electrode. Conductive Level Switches detect the level resistance when their electrodes are covered by the medium. An electrically conductive tank wall may be used as the reference electrode. If the tank is made of plastic, concrete or any other non-conductive material, an additional electrode is required to act as a reference. Conductive Level Switches CLF-(1 up to 5) Fixed Rods CLR-(1 up to 5) Removable Rods CLP-(1 up to 5) Pendular Electrodes CLE-1 Pendular Electrode without enclosure CL1-DC Single Point Detection/Controller built into the housing CL2-DC Low & High Level Point Level Detection/Controller built into the enclosure

Upload: veederline

Post on 29-Mar-2016

241 views

Category:

Documents


0 download

DESCRIPTION

Technology Models: Introduction Controllers: The probes work through the variation of the electrical resistance between the reference electrode and the level control electrode. Conductive Level Switches detect the level resistance when their electrodes are covered by the medium. An electrically conductive tank wall may be used as the reference electrode. If the tank is made of plastic, concrete or any other non-conductive material, an additional electrode is required to act as a reference.

TRANSCRIPT

Page 1: Sitron-Conductive Catalog

Models:

Controllers:

BS/16 CN/16D

Introduction

Sitron´s line of Conductive Level Switches offer a wide range of customized options to meet any application's need. CL models are designed to control the level of all conductive mediums with up to 5 different points of level detection. Models are available with Fixed rigid rods, Removable rigid rods, or with Pendular electrodes attached to the housing with cables. Applications involve both alarm point level detection as well as on/off pump valve control. Like all of Sitron's products, the series of Conductive Level Switches feature easy installation and maintenance free reliability.

Technology

The probes work through the variation of the electrical resistance between the reference electrode and the level control electrode. Conductive Level Switches detect the level resistance when their electrodes are covered by the medium. An electrically conductive tank wall may be used as the reference electrode. If the tank is made of plastic, concrete or any other non-conductive material, an additional electrode is required to act as a reference.

Conductive Level Switches

CLF-(1 up to 5) Fixed Rods CLR-(1 up to 5) Removable Rods CLP-(1 up to 5) Pendular Electrodes CLE-1 Pendular Electrode without enclosure CL1-DC Single Point Detection/Controller built into the housing CL2-DC Low & High Level Point Level Detection/Controller built into the enclosure

Page 2: Sitron-Conductive Catalog

Models

Sitron has several types of conductive switches:

The CLF-(1 up to 5) has fixed rods and is available with up to five points of level detection and control. The CLR-(1 up to 5) has removable rods designed for easy handling and installation and is also available with up to five points of level detection and control. The CLP-(1 up to 5) has pendular electrodes designed for deep well or tank applications and is also available with up to five points of level detection and control. The CLE is a single pendular electrode without the enclosure or the process connection.

These models are all used along with an external controller.

However, there are two other types of conductive probes that do not require an external controller. The CL1-DC and CL2-DC have self-contained controllers built into the head. These models are available for single or high and low point level detection.

Features

Easy to install and to operateRugged constructionLow costBuilt-in units (probe and controller)Removable rodsUp to five points of level control (or more upon request)Rods can be coated when necessaryAvailable with 316 S.S. sanitary, flange or threaded connections approved

Sitron-USA, Inc. 21 West Nicholai St. Hicksville, NY 11801 Ph:(516) 935-8001 Fax: (516) 935-6001 e-mail: [email protected] -

Page 3: Sitron-Conductive Catalog

DIMENSIONS WIRING DIAGRAM

2 ½

” (64

mm

)

3 ½” (89mm)

1/4"

L 1

L1

CLF (1 - 5)

Conductive Level Switch with Fixed Rods

Sitron's model CLF (1 up to 5) level switch is the most commonly specified conductive level switch.

The CLF (1 up to 5) can accommodate up to five 316S.S. fixed rods for five (or more upon request) different levels of control. The rods are isolated with a PTFE joggle and can also be coated with PTFE or epoxy when the probe is applied in aggressive or sticky mediums prone to build up.

Operating levels in the tank can be easily modified by cutting the length of the electrodes.

Like all of Sitron´s products the CLF models have a rugged, compact and modern no-moving-parts design. This makes the CLF models very reliable switches for controlling all conductive mediums as well as for high pressure applications.

CLF probes are available with 316S.S. threaded, flanged or with sanitary connections.

CLF models are used along with two types of controllers: the BS/16 and the CN/16D.

Page 4: Sitron-Conductive Catalog

DIMENSIONS WIRING DIAGRAM

2 ½

” (64

mm

)

3 ½”(89mm)

1/4"

L 1

L1

CLR (1 - 5)

Conductive Level Switch with Removable Rods

Along with the same features as the CLF model, the CLP (1 up to 5) comes with unique removable 316S.S. threaded rods, which make it possible to switch the rods. Rods can be ordered separately in longer length and can then be custom cut to fit any type of application. Removable rods make the system more versatile, easier to handle as well as more forgiving if the rod's length is cut incorrectly.

CLR model probes are available with 316S.S. threaded, flanged or with sanitary connections.

CLR models are also used along with two types of controllers: The BS/16 and the CN/16D.We do not recommend any type of coating on the removable rods.

Sitron-USA, Inc. 21 West Nicholai St. Hicksville, NY 11801 Ph:(516) 935-8001 Fax: (516) 935-6001 e-mail: [email protected] -

Page 5: Sitron-Conductive Catalog

DIMENSIONS WIRING DIAGRAM

5 1/4” (134mm

)

7/8”ELECTRODE

CLP (1 - 5)

CLE

Conductive Level PendularProbe

Conductive Level Electrode

Along with the same features as the rigid rod probes, Sitron's CLP (1 up to 5) pendular probes can also accommodate up to five CLE electrodes (or more upon request). The CLP probes are ideal for deep measurements in wells or large tanks where long rods would be impractical, but they work equally well for shorter length applications. Because the electrodes are hung from PVC cables that allow for longer lengths, installation and handling are made easy. As with all of Sitron's other products, these probes are highly reliable as well as low in cost.

CLP model probes are available with 316S.S. threaded, flanged or with sanitary connections.

CLP models are also used along with two types of controllers: the BS/16 and the CN/16D.

Sitron's electrode model CLE is the simplest version of all conductive probes. A small polypropylene enclosure houses a 316S.S. rod that is attached to a PVC cable. This option eliminates the need for a process connection.

Sitron recommends that the CLE should be used along with the BS/16 and/or CN/16D controller.

Page 6: Sitron-Conductive Catalog

00 2525 5050 7575 100%100%

FlowFlow

4/20mA4/20mAOutOut

SondaSonda

SC400SC400

5 A 250V AC5 A 250V AC

PowerPower

11++__

22 SS

10

6789 1

0

2 3

4 5

5s5s0.1s0.1sDelayDelay

SenseSense

BS16BS16

5 A 250V AC5 A 250V AC

11 22 33 44 55 66 77 88

151599 1111 1313 141412121010 1616

PowerPower

LOW

HIGH

TANK 1 TANK 2

DIMENSIONS WIRING DIAGRAM

BS/16CN/16D

Conductive Level Controllers

Introduction

These conductive liquid level controllers are used to power all of Sitron's level probes. The BS/16 and the CN/16D are electronically controlled devices that open and close an electrical contact to effect the operation of other devices in the same, or another, electric circuit.

The BS/16 is able to control the differential of high and low level with an adjustment for sensitivity. The controller has 1 SPDT contact.The CN/16D controls two independent levels and has two SPDT contacts. It also includes a sensitivity adjustment. The BS/16 and the CN/16D are designed so that multiple units may be used in combination, to provide a variety of control functions, including multiple alarms and/or on/off control for alternating pumps. Both models are available with DIN rail sockets or with screws.

10 10

6 67 7

8 89 9 1 1

0 0

2 2 3 3

4 4 5 5

Sense A

Power

AA

B

B

Sense B

5 A 250V AC

5 A 250V AC

1 2 3 4 5 6 7 8

159 11 13 141210 16

Features

Sitron-USA, Inc. 21 West Nicholai St. Hicksville, NY 11801 Ph:(516) 935-8001 Fax: (516) 935-6001 e-mail: [email protected] -

Page 7: Sitron-Conductive Catalog

DIMENSIONS WIRING DIAGRAM

2 ½

” (64

mm

)

3 ½”(89mm)

1/4"

L 1

( I. Max 5 A )( V. 250 AC )( I. Max 5 A )( V. 250 AC )

AdjustAdjustonon

Electrical connections

DC / 24 V+ -

Status LED

Relay

Time Delay

SensitivityAdjustment

TimerSens.100 0

52,5

5

CL1-DCCL2-DC

Conductive Level Switchwith Built-in Controllers

The CL1-DC and CL2-DC are Conductive Level Switches with built-in controllers. The CL1-DC and CL2-DC operate with identical features offered with Sitron's other conductive models, with one added feature: The entire electronic controller is contained within the enclosure.

The CL1-DC has one single rod and is able to control one point of level. The model CL2-DC can accommodate up to two rods and is able to control high and low level. Both models feature a 24VDC power supply and internal controller that replaces the need for an external controller. As with all other conductive probes, the rods for these two models can be custom cut and made with any process connection, such as threaded, flanged or sanitary. In addition, the electrodes operate with alternate current to prevent electrolyses.

Rods can be coated when necessary.

Page 8: Sitron-Conductive Catalog

MODELS

SPECIFICATIONS

CLF 01 - Fixed rodCLR 01 - Removable rodCLE 01 - Pendular electrode

CLF 02 - Fixed rodsCLR 02 - Removable rodsCLE 02 - Pendular electrodes

CLF 03 - Fixed rodsCLR 03 - Removable rodsCLE 03 - Pendular electrodes

CLF 04 - Fixed rodsCLR 04 - Removable rodsCLE 04 - Pendular electrodes

CLF 05 - Fixed rodsCLR 05 - Removable rodsCLE 05 - Pendular electrodes

L1L2

L3

L1

L2L3

L4

L1L2

L3L4

L5

L1L1

L 2

2 ½

” (6

4mm

)

3 ½” (89mm)

1/4"

L 1

L 1 L

1 L 1

L 1

L 1 L

1

L 1 L 1

L 1

L 4

L 4

L 4

L 5

L 4

L 5

L 3

L 3

L 3

L 3

L 3

L 3L

2 L 2

L 2

L 2

L 2

L 2

L 2

L 2

7/8”

5 1/4”(134mm)

ApplicationLevel of Conductive liquids

in tanks and pipes Level of Conductive liquids

in tanks and pipes Level of Conductive liquids

in tanks and pipes Level of Conductive liquids

in tanks and pipes Level of Conductive liquids

in tanks and pipes

Electrode

Length

Rod: 0,33 up to 6,57f(100mm up to 2000mm)Cable: 1,64” up to 65,7 ft(500mm up to 20000mm)

Rod: 0,33 up to 6,57f(100mm up to 2000mm)Cable: 1,64” up to 65,7 ft(500mm up to 20000mm)

Rod: 0,33 up to 6,57f(100mm up to 2000mm)Cable: 1,64” up to 65,7 ft(500mm up to 20000mm)

Rod: 0,33 up to 6,57f(100mm up to 2000mm)Cable: 1,64” up to 65,7 ft(500mm up to 20000mm)

Rod: 0,33 up to 6,57f(100mm up to 2000mm)Cable: 1,64” up to 65,7 ft(500mm up to 20000mm)

Electricalconnection

Cable gland with ½”NPTconduit entry

Cable gland with ½”NPTconduit entry

Cable gland with ½”NPTconduit entry

Cable gland with ½”NPTconduit entry

Cable gland with ½”NPTconduit entry

1 fixed rod1 removable rod

1 pendular by cable

2 fixed rods2 removable rods

2 pendular by cable

3 fixed rods3 removable rods

3 pendular by cable

4 fixed rods4 removable rods

4 pendular by cable

5 fixed rods5 removable rods

5 pendular by cable

EnclosureMaterial

Glass filled nylon Glass filled nylon Glass filled nylon Glass filled nylonGlass filled nylon

Max pressure

290 PSI (20 Bar) 290 PSI (20 Bar) 290 PSI (20 Bar) 290 PSI (20 Bar) 290 PSI (20 Bar)

Temperatureoperation

Class protection NEMA 4 (IP 65) NEMA 4 (IP 65) NEMA 4 (IP 65) NEMA 4 (IP 65) NEMA 4 (IP 65)

Processconnection

1/2” … 1 ½” BSP or NPTsanitary and flanges

1/2” … 1 ½” BSP or NPTsanitary and flanges

1/2” … 1 ½” BSP or NPTsanitary and flanges

1 ½” BSP or NPTsanitary and flanges

1 ½” BSP or NPTsanitary and flanges

14 to 248º F(-10 to 120ºC)

14 to 248º F(-10 to 120ºC)

14 to 248º F(-10 to 120ºC)

14 to 248º F(-10 to 120ºC)

14 to 248º F(-10 to 120ºC)

Sitron-USA, Inc. 21 West Nicholai St. Hicksville, NY 11801 Ph:(516) 935-8001 Fax: (516) 935-6001 e-mail: [email protected] -

Page 9: Sitron-Conductive Catalog

SPECIFICATIONS

00 2525 5050 7575 100%100%

SetSet

FlowFlow

AdjustAdjust

4/20mA4/20mAOutOut

SondaSonda

SC400SC400

5 A 250V AC5 A 250V AC

PowerPower

LV 400/2LV 400/2

11++__

22 SS

1010

66778899 1 1

00

2 2 3 3

4 4 5 5

5s5s0.1s0.1sDelayDelay

SenseSense

BS16BS16

5 A 250V AC5 A 250V AC

11 22 33 44 55 66 77 88

151599 1111 1313 141412121010 1616

PowerPower

BS16

3 1/

4” (

82m

m)

3 1/

4” (

82m

m)

4 3/8” (111mm)

4 3/8” (111mm)

1 3/4”(44m)

1 3/4”(44m)

CN16D

00 2525 5050 7575 100%100%

SetSet

FlowFlow

AdjustAdjust

4/20mA4/20mAOutOut

SondaSonda

SC400SC400

5 A 250V AC5 A 250V AC

PowerPower

LV 400/2LV 400/2

11++__

22 SS

CN 16 DCN 16 D

1010

66778899 1 1

00

2 2 3 3

4 4 5 5

Sense BSense B1010

66778899 1 1

00

2 2 3 3

4 4 5 5

Sense ASense A

5 A 250V AC5 A 250V AC

5 A 250V AC5 A 250V AC

11 22 33 44 55 66 77 88

151599 1111 1313 141412121010 1616

PowerPower

AAAA

BB

BB

( I. Max 5 A )( V. 250 AC )( I. Max 5 A )( V. 250 AC )

( I. Max 5 A )( V. 250 AC )( I. Max 5 A )( V. 250 AC )

AdjustAdjust AdjustAdjustonon onon

Electrical connections Electrical connections

DC / 24 VDC / 24 V DC / 24 VDC / 24 V++ ++-- --

Time Delay Time Delay

Sensitivityadjustment

Sensitivityadjustment

TimerTimer TimerTimerSens.Sens. Sens.Sens.1010 101000 0000 00

55 552,52,5 2,52,5

55 55L 1

L 2 L

1

Application

Operating voltage

Current Consumption

Electrical connectionCable gland with ½”NPT conduit entry

or M12 connectorCable gland with ½”NPT conduit entry

or M12 connector

Output voltage forthe electrodes

24 Vdc +/- 10%

Max. 2VA

12V - 100Hz 12V - 100Hz

Max. 2VA

24 Vdc +/- 10%

Application

OperatingVoltage

CurrentConsumption

Sensitivity adjustment

Output

Control of high and low levelfor conductive level probes

Control of 2 different levelsfor conductive level probes

24 Vdc (+/- 10%)115 or 230 Vac (50/60Hz)

24 Vdc (+/- 10%)115 or 230 Vac (50/60Hz)

0,5 to 50K Ohms (potentiometer)

0,5 to 50K Ohms (potentiometer) 0,5 to 50K Ohms (potentiometer)

0,5 to 50K Ohms (potentiometer)

2 VA 3 VA

Level detection of conductive liquidsin tanks and pipes

Level detection of conductive liquidsin tanks and pipes

Electrodes Single - 316 Stainless Steel fixed rod high and low - 316 Stainless Steel fixed rod

EnclosureMaterial Glass filled nylon Glass filled nylon

Length

Max pressure

Temperatureoperation

OperatingTemperature

14º to 140ºF (-10 to 60ºC) 14º to 140ºF (-10 to 60ºC)

Class protection

Class protection

Enclosurematerial ABS ABS

DIN rail or screws DIN rail or screwsMounting

NEMA 4 (IP 65) NEMA 4 (IP 65)

IP 40 IP 40

Proccessconnection

Output

Relay (SPDT) 5A max (250Vac)

Relay (SPDT) 5A max (250Vac)

Relay (SPDT) 5A max (250Vac)

2 Relay (SPDT) 5A max (250Vac)

Sensitivity adjustment

0,1 to 5 seconds (adjustable) 0,1 to 5 seconds (adjustable)

0,1 to 5 seconds (adjustable) 1 second

Time delay

Time delay

1/2” … 1 ½” BSP or NPTsanitary and flanges

3/4” … 1 ½” BSP or NPTsanitary and flanges

MODELS

MODELS CL1 DC CL2 DC

0,33 to 6,57 ft (100mm to 2.000mm) 0,33 to 6,57 ft (100mm to 2.000mm)

290 PSI (20 Bar) 290 PSI (20 Bar)

14 to 248º F(-10 to 120ºC)

14 to 248º F(-10 to 120ºC)

Page 10: Sitron-Conductive Catalog

EXAMPLES OF APPLICATIONS

Relay BS 16

1 Level Minimmum andmaximum levell

L1

L1 L1

L 2 L 2 L 3

Minimmum and maximum levelusing an electrod as referencel

PowerPower

Relay CN 16D

1010

66778899 1 1

00

2 2 3 3

4 4 5 5

5s5s0.1s0.1sDelayDelay

SenseSense

BS16BS16

5 A 250V AC5 A 250V AC

11 22 33 44 55 66 77 88

151599 1111 1313 141412121010 1616

PowerPower

Level

Level

Installationin pipes

LEVEL

LEVEL

LEVEL

TIME

TIME

TIME

ON ON

OFF OFF OFF

High and Lowlevel

Controller BS16

Controller CN16D

High and Low level usingan electrod as a reference

Sitron-USA, Inc. 21 West Nicholai St. Hicksville, NY 11801 Ph:(516) 935-8001 Fax: (516) 935-6001 e-mail: [email protected] -

Page 11: Sitron-Conductive Catalog

CodeCLFCLRCLP

Code12345

Code123456

CodeBN0

CodeL

CodeNA

CodeC T

CodePTFE

EP0X

- - - - - - -

CodeCLE

CodeL0

-

CodeBS/16

CN/16D

Code241123

-

NOTE2: ALL CONDUCTIVE APPLICATIONS MUST HAVE A REFERENCE POINT, SUCH AS THE METALLIC TANK

WALL OR IF THE TANK IS NON METALLIC, ANOTHER ROD OR ELECTRODE MUST BE ADDED.

2 rods or electrodes for high and low point level detection3 rods or electrodes for 3 points of level detection

NPT

Type of threadBSP

Glass filled nylon

Rod's or Cable LengthSpecify length

None

Aluminum die cast

Electrical ConnectionCable gland -1/2" NPT conduit entry1/2" NPT conduit entry

NOTE1: RODS MUST BE COATED W HEN USING THE PROBE IN TEMPERATURES ABOVE 180°F (80°C).

Other - Specify

Conductive Level Probe with Fixed rod to be used along with BS/16 or CN/16D controller

Conductive Level Probe with Pendular electrode to be used along with BS/16 or CN/16D controller

4 rods or electrodes for 4 points of level detection

1 rod or electrode for single point level detection

Not a thread

Epoxy

Enclosure

Conductive Controller for low and high level to be used with conductive probesSpecifications

ORDERING INFORMATION FOR CONTROLLERS

Single electrode in a polypropylene enclosure

Cable LengthSpecify lengthNone

Conductive Controller for 2 different levels to be used with conductive probes

Supply Voltage

CoatingHallar / Tefzel

24 VDC +/- 10%115 VAC (50/60 Hz)230 VAC (50/60Hz)

Specifications

NOTE3: RODS CAN BE CUSTOM CUT BY CUSTOMER TO BETTER SUIT APPLICATIO N.

Number of Rods or Electrodes (See Note 2)

Process Connection1/2" Thread

Conductive Level Probe with Removable rod to be used along with BS/16 or CN/16D controller

POINT LEVEL DETECTION - CONDUCTIVEORDERING INFORMATION

Other - Specify

3/4" Thread1" Thread

1 1/2" Tri-Clamp1 1/2" Thread

5 rods or electrodes for 5 points of level detection

Specifications

Page 12: Sitron-Conductive Catalog

Sitron-USA, Inc. 21 West Nicholai St. Hicksville, NY 11801 Ph:(516) 935-8001 Fax: (516) 935-6001 e-mail: [email protected] -

CodeCL1-DCCL2-DC

Code1234567

CodeBN0

CodeL

CodeNA

CodeC MT

CodePTFE

EP0X

- - - - - -

NOTE1: RODS MUST COATED W HEN USING THE PROBE IN TEMPERATURES ABOVE 180°F (80°C).

NOTE3: RODS CAN BE CUSTOM CUT BY CUSTOMER TO BETTER SUIT APPLICATION.

POINT LEVEL DETECTION BUILT-IN UNITSORDERING INFORMATION

Conductive Level Probe with 2 Fixed rods and electronics integrated into the enclosure

NPT

1 1/2" Thread

1/2" Thread

1 1/2" Tri-Clamp

EnclosureGlass filled nylon

Rod's length

Not a thread

Specifications

Process Connection

Specify length

Conductive Level Probe with 1 Fixed rod and electronics integrated into the enclosure

Other - Specify

Type of ThreadBSP

Flange 2" ANSI, 150lb. 316 S.S.

Electrical ConnectionCable gland with 1/2"NPT conduit entryM12 connector

CoatingHallar - TefzelEpoxy

1/2" NPT conduit entry

NOTE2: ALL CONDUCTIVE APPLICATIONS MUST HAVE A REFERENCE POINT, SUCH AS THE METALLIC TANK

WALL OR IF THE TANK IS NON METALLIC, ANOTHER ROD OR ELECTRODE MUST BE ADDED.

3/4" Thread1" Thread

NoneOther - Specify

Aluminum die cast