Sital Marble (MFG.)L.L.C Survey Report

Conducted By: Green Line Company

Page 2: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Factor Readings:

Predicting the Energy savingsBefore Installing Powerboss

Power Readings:

Small Cutting Machine 1 (9.2kW Motor)Small Cutting Machine 1 (9.2kW Motor)

Load Percentage:

On Load: 50%Off Load: 50%

Formula: Ave kW / Ave Kvar (100) = Saving Factor

On Load: 5.877 / 5.904 (100) = 99.54

Off Load: 1.05 / 5.849 (100) = 17.95

Off Load

On Load

Off Load

On Load

Page 3: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Formula: Saving Factor Vs. kW Saving % X Load Percentage = Saving %

Power Savings

Formula: Saving Factor Vs. kvar Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kva Saving % X Load Percentage = Saving %

Total Kvar Saving % = 26.25%

Total Kva Saving % = 31%

Total Kw Saving % = 17%

Off Load: 17.95 --------- 34 X 50% = 17%

On Load: 99.54 --------- 0 X 50% = 0%

Off Load: 17.95 --------- 52.5 X 50% = 26.25%

On Load: 99.54 --------- 0 X 50% = 0%

Off Load: 17.95 --------- 62 X 50% = 31%

On Load: 99.54 --------- 0 X 50% = 0%

Page 4: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Factor Readings:

Load Percentage:

Predicting the Energy savingsBefore Installing Powerboss

Formula: Ave kW / Ave Kvar (100) = Saving Factor

Power Readings:

Small Cutting Machine 2 (9.2kW Motor)Small Cutting Machine 2 (9.2kW Motor)

On Load: 50%

On Load: 4.475 / 5.997 (100) = 74.62

Off Load: 50%

Off Load: 1.078 / 6.09 (100) = 17.70

Off Load

On Load

Off Load

On Load

Page 5: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Savings

Formula: Saving Factor Vs. kW Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kvar Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kva Saving % X Load Percentage = Saving %

Total Kvar Saving % = 26.25%

Total Kva Saving % = 31%

Total Kw Saving % = 17%

Off Load: 17.70 --------- 34 X 50% = 17%

On Load: 74.62 --------- 0 X 50% = 0%

Off Load: 17.70 --------- 52.5 X 50% = 26.25%

On Load: 74.62 --------- 0 X 50% = 0%

Off Load: 17.70 --------- 62 X 50% = 31%

On Load: 74.62 --------- 0 X 50% = 0%

Page 6: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Factor Readings:

Load Percentage:

Predicting the Energy savingsBefore Installing Powerboss

Formula: Ave kW / Ave Kvar (100) = Saving Factor

Power Readings:

Small Cutting Machine 3 (11kW Motor)Small Cutting Machine 3 (11kW Motor)

On Load: 50%

On Load: 8.562 / 5.305 (100) = 161.39

Off Load: 50%

Off Load: 1.364 / 4.954 (100) = 27.53

Off Load

On Load

Off Load On Load

Page 7: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Savings

Formula: Saving Factor Vs. kW Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kvar Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kva Saving % X Load Percentage = Saving %

Total Kvar Saving % = 24.75%

Total Kva Saving % = 28.75%

Total Kw Saving % = 14%

Off Load: 27.53 --------- 28 X 50% = 14%

On Load: 161.39 --------- 0 X 50% = 0%

Off Load: 27.53 --------- 52.5 X 50% = 24.75%

On Load: 161.39 --------- 0 X 50% = 0%

Off Load: 27.53 --------- 57.5 X 50% = 28.75%

On Load: 161.39 --------- 0 X 50% = 0%

Page 8: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Factor Readings:

Load Percentage:

Predicting the Energy savingsBefore Installing Powerboss

Formula: Ave kW / Ave Kvar (100) = Saving Factor

Power Readings:

Bridge Cutting Machine 1 (22kW Motor)Bridge Cutting Machine 1 (22kW Motor)

On Load: 50%

On Load: 2.711 / 9.052 (100) = 29.95

Off Load: 50%

Off Load: 1.474 / 9.089 (100) = 16.22

Off Load

On Load

Off Load On Load

Page 9: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Savings

Formula: Saving Factor Vs. kW Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kvar Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kva Saving % X Load Percentage = Saving %

Total Kvar Saving % = 50%

Total Kva Saving % = 58.25%

Total Kw Saving % = 30.5%

Off Load: 16.22 --------- 34 X 50% = 17%

On Load: 29.95 --------- 27 X 50% = 13.5%

Off Load: 16.22 --------- 53 X 50% = 26.5%

On Load: 29.95 --------- 27 X 50% = 23.5%

Off Load: 16.22 --------- 62.5 X 50% = 31.25%

On Load: 29.95 --------- 54 X 50% = 27%

Page 10: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Factor Readings:

Load Percentage:

Predicting the Energy savingsBefore Installing Powerboss

Formula: Ave kW / Ave Kvar (100) = Saving Factor

Power Readings:

Bridge Cutting Machine 2 (22kW Motor-Slow & Fast Speed)Bridge Cutting Machine 2 (22kW Motor-Slow & Fast Speed)

On Load: 50%

On Load: 5.979 / 13.554 (100) = 44.11

Off Load: 50%

Off Load: 1.576 / 14.016 (100) = 11.24

Off Load

On Load

Off Load On Load

Page 11: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Savings

Formula: Saving Factor Vs. kW Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kvar Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kva Saving % X Load Percentage = Saving %

Total Kvar Saving % = 43.25%

Total Kva Saving % = 49.5%

Total Kw Saving % = 24%

Off Load: 11.24 --------- 37 X 50% = 18.5%

On Load: 44.11 --------- 11 X 50% = 5.5%

Off Load: 11.24 --------- 57 X 50% = 18.5%

On Load: 44.11 --------- 29.5 X 50% = 14.75%

Off Load: 11.24 --------- 68 X 50% = 34%

On Load: 44.11 --------- 29.5 X 50% = 15.5%

Page 12: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Factor Readings:

Load Percentage:

Predicting the Energy savingsBefore Installing Powerboss

Formula: Ave kW / Ave Kvar (100) = Saving Factor

Power Readings:

Water Jet (37kW Motor)Water Jet (37kW Motor)

On Load: 100%

On Load: 14.451 / 22.432 (100) = 64.42

Off Load On Load

Page 13: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Savings

Formula: Saving Factor Vs. kW Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kvar Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kva Saving % X Load Percentage = Saving %

Total Kvar Saving % = 20%

Total Kva Saving % = 22%

Total Kw Saving % = 5%

On Load: 64.42 --------- 5 X 100% = 5%

On Load: 64.42 --------- 20 X 100% = 20%

On Load: 64.42 --------- 22 X 100% = 22%

Page 14: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Factor Readings:

Load Percentage:

Predicting the Energy savingsBefore Installing Powerboss

Formula: Ave kW / Ave Kvar (100) = Saving Factor

Power Readings:

Polishing Machine (5kW Motor)Polishing Machine (5kW Motor)

On Load: 100%

On Load: 0.829 / 2.292 (100) = 36.17

Page 15: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Power Savings

Formula: Saving Factor Vs. kW Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kvar Saving % X Load Percentage = Saving %

Formula: Saving Factor Vs. kva Saving % X Load Percentage = Saving %

Total Kvar Saving % = 33%

Total Kva Saving % = 41%

Total Kw Saving % = 25%

On Load: 36.17 --------- 25 X 100% = 25 %

On Load: 36.17 --------- 33 X 100% = 33%

On Load: 36.17 --------- 41 X 100% = 41%

Page 16: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Consumption & Savings

Based on Per Day/24 Hours Operation

Page 17: Sital Marble (MFG.)L.L.C Survey Report Conducted By: Green Line Company

Benefits from PowerBoss

These machines can benefit greatly from Powerboss. The softstart function will reduce both starting current drawn by the motor and mechanical strain on bearings, gears, belts and etc. The reduction in starting current will also increase motor’s life.

The optimization function will reduce the power supplied to theMotor without changing its torque and rpm. Reducing the power supplied tothe motor will significantly reduce the heat, vibration and noise. Reducing wasted energy will also reduce the maintenance cost and production downtime.