sinvert pvs central inverters, from 350 kw -...

34
Siemens RE 10 · 2012 3 Central inverters according to IEC PVS 600 Series, 500 ... 2400 kW 3/2 Overview 3/4 Benefits, Application, Design, Function 3/6 Integration 3/7 Configuration 3/8 Technical specifications 3/12 Selection and ordering data 3/14 Options 3/15 Schematics Central inverters according to UL 3/16 Overview, Benefits, Application 3/17 Design, Function 3/19 Integration, Configuration 3/20 Technical specifications 3/22 Selection and ordering data 3/23 Options 3/24 Schematics Inverter stations according to IEC 3/25 Overview, Benefits, Application, Design 3/26 Function 3/27 Inegration 3/28 Configuration, Technical specifications 3/29 Selection and ordering data, Options, Schematics System components and accessories 3/30 Overview, Benefits 3/31 Application, Design, Function 3/33 Integration, Technical specifications, Selection and ordering data 3/34 Schematics You will find more information on the Internet at: see Appendix, page 6/2 SINVERT PVS Central Inverters, from 350 kW © Siemens AG 2012

Upload: doquynh

Post on 22-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

Siemens RE 10 · 2012

3Central inverters according to IECPVS 600 Series, 500 ... 2400 kW

3/2 Overview3/4 Benefits, Application, Design, Function3/6 Integration3/7 Configuration3/8 Technical specifications3/12 Selection and ordering data3/14 Options3/15 Schematics

Central inverters according to UL3/16 Overview, Benefits, Application3/17 Design, Function3/19 Integration, Configuration3/20 Technical specifications3/22 Selection and ordering data3/23 Options3/24 Schematics

Inverter stations according to IEC3/25 Overview, Benefits, Application, Design3/26 Function3/27 Inegration3/28 Configuration, Technical specifications3/29 Selection and ordering data, Options,

Schematics

System components and accessories3/30 Overview, Benefits3/31 Application, Design, Function3/33 Integration, Technical specifications,

Selection and ordering data3/34 Schematics

You will find more information on the Internet at: see Appendix, page 6/2

SINVERT PVS Central Inverters, from 350 kW

Chapter3.book Seite 1 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 2: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

PVS 600 Series, 500 ... 2400 kW

3/2 Siemens RE 10 · 2012

3

■ Overview

Central inverter according to IEC

Our transformerless, 3-phase SINVERT PVS inverters are reli-able, grid-compatible and cost-effective photovoltaic inverters which are used to convert solar energy into grid-compliant AC voltage for infeed into conventional power supply networks.

The compact inverters in the SINVERT PVS 600 series are avail-able with outputs between 500 and 2 000 kW or from 600 to 2 400 kW.

Their characteristics are described below.

Output and efficiency• SINVERT PVS inverters are particularly efficient in every oper-

ating point. They are capable of top efficiency levels of up to 98.7 %.

• SINVERT PVS inverters have integral DC and AC connections.• They feature a terminal compartment with separate panels for

DC and AC connections.• The DC and AC cables are connected from below through

duct openings in the the closed base panel.• SINVERT PVS inverters must be installed on a dry, non-com-

bustible and level surface.

Interfaces• Ethernet

Operator control and monitoring• SINVERT PVS inverters have a compact panel with 4.3" TFT

widescreen display (480 x 272 pixels and 256 colors) that clearly shows current infeed power data and other informa-tion.

• The devices are operated using touch screen with intuitive menu prompting.

Area of application

SINVERT PVS inverters are suitable for any application which re-quires compliance with the relevant IEC standards.

The devices have degree of protection IP20 and are suitable for installation indoors.

Chapter3.book Seite 2 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 3: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

3/3Siemens RE 10 · 2012

PVS 600 Series, 500 ... 2400 kW

3

Order number reassignment table

The order numbers for the SINVERT PVS central inverters will change from January 2012. The table below lists the existing or-der numbers with the corresponding new order numbers that will

be valid from January 2012 onwards. Instead of the expansion code letter "-Z" and the short designation used previously, each option will now have its own separate order number.

For additional ordering information see page 3/12.

SINVERT inverter Type series Number of masters/slaves

Compliant with Existing order numbers Order numbers as of January 2012

Grid frequency 50 Hz (rated value)

PVS500 500 1 M IEC 6AG3111-1PU30-0AB0 6AG3111-1AH00-3AB0

PVS1000 500 1 M/1 S IEC 6AG3111-1SB30-0AB0 6AG3111-1AH10-3AB0

PVS1500 500 1 M/2 S IEC 6AG3111-1SG30-0AB0 6AG3111-1AH20-3AB0

PVS2000 500 1 M/3 S IEC 6AG3111-1SM30-0AB0 6AG3111-1AH30-3AB0

PVS600 600 1 M IEC 6AG3111-1QF30-0AB0 6AG3111-1AH00-0AB0

PVS1200 600 1 M/1 S IEC 6AG3111-1SD30-0AB0 6AG3111-1AH10-0AB0

PVS1800 600 1 M/2 S IEC 6AG3111-1SK30-0AB0 6AG3111-1AH20-0AB0

PVS2400 600 1 M/3 S IEC 6AG3111-1SR30-0AB0 6AG3111-1AH30-0AB0

Grid frequency 60 Hz (rated value)

PVS500 500 1 M IEC 6AG3111-2PU30-0AB0 6AG3111-2AH00-3AB0

PVS1000 500 1 M/1 S IEC 6AG3111-2SB30-0AB0 6AG3111-2AH10-3AB0

PVS1500 500 1 M/2 S IEC 6AG3111-2SG30-0AB0 6AG3111-2AH20-3AB0

PVS2000 500 1 M/3 S IEC 6AG3111-2SM30-0AB0 6AG3111-2AH30-3AB0

PVS600 600 1 M IEC 6AG3111-2QF30-0AB0 6AG3111-2AH00-0AB0

PVS1200 600 1 M/1 S IEC 6AG3111-2SD30-0AB0 6AG3111-2AH10-0AB0

PVS1800 600 1 M/2 S IEC 6AG3111-2SK30-0AB0 6AG3111-2AH20-0AB0

PVS2400 600 1 M/3 S IEC 6AG3111-2SR30-0AB0 6AG3111-2AH30-0AB0

Options For SINVERT inverter Number of masters/slaves

Compliant with Existing short designation

Separate order num-bers as of January 2012

Maximum permissible input voltage 1 000 V (1000 V option)

PVS500/PVS600 1 M IEC D61 6AG3911-3GA00-0AH0

PVS1000/PVS1200 1 M/1 S IEC D61 6AG3911-3GA10-0AH0

PVS1500/PVS1800 1 M/2 S IEC D61 6AG3911-3GA20-0AH0

PVS2000/PVS2400 1 M/3 S IEC D61 6AG3911-3GA30-0AH0

PV array grounding positive pole

PVS500/PVS600 1 M IEC D30 6AG3911-3FA00-0AH0

PVS1000/PVS1200 1 M/1 S IEC D30 6AG3911-3FA10-0AH0

PVS1500/PVS1800 1 M/2 S IEC D30 6AG3911-3FA20-0AH0

PVS2000/PVS2400 1 M/3 S IEC D30 6AG3911-3FA30-0AH0

PV array grounding negative pole

PVS500/PVS600 1 M IEC D40 6AG3911-3FB00-0AH0

PVS1000/PVS1200 1 M/1 S IEC D40 6AG3911-3FB10-0AH0

PVS1500/PVS1800 1 M/2 S IEC D40 6AG3911-3FB20-0AH0

PVS2000/PVS2400 1 M/3 S IEC D40 6AG3911-3FB30-0AH0

Cabinet heating PVS500/PVS600 1 M IEC S10 6AG3911-3HA00-1AH0

PVS1000/PVS1200 1 M/1 S IEC S10 6AG3911-3HA10-1AH0

PVS1500/PVS1800 1 M/2 S IEC S10 6AG3911-3HA20-1AH0

PVS2000/PVS2400 1 M/3 S IEC S10 6AG3911-3HA30-1AH0

Symmetry monitoring PVS500/PVS600 1 M IEC M10 6AG3911-3EA00-0AH0

PVS1000/PVS1200 1 M/1 S IEC M10 6AG3911-3EA10-0AH0

PVS1500/PVS1800 1 M/2 S IEC M10 6AG3911-3EA20-0AH0

PVS2000/PVS2400 1 M/3 S IEC M10 6AG3911-3EA30-0AH0

Chapter3.book Seite 3 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 4: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

PVS 600 Series, 500 ... 2400 kW

3/4 Siemens RE 10 · 2012

3

■ Benefits

• Maximum efficiency of up to 98.7 % guarantees maximum PV plant yields.

• The master/slave principle with "rotating master" employs an ingenious process to connect or disconnect inverter subunits depending on irradiation levels Using this system, it is possi-ble to operate the photovoltaic plant extremely efficiently to produce maximum plant yields even when irradiation levels are low.

• In master/slave systems, the "rotating master" always starts the inverter subunit with the fewest operating hours first. In this way, the total operating hours are evenly distributed among all the subunits. The durability and availability of the system are enhanced as a result, helping to minimize the total cost of ownership.

• Low servicing and maintenance costs through the use of fully developed, tried-and-tested standard industrial products

• High availability by virtue of low-maintenance design with rug-ged, durable components

■ Application

Inverters of the SINVERT PVS 600 product series are ideally suited for application in photovoltaic power plants ("Power Plant" segment) with outputs in excess of 500 kW.

They are typically employed in ground-mounted systems.

SINVERT PVS inverters are manufactured to relevant standards and regulations. They are suitable for application in countries which require conformance to IEC standards (see "Technical data", page 3/8).

The devices have degree of protection IP20 and are suitable for installation indoors.

■ Design

SINVERT PVS inverters are characterized by their compact and rugged design. They are based on fully developed, tried-and-tested standard industrial products.

On units which operate according to the master/slave principle with "rotating master", up to four inverter subunits can be inter-connected to form a master/slave system.

SINVERT PVS inverters are self-commutated, IGBT-based (IGBT: Insulated Gate Bipolar Transistor) units with pulse width modula-tion.

They are equipped with integral, low-noise fans for dissipating heat losses. Air is drawn in through ventilation grilles on the lower half of the front panel. Once through the grille, the air is guided upwards through air ducts which gradually narrow in order to in-crease the flow rate and strengthen the heat dissipating effect. The air exits at the top.

SINVERT PVS inverters have several DC inputs (see "Technical data", page 3/8), each of which is equipped with LV HRC fuses and DC contactors. The SINVERT PVS inverter can be discon-nected from the photovoltaic generator by means of the DC con-tactors.

The SINVERT PVS inverters are equipped with one AC contactor and one circuit breaker at the AC end. This switchgear can be used to decouple the SINVERT PVS inverter from the low-voltage or medium-voltage network.

Surge protection devices are integrated at the AC and DC ends.

SINVERT PVS inverters feature a terminal compartment with separate panels for DC and AC connections.

The DC and AC cables are connected from below through duct openings in the the closed base panel.

All parts of the SINVERT PVS cabinet can be recycled.

A control and display panel is mounted in the door of the AC cu-bicle. The compact panel with 4.3" TFT widescreen display clearly shows the infeed power data and other information, and allows intuitive operation of the inverter by the touch screen method (see "Function").

Indicator lamps are located below the control and display panel. These indicate the current operating state of the SINVERT PVS inverter (see "Function").

■ Function

Basic function

Within photovoltaic plants, SINVERT PVS inverters are the link between the photovoltaic generator (total of all electrically inter-connected photovoltaic modules) and the public AC grid. Their basic function is to convert the direct current produced by the photovoltaic generator into an alternating current and to adjust this current to the frequency and magnitude of a specified volt-age for infeed into the public grid. Conversion to grid-compliant AC can be carried out with minimum losses using modern power electronics.

Temperature monitoring

SINVERT PVS inverters have internal temperature monitoring that protects against violation of the permissible ambient tem-perature.

Control and display panel

The control and display panel is a touch panel which shows a corresponding "screen" for each menu item. The user navigates between menu items and between functions within individual items by touching the panel at the "screen" position at which a button with the corresponding command (e.g. "Back", "Settings" or "Service") is displayed.

In addition to the "screens" which display current values or fault messages, for example, there are also "screens" for changing system settings and servicing activities. The items "Settings" and "Service" in the main menu are protected by a password.

Control and display panel

Chapter3.book Seite 4 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 5: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

3/5Siemens RE 10 · 2012

PVS 600 Series, 500 ... 2400 kW

3

Status displays

There are two indicator lamps for visualizing the different inverter statuses.

Communications

SINVERT PVS inverters have an Ethernet interface. When the in-verter is linked to an Ethernet network, it can exchange data with a visualization system such as WinCC via the Ethernet interface (see Chapter 4 "Software and monitoring"). With a visualization system it is possible, for example, to operate and visualize the photovoltaic installation and to acquire, store and visualize mea-sured data and messages. Integrating the inverter into a network also makes it easier to analyze the photovoltaic yield data (set-point/actual value comparisons) and operate the installation from a remote location. This in turn facilitates the arrangement of service callouts at short notice, reduces system downtimes to a minimum and thus optimizes the yield of the plant. Interfaces to other communication channels (e.g. DSL, analog telephone, ISDN, GSM) can be provided if necessary.

Master/slave

The master/slave principle with "rotating master" is a mas-ter/slave system comprising up to four interconnected inverter subunits. It employs an ingenious process to connect or discon-nect inverter subunits depending on irradiation levels (calcu-lated according to the sun's path, cloud conditions, etc.). One inverter subunit acts as the master. The master is started up first and operates when irradiation levels are low. As irradiation levels increase, the power limit of the master is reached and the next inverter subunit, i.e. the slave, is switched in. Depending on the configuration, up to three slaves can be switched in. As irradia-tion levels drop again, the subunits are disconnected in stages. One advantage of the master/slave principle is that the inverters operate more efficiently and produce higher yields when irradia-tion levels (which determine the PV generator output) are low than would be achieved if only one single central inverter were used.

In master/slave systems, the "rotating master" always starts the inverter subunit with the fewest operating hours as the master. In this way, the total operating hours are evenly distributed among all the subunits.

Insulation (ISO) measurement

An insulation measurement is integrated in each inverter in order to protect personnel. The insulation measurement function mon-itors the system for low resistance to ground resulting from an in-sulation fault (e.g. caused by a damaged cable). Depending on the type of insulation fault, an alarm is output or the inverter is tripped

Provision of supplementary functions by options

The standard scope of functions of SINVERT PVS 600 series in-verters can be optionally expanded. Optionally available are, for example, a PV array grounding system, an increase in the maximum permissible operating voltage from 820 to 1 000 V, a DC input symmetry monitoring system or a cabinet heating for plants installed in cold regions (see "Options", page 3/14).

Indicators Status Description

Green indicator light "Run" Not lit: No infeed voltage present on AC side of SINVERT PVS inverter.The control unit has failed.

Flashing slowly, 1 s cycle: The key switch is not in position "2".The inverter subunit is in the "Ready" state.

Flashing fast, 250 ms cycle: The inverter subunit is in the "Run" state.

Illuminated steadily: The inverter subunit is in the "Infeed" state.The inverter subunit is feeding energy back into the grid.

Yellow indicator light "Fault" Not lit: No faults detected.

Flashing slowly, 1 s cycle: The control unit has signaled a warning. The inverter subunit remains in operation, but maintenance is required.

Flashing fast, 250 ms cycle: The control unit has signaled a fault which will be automatically acknowledged after a wait period. The inverter subunit will start up again after the fault has been acknowledged.

Illuminated steadily: The control unit has signaled a fault which must be acknowledged man-ually.

Key-operated switch "1/2/3" 1 – Lock: The inverter subunit is in the "Ready" state.

Switchover from "1" to "2": By turning the key-operated switch from position "1" to position "2", you can manually acknowledge all active faults

2 – Enable: The inverter subunit is in the "Ready" or "Infeed" state.

3 – Quick start (non-latching): The inverter subunit executes a quick start. The standard waiting times following a fault no longer apply.

Chapter3.book Seite 5 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 6: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

PVS 600 Series, 500 ... 2400 kW

3/6 Siemens RE 10 · 2012

3

■ Integration

The SINVERT PVS inverters can be seamlessly integrated into a photovoltaic installation by means of appropriate system com-ponents and accessories (see page 3/30) and software (see Chapter 4 "Software and monitoring").

The inverter is provided with standardized interfaces so that it can be integrated into a control system or an existing customer installation. The interfaces can also be used to remotely monitor and operate the device, for example, through the Internet portal or by means of the WinCC visualization system.

Professional operations management can be implemented us-ing the WinCC visualization system (see Chapter 4 "Software and monitoring").

The advantages of the WinCC visualization system include:• Clear display of plants, plant sections (subplants) and invert-

ers• Remote access to inverters• Remote monitoring• Acquisition, long-term storage and display of current and his-

torical data• Graphical representation of the monitored data• Plant monitoring• Messaging services using e-mail and text message• Fault messages can be specifically configured for customized

operations management• Map

Integration of SINVERT PVS inverters into a photovoltaic plant without solar PV plant control with communication via an Ethernet network and monitoring by means of SINVERT WebMonitor

SCALANCE S VPN Router

SINVERT PVS ComBox 200

Inverter - Station 1

InverterSINVERT PVS

Weather sensors

SINVERT PVS ComBox 100

Inverter - Stations 2-n

InverterSINVERT PVS

Client

DSL-Router

SINVERT WebMonitor

Industrial Ethernet FOC ring

Industrial Ethernet

Internet

RE10_00033d

SINVERT PVSWeatherStation 200

Chapter3.book Seite 6 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 7: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

3/7Siemens RE 10 · 2012

PVS 600 Series, 500 ... 2400 kW

3

Integration of SINVERT PVS inverters into a photovoltaic plant with communication via an Ethernet network, solar PV plant control by means of the SINVERT PVS ControlBox 300, and monitoring with WinCC

■ Configuration

The SINVERT Select software is available to support the config-uring of photovoltaic plants.

This configuring program is designed to determine the ideal configuration for a photovoltaic plant with SINVERT PVS invert-ers. The program calculates all practical combinations for most of the photovoltaic modules available on the market in conjunc-tion with SINVERT inverters, and enables evaluation and optimi-zation of the calculated combinations in a simple and under-standable way.

Only a few details, such as the location, type of photovoltaic module, and plant size are required for the dimensioning pro-cess.

Two methods are available for dimensioning the inverters:• With the automatic dimensioning method, the ideal SINVERT

inverters for the selected photovoltaic module and power specifications are selected from the entire spectrum of SIN-VERT inverters. You can optionally specify the required num-ber of photovoltaic modules per string and the applicable lim-its with respect to power specifications (i.e. area, number of modules or total power output).

• With the manual dimensioning method, you can specify up to two SINVERT inverters from the SINVERT range for calculation of the installation.

For further information, see Chapter 4 "Software and monitoring".

WinCC PC

SCALANCE S VPN Router

SINVERT PVS ComBox 100

Inverter - Station 1

Circle controlreceiver

EVU

InverterSINVERT PVS

SINVERT PVS ComBox 100

Inverter - Stations 2-n

InverterSINVERT PVS

SINVERT PVS ControlBox 300

Weather sensors

Internet

WinCC WebNavigator

DSL-Router

Industrial Ethernet FOC ring

Industrial Ethernet

RE10_00029d

SINVERT PVSWeatherStation 200

0 %

100 %

Chapter3.book Seite 7 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 8: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

PVS 600 Series, 500 ... 2400 kW

3/8 Siemens RE 10 · 2012

3

■ Technical specifications

PVS500, PVS1000, PVS1500 and PVS2000 in 50 and 60 Hz

6AG3111-1AH00-3AB0

6AG3111-2AH00-3AB0

6AG3111-1AH10-3AB0

6AG3111-2AH10-3AB0

6AG3111-1AH20-3AB0

6AG3111-2AH20-3AB0

6AG3111-1AH30-3AB0

6AG3111-2AH30-3AB0

General technical data

Product type designation SINVERT PVS500

SINVERT PVS500

SINVERT PVS1000

SINVERT PVS1000

SINVERT PVS1500

SINVERT PVS1500

SINVERT PVS2000

SINVERT PVS2000

Line frequency suitable for infeed operation nominal value

Hz 50 60 50 60 50 60 50 60

Output class for PV inverters 500 500 1000 1000 1500 1500 2000 2000

Design of PV inverter unit single device single device master-slave combination

master-slave combination

master-slave combination

master-slave combination

master-slave combination

master-slave combination

Number of PV inverter sub-units 1 1 2 2 3 3 4 4

Degree of protection IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20

Installation altitude• minimum m 0 0 0 0 0 0 0 0• maximum m 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000• for nominal active power

- minimum permissible m 0 0 0 0 0 0 0 0- maximum permissible m 1 000 1 000 1 000 1 000 1 000 1 000 1 000 1 000

Incoming air temperature at nominal value of active power supplied maximum

°C 40 40 40 40 40 40 40 40

Ambient temperature• during operating °C 0 … 50 0 … 50 0 … 50 0 … 50 0 … 50 0 … 50 0 … 50 0 … 50• during storage °C -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70• during transport °C -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70

Connection method for PV inverters

without trans-former

without trans-former

without trans-former

without trans-former

without trans-former

without trans-former

without trans-former

without trans-former

Inputs

MPP voltage V 450 … 750 450 … 750 450 … 750 450 … 750 450 … 750 450 … 750 450 … 750 450 … 750

Input voltage on the DC side• for the start of the infeed operation V 600 600 600 600 600 600 600 600• for possible infeed operation V 450 … 750 450 … 750 450 … 750 450 … 750 450 … 750 450 … 750 450 … 750 450 … 750• nominal value V 465 465 465 465 465 465 465 465• maximum permissible V 820 820 820 820 820 820 820 820

Consumed active power on the DC side nominal value

kW 513 513 1 026 1 026 1 539 1 539 2 052 2 052

Total power used on the DC side maximum

A 1 103 1 103 2 206 2 206 3 309 3 309 4 412 4 412

Number of inputs on the DC side 3 3 6 6 9 9 12 12

Input current per DC input maximum

A 368 368 368 368 368 368 368 368

Outputs

Output voltage on the AC side for infeed operation nominal value

V 288 288 288 288 288 288 288 288

Active power supplied on the AC side• in permanent operation nominal

valuekW 500 500 1 000 1 000 1 500 1 500 2 000 2 000

• maximum kW 500 500 1 000 1 000 1 500 1 500 2 000 2 000

Current supplied on the AC side maximum

A 1 002 1 002 2 004 2 004 3 006 3 006 4 008 4 008

Power factor at nominal value of active power supplied nominal value

1 1 1 1 1 1 1 1

Power factor inductive 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95

Power factor capacitive 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95

10139489.fm Seite 8 Dienstag, 17. Januar 2012 2:45 14

© Siemens AG 2012

Page 9: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

3/9Siemens RE 10 · 2012

PVS 600 Series, 500 ... 2400 kW

3

Efficiency / heat loss

Efficiency• maximum possible % 98.4 98.4 98.4 98.4 98.4 98.4 98.4 98.4• according to Euro % 98.1 98.1 98.3 98.3 98.3 98.3 98.3 98.3• according to CEC % 98.2 98.2 98.3 98.3 98.3 98.3 98.3 98.3

Type of installation indoor instal-lation

indoor instal-lation

indoor instal-lation

indoor instal-lation

indoor instal-lation

indoor instal-lation

indoor instal-lation

indoor instal-lation

Auxiliary voltage nominal value V 400 400 400 400 400 400 400 400

Auxiliary voltage frequency nominal value

Hz 50 60 50 60 50 60 50 60

Active power inputfrom external auxiliary voltage• for infeed mode

- without cabinet heating maximum

W 2 650 3 500 5 300 7 000 7 950 10 500 10 600 14 000

• for night mode- without cabinet heating

maximumW 190 350 380 700 570 1 050 760 1 400

- with cabinet heating maximum W 440 600 880 1 200 1 320 1 800 1 760 2 400

Mounting / fastening / dimensions

Built in orientation vertical vertical vertical vertical vertical vertical vertical vertical

Type of mounting Floor mount-ing installa-tion

Floor mount-ing installa-tion

Floor mount-ing installa-tion

Floor mount-ing installa-tion

Floor mount-ing installa-tion

Floor mount-ing installa-tion

Floor mount-ing installa-tion

Floor mount-ing installa-tion

Width of PV inverter subunits m 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

Height of PV inverter subunits m 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

Depth of PV inverter subunits m 0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73

Weight of the single device kg 2 085 2 085 2 085 2 085 2 085 2 085 2 085 2 085

Certifications / approvals

Verification of suitability CE mark Yes Yes Yes Yes Yes Yes Yes Yes

Standard for safety EN 50178 Yes Yes Yes Yes Yes Yes Yes Yes

Product quality EMC interfer-ence resistance industry according to IEC 61000-6-2

Yes Yes Yes Yes Yes Yes Yes Yes

Product quality EMC emitted interference industry according to IEC 61000-6-4

Yes Yes Yes Yes Yes Yes Yes Yes

Standard for harmonics IEC 61400-21

Yes Yes Yes Yes Yes Yes Yes Yes

Ordering options

• 1000 V option 6AG3911-3GA00-0AH0

6AG3911-3GA00-0AH0

6AG3911-3GA10-0AH0

6AG3911-3GA10-0AH0

6AG3911-3GA20-0AH0

6AG3911-3GA20-0AH0

6AG3911-3GA30-0AH0

6AG3911-3GA30-0AH0

• PV array grounding negative pole 6AG3911-3FB00-0AH0

6AG3911-3FB00-0AH0

6AG3911-3FB10-0AH0

6AG3911-3FB10-0AH0

6AG3911-3FB20-0AH0

6AG3911-3FB20-0AH0

6AG3911-3FB30-0AH0

6AG3911-3FB30-0AH0

• PV array grounding positive pole 6AG3911-3FA00-0AH0

6AG3911-3FA00-0AH0

6AG3911-3FA10-0AH0

6AG3911-3FA10-0AH0

6AG3911-3FA20-0AH0

6AG3911-3FA20-0AH0

6AG3911-3FA30-0AH0

6AG3911-3FA30-0AH0

• Cabinet heating 6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

• Symmetry monitoring 6AG3911-3EA00-0AH0

6AG3911-3EA00-0AH0

6AG3911-3EA10-0AH0

6AG3911-3EA10-0AH0

6AG3911-3EA20-0AH0

6AG3911-3EA20-0AH0

6AG3911-3EA30-0AH0

6AG3911-3EA30-0AH0

6AG3111-1AH00-3AB0

6AG3111-2AH00-3AB0

6AG3111-1AH10-3AB0

6AG3111-2AH10-3AB0

6AG3111-1AH20-3AB0

6AG3111-2AH20-3AB0

6AG3111-1AH30-3AB0

6AG3111-2AH30-3AB0

Chapter3.book Seite 9 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 10: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

PVS 600 Series, 500 ... 2400 kW

3/10 Siemens RE 10 · 2012

3

PVS600, PVS1200, PVS1800 and PVS2400 in 50 and 60 Hz

6AG3111-1AH00-0AB0

6AG3111-2AH00-0AB0

6AG3111-1AH10-0AB0

6AG3111-2AH10-0AB0

6AG3111-1AH20-0AB0

6AG3111-2AH20-0AB0

6AG3111-1AH30-0AB0

6AG3111-2AH30-0AB0

General technical data

Product type designation SINVERT PVS600

SINVERT PVS600

SINVERT PVS1200

SINVERT PVS1200

SINVERT PVS1800

SINVERT PVS1800

SINVERT PVS2400

SINVERT PVS2400

Line frequency suitable for infeed operation nominal value

Hz 50 60 50 60 50 60 50 60

Output class for PV inverters 600 600 1200 1200 1800 1800 2400 2400

Design of PV inverter unit single device single device master-slave combination

master-slave combination

master-slave combination

master-slave combination

master-slave combination

master-slave combination

Number of PV inverter sub-units 1 1 2 2 3 3 4 4

Protection class IP IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20

Installation altitude• minimum m 0 0 0 0 0 0 0 0• maximum m 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000• for nominal active power

- minimum permissible m 0 0 0 0 0 0 0 0- maximum permissible m 1 000 1 000 1 000 1 000 1 000 1 000 1 000 1 000

Incoming air temperature at nominal value of active power supplied maximum

°C 40 40 40 40 40 40 40 40

Ambient temperature• during operating °C 0 … 50 0 … 50 0 … 50 0 … 50 0 … 50 0 … 50 0 … 50 0 … 50• during storage °C -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70• during transport °C -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70

Connection methodfor PV inverters

without trans-former

without trans-former

without trans-former

without trans-former

without trans-former

without trans-former

without trans-former

without trans-former

Inputs

MPP voltage V 570 … 750 570 … 750 570 … 750 570 … 750 570 … 750 570 … 750 570 … 750 570 … 750

Input voltage on the DC side• for the start of the infeed operation V 700 700 700 700 700 700 700 700• for possible infeed operation V 570 … 750 570 … 750 570 … 750 570 … 750 570 … 750 570 … 750 570 … 750 570 … 750• nominal value V 570 570 570 570 570 570 570 570• maximum permissible V 820 820 820 820 820 820 820 820

Consumed active power on the DC side nominal value

kW 613 613 1 226 1 226 1 839 1 839 2 452 2 452

Total power used on the DC side maximum

A 1 104 1 104 2 208 2 208 3 312 3 312 4 416 4 416

Number of inputs on the DC side 3 3 6 6 9 9 12 12

Input current per DC input maximum

A 368 368 368 368 368 368 368 368

Outputs

Output voltage on the AC side for infeed operation nominal value

V 370 370 370 370 370 370 370 370

Active power supplied on the AC side• in permanent operation nominal

valuekW 600 600 1 200 1 200 1 800 1 800 2 400 2 400

• maximum kW 600 600 1 200 1 200 1 800 1 800 2 400 2 400

Current supplied on the AC side maximum

A 936 936 1 872 1 872 2 808 2 808 3 744 3 744

Power factor at nominal value of active power supplied nominal value

1 1 1 1 1 1 1 1

Power factor inductive 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95

Power factor capacitive 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95

Chapter3.book Seite 10 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 11: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

3/11Siemens RE 10 · 2012

PVS 600 Series, 500 ... 2400 kW

3

Efficiency / heat loss

Efficiency• maximum possible % 98.7 98.7 98.7 98.7 98.7 98.7 98.7 98.7• according to Euro % 98.4 98.4 98.6 98.6 98.6 98.6 98.6 98.6• according to CEC % 98.5 98.5 98.6 98.6 98.6 98.6 98.6 98.6

Type of installation indoor installation

indoor installation

indoor installation

indoor installation

indoor installation

indoor installation

indoor installation

indoor installation

Auxiliary voltage nominal value V 400 400 400 400 400 400 400 400

Auxiliary voltage frequency nominal value

Hz 50 60 50 60 50 60 50 60

Active power inputfrom external auxiliary voltage• for infeed mode

- without cabinet heating maximum

W 2 650 3 500 5 300 7 000 7 950 10 500 10 600 14 000

• for night mode- without cabinet heating

maximumW 190 350 380 700 570 1 050 760 1 400

- with cabinet heating maximum W 440 600 880 1 200 1 320 1 800 1 760 2 400

Mounting / fastening / dimensions

Built in orientation vertical vertical vertical vertical vertical vertical vertical vertical

Type of mounting Floor mount-ing installa-tion

Floor mount-ing installa-tion

Floor mount-ing installa-tion

Floor mount-ing installa-tion

Floor mount-ing installa-tion

Floor mount-ing installa-tion

Floor mount-ing installa-tion

Floor mount-ing installa-tion

Width of PV inverter subunits m 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

Height of PV inverter subunits m 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

Depth of PV inverter subunits m 0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73

Weight of the single device kg 2 085 2 085 2 085 2 085 2 085 2 085 2 085 2 085

Certifications / approvals

Verification of suitability CE mark Yes Yes Yes Yes Yes Yes Yes Yes

Standard for safety EN 50178 Yes Yes Yes Yes Yes Yes Yes Yes

Product quality EMC interfer-ence resistance industry according to IEC 61000-6-2

Yes Yes Yes Yes Yes Yes Yes Yes

Product quality EMC emitted interference industry according to IEC 61000-6-4

Yes Yes Yes Yes Yes Yes Yes Yes

Standard for harmonics IEC 61400-21

Yes Yes Yes Yes Yes Yes Yes Yes

Ordering options

• 1000 V option 6AG3911-3GA00-0AH0

6AG3911-3GA00-0AH0

6AG3911-3GA10-0AH0

6AG3911-3GA10-0AH0

6AG3911-3GA20-0AH0

6AG3911-3GA20-0AH0

6AG3911-3GA30-0AH0

6AG3911-3GA30-0AH0

• PV array grounding negative pole 6AG3911-3FB00-0AH0

6AG3911-3FB00-0AH0

6AG3911-3FB10-0AH0

6AG3911-3FB10-0AH0

6AG3911-3FB20-0AH0

6AG3911-3FB20-0AH0

6AG3911-3FB30-0AH0

6AG3911-3FB30-0AH0

• PV array grounding positive pole 6AG3911-3FA00-0AH0

6AG3911-3FA00-0AH0

6AG3911-3FA10-0AH0

6AG3911-3FA10-0AH0

6AG3911-3FA20-0AH0

6AG3911-3FA20-0AH0

6AG3911-3FA30-0AH0

6AG3911-3FA30-0AH0

• Cabinet heating 6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

6AG3911-3HA20-1AH0

• Symmetry monitoring 6AG3911-3EA00-0AH0

6AG3911-3EA00-0AH0

6AG3911-3EA10-0AH0

6AG3911-3EA10-0AH0

6AG3911-3EA20-0AH0

6AG3911-3EA20-0AH0

6AG3911-3EA30-0AH0

6AG3911-3EA30-0AH0

6AG3111-1AH00-0AB0

6AG3111-2AH00-0AB0

6AG3111-1AH10-0AB0

6AG3111-2AH10-0AB0

6AG3111-1AH20-0AB0

6AG3111-2AH20-0AB0

6AG3111-1AH30-0AB0

6AG3111-2AH30-0AB0

Chapter3.book Seite 11 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 12: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

PVS 600 Series, 500 ... 2400 kW

3/12 Siemens RE 10 · 2012

3

■ Selection and ordering data

Ordering information

The SINVERT PVS inverter can be ordered with additional op-tions (see page 3/14). The order number of the option must be specified after the order number of the basic unit. The options are pre-installed in the basic unit prior to shipment and can be ordered only in conjunction with a basic unit.

Retrospective ordering of options is not possible.

Example of an order with two options

Scope of order: Basic unit PVS1000 with 50 Hz including 1000 V option and PV array grounding positive pole

1st item: 6AG3111-1AH10-3AB0 (basic unit PVS1000 600 series IEC-compliant 50 Hz M1S)

2nd item: 6AG3911-3GA10-0AH0 (1000 V option 600 series M1S)

3rd item: 6AG3911-3FA10-0AH0 (PV array grounding positive pole M1S)

Product type designation

Active power outputRated value

Output voltageRated value

MPP voltage Input voltageMaximum permissible

Order No.

kW V V V

SINVERT PVS 600 series invertersGrid frequency 50 Hz (rated value)PVS500 500 288 450 … 750 820 6AG3111-1AH00-3AB0

PVS1000 1 000 288 450 … 750 820 6AG3111-1AH10-3AB0

PVS1500 1 500 288 450 … 750 820 6AG3111-1AH20-3AB0

PVS2000 2 000 288 450 … 750 820 6AG3111-1AH30-3AB0

PVS600 600 370 570 … 750 820 6AG3111-1AH00-0AB0

PVS1200 1 200 370 570 … 750 820 6AG3111-1AH10-0AB0

PVS1800 1 800 370 570 … 750 820 6AG3111-1AH20-0AB0

PVS2400 2 400 370 570 … 750 820 6AG3111-1AH30-0AB0Grid frequency 50 Hz (rated value)PVS500 500 288 450 … 750 820 6AG3111-2AH00-3AB0

PVS1000 1 000 288 450 … 750 820 6AG3111-2AH10-3AB0

PVS1500 1 500 288 450 … 750 820 6AG3111-2AH20-3AB0

PVS2000 2 000 288 450 … 750 820 6AG3111-2AH30-3AB0

PVS600 600 370 570 … 750 820 6AG3111-2AH00-0AB0

PVS1200 1 200 370 570 … 750 820 6AG3111-2AH10-0AB0

PVS1800 1 800 370 570 … 750 820 6AG3111-2AH20-0AB0

PVS2400 2 400 370 570 … 750 820 6AG3111-2AH30-0AB0

Chapter3.book Seite 12 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 13: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

3/13Siemens RE 10 · 2012

PVS 600 Series, 500 ... 2400 kW

3

Further options can be ordered in addition:

Notes:

The option "PV array grounding positive pole" cannot be ordered in combination with the option "PV array grounding negative pole".

The option "PV array grounding negative pole" cannot be or-dered in combination with the option "PV array grounding posi-tive pole".

Weitere Informationen für zusätzliche Optionen see "Options", page 3/14".

The assignment between options and the respective basic units can be identified by the designation. Each order number is coded to indicate the master/slave configuration in which the unit is available (M = master, X = number of slaves, S = slave). A matching code is also used in the option designations. This coding clearly identifies the assignment between unit and con-figuration.

Product type designation For inverter Order No.

Options for SINVERT PVS 600 series inverters1000 V option 600 series1000 V option 600 series M PVS500/600 6AG3911-3GA00-0AH0

1000 V option 600 series M1S PVS1000/1200 6AG3911-3GA10-0AH0

1000 V option 600 series M2S PVS1500/1800 6AG3911-3GA20-0AH0

1000 V option 600 series M3S PVS2000/2400 6AG3911-3GA30-0AH0

PV array grounding 600 seriesPV array grounding positive pole 600 series M PVS500/600 6AG3911-3FA00-0AH0

PV array grounding positive pole 600 series M1S PVS1000/1200 6AG3911-3FA10-0AH0

PV array grounding positive pole 600 series M2S PVS1500/1800 6AG3911-3FA20-0AH0

PV array grounding positive pole 600 series M3S PVS2000/2400 6AG3911-3FA30-0AH0

PV array grounding negative pole 600 series M PVS500/600 6AG3911-3FB00-0AH0

PV array grounding negative pole 600 series M1S PVS1000/1200 6AG3911-3FB10-0AH0

PV array grounding negative pole 600 series M2S PVS1500/1800 6AG3911-3FB20-0AH0

PV array grounding negative pole 600 series M3S PVS2000/2400 6AG3911-3FB30-0AH0

Cabinet heating 600 seriesCabinet heating 600 series M PVS500/600 6AG3911-3HA00-1AH0

Cabinet heating 600 series M1S PVS1000/1200 6AG3911-3HA10-1AH0

Cabinet heating 600 series M2S PVS1500/1800 6AG3911-3HA20-1AH0

Cabinet heating 600 series M3S PVS2000/2400 6AG3911-3HA30-1AH0

Symmetry monitoring 600 seriesSymmetry monitoring 600 series M PVS500/600 6AG3911-3EA00-0AH0

Symmetry monitoring 600 series M1S PVS1000/1200 6AG3911-3EA10-0AH0

Symmetry monitoring 600 series M2S PVS1500/1800 6AG3911-3EA20-0AH0

Symmetry monitoring 600 series M3S PVS2000/2400 6AG3911-3EA30-0AH0

Chapter3.book Seite 13 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 14: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

PVS 600 Series, 500 ... 2400 kW

3/14 Siemens RE 10 · 2012

3

■ Options

1000 V option 600 series

The 1000 V option increases the maximum permissible input voltage of the SINVERT PVS inverter from 820 to 1 000 V. Provi-sion of this option ensures that the PV plant will go into operation smoothly even with voltages in excess of 820 V which can de-velop, for example, on cold days or in arrays containing thin-film modules. The option thus maximizes the potential yield of the in-stallation. The MPP voltage range of the SINVERT PVS inverter is not changed.

PV array grounding positive pole 600 series

The "PV array grounding positive pole" option allows functional grounding of the positive conductor inside the SINVERT PVS in-verter if this is a requirement of the photovoltaic modules used (e.g. large number of thick-film modules). The current is mea-sured between ground and the positive pole for the purpose of monitoring plant behavior. When the current increases to a risky level, the ground connection is automatically separated. It is only by this ground that damage to modules and a steady loss of power can be prevented. In other words, this grounding ar-rangement can ensure continuous maximum yields from the so-lar panels

Note:

The option "PV array grounding positive pole" cannot be ordered in combination with the option "PV array grounding negative pole".

PV array grounding negative pole 600 series

The "PV array grounding negative pole" option allows functional grounding of the negative conductor inside the SINVERT PVS in-verter if this is a requirement of the photovoltaic modules used (e.g. large number of thin-film modules). The current is mea-sured between ground and the negative pole for the purpose of monitoring plant behavior. When the current increases to a risky level, the ground connection is automatically separated. It is only by this ground that damage to modules and a steady loss of power can be prevented. In other words, this grounding ar-rangement can ensure continuous maximum yields from the so-lar panels.

Note:

The option "PV array grounding negative pole" cannot be or-dered in combination with the option "PV array grounding posi-tive pole".

Cabinet heating 600 series

The "Cabinet heating" option minimizes the risk of condensation forming on moisture-sensitive components in the SINVERT PVS inverter at low ambient temperatures and ensures an ideal (min-imum) operating temperature for reliable operation of the in-verter. Reliable operation and maximum energy yields to the grid are dependent on compliance with the operating temperature range prescribed for the relevant SINVERT PVS inverter. This function is recommended for locations at which the ambient tem-perature can drop below 7 °C.

Symmetry monitoring 600 series

The "Symmetry monitoring" option measures the normalized cur-rents at the DC inputs internally and cross-compares the values. If this comparison indicates deviations over time, a message is generated. The message can be used as a guide to localizing faults early in sections of the PV generator (e.g. cell failure).

Chapter3.book Seite 14 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 15: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kWCentral Inverters according to IEC

3/15Siemens RE 10 · 2012

PVS 600 Series, 500 ... 2400 kW

3

■ Schematics

Block diagram of SINVERT PVS, master with touch panel and slave without touch panel

=

~

RE10_00039

Pho

tovo

ltaic

arr

ay

DC input 1

DC cabinet AC cabinet

Touchpanel (master only) Power supply

Control system

FilterEMC filter

EMC filter

DC input 2

DC input 3

Med

ium

-vol

tage

tran

sfor

mer

Aux

iliar

y po

wer

su

pply

AC outputL1, L2, L3

Chapter3.book Seite 15 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 16: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

Central inverters according to UL

3/16 Siemens RE 10 · 2012

3

■ Overview

Central Inverter according to UL

The 3-phase SINVERT PVS inverters with integral low-voltage transformer are reliable, grid-compatible and cost-effective pho-tovoltaic inverters which are used to convert solar energy into grid-compliant AC voltage for infeed into conventional power supply networks.

SINVERT PVS compact inverters are available with power out-puts of 350, 700, 1 050 and 1 400 kW.

Their characteristics are described below.

Output and efficiency• SINVERT PVS inverters are particularly efficient in every ope-

rating point. They are capable of top efficiency levels of up to 97.2%.

• They are suitable for photovoltaic installations with a power output of 350 kW and above.

Connection and installation• SINVERT PVS inverters have integral DC and AC connections.• They feature a terminal compartment with separate panels for

DC and AC connections.• The DC and AC cables are connected from below through

duct openings in the the closed base panel.• SINVERT PVS inverters must be installed on a dry, non-com-

bustible and level surface.

Interfaces• Ethernet

Operator control and monitoring• SINVERT PVS inverters have a compact panel with 4.3" TFT

widescreen display (480 x 272 pixels and 256 colors) that clearly shows current infeed power data and other informa-tion.

• SINVERT PVS inverters are operated using touch screen with intuitive menu prompting.

■ Benefits

• Maximum efficiency of up to 97.2% guarantees maximum PV plant yields.

• The master/slave principle with "rotating master" employs an ingenious process to connect or disconnect inverter subunits depending on irradiation levels Using this system, it is possi-ble to operate the photovoltaic plant extremely efficiently to produce maximum plant yields even when irradiation levels are low.

• In master/slave systems, the "rotating master" always starts the inverter subunit with the fewest operating hours first. In this way, the total operating hours are evenly distributed among all the subunits. The durability and availability of the system are enhanced as a result, helping to minimize the total cost of ow-nership.

• Low servicing and maintenance costs through the use of fully developed, tried-and-tested standard industrial products

• High availability by virtue of low-maintenance design with rugged, durable components

■ Application

SINVERT PVS inverters are ideally suitable for application in photovoltaic power plants ("Power Plant" segment) with outputs of 350 kW and above.

They are typically employed in ground-mounted systems.

SINVERT PVS inverters are manufactured to relevant standards and regulations. They are designed for application in countries which require UL certification (see "Technical data", page 3/20).

Chapter3.book Seite 16 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 17: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

3/17Siemens RE 10 · 2012

Central inverters according to UL

3

■ Design

SINVERT PVS inverters are characterized by their compact and rugged design. They are based on fully developed, tried-and-tested standard industrial products.

On units which operate according to the master/slave principle with "rotating master", up to four inverter subunits can be inter-connected to form a master/slave system.

SINVERT PVS inverters are self-commutated, IGBT-based (IGBT: Insulated Gate Bipolar Transistor) units with pulse width modula-tion.

They are equipped with integral, low-noise fans for dissipating heat losses. Air is drawn in through ventilation grilles on the lower half of the front panel. Once through the grille, the air is guided upwards through air ducts which gradually narrow in order to in-crease the flow rate and strengthen the heat dissipating effect. The air exits at the top.

SINVERT PVS inverters have a separate air duct for the transfor-mer. This segregates the transformer heat losses from the con-trol components.

SINVERT PVS inverters have several DC inputs (see "Technical data", page 3/20), each of which is equipped with LV HRC fuses and DC contactors. The SINVERT PVS inverter can be discon-nected from the photovoltaic generator by means of the DC con-tactors.

The SINVERT PVS inverters are equipped with one AC contactor and one circuit breaker at the AC end. This switchgear can be used to decouple the SINVERT PVS inverter from the low-voltage or medium-voltage network.

Surge protection devices are integrated at the AC and DC ends.

SINVERT PVS inverters feature a terminal compartment with se-parate panels for DC and AC connections.

The DC and AC cables are connected from below through duct openings in the the closed base panel.

All parts of the SINVERT PVS cabinet can be recycled.

A control and display panel is mounted in the door of the AC cu-bicle (see "Function").

The compact panel with 4.3" TFT widescreen display clearly shows the infeed power data and other information, and allows operation of the inverter by the touch screen method (see "Func-tion").

Indicator lamps are located below the control and display panel. These indicate the current operating state of the SINVERT PVS inverter (see "Function").

■ Function

Basic function

Within photovoltaic plants, SINVERT PVS inverters are the link between the photovoltaic generator (total of all electrically inter-connected photovoltaic modules) and the public AC grid. Their basic function is to convert the direct current produced by the photovoltaic generator into an alternating current and to adjust this current to the frequency and magnitude of a specified vol-tage for infeed into the public grid. Conversion to grid-compliant AC can be carried out with minimum losses using modern power electronics.

Temperature monitoring

SINVERT PVS inverters have internal temperature monitoring that protects against violation of the permissible ambient tempe-rature.

Control and display panel

The control and display panel is a touch panel which shows a corresponding "screen" for each menu item. The user navigates between menu items and between functions within individual items by touching the panel at the "screen" position at which a button with the corresponding command (e.g. "Back", "Settings" or "Service") is displayed.

In addition to the "screens" which display current values or fault messages, for example, there are also "screens" for changing system settings and servicing activities. The items "Settings" and "Service" in the main menu are protected by a password.

Control and display panel

Chapter3.book Seite 17 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 18: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

Central inverters according to UL

3/18 Siemens RE 10 · 2012

3

Status displays

There are two indicator lamps for visualizing the different inverter statuses.

Communications

SINVERT PVS inverters have an Ethernet interface. When the in-verter is linked to an Ethernet network, it can exchange data with a visualization system such as WinCC via the Ethernet interface (see Chapter 4 "Software and monitoring"). With a visualization system it is possible, for example, to operate and visualize the photovoltaic installation and to acquire, store and visualize mea-sured data and messages. Integrating the inverter into a network also makes it easier to analyze the photovoltaic yield data (set-point/actual value comparisons), operate the installation from a remote location, arrange service callouts at short notice, reduce system downtimes to a minimum, and thus optimize the yield of the plant. Interfaces to other communication channels (e.g. DSL, analog telephone, ISDN, GSM) can be provided if necessary.

Master/slave

The master/slave principle with "rotating master" is a mas-ter/slave system comprising up to four interconnected inverter subunits. It employs an ingenious process to connect or discon-nect inverter subunits depending on irradiation levels (calcula-ted according to the sun's path, cloud conditions, etc.). One in-verter subunit acts as the master. The master is started up first and operates when irradiation levels are low. As irradiation levels increase, the power limit of the master is reached and the next inverter subunit, i.e. the slave, is switched in. Depending on the configuration, up to three slaves can be switched in. As irradia-tion levels drop again, the subunits are disconnected in stages. One advantage of the master/slave principle is that the inverters operate more efficiently and produce higher yields when irradia-tion levels (which determine the PV generator output) are low than would be achieved if only one single central inverter were used.

In master/slave systems, the "rotating master" always starts the inverter subunit with the fewest operating hours as the master. In this way, the total operating hours are evenly distributed among all the subunits.

Provision of supplementary functions by options

The standard scope of functions of SINVERT PVS inverters can be optionally expanded. Optionally available are, for example, a PV array grounding system or a voltage measurement at the DC inputs (see "Options", page 3/23).

Indicators Status Description

Green indicator light "Run" Not lit: No infeed voltage present on AC side of SINVERT PVS inverter.The control unit has failed.

Flashing slowly, 1 s cycle: The key switch is not in position "2".The inverter subunit is in the "Ready" state.

Flashing fast, 250 ms cycle: The inverter subunit is in the "Run" state.

Illuminated steadily: The inverter subunit is in the "Infeed" state.The inverter subunit is feeding energy back into the grid.

Yellow indicator light "Fault" Not lit: No faults detected.

Flashing slowly, 1 s cycle: The control unit has signaled a warning. The inverter subunit remains in operation, but maintenance is required.

Flashing fast, 250 ms cycle: The control unit has signaled a fault which will be automatically acknow-ledged after a wait period. The inverter subunit will start up again after the fault has been acknowledged.

Illuminated steadily: The control unit has signaled a fault which must be acknowledged manually.

Key-operated switch "1/2/3" 1 – Lock: The inverter subunit is in the "Ready" state.

Switchover from "1" to "2": By turning the key-operated switch from position "1" to position "2", you can manually acknowledge all active faults

2 – Enable: The inverter subunit is in the "Ready" or "Infeed" state.

3 – Quick start (non-latching): The inverter subunit executes a quick start. The standard waiting times following a fault no longer apply.

Chapter3.book Seite 18 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 19: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

3/19Siemens RE 10 · 2012

Central inverters according to UL

3

■ Integration

The inverter is provided with standardized interfaces so that it can be integrated into a control system or an existing customer installation. The interfaces can also be used to remotely monitor and operate the device, for example, through the Internet portal or by means of the WinCC visualization system.

Professional operations management can be implemented using the WinCC visualization system (see Chapter 4 "Software and monitoring").

The advantages of the WinCC visualization system include:• Clear display of plants, plant sections (subplants) and inver-

ters• Remote access to inverters• Remote monitoring• Acquisition, long-term storage and display of current and his-

torical data• Graphical representation of the monitored data• Plant monitoring• Messaging services using e-mail and text message• Fault messages can be specifically configured for customized

operations management• Map

■ Configuration

The SINVERT Select software is available to support the configu-ring of photovoltaic plants.

This configuring program is designed to determine the ideal configuration for a photovoltaic plant with SINVERT PVS inver-ters. The program calculates all practical combinations for most of the photovoltaic modules available on the market in conjunc-tion with SINVERT inverters, and enables evaluation and optimi-zation of the calculated combinations in a simple and understan-dable way.

Only a few details, such as the location, type of photovoltaic mo-dule, and plant size are required for the dimensioning process.

Two methods are available for dimensioning the inverters:• With the automatic dimensioning method, the ideal SINVERT

inverters for the selected photovoltaic module and power spe-cifications are selected from the entire spectrum of SINVERT inverters. You can optionally specify the required number of photovoltaic modules per string and the applicable limits with respect to power specifications (i.e. area, number of modules or total power output).

• With the manual dimensioning method, you can specify up to two SINVERT inverters from the SINVERT range for calculation of the installation.

For further information, see Chapter 4 "Software and monitoring".

Chapter3.book Seite 19 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 20: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

Central inverters according to UL

3/20 Siemens RE 10 · 2012

3

■ Technical specifications

6AG3101-4PD00-0AA0 6AG3101-4QR00-0AA0 6AG3101-4SC00-0AA0 6AG3101-4SF00-0AA0

General technical data

Product type identification SINVERT PVS351 UL SINVERT PVS701 UL SINVERT PVS1051 UL SINVERT PVS1401 UL

Rating class for PV inverter 350 700 1050 1400

Version of PV inverter unit Single device Master-slave combination Master-slave combination Master-slave combination

Number of PV inverter subunits 1 2 3 4

Degree of protection IP21 IP21 IP21 IP21

Installation altitude• minimum permissible m 0 0 0 0• maximum permissible m 2 000 2 000 2 000 2 000• at rated power value

- minimum permissible m 0 0 0 0- maximum permissible m 1 000 1 000 1 000 1 000

Inlet air temperature/ at rated value of AC active power output/ maximum

°C 30 30 30 30

Ambient temperature• during operation °C 0 … 50 0 … 50 0 … 50 0 … 50• during storage °C 0 … 70 0 … 70 0 … 70 0 … 70• during transport °C 0 … 70 0 … 70 0 … 70 0 … 70

Connection method for PV inverter

With transformer With transformer With transformer With transformer

Inputs

MPP voltage V 330 … 480 330 … 480 330 … 480 330 … 480

Input voltage/ at DC end• for starting infeed operation V 330 330 330 330• for possible infeed operation V 330 … 600 330 … 600 330 … 600 330 … 600• rated value V 400 400 400 400• maximum permissible V 600 600 600 600

Active power input/ at DC end/ rated value

kW 364 728 1 092 1 456

Total current input/ at DC end/ maximum

A 1 103 2 206 3 309 4 412

Number of inputs/ at DC end 3 6 9 12

Input current/ per DC input/ maximum

A 368 368 368 368

Outputs

Output voltage/ at AC end/ for infeed mode/ rated value

V 480 480 480 480

Grid frequency/ for infeed mode/ rated value

Hz 60 60 60 60

Active power output/ at AC end• in permanent operation /

rated valuekW 350 700 1 050 1 400

• maximum kW 385 770 1 155 1 540

Current output/ at AC end/ maximum

A 424 848 1 272 1 696

Power factor/ at rated value of AC active power output/ rated value

1 1 1 1

Power factor inductive minimum 0.95 0.95 0.95 0.95

Power factor capacitive minimum 0.95 0.95 0.95 0.95

Chapter3.book Seite 20 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 21: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

3/21Siemens RE 10 · 2012

Central inverters according to UL

3

1) Value when option S30 is selected2) Without option S10

Efficiency / heat loss

Efficiency/ maximum possible % 97.2 97.2 97.2 97.2

CEC efficiency factor % 96.6 96.8 96.7 96.4

Auxiliary voltage/ rated value V 480 1) 480 1) 480 1) 480 1)

Auxiliary voltage frequency/ rated value

Hz 60 1) 60 1) 60 1) 60 1)

Active power inputfrom external auxiliary voltage• for infeed mode W 2 650 1)2) 5 300 1)2) 7 950 1)2) 10 600 1)2)

• in night-time operation VA 205 1)2) 255 1)2) 305 1)2) 355 1)2)

Mounting / fastening / dimensions

Mounting position Vertical Vertical Vertical Vertical

Type of mounting Floor mounting Floor mounting Floor mounting Floor mounting

Width/ of single device mm 2 804 2 804 2 804 2 804

Height/ of single device mm 2 200 2 200 2 200 2 200

Depth/ of single device mm 745 745 745 745

Weight/ of single device kg 3 250 3 250 3 250 3 250

Certifications / approvals

Certificate of suitability UL / CSA UL / CSA UL / CSA UL / CSA

Product quality• for interference immunity

in industrial environmentsto IEC 61000-6-2

Yes Yes Yes Yes

• for interference emissionsin industrial environments to IEC 61000-6-4

Yes Yes Yes Yes

Standard• for safety UL 1741 UL 1741 UL 1741 UL 1741• for current harmonics UL 1741 UL 1741 UL 1741 UL 1741

6AG3101-4PD00-0AA0 6AG3101-4QR00-0AA0 6AG3101-4SC00-0AA0 6AG3101-4SF00-0AA0

Chapter3.book Seite 21 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 22: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

Central inverters according to UL

3/22 Siemens RE 10 · 2012

3

■ Selection and ordering data

Further options can be ordered in addition:

For further information about additional options see "Options", page 3/23.

Example of an order number with two order codes

Scope of order: Basic unit PVS351 UL with 60 Hz including PV array grounding positive pole and voltage measurement at DC inputs

6AG3101-4PD00-0AA0-Z D30 + D70

The two options "D30" and "D70" have been added to the order for a unit with Order No. 6AG3111-4PD00-0AA0.

Product typeidentification

Active power out-put / rated value

Output voltage / rated value

MPP voltage Input voltage /max. permissible

Order No.(for order code(s) see the table below)kW V V V

SINVERT inverter

Grid frequency 60 Hz (rated value)

PVS351 UL 350 000 480 330 ... 480 600 6AG3101-4PD00-0AA0-Z

PVS701 UL 700 000 480 330 ... 480 600 6AG3101-4QR00-0AA0-Z

PVS1051 UL 1 050 000 480 330 ... 480 600 6AG3101-4SC00-0AA0-Z

PVS1401 UL 1 400 000 480 330 ... 480 600 6AG3101-4SF00-0AA0-Z

Note:

The SINVERT PVS inverter can be ordered only with option D30 or D40.

PV array grounding positive pole

Note:

Option "D30" must not be ordered in combination with option "D40".

D30

PV array grounding negative pole

Note:

Option "D40" must not be ordered in combination with option "D30".

D40

For ordering, the complete Order No. must be supplemented with the required order code(s).

Order codes must not be repeated in plain text in the order.

The symbol "+" must be used to add further options.

Order No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

6 A G 3 1 0 1 - 4 . . 0 0 - 0 A A 0 - Z D . 0and additional order code(s)+ + . . . + . . . + . . .

Voltage measurement at DC inputs D70

Symmetry monitoring M10

Insulation (ISO) measurement M20

Interface to medium-voltage data

Note:

Option "P40" must always be ordered in combination with option "P50".

P40

Interface to container data

Note:

Option "P50" must always be ordered in combination with option "P40".

P50

Cabinet heating S10

AC auxiliary supply

Note:

Option "S30" must always be ordered in combination with option "S40".

S30

AC outputs for external loads

Note:

Option "S40" must always be ordered in combination with option "S30".

S40

Chapter3.book Seite 22 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 23: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

3/23Siemens RE 10 · 2012

Central inverters according to UL

3

■ Options

Option "D30" – PV array grounding positive pole

The "PV array grounding positive pole" option allows functional grounding of the positive conductor inside the SINVERT PVS in-verter if this is a requirement of the photovoltaic modules used (e.g. large number of thick-film modules). The current is measu-red between ground and the positive pole for the purpose of mo-nitoring plant behavior. When the current increases to a risky le-vel, the ground connection is automatically separated. It is only by this ground that damage to modules and a steady loss of po-wer can be prevented. In other words, this grounding arrange-ment can ensure continuous maximum yields from the solar pa-nels. This option must be employed if modules which require its use are installed in the plant.

Note:

Option "D30" must not be ordered in combination with option "D40".

Option "D40" – PV array grounding negative pole

The "PV array grounding negative pole" option allows functional grounding of the negative conductor inside the SINVERT PVS in-verter if this is a requirement of the photovoltaic modules used (e.g. large number of thin-film modules). The current is measu-red between ground and the negative pole for the purpose of monitoring plant behavior. When the current increases to a risky level, the ground connection is automatically separated. It is only by this ground that damage to modules and a steady loss of po-wer can be prevented. In other words, this grounding arrange-ment can ensure continuous maximum yields from the solar pa-nels.

Note:

Option "D40" must not be ordered in combination with option "D30".

Option "D70" – Voltage measurement at DC inputs

The "Voltage measurement at DC inputs" option measures the voltage applied to the DC inputs upcircuit of the DC contactors (at photovoltaic array end). The DC contactors for the DC inputs are switched by means of a software function only when the vol-tage has reached a defined value.

Option "M10" – Symmetry monitoring

The "Symmetry monitoring" option measures the normalized cur-rents at the DC inputs internally and cross-compares the values. If this comparison indicates deviations over time, a message is generated. The message can be used as a guide to localizing faults early in sections of the PV generator (e.g. cell failure).

Option "M20" – Insulation (ISO) measurement

The "Insulation measurement" option monitors the system for low resistance to ground resulting from an insulation fault (e.g. caused by a damaged cable). Depending on the type of insula-tion fault, an alarm is output or the inverter is tripped in order to protect personnel.

Option "P40" – Interface to medium-voltage data

The "Interface to medium-voltage data" option acquires the fol-lowing signals from the medium-voltage switchgear: Ground "connected", ground "disconnected", circuit breaker "closed", circuit-breaker "open", fuse tripped, fault on auxiliary switch, me-ter pulse.

The signals are displayed in the monitoring systems. The meter pulse (= pulse of an electricity meter) can be used to measure the energy feed into the grid.

By visualizing signals in the monitoring system and acquiring meter pulses, it is possible to implement a simple method of mo-nitoring the power infeed by the PV plant into the medium-vol-tage grid.

Note:

Option "P40" can only be ordered in combination with option "P50".

Option "P50" – Interface to container data

The "Interface to container data" option allows signals from the container to be acquired/displayed via appropriate inputs and outputs: Container temperature, supply air temperature, smoke detector, "horn" activation.

The smoke alarm signal is read in and transferred to the monito-ring systems. The signal is also applied to an output which can be configured, for example, to activate a horn.

The container temperature and supply air temperature signals can be used to drive the SINVERT PVS inverter cabinet fans in energy-saving mode.

Reliable operation and maximum energy yields to the grid are dependent on compliance with the operating temperature ran-ges prescribed for the components installed in the container and detection of smoke detector signals.

Note:

Option "P50" can only be ordered in combination with option "P40".

Option "S10" – Cabinet heating

The "Cabinet heating" option minimizes the risk of condensation forming on moisture-sensitive components in the SINVERT PVS inverter at low ambient temperatures and ensures an ideal (mi-nimum) operating temperature for reliable operation of the inver-ter. Reliable operation and maximum energy yields to the grid are dependent on compliance with the operating temperature range prescribed for the relevant SINVERT PVS inverter. This function is recommended for locations at which the ambient tem-perature can drop below 7 °C.

Option "S30" – AC auxiliary supply

The "AC auxiliary supply" option provides a power supply for the components of the SINVERT PVS inverter (fans, cabinet heating, communications options, etc.). Supplying these components from the PV generator is generally less economical as the energy supplied to the grid is reimbursed at a higher rate than the cost of the power consumed by the components listed above. The plant yield can therefore be optimized by providing an external power supply. This can be connected to a separate energy meter if desired.

Note:

Option "S30" can only be ordered in combination with option "S40".

Option "S40" – AC outputs for external loads

The option "AC outputs for external loads" allows external loads (electric drill, for example) to be supplied via the two protected load outputs.

One output is rated for 400 V AC (3-phase, PE, 16 A) and the other for 230 V AC (1-phase, about 500 VA).

Note:

Option "S40" can only be ordered in combination with option "S30".

Chapter3.book Seite 23 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 24: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

Central inverters according to UL

3/24 Siemens RE 10 · 2012

3

■ Schematics

Block diagram of SINVERT PVS, master with touch panel and slave without touch panel

=

~

Pho

tovo

ltaic

arr

ay

DC input 1

DC cabinet AC cabinet

RE10_00024

Touchpanel (master only)

Control system

FilterEMC filter

EMC filter

DC input 2

DC input 3

Med

ium

-vol

tage

tran

sfor

mer

AC outputL1, L2, L3

Chapter3.book Seite 24 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 25: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

3/25Siemens RE 10 · 2012

Inverter stations according to IEC

3

■ Overview

Inverter station according to IEC

The inverter stations are system solutions for fast, simple imple-mentation of turnkey photovoltaic stations. These are available as container solutions.

They include SINVERT PVS inverters and, depending on the variant selected, medium-voltage switchgear and medium-volt-age transformers. They are designed to convert solar energy re-liably and cost-effectively into a grid-compatible voltage for in-feed into conventional power supply networks.

All individual components of the inverter stations, such as SINVERT PVS inverters and medium-voltage transformers, are technically fully developed, designed for extreme ruggedness and durability, perfectly coordinated in terms of their electrical and mechanical properties, and completely wired and tested.

The inverter stations, which can be supplied in steel or concrete, are available with power outputs 1 000, 1 200, 1 500, 1 800, 2 000 and 2 400 kW.

Their characteristics are described below.

Output and efficiency• The inverter stations are optimized for minimum losses over

the entire energy transmission path.• The SINVERT PVS photovoltaic inverters integrated in the in-

verter stations are highly efficient in every operating point.• They are suitable for photovoltaic installations with power out-

puts of 1 000 kW and above.

Interfaces• Ethernet

Area of application

The inverter stations are suitable for any application which re-quires compliance with the relevant IEC standards. The stations are suitable for outdoor installation in virtually any conditions.

■ Benefits

• Precisely coordinated, fully tested complete system package can be commissioned quickly, simply and efficiently.

• A rugged, durable and low-maintenance design combined with the use of fully developed, tried-and-tested standard in-dustrial products keep servicing and maintenance costs low, ensure an exceptionally long service life, high availability, and low total cost of ownership.

■ Application

The inverter stations are ideally suited for application in photo-voltaic power plants ("Power Plant" segment) with outputs starting at 1 000 kW.

They are typically employed in ground-mounted systems.

The stations are manufactured in accordance with the relevant standards and regulations and are suitable for application in countries which require conformance to IEC standards.

■ Design

The inverter stations which are available in steel or concrete are characterized by their high-quality, compact and rugged de-sign.

The stations are equipped with integral low-noise fans for dissi-pating heat losses. The air supply and extraction systems are specially tailored to the integrated components. The supply and extraction systems for the inverter and transformer compart-ments are decoupled.

The stations contain between two and four inverter subunits which are interconnected in a master/slave system, as well as an AC distribution container section (customer-specific). As an op-tion, the station can be equipped with a medium-voltage trans-former and medium-voltage switchgear. All components are per-manently installed, completely wired, and tested. Only the connections necessary for operation, such as the DC connec-tions of the photovoltaic generators, the AC grid connection, and the communication connections have to be implemented.

The DC and AC cables are connected from below through duct openings in the closed base panel.

10088052.fm Seite 25 Dienstag, 17. Januar 2012 2:13 14

© Siemens AG 2012

Page 26: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

Inverter stations according to IEC

3/26 Siemens RE 10 · 2012

3

■ Function

Basic function

Within photovoltaic plants, the inverter stations are the link be-tween the photovoltaic generator (total of all electrically intercon-nected photovoltaic modules) and the public AC grid.

Inverters

The SINVERT PVS photovoltaic inverters which are an integral component of the stations convert the direct current produced by the photovoltaic generator into an alternating current and then adjust this current to the frequency and magnitude of a specified voltage (low voltage). Thanks to its modern power electronics, it can perform the DC-to-AC conversion with mini-mum losses.

AC distribution system

The AC distribution system is perfectly tailored to the require-ments of the inverter stations. It powers, controls and monitors the components in the station (e.g. it controls the container fans or monitors the temperature of the two-tier transformer).

The power to the AC distribution system can be supplied by an external 400 V AC infeed (50 or 60 Hz) provided by the cus-tomer. Alternatively, it can be supplied by an auxiliaries trans-former connected directly to the SINVERT PVS inverter which transforms the output voltage (288 or 370 V) of the SINVERT PVS inverter into a 400 V voltage (50 or 60 Hz).

The AC distribution system is tailored to customer requirements.

Medium-voltage transformer

The medium-voltage transformer transforms the low voltage supplied by the SINVERT PVS photovoltaic inverter into a de-fined medium voltage of, for example, 20 kV for feeding into the grid.

Several medium-voltage transformer brands are available, e.g. the loss-optimized GEAFOL medium-voltage transformer (cast-resin two-tier transformer), which has been specially designed for photovoltaic applications.

Medium-voltage switchgear

The medium-voltage switchgear is available as an option. It dis-tributes energy and feeds power into the medium-voltage net-work. The following medium-voltage switchgear configurations are available: RT, RRT, RTT, RRTT, RL, RRL, RLT or RRLT1). 1) 1) R = ring-main panel, T = transformer panel, L = circuit breaker panel

without voltage transformer.

Control and display panel

The control and display panel is the same as the unit supplied with the IEC-compliant central inverter (see page 3/4).

Communications

The inverter stations have an Ethernet interface. When the sta-tion is linked to an Ethernet network, it can exchange data with other stations and with a visualization system such as WinCC via the Ethernet interface (see Chapter 4 "Software and monitoring"). With a visualization system it is possible, for example, to operate and visualize the photovoltaic installation and to acquire, store and visualize measured data and messages. Integrating the sta-tion into a network also makes it easier to analyze the photovol-taic yield data (setpoint/actual value comparisons), operate the installation from a remote location, arrange service callouts at short notice, reduce system downtimes to a minimum, and thus optimize the yield of the plant. Interfaces to other communication channels (e.g. DSL, analog telephone, ISDN, GSM) can be pro-vided if necessary.

Master/slave

The SINVERT PVS inverters integrated in the inverter stations op-erate with a "rotating master" according to the master/slave prin-ciple. This is a master/slave system comprising between two and four interconnected inverter subunits. It employs an inge-nious process to connect or disconnect inverter subunits de-pending on the level of solar radiation (determined according to the sun's path, cloud conditions, etc.). One inverter subunit acts as the master. The master is started up first and operates even when irradiation levels are low. As irradiation levels increase, the power limit of the master is reached and the next inverter sub-unit, i.e. the slave, is switched in. Depending on the configura-tion, up to three slaves can be switched in. As irradiation levels drop again, the subunits are disconnected in stages. One ad-vantage of the master/slave principle is that the inverters operate more efficiently when irradiation levels (which determine the PV generator output) are low than would be achieved if only one sin-gle central inverter were used.

In master/slave systems, the "rotating master" always starts the inverter subunit with the fewest operating hours as the master. In this way, the total operating hours are evenly distributed among all the subunits.

Insulation (ISO) measurement

The insulation measurement function monitors the system for low resistance to ground resulting from an insulation fault (e.g. caused by a damaged cable). Depending on the type of insula-tion fault, an alarm is output or the inverter is tripped in order to protect personnel.

Provision of supplementary functions by options

The standard scope of functions of the integral SINVERT PVS in-verters can be optionally expanded. Optionally available are, for example, a PV array grounding system or an increase in the maximum operating voltage from 820 to 1000 V (see "IEC-compliant central inverters", page 3/14).

Chapter3.book Seite 26 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 27: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

3/27Siemens RE 10 · 2012

Inverter stations according to IEC

3

■ Integration

The inverter stations can be seamlessly integrated into a photo-voltaic installation by means of appropriate system components and accessories (see page 3/30) and "Software" (see Chapter 4 "Software and monitoring").

The inverter is provided with standardized interfaces so that it can be integrated into a control system or an existing customer installation. The interfaces can also be used to remotely monitor and operate the device, for example, through the Internet portal or by means of the WinCC visualization system.

The WinCC visualization system supports professional opera-tions management.

The advantages of the WinCC visualization system include:• Clear display of plants, plant sections (subplants) and invert-

ers• Remote access to inverters• Remote monitoring• Acquisition, long-term storage and display of current and his-

torical data• Graphical representation of the monitored data• Plant monitoring• Messaging services using e-mail and text message• Fault messages can be specifically configured for customized

operations management• Map

Integration of SINVERT PVS inverters into a photovoltaic plant without solar PV plant control with communication via an Ethernet network and monitoring by means of SINVERT WebMonitor

SCALANCE S VPN Router

SINVERT PVS ComBox 200

Inverter - Station 1

InverterSINVERT PVS

Weather sensors

SINVERT PVS ComBox 100

Inverter - Stations 2-n

InverterSINVERT PVS

Client

DSL-Router

SINVERT WebMonitor

Industrial Ethernet FOC ring

Industrial Ethernet

Internet

RE10_00033d

SINVERT PVSWeatherStation 200

Chapter3.book Seite 27 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 28: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

Inverter stations according to IEC

3/28 Siemens RE 10 · 2012

3

Integration of SINVERT PVS inverters into a photovoltaic plant with communication via an Ethernet network, solar PV plant control by means of the SINVERT PVS ControlBox 300, and monitoring with WinCC

■ Configuration

The SINVERT Select program supports you with configuring photovoltaic installations. This configuration program allows the best possible configuration of SINVERT PVS inverters to be de-termined for a defined photovoltaic installation.

SINVERT Select is a dimensioning program designed to deter-mine the ideal configuration for a photovoltaic plant with SINVERT inverters. The program calculates all practical combi-nations for most of the photovoltaic modules available on the market in conjunction with SINVERT inverters, and enables eval-uation and optimization of the calculated combinations in a sim-ple and understandable way.

Only a few details, such as the location, type of photovoltaic module, and plant size are required for the dimensioning pro-cess.

Two methods are available for dimensioning the inverters: • With the automatic dimensioning method, the ideal SINVERT

inverters for the selected photovoltaic module and power specifications are selected from the entire spectrum of SIN-VERT inverters. You can optionally specify the required num-ber of photovoltaic modules per string and the applicable lim-its with respect to power specifications (i.e. area, number of modules or total power output).

• With the manual dimensioning method, you can specify up to two SINVERT inverters from the SINVERT range for calculation of the installation.

Inverter stations can only be dimensioned with combinations of SINVERT PVS inverters with power outputs of 1 000, 1 200, 1 500, 1 800, 2 000 and 2 400 kW.

For further information, see Chapter 4 "Software and monitoring".

■ Technical specifications

Inverter stations

For the technical data of inverter stations configured with the full equipment complement, please contact your sales representa-tive.

Individual components of inverter stations

SINVERT PVS inverters

See "IEC-compliant central inverters", page 3/4.

AC distribution system

The AC distribution system is tailored to customer requirements.

For the exact technical data for your specification, please con-tact your sales representative.

Medium-voltage transformer

See Catalog TV 1 "GEAFOL Cast-Resin Transformers 100 to 16 000 kVA".

For the exact technical data for your specification, please con-tact your sales representative.

Medium-voltage switchgear

See Catalog HA 40.2 "Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated"

For the exact technical data for your specification, please con-tact your sales representative.

WinCC PC

SCALANCE S VPN Router

SINVERT PVS ComBox 100

Inverter - Station 1

Circle controlreceiver

EVU

InverterSINVERT PVS

SINVERT PVS ComBox 100

Inverter - Stations 2-n

InverterSINVERT PVS

SINVERT PVS ControlBox 300

Weather sensors

Internet

WinCC WebNavigator

DSL-Router

Industrial Ethernet FOC ring

Industrial Ethernet

RE10_00029d

SINVERT PVSWeatherStation 200

0 %

100 %

Chapter3.book Seite 28 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 29: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

3/29Siemens RE 10 · 2012

Inverter stations according to IEC

3

■ Selection and ordering data

For the ordering options for IEC-compliant inverter stations, please contact your sales representative.

■ Options

For possible options see options of "IEC-compliant central in-verters" -> "PVS 600 series, 500 to 2400 kW", page 3/14.

■ Schematics

The basic interconnection between components can be seen in the circuit diagram below.

The power cables in the inverter station are installed either in the cable vault or cable floor.

Basic interconnection of components in the inverter station in a configuration containing a SINVERT PVS2000 or SINVERT PVS2400 inverter (consisting in each case of four individual SINVERT PVS500 or SINVERT PVS600 units).

RE10_00025

Inverter station

Medium-voltage switchgear

Medium-voltage transformer

SINVERT PVS inverters

Chapter3.book Seite 29 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 30: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

System components and accessories

3/30 Siemens RE 10 · 2012

3

■ Overview

System components and accessories are available as add-ons for the SINVERT PVS inverters and inverter stations.

Suitable

-- Not suitable

These system components and accessories are provided so that users can flexibly create the perfect, individualized photo-voltaic plant around the SINVERT PVS inverters and inverter sta-tions and enhance the functionality of the overall system.

SINVERT PVS CombinerBoxes 124, 204, 120, 108 (from left to right)

SINVERT PVS WeatherStation 200

SINVERT PVS ComBox 100

SINVERT PVS ControlBox 300

■ Benefits

• The system components and accessories are perfectly coor-dinated with the SINVERT PVS inverters and inverter stations.

• They allow users to flexibly create the perfect, individualized photovoltaic plant and extend the overall system – ranging from components to collect individual strings of the photovol-taic generator to options for the grid infeed point, including communications solutions.

• They support the implementation of professional plant moni-toring and operations management solutions, such as early detection of problems in the plant, calculation of yield data, etc.

• These system components conform to legal requirements such as the BDEW Guideline "Generating Plants in the Me-dium-Voltage Grid", and the specifications of grid operators in individual countries.

• Accessories can be installed to extend and optimize the func-tions of the basic units.

Description IEC-compli-ant central inverters

IEC-compli-ant inverter stations

System components

SINVERT PVS CombinerBoxes 108, 120, 124, 204

SINVERT PVS WeatherStation 200

SINVERT PVS ComBoxes 100, 200

SINVERT PVS ControlBox 300

Accessories

LV HRC fuse linksfor SINVERT PVS CombinerBoxes

Fan shrouds --

Chapter3.book Seite 30 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 31: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

3/31Siemens RE 10 · 2012

System components and accessories

3

■ Application

The system components and accessories for SINVERT PVS are ideally suitable for building photovoltaic power plants ("Power Plant" segment) around IEC-compliant central inverters and in-verter stations.

The components are manufactured in accordance with the rele-vant standards and regulations and are suitable for application in countries which require conformance to IEC standards.

■ Design

The system components and accessories are characterized by their high-quality, compact, and rugged design.

Depending on their intended site of installation, they are avail-able with degree of protection IP20 (indoor installation) or IP54 (indoor/outdoor installation).

■ Function

SINVERT PVS CombinerBoxes

With the SINVERT PVS CombinerBox, the individual strings of the photovoltaic generator are collected in the field, connected in parallel, and the energy conveyed across large cross-sec-tions of cable to the SINVERT PVS inverter or the inverter station.

Module strings can be "collected" and their energy transported to the SINVERT PVS inverter or inverter station using a single-stage or two-stage connection concept:• With the single-stage system, the energy supplied by the

module strings to the inputs of the SINVERT PVS Combiner-Boxes is transported directly to the SINVERT PVS inverter or the inverter station via one box output in each case.

Bundling of the solar direct current using SINVERT PVS CombinerBoxes (single-stage concept)

• With the two-stage concept, the module strings are brought together in the SINVERT PVS CombinerBoxes (first stage). The outputs of these SINVERT PVS CombinerBoxes are then connected to other SINVERT PVS CombinerBoxes (second stage). The outputs of the SINVERT PVS CombinerBoxes of the second stage are then connected to the inputs of the SIN-VERT PVS inverters or inverter stations. The advantage of this two-stage concept is that power losses are reduced thanks to the increased cable cross-sections.

Bundling of the solar direct current using SINVERT PVS CombinerBoxes (two-stage concept)

The SINVERT PVS CombinerBoxes 108, 120, 124 with eight, twenty, and twenty-four inputs are used in the first stage. The SINVERT PVS CombinerBox 204 with four inputs is used in the second stage.

The SINVERT PVS CombinerBox is designed for wall mounting.

The inputs of the SINVERT PVS CombinerBox are protected by fuses. The fuses are not included in the scope of supply of the SINVERT PVS CombinerBox and must be ordered separately. The output of the SINVERT PVS CombinerBox can be optionally equipped with or without a switch disconnector. A SINVERT PVS CombinerBox with switch disconnector is capable of discon-necting the connected section of the photovoltaic generator from the SINVERT PVS inverter, e.g. for maintenance purposes.

The SINVERT PVS CombinerBox is optionally available with or without surge protection which is designed to protect the mod-ules.

The SINVERT PVS CombinerBox has degree of protection IP54 and is rated for voltages up to 1 000 V.

Photovoltaic arrayService room

Photovoltaic modules

SINVERT PVS CombinerBoxes 120

SINVERT PVS inverters

RE1

0_00

027a

SINVERT PVS CombinerBoxes

108 120 124 204

Number of inputs 8 20 24 4

Maximum protection per input

A 15 A 20 A 20 A 160 A

Voltage V 1 000 V 1 000 V 1 000 V 1 000 V

Switch disconnector Optional Optional Optional --

Surge arrester Optional -- -- --

RE1

0_00

026a

Photovoltaic arrayService room

Photovoltaic modules

SINVERT PVS CombinerBoxes 108

SINVERT PVS CombinerBoxes 204

SINVERT PVS inverters

Chapter3.book Seite 31 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 32: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

System components and accessories

3/32 Siemens RE 10 · 2012

3

SINVERT PVS WeatherStation

The SINVERT PVS WeatherStation 200 acquires data about the weather at the photovoltaic plant site. from sensors.

The following sensors are included in the scope of supply of the SINVERT PVS WeatherStation 200:• Insolation• Module temperature• Ambient temperature

Additional sensors such as wind speed or rain sensors can be connected.

Using the acquired data, it is possible to create and communi-cate very precise weather recordings. The target yield of the photovoltaic plant can be calculated from the recorded weather data. By comparing the actual and target yields, it is possible to make a quick assessment of the plant's operating performance and detect any irregularities very promptly.

The SINVERT PVS WeatherStation 200 contains the following main components:• SIMATIC ET 200S with six analog inputs• PROFINET communications interface• SITOP power supply module• Sensor for insolation• Sensor for ambient temperature• Sensor for module temperature

SINVERT PVS ComBoxes

The SINVERT PVS ComBoxes enable SINVERT PVS inverters to communicate with other inverters or network-capable compo-nents and are used in installations which have no AC distribution system that can provide equivalent communication functions.

There are two variants of communications box with different lev-els of functionality:

SINVERT PVS ComBox 100

SINVERT PVS ComBox 100

The SINVERT PVS ComBox 100 interconnects the inverter sta-tions (in linear or ring topologies) with copper or fiber-optic LAN cabling, and also connects network-capable components in the inverter stations, e.g. SINVERT PVS inverters.

The SINVERT PVS ComBox 100 contains the following main components:• SCALANCE XF204-2 network switch with four RJ45 ports• Two fiber-optic ports, for cable lengths up to 5 km• SITOP power supply module

SINVERT PVS ComBox 200

SINVERT PVS ComBox 200

The SINVERT PVS ComBox 200 has the same scope of func-tions as the SINVERT PVS ComBox 100. It additionally provides the capability of transferring data from the SINVERT PVS invert-ers and from additional network-capable components to the SINVERT WebMonitor web application for monitoring photovol-taic plants.

The SINVERT PVS ComBox 200 contains the following main components:• SCALANCE XF204-2 network switch with four RJ45 ports• Two fiber-optic ports, for cable lengths up to 5 km• SITOP power supply module• SIMATIC IPC427C industrial PC (MICRO BOX PC)

Chapter3.book Seite 32 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 33: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

3/33Siemens RE 10 · 2012

System components and accessories

3

SINVERT PVS ControlBox

SINVERT PVS ControlBox 300

The purpose of the SINVERT PVS ControlBox 300 is to regulate the active and reactive power of a photovoltaic plant containing SINVERT PVS inverters and to ensure compliance with legal re-quirements (according to the current amendment of the Renew-able Energy Act (EEG), in force since January 2009).

The BDEW guideline "Generating Plants in the Medium-Voltage Grid“ stipulates this requirement for all systems feeding in at the medium-voltage level. Its primary benefit is that it enables grid operators to limit the output of the plant by remote control in ac-cordance with §6 of the Renewable Energy Sources Act 2009.

The SINVERT PVS ControlBox 300 offers a wide range of open-loop and closed-loop control functions, e.g.:• Specification of a fixed active power for all individual

SINVERT PVS inverters in the photovoltaic plant, e.g. setpoint value = 2 MW (fixed active power value)

• Specification of a fixed reactive power for all individual SINVERT PVS inverters in the photovoltaic plant, e.g. setpoint value = 100 kvar inductive (fixed reactive power value)

• Specification of a fixed power factor cos φ for all individual SINVERT PVS inverters in the photovoltaic plant, e.g. setpoint value = -0.95

• Regulation of the active power for individual SINVERT PVS in-verters in the photovoltaic plant as a function of the active power actually measured at the grid infeed point, to 0%, 30%, 60%, and 100% of the rated active power of the photovoltaic plant. (Active power reduction in accordance with § 6 EEG)

• Regulation according to Q(U) characteristic• Regulation according to Q(t) characteristic• Regulation according to P(f) characteristic• Ramps for system ramp-up and ramp-down, i.e. continuously

approaching the setpoint

The SINVERT PVS ControlBox 300 contains the following main components:• SIMATIC components with digital inputs• SIMATIC IPC427C industrial PC (MICRO BOX PC)• SITOP power supply module• SENTRON PAC3200 Power Monitoring Device for measuring

actual values at the grid infeed point• SCALANCE XF204-2 network switch with four RJ45 ports, two

fiber-optic cable ports, for cable lengths up to 5 km

■ Integration

For integration of the system components in a plant, see "IEC-compliant central inverters", page 3/4 or "IEC-compliant inverter stations", page 3/27.

■ Technical specifications

SINVERT PVS CombinerBoxes 108, 120, 124, 204, SINVERT PVS WeatherStation 200, SINVERT PVS ComBoxes 100, 200 and SINVERT PVS ControlBox 300

For technical data, see http://www.siemens.com/sinvert/support

■ Selection and ordering data

✓ included

--not included

Product type designation

Number of inputs

Fuse type atinput

Input currentper inputmaximum

Product compo-nent at outputdisconnecting device

Product functionsurge protection

Order No.

ASINVERT PVS CombinerBoxesSubgenerator junction boxCombinerBox 108 8 Cylindrical fuse-link 10 x 38 10 -- -- 6AG3611-3FF21-1AA0

CombinerBox 108 8 Cylindrical fuse-link 10 x 38 10 -- ✓ 6AG3611-3FF21-1BA0

CombinerBox 108 8 Cylindrical fuse-link 10 x 38 10 ✓ -- 6AG3611-3FF21-1CA0

CombinerBox 108 8 Cylindrical fuse-link 10 x 38 10 ✓ ✓ 6AG3611-3FF21-1DA0

CombinerBox 120 20 Cylindrical fuse-link 10 x 38 13 -- -- 6AG3611-3FL21-1AA0

CombinerBox 120 20 Cylindrical fuse-link 10 x 38 13 ✓ -- 6AG3611-3FL21-1CA0

CombinerBox 124 24 Cylindrical fuse-link 10 x 38 13 -- -- 6AG3611-3FM21-1AA0

CombinerBox 124 24 Cylindrical fuse-link 10 x 38 13 ✓ -- 6AG3611-3FM21-1CA0

Generator junction boxCombinerBox 204 4 LV HRC fuse link size 1 160 -- -- 6AG3611-3FD01-1AA0

Chapter3.book Seite 33 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012

Page 34: SINVERT PVS Central Inverters, from 350 kW - Siemensw3app.siemens.com/.../RE10_Chap03_English_2012.pdf · The order numbers for the SINVERT PVS central inverters will ... heat losses

SINVERT PVS Central Inverters, from 350 kW

System components and accessories

3/34 Siemens RE 10 · 2012

3✓ included

--not included

✓included

■ Schematics

SINVERT PVS CombinerBoxes 108, 120, 124, 204, SINVERT PVS WeatherStation 200, SINVERT PVS ComBoxes 100, 200 and SINVERT PVS ControlBox 300

For more detailed information, refer to Operating Instructions at http://www.siemens.com/sinvert/support.

Product type designation

Product description

Sensor type Number of digital inputs

Order No.

for sensing irradiation

for sensing ambient temperature

for sensing PV module temper-ature

for measuring rain

SINVERT PVS WeatherStationWeatherStation 200 Box for connec-

tion of weather sensors

0 ... 10 V active, 0 ... 10 V Pt100 24 V DC/AC power supply, 230 V switching voltage, 5 A switching current

8 6AG3611-3BA00-2AA0

Product type designation

Product description

Product functionWeb-based diagnostics

Type ofcommunication interface

Number of 10/100/1000 Mbit/s RJ45 ports

Order No.

SINVERT PVS ComBoxesComBox 100 Box for connec-

tion of fiber-optic cables

-- Ethernet 3 6AG3611-3AB00-1AA0

ComBox 200 Box for connec-tion of fiber-optic cables and web portal

✓ Ethernet 2 6AG3611-3AB00-2AA0

Product type designation

Product description

Product functionWeb-based diagnos-tics

Current inputat rated supply voltage

Signal voltageat DCrated value

Number of digital inputs

Number of analog inputsfor input range 4 ... 20 mA

Number of analog outputsfor output range 0 ... 10 V

Number of 10/100/1000 Mbit/s RJ45 ports

Order No.

A VSINVERT PVS ControlBoxControlBox 300 Box for solar PV

plant control and connection of WinCC and web portal

✓ 2.4 24 8 2 2 1 6AG3611-3AA00-3AA0

Size of fuse systemin acc. with IEC 60269-1

Duty category of fuse link

Currentat ACrated value

Supply voltageat ACrated value

Effective power loss

Order No.

A V W

LV HRC fuse links for SINVERT PVS CombinerBoxesLV HRC1 gPV 80 1 000 20 3NE1220-4

LV HRC1 gPV 100 1 000 24 3NE1221-4

LV HRC1 gPV 125 1 000 26 3NE1222-4

LV HRC1 gPV 160 1 000 32 3NE1224-4Fan shroudsFan shrouds for optimum air supply and extraction 6AG3911-3CA20-1AY0

Chapter3.book Seite 34 Dienstag, 17. Januar 2012 2:04 14

© Siemens AG 2012