Component description and ordering document, SINAMICS S120 AC Drive V1.0
SINAMICS S120
POWER MODULES Blocksize and Chassis formats
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 2/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Table of contents
1 Control Unit CU310 DP 3
2 Power Modules PM340 Blocksize format 7 2.1 Overview 7 2.2 Technical data 10 2.3 Selection and ordering data 18 2.4 Line reactors for Power Modules PM340 20 2.5 Line filter for Power Modules PM340 24 2.6 Braking resistors for Power Modules PM340 26 2.7 Motor reactors for Power Modules PM340 28
3 Power Modules, Chassis format 32 3.1 Overview 32 3.2
Technical data 34
3.3 Selection and ordering data 38 3.4 Line reactors for Power Modules, Chassis format 38 3.5 Line filters for Power Modules, Chassis format 40 3.6 Braking Modules and braking resistors for Power Modules, Chassis format 41 3.7 Motor reactors and sinusoidal filters for Power Modules, Chassis format 41
Page 2
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 3/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
1 Control Unit CU310 DP
The Control Unit CU310 DP is designed for the communication and open/closed-loop control functions of a Power
Module. Together with the Power Module it forms a high-performance single-motor drive. As standard, the Control
Unit CU310 DP features the following interfaces:
• 1 DRIVE-CLiQ socket that permits communications to additional DRIVE-CLiQ devices, e.g. Sensor
Modules, Terminal Modules
• 1 PM-IF interface to communicate with Power Modules, Blocksize format
• 1 interface to the Basic Operator Panel BOP20
• 1 PROFIBUS interface
• 1 encoder evaluation HTL/TTL
• 4 parameterizable digital inputs (floating)
• 4 parameterizable bidirectional digital inputs/digital outputs (non-floating)
• 1 serial RS232 port
• 1 slot for the CompactFlash card which is used to save the firmware and parameters
• 3 test sockets and a reference ground to support commissioning
• 1 connection for the electronics power supply via the 24 V DC supply connector
• 1 PE/protective conductor connection
Multi-color LEDs are used to display the status of the Control Unit CU310 DP. A Basic Operator Panel BOP20
can be snapped directly onto the Control Unit CU310 DP - e.g. for diagnostics. The firmware and parameters that
have been set are stored on the plug-in CompactFlash card. This means that Control Units can be replaced
without requiring any additional equipment. The same CompactFlash card (same firmware) is used for the Control
Unit CU310 and CU320.
The Control Unit CU310 DP controls the Power Modules, Blocksize format via the PM-IF interface. In this case,
additional DRIVE-CLiQ components can be connected at the DRIVE-CLiQ socket of the Control Unit CU310 DP.
These DRIVE-CLiQ components include, for instance, Sensor Modules and Terminal Modules. The Power
Modules, Chassis format are controlled from the Control Unit CU310 DP via the DRIVE-CLiQ interface. Here,
Sensor Modules and Terminal Modules can be connected to the free DRIVE-CLiQ sockets of the Power Module.
Page 3
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 4/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Parameters can be changed using the Basic Operator Panel BOP20. The Basic Operator Panel BOP20 can also
be snapped onto the Control Unit CU310 DP during operation for diagnostic purposes.
The STARTER commissioning tool is used to commission and diagnose the Control Unit CU310 DP as well as
the connected components.
Communications between a Control Unit CU310 DP and the higher-level control are established via PROFIBUS.
The integrated safety functions - such as e.g. "Safe Torque Off" - should be selected through two channels. Two
digital inputs are required on the Control Unit CU310 DP for this purpose.
CU310 DP
ext
.24 V
+
(sind geschirmt
3) Als Ein-/Ausgangeinzeln parametrierbar
M X100PROFIBU
S
X21
M
+
3)
Serial interface
R x D T
x D M
X226)
2)
DI0
4
DI1
DI
3
DI2
M1
M
DI/DO 8
1)
7
3
2
1
5
6
8
9
10
11
12
DI/DO 9
1)
DI/DO 101)
DI/DO 111)
M
M
+ 24
V
M
X124
M
+
M
+
M
X121
D R I V E - C L i Q s
o c k e t 0
X232 3 5
+Temp
5)-Temp
5)
EPM1
EP +24 V
4)
4) Erforderlich bei Safety
4
3
2
1
5
6
8
7
X120
M
nc
nc
nc
E n c o
d e r i n t e r f a c e
+ 24
V
6) Nur Entwicklungsschnittstelle
1) Use shielded cables when connecting to fast inputs2) Jumper open: Digital inputs are electrically isolated (DI)3) Can be individually parameterized as input/output4) Required for safety "Safe Torque OFF"5) Use shielded cables6) Only a development interface
CompactFlash card
OUT
PM-IFinterface
Page 4
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 5/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Technical data
Control Unit CU310 DP
6SL3040-0LA00-0AA0
Max. current drain (at 24 V DC) without taking into account the digital outputs 0.85 A
Max. cross-section that can be connected 2.5 mm2
Max. fusing 20 A
Digital inputs 4 floating digital inputs, 4 bidirectional, non-floating digital
inputs/digital outputs
Voltage – 3 V to 30 V
Low signal level (an open-circuit digital input is interpreted as "low") – 3 V to 5 V
High signal level 15 V to 30 V
Current drain (typical, at 24 V DC) 10 mA
Signal run times of the digital inputs 1) L → H: approx. 50 μs H → L: approx. 100 μs
Signal run times of the fast digital inputs 1)
(fast digital inputs can be used to sense the position)
L → H: approx. 5 μs H → L: approx. 50 μs
Max. cross-section that can be connected 0.5 mm2
Digital outputs (with continuous short-circuit protection) 4 bidirectional, non-floating digital outputs/digital inputs
Voltage 24 V DC
Max. load current per digital output 2) 500 mA
Max. cross-section that can be connected 0.5 mm2
Encoder evaluation Incremental encoder, TTL or HTL (this can be parameterized)
Limit frequency 500 kHz
Max. cable length for TTL incremental encoders 100 m (only bipolar signals permissible)
Max. cable length for HTL incremental encoders 100 m for unipolar signals, 300 m for bipolar signals
Power loss < 20 W
PE connection At the housing using an M5 stud
Width 73 mm
Height 183.2 mm
Depth 89.6 mm
Weight, approx. 0.95 kg
Approvals/certification cULus (File No.: E164110)
1) The specified signal run times refer to the hardware. The actual response time depends on the time slice in which the digital
input or digital output is processed.
2) In order to use digital outputs, an external 24 V power supply must be connected to terminal X124.
Page 5
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 6/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Selection and ordering data
Description Order No.
Control Unit CU310 DP
(without CompactFlash card)
6SL3040-0LA00-0AA0
Accessories
Description Order No.
PROFIBUS connector
without PG/PC connection
6ES7972-0BA41-0XA0
PROFIBUS connector
with PG/PC connection
6ES7972-0BB41-0XA0
STARTER commissioning tool 6SL3072-0AA00-0AG0
Page 6
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 7/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
2 Power Modules PM340 Blocksize format
2.1 Overview
Power Module PM340, frame size FSA Power Module PM340, frame size FSE
As standard; the Power Modules PM340 Blocksize format are provided with the following interfaces:
• DC link terminals DCP/R1 and DCN
• Terminals DCP/R1 and R2 to connect an external braking resistor
• PM-IF interface that establishes the connection between the Power Module PM340 and the Control UnitCU310 or Control Unit Adapter CUA31. The Power Module PM340 also provides power to the Control UnitCU310 or Control Unit Adapters CUA31 using an integrated power supply
• The motor is connected through screw terminals or studs
• Control for the Safe Brake Relay or the Brake Relay to control a holding brake
• 2 PE/protective conductor connections.
Power Modules with integrated line filter may only be connected to TN line supplies. Power Modules withoutintegrated line filter can be connected to grounded (TN, TT) and non-grounded (IT) line supplies.
NotePower Modules have been designed for use in the industrial environment and generate currentharmonics on the line side as a result of their rectifier circuit. When a machine with integrated PowerModules is connected to the public low-voltage supply, then authorization is required from the localelectric utility company, if
- the rated input current of the machine is ≤ 16 A per conductor, and
- the input current of the machine does not fulfill the requirements of EN 61000-3-2 regarding currentharmonics.
Page 7
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 8/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
The integrated braking unit (braking chopper) is dimensioned so that it can continuously control the externalbraking resistor. The temperature of the external braking resistor must be monitored to protect it against thermaloverload.
The Power Modules PM340 communicate with the Control Unit CU310 resp. the Control Unit Adapter CUA31 via
the PM-IF interface.
==
*) only for PM340 with integrated filter
*)
µP
PEU1/
L1
V1/
L2
W1/
L3
U2
R2
DCP/R1
DCN
V2 W2 PE
-X ??
PM-IF interface to ControlUnit CU310
orControl Unit Adapter
CUA31
Line reactor
3-ph. 380 V - 480 V AC
L1 L2 L3 PE
M3~
Power
ModulePM340
SafeBrakeRelay
24 V DCsupply forthe brake
Braking resistor
PEL N
Line reactor
1 AC 200 V - 240 V
L N PE
P24
Connection example, Power Module PM340
Power Module PM340 with Power Module PM340 with
Page 8
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 9/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Control Unit CU310 DP Control Unit Adapter CUA31
Many of the system components for the Power Modules PM340 have been designed as sub-chassis components.This means that the components are mounted onto a mounting plate and above them the Power Module PM340to create a space-saving solution. Up to two sub-chassis components can be mounted above one another.
FSA FSB FSC FSD FSE FSF
Line filter U - - - - -
Line reactor U U U U U N
Brakingresistor
U U N N N N
Motor reactor U U U N N N
List of the components that can be mounted below the Power Module PM340
U = can be mounted below the Power ModuleN = cannot be mounted below the Power Module- = not available
The principle arrangement of a Power Module PM340 with sub-chassis line reactor is shown in Fig. 1. The line
reactors are connected on the line side using terminals and to the Power Module using a pre-fabricated cable. Forframe sizes FSA to FSC – when installed - the line supply terminals are located at the top; for frame sizes FSD toFSE they are located at the bottom.
If, for frame size FSA, a line filter is used in addition to the line reactor, then the components should be arrangedaccording to Fig. 2. In this case, the line supply is connected at the bottom.
From frame size FSB, Power Modules can be ordered with an integrated line filter; an external line filter is thennot required.
Line reactor
Line
Line reactor
Line
Line filter
Fig. 1PM340 frame size FSA with line reactor
Fig. 2PM340 frame size FSA with line reactor and line filter
For more than two system components that can be mounted as sub-chassis units - e.g. line reactor + motorreactor + braking resistor - the individual components should be mounted at the side next to the Power Modules.In so doing, the line reactor and motor reactor should be mounted below the Power Module and the brakingresistor at the side (Figs. 3 and 4).
Linereactor
Line
Motorreactor
To the motor
Line
Line filter
Linereactor
Motorreactor
To the motor
Fig. 3PM340 frame size FSA with line reactor and motor
Fig. 4PM340 with line reactor, line filter and motor reactor
Page 9
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 10/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
reactor
2.2 Technical data
General technical data
Electrical data
Line supply voltage(up to 2000 m above sea level)
1-ph. 200 V to 240 V AC ±10% (-15% < 1 min) or
3-ph. 380 V to 480 V AC ±10% (-15% < 1 min)
Line frequency 47 Hz to 63 Hz
Line power factor at the rated power
- basic fundamental (cos ϕ1)
- total (λ)1-ph. 200 V to 240 V AC3-ph. 380 V to 480 V AC
> 0.96
0.45 to 0.70.65 to 0.95
Overvoltage Category Class III according to EN 60664-1
Pre-charging frequency of the DC link Max. 1x every 30 seconds
DC link voltage Approx. 1.35 x line supply voltage
Output frequency
- servo closed-loop control type 0 Hz to 650 Hz *)
- vector closed-loop control type 0 Hz to 300 Hz *)
- closed-loop control type V/f 0 Hz to 300 Hz *)
Electronics power supply 24 V DC, -15/+20%
Radio interference suppression
- standard No radio interference suppression
- with line filter Class A1 according to EN 55011 andCategory C2 according to EN 61800-3
Ambient conditions
Cooling type Internal air cooling, power units are force cooled using anintegrated fan
Permissible ambient and coolant temperature(air) in operation for line-side components, LineModules and Motor Modules
0 °C to +40 °C without derating,> 40 °C to +55 °C, refer to derating characteristics
Installation altitude Up to 1000 m above sea level without derating,> 1000 m up to 4000 m above sea level, refer to the deratingcharacteristics
Conformance CE (Low-Voltage and EMC Directives)
Approvals (being prepared) cULus
1-ph. 200 V to 240 V ACframe size FSA (File No.: E192450)3-ph. 380 V to 480 V ACframe sizes FSA to FSC (File No.: E121068)frame sizes FSD to FSF (File No.: E192450)
Certifications (being prepared) Safety Integrity Level 2 (SIL 2) according to IEC 61508,Control Category 3 acc. to EN 954-1 for Safety Integrated – STO = Safe Torque Off and SBC = Safe Brake Control inconjunction with "Safe Brake Relay"
*) Carefully observe the interrelationship between the max. output frequency and pulse frequency as well as thecurrent derating
Page 10
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 11/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Technical data
Line supply voltage1-ph. 200 V to 240 V AC
Power Modules PM340, Blocksize format
Power Module PM340
PM340 with integrated line filter 6SL3210-1SB11-0UA0
6SL3210-1SB11-0AA0
6SL3210-1SB12-3UA0
6SL3210-1SB12-3AA0
6SL3210-1SB14-0UA0
6SL3210-1SB14-0AA0
Ratedoutput current I n
A 0.9 2.3 3.9
Base load current I H A 0.8 2.0 3.4
Output currentfor S6 duty (40%) I S6
A 1.4 3.3 5.5
Max. output current I max A 2.0 4.6 7.8
Rated powerbased on I n
kW 0.12 0.37 0.75
Rated pulse frequency kHz 4 4 4
Efficiency η 0.80 0.90 0.91
Power loss kW 0.060 0.075 0.11
Cooling air flow m3 /s 0.005 0.005 0.005
Sound pressure level dB(A) < 45 < 45 < 45
24 V DC power supply for theControl Unit
A 1.0 1.0 1.0
Rated input current 1)with line reactorwithout line reactor
A 1.9 2.2
4.8 6.0
8 9.9
Resistance value of the externalbrake resistor
Ohm ≥ 180 ≥ 180 ≥ 180
Max. cable length to the brakingresistor
m 15 15 15
Line supply connectionL, N
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Motor connectionU2, V2, W2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
DC link connection,connection for braking resistorDCP/R1, DCN, R2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
PE connection At the housing with M4 stud At the housing with M4 stud At the housing with M4 stud
Max. motor cable length 2)(without external options)
m 50 (shielded)
75 (non-shielded)
50 (shielded)
75 (non-shielded)
50 (shielded)
75 (non-shielded)
Degree of protection IP20 IP20 IP20
Width mm 73 73 73
Height mm 173 173 173
DepthPower Module PM340PM340 with Control Unit CU310PM340 with CUA31
mm145234.6175.3
145234.6175.3
145234.6175.3
Frame size FSA FSA FSA
Weight, approx. kg 1.2 1.3 1.3
1) The input current depends on the motor load and line supply impedance. The input currents apply to a loadwith rated power (based on In) with a line supply impedance corresponding to uk = 1 %
2) Max. motor cable length 25 m (shielded) for Power Modules PM340 with integrated line filter in order to complywith the limit values stated in EN 61800-3 Category C2
Page 11
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 12/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Line supply voltage3-ph. 380 V to 480 V AC
Power Modules PM340, Blocksize format
Power Module PM340
PM340 with integrated line filter
6SL3210-1SE11-3UA0
-
6SL3210-1SE11-7UA0
-
6SL3210-1SE12-2UA0
-
6SL3210-1SE13-1UA0
-
6SL3210-1SE14-1UA0
-
Ratedoutput current I n
A 1.3 1.7 2.2 3.1 4.1
Base load current I H A 1.1 1.5 1.9 2.7 3.6
Output currentfor S6 duty (40%) I S6
A 1.3 2.0 2.5 3.5 4.5
Max. output current I max A 2.6 3.4 4.4 6.2 8.2
Rated powerbased on I n
kW 0.37 0.55 0.75 1.1 1.5
Rated powerbased on I H
kW 0.37 0.55 0.75 1.1 1.5
Rated pulse frequency kHz 4 4 4 4 4
Efficiency η 0.97 0.97 0.97 0.97 0.97
Power loss kW
Cooling air flow m3 /s 0.005 0.005 0.005 0.005 0.005
Sound pressure level dB(A) < 45 < 45 < 45 < 45 < 45
24 V DC power supply for theControl Unit
A 1.0 1.0 1.0 1.0 1.0
Rated input current 1)with line reactorwithout line reactor
A1.4 1.6
1.8 2.0
2.3 2.5
3.2 3.8
4.3 4.8
Resistance value of the externalbrake resistor
Ohm ≥ 390 ≥ 390 ≥ 390 ≥ 390 ≥ 390
Max. cable length to the brakingresistor
m 15 15 15 15 15
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals for
cable cross-sections1.0 to 2.5 mm2
Screw terminals for
cable cross-sections1.0 to 2.5 mm2
Screw terminals for
cable cross-sections1.0 to 2.5 mm2
Screw terminals for
cable cross-sections1.0 to 2.5 mm2
Screw terminals for
cable cross-sections1.0 to 2.5 mm2
Motor connectionU2, V2, W2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
DC link connection,connection for braking resistorDCP/R1, DCN, R2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
Screw terminals forcable cross-sections1.0 to 2.5 mm
2
PE connection At the housing withM4 stud
At the housing withM4 stud
At the housing withM4 stud
At the housing withM4 stud
At the housing withM4 stud
Max. motor cable length 2) m 50 (shielded)
75 (non-shielded)
50 (shielded)
75 (non-shielded)
50 (shielded)
75 (non-shielded)
50 (shielded)
75 (non-shielded)
50 (shielded)
75 (non-shielded)
Degree of protection IP20 IP20 IP20 IP20 IP20
Width mm 73 73 73 73 73
Height mm 173 173 173 173 173
DepthPower Module PM340PM340 with Control Unit CU310PM340 with CUA31
mm145234.6175.3
145234.6175.3
145234.6175.3
145234.6175.3
145234.6175.3
Frame size FSA FSA FSA FSA FSA
Weight, approx. kg 1.2 1.2 1.2 1.2 1.2
1) The input current depends on the motor load and line supply impedance. The input currents apply to a loadwith rated power (based on In) with a line supply impedance corresponding to uk = 1 %
2) Max. motor cable length 25 m (shielded) for Power Modules PM340 with integrated line filter in order to complywith the limit values stated in EN 61800-3 Category C2
Page 12
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 13/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Line supply voltage3-ph. 380 V to 480 V AC
Power Modules PM340, Blocksize format
PM340
PM340 with integrated line filter
6SL3210-1SE16-0UA0
6SL3210-1SE16-0AA0
6SL3210-1SE17-7UA0
6SL3210-1SE17-7AA0
6SL3210-1SE21-0UA0
6SL3210-1SE21-0AA0
6SL3210-1SE21-8UA0
6SL3210-1SE21-8AA0
6SL3210-1SE22-5UA0
6SL3210-1SE22-5AA0
Ratedoutput current I n
A 5.9 7.7 10.2 18 25
Base load current I H A 5.2 6.8 9.1 14 21
Output currentfor S6 duty (40%) I S6
A 6.4 8.3 10.8 19.6 27.8
Max. output current I max A 11.8 15.4 20.4 26.4 38
Rated powerbased on I n
kW 2.2 3 4 7.5 11
Rated powerbased on I H
kW 2.2 3 4 5.5 7.5
Rated pulse frequency kHz 4 4 4 4 4
Efficiency η 0.97 0.97 0.97 0.97 0.97
Power loss kW
Cooling air flow m3 /s 0.009 0.009 0.009 0.038 0.038
Sound pressure level dB(A) < 50 < 50 < 50 < 60 < 60
24 V DC power supply for theControl Unit
A 1.0 1.0 1.0 1.0 1.0
Rated input current 1)with line reactorwithout line reactor
A6.17.6
8 10.2
10.4 13.4
18.7 21.9
26 31.5
Resistance value of the externalbrake resistor
Ohm ≥ 160 ≥ 160 ≥ 160 ≥ 56 ≥ 56
Max. cable length to the brakingresistor
m 15 15 15 15 15
Line supply connectionU1/L1, V1/L2, W1/L3
Screw terminals forcable cross-sections1.0 to 6 mm
2
Screw terminals forcable cross-sections1.0 to 6 mm
2
Screw terminals forcable cross-sections1.0 to 6 mm
2
Screw terminals forcable cross-sections2.5 to 10 mm
2
Screw terminals forcable cross-sections2.5 to 10 mm
2
Motor connectionU2, V2, W2 Screw terminals forcable cross-sections1.0 to 6 mm
2
Screw terminals forcable cross-sections1.0 to 6 mm
2
Screw terminals forcable cross-sections1.0 to 6 mm
2
Screw terminals forcable cross-sections2.5 to 10 mm
2
Screw terminals forcable cross-sections2.5 to 10 mm
2
DC link connection,connection for braking resistorDCP/R1, DCN, R2
Screw terminals forcable cross-sections1.0 to 6 mm
2
Screw terminals forcable cross-sections1.0 to 6 mm
2
Screw terminals forcable cross-sections1.0 to 6 mm
2
Screw terminals forcable cross-sections2.5 to 10 mm
2
Screw terminals forcable cross-sections2.5 to 10 mm
2
PE connection At the housing withM5 stud
At the housing withM5 stud
At the housing withM5 stud
At the housing withM5 stud
At the housing withM5 stud
Max. motor cable length 2) m 50 (shielded)
75 (non-shielded)
50 (shielded)
75 (non-shielded)
50 (shielded)
75 (non-shielded)
50 (shielded)
75 (non-shielded)
50 (shielded)
75 (non-shielded)
Degree of protection IP20 IP20 IP20 IP20 IP20
Width mm 153 153 153 188.4 188.4
Height mm 270 270 270 333.4 333.4
DepthPower Module PM340PM340 with Control Unit CU310PM340 with CUA31
mm165254.6195.3
165254.6195.3
165254.6195.3
185274.6215.3
185274.6215.3
Frame size FSB FSB FSB FSC FSC
Weight, approx. kg 4.0 4.0 4.0 6.5 6.5
1) The input current depends on the motor load and line supply impedance. The input currents apply to a loadwith rated power (based on In) with a line supply impedance corresponding to uk = 1 %
2) Max. motor cable length 25 m (shielded) for Power Modules PM340 with integrated line filter in order to complywith the limit values stated in EN 61800-3 Category C2
Page 13
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 14/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Line supply voltage3-ph. 380 V to 480 V AC
Power Modules PM340, Blocksize format
PM340
PM340 with integrated line filter
6SL3210-1SE23-2UA0
6SL3210-1SE23-2AA0
6SL3210-1SE23-8UA0
6SL3210-1SE23-8AA0
6SL3210-1SE24-5UA0
6SL3210-1SE24-5AA0
6SL3210-1SE26-0UA0
6SL3210-1SE26-0AA0
6SL3210-1SE27-5UA0
6SL3210-1SE27-5AA0
Rated output current I n A 32 38 45 60 75
Base load current I H A 27 33 40 48 65
Output currentfor S6 duty (40%) I S6
A 37.1 49 58 78 98
Max. output current I max A 52 64 76 90 124
Rated powerbased on I n
kW 15 18.5 22 30 37
Rated powerbased on I H
kW 11 15 18.5 22 30
Rated pulse frequency kHz 4 4 4 4 4
Efficiency η 0.97 0.97 0.97 0.97 0.97
Power loss kW 0.38 0.51 0.69 0.99
Cooling air flow m3 /s 0.038 0.022 0.022 0.039 0.022
Sound pressure level dB(A) < 60 < 60 < 60 < 61 < 6024 V DC power supply for theControl Unit
A 1.0 1.0 1.0 1.0 1.0
Rated input current 1)with line reactorwithout line reactor
A33 39.4
4046
4753
6372
7888
Resistance value of the externalbrake resistor
Ohm ≥ 56 ≥ 27 ≥ 27 ≥ 27 ≥ 15
Max. cable length to the brakingresistor
m 15 15 15 15 15
Line supply connectionU1/L1, V1/L2, W1/L3
Screw terminals forcable cross-sections2.5 to 10 mm
2
M6 studsfor cable cross-sections 10 to35 mm
2
M6 studs for cablecross-sections 10 to35 mm
2
M6 studs for cablecross-sections 10 to35 mm
2
M6 studs for cablecross-sections 10 to35 mm
2
Motor connectionU2, V2, W2 Screw terminals forcable cross-sections2.5 to 10 mm
2
M6 studsfor cable cross-sections 10 to35 mm
2
M6 studsfor cable cross-sections 10 to35 mm
2
M6 studsfor cable cross-sections 10 to35 mm
2
M6 studsfor cable cross-sections 10 to35 mm
2
DC link connection,connection for braking resistorDCP/R1, DCN, R2
Screw terminals forcable cross-sections2.5 to 10 mm
2
M6 studsfor cable cross-sections 10 to35 mm
2
M6 studsfor cable cross-sections 10 to35 mm
2
M6 studsfor cable cross-sections 10 to35 mm
2
M6 studsfor cable cross-sections 10 to35 mm
2
PE connection At the housing withM5 stud
At the housing withM6 stud
At the housing withM6 stud
At the housing withM6 stud
At the housing withM6 stud
Max. motor cable length 2) m 50 (shielded)
75 (non-shielded)
70 (shielded)
100 (non-shielded)
70 (shielded)
100 (non-shielded)
70 (shielded)
100 (non-shielded)
70 (shielded)
100 (non-shielded)
Degree of protection IP20 IP20 IP20 IP20 IP20
Width mm 188.4 275 275 275 275
HeightPower Module PM340PM 340 with integrated filter
mm333.4333.4
418.3511
418.3511
418.3511
498.3633
DepthPower Module PM340PM340 with Control Unit CU310PM340 with CUA31
mm185274.6215.3
203.5293.1233.8
203.5293.1233.8
203.5293.1233.8
203.5293.1233.8
Frame size FSC FSD FSD FSD FSE
Weight, approx. non-filtered/
with integrated filter
kg 6.5
6.5
15.9
19.3
15.9
19.3
15.9
19.3
19.8
27.1
1) The input current depends on the motor load and line supply impedance. The input currents apply to a loadwith rated power (based on In) with a line supply impedance corresponding to uk = 1 %
2) Max. motor cable length 25 m (shielded) for Power Modules PM340 with integrated line filter in order to comply
with the limit values stated in EN 61800-3 Category C2
Page 14
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 15/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Line supply voltage3-ph. 380 V to 480 V AC
Power Modules PM340, Blocksize format
PM340
PM340 with integrated line filter
6SL3210-1SE31-0UA0
6SL3210-1SE31-0AA0
6SL3210-1SE31-1UA0
6SL3210-1SE31-1AA0
6SL3210-1SE31-5UA0
6SL3210-1SE31-5AA0
6SL3210-1SE31-8UA0
6SL3210-1SE31-8AA0
Rated output current I n A 90 110 145 178
Base load current I H A 80 95 115 155
Output currentfor S6 duty (40%) I S6
A 117 143 188 231
Max. output current I max A 150 180 220 290
Rated powerbased on I n
kW 45 55 75 90
Rated powerbased on I H
kW 37 45 55 75
Rated pulse frequency kHz 4 4 4 4
Efficiency η 0.97 0.97 0.97 0.97
Power loss kW 1.21 1.42 1.93 2.31
Cooling air flow m3 /s 0.039 0.094 0.094 0.117
Sound pressure level dB(A) 62 < 60 < 60 6524 V DC power supply for theControl Unit
A 1.0 1.0 1.0 1.0
Rated input current 1)with line reactorwithout line reactor
A94105
115129
151168
186204
Resistance value of the externalbrake resistor
Ohm ≥ 15 ≥ 8.2 ≥ 8.2 ≥ 8.2
Max. cable length to the brakingresistor
m 15 15 15 15
Line supply connectionU1/L1, V1/L2, W1/L3
M6 studs for cable cross-sections 10 to 35 mm
2M8 studs for max. cablecross-sections 1 x120 mm
2or 2 x 50 mm
2
M8 studs for max. cablecross-sections 1 x120 mm
2or 2 x 50 mm
2
M8 studs for max. cablecross-sections 1 x120 mm
2or 2 x 50 mm
2
Motor connection
U2, V2, W2
M6, studs for cable cross-
sections 10 to 35 mm2
M8 studs for max. cable
cross-sections 1 x120 mm2
or 2 x 50 mm2
M8 studs for max. cable
cross-sections 1 x120 mm2
or 2 x 50 mm2
M8 studs for max. cable
cross-sections 1 x120 mm2
or 2 x 50 mm2
DC link connection,connection for braking resistorDCP/R1, DCN, R2
M6 studs for cable cross-sections 10 to 35 mm
2M8 studs for max. cablecross-sections 1 x120 mm
2or 2 x 50 mm
2
M8 studs for max. cablecross-sections 1 x120 mm
2or 2 x 50 mm
2
M8 studs for max. cablecross-sections 1 x120 mm
2or 2 x 50 mm
2
PE connection At the housing with M6stud
At the housing with M8stud
At the housing with M8stud
At the housing with M8stud
Max. motor cable length 2) m 70 (shielded)
100 (non-shielded)
70 (shielded)
100 (non-shielded)
70 (shielded)
100 (non-shielded)
70 (shielded)
100 (non-shielded)
Degree of protection IP20 IP20 IP20 IP20
Width mm 275 350 350 350
HeightPower Module PM340PM340 with integrated filter
mm498.3633
634934
634934
634934
DepthPower Module PM340PM340 with Control Unit CU310with CUA31
mm203.5293.1233.8
315.5405.1345.8
315.5405.1345.8
315.5405.1345.8
Frame size FSE FSF FSF FSF
Weight, approx. non-filtered/
with integrated filter
kg 19.8
27.1
50.7
66.7
50.7
66.7
50.7
66.7
1) The input current depends on the motor load and line supply impedance. The input currents apply to a loadwith rated power (based on In) with a line supply impedance corresponding to uk = 1 %
2) Max. motor cable length 25 m (shielded) for Power Modules PM340 with integrated line filter in order to complywith the limit values stated in EN 61800-3 Category C2
Page 15
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 16/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Characteristics
Overload capacity
Load cycle with pre-load condition Load cycle without pre-load condition
S6 load cycle with pre-load condition S6 load cycle with pre-load condition
Load cycle with 60 s overload for a load cycle of 300 s Load cycle with 30 s overload for a load cycle of 300 s
Page 16
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 17/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Derating characteristic for Power Modules, Blocksize format
1-ph. 200 V to 240 V AC
10
20
30
40
50
60
70
80
90
100
0 2 4 6 8 10 12 14 16 18 20
Pulsfrequenz kHz
z u l ä s s i g e r A u s g a n g s s t r o m %
Frame size FSAoutput current dependent on the pulse frequency
Legend: Zulässiger Ausgangsstrom = permissible outputcurrent
Pulsfrequenz = pulse frequency
3-ph. 380 V to 480 V AC
10
20
30
40
50
60
70
80
90
100
0 2 4 6 8 10 12 14 16 18 20
Pulsfrequenz kHz
z u l ä s s i g e r A u s g a n g s s t r o m %
10
20
30
40
50
60
70
80
90
100
0 2 4 6 8 10 12 14 16 18 20
Pulsfrequenz kHz
z u l ä s s i g e r A u s g a n g s s t r o m %
Frame size FSA, FSB, FSC, FSD and FSEoutput current dependent on the pulse frequency
Frame size FSFoutput current dependent on the pulse frequency
Output current dependent on the ambient temperature
Legend: Umgebungstemperatur = ambient temperature
Output current depending on the installation altitude
Legend: Aufstellhöhe… = installation altitude above sea level
Voltage correction factor depending on the installation altitudeLegend: zulässige … = permissible input voltage in % of the rated voltage; Korrekturfaktor = correction factor
Page 17
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 18/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
2.3 Selection and ordering data Power Modules PM340 Rated output current Rated power Power Module PM340
Order No.
Line supply voltage 1-ph. 200 V to 240 V AC
0.9 A 0.12 kW 6SL3210-1SB11-0UA0
2.3 A 0.37 kW 6SL3210-1SB12-3UA0
3.9 A 0.75 kW 6SL3210-1SB14-0UA0
Line supply voltage 3-ph. 380 V to 480 V AC
1.3 A 0.37 kW 6SL3210-1SE11-3UA0
1.7 A 0.55 kW 6SL3210-1SE11-7UA0
2.2 A 0.75 kW 6SL3210-1SE12-2UA0
3.1 A 1.1 kW 6SL3210-1SE13-1UA0
4.1 A 1.5 kW 6SL3210-1SE14-1UA0
5.9 A 2.2 kW 6SL3210-1SE16-0UA0
7.7 A 3 kW 6SL3210-1SE17-7UA0
10 A 4 kW 6SL3210-1SE21-0UA0
18 A 7.5 kW 6SL3210-1SE21-8UA0
25 A 11 kW 6SL3210-1SE22-5UA0
32 A 15 kW 6SL3210-1SE23-2UA0
38 A 18.5 kW 6SL3210-1SE23-8UA0
45 A 22 kW 6SL3210-1SE24-5UA0
60 A 30 kW 6SL3210-1SE26-0UA0
75 A 37 kW 6SL3210-1SE27-5UA0
90 A 45 kW 6SL3210-1SE31-0UA0
110 A 55 kW 6SL3210-1SE31-1UA0
145 A 75 kW 6SL3210-1SE31-5UA0
178 A 90 kW 6SL3210-1SE31-8UA0
Power Modules PM340 with integrated line filter Rated output current Rated power Power Module PM340 with integrated line filter
Order No.
Line supply voltage 1-ph. 200 V to 240 V AC
0.9 A 0.12 kW 6SL3210-1SB11-0AA0
2.3 A 0.37 kW 6SL3210-1SB12-3AA0
3.9 A 0.75 kW 6SL3210-1SB14-0AA0
Line supply voltage 3-ph. 380 V to 480 V AC
5.9 A 2.2 kW 6SL3210-1SE16-0AA0
7.7 A 3 kW 6SL3210-1SE17-7AA0
10 A 4 kW 6SL3210-1SE21-0AA0
18 A 7.5 kW 6SL3210-1SE21-8AA0
25 A 11 kW 6SL3210-1SE22-5AA0
32 A 15 kW 6SL3210-1SE23-2AA0
38 A 18.5 kW 6SL3210-1SE23-8AA0
45 A 22 kW 6SL3210-1SE24-5AA0
60 A 30 kW 6SL3210-1SE26-0AA0
75 A 37 kW 6SL3210-1SE27-5AA0
90 A 45 kW 6SL3210-1SE31-0AA0
110 A 55 kW 6SL3210-1SE31-1AA0
Page 18
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 19/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
145 A 75 kW 6SL3210-1SE31-5AA0
178 A 90 kW 6SL3210-1SE31-8AA0
Accessories
Description Order No.
Shield connecting plate
• PM340 frame size FSAPM340 with integrated filter, frame size FSA
6SL3262-1AA00-0BA0
• PM340 frame size FSBPM340 with integrated filter, frame size FSB
6SL3262-1AB00-0DA0
• PM340 frame size FSCPM340 with integrated filter, frame size FSC
6SL3262-1AC00-0DA0
• PM340 frame size FSD und FSEPM340 with integrated filter, frame sizes FSD and FSE
6SL3262-1AD00-0DA0
• PM340 frame size FSFPM340 with integrated filter, frame size FSF
6SL3262-1AF00-0DA0
Shield connecting plate for PM340, frame sizeFSB
PM340 frame size FSB with shield connecting plate
Page 19
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 20/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
2.4 Line reactors for Power Modules PM340
Line reactor for Power Modules PM340, frame sizesFSA to FSE
Line reactor for Power Modules PM340, frame size FSF
Line reactors limit low-frequency harmonics that are fed back into the line supply and reduce the level of stress on
the rectifiers of the Power Modules. If the effective line impedance uk ≥ 1%, a line reactor is not required. The
voltage drop uk across the line impedance increases with the current. This is the reason that the specified
condition is more easily fulfilled as the rated power of the Power Module increases.
Technical data
Line supply voltage 1-ph. 200 V to 240 V
AC
Line reactor
Line reactor 6SE6400-3CC00-4AB3 6SE6400-3CC01-0AB3
Rated current A 3.4 8.1
Power loss at 50 / 60 Hz approx. W 12.5 / 15 11.5 / 14.5
Line supply connection U1, V1, W1 Screw terminals 6 mm2 Screw terminals 6 mm2
Load connection Cable 3x AWG16 (1.5 mm2)
length approx. 0.38 m
Cable 3x AWG16 (1.5 mm2)
length approx. 0.38 m
PE connection M5 studs M5 studs
Degree of protection 1)IP20 IP20
Width mm 75.5 75.5
Height mm 201 201
Depth mm 50 50
Weight, approx. kg 1.3 1.3
Matching
Power Module PM340
Type 6SL3210-1SB11-0...
6SL3210-1SB12-3...
6SL3210-1SB14-0...
1) when the cable connecting the load is correctly connected
Page 20
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 21/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Line supply voltage
3-ph. 380 V to 480 V
AC
Line reactor
Line reactor 6SE6400-
3CC00-2AD3
6SE6400-
3CC00-4AD3
6SE6400-
3CC00-6AD3
6SL3203-
0CD21-0AA0
6SL3203-
0CD21-4AA0
6SL3203-
0CD22-2AA0
Rated current A 1.9 3.5 4.8 9 11.6 25
Power loss at
50 Hz/60 Hz
W 6 / 7 12.5 / 15 7.5 / 9 9 / 11 27 / 32 98 / 118
Line supply
connection
U1, V1, W1
Screw terminals
6 mm2
Screw terminals
6 mm2
Screw terminals
6 mm2
Screw terminals
6 mm2
Screw terminals
6 mm2
Screw terminals
6 mm2
Load connection Cable
4× AWG16
(1.5 mm2 )
length, approx.
0.38 m
Cable
4× AWG16
(1.5 mm2 )
length, approx.
0.38 m
Cable
4× AWG16
(1.5 mm2 )
length, approx.
0.38 m
Cable
4x AWG16
(1.5 mm2 )
length, approx.
0.46 m
Cable
4x AWG16
(1.5 mm2 )
length, approx.
0.46 m
Cable
4x AWG10
(2.5 mm2)
length, approx.
0.49 m
PE connection At the housing
with M5 stud
At the housing
with M5 stud
At the housing
with M5 stud
At the housing
with M5 stud
At the housing
with M5 stud
At the housing
with M5 stud
Degree of
protection 1)
IP20 IP20 IP20 IP20 IP20 IP20
Width mm75.5 75.5 75.5
153 153 190
Height mm 201 201 201 290 290 370
Depth mm 50 50 50 70 70 50
Weight, approx. kg 1.2 1.3 1.3 3.4 3.4 6.3
Matching
Power Module
PM340
Type 6SL3210-
1SE11-3...
6SL3210-
1SE11-7...
6SL3210-
1SE12-2...
6SL3210-
1SE13-1...
6SL3210-
1SE14-1...
6SL3210-
1SE16-0...
6SL3210-
1SE17-7...
6SL3210-
1SE21-0...
6SL3210-
1SE21-8...
6SL3210-
1SE22-5...
1) when the cable connecting the load is correctly connected
Page 21
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 22/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Line supply voltage
3-ph. 380 V to 480 V
AC
Line reactor
Line reactor 6SL3203-
0CD23-5AA0
6SL3203-
0CJ24-5AA0
6SL3203-
0CD25-3AA0
6SL3203-
0CJ28-6AA0
6SE6400-
3CC11-2FD0
6SE6400-
3CC11-7FD0
Rated current A 31.3 54 71 105 178 225
Power loss at
50 Hz/60 Hz
W 37 / 44 90/115 90/115 170/215 280/360 280/360
Line supply
connection
U1, V1, W1
Screw terminals
6 mm2
Screw terminals
16 mm2
Screw terminals
16 mm2
Screw terminals
50 mm2
Flat termination
for cable lug
M10
Flat termination
for cable lug
M10
Load connection Cable
4x AWG10
(2.5 mm2)
length, approx.
0.49 m
Cable
4× 16 mm2
length, approx.
0.70 m
Cable
4× 16 mm2
length, approx.
0.70 m
Cable
4× 35 mm2
length, approx.
0.70 m
Flat termination
for cable lug
M10
Flat termination
for cable lug
M10
PE connection At the housing
with M5 stud
At the housing
with M8 screw
At the housing
with M8 screw
At the housing
with M8 screw
At the housing
with M8 stud
At the housing
with M8 stud
Degree of
protection 1)
IP20 IP20 IP20 IP20 IP00 IP00
Width mm 190 275 275 275 240 240
Height mm 370 455 455 577 228 228
Depth mm 50 83,5 83.5 93,5 141 141
Weight, approx. kg 6.4 13 13 19 25 25
Matching
Power Module
PM340
Type 6SL3210-
1SE23-2...
6SL3210-
1SE23-8...
6SL3210-
1SE24-5...
6SL3210-
1SE26-0...
6SL3210-
1SE27-5...
6SL3210-
1SE31-0...
6SL3210-
1SE31-1...
6SL3210-
1SE31-5...
6SL3210-
1SE31-8...
1) when the cable connecting the load is correctly connected
Page 22
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 23/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Selection and ordering data
Rated output current Rated power Matching
Power Module PM340
Line reactor
A kW Type Frame size Order No.
Line supply voltage 1-ph. 200 V to 240 V AC
0.9 0.12 6SL3210-1SB11-0... FSA 6SE6400-3CC00-4AB3
2.3 0.37 6SL3210-1SB12-3... FSA 6SE6400-3CC00-4AB3
3.9 0.75 6SL3210-1SB14-0... FSA 6SE6400-3CC01-0AB3
Line supply voltage 3-ph. 380 V to 480 V AC
1.3 0.37 6SL3210-1SE11-3UA0 FSA 6SE6400-3CC00-2AD3
1.7 0.55 6SL3210-1SE11-7UA0 FSA 6SE6400-3CC00-2AD3
2.2 0.75 6SL3210-1SE12-2UA0 FSA 6SE6400-3CC00-4AD3
3.1 1.1 6SL3210-1SE13-1UA0 FSA 6SE6400-3CC00-4AD3
4.1 1.5 6SL3210-1SE14-1UA0 FSA 6SE6400-3CC00-6AD3
5.9 2.2 6SL3210-1SE16-0... FSB 6SL3203-0CD21-0AA0
7.7 3 6SL3210-1SE17-7... FSB 6SL3203-0CD21-0AA0
10 4 6SL3210-1SE21-0... FSB 6SL3203-0CD21-4AA0
18 7.5 6SL3210-1SE21-8... FSC 6SL3203-0CD22-2AA0
25 11 6SL3210-1SE22-5... FSC 6SL3203-0CD22-2AA0
32 15 6SL3210-1SE23-2... FSC 6SL3203-0CD23-5AA0
38 18.5 6SL3210-1SE23-8... FSD 6SL3203-0CJ24-5AA0
45 22 6SL3210-1SE24-5... FSD 6SL3203-0CJ24-5AA0
60 30 6SL3210-1SE26-0... FSD 6SL3203-0CD25-3AA0
75 37 6SL3210-1SE27-5... FSE 6SL3203-0CJ28-6AA0
90 45 6SL3210-1SE31-0... FSE 6SL3203-0CJ28-6AA0
110 55 6SL3210-1SE31-1... FSF 6SE6400-3CC11-2FD0
145 75 6SL3210-1SE31-5... FSF 6SE6400-3CC11-2FD0
178 90 6SL3210-1SE31-8... FSF 6SE6400-3CC11-7FD0
Page 23
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 24/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
2.5 Line filter for Power Modules PM340
When the system is consistently configured, the line filter for frame size FSA limits the cable-borne noise and
disturbances emitted from the Power Module PM340 to limit values in compliance with Class A1 according toEN 55011 and Category C2 according to EN 61800-3. The line filter may only be directly connected to TN line
supplies.
Note: The line filter is only suitable for Power Modules PM340, frame size FSA and line supply voltages 3-ph.
380 V to 480 V AC. All of the other Power Modules PM340 can be ordered with an integrated line filter.
Line filter, line reactor and Power Module can be mounted on top of one another.
Line reactor
Line
Line filter
Technical data
Line supply voltage
3-ph. 380 V to 480 V AC
Line filter
Line filter 6SE6400-2FA00-6AD0
Rated current A 6
Power loss W < 5
Line supply connection
L1, L2, L3
Screw terminals 2.5 mm2
PE connection At the housing using M4 studs
Load connection
U, V, W
Shielded cable 3 × 2.5 mm2
0.4 m long
Degree of protection IP20 (when the cable connecting the load is correctly connected)
Weight, approx. kg 0.5
Width mm 73.5
Height mm 200
Depth mm 44
Matching
Power Module PM340
Type 6SL3210-1SE11-...
6SL3210-1SE12-...
Page 24
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 25/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Line supply voltage
3-ph. 380 V to 480 V AC
Line filter
6SL3210-1SE13-...
6SL3210-1SE14-...
Selection and ordering data
Matching Power Module PM340
frame size FSA
Line filter
Type Order No.
Line supply voltage 3-ph. 380 V to 480 V AC
6SL3210-1SE11-...6SL3210-1SE12-...
6SL3210-1SE13-...
6SL3210-1SE14-...
6SE6400-2FA00-6AD0
Page 25
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 26/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
2.6 Braking resistors for Power Modules PM340
Power Modules PM340 cannot regenerate energy back into the line supply. When generating, e.g. when braking
a flywheel load (high-inertia load), a braking resistor must be connected that converts the regenerated energy into
heat (thermal energy).
The braking resistor is connected to terminals DCP/R1 and R2.
The braking resistors can be mounted at the side next to the Power Modules PM340. The braking resistors, frame
sizes FSA and FSB are designed as sub-chassis components. If Power Modules PM340, frame sizes FSA or FSB
are operated without a line reactor, then the braking resistors can also be mounted below the Power Modules.
The braking resistors for Power Modules, frame sizes FSC to FSF should be mounted outside the control cabinet
resp. outside the switchgear room so that the power loss is dissipated away from the Power Modules. This
reduces the costs associated with climate control.
Every braking resistor is equipped with a temperature switch (UL listed). The temperature switch must be
evaluated in order to avoid damage if the braking resistor is thermally overloaded.
Technical data
DC link voltage 240 V to 360 V DC Braking resistor for Power Modules, Blocksize format
Braking resistor 6SE6400-4BC05-0AA0
Resistance 180 Ohm
Rating P DB 0.05 kW
Peak rating P max 1 kW
Degree of protection IP20 (when the power connections are correctly connected)
Power connections Cable
3 × 1.5 mm2 (shielded)
length, 0.5 m
Thermo switch (NC contact)
- switching capacity
- cable cross-section that can be
connected
250 VAC / max. 2.5 A
0.5 to 2.5 mm2
Width 72 mm
Height 230 mm
Depth 43.5 mm
Weight, approx. 1.0 kg
Page 26
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 27/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
DC link voltage
510 V to 720 V DC
Braking resistors for Power Modules, Blocksize format
Braking resistors 6SE6400-
4BD11-0AA0
6SL3201-
0BE12-0AA0
6SE6400-
4BD16-5CA0
6SE6400-
4BD21-2DA0
6SE6400-
4BD22-2EA0
6SE6400-
4BD24-0FA0
Resistance Ohm 390 160 56 27 15 8.2
Rating P DB kW 0.1 0.2 0.65 1.2 2.2 4.0
Peak rating P max kW 1.7 4.1 12 24 44 80
Degree of protection 1) IP20 IP20 IP20 IP20 IP20 IP20
Power connections Cable
3 × 1.5 mm2
(shielded)
length, 0.5 m
Cable
3 × 1.5 mm2
(shielded)
length, 0.5 m
Cable
3 × 1.5 mm2
(shielded)
length, 0.9 m
M6 studs M6 studs M6 studs
Thermo switch (NC
contact)
- switching capacity
- cable cross-section
that can be connected
250 VAC /
max. 2.5 A
0.5 to 2.5
mm2
250 VAC /
max. 2.5 A
0.5 to 2.5
mm2
250 VAC /
max. 2.5 A
0.5 to 2.5
mm2
250 VAC /
max. 2.5 A
0.5 to 2.5
mm2
250 VAC /
max. 2.5 A
0.5 to 2.5
mm2
250 VAC /
max. 0.2 A
0.5 to 2.5
mm2
Width mm 72 153 185 270 270 400
Height mm 230 329 285 515 645 650
Depth mm 43.5 43,5 150 175 175 315
Weight, approx. kg 1.0 1.6 3.8 7.4 10.6 16.7
1) when the power connections are correctly connected
Characteristics
Ta = 12 s T = 240 s
Load diagram for braking resistors, Blocksize format
Page 27
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 28/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Selection and ordering data
Description Matching Power Module, Blocksize
format
Order No.
DC link voltage 240 V to 360 V DC (line supply voltage 1-ph. 200 to 240 V AC)
Braking
resistor
180 Ohm Frame size FSA 6SE6400-4BC05-0AA0
DC link voltage 510 V to 720 V DC (line supply voltage 3-ph. 380 V to 480 V AC)
Braking
resistor
390 Ohm Frame size FSA 6SE6400-4BD11-0AA0
160 Ohm Frame size FSB 6SL3201-0BE12-0AA0
56 Ohm Frame size FSC 6SE6400-4BD16-5CA0
27 Ohm Frame size FSD 6SE6400-4BD21-2DA0
15 Ohm Frame size FSE 6SE6400-4BD22-2EA0
8.2 Ohm Frame size FSF 6SE6400-4BD24-0FA0
2.7 Motor reactors for Power Modules PM340
Output reactor for frame sizeFSA
Output reactor for frame sizesFSB and FSC
Output reactor for frame sizeFSD .... FSF
Motor reactors reduce the voltage stress on the motor windings. The capacitive re-charging currents aresimultaneously reduced. These re-charging currents additionally load the power unit when using long motorcables. When a motor reactor is used the max. permissible output frequency is 150 Hz.
The motor reactors for Power Modules 3-ph. 380 V to 480 V AC are suitable for pulse frequencies of 4 kHz.Higher pulse frequencies are not permissible.
The motor reactor should be mounted as close as possible to the Power Module.
Motor reactors have only been released in conjunction with the "Vector" and "V/f open-loop control" control types.
Page 28
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 29/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Technical data
DC link voltage510 V to 720 V DC(line supply voltage 3-ph. 380 V to 480V AC)
Motor reactor (for a 4 kHz pulse frequency)
6SE6400-3TC00-4AD2 6SL3202-0AE21-
0CA0
Rated current A 4.5 10
Power loss kW 0.005 0.02
Connection to the PowerModule
Cable 4x AWG16 (1.5 mm2)length, approx. 0.3 m
Cable 4x AWG14(1.5 mm2)length, approx.0.4 m
Motor connection Screw terminals for 6 mm2 cable cross-sections Screw terminalsfor 6 mm2 cablecross-sections
PE connection M5 studs M5 studs
Max. permissible cablelength between the motorreactor and motor
m
100 (shielded)150 (unshielded)
100 (shielded)150 (unshielded)
100 (shielded)150 (unshielded)
100 (shielded)150 (unshielded)
100 (shielded)150 (unshielded)
100 (shielded)150 (unshielded)
Width mm 75.5 153
Height mm 201 285
Depth mm 110 70
Degree of protection 1) IP20 IP20
Weight, approx. kg 2 4.5
MatchingPower Module, Blocksizeformat
Type 6SL3210-1SE11-3UA0
6SL3210-1SE11-7UA0
6SL3210-1SE12-2UA0
6SL3210-1SE13-1UA0
6SL3210-1SE14-1UA0
6SL3210-1SE16-0UA0
6SL3210-1SE16-0AA0
Frame size FSA FSA FSA FSA FSA FSB
Motor reactor (for a 4 kHz pulse frequency)
6SL3202-0AE21-0CA0 6SL3202-0AJ23-2CA0 6SE6400-3TC05-4DD0
Rated current A 10 32 68
Power loss kW 0.02 0.06 0.2
Connection to the PowerModule
Cable 4x AWG14 (1.5 mm2)length, approx. 0.4 m
Cable 4x AWG14 (1.5 mm2)length, approx. 0.35 m
Flat terminationfor M6 cable lug
Motor connection Screw terminals for 6 mm2 cablecross-sections
Screw terminals for 6 mm2 cable cross-sections Flat terminationfor M6 cable lug
PE connection M5 studs M5 studs M6 studs
Max. permissible cablelength between the motorreactor and motor m
100 (shielded)150 (unshielded)
100 (shielded)150 (unshielded)
100 (shielded)150 (unshielded)
100 (shielded)150 (unshielded)
100 (shielded)150 (unshielded)
200 (shielded)300 (unshielded)
Width mm 153 189 225
Height mm 285 351 210
Depth mm 70 80 140
Degree of protection 1) IP20 IP20 IP00
Weight, approx. kg 4.5 9 11.5
MatchingPower Module, Blocksizeformat
Type 6SL3210-1SE17-7UA0
6SL3210-1SE17-7AA0
6SL3210-1SE21-0UA0
6SL3210-1SE21-0AA0
6SL3210-1SE21-8UA0
6SL3210-1SE21-8AA0
6SL3210-1SE22-5UA0
6SL3210-1SE22-5AA0
6SL3210-1SE23-2UA0
6SL3210-1SE23-2AA0
6SL3210-1SE23-8UA0
6SL3210-1SE23-8AA0
Frame size FSB FSB FSC FSC FSC FSD
1) when the power connections are correctly connected
Page 29
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 30/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Motor reactor (for a 4 kHz pulse frequency)
6SE6400-3TC03-8DD0
6SE6400-3TC05-4DD0
6SE6400-3TC08-0ED0
6SE6400-3TC07-5ED0
6SE6400-3TC14-5FD0
6SE6400-3TC15-4FD0
Rated current A 45 68 104 90 178 178
Power loss kW 0.2 0.2 0.17 0.27 0.47 0.25 Connection to the PowerModule
Flat terminationfor M6 cable lug
Flat terminationfor M6 cable lug
Flat terminationfor M6 cable lug
Flat terminationfor M6 cable lug
Flat terminationfor M8 cable lug
Flat terminationfor M8 cable lug
Motor connection Flat terminationfor M6 cable lug
Flat terminationfor M6 cable lug
Flat terminationfor M6 cable lug
Flat terminationfor M6 cable lug
Flat terminationfor M8 cable lug
Flat terminationfor M8 cable lug
PE connection M6 stud M6 stud M6 stud M6 stud M8 stud M6 stud Max. permissible cablelength between the motorreactor and motor
m
200 (shielded)300 (unshielded)
200 (shielded)300 (unshielded)
200 (shielded)300 (unshielded)
200 (shielded)300 (unshielded)
200 (shielded)300 (unshielded)
200 (shielded)300 (unshielded)
Width mm 225 225 225 270 357 270
Height mm 210 210 210 248 321 248
Depth mm 164 140 140 189 221 189
Degree of protection IP00 IP00 IP00 IP00 IP00 IP00
Weight, approx. kg 19 11.5 12 27 57 24
MatchingPower Module, Blocksizeformat
Type 6SL3210-1SE24-5UA0
6SL3210-1SE24-5AA0
6SL3210-1SE26-0UA0
6SL3210-1SE26-0AA0
6SL3210-1SE27-5UA0
6SL3210-1SE27-5AA0
6SL3210-1SE31-0UA0
6SL3210-1SE31-0AA0
6SL3210-1SE31-1UA0
6SL3210-1SE31-1AA0
6SL3210-1SE31-5UA0
6SL3210-1SE31-5AA0
Frame size FSD FSD FSE FSE FSF FSF
Motor reactor (for a 4 kHz pulsefrequency)
6SE6400-3TC14-5FD0
Rated current A 178
Power loss kW 0.47
Connection to the PowerModule
Flat termination for M8 cable lug
Motor connection Flat termination for M8 cable lug
PE connection M8 stud
Max. permissible cablelength between the motorreactor and motor
m
200 (shielded)300 (non-shielded)
Width mm 357
Height mm 321
Depth mm 221
Degree of protection IP00
Weight, approx. kg 57
MatchingPower Module, Blocksizeformat
Type 6SL3210-1SE31-8UA0
6SL3210-1SE31-8AA0
Frame size FSF
Selection and ordering data
Page 30
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 31/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Rated current (power) of the Power Module Matching Power Module Frame size Motor reactorOrder No.
DC link voltage 510 V to 720 V DC (line supply voltage 3-ph. 380 V to 480 V AC)
1.3 A (0.37 kW) 6SL3210-1SE11-3UA0 FSA 6SE6400-3TC00-4AD2
1.7 A (0.55 kW) 6SL3210-1SE11-7UA0 FSA 6SE6400-3TC00-4AD2
2.2 A (0.75 kW) 6SL3210-1SE12-2UA0 FSA 6SE6400-3TC00-4AD2
3.1 A (1.1 kW) 6SL3210-1SE13-1UA0 FSA 6SE6400-3TC00-4AD2
4.1 A (1.5 kW) 6SL3210-1SE14-1UA0 FSA 6SE6400-3TC00-4AD2
5.9 A (2.2 kW) 6SL3210-1SE16-0UA0
6SL3210-1SE16-0AA0
FSB 6SL3202-0AE21-0CA0
7.7 A (3 kW) 6SL3210-1SE17-7UA0
6SL3210-1SE17-7AA0
FSB 6SL3202-0AE21-0CA0
10 A (4 kW) 6SL3210-1SE21-0UA0
6SL3210-1SE21-0AA0
FSB 6SL3202-0AE21-0CA0
18 A (7.5 kW) 6SL3210-1SE21-8UA0
6SL3210-1SE21-8AA0
FSC 6SL3202-0AJ23-2CA0
25 A (11 kW) 6SL3210-1SE22-5UA0
6SL3210-1SE22-5AA0
FSC 6SL3202-0AJ23-2CA0
32 A (15 kW) 6SL3210-1SE23-2UA0
6SL3210-1SE23-2AA0
FSC 6SL3202-0AJ23-2CA0
38 A (18,5 kW) 6SL3210-1SE23-8UA0
6SL3210-1SE23-8AA0
FSD 6SE6400-3TC05-4DD0
45 A (22 kW) 6SL3210-1SE24-5UA0
6SL3210-1SE24-5AA0
FSD 6SE6400-3TC03-8DD0
60 A (30 kW) 6SL3210-1SE26-0UA0
6SL3210-1SE26-0AA0
FSD 6SE6400-3TC05-4DD0
75 A (37 kW) 6SL3210-1SE27-5UA0
6SL3210-1SE27-5AA0
FSE 6SE6400-3TC08-0ED0
90 A (45 kW) 6SL3210-1SE31-0UA0
6SL3210-1SE31-0AA0
FSE 6SE6400-3TC07-5ED0
110 A (55 kW) 6SL3210-1SE31-1UA0
6SL3210-1SE31-1AA0
FSF 6SE6400-3TC14-5FD0
145 A (75 kW) 6SL3210-1SE31-5UA0
6SL3210-1SE31-5AA0
FSF 6SE6400-3TC15-4FD0
178 A (90 kW) 6SL3210-1SE31-8UA0
6SL3210-1SE31-8AA0
FSF 6SE6400-3TC14-5FD0
Page 31
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 32/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
3 Power Modules, Chassis format
3.1 Overview
Power Module, Chassis format, frame size GX
As standard, the Power Modules, Chassis format are provided with the following interfaces:
• 1 line supply connection
• 2 DC link connections for options - e.g. "Braking Module"
• 3 DRIVE-CLiQ sockets
• 1 safe standstill (Safe Torque Off) input (enable pulses)
• 1 temperature sensor input (KTY84-130 or PTC)
• 1 electronics power supply connection
• 1 motor connection
• 2 PE/protective conductor connections
The Control Unit CU310 can be installed in the Power Modules, Chassis format.
The following are included in the scope of supply of the Power Modules:
• 1 DRIVE-CLiQ cable to connect to the Control Unit CU310
• 1 24 V connecting cable to supply the Control Unit CU310
• 1 mounting plate to mount the Control Unit CU310
Page 32
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 33/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
The Power Modules, Chassis format communicate with the higher-level control unit via DRIVE-CLiQ. This Control
Unit can be a Control Unit CU310, CU320 or a Control Unit SIMOTION D.
==
µP
PEU1 V1 W1
U2
DCNS
V2 W2 PE
-X9
Line reactor
3-ph. 380 V - 480 V AC
L1 L2 L3 PE
M3~
Braking resistor
DCPS
DCPA
DCNA
DRIVE-CLiQ socket 0
DRIVE-CLiQ socket 1
DRIVE-CLiQ socket 2
Control Unit
H200 (Ready)
H201 (DC Link)
1
2
-X41
Option,Braking
Module
R1
R2
Power Module,Chassis format
M1~
1
2
3
4 +Temp
-Temp
EP +24V
EP M1
E
DRIVE-CLiQ
P24_1
M_1
5
6
DC24 V
1-ph. 230 V AC
Connection example, Power Module, Chassis format
Page 33
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 34/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
3.2 Technical data
General technical data
Electrical data
Line supply voltage(up to 2000 m above sea level)
3-ph. 380 V to 480 V AC ±10% (-15% < 1 min)
Line frequency 47 Hz to 63 Hz
Line supply power factor at rated power
- basic fundamental (cos ϕ1)
- total (λ)
> 0.96
0.75 to 0.93
Overvoltage Category Class III according to EN 60664-1
Pre-charging frequency of the DC link Max. 1x every 300 seconds
DC link voltage Approx. 1.35 x line supply voltage
Output frequency
- servo closed-loop control type 0 Hz to 650 Hz *)
- vector closed-loop control type 0 Hz to 300 Hz *)
- V/f control type 0 Hz to 300 Hz *)
Electronics power supply 24 V DC, -15/+20%
Main contactor control
(terminal strip X9/4-5)
240 V AC/ max. 8 A 30 V DC/ max. 1 A
Radio interference suppression
- standard Category C3 according to EN 61800-3
- with line filter Category C2 according to EN 61800-3
Ambient conditions
Cooling type Internal air cooling, power units are force-ventilated using anintegrated fan
Permissible ambient or coolant temperatures(air) in operation for line-side components - LineModules and Motor Modules
0 °C to +40 °C without derating,> 40 °C to +55 °C, refer to derating characteristics
Installation altitude Up to 2000 m above sea level without derating,> 2000 m up to 4000 m above sea level, refer to the deratingcharacteristics
In conformance with CE (Low-Voltage and EMC Directive)
Approvals, listings cULus (File No.: E192450)
Certifications (being prepared) Safety Integrity Level 2 (SIL 2) according to IEC 61508,Control Category 3 according to EN 954-1 for SafetyIntegrated – STO = Safe Torque Off
*) observe the interrelationship between the max. output frequency and pulse frequency and currentderating - refer to the Configuration Manual
Page 34
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 35/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Technical data
Line supply voltage 3-ph. 380 V to
480 V AC
Power Modules, Chassis format
Power Module PM340 Type 6SL3310-1TE32-1AA0
6SL3310-1TE32-6AA0
6SL3310-1TE33-1AA0
6SL3310-1TE33-8AA0
6SL3310-1TE35-0AA0
Rated output current I n A 210 260 310 380 490
Base load current I H A 180 233 277 340 438
Output current for S6 duty (40%)I S6
A 230 285 340 430 540
Max. output current I max A 307 375 453 555 715
Rated power based on I n kW 110 132 160 200 250
Rated power based on I H kW 90 110 132 160 200
Rated pulse frequency kHz 2 2 2 2 2
Efficiency η 0.986 0.986 0.986 0.986 0.986
Power loss kW 2.46 3.27 4.0 4.54 5.78
Cooling air flow m3 /s 0.17 0.23 0.36 0.36 0.36
Sound pressure level at50 Hz/60 Hz
dB(A) 66/67 68/72 68/72 68/72 68/72
Rated input current A 218 270 322 395 510
Line supply connectionU1, V1, W1
Flat termination for M10 cable lug, max. connection cross-section 2 × 185 mm2
DC link connection,DCPA, DCNA(option, Braking Module)
Flat termination for M8 cable lug, max.connection cross-section 1 × 35 mm
2Flat termination for M8 cable lug, max. connection cross-section
1 × 50 mm2
DC link connection,DCPS, DCNS(option, dv/dt filter)
Flat termination for M8 cable lug, max.connection cross-section 1 × 35 mm
2Flat termination for M8 cable lug, max. connection cross-section
1 × 70 mm2
Motor connectionU2, V2, W2
Flat termination for M10 cable lug, max. connection cross-section 2 × 185 mm2
PE connection Flat termination for M10 cable lug, max. connection cross-section 2 × 185 mm2
Max. motor cable length1)
m 300 (shielded)450 (non-shielded)
300 (shielded)450 (non-shielded)
300 (shielded)450 (non-shielded)
300 (shielded)450 (non-shielded)
300 (shielded)450 (non-shielded)
Degree of protection IP20 IP20 IP20 IP20 IP20
Width mm 326 326 326 326 326
Height mm 1400 1400 1533 1533 1533
Depth mm 356 356 545 545 545
Frame size FX FX GX GX GX
Weight, approx. kg 104 104 162 162 162
1) Max. motor cable length 100 m (shielded) in conjunction with a line filter to comply with limit values according to EN 61800-3Category C2.
Page 35
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 36/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Characteristics
Overload capability
Load cycle data of the Power Modules, Chassis format
The base load current I H is based on a 150% load cycle for 60 s resp. 160% load cycle for 10 s with a load cycle
duration of 300 s.
High overload
Legend: Umrichterstrom = converter current, Kurzzeitstrom ... = short-time current (continuous)Grundlaststrom … Base load currentIH for high overloads
Derating factors
Output current as a function of the pulse frequency
Power Module,
Chassis format
Rated output
current InDerating factor
Type A At a pulse frequency
of 2.5 kHz-
At a pulse frequency of 4 kHz
6SL3310-1TE32-
1AA0
210 0.95 0.82
6SL3310-1TE32-
6AA0
260 0.95 0.83
6SL3310-1TE33-
1AA0
310 0.97 0.88
6SL3310-1TE33-
8AA0
380 0.96 0.87
6SL3310-1TE35-
0AA0
490 0.94 0.78
Page 36
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 37/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Current derating dependent on the ambient temperature
Legend: Korrekturfaktor = correction factor, Umgebungstemperatur = ambient temperature
Note: A factor kT > 1 should only be taken into account in conjunction with the current derating dependent on the installation
altitude, refer to Chapter "Engineering information"
Current derating as a function of the installation altitude
Legend: zulässiger … = permissible continuous current in % of the rated current;
Aufstellhöhe = installation altitude above sea level; Korrekturfaktor = correction factor
Voltage derating as a function of the installation altitude
Legend: zulässige… = permissible input voltage in % of the rated voltage; Aufstellhöhe… = installation altitude above sea level;
Korrekturfaktor = correction factor
Page 37
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 38/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
3.3 Selection and ordering data
Rated output current Rated power Power Module, Chassis format
A kW Order No.
Line supply voltage 3-ph. 380 V to 480 V AC
210 110 6SL3310-1TE32-1AA0
260 132 6SL3310-1TE32-6AA0
310 160 6SL3310-1TE33-1AA0
380 200 6SL3310-1TE33-8AA0
490 250 6SL3310-1TE35-0AA0
Warning labels and information in foreign languages
Other warning labels can be attached to the standard English or German warning labels and information.
For the Chassis format drive units, the following labels are already included in the scope of supply:
Chinese, Danish, Finnish, French, Greek, Italian, Japanese, Korean, Dutch, Polish, Portuguese, Russian,
Swedish, Spanish, Czech and Turkish.
3.4 Line reactors for Power Modules, Chassis format
Line reactors limit low-frequency harmonics fed back into the line supply and relieve the rectifier of the Power
Modules. The necessary inductance of the line reactors is reduced to the same extent as the Power Module rated
power increases. A line reactor is not required for effective line impedances > 3% uk. More detailed information is
provided in the Chapter "Engineering information".
Page 38
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 39/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
Technical data
Line supply voltage 3-
ph. 380 V to 480 V AC
Line reactor
Line reactor 6SL3000-0CE32-3AA0 6SL3000-0CE32-8AA0 6SL3000-0CE33-3AA0 6SL3000-0CE35-1AA0
Rated current A 224 278 331 508
Power loss at
50 Hz/60 Hz
kW 0.24 / 0.27 0.21 / 0.25 0.23 / 0.27 0.31 / 0.37
Line supply
connection
1U1, 1V1, 1W1
Flat termination for M10
cable lug
Flat termination for M10
cable lug
Flat termination for M10
cable lug
Flat termination for
M12 cable lug
Load connection
1U2, 1V2, 1W2
Flat termination for M10
cable lug
Flat termination for M10
cable lug
Flat termination for M10
cable lug
Flat termination for
M12 cable lug
PE connection M6 screw M6 screw M6 screw M6 screw
Degree of
protection
IP00 IP00 IP00 IP00
Width mm 270 270 270 300
Height mm 248 248 248 269
Depth mm 200 200 200 212.5
Weight, approx. kg 24.4 26 27.8 38
Matching
Power Module
Type 6SL3310-1TE32-1... 6SL3310-1TE32-6... 6SL3310-1TE33-1... 6SL3310-1TE33-8...
6SL3310-1TE35-0...
Selection and ordering data
Rated output current Rated power Matching Power Module Line reactor
A kW Type Order No.
Line supply voltage 3-ph. 380 V to 480 V AC
210 110 6SL3310-1TE32-1AA0 6SL3000-0CE32-3AA0
260 132 6SL3310-1TE32-6AA0 6SL3000-0CE32-8AA0
310 160 6SL3310-1TE33-1AA0 6SL3000-0CE33-3AA0
380 200 6SL3310-1TE33-8AA0 6SL3000-0CE35-1AA0
490 250 6SL3310-1TE35-0AA0 6SL3000-0CE35-1AA0
Page 39
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 40/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
3.5 Line filters for Power Modules, Chassis format
Line filters limit the cable-borne noise and disturbances that Power Modules emit in conjunction with line reactorsand a consistent system configuration. These noise and disturbances are limited to limit values Class C2according to EN 61800-3. The line filters may only be directly connected to TN line supplies.
Technical data
Line supply voltage 3-ph. 380 V to 480 VAC
Line filter
Line filter 6SL3000-0BE32-5AA0 6SL3000-0BE34-4AA0 6SL3000-0BE36-0AA0
Rated current A 250 440 600
Power loss kW 0.05 0.05 0.06
Line supply connection1U1, 1V1, 1W1
Flat termination for M10 cable lug Flat termination for M10 cable lug Flat termination for M10 cable lug
Load connection1U2, 1V2, 1W2
Flat termination for M10 cable lug Flat termination for M10 cable lug Flat termination for M10 cable lug
Degree of protection IP00 IP00 IP00
Width mm 330 360 400
Height mm 240 240 265
Depth mm 116 116 140
Weight, approx. kg 12.5 12.5 19
MatchingPower Module
Type 6SL3310-1TE32-1... 6SL3310-1TE32-6...6SL3310-1TE33-1...6SL3310-1TE33-8...
6SL3310-1TE35-0...
Selection and ordering data
Rated output current Rated power Matching Power Module Line filter
A kW Type Order No.
Line supply voltage 3-ph. 380 V to 480 V AC
210 110 6SL3310-1TE32-1AA0 6SL3000-0BE32-5AA0
260 132 6SL3310-1TE32-6AA0 6SL3000-0BE34-4AA0
310 160 6SL3310-1TE33-1AA0 6SL3000-0BE34-4AA0
380 200 6SL3310-1TE33-8AA0 6SL3000-0BE34-4AA0
490 250 6SL3310-1TE35-0AA0 6SL3000-0BE36-0AA0
Page 40
8/2/2019 SINAMICS S120 POWER MODULES Blocksize and Chassis Formats Www.otomasyonegitimi.com
http://slidepdf.com/reader/full/sinamics-s120-power-modules-blocksize-and-chassis-formats-wwwotomasyonegitimicom 41/41
Component description and ordering document, SINAMICS S120 AC Drive V1.0
3.6 Braking Modules and braking resistors for Power Modules,Chassis format
The Braking Modules and braking resistors of Motor Modules with the same power rating are used. Technicaldata, refer to Catalog D21.1 (2005), Pages 2/63 and 2/67
3.7 Motor reactors and sinusoidal filters for Power Modules,Chassis format
The motor reactors and sinusoidal filters of the Motor Modules with the same power rating are used. Refer toCatalog D21.1 (2005), Pages 2/75 and 2/73 for technical data.