Simplified Space Conditioning

Duncan Prahl, RAIBACOS, Inc.

Building America Technical UpdateApril 29, 2013

Simplified Space Conditioning

Rethinking HVAC Design

• Traditional Method – Assume envelope losses dictate the load – Room by room load analysis – Pick Equipment and distribute to meet the load in each room

• New Method – Consider how the occupants live in the building– Seriously consider internal gains in both heating and cooling– Consider ventilation strategy– Design system

Simplified Space Conditioning

If you are:

• A production builder• Participating in “above code” programs• Following ACCA Manual RS or ASHRAE 55• Need to prove “delivering heat to each habitable room”• Concerned about litigation

• Play it safe, Use Manual J, S & D and condition every space– But you still might have comfort complaints…

Simplified Space Conditioning

Research Results

• A Typical Production Home, Central CA

Simplified Space Conditioning

Assembly SpecificationsConcrete Slab R-10 vertical slab edge insulationFramed Walls 2x4 16-in. O.C. with R-15 cavity plus R-3 sheathing

Roof R-49 blown attic insulation at floor, radiant barrier at roof sheathing

Windows U = 0.28, SHGC = 0.26Building Air Leakage 2.45 ACH at 50Pa

Windows U = 0.28, SHGC = 0.26Building Air Leakage 2.45 ACH at 50Pa

Heating Load 23,891 BtuhCooling Load 17,193 Btuh

System 95% AFUE Gas furnace with 16 SEER ACDistribution Insulated Flexible Ductwork located in conditioned

spaceVentilation Bathroom exhaust fans, Fresh air duct into AHU Return

Roseville, CA. ~1800 s.f. single story

Simplified Space Conditioning

Single Story, 4 Bedroom, Central CA

• Distribution to Each Room

• Compact Duct System in Conditioned Space

• Right Sized• Never 100% balanced by

the HVAC contractor• Probably represents a

“typical” good HVAC job

MechCoffer

Simplified Space Conditioning

Room Temperature Performance

Room to t’stat temperatures over 2012/13 heating season mostly within +/- 2oF, cooling within +/- 3oF

Simplified Space Conditioning

Room Temperature – late winter

Simplified Space Conditioning

A “client-tuned” HVAC system:

• Do you want temperatures in each room to be uniform with one another?

• Do you want individual control in each room?• Do you keep your doors closed frequently?• Do you like to adjust your thermostat a lot?• TV’s, computers, etc. in the bedrooms?

Simplified Space Conditioning

One House Many Systems

Simplified Space Conditioning

Assembly Specifications Concrete Slab R-10 continuous below slab Basement Walls R-25 finished portion, R-19.5 unfinished portion

Framed Walls R-30 cavity insulation - framing fraction of 15% R-10 continuous exterior sheathing

Roof R-60 blown insulation at floor of vented attic Windows 306 sq. ft., U = 0.24, SHGC = 0.22 Building Air Leakage 0.54 ACH at 50Pa Heating Load 18,526 Btu/h (5,430 W) Cooling Load 11,236 Btu/h (3,293 W)

Distribution Systems“Right Sized” Fully Ducted Full Volume; Partially Ducted Low Volume; Dual Point

Ventilation ERV - Exhausted from bathrooms - Supplied into AHU return or to bedrooms

Pittsburgh PA

Simplified Space Conditioning

Winter 2012 – Cold Days

Simplified Space Conditioning

Single Point on 1st Floor

Supply

Return

Simplified Space Conditioning

Single Point on 1st Floor – Winter Cloudy Day

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

-26

-24

-22

-20

-18

-16

-14

-12

-10

-8

-6

-4

-2

0

2

4

6

8

0:00

1:00

2:00

3:00

4:00

5:00

6:00

7:00

8:00

9:00

10:0

0

11:0

0

12:0

0

13:0

0

14:0

0

15:0

0

16:0

0

17:0

0

18:0

0

19:0

0

20:0

0

21:0

0

22:0

0

23:0

0

0:00

Tem

pera

ture

(F)

Tem

pera

ture

Rel

ativ

e to

The

rmos

tat (

F)

Hour of Day

System On

Dining Room

Living Room

Breakfast Room

Comfort Band

Outdoor

At Thermostat

Coast Down Steady StateResponse

Simplified Space Conditioning

“Right Sized” on 1st Floor

Return

Simplified Space Conditioning

“Right Sized 1st Floor – Winter Sunny Day

Simplified Space Conditioning

Single Point on 2nd Floor

Simplified Space Conditioning

Single Point on 2nd Floor –Doors Open Sunny Day

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

-26

-24

-22

-20

-18

-16

-14

-12

-10

-8

-6

-4

-2

0

2

4

6

80:

00

1:00

2:00

3:00

4:00

5:00

6:00

7:00

8:00

9:00

10:0

0

11:0

0

12:0

0

13:0

0

14:0

0

15:0

0

16:0

0

17:0

0

18:0

0

19:0

0

20:0

0

21:0

0

22:0

0

23:0

0

0:00

Tem

pera

ture

(F)

Tem

pera

ture

Rel

ativ

e to

The

rmos

tat (

F)

Hour of Day

System On

Northwest Bedroom

West Bedroom

Southwest Bedroom

Master Bedroom (Northeast)Comfort Band

Outdoor

At Thermostat

At Hallway

Doors OpenSystem Off

Doors Open1st Floor System On

Doors Open2nd Floor System OnDoors Closed

Simplified Space Conditioning

Single Point on 2nd Floor –Doors Closed, Transfer Fans, Cold Cloudy Day

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

-26

-24

-22

-20

-18

-16

-14

-12

-10

-8

-6

-4

-2

0

2

4

6

80:

00

1:00

2:00

3:00

4:00

5:00

6:00

7:00

8:00

9:00

10:0

0

11:0

0

12:0

0

13:0

0

14:0

0

15:0

0

16:0

0

17:0

0

18:0

0

19:0

0

20:0

0

21:0

0

22:0

0

23:0

0

0:00

Tem

pera

ture

(F)

Tem

pera

ture

Rel

ativ

e to

The

rmos

tat (

F)

Hour of Day

System On

Northwest Bedroom

West Bedroom

Southwest Bedroom

Master Bedroom (Northeast)Comfort Band

Outdoor Temperature

At 1st Flr Thermostat

At Hallway

Simplified Space Conditioning

Single Point on 2nd Floor -Doors Closed & Transfer Fans, Cold Sunny Day

Simplified Space Conditioning

Multi point 2nd FloorDoors Closed 15 CFM/Room

Simplified Space Conditioning

Multi point 2nd Floor - Doors Closed , Cold Sunny Day

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

-26

-24

-22

-20

-18

-16

-14

-12

-10

-8

-6

-4

-2

0

2

4

6

8

0:00

1:00

2:00

3:00

4:00

5:00

6:00

7:00

8:00

9:00

10:0

0

11:0

0

12:0

0

13:0

0

14:0

0

15:0

0

16:0

0

17:0

0

18:0

0

19:0

0

20:0

0

21:0

0

22:0

0

23:0

0

0:00

Tem

pera

ture

(F)

Tem

pera

ture

Rel

ativ

e to

The

rmos

tat (

F)

Hour of Day

System On

Northwest Bedroom

West Bedroom

Southwest Bedroom

Master Bedroom (Northeast)Comfort Band

Outdoor

At Thermostat

At Hallway

Simplified Space Conditioning

“Right Sized 2nd Floor – Supply in every room

Simplified Space Conditioning

“Right Sized 2nd Floor - Doors Closed T’Stat in Hall, Cold Sunny Day

Simplified Space Conditioning

Why?

• Room to wall area ratio– “Panel Heating”– Need Highly Conductive

Walls?• Location of Single Point

supply relative to transfer fan / door locations

• Solar gains not equal

Simplified Space Conditioning

Summer 2012 – Hot, Sunny Days

Supply

Return

Simplified Space Conditioning

Single Point , 1st Floor –Transfer Fans Sunny Hot Summer Day

Simplified Space Conditioning

Single Point on 2nd Floor –Transfer Fans, Hot Sunny day

Simplified Space Conditioning

Ventilation Airflow, 1st Floor –15 CFM/Room Sunny Hot Day

Simplified Space Conditioning

Ventilation Airflow, 2nd Floor –15 CFM/Room Sunny Hot Day

Simplified Space Conditioning

“Right Sized” 1st Floor –Distribution to Each Room, Sunny Hot Day

Simplified Space Conditioning

“Right Sized” 2nd Floor –Distribution to Each Room, Sunny Hot Day

Simplified Space Conditioning

Conclusions

• Large open spaces can be effectively conditioned form one point– Proper location in house, register selection / throw pattern

critical• Set up / Set back is hard to do uniformly• Factors to consider when designing a HVAC system for

a low-load house:– Sunlight (windows)– Internal gains and interior door positions (occupants lifestyle)– Ventilation strategy

Simplified Space Conditioning

What Should Grandma Do?

• RIP• Slow and Steady wins the race

– High sidewall supply outlets work well

• Comfort uniformity is enhanced by periodic fan circulation – like what you need for fresh air– Multiple temperature sensors to control fan only

operation– Locate sensors in “worst case” rooms

• To truly zone you probably need a unit in each room, or match rooms with equal solar gains– Zoning by floor with multiple temp sensors per system

or per zone

Simplified Space Conditioning

Thank You