Page 1: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 2: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 3: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 4: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 5: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 6: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

SUMMARY OF EXISTING LC-DIMONDLOAD CENTER TYPE: TYPE 2 DUAL-PANEL SINGLE-POLE MOUNTED

MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA) & MUNICIPALITY OF ANCHORAGE (MOA)SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)

SERVICE CONDUIT TYPE: RMC & PVCLOAD CENTER LOCATION DATA (61.144573°, -149.855952°)

LOAD CENTER: NEW SEWARD HWY & DIMOND BLVD (SE)POWER SOURCE: EXISTING 25 kVA CEA PAD-MOUNT SERVICE TRANSFORMER (61.144624°, -149.855861°) (NOTE 2)

PHOTOELECTRIC CONTROL: EXISTING AT LOAD CENTERSERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL

PROVIDE METER SOCKET: EXISTING METERS (136 716 646, SOA) (136 716 645, MOA)PANEL A (SOA) MAIN SERVICE DISCONNECT 480V, 2-POLE, 200APANEL B (MOA) MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A

CONTACTORS A & B: EXISTINGAIC RATING, PANELS A & B: 10 kAIC @ 480V

PANEL A - 240/480 VAC, 200A BUS

POLE AMPTRIP DESCRIPTION CKT

kVA AѲ BѲ CKTkVA DESCRIPTION AMP

TRIP POLE

1 20/2 SPARE (NOTE 3) 0 0 0SPARE 20/2 2

3 0 0 0 45

40/2LUMINAIRES EAST & WEST

OF OVERPASS & UNDERBRIDGE *

1.3 1.3 0SPARE 40/2

67 1.3 1.3 0 89 - SPACE 0 0 0 SPACE 30/1 10

11 - SPACE 0 0 0 SPACE 30/1 1213 - SPACE 0 0 0 SPACE - 1415 - SPACE 0 0 0 SPACE - 1617 - SPACE 0 0 0 SPACE - 18

PANEL B - 240/480 VAC, 100A BUS

POLE AMPTRIP DESCRIPTION CKT

kVA AѲ BѲ CKTkVA DESCRIPTION AMP

TRIP POLE

1 70/1 SPARE 0 0 0 SIGNAL CABINET XFMRPRIMARY(NOTE 4)

40/22

3 70/1 SIGNAL CABINET (NOTE 5) 1.1 1.1 0 4

5 15/1DIMOND/NSH WEST

INTXL**(2 LED, 2HPS)

1.5 1.6 0.1 PEC CONTROL 15/1 6

7 15/1 SPARE 0 0 0 - - 8* CIRCUITED THROUGH CONTACTOR A & TIMER SWITCH

** CIRCUITED THROUGH CONTACTOR B2.9 2.4 TOTAL kVA 5.3

TOTAL AMPS AT 480V 11.0

SHORT CIRCUIT CALCULATION LC-C480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM CONDUCTOR PER PHASE IN A RMC.

TEMPERATURE RATING 75 DEG CTRANSFORMER RATING 25kVA

VOLTAGE 240/480VTRANSFORMER IMPEDANCE 1.20%

TRANSFORMER LET-THRU SHORT CIRCUITCURRENT (INFINITE BUS) 3389A

LENGTH TO FAULT 60'SERVICE CONDUCTOR SIZE 1/0 Aluminum Conductors

SERVICE CONDUIT 2" RMCLINE-LINE FAULT 3179A

ARC FLASH AND SHOCK HAZARD RESULTS LC-DIMONDARC FLASH BOUNDARY

INCIDENT ENERGY IN CAL/CM2WORKING DISTANCE 18 INCHES

SHOCK HAZARD EXPOSUREINSULATING GLOVES CLASS 00

SHOCK HAZARDLIMITED APPROACH BOUNDARY 42 INCHES

RESTRICTED APPROACH BOUNDARY 12 INCHES

CALCULATED DATE

Page 7: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 8: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 9: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

SERVICE: LC-D240/480V, 200A

REUSE EXISTINGCONDUIT & CABLE

LUMINAIRE NUMBER, TYP.

Page 10: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

VOLTAGE DROPS "LC-D"240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.9, 1 COPPER CONDUCTOR PER PHASE IN A RMC. TEMPERATURE

RATING 75 DEG C

CKT # SEGMENT SEGMENT SIZE(AWG)

SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP

(%VD)CUMULATIVEDROP (%VD)

D-1E102 TO E104 8 161 166.67 0.72 0.07 0.13

E104 TO LC D 8 65 333.33 1.45 0.06 0.06

D-3E108 &E109 TO E107 8 158 333.33 1.45 0.14 0.33

E107 TO LC D 8 139 500.00 2.17 0.19 0.19

D-4

E103 TO E105 8 154 166.67 0.72 0.07 0.39

E106 TO E105 8 173 166.67 0.72 0.08 0.40

E105 TO E104 8 288 333.33 1.45 0.26 0.32

E104 TO LC D 8 65 333.33 1.45 0.06 0.06

D-5

E1 TO E2 8 228 215.56 0.94 0.13 0.83

E2 TO E3 8 222 431.11 1.87 0.26 0.70

E3 TO LC D 8 246 646.67 2.81 0.44 0.44

D-6

E13 TO E12 6 232 215.56 0.94 0.09 2.93

E12 TO E11 6 232 431.11 1.87 0.18 2.84

E11 TO E10 6 205 646.67 2.81 0.23 2.66

E10 TO E9 6 232 862.22 3.75 0.35 2.43

E9 TO E8 6 226 1077.78 4.69 0.43 2.08

E8 TO E105 6 308 1293.33 5.62 0.70 1.66

E105 TO E104 6 288 1508.89 6.56 0.76 0.96

E104 TO LC D 6 65 1724.44 7.50 0.20 0.20

D-8/10

HT1 TO JB 1A 4 425 8000.00 17.02 0.92 2.90

JB1A TO E1 4 215 8000.00 17.02 0.47 1.98

E1 TO E2 4 228 8000.00 17.02 0.50 1.51

E2 TO E3 4 222 8000.00 17.02 0.48 1.02

E3 TO LC D 4 246 8000.00 17.02 0.53 0.53

SUMMARY OF NEW LOAD CENTER "LC-D"LOAD CENTER TYPE: TYPE 1A

MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)

SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)

SERVICE CONDUIT TYPE: RMC UNDERGROUND FEED FROM UNDERGROUND SERVICE

LOAD CENTER LOCATION DATA (STATION : 2352+35' OFFSET:52' LT)

LOAD CENTER: NEW SEWARD HWY & O'MALLEY RD (SW)

POWER SOURCE: NEW CEA PROVIDED SERVICE TRANSFORMER AND UNDERGROUND SERVICE

PHOTOELECTRIC CONTROL: YES

SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL

PROVIDE METER SOCKET: YES,200A SOCKET

PANEL MAIN SERVICE DISCONNECT 480V, 2-POLE, 200A

PANEL B MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A

CONTACTOR A: 600V, 10 POLES, 30A

AIC RATING, PANEL D : 10kAIC @480V

PANEL D - 240/480 VAC, 200A BUS

POLE AMPTRIP DESCRIPTION CKT

kVA AѲ BѲ CKTkVA DESCRIPTION AMP

TRIP POLE

1 20/1 LUMINAIRE 102,104 * 0.33 0.43 0.1 CONTROL 15/1 2

3 20/1 LUMINAIRE 107-109 * 0.50 0.83 0.33 LUMINAIRE 103-106 * 20/1 4

5 20/1 LUMINAIRE 1-3 * 0.65 2.37 1.72 LUMINAIRE 8-13 * 20/1 6

7 15/1CABINET TRANSFORMER 240 TO

120V FOR RECEPTACLE, LIGHT ANDHEATER

1 5.00 4EXISTING HIGHTOWER 1* 30/2

8

9 - SPACE 0 4.00 4 10

11 - SPACE 0 0SPACE -

12

13 - SPACE 0 0 14

15 - SPACE 0 0 0 SPACE - 16

17 - SPACE 0 0 0 SPACE - 18

* CIRCUITED THROUGH CONTACTOR A6.80 5.83 TOTAL kVA 12.64

TOTAL AMPS AT 480V 26.3

SHORT CIRCUIT CALCULATION "LC-D"480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.9, 1 ALUMINUM CONDUCTOR

PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C

TRANSFORMER RATING 25kVA

VOLTAGE 240/480V

TRANSFORMER IMPEDANCE 0.012

TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A

LENGTH TO FAULT 60'

SERVICE CONDUCTOR SIZE (3) 1/0 Aluminum Conductors

SERVICE CONDUIT 2" RMC

LINE-LINE FAULT 3178A

ARC FLASH AND SHOCK HAZARD RESULTS "LC-D"ARC FLASH BOUNDARY

INCIDENT ENERGY IN CAL/CM2

WORKING DISTANCE 18 INCHES

SHOCK HAZARD EXPOSURE

INSULATING GLOVES CLASS 00

SHOCK HAZARD

LIMITED APPROACH BOUNDARY 42 INCHES

RESTRICTED APPROACH BOUNDARY 12 INCHES

CALCULATED DATE

Page 11: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

SERVICE: LC-E240/480V, 200A

LUMINAIRE NUMBER, TYP.

Page 12: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

SUMMARY OF NEW LOAD CENTER "LC-E"LOAD CENTER TYPE: TYPE 1A

MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)

SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)

SERVICE CONDUIT TYPE: RMC UNDERGROUND FEED FROM UNDERGROUND SERVICE

LOAD CENTER LOCATION DATA (STATION : 2250+0' , OFFSET: 52.1' RT )

LOAD CENTER: NEW SEWARD HWY & O'MALLEY RD (SE)

POWER SOURCE: NEW CEA PROVIDED SERVICE TRANSFORMER AND UNDERGROUND SERVICE

PHOTOELECTRIC CONTROL: YES

SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL

PROVIDE METER SOCKET: YES, 200A SOCKET

PANEL MAIN SERVICE DISCONNECT 480V, 2-POLE, 200A

CONTACTOR A: 600V, 10 POLES, 30A

AIC RATING, PANEL E: 10kAIC @ 480V

PANEL E - 240/480 VAC, 200A BUS

POLE AMPTRIP DESCRIPTION CKT

kVA AѲ BѲ CKTkVA DESCRIPTION AMP

TRIP POLE

1 20/1 LUMINAIRE 114 * 0.17 0.33 0.17 LUMINAIRES 113&115* 20/1 2

3 20/1 LUMINAIRES 110-112 * 0.50 1.79 1.29 LUMINAIRES 14-19* 20/1 4

5 20/1 LUMINAIRES 4-7 * 0.65 0.75 0.1 CONTROL 15/1 6

7 15/1CABINET TRANSFORMER 240 TO

120V FOR RECEPTACLE, LIGHT ANDHEATER

1 1.00 0 SPACE - 8

9 - SPACE 0 0.00 0 SPACE - 10

11 - SPACE 0 0.00 0 SPACE - 12

1320/2 SPARE

0 0 0SPARE 20/2

14

15 0 0 0 16

17 - SPACE 0 0 0 SPACE - 18

* CIRCUITED THROUGH CONTACTOR A1.08 2.79 PANEL E TOTAL kVA 3.87

PANEL E AMPS AT 480V 8.1

VOLTAGE DROPS - "LC-E"240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC.

TEMPERATURE RATING 75 DEG C

CKT # SEGMENT SEGMENT SIZE(AWG)

SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP

(%VD)CUMULATIVEDROP (%VD)

E-1 E114 TO LC E 8 179 166.67 0.72 0.08 0.08

E-2E115 TO E113 8 201 166.67 0.72 0.09 0.26

E113 TO LC E 8 181 333.33 1.45 0.17 0.17

E-3

E110 &E111 TO E112 8 154 333.33 1.45 0.14 0.66

E112 TO JB 113A 8 77 500.00 2.17 0.11 0.52

JB 113A TO E113 8 124 500.00 2.17 0.17 0.42

E113 TO LC E 8 181 500.00 2.17 0.25 0.25

E-4

E19 TO E18 8 221 215.56 0.94 0.13 3.88

E18 TO E17 8 222 431.11 1.87 0.26 3.75

E17 TO E16 8 236 646.67 2.81 0.42 3.48

E16 TO E15 8 236 862.22 3.75 0.56 3.07

E15 TO E14 8 239 1077.78 4.69 0.71 2.51

E14 TO JB 113A 8 204 1293.33 5.62 0.72 1.80

JB 113A TO E113 8 124 1293.33 5.62 0.44 1.08

E113 TO LC E 8 181 1293.33 5.62 0.64 0.64

E-5

E4 TO E5 8 205 215.56 0.94 0.12 1.06

E5 TO E6 8 230 431.11 1.87 0.27 0.94

E6 TO E7 8 227 646.67 2.81 0.40 0.66

E7 TO LC E 8 111 862.22 3.75 0.26 0.26

SHORT CIRCUIT CALCULATION "LC-E"480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM

CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C

TRANSFORMER RATING 25kVA

VOLTAGE 240/480V

TRANSFORMER IMPEDANCE 1.20%

TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A

LENGTH TO FAULT 60'

SERVICE CONDUCTOR SIZE (3) 1/0 Aluminum

SERVICE CONDUIT 2" RMC

LINE-LINE FAULT 3178A

ARC FLASH AND SHOCK HAZARD RESULTS "LC-E"ARC FLASH BOUNDARY

INCIDENT ENERGY IN CAL/CM2

WORKING DISTANCE 18 INCHES

SHOCK HAZARD EXPOSURE

INSULATING GLOVES CLASS 00

SHOCK HAZARD

LIMITED APPROACH BOUNDARY 42 INCHES

RESTRICTED APPROACH BOUNDARY 12 INCHES

CALCULATED DATE

Page 13: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

SERVICE: LC-F240/480V, 200A

LUMINAIRE NUMBER, TYP.

Page 14: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

SUMMARY OF NEW LOAD CENTER "LC-F"LOAD CENTER TYPE: TYPE 1A

MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)

SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)

SERVICE CONDUIT TYPE: RMC UNDERGROUND FEED FROM UNDERGROUND SERVICE

LOCATION DATA (STATION : 5233+11.78' , OFFSET : 31.54'RT)

LOAD CENTER: BRAYTON DR, NSH OFF RAMP

POWER SOURCE: NEW CEA PROVIDED SERVICE TRANSFORMER AND UNDERGROUND SERVICE

PHOTOELECTRIC CONTROL: YES

SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL

PROVIDE METER SOCKET: YES, 200A SOCKET

PANEL F MAIN SERVICE DISCONNECT 480V, 2-POLE, 200A

CONTACTOR A: 600V, 10 POLES, 30A

AIC RATING, PANEL F: 10kAIC @ 480V

PANEL F - 240/480V,200A BUS

POLE AMPTRIP DESCRIPTION CKT

kVA AѲ BѲ CKTkVA DESCRIPTION AMP

TRIP POLE

1 20/1 LUMINAIRE 20-22 * 0.65 0.75 0.1 CONTROL 15/1 2

3 15/1CABINET TRANSFORMER 240 TO

120V FOR RECEPTACLE, LIGHT ANDHEATER

1 2.51 1.51 LUMINAIRE 23-29 * 20/1 4

5SPACE

0 0.00 0 SPACE - 6

7 0 0 0SPACE -

8

9SPACE

0 0 0 10

11 0 0 0SPACE -

12

13SPACE

0 0 0 14

15 0 0 0SPACE -

16

17 SPACE 0 0 0 18

* CIRCUITED THROUGH CONTACTOR A0.75 2.51 PANEL F TOTAL kVA 3.26

PANEL F AMPS AT 480V 6.8

ARC FLASH AND SHOCK HAZARD RESULTS "LC-F"ARC FLASH BOUNDARY

INCIDENT ENERGY IN CAL/CM2

WORKING DISTANCE 18 INCHES

SHOCK HAZARD EXPOSURE

INSULATING GLOVES CLASS 00

SHOCK HAZARD

LIMITED APPROACH BOUNDARY 42 INCHES

RESTRICTED APPROACH BOUNDARY 12 INCHES

CALCULATED DATE

SHORT CIRCUIT CALCULATION "LC-F"480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM

CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C

TRANSFORMER RATING 25kVA

VOLTAGE 240/480V

TRANSFORMER IMPEDANCE 1.20%

TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A

LENGTH TO FAULT 60'

SERVICE CONDUCTOR SIZE (3) 1/0 Aluminum conductors

SERVICE CONDUIT 2" RMC

LINE-LINE FAULT 3179A

VOLTAGE DROPS "LC-F"240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC.

TEMPERATURE RATING 75 DEG C

CKT # SEGMENT SEGMENT SIZE(AWG)

SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP

(%VD)CUMULATIVEDROP (%VD)

F-1

E20 TO E21 8 196 215.56 0.94 0.12 0.75

E21 TO E22 8 231 431.11 1.87 0.27 0.64

E22 TO LC F 8 206 646.67 2.81 0.36 0.36

F-4

E29 TO E28 8 163 215.56 0.94 0.10 2.80

E28 TO E27 8 226 431.11 1.87 0.27 2.71

E27 TO E26 8 209 646.67 2.81 0.37 2.44

E26 TO E25 8 218 862.22 3.75 0.51 2.07

E25 TO E24 8 217 1077.78 4.69 0.64 1.55

E24 TO E23 8 205 1293.33 5.62 0.73 0.91

E23 TO LC F 8 45 1508.89 6.56 0.19 0.19

Page 15: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

SERVICE: LC-G240/480V, 100A

EXISTING LUMINAIRE , TYP.

EXISTING J BOX, TYP.

Page 16: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

SUMMARY OF NEW LOAD CENTER "LC-G"LOAD CENTER TYPE: TYPE 1A

MAINTENANCE RESPONSIBILITY: MUNICIPALITY OF ANCHORAGE (MOA)

SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)

SERVICE CONDUIT TYPE: RMC UNDERGROUND FEED FROM UNDERGROUND SERVICE

LOAD CENTER LOCATION DATA (STATION : 3316+0' OFFSET : 53.4'LT )

LOAD CENTER: HOMER DR (FROM SCOOTER AVE), SSH ON RAMP

POWER SOURCE: NEW CEA PROVIDED SERVICE TRANSFORMER AND UNDERGROUND SERVICE

PHOTOELECTRIC CONTROL: YES

SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL

PROVIDE METER SOCKET: YES, 100A SOCKET

PANEL MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A

CONTACTOR A: 600V, 10 POLES, 30A

AIC RATING, PANEL G: 10kAIC @ 480V

PANEL G - 240/480 VAC, 100A BUS

POLE AMPTRIP DESCRIPTION CKT

kVA AѲ BѲ CKTkVA DESCRIPTION AMP

TRIP POLE

120/2 5 EXISTING LUMINAIRES*

(SEE NOTE 2)

1.33 1.43 0.1 CONTROL 15/1 2

3 1.33 1.33 0

SPACE 20/2

4

5 15/1CABINET TRANSFORMER 240 TO

120V FOR RECEPTACLE, LIGHT ANDHEATER

1 1 0 6

7 - SPACE 0 0 0SPACE 20/2

8

920/2 SPACE

0 0 0 10

11 0 0 0 SPACE 12

1320/2 SPACE

0 0 0 SPACE 14

15 0 0 0 SPACE 16

17 0 0 SPACE 18

* CIRCUITED THROUGH CONTACTOR A2.43 1.33 PANEL G TOTAL kVA 3.77

PANEL G AMPS AT 480V 7.8

ARC FLASH AND SHOCK HAZARD RESULTS "LC-G"ARC FLASH BOUNDARY

INCIDENT ENERGY IN CAL/CM2

WORKING DISTANCE 18 INCHES

SHOCK HAZARD EXPOSURE

INSULATING GLOVES CLASS 00

SHOCK HAZARD

LIMITED APPROACH BOUNDARY 42 INCHES

RESTRICTED APPROACH BOUNDARY 12 INCHES

CALCULATED DATE

SHORT CIRCUIT CALCULATION "LC-G"480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINIUM

CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C

TRANSFORMER RATING 25kVA

VOLTAGE 240/480V

TRANSFORMER IMPEDANCE 1.20%

TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A

LENGTH TO FAULT 60'

SERVICE CONDUCTOR SIZE (3) 1/0 ALUMINIUM

SERVICE CONDUIT 2" RMC

LINE-LINE FAULT 3178A

VOLTAGE DROPS "LC-G"240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING

75 DEG C

CKT # SEGMENT SEGMENTSIZE (AWG)

SEGMENTLENGTH (FT) LOAD (VA) TOTAL

(AMPS)SEQ. DROP

(%VD)

CUMULATIVE DROP(%VD)

G-1

EXISTING LIGHT POLE 5TO 4 8 221 533.33 1.13 0.08 1.31

EXISTING LIGHT POLE 4TO 3 8 222 1066.67 2.27 0.16 1.23

EXISTING LIGHT POLE 3TO 2 8 219 1600.00 3.40 0.23 1.08

EXISTING LIGHT POLE 2TO 1 8 221 2133.33 4.54 0.31 0.85

EXISTING LIGHT POLE 3TO LC G 8 307 2666.67 5.67 0.54 0.54

Page 17: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

EXISTING SERVICE: LC-H240/480V, 100A

EXISTING JB, TYP.

LUMINAIRE NUMBER, TYP.

Page 18: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

ARC FLASH AND SHOCK HAZARD RESULTS LC-HARC FLASH BOUNDARY

INCIDENT ENERGY IN CAL/CM2

WORKING DISTANCE 18 INCHES

SHOCK HAZARD EXPOSURE

INSULATING GLOVES CLASS 00

SHOCK HAZARD

LIMITED APPROACH BOUNDARY 42 INCHES

RESTRICTED APPROACH BOUNDARY 12 INCHES

CALCULATED DATE

SHORT CIRCUIT CALCULATION LC-H480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM

CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C

TRANSFORMER RATING 25kVA

VOLTAGE 240/480V

TRANSFORMER IMPEDANCE 1.20%

TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A

LENGTH TO FAULT 60'

SERVICE CONDUCTOR SIZE 1/0 Aluminum Conductors

SERVICE CONDUIT 2" RMC

LINE-LINE FAULT 3179A

VOLTAGE DROPS LC-H240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC.

TEMPERATURE RATING 75 DEG C

CKT # SEGMENT SEGMENT SIZE(AWG)

SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP

(%VD)CUMULATIVEDROP (%VD)

H-4

E206 to E204 8 205 183 0.8 0.10 1.85

E204 to E202 8 130 367 1.6 0.13 1.74

E202 to LC-H 8 1070 550 2.4 1.61 1.61

H-6

E207 TO E205 8 115 183 0.8 0.06 2.32

E205 TO E203 8 150 367 1.6 0.15 2.26

E203 TO E201 8 205 551 2.4 0.31 2.11

E201 TO LC-H 8 895 733 3.2 1.80 1.80

SUMMARY OF EXISTING LOAD CENTER LC-HLOAD CENTER TYPE: TYPE 1A

MAINTENANCE RESPONSIBILITY: MUNICIPALITY OF ANCHORAGE (MOA)

SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)

SERVICE CONDUIT TYPE: RMC & PVC

LOAD CENTER LOCATION DATA (61.137236°, -149.863658°, APPROX.)

LOAD CENTER: OLD SEWARD HWY AND SCOOTER AVE, SE

POWER SOURCE: EXISTING 25 kVA CEA PAD-MOUNT SERVICE TRANSFORMER (61.137204°, -149.858690°, APPROX.)(NOTE 2)

PHOTOELECTRIC CONTROL: EXISTING AT LOAD CENTER

SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL

PROVIDE METER SOCKET: EXISTING METER

PANEL H MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A

CONTACTOR A: EXISTING 12-POLE, 30A

AIC RATING, PANEL H: 14 kAIC @ 480V

PANEL H- 240/480 VAC, 100A BUS

POLE AMPTRIP DESCRIPTION CKT

kVA AѲ BѲ CKTkVA DESCRIPTION AMP

TRIP POLE

120/2 L1-L7, ODD *

(LUM'S L1,L3,L5) (L7 REMOVED)

0.43 0.53 0.1 CONTROL 15/1 2

3 0.43 0.98 0.55 E202-E206,EVEN*(LUM'S E202,E204,E206) 20/1 4

520/2 L2-L8, EVEN *

(LUM'S L2,L4,L6) (L8 REMOVED)

0.43 1.16 0.73E201-E207,ODD*

(LUM'S E201, E203,E205,E207)

20/1 6

7 0.43 0.43 0SPARE 20/2

8

920/2 SPARE

0 0 0 10

11 0 0 0 SPACE - 12

1320/2 SPARE

0 0 0 SPACE - 14

15 0 0 0 SPACE - 16

17 - SPACE 0 0 0 SPACE - 18

* CIRCUITED THROUGH CONTACTOR A1.69 1.41 PANEL H TOTAL kVA 3.10

PANEL H AMPS AT 480V 6.5

Page 19: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

SERVICE: LC-I240/480V, 100A

LUMINAIRE NUMBER, TYP.

Page 20: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

VOLTAGE DROPS LC-I240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC.

TEMPERATURE RATING 75 DEG C

CKT # SEGMENT SEGMENT SIZE(AWG)

SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP

(%VD)CUMULATIVEDROP (%VD)

I-1(SEGMENT1)

E214 TO E213 8 280 183 0.8 0.14 0.76

E213 TO E212 8 240 367 1.6 0.24 0.62

E212 TO LC-I 8 150 917 4.0 0.38 0.38

I-1(SEGMENT2)

E208 TO E210 8 170 183 0.8 0.09 0.54

E210 TO E212 8 80 367 1.6 0.08 0.46

E212 TO LC-I 8 150 917 4.0 0.38 0.38

I-3E209 TO E211 8 200 183 0.8 0.10 0.17

E211 TO LC-I 8 65 367 1.6 0.07 0.07

SUMMARY OF NEW LOAD CENTER LC-ILOAD CENTER TYPE: TYPE 1A

MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)

SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)

SERVICE CONDUIT TYPE: RMC & PVC

LOAD CENTER LOCATION DATA (STATION: 3017+12.2, OFFSET: 52.57' RT)

LOAD CENTER: SEWARD HWY AND SCOOTER AVE, SE

POWER SOURCE: NEW CEA PROVIDED SERVICE TRANSFORMER AND UNDERGROUND SERVICE

PHOTOELECTRIC CONTROL: YES

SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL

PROVIDE METER SOCKET: YES, 100A SOCKET

PANEL I MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A

CONTACTOR A: YES, 4-POLE, 30A

AIC RATING, PANEL I: 10 kAIC @ 480V

PANEL I - 240/480 VAC, 100A BUS

POLE AMPTRIP DESCRIPTION CKT

kVA AѲ BѲ CKTkVA DESCRIPTION AMP

TRIP POLE

1 20/1 LUM'SE208,E210,E212,E213,E214* 0.92 0.97 0 SPARE 20/1 2

3 20/1 LUM'S E209,E211* 0.37 1.39 1CABINET TRANSFORMER

240V TO 120V FORRECEPTACLE, LIGHT, PECONTROL AND HEATER

15/1 4

520/2 SPARE

0 0 0 SPARE 20/1 6

7 0 0 0SPARE 20/2

8

920/2 SPARE

0 0 0 10

11 0 0 0 SPACE - 12

1320/2 SPARE

0 0 0 SPACE - 14

15 0 0 0 SPACE - 16

17 - SPACE 0 0 0 SPACE - 18

* CIRCUITED THROUGH CONTACTOR A0.97 1.39 PANEL I TOTAL kVA 2.36

PANEL I AMPS AT 480V 4.9

SHORT CIRCUIT CALCULATION LC-I480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM CONDUCTOR PER PHASE IN

A RMC. TEMPERATURE RATING 75 DEG C

TRANSFORMER RATING 25kVA

VOLTAGE 240/480V

TRANSFORMER IMPEDANCE 1.20%

TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A

LENGTH TO FAULT 60'

SERVICE CONDUCTOR SIZE 1/0 Aluminum Conductors

SERVICE CONDUIT 2" RMC

LINE-LINE FAULT 3179A

Page 21: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

SERVICE: LC-J240/480V, 100A

LUMINAIRE NUMBER, TYP.

Page 22: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

SHORT CIRCUIT CALCULATION LC-J480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM CONDUCTOR PER

PHASE IN A RMC. TEMPERATURE RATING 75 DEG C

TRANSFORMER RATING 25kVA

VOLTAGE 240/480V

TRANSFORMER IMPEDANCE 1.20%

TRANSFORMER LET-THRU SHORT CIRCUITCURRENT (INFINITE BUS) 3389A

LENGTH TO FAULT 60'

SERVICE CONDUCTOR SIZE 1/0 Aluminum Conductors

SERVICE CONDUIT 2" RMC & PVC

LINE-LINE FAULT 3179A

ARC FLASH AND SHOCK HAZARD RESULTS LC-JARC FLASH BOUNDARY

INCIDENT ENERGY IN CAL/CM2

WORKING DISTANCE 18 INCHES

SHOCK HAZARD EXPOSURE

INSULATING GLOVES CLASS 00

SHOCK HAZARD

LIMITED APPROACH BOUNDARY 42 INCHES

RESTRICTED APPROACH BOUNDARY 12 INCHES

CALCULATED DATE

SUMMARY OF NEW LOAD CENTER LC-JLOAD CENTER TYPE: TYPE 1A

MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)

SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)

SERVICE CONDUIT TYPE: RMC & PVC

LOAD CENTER LOCATION DATA (Station: 4204+76.1’ , Offset : 38.2’RT)

LOAD CENTER: SEWARD HWY AND BRAYTON DRIVE, SE

POWER SOURCE: NEW CEA PROVIDED SERVICE TRANSFORMER AND UNDERGROUND SERVICE

PHOTOELECTRIC CONTROL: YES

SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL

PROVIDE METER SOCKET: YES, 100A SOCKET

PANEL J MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A

CONTACTOR A: YES, 4-POLE, 30A

AIC RATING, PANEL J: 10 kAIC @ 480V

PANEL J - 240/480 VAC, 100A BUS

POLE AMPTRIP DESCRIPTION CKT

kVA AѲ BѲ CKTkVA DESCRIPTION AMP

TRIP POLE

1 20/1 LUM'S E40,E41,E42,E43,E44* 1.08 1.18 0.1 CONTROL 15/1 2

3 15/1CABINET TRANSFORMER 240V TO

120V FOR RECEPTACLES, LIGHT, PECONTROL AND HEATER

1 1 0SPARE 20/2

4

520/2 SPARE

0 0 0 6

7 0 0 0SPARE 20/2

8

920/2 SPARE

0 0 0 10

11 0 0 0 SPACE - 12

1320/2 SPARE

0 0 0 SPACE - 14

15 0 0 0 SPACE - 16

17 - SPACE 0 0 0 SPACE - 18

* CIRCUITED THROUGH CONTACTOR A1.18 1 PANEL J TOTAL kVA 2.18

PANEL J AMPS AT 480V 4.5

VOLTAGE DROPS LC-J240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C

CKT # SEGMENT SEGMENT SIZE(AWG)

SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP

(%VD)CUMULATIVEDROP (%VD)

J-1(Segmen

t 1)

E40 TO E41 8 225 216 0.9 0.13 0.54

E41 TO E42 8 200 431 1.9 0.24 0.40

E42 TO LC-J 8 95 647 2.8 0.17 0.17

J-1(Segmen

t 2)

E44 TO E43 8 230 216 0.9 0.14 0.38

E43 TO LC-J 8 205 431 1.9 0.24 0.24

Page 23: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

EXISTING SERVICE: LC-K240/480V, 100A

EXISTING JB, TYP. LUMINAIRE NUMBER, TYP.

Page 24: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

ARC FLASH AND SHOCK HAZARD RESULTS LC-KARC FLASH BOUNDARY

INCIDENT ENERGY IN CAL/CM2

WORKING DISTANCE 18 INCHES

SHOCK HAZARD EXPOSURE

INSULATING GLOVES CLASS 00

SHOCK HAZARD

LIMITED APPROACH BOUNDARY 42 INCHES

RESTRICTED APPROACH BOUNDARY 12 INCHES

CALCULATED DATE

SHORT CIRCUIT CALCULATION LC-K480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM CONDUCTOR PER PHASE IN

A RMC. TEMPERATURE RATING 75 DEG C

TRANSFORMER RATING 25kVA

VOLTAGE 240/480V

TRANSFORMER IMPEDANCE 1.20%

TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A

LENGTH TO FAULT 60'

SERVICE CONDUCTOR SIZE 1/0 Aluminum Conductors

SERVICE CONDUIT 2" RMC

LINE-LINE FAULT 3179A

SUMMARY OF EXISTING LOAD CENTER LC-KLOAD CENTER TYPE: TYPE 1A

MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)

SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)

SERVICE CONDUIT TYPE: RMC & PVC

LOAD CENTER LOCATION DATA (61.144392°, -149.852389°)

LOAD CENTER: DIMOND BLVD AND BRAYTON DR, SE

POWER SOURCE: EXISTING 25 kVA CEA PAD-MOUNT SERVICE TRANSFORMER (61.144381°, -149.852475°, APPROX.)(NOTE 2)

PHOTOELECTRIC CONTROL: EXISTING AT LOAD CENTER

SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL

PROVIDE METER SOCKET: EXISTING METER 144 826 226

PANEL K MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A

CONTACTOR A: 11.7

AIC RATING, PANEL K: 10 kAIC @ 480V

PANEL K - 240/480 VAC, 100A BUS

POLE AMPTRIP DESCRIPTION CKT

kVA AѲ BѲ CKTkVA DESCRIPTION AMP

TRIP POLE

1.0 20/1 LUM'S E51 TO E54* 0.9 0.9 0.0MAIN SERVICE DISCONNECT 100/2

2

3.0 20/1 LUM'S E55 TO E57* 0.6 0.6 0.0 4

5.020/2 LUMINAIRES *

(UNK.)

0.2 0.3 0.1 CONTROL 15/1 6

7.0 0.2 1.1 0.9EAST RAMP LUMINAIRES * 20/2

8

9.020/2 HIGHTOWER #2* (REMOVED)

0.0 0.9 0.9 10

11.0 0.0 0.0 0.0SPARE 20/2

12

13.020/2 LUMINAIRES *

(NB ON RAMP)

0.9 0.9 0.0 14

15.0 0.9 0.9 0.0SPARE 20/2

16

17.0 - SPACE 0.0 0.0 0.0 18

* CIRCUITED THROUGH CONTACTOR A3.0 2.6 PANEL K TOTAL kVA 5.6

PANEL K AMPS AT 480V 11.7

VOLTAGE DROPS LC-K240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C

CKT # SEGMENT SEGMENT SIZE(AWG)

SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP

(%VD)CUMULATIVEDROP (%VD)

K-1

E54 TO E53 6 210 216 0.9 0.08 2.01

E53 TO E52 6 190 431 1.9 0.14 1.93

E52 TO E51 6 240 647 2.8 0.27 1.79

E51 TO LC-K 6 1005 862 3.7 1.52 1.52

K-3

E57 TO E56 6 210 216 0.9 0.08 2.38

E56 TO E55 6 250 431 1.9 0.19 2.30

E55 TO LC-K 6 1865 647 2.8 2.11 2.11

Page 25: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

EXISTING SERVICE LC-L240/480V, 100A EXISTING JB, TYP

LUMINAIRE NUMBER, TYP

Page 26: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

ARC FLASH AND SHOCK HAZARD RESULTS LC-LARC FLASH BOUNDARY

INCIDENT ENERGY IN CAL/CM2

WORKING DISTANCE 18 INCHES

SHOCK HAZARD EXPOSURE

INSULATING GLOVES CLASS 00

SHOCK HAZARD

LIMITED APPROACH BOUNDARY 42 INCHES

RESTRICTED APPROACH BOUNDARY 12 INCHES

CALCULATED DATE

SHORT CIRCUIT CALCULATION LC-L480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM

CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C

TRANSFORMER RATING 25kVA

VOLTAGE 240/480V

TRANSFORMER IMPEDANCE 1.20%

TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A

LENGTH TO FAULT 60'

SERVICE CONDUCTOR SIZE 1/0 Aluminum Conductors

SERVICE CONDUIT 2" RMC

LINE-LINE FAULT 3179A

VOLTAGE DROPS LC-L240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC.

TEMPERATURE RATING 75 DEG C

CKT # SEGMENT SEGMENT SIZE(AWG)

SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP

(%VD)CUMULATIVEDROP (%VD)

L-1

E50 TO E49 6 230 216 0.94 0.09 2.31

E49 TO E48 6 235 431 1.87 0.18 2.23

E48 TO E47 6 245 647 2.81 0.28 2.05

E47 TO E46 6 230 862 3.75 0.35 1.77

E46 TO E45 6 245 1078 4.69 0.46 1.43

E45 TO LC-L 6 425 1293 5.62 0.96 0.96

L-3

E33 TO E34 6 240 216 0.94 0.09 2.96

E34 TO E35 6 235 431 1.87 0.18 2.87

E35 TO E36 6 185 647 2.81 0.21 2.69

E36 TO E37 6 260 862 3.75 0.39 2.48

E37 TO E38 6 230 1078 4.69 0.43 2.09

E38 TO E39 6 230 1293 5.62 0.52 1.66

E39 TO LC-L 6 430 1509 6.56 1.14 1.14

L-17

E31 TO E30 6 125 216 0.94 0.05 3.16

E30 TO E32 6 240 431 1.87 0.18 3.11

E32 TO LC-L 6 2585 647 2.81 2.93 2.93

SUMMARY OF EXISTING LOAD CENTER LC-LLOAD CENTER TYPE: TYPE 1A (STATE OF ALASKA OWNED)

MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)

SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)

SERVICE CONDUIT TYPE: RMC & PVC

LOAD CENTER LOCATION DATA (61.144553°, -149.858410°)

LOAD CENTER: E DIMOND BLVD AND HOMER DR, SW

POWER SOURCE: EXISTING 50 kVA CEA PAD-MOUNT SERVICE TRANSFORMER (61.144514°, -149.858690°) (NOTE 3)

PHOTOELECTRIC CONTROL: EXISTING AT LOAD CENTER

SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL

PROVIDE METER SOCKET: EXISTING METER 144 826 201

PANEL L MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A

CONTACTOR A: EXISTING 8-POLE

AIC RATING, PANEL L: 10 kAIC @ 480V

PANEL L - 240/480 VAC, 100A BUS

POLE AMPTRIP DESCRIPTION CKT

kVA AѲ BѲ CKTkVA DESCRIPTION AMP

TRIP POLE

1 20/1 LUM'S E45 TO E50 * 1.3 1.3 0.0MAIN SERVICE DISCONNECT 100/2

2

3 20/1 LUM'S E33 TO E39* 1.5 1.5 0.0 4

525/2 HIGH TOWER HT03 * (REMOVED)

0.0 0.1 0.1 CONTROL 15/1 6

7 0.0 0.0 0.0 HIGH TOWER HT04 *(REMOVED) 20/2

8

920/2 HIGH TOWER HT01*

(REMOVED)

0.0 0.0 0.0 10

11 0.0 0.0 0.0SPARE 20/2

12

1320/2 HIGH TOWER HT05

(NOTE 2) (REMOVED)

0.0 0.0 0.0 14

15 0.0 0.0 0.0SPARE 20/2

16

17 20/1 LUM'S E30 TO E32 * 0.6 0.6 0.0 18

* CIRCUITED THROUGH CONTACTOR A2.0 1.5 PANEL L TOTAL kVA 3.5

PANEL L AMPS AT 480V 7.4

Page 27: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6

≥ ≥ ≤≤

Page 28: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 29: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 30: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 31: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 32: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 33: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 34: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 35: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6
Page 36: Sheets_Part3.pdf · e104 to lc d 8 65 333.33 1.45 0.06 0.06 d-5 e1 to e2 8 228 215.56 0.94 0.13 0.83 e2 to e3 8 222 431.11 1.87 0.26 0.70 e3 to lc d 8 246 646.67 2.81 0.44 0.44 d-6