SUMMARY OF EXISTING LC-DIMONDLOAD CENTER TYPE: TYPE 2 DUAL-PANEL SINGLE-POLE MOUNTED
MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA) & MUNICIPALITY OF ANCHORAGE (MOA)SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)
SERVICE CONDUIT TYPE: RMC & PVCLOAD CENTER LOCATION DATA (61.144573°, -149.855952°)
LOAD CENTER: NEW SEWARD HWY & DIMOND BLVD (SE)POWER SOURCE: EXISTING 25 kVA CEA PAD-MOUNT SERVICE TRANSFORMER (61.144624°, -149.855861°) (NOTE 2)
PHOTOELECTRIC CONTROL: EXISTING AT LOAD CENTERSERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL
PROVIDE METER SOCKET: EXISTING METERS (136 716 646, SOA) (136 716 645, MOA)PANEL A (SOA) MAIN SERVICE DISCONNECT 480V, 2-POLE, 200APANEL B (MOA) MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A
CONTACTORS A & B: EXISTINGAIC RATING, PANELS A & B: 10 kAIC @ 480V
PANEL A - 240/480 VAC, 200A BUS
POLE AMPTRIP DESCRIPTION CKT
kVA AѲ BѲ CKTkVA DESCRIPTION AMP
TRIP POLE
1 20/2 SPARE (NOTE 3) 0 0 0SPARE 20/2 2
3 0 0 0 45
40/2LUMINAIRES EAST & WEST
OF OVERPASS & UNDERBRIDGE *
1.3 1.3 0SPARE 40/2
67 1.3 1.3 0 89 - SPACE 0 0 0 SPACE 30/1 10
11 - SPACE 0 0 0 SPACE 30/1 1213 - SPACE 0 0 0 SPACE - 1415 - SPACE 0 0 0 SPACE - 1617 - SPACE 0 0 0 SPACE - 18
PANEL B - 240/480 VAC, 100A BUS
POLE AMPTRIP DESCRIPTION CKT
kVA AѲ BѲ CKTkVA DESCRIPTION AMP
TRIP POLE
1 70/1 SPARE 0 0 0 SIGNAL CABINET XFMRPRIMARY(NOTE 4)
40/22
3 70/1 SIGNAL CABINET (NOTE 5) 1.1 1.1 0 4
5 15/1DIMOND/NSH WEST
INTXL**(2 LED, 2HPS)
1.5 1.6 0.1 PEC CONTROL 15/1 6
7 15/1 SPARE 0 0 0 - - 8* CIRCUITED THROUGH CONTACTOR A & TIMER SWITCH
** CIRCUITED THROUGH CONTACTOR B2.9 2.4 TOTAL kVA 5.3
TOTAL AMPS AT 480V 11.0
SHORT CIRCUIT CALCULATION LC-C480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM CONDUCTOR PER PHASE IN A RMC.
TEMPERATURE RATING 75 DEG CTRANSFORMER RATING 25kVA
VOLTAGE 240/480VTRANSFORMER IMPEDANCE 1.20%
TRANSFORMER LET-THRU SHORT CIRCUITCURRENT (INFINITE BUS) 3389A
LENGTH TO FAULT 60'SERVICE CONDUCTOR SIZE 1/0 Aluminum Conductors
SERVICE CONDUIT 2" RMCLINE-LINE FAULT 3179A
ARC FLASH AND SHOCK HAZARD RESULTS LC-DIMONDARC FLASH BOUNDARY
INCIDENT ENERGY IN CAL/CM2WORKING DISTANCE 18 INCHES
SHOCK HAZARD EXPOSUREINSULATING GLOVES CLASS 00
SHOCK HAZARDLIMITED APPROACH BOUNDARY 42 INCHES
RESTRICTED APPROACH BOUNDARY 12 INCHES
CALCULATED DATE
SERVICE: LC-D240/480V, 200A
REUSE EXISTINGCONDUIT & CABLE
LUMINAIRE NUMBER, TYP.
VOLTAGE DROPS "LC-D"240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.9, 1 COPPER CONDUCTOR PER PHASE IN A RMC. TEMPERATURE
RATING 75 DEG C
CKT # SEGMENT SEGMENT SIZE(AWG)
SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP
(%VD)CUMULATIVEDROP (%VD)
D-1E102 TO E104 8 161 166.67 0.72 0.07 0.13
E104 TO LC D 8 65 333.33 1.45 0.06 0.06
D-3E108 &E109 TO E107 8 158 333.33 1.45 0.14 0.33
E107 TO LC D 8 139 500.00 2.17 0.19 0.19
D-4
E103 TO E105 8 154 166.67 0.72 0.07 0.39
E106 TO E105 8 173 166.67 0.72 0.08 0.40
E105 TO E104 8 288 333.33 1.45 0.26 0.32
E104 TO LC D 8 65 333.33 1.45 0.06 0.06
D-5
E1 TO E2 8 228 215.56 0.94 0.13 0.83
E2 TO E3 8 222 431.11 1.87 0.26 0.70
E3 TO LC D 8 246 646.67 2.81 0.44 0.44
D-6
E13 TO E12 6 232 215.56 0.94 0.09 2.93
E12 TO E11 6 232 431.11 1.87 0.18 2.84
E11 TO E10 6 205 646.67 2.81 0.23 2.66
E10 TO E9 6 232 862.22 3.75 0.35 2.43
E9 TO E8 6 226 1077.78 4.69 0.43 2.08
E8 TO E105 6 308 1293.33 5.62 0.70 1.66
E105 TO E104 6 288 1508.89 6.56 0.76 0.96
E104 TO LC D 6 65 1724.44 7.50 0.20 0.20
D-8/10
HT1 TO JB 1A 4 425 8000.00 17.02 0.92 2.90
JB1A TO E1 4 215 8000.00 17.02 0.47 1.98
E1 TO E2 4 228 8000.00 17.02 0.50 1.51
E2 TO E3 4 222 8000.00 17.02 0.48 1.02
E3 TO LC D 4 246 8000.00 17.02 0.53 0.53
SUMMARY OF NEW LOAD CENTER "LC-D"LOAD CENTER TYPE: TYPE 1A
MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)
SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)
SERVICE CONDUIT TYPE: RMC UNDERGROUND FEED FROM UNDERGROUND SERVICE
LOAD CENTER LOCATION DATA (STATION : 2352+35' OFFSET:52' LT)
LOAD CENTER: NEW SEWARD HWY & O'MALLEY RD (SW)
POWER SOURCE: NEW CEA PROVIDED SERVICE TRANSFORMER AND UNDERGROUND SERVICE
PHOTOELECTRIC CONTROL: YES
SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL
PROVIDE METER SOCKET: YES,200A SOCKET
PANEL MAIN SERVICE DISCONNECT 480V, 2-POLE, 200A
PANEL B MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A
CONTACTOR A: 600V, 10 POLES, 30A
AIC RATING, PANEL D : 10kAIC @480V
PANEL D - 240/480 VAC, 200A BUS
POLE AMPTRIP DESCRIPTION CKT
kVA AѲ BѲ CKTkVA DESCRIPTION AMP
TRIP POLE
1 20/1 LUMINAIRE 102,104 * 0.33 0.43 0.1 CONTROL 15/1 2
3 20/1 LUMINAIRE 107-109 * 0.50 0.83 0.33 LUMINAIRE 103-106 * 20/1 4
5 20/1 LUMINAIRE 1-3 * 0.65 2.37 1.72 LUMINAIRE 8-13 * 20/1 6
7 15/1CABINET TRANSFORMER 240 TO
120V FOR RECEPTACLE, LIGHT ANDHEATER
1 5.00 4EXISTING HIGHTOWER 1* 30/2
8
9 - SPACE 0 4.00 4 10
11 - SPACE 0 0SPACE -
12
13 - SPACE 0 0 14
15 - SPACE 0 0 0 SPACE - 16
17 - SPACE 0 0 0 SPACE - 18
* CIRCUITED THROUGH CONTACTOR A6.80 5.83 TOTAL kVA 12.64
TOTAL AMPS AT 480V 26.3
SHORT CIRCUIT CALCULATION "LC-D"480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.9, 1 ALUMINUM CONDUCTOR
PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C
TRANSFORMER RATING 25kVA
VOLTAGE 240/480V
TRANSFORMER IMPEDANCE 0.012
TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A
LENGTH TO FAULT 60'
SERVICE CONDUCTOR SIZE (3) 1/0 Aluminum Conductors
SERVICE CONDUIT 2" RMC
LINE-LINE FAULT 3178A
ARC FLASH AND SHOCK HAZARD RESULTS "LC-D"ARC FLASH BOUNDARY
INCIDENT ENERGY IN CAL/CM2
WORKING DISTANCE 18 INCHES
SHOCK HAZARD EXPOSURE
INSULATING GLOVES CLASS 00
SHOCK HAZARD
LIMITED APPROACH BOUNDARY 42 INCHES
RESTRICTED APPROACH BOUNDARY 12 INCHES
CALCULATED DATE
SERVICE: LC-E240/480V, 200A
LUMINAIRE NUMBER, TYP.
SUMMARY OF NEW LOAD CENTER "LC-E"LOAD CENTER TYPE: TYPE 1A
MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)
SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)
SERVICE CONDUIT TYPE: RMC UNDERGROUND FEED FROM UNDERGROUND SERVICE
LOAD CENTER LOCATION DATA (STATION : 2250+0' , OFFSET: 52.1' RT )
LOAD CENTER: NEW SEWARD HWY & O'MALLEY RD (SE)
POWER SOURCE: NEW CEA PROVIDED SERVICE TRANSFORMER AND UNDERGROUND SERVICE
PHOTOELECTRIC CONTROL: YES
SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL
PROVIDE METER SOCKET: YES, 200A SOCKET
PANEL MAIN SERVICE DISCONNECT 480V, 2-POLE, 200A
CONTACTOR A: 600V, 10 POLES, 30A
AIC RATING, PANEL E: 10kAIC @ 480V
PANEL E - 240/480 VAC, 200A BUS
POLE AMPTRIP DESCRIPTION CKT
kVA AѲ BѲ CKTkVA DESCRIPTION AMP
TRIP POLE
1 20/1 LUMINAIRE 114 * 0.17 0.33 0.17 LUMINAIRES 113&115* 20/1 2
3 20/1 LUMINAIRES 110-112 * 0.50 1.79 1.29 LUMINAIRES 14-19* 20/1 4
5 20/1 LUMINAIRES 4-7 * 0.65 0.75 0.1 CONTROL 15/1 6
7 15/1CABINET TRANSFORMER 240 TO
120V FOR RECEPTACLE, LIGHT ANDHEATER
1 1.00 0 SPACE - 8
9 - SPACE 0 0.00 0 SPACE - 10
11 - SPACE 0 0.00 0 SPACE - 12
1320/2 SPARE
0 0 0SPARE 20/2
14
15 0 0 0 16
17 - SPACE 0 0 0 SPACE - 18
* CIRCUITED THROUGH CONTACTOR A1.08 2.79 PANEL E TOTAL kVA 3.87
PANEL E AMPS AT 480V 8.1
VOLTAGE DROPS - "LC-E"240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC.
TEMPERATURE RATING 75 DEG C
CKT # SEGMENT SEGMENT SIZE(AWG)
SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP
(%VD)CUMULATIVEDROP (%VD)
E-1 E114 TO LC E 8 179 166.67 0.72 0.08 0.08
E-2E115 TO E113 8 201 166.67 0.72 0.09 0.26
E113 TO LC E 8 181 333.33 1.45 0.17 0.17
E-3
E110 &E111 TO E112 8 154 333.33 1.45 0.14 0.66
E112 TO JB 113A 8 77 500.00 2.17 0.11 0.52
JB 113A TO E113 8 124 500.00 2.17 0.17 0.42
E113 TO LC E 8 181 500.00 2.17 0.25 0.25
E-4
E19 TO E18 8 221 215.56 0.94 0.13 3.88
E18 TO E17 8 222 431.11 1.87 0.26 3.75
E17 TO E16 8 236 646.67 2.81 0.42 3.48
E16 TO E15 8 236 862.22 3.75 0.56 3.07
E15 TO E14 8 239 1077.78 4.69 0.71 2.51
E14 TO JB 113A 8 204 1293.33 5.62 0.72 1.80
JB 113A TO E113 8 124 1293.33 5.62 0.44 1.08
E113 TO LC E 8 181 1293.33 5.62 0.64 0.64
E-5
E4 TO E5 8 205 215.56 0.94 0.12 1.06
E5 TO E6 8 230 431.11 1.87 0.27 0.94
E6 TO E7 8 227 646.67 2.81 0.40 0.66
E7 TO LC E 8 111 862.22 3.75 0.26 0.26
SHORT CIRCUIT CALCULATION "LC-E"480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM
CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C
TRANSFORMER RATING 25kVA
VOLTAGE 240/480V
TRANSFORMER IMPEDANCE 1.20%
TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A
LENGTH TO FAULT 60'
SERVICE CONDUCTOR SIZE (3) 1/0 Aluminum
SERVICE CONDUIT 2" RMC
LINE-LINE FAULT 3178A
ARC FLASH AND SHOCK HAZARD RESULTS "LC-E"ARC FLASH BOUNDARY
INCIDENT ENERGY IN CAL/CM2
WORKING DISTANCE 18 INCHES
SHOCK HAZARD EXPOSURE
INSULATING GLOVES CLASS 00
SHOCK HAZARD
LIMITED APPROACH BOUNDARY 42 INCHES
RESTRICTED APPROACH BOUNDARY 12 INCHES
CALCULATED DATE
SERVICE: LC-F240/480V, 200A
LUMINAIRE NUMBER, TYP.
SUMMARY OF NEW LOAD CENTER "LC-F"LOAD CENTER TYPE: TYPE 1A
MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)
SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)
SERVICE CONDUIT TYPE: RMC UNDERGROUND FEED FROM UNDERGROUND SERVICE
LOCATION DATA (STATION : 5233+11.78' , OFFSET : 31.54'RT)
LOAD CENTER: BRAYTON DR, NSH OFF RAMP
POWER SOURCE: NEW CEA PROVIDED SERVICE TRANSFORMER AND UNDERGROUND SERVICE
PHOTOELECTRIC CONTROL: YES
SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL
PROVIDE METER SOCKET: YES, 200A SOCKET
PANEL F MAIN SERVICE DISCONNECT 480V, 2-POLE, 200A
CONTACTOR A: 600V, 10 POLES, 30A
AIC RATING, PANEL F: 10kAIC @ 480V
PANEL F - 240/480V,200A BUS
POLE AMPTRIP DESCRIPTION CKT
kVA AѲ BѲ CKTkVA DESCRIPTION AMP
TRIP POLE
1 20/1 LUMINAIRE 20-22 * 0.65 0.75 0.1 CONTROL 15/1 2
3 15/1CABINET TRANSFORMER 240 TO
120V FOR RECEPTACLE, LIGHT ANDHEATER
1 2.51 1.51 LUMINAIRE 23-29 * 20/1 4
5SPACE
0 0.00 0 SPACE - 6
7 0 0 0SPACE -
8
9SPACE
0 0 0 10
11 0 0 0SPACE -
12
13SPACE
0 0 0 14
15 0 0 0SPACE -
16
17 SPACE 0 0 0 18
* CIRCUITED THROUGH CONTACTOR A0.75 2.51 PANEL F TOTAL kVA 3.26
PANEL F AMPS AT 480V 6.8
ARC FLASH AND SHOCK HAZARD RESULTS "LC-F"ARC FLASH BOUNDARY
INCIDENT ENERGY IN CAL/CM2
WORKING DISTANCE 18 INCHES
SHOCK HAZARD EXPOSURE
INSULATING GLOVES CLASS 00
SHOCK HAZARD
LIMITED APPROACH BOUNDARY 42 INCHES
RESTRICTED APPROACH BOUNDARY 12 INCHES
CALCULATED DATE
SHORT CIRCUIT CALCULATION "LC-F"480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM
CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C
TRANSFORMER RATING 25kVA
VOLTAGE 240/480V
TRANSFORMER IMPEDANCE 1.20%
TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A
LENGTH TO FAULT 60'
SERVICE CONDUCTOR SIZE (3) 1/0 Aluminum conductors
SERVICE CONDUIT 2" RMC
LINE-LINE FAULT 3179A
VOLTAGE DROPS "LC-F"240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC.
TEMPERATURE RATING 75 DEG C
CKT # SEGMENT SEGMENT SIZE(AWG)
SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP
(%VD)CUMULATIVEDROP (%VD)
F-1
E20 TO E21 8 196 215.56 0.94 0.12 0.75
E21 TO E22 8 231 431.11 1.87 0.27 0.64
E22 TO LC F 8 206 646.67 2.81 0.36 0.36
F-4
E29 TO E28 8 163 215.56 0.94 0.10 2.80
E28 TO E27 8 226 431.11 1.87 0.27 2.71
E27 TO E26 8 209 646.67 2.81 0.37 2.44
E26 TO E25 8 218 862.22 3.75 0.51 2.07
E25 TO E24 8 217 1077.78 4.69 0.64 1.55
E24 TO E23 8 205 1293.33 5.62 0.73 0.91
E23 TO LC F 8 45 1508.89 6.56 0.19 0.19
SERVICE: LC-G240/480V, 100A
EXISTING LUMINAIRE , TYP.
EXISTING J BOX, TYP.
SUMMARY OF NEW LOAD CENTER "LC-G"LOAD CENTER TYPE: TYPE 1A
MAINTENANCE RESPONSIBILITY: MUNICIPALITY OF ANCHORAGE (MOA)
SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)
SERVICE CONDUIT TYPE: RMC UNDERGROUND FEED FROM UNDERGROUND SERVICE
LOAD CENTER LOCATION DATA (STATION : 3316+0' OFFSET : 53.4'LT )
LOAD CENTER: HOMER DR (FROM SCOOTER AVE), SSH ON RAMP
POWER SOURCE: NEW CEA PROVIDED SERVICE TRANSFORMER AND UNDERGROUND SERVICE
PHOTOELECTRIC CONTROL: YES
SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL
PROVIDE METER SOCKET: YES, 100A SOCKET
PANEL MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A
CONTACTOR A: 600V, 10 POLES, 30A
AIC RATING, PANEL G: 10kAIC @ 480V
PANEL G - 240/480 VAC, 100A BUS
POLE AMPTRIP DESCRIPTION CKT
kVA AѲ BѲ CKTkVA DESCRIPTION AMP
TRIP POLE
120/2 5 EXISTING LUMINAIRES*
(SEE NOTE 2)
1.33 1.43 0.1 CONTROL 15/1 2
3 1.33 1.33 0
SPACE 20/2
4
5 15/1CABINET TRANSFORMER 240 TO
120V FOR RECEPTACLE, LIGHT ANDHEATER
1 1 0 6
7 - SPACE 0 0 0SPACE 20/2
8
920/2 SPACE
0 0 0 10
11 0 0 0 SPACE 12
1320/2 SPACE
0 0 0 SPACE 14
15 0 0 0 SPACE 16
17 0 0 SPACE 18
* CIRCUITED THROUGH CONTACTOR A2.43 1.33 PANEL G TOTAL kVA 3.77
PANEL G AMPS AT 480V 7.8
ARC FLASH AND SHOCK HAZARD RESULTS "LC-G"ARC FLASH BOUNDARY
INCIDENT ENERGY IN CAL/CM2
WORKING DISTANCE 18 INCHES
SHOCK HAZARD EXPOSURE
INSULATING GLOVES CLASS 00
SHOCK HAZARD
LIMITED APPROACH BOUNDARY 42 INCHES
RESTRICTED APPROACH BOUNDARY 12 INCHES
CALCULATED DATE
SHORT CIRCUIT CALCULATION "LC-G"480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINIUM
CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C
TRANSFORMER RATING 25kVA
VOLTAGE 240/480V
TRANSFORMER IMPEDANCE 1.20%
TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A
LENGTH TO FAULT 60'
SERVICE CONDUCTOR SIZE (3) 1/0 ALUMINIUM
SERVICE CONDUIT 2" RMC
LINE-LINE FAULT 3178A
VOLTAGE DROPS "LC-G"240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING
75 DEG C
CKT # SEGMENT SEGMENTSIZE (AWG)
SEGMENTLENGTH (FT) LOAD (VA) TOTAL
(AMPS)SEQ. DROP
(%VD)
CUMULATIVE DROP(%VD)
G-1
EXISTING LIGHT POLE 5TO 4 8 221 533.33 1.13 0.08 1.31
EXISTING LIGHT POLE 4TO 3 8 222 1066.67 2.27 0.16 1.23
EXISTING LIGHT POLE 3TO 2 8 219 1600.00 3.40 0.23 1.08
EXISTING LIGHT POLE 2TO 1 8 221 2133.33 4.54 0.31 0.85
EXISTING LIGHT POLE 3TO LC G 8 307 2666.67 5.67 0.54 0.54
EXISTING SERVICE: LC-H240/480V, 100A
EXISTING JB, TYP.
LUMINAIRE NUMBER, TYP.
ARC FLASH AND SHOCK HAZARD RESULTS LC-HARC FLASH BOUNDARY
INCIDENT ENERGY IN CAL/CM2
WORKING DISTANCE 18 INCHES
SHOCK HAZARD EXPOSURE
INSULATING GLOVES CLASS 00
SHOCK HAZARD
LIMITED APPROACH BOUNDARY 42 INCHES
RESTRICTED APPROACH BOUNDARY 12 INCHES
CALCULATED DATE
SHORT CIRCUIT CALCULATION LC-H480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM
CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C
TRANSFORMER RATING 25kVA
VOLTAGE 240/480V
TRANSFORMER IMPEDANCE 1.20%
TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A
LENGTH TO FAULT 60'
SERVICE CONDUCTOR SIZE 1/0 Aluminum Conductors
SERVICE CONDUIT 2" RMC
LINE-LINE FAULT 3179A
VOLTAGE DROPS LC-H240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC.
TEMPERATURE RATING 75 DEG C
CKT # SEGMENT SEGMENT SIZE(AWG)
SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP
(%VD)CUMULATIVEDROP (%VD)
H-4
E206 to E204 8 205 183 0.8 0.10 1.85
E204 to E202 8 130 367 1.6 0.13 1.74
E202 to LC-H 8 1070 550 2.4 1.61 1.61
H-6
E207 TO E205 8 115 183 0.8 0.06 2.32
E205 TO E203 8 150 367 1.6 0.15 2.26
E203 TO E201 8 205 551 2.4 0.31 2.11
E201 TO LC-H 8 895 733 3.2 1.80 1.80
SUMMARY OF EXISTING LOAD CENTER LC-HLOAD CENTER TYPE: TYPE 1A
MAINTENANCE RESPONSIBILITY: MUNICIPALITY OF ANCHORAGE (MOA)
SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)
SERVICE CONDUIT TYPE: RMC & PVC
LOAD CENTER LOCATION DATA (61.137236°, -149.863658°, APPROX.)
LOAD CENTER: OLD SEWARD HWY AND SCOOTER AVE, SE
POWER SOURCE: EXISTING 25 kVA CEA PAD-MOUNT SERVICE TRANSFORMER (61.137204°, -149.858690°, APPROX.)(NOTE 2)
PHOTOELECTRIC CONTROL: EXISTING AT LOAD CENTER
SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL
PROVIDE METER SOCKET: EXISTING METER
PANEL H MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A
CONTACTOR A: EXISTING 12-POLE, 30A
AIC RATING, PANEL H: 14 kAIC @ 480V
PANEL H- 240/480 VAC, 100A BUS
POLE AMPTRIP DESCRIPTION CKT
kVA AѲ BѲ CKTkVA DESCRIPTION AMP
TRIP POLE
120/2 L1-L7, ODD *
(LUM'S L1,L3,L5) (L7 REMOVED)
0.43 0.53 0.1 CONTROL 15/1 2
3 0.43 0.98 0.55 E202-E206,EVEN*(LUM'S E202,E204,E206) 20/1 4
520/2 L2-L8, EVEN *
(LUM'S L2,L4,L6) (L8 REMOVED)
0.43 1.16 0.73E201-E207,ODD*
(LUM'S E201, E203,E205,E207)
20/1 6
7 0.43 0.43 0SPARE 20/2
8
920/2 SPARE
0 0 0 10
11 0 0 0 SPACE - 12
1320/2 SPARE
0 0 0 SPACE - 14
15 0 0 0 SPACE - 16
17 - SPACE 0 0 0 SPACE - 18
* CIRCUITED THROUGH CONTACTOR A1.69 1.41 PANEL H TOTAL kVA 3.10
PANEL H AMPS AT 480V 6.5
SERVICE: LC-I240/480V, 100A
LUMINAIRE NUMBER, TYP.
VOLTAGE DROPS LC-I240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC.
TEMPERATURE RATING 75 DEG C
CKT # SEGMENT SEGMENT SIZE(AWG)
SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP
(%VD)CUMULATIVEDROP (%VD)
I-1(SEGMENT1)
E214 TO E213 8 280 183 0.8 0.14 0.76
E213 TO E212 8 240 367 1.6 0.24 0.62
E212 TO LC-I 8 150 917 4.0 0.38 0.38
I-1(SEGMENT2)
E208 TO E210 8 170 183 0.8 0.09 0.54
E210 TO E212 8 80 367 1.6 0.08 0.46
E212 TO LC-I 8 150 917 4.0 0.38 0.38
I-3E209 TO E211 8 200 183 0.8 0.10 0.17
E211 TO LC-I 8 65 367 1.6 0.07 0.07
SUMMARY OF NEW LOAD CENTER LC-ILOAD CENTER TYPE: TYPE 1A
MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)
SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)
SERVICE CONDUIT TYPE: RMC & PVC
LOAD CENTER LOCATION DATA (STATION: 3017+12.2, OFFSET: 52.57' RT)
LOAD CENTER: SEWARD HWY AND SCOOTER AVE, SE
POWER SOURCE: NEW CEA PROVIDED SERVICE TRANSFORMER AND UNDERGROUND SERVICE
PHOTOELECTRIC CONTROL: YES
SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL
PROVIDE METER SOCKET: YES, 100A SOCKET
PANEL I MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A
CONTACTOR A: YES, 4-POLE, 30A
AIC RATING, PANEL I: 10 kAIC @ 480V
PANEL I - 240/480 VAC, 100A BUS
POLE AMPTRIP DESCRIPTION CKT
kVA AѲ BѲ CKTkVA DESCRIPTION AMP
TRIP POLE
1 20/1 LUM'SE208,E210,E212,E213,E214* 0.92 0.97 0 SPARE 20/1 2
3 20/1 LUM'S E209,E211* 0.37 1.39 1CABINET TRANSFORMER
240V TO 120V FORRECEPTACLE, LIGHT, PECONTROL AND HEATER
15/1 4
520/2 SPARE
0 0 0 SPARE 20/1 6
7 0 0 0SPARE 20/2
8
920/2 SPARE
0 0 0 10
11 0 0 0 SPACE - 12
1320/2 SPARE
0 0 0 SPACE - 14
15 0 0 0 SPACE - 16
17 - SPACE 0 0 0 SPACE - 18
* CIRCUITED THROUGH CONTACTOR A0.97 1.39 PANEL I TOTAL kVA 2.36
PANEL I AMPS AT 480V 4.9
SHORT CIRCUIT CALCULATION LC-I480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM CONDUCTOR PER PHASE IN
A RMC. TEMPERATURE RATING 75 DEG C
TRANSFORMER RATING 25kVA
VOLTAGE 240/480V
TRANSFORMER IMPEDANCE 1.20%
TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A
LENGTH TO FAULT 60'
SERVICE CONDUCTOR SIZE 1/0 Aluminum Conductors
SERVICE CONDUIT 2" RMC
LINE-LINE FAULT 3179A
SERVICE: LC-J240/480V, 100A
LUMINAIRE NUMBER, TYP.
SHORT CIRCUIT CALCULATION LC-J480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM CONDUCTOR PER
PHASE IN A RMC. TEMPERATURE RATING 75 DEG C
TRANSFORMER RATING 25kVA
VOLTAGE 240/480V
TRANSFORMER IMPEDANCE 1.20%
TRANSFORMER LET-THRU SHORT CIRCUITCURRENT (INFINITE BUS) 3389A
LENGTH TO FAULT 60'
SERVICE CONDUCTOR SIZE 1/0 Aluminum Conductors
SERVICE CONDUIT 2" RMC & PVC
LINE-LINE FAULT 3179A
ARC FLASH AND SHOCK HAZARD RESULTS LC-JARC FLASH BOUNDARY
INCIDENT ENERGY IN CAL/CM2
WORKING DISTANCE 18 INCHES
SHOCK HAZARD EXPOSURE
INSULATING GLOVES CLASS 00
SHOCK HAZARD
LIMITED APPROACH BOUNDARY 42 INCHES
RESTRICTED APPROACH BOUNDARY 12 INCHES
CALCULATED DATE
SUMMARY OF NEW LOAD CENTER LC-JLOAD CENTER TYPE: TYPE 1A
MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)
SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)
SERVICE CONDUIT TYPE: RMC & PVC
LOAD CENTER LOCATION DATA (Station: 4204+76.1’ , Offset : 38.2’RT)
LOAD CENTER: SEWARD HWY AND BRAYTON DRIVE, SE
POWER SOURCE: NEW CEA PROVIDED SERVICE TRANSFORMER AND UNDERGROUND SERVICE
PHOTOELECTRIC CONTROL: YES
SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL
PROVIDE METER SOCKET: YES, 100A SOCKET
PANEL J MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A
CONTACTOR A: YES, 4-POLE, 30A
AIC RATING, PANEL J: 10 kAIC @ 480V
PANEL J - 240/480 VAC, 100A BUS
POLE AMPTRIP DESCRIPTION CKT
kVA AѲ BѲ CKTkVA DESCRIPTION AMP
TRIP POLE
1 20/1 LUM'S E40,E41,E42,E43,E44* 1.08 1.18 0.1 CONTROL 15/1 2
3 15/1CABINET TRANSFORMER 240V TO
120V FOR RECEPTACLES, LIGHT, PECONTROL AND HEATER
1 1 0SPARE 20/2
4
520/2 SPARE
0 0 0 6
7 0 0 0SPARE 20/2
8
920/2 SPARE
0 0 0 10
11 0 0 0 SPACE - 12
1320/2 SPARE
0 0 0 SPACE - 14
15 0 0 0 SPACE - 16
17 - SPACE 0 0 0 SPACE - 18
* CIRCUITED THROUGH CONTACTOR A1.18 1 PANEL J TOTAL kVA 2.18
PANEL J AMPS AT 480V 4.5
VOLTAGE DROPS LC-J240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C
CKT # SEGMENT SEGMENT SIZE(AWG)
SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP
(%VD)CUMULATIVEDROP (%VD)
J-1(Segmen
t 1)
E40 TO E41 8 225 216 0.9 0.13 0.54
E41 TO E42 8 200 431 1.9 0.24 0.40
E42 TO LC-J 8 95 647 2.8 0.17 0.17
J-1(Segmen
t 2)
E44 TO E43 8 230 216 0.9 0.14 0.38
E43 TO LC-J 8 205 431 1.9 0.24 0.24
EXISTING SERVICE: LC-K240/480V, 100A
EXISTING JB, TYP. LUMINAIRE NUMBER, TYP.
ARC FLASH AND SHOCK HAZARD RESULTS LC-KARC FLASH BOUNDARY
INCIDENT ENERGY IN CAL/CM2
WORKING DISTANCE 18 INCHES
SHOCK HAZARD EXPOSURE
INSULATING GLOVES CLASS 00
SHOCK HAZARD
LIMITED APPROACH BOUNDARY 42 INCHES
RESTRICTED APPROACH BOUNDARY 12 INCHES
CALCULATED DATE
SHORT CIRCUIT CALCULATION LC-K480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM CONDUCTOR PER PHASE IN
A RMC. TEMPERATURE RATING 75 DEG C
TRANSFORMER RATING 25kVA
VOLTAGE 240/480V
TRANSFORMER IMPEDANCE 1.20%
TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A
LENGTH TO FAULT 60'
SERVICE CONDUCTOR SIZE 1/0 Aluminum Conductors
SERVICE CONDUIT 2" RMC
LINE-LINE FAULT 3179A
SUMMARY OF EXISTING LOAD CENTER LC-KLOAD CENTER TYPE: TYPE 1A
MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)
SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)
SERVICE CONDUIT TYPE: RMC & PVC
LOAD CENTER LOCATION DATA (61.144392°, -149.852389°)
LOAD CENTER: DIMOND BLVD AND BRAYTON DR, SE
POWER SOURCE: EXISTING 25 kVA CEA PAD-MOUNT SERVICE TRANSFORMER (61.144381°, -149.852475°, APPROX.)(NOTE 2)
PHOTOELECTRIC CONTROL: EXISTING AT LOAD CENTER
SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL
PROVIDE METER SOCKET: EXISTING METER 144 826 226
PANEL K MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A
CONTACTOR A: 11.7
AIC RATING, PANEL K: 10 kAIC @ 480V
PANEL K - 240/480 VAC, 100A BUS
POLE AMPTRIP DESCRIPTION CKT
kVA AѲ BѲ CKTkVA DESCRIPTION AMP
TRIP POLE
1.0 20/1 LUM'S E51 TO E54* 0.9 0.9 0.0MAIN SERVICE DISCONNECT 100/2
2
3.0 20/1 LUM'S E55 TO E57* 0.6 0.6 0.0 4
5.020/2 LUMINAIRES *
(UNK.)
0.2 0.3 0.1 CONTROL 15/1 6
7.0 0.2 1.1 0.9EAST RAMP LUMINAIRES * 20/2
8
9.020/2 HIGHTOWER #2* (REMOVED)
0.0 0.9 0.9 10
11.0 0.0 0.0 0.0SPARE 20/2
12
13.020/2 LUMINAIRES *
(NB ON RAMP)
0.9 0.9 0.0 14
15.0 0.9 0.9 0.0SPARE 20/2
16
17.0 - SPACE 0.0 0.0 0.0 18
* CIRCUITED THROUGH CONTACTOR A3.0 2.6 PANEL K TOTAL kVA 5.6
PANEL K AMPS AT 480V 11.7
VOLTAGE DROPS LC-K240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C
CKT # SEGMENT SEGMENT SIZE(AWG)
SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP
(%VD)CUMULATIVEDROP (%VD)
K-1
E54 TO E53 6 210 216 0.9 0.08 2.01
E53 TO E52 6 190 431 1.9 0.14 1.93
E52 TO E51 6 240 647 2.8 0.27 1.79
E51 TO LC-K 6 1005 862 3.7 1.52 1.52
K-3
E57 TO E56 6 210 216 0.9 0.08 2.38
E56 TO E55 6 250 431 1.9 0.19 2.30
E55 TO LC-K 6 1865 647 2.8 2.11 2.11
EXISTING SERVICE LC-L240/480V, 100A EXISTING JB, TYP
LUMINAIRE NUMBER, TYP
ARC FLASH AND SHOCK HAZARD RESULTS LC-LARC FLASH BOUNDARY
INCIDENT ENERGY IN CAL/CM2
WORKING DISTANCE 18 INCHES
SHOCK HAZARD EXPOSURE
INSULATING GLOVES CLASS 00
SHOCK HAZARD
LIMITED APPROACH BOUNDARY 42 INCHES
RESTRICTED APPROACH BOUNDARY 12 INCHES
CALCULATED DATE
SHORT CIRCUIT CALCULATION LC-L480V IN A 1-PH, 3W CONFIGURATION WITH A POWER-FACTOR OF 0.90, 1 ALUMINUM
CONDUCTOR PER PHASE IN A RMC. TEMPERATURE RATING 75 DEG C
TRANSFORMER RATING 25kVA
VOLTAGE 240/480V
TRANSFORMER IMPEDANCE 1.20%
TRANSFORMER LET-THRU SHORT CIRCUIT CURRENT(INFINITE BUS) 3389A
LENGTH TO FAULT 60'
SERVICE CONDUCTOR SIZE 1/0 Aluminum Conductors
SERVICE CONDUIT 2" RMC
LINE-LINE FAULT 3179A
VOLTAGE DROPS LC-L240V IN A 1-PH, 2W CONFIGURATION WITH A POWER FACTOR OF 0.90, 1 COPPER CONDUCTOR PER PHASE IN A RMC.
TEMPERATURE RATING 75 DEG C
CKT # SEGMENT SEGMENT SIZE(AWG)
SEGMENTLENGTH (FT) LOAD (VA) TOTAL (AMPS) SEQ. DROP
(%VD)CUMULATIVEDROP (%VD)
L-1
E50 TO E49 6 230 216 0.94 0.09 2.31
E49 TO E48 6 235 431 1.87 0.18 2.23
E48 TO E47 6 245 647 2.81 0.28 2.05
E47 TO E46 6 230 862 3.75 0.35 1.77
E46 TO E45 6 245 1078 4.69 0.46 1.43
E45 TO LC-L 6 425 1293 5.62 0.96 0.96
L-3
E33 TO E34 6 240 216 0.94 0.09 2.96
E34 TO E35 6 235 431 1.87 0.18 2.87
E35 TO E36 6 185 647 2.81 0.21 2.69
E36 TO E37 6 260 862 3.75 0.39 2.48
E37 TO E38 6 230 1078 4.69 0.43 2.09
E38 TO E39 6 230 1293 5.62 0.52 1.66
E39 TO LC-L 6 430 1509 6.56 1.14 1.14
L-17
E31 TO E30 6 125 216 0.94 0.05 3.16
E30 TO E32 6 240 431 1.87 0.18 3.11
E32 TO LC-L 6 2585 647 2.81 2.93 2.93
SUMMARY OF EXISTING LOAD CENTER LC-LLOAD CENTER TYPE: TYPE 1A (STATE OF ALASKA OWNED)
MAINTENANCE RESPONSIBILITY: STATE OF ALASKA (SOA)
SERVING UTILITY: CHUGACH ELECTRIC ASSOCIATION (CEA)
SERVICE CONDUIT TYPE: RMC & PVC
LOAD CENTER LOCATION DATA (61.144553°, -149.858410°)
LOAD CENTER: E DIMOND BLVD AND HOMER DR, SW
POWER SOURCE: EXISTING 50 kVA CEA PAD-MOUNT SERVICE TRANSFORMER (61.144514°, -149.858690°) (NOTE 3)
PHOTOELECTRIC CONTROL: EXISTING AT LOAD CENTER
SERVICE VOLTAGE: 1-PHASE, 3-WIRE, 240/480 VOLTS AC WITH GROUNDED NEUTRAL
PROVIDE METER SOCKET: EXISTING METER 144 826 201
PANEL L MAIN SERVICE DISCONNECT 480V, 2-POLE, 100A
CONTACTOR A: EXISTING 8-POLE
AIC RATING, PANEL L: 10 kAIC @ 480V
PANEL L - 240/480 VAC, 100A BUS
POLE AMPTRIP DESCRIPTION CKT
kVA AѲ BѲ CKTkVA DESCRIPTION AMP
TRIP POLE
1 20/1 LUM'S E45 TO E50 * 1.3 1.3 0.0MAIN SERVICE DISCONNECT 100/2
2
3 20/1 LUM'S E33 TO E39* 1.5 1.5 0.0 4
525/2 HIGH TOWER HT03 * (REMOVED)
0.0 0.1 0.1 CONTROL 15/1 6
7 0.0 0.0 0.0 HIGH TOWER HT04 *(REMOVED) 20/2
8
920/2 HIGH TOWER HT01*
(REMOVED)
0.0 0.0 0.0 10
11 0.0 0.0 0.0SPARE 20/2
12
1320/2 HIGH TOWER HT05
(NOTE 2) (REMOVED)
0.0 0.0 0.0 14
15 0.0 0.0 0.0SPARE 20/2
16
17 20/1 LUM'S E30 TO E32 * 0.6 0.6 0.0 18
* CIRCUITED THROUGH CONTACTOR A2.0 1.5 PANEL L TOTAL kVA 3.5
PANEL L AMPS AT 480V 7.4
≥ ≥ ≤≤