SPLIT-TYPE, AIR CONDITIONERS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS CONTENTS 1. TECHNICAL CHANGES ····································3 2. PART NAMES AND FUNCTIONS······················3 3. SPECIFICATION·················································5 4. NOISE CRITERIA CURVES ·······························5 5. OUTLINES AND DIMENSIONS ·························6 6. WIRING DIAGRAM ············································7 7. REFRIGERANT SYSTEM DIAGRAM ················8 8. SERVICE FUNCTIONS ······································8 9. TROUBLESHOOTING······································11 10. DISASSEMBLY INSTRUCTIONS·····················18 11. PARTS LIST······················································20 12. RoHS PARTS LIST···········································22 13. OPTIONAL PARTS ·························BACK PAGE MSC-GA20VB - MSC-GA25VB - MSC-GA35VB - E1 E1 E1 SERVICE MANUAL Wireless type Models INDOOR UNIT NOTE: This service manual describes technical data of the indoor units. RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS PARTS LIST (RoHS compliant). Outdoor unit service manual MU-GA•VB Series (OB386) MUH-GA•VB Series (OB387) MUX-A•VB Series (OB384) MXZ-A•WV Series (OB319) No. OB385 REVISED EDITION-B Revision B: • Indoor heat exchanger of MSC-GA35VB - has been changed. E1 Please void OB385 REVISED EDITION-A.

Upload: others

Post on 30-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • SPLIT-TYPE, AIR CONDITIONERSSPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

    CONTENTS

    1. TECHNICAL CHANGES ····································32. PART NAMES AND FUNCTIONS······················33. SPECIFICATION·················································54. NOISE CRITERIA CURVES·······························55. OUTLINES AND DIMENSIONS ·························66. WIRING DIAGRAM ············································77. REFRIGERANT SYSTEM DIAGRAM················88. SERVICE FUNCTIONS ······································89. TROUBLESHOOTING······································11

    10. DISASSEMBLY INSTRUCTIONS·····················1811. PARTS LIST······················································2012. RoHS PARTS LIST···········································2213. OPTIONAL PARTS ·························BACK PAGE

    MSC-GA20VB -MSC-GA25VB -MSC-GA35VB - E1

    E1

    E1

    SERVICE MANUAL

    Wireless typeModels

    INDOOR UNIT

    NOTE:This service manual describes technical data of the indoor units.RoHS compliant products have mark on the spec name plate.For servicing of RoHS compliant products, refer to the RoHS PARTS LIST (RoHS compliant).

    Outdoor unit service manualMU-GA•VB Series (OB386)

    MUH-GA•VB Series (OB387)MUX-A•VB Series (OB384)MXZ-A•WV Series (OB319)

    No. OB385REVISED EDITION-B

    Revision B:• Indoor heat exchanger of MSC-GA35VB -

    has been changed. E1

    Please void OB385 REVISED EDITION-A.

    OB385B.qxp 07.5.21 4:41 PM Page 1

  • 2

    Revision B:• Indoor heat exchanger of MSC-GA35VB - has been changed. E1

    Revision A:• RoHS PARTS LIST has been added.

    OB385B.qxp 07.5.21 4:41 PM Page 2

  • 3

    PART NAMES AND FUNCTIONS2

    MSC-GA20VB MSC-GA25VB MSC-GA35VB

    Emergency operation switch

    Fan

    Catechin air filter(With deodorizer)

    Air outlet

    Vertical vanes

    Air inlet

    to Breaker

    Remote controlreceiving section

    Display section

    Air cleaning filter(option)(white bellows type)

    Front panel

    Power supply cord

    Panel

    Horizontal vane

    Operation section

    (When the front panel is opened)

    Remote controller

    Operation indicator lamp

    Remote controlreceiving section

    TECHNICAL CHANGES1

    MSC-A07YV - ➔ MSC-GA20VB -1. Indication of capacity has been changed. (BTU base ➔ kW)2. P.C. board has been changed.3. Air cleaning filter has been changed to optional parts.4. Fan motor has been changed.5. Fan motor capacitor has been changed.6. Color of indoor unit has been changed.

    MSC-A09YV - ➔ MSC-GA25VB -1. Indication of capacity has been changed. (BTU base ➔ kW)2. P.C. board has been changed.3. Air cleaning filter has been changed to optional parts.4. Fan motor has been changed.5. Fan motor capacitor has been changed.6. Color of indoor unit has been changed.

    MSC-A12YV - ➔ MSC-GA35VB -1. Indication of capacity has been changed. (BTU base ➔ kW)2. P.C. board has been changed.3. Air cleaning filter has been changed to optional parts.4. Fan motor has been changed.5. Fan motor capacitor has been changed.6. Color of indoor unit has been changed.

    E1E1

    E1E1

    E1E1

    OB385B.qxp 07.5.21 4:41 PM Page 3

  • 4

    ACCESSORIES

    MSC-GA20VBMSC-GA25VBMSC-GA35VB

    Installation plate

    Installation plate fixing screw 4 o 25 mm

    Remote controller holder

    Fixing screw for 3 3.5 o 16 mm

    Battery (AAA) for remote controller

    Wireless remote controller

    Felt tape (Used for left or left-rear piping)

    1

    5

    1

    2

    2

    1

    1

    1

    2

    3

    4

    5

    6

    7

    ON/OFF

    FAN

    TOOWARM

    TOOCOOL

    VANE

    MODE

    ECONO COOL

    STOP

    START

    HR.

    MIN.

    I FEEL COOL

    DRY

    PMCLOCK

    AM

    RESET CLOCK

    HEAT/FAN

    /

    Open the front lid.

    ON/OFF TOOCOOL

    PM

    AM

    TOOWARM

    Signal transmitting section

    Operation display section

    OPERATE /STOP(ON /OFF) button

    TEMPERATURE buttons

    Indication of remote controller model is on back.

    OPERATION SELECT button

    FAN SPEED CONTROL buttonOFF-TIMER button

    HR. buttonMIN. button

    (TIME SET button)

    ON-TIMER button

    RESET button

    ECONO COOL button

    VANE CONTROL buttonCLOCK SET button

    REMOTE CONTROLLER

    OB385B.qxp 07.5.21 4:41 PM Page 4

  • 5

    SPECIFICATION3

    Indoor modelFunction

    Indoor unit power supply

    Air flow(High/Med. /Low )Power outletRunning currentPower inputPower factorFan motor currentModelWinding resistance(at 20:)Dimensions WOHODWeightAir directionSound level(High/Med. /Low )Fan speed(High/Med. /Low )Fan speed regulatorThermistor RT11(at 25:)Thermistor RT12(at 25:)Remote controller model

    K /hAAW%A

    "

    mmkg

    dBrpm

    k"k"

    MSC-GA20VB

    Single phase230V,50Hz

    10 0.173590

    0.17 RC4V19-JA

    WHT-BLK 283 BLK-RED 188 815O278O244

    95

    31010

    KP1A or KM04F

    Cooling

    474/372 /276

    36/31 /25900/750 /600

    Heating

    510/420 /342

    36/31 /25950/820 /700

    MSC-GA25VB

    Single phase230V,50Hz

    10 0.173590

    0.17 RC4V19-JA

    WHT-BLK 283 BLK-RED 188 815O278O244

    95

    31010

    KP1A or KM04F

    Cooling

    474/384 /306

    36/31 /25900/770 /650

    Heating

    588/456 /342

    39/32 /251,050/870 /700

    MSC-GA35VB

    Single phase230V,50Hz

    10 0.194092

    0.19 RC4V19-HA

    WHT-BLK 224 BLK-RED 318 815O278O244

    105

    31010

    KP1A or KM04F

    Cooling

    582/444 /324

    40/33 /26930/760 /600

    Heating

    606/498 /396

    39/33 /26960/830 /700

    Ele

    ctric

    alda

    taF

    an

    mot

    orS

    peci

    alre

    mar

    ks

    Capacity

    w w

    w w

    w w w w w w w w w w

    w w w w w w w w w w w

    w w w w w w w w w w w w

    w

    w w w w

    NOTE: 1. Test conditions are based on ISO 5151.Cooling : Indoor DB27°C WB19°C Heating : Indoor DB20°C

    Outdoor DB35°C WB24°C Outdoor DB7°C WB6°CIndoor-Outdoor piping length 5m

    W Reference value

    NOISE CRITERIA CURVES4

    90

    80

    70

    60

    50

    40

    30

    20

    1063 125 250 500 1000 2000 4000 8000

    APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    NC-70

    OC

    TAV

    E B

    AN

    D S

    OU

    ND

    PR

    ES

    SU

    RE

    LE

    VE

    L, d

    B r

    e 0.

    0002

    MIC

    RO

    BA

    R

    BAND CENTER FREQUENCIES, Hz

    Test conditions,Cooling : DB27: WB19:Heating : DB20: WB -:

    MSC-GA20VBCOOLING

    High

    FUNCTIONFAN SPEED

    36HEATING

    SPL(dB(A)) LINE

    90

    80

    70

    60

    50

    40

    30

    20

    1063 125 250 500 1000 2000 4000 8000

    APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    NC-70

    OC

    TAV

    E B

    AN

    D S

    OU

    ND

    PR

    ES

    SU

    RE

    LE

    VE

    L, d

    B r

    e 0.

    0002

    MIC

    RO

    BA

    R

    BAND CENTER FREQUENCIES, Hz

    Test conditions.Cooling : DB27: WB19:Heating : DB20: WB -:

    MSC-GA25VBCOOLING

    High

    FUNCTIONFAN SPEED

    36

    HEATING 39

    SPL(dB(A)) LINE

    OB385B.qxp 07.5.21 4:41 PM Page 5

  • 6

    OUTLINES AND DIMENSIONS5

    MSC-GA20VB MSC-GA25VB

    244

    242 5

    7 or

    mor

    e

    90

    11030149606

    278

    60

    815

    783

    Power supply cordLead to right 1.0mLead to left 0.3m

    Air out

    Installation plate

    Insulation [28

    Drain hose [16(Connected part O,D)

    Air in

    Liquid line [6.35-0.5mGas line [9.52-0.43mInsulation [37 O.D [21 I.D

    {

    Wireless remote controller

    162

    1958

    81.581.5

    41 2.5

    42

    271

    231.

    5

    4.581.5 133.5

    326326

    Wall hole [65

    Indoor unit

    Installation plate

    Unit: mm

    90

    80

    70

    60

    50

    40

    30

    20

    1063 125 250 500 1000 2000 4000 8000

    APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    NC-70

    OC

    TAV

    E B

    AN

    D S

    OU

    ND

    PR

    ES

    SU

    RE

    LE

    VE

    L, d

    B r

    e 0.

    0002

    MIC

    RO

    BA

    R

    BAND CENTER FREQUENCIES, Hz

    Test conditions.Cooling : DB27: WB19:Heating : DB20: WB -:

    MSC-GA35VBCOOLING

    FUNCTIONFAN SPEED

    40

    HEATINGHigh

    39

    SPL(dB(A)) LINE

    INDOOR UNITWALL

    MICROPHONE

    0.8m

    1m

    OB385B.qxp 07.5.22 7:48 AM Page 6

  • 7

    MSC-GA35VB

    244

    242

    218.

    5

    258

    81.581.5

    41 422.5

    17.5

    161.5161.5

    326326

    5

    7 or

    mor

    e90

    11030149606

    278

    60

    815

    783

    Power supply cordLead to right 1.0mLead to left 0.3m

    Air out

    Indoor unit

    Installation plate

    Wall hole [65

    Installation plate

    Insulation [28

    Drain hose [16(Connected part O,D)

    Liquid line [6.35-0.5mGas line [9.52-0.43mInsulation [37 O.D [21 I.D

    {

    Wireless remote controller

    162

    1958

    Air in

    WIRING DIAGRAM6

    MSC-GA20VB MSC-GA25VB MSC-GA35VB

    SYMBOL

    NR11

    RT11

    RT12

    SR141

    NAME NAME NAME

    INDOOR FAN CAPACITOR

    FUSE(3.15A)

    INDOOR FAN MOTOR (INNER FUSE)

    VANE MOTOR

    VARISTOR

    ROOM TEMPERATURE THERMISTOR

    INDOOR COIL THERMISTOR

    SOLID STATE RELAY

    TERMINAL BLOCKSYMBOL

    C11

    F11

    MF

    MV

    TRANSFORMER

    SYMBOL

    TB

    T11

    MF

    123456

    125CNCN

    109

    5

    REMOTECONTROLLER

    23

    POWER MONITORRECEIVER P.C.BOARD

    GRN

    LD103

    PE

    12V

    FORMU ORMUX TYPE

    FOR MUH ORMXZ-A TYPE

    MV

    GRN/

    YLW

    POWERSUPPLYCORD~/N 230V50Hz

    TO OUTDOORUNITCONNECTING

    12V

    1

    2

    N

    3

    L

    BRN

    BLU

    BLK

    WHT

    BLU

    RED

    BRN

    5

    CN151

    12

    CN202123

    CN201

    LD105

    CN211

    ELECTRONIC CONTROL P.C. BOARD

    F11

    T11

    NR11

    RT11

    RT12CN112CN111

    531

    CN121

    BLKGRYYLWBRN

    3

    WHTRED

    C11SR141

    CIRCUIT BREAKER

    TB

    NOTE:1. About the outdoor side electric wiring, refer to the outdoor unit electric wiring diagram for servicing.2. Use copper conductors only. (For field wiring)3. Symbols below indicate./: Terminal block, : Connector

    Unit: mm

    OB385B.qxp 07.5.21 4:41 PM Page 7

  • REFRIGERANT SYSTEM DIAGRAM

    8

    7

    SERVICE FUNCTIONS8

    8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATIONA maximum of 4 indoor units with wireless remote controllers can be used in a room.In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must bemodified according to the number of the indoor unit.

    8-1. TIMER SHORT MODEFor service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board.The time will be shortened as follows. (Refer to 9-6.)

    Set time : 1 minute ➔ 1-secondSet time : 3 minutes ➔ 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is

    shortened by short circuit of JPG and JPS.)

    How to modify the remote controller P.C. boardRemove batteries before modification. The board has a print as shown below :

    NOTE : For modification, take out the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After modification, put back the batteries then press the RESET button.

    MSC-GA20VB MSC-GA25VB MSC-GA35VB

    J2

    J1

    MSC-GA20VB MSC-GA25VB MSC-GA35VB

    Indoorheatexchanger

    Room temperaturethermistorRT11

    Refrigerant pipe [9.52(with heat insulator)

    Unit:mm

    Indoor coilthermistorRT12

    Flared connection

    Flared connection

    Refrigerant pipe [6.35(with heat insulator)

    Refrigerant flow in cooling

    Remote controller model : KP1A

    OB385B.qxp 07.5.21 5:14 PM Page 8

  • 9

    The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.After modification, press the RESET button.

    Table 1

    No. 1 unitNo. 2 unitNo. 3 unitNo. 4 unit

    1 unit operationNo modification

    –––

    2 units operationSame as at left

    Solder J1––

    3 units operationSame as at leftSame as at left

    Solder J2–

    4 units operationSame as at leftSame as at leftSame as at left

    Solder both J1 and J2

    How to set the remote controller exclusively for particular indoor unitAfter you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as theremote controller for the indoor unit.The indoor unit only accepts the signal from the remote controller that has been assigned to the indoor unit once they areset.The setting will be cancelled if the breaker has turned OFF, or the power supply has shut down.Please conduct the above setting once again after the power has restored.

    Slide switchType

    The position of the slide switch

    COOL ONLYCOOL & HEAT

    8-3. REMOTE CONTROLLER (How to set the type)This remote controller setting needs to be switched according to the type of air conditioner (COOL & HEAT or COOLONLY).If the setting is incorrect, the air conditioner does not operate normally. Therefore, check if the setting corresponds to the type of air conditioner. If not, correct the setting as shown below.

    Remote controller model : KM04F

    J1 J2

    OB385B.qxp 07.5.21 4:41 PM Page 9

  • 10

    NOTE• The operation settings are memorized when 10 seconds have passed after the remote controller was operated.• If main power is cut while AUTO START/STOP timer is active, the timer setting is cancelled.• If the unit has been off with the remote controller before power failure, the auto restart function does not work as the

    power button of the remote controller is off.• To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn ON at the same

    time.• When some air conditioners are connected to the same supply system, if they are operated before power failure, the

    starting current of all the compressors may flow simultaneously at restart.Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding system that allows the units to start one by one.

    1. MU & MUX TYPE / MUH & MXZ TYPE SWITCH OVER The indoor units for MU & MUX type and MUH & MXZ typeare common specifications. Set switch according to thetype of outdoor unit. The units are set for MUH & MXZ type when they are shipped from the factory.

    How to release “AUTO RESTART FUNCTION”! Turn OFF the main power for the unit. @ Pull out the electronic control P.C. board, and change switch(SW2-1) on the indoor electronic control P.C. board as

    following figures.

    SW2-1 sets the AUTO RESTART FUNCTION ON / OFF.SW2-2 switches over the MU & MUX type / MUH & MXZ type. When the units are shipped from the factory, SW2 is as follows. SW2-1: AUTO RESTART FUNCTION ON SW2-2: MUH & MXZ type }

    SW2

    FRONT

    12

    12

    IC101

    CN

    151

    SW1

    CN

    112C

    N121

    L101C

    N201

    F11

    CN202

    C11CN211

    SW2

    LD105

    Operation! If the main power (230V AC) has been cut, the operation settings remain.@ After the power is restored, the unit restarts automatically according to the memory. (However, it takes at least 3

    minutes for the compressor to start running.)

    8-4. MU & MUX TYPE / MUH & MXZ TYPE SWITCH OVER AND AUTO RESTART FUNCTION

    2. AUTO RESTART FUNCTIONWhen the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the momentpower has restored after power failure.Then, the unit will restart automatically. However if the unit is operated in “IFEEL CONTROL” mode before power failure, the operation is not memorized. In “I FEEL CONTROL” mode, the opera-tion is decided by the initial room temperature. “AUTO RESTART FUNCTION” is ON when the units are shipped fromthe factory.

    1 21 2

    1 2 SW2 SW21 2

    Outdoor unit MUH & MXZ type

    Set 2 switch downside.

    Outdoor unit MU & MUX type

    Set 2 switch upside.

    NOTE:•If the indoor-outdoor connecting wire is incorrectly connected on the terminal block, the unit does not operate normally.

    •If a ground is incorrect, it may cause an electric shock.

    How to switch over MU & MUX TYPE / MUH & MXZ TYPE! Turn OFF the main power for the unit.@ Pull out the electronic control P.C. board, and change

    switch(SW2-2) on the indoor electronic control P.C. boardaccording to the type of outdoor unit as following figures.

    1 2 SW2 SW21 2

    1 21 2

    AUTO RESTART FUNCTION ON

    Set 1 switch downside.

    AUTO RESTART FUNCTION OFF

    Set 1 switch upside.

    OB385B.qxp 07.5.21 4:41 PM Page 10

  • 11

    TROUBLESHOOTING9

    3. Troubleshooting procedure1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.

    To make sure, check how many times the abnormality indication is flashing on and off before starting service work.2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the

    components for bursting and discoloration.3) When troubleshooting, refer to 9-2. “Instruction of troubleshooting” and 9-3. “Troubleshooting check table”.

    Lead wiring Housing point

    9-1. Cautions on troubleshooting1. Before troubleshooting, check the following:

    1) Check the power supply voltage.2) Check the indoor/outdoor connecting wire for mis-wiring.

    2. Take care of the following during servicing1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller. After confirming

    the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic

    control P.C. board.3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the

    components.4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.

    MSC-GA20VBMSC-GA25VBMSC-GA35VB

    4. How to replace batteries Weak batteries may cause the remote controller malfunction.In this case, replace the batteries to operate the remote controller normally.

    NOTE1 : If the RESET button is not pressed, the remote controller may not operate correctly.

    Insert the negative pole of the batteries first.Check if the polarity of the batteries is correct.

    HEAT/FAN/

    RESET button

    HEAT/FAN/

    1 Remove the front lid and insert batteries.Then reattach the front lid.

    2 Press the RESET button.

    NOTE2 : INFORMATION FOR MULTI SYSTEM AIR CONDITIONER (OUTDOOR UNIT : MXZ-A14WV MXZ-A18WV MXZ-A26WV MXZ-A32WV )

    Multi system air conditioner (Outdoor unit MXZ-A14WV MXZ-A18WV MXZ-A26WV MXZ-A32WV) can connect two ormore indoor units with one outdoor unit. According to the capacity, two or more units can operate simultaneously.

    •When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and theother for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units thatwill start the operation later cannot operate, indicating as shown in the figure below. In this case, please set all theindoor units to the same operation mode.

    •When indoor units starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes(max. 10 minutes) to blow out the warm air.

    •In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowingmay be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.

    lighted

    flashing

    Operation Indicator

    OB385B.qxp 07.5.21 4:41 PM Page 11

  • 12

    9-2. Instruction of troubleshooting

    Start

    Indoor unit operates.Outdoor unit doesn't operate.

    Indoor unit doesn't receive the signal from remote controller.

    Indoor unit operates.Outdoor unitdoesn't operatenormally.

    OPERATIONINDICATORlamp on theindoor unit is flashing on and off.

    Outdoor unit operates only in Test Run operation.w2

    Outdoor unit doesn't operate even in Test Run operation.w2

    Indoor unit operates,when theEMERGENCY OPERATION switch ispressed.

    Indoor unit doesn't operate,when the EMERGENCY OPERATION switch ispressed.

    Check room temperature thermistor.Refer to 9-6. "Test point diagram and voltage".

    MUH-GA20/GA25/GA35VB MUX-2A28/2A59/3A60/3A63/2A70/4A73VBRefer to "Check of outdoor unit".

    Refer to 9-5.B "Check of remotecontroller and receiver P.C. board".

    MUH-GA20/GA25/GA35VBMXZ-A14/A18/A26/A32WVFlash on and off at 0.5-second intervalsCause: Indoor/Outdoor unit• Mis-wiring or trouble of serial signal

    2-time flash Cause:Indoor unit• Trouble of room temp- erature/ indoor coil thermistor

    3-time flash Cause:Indoor unit• Trouble of indoor fan motor

    6-time flash Cause: Outdoor unit• Trouble of thermistor in outdoor unit

    7-time flash Cause: Outdoor unit• Trouble of outdoor control system

    Check room temperature thermistor and indoor coil thermis-tor.Refer to 9-6."Test point diagram and voltage".

    Refer to 9-5.A "Check of indoor fan motor".

    4-time flash Cause:Indoor unit• Trouble of indoor unit control system

    Replace theindoor electronic control P.C. board.

    MUH-GA20/GA25/GA35VBMXZ-A14/A18/A26/A32WVRefer to "Check of outdoor thermistor" and others.

    MUH-GA20/GA25/GA35VBMXZ-A14/A18/A26/A32WVReplace the deicer P.C. board and others.

    Refer to 9-5. D "How to check mis-wiring and serial signal error (When outdoor unit doesn't work)".W1

    1. Check indoor / outdoor connecting wire.2. Refer to 9-5. C "Check of indoor electronic control P.C. board".

    Outdoor unit doesn't stop even if indoor unit stops.

    Unit doesn't operate normaloperation in COOL or HEAT mode.

    MU-GA20/GA25/GA35VBCheck of wiring diagram of outdoor unit".MUH-GA20/GA25/GA35VB Refer to "Check of outdoor unit".

    MUH-GA20/GA25/GA35VB MXZ-A14/A18/A26/A32WVRefer to "Check of R.V. coil" and others.

    W1. When the power is turned off and turned on again, the indication shows “the trouble of mis-wiring”.

    Refer to outdoor unit service manual.

    Indoor unit operates.But indoorunit doesn'tblow out cool air.

    MUX-2A28/2A59/3A60/3A63/2A70/4A73VB Refer to "Check of indoor/outdoorunits' connectionand outdoor unit".

    w2."Test Run operation" means the operation within 30 minutes after EMERGENCY OPERATION switch is pressed.

    10-time flash Cause: Outdoor unitMXZ type• Outdoor refrigerant system abnormality

    MXZ typeRefer tooutdoor refrigerant system related items.

    MXZ type5-time flash Cause: Outdoor unit• Outdoor power system abnormality

    Refer to"Check of inverter/ compressor" and "Check of power supply".

    MSC-GA20VB MSC-GA25VB MSC-GA35VB

    OB385B.qxp 07.5.21 4:41 PM Page 12

  • 13

    9-3. Troubleshooting check table

    Operation Indicator· Flashing of the OPERATION INDICATOR lamp (on the left-hand side) indicates possible abnormalities.· The OPERATION INDICATOR lamp (on the left-hand side) is lighting during normal operation.

    flashing• The following indication does not depend on the shape of lamp.

    ❈ Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.Self check table

    No.

    1

    2

    5

    7

    8

    SymptomOperation indicator lamp Detection method Checkpoint

    0.5-second ON

    0.5-second OFF

    MUH or MXZ typeMis-wiring or Serial signal

    MUH or MXZ typeDefrostthermistor

    MUH or MXZ typeOutdoorcontrolsystem error

    When the defrost thermistor shorts or opens after the compressor start-up.

    When it cannot properly read data in the non-volatile memory of outdoor electronic control P.C. board.

    When the operation mode of each indoor unit is differently set to COOL(includes DRY) and HEAT at same time, the operation mode of indoor unit that has operated at first has the priority.

    ● Check outdoor DEICER P.C. board and others.● Check resistance of thermistor.● Reconnect connector. Refer to outdoor unit service

    manual.

    ● Check outdoor DEICER P.C. board and others.

    Refer to outdoor unit service manual.

    ● Unify the operation mode.

    ● Check switch SW2-2.(MU & MUX type or MUH & MXZ type)● Check wiring (visual check and conductivity check).● Check indoor electronic control P.C.board.● Check outdoor DEICER P.C. board and others.● Check electrical parts.

    ● Check resistance of thermistor.● Reconnect connector.● Check indoor electronic control P.C.board.

    3

    Indoor coil thermistor

    Room temperature thermistor

    9

    MXZ typeOutdoor refrigerant system error

    When the compressor operation has been in-terrupted by LEV protection continuously 5 minutes, the compressor stops operation.

    Abnormal point

    Outdoor unit does not run.

    Outdoor unit does not run.

    Outdoor unit does not run.

    Outdoor unit does not run.

    Outdoor unit does not run.

    Outdoor unit does not run.

    2-time flash

    2.5-second OFF

    When serial signal from outdoor unit stops for 4 to 5 seconds.

    Detect Indoor coil/room temperature thermis-tor short or open circuit every 8 seconds dur-ing operation.

    3-time flash

    2.5-second OFF

    Indoor fan motor repeats 12 sec-onds ON and 3 minutes OFF.When the indoor fan motor breaks, the fan keeps stopping.

    When rotational frequency feedback pulse signal is not emit during 12-second indoor fan operation.

    When the compressor operation is continuously three times interrupted by over current protection within 1 minute after start-up , it stops operation.

    ● Disconnect connector CN211 and check connector CN121 2-3 to make sure rotational frequency feedback signal of 1.5V or over exists.● Check indoor electronic control P.C. board.● Check indoor fan motor.● Reconnect connector.

    ● Check the inverter output.● Check the compressor.

    Indoor fan motor

    6-time flash

    2.5-second OFF

    ● Refer to "Check of LEV".● Check refrigerant circuit and refrigerant amount.● Check outdoor electronic control P.C. board. Refer to outdoor unit service

    manual.

    6

    5-time flash

    2.5-second OFF

    Operation IndicatorMXZ typeOperation mode setting

    LightedFlashing

    Outdoor unit operates but indoor unit does not run.

    4

    4-time flash

    2.5-second OFF

    Indoor control system

    When it cannot properly read data in the nonvolatile memory of indoor electronic control P.C. board.

    Outdoor unit does not operate.

    ● Replace the indoor electronic control P.C. board.

    7-time flash

    2.5-second OFF

    10-time flash

    2.5-second OFF

    MXZ type Outdoor power system

    2.5-second OFF

    OB385B.qxp 07.5.21 4:41 PM Page 13

  • 14

    AA Check of indoor fan motor

    Is soldered point of the connector correctly soldered?

    Is resistance 0 (short circuit) or ∞ (open circuit)?

    Yes ( 0 or ∞ )

    Yes

    NoYesNo

    Turn OFF the power supply.Check connector CN211 visually.

    Disconnect lead wires from connector CN211 on indoor electronic control P.C. board.Measure resistance between lead wires No.1 and No.5, then No.3 and No.5.

    When OPERATION INDICATOR lamp flashes 3-time.Indoor fan motor doesn’t operate.

    Turn ON the power supply. Stop it if the unit operates.Insert screwdriver into air outlet to rotate indoor fanmotor slowly for 1 revolution or over, and measure volt-age No.2(+) and No.3(-) on CN121.

    No(others)

    Replace the indoor electronic control P.C. board.

    Does voltage repeat 0V DC and 5V DC?

    Yes

    No

    Are lead wires connected?Reconnect the lead wires. Resolder it.

    Repair or replace the indoor fan motor.

    Measure the resistance between the terminals with a tester.(Coil wiring temperature10°C ~ 30°C)

    Room temperaturethermistor (RT11)

    9-4. Trouble criterion of main parts

    Part name

    Indoor coilthermistor (RT12)

    Indoor fanmotor (MF)INNER FUSE136i3°CCUT OFF

    Mot

    or p

    art

    Sen

    sor

    part

    Check method and criterion

    Measure the resistance with a tester.(Part temperature 10°C ~ 30°C)

    Measure the voltage Power ON.

    Figure

    8kΩ ~ 20kΩ

    NormalAbnormal

    Open or short-circuit

    271 ~ 295ΩWHT-BLKBLK-RED

    BRN-YLW

    YLW-GRY

    Normal

    4.5 ~ 5.5V

    Abnormal

    Remain 0V or 5V(When fan revolved one time)0V➔ 5V➔ 0V

    (Approx.)

    MSC-GA20/GA25VB

    180 ~ 196Ω

    RED

    BLK

    YLW

    FUSE

    GRY

    BRN

    WHT

    MSC-GA20VBMSC-GA25VBMSC-GA35VB

    Normal Abnormal

    Open or short-circuit

    MSC-GA20/GA25/GA35VB

    MSC-GA20/GA25/GA35VB

    Vane motor(MV)

    Measure the resistance between the terminals with a tester.(Part temperature10°C ~ 30°C)

    Normal Abnormal

    Open or short-circuit240 ~ 260Ω

    RED

    YLW

    BRN

    ORN GRN

    ROTOR

    MSC-GA20/GA25/GA35VB

    Color oflead wire

    215 ~ 233ΩMSC-GA35VB

    305 ~ 331Ω

    Color oflead wire

    9-5. Troubleshooting flow

    OB385B.qxp 07.5.21 4:41 PM Page 14

  • 15

    BB Check of remote controller and receiver P.C. board

    Indoor unit operates by pressing the EMERGENCY OPERATION switch, but doesn’t operate with the remote controller.

    Yes

    Replace the batteries. (Refer to 9-1-4.)

    Turn ON a radio to AM and press switchon the remote controller.

    Is noise heard from radio?

    Are there any fluorescent lights ofinverter or rapid-start type withinthe range of 1m?

    Replace the remote controller.

    • Reinstall the unit away from lights.• Attach a filter on receiving part.

    Switch on the remote controller.

    Is LCD display on the remote con-troller displayed?

    Remove batteries, then set them back and press the RESETbutton. Check if the unit operates with the remote controller.

    Yes

    Does the unit operate with theremote controller?

    Yes

    OK

    No

    (not clear)

    Yes

    No

    No

    Yes

    Measure the voltage between receiver P.C. board connector CN302No.3(–) and No.5(+) when the remote controller button is pressed.

    Is the voltage approx. 4V DC?Replace the indoor electronic controlP.C. board.

    Replace the power monitor, receiver P.C. board.

    No(5V or 0V DC)

    No

    wCheck the remote controller is exclusive for this air conditioner.

    CC Check of indoor electronic control P.C. board

    Check the both “parts side” and “pattern side” of indoor electronic control P.C. board visually.

    Replace the fuse.

    Is fuse (F11) blown?

    Be sure to check both fuse and varistor in any case.

    Replace the fan motor.

    Replace the indoor electronic control P.C. board.

    Is winding resistance of fan motor 0 "?

    Is winding resistance of vane motor 0 "?

    No

    Yes

    Replace the vane motor.

    No

    Yes

    Yes

    Is varistor (NR11) burnt?

    Replace the varistor.

    Yes

    Turn OFF the power supply.Remove indoor fan motor connector CN211 and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply.

    No

    Does the unit operate with the remote controller?Does the OPERATION INDICATOR lamp light up by pressing the EMERGENCY OPERATION switch?

    Yes

    No

    Be sure to check both resistances.

    Turn OFF the power supply.

    Turn OFF the power supply.

    No

    The unit doesn’t operate with the remote controller.Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.

    OB385B.qxp 07.5.21 4:41 PM Page 15

  • 16

    DD How to check mis-wiring and serial signal error

    Serial signal error is indicated.(0.5-sec. ON, 0.5-sec. OFF)

    1. Turn OFF the power supply(indoor / outdoor unit) and disconnect indoor and outdoor connecting wire on indoor side.2. Short-circuit between indoor terminal block N and 3.3. Turn ON the power supply(indoor unit) and press once EMERGENCY OPERATION switch.

    During EMERGENCY OPERATION, is there 10V DC between both ends of R601?(By tester, the stylus is between 5 ~10V)

    Start

    Turn OFF the power supply(indoor/outdoor unit).

    No

    NoIs there 20V DC between both ends of R132 on indoor electronic control P.C. board ?( By tester, the stylus is between 0 ~ 20V. )

    •Turn OFF the power supply(indoor unit).•Connect indoor and outdoor connecting wire.

    Is the outdoor unit "MUH" type?

    •Turn ON the power supply(indoor/outdoor unit).•Press once EMERGENCY OPERATION switch.•3 min. later, check the self-check result displayed on OPERATION INDICATOR lamp on indoor unit. w 2

    Is this mis-wiring, poor contact, or disconnection of wire?Correct them.

    Replace the indoor electronic control P.C. board.

    Turn ON the power supply(outdoor unit).

    Is there 230V AC between outdoor terminalblock L-N (TB1)?

    No Check the outdoor power supply, power supply cord and connection.

    Yes

    Turn ON the power supply(indoor unit).

    NoReplace the deicer P.C. board.

    Yes

    No Correct the wiring between CN730 on the deicer P.C. board and outdoor terminal block.

    Replace the deicer P.C. board.

    Yes

    Yes

    Yes

    Set the switch(SW2-2) on the indoor electronic control P.C. board to MU or MUX type. w1

    Yes

    Does the unit operate? OKYes

    No

    NoRefer to the "Instruction of troubleshooting."

    w 2 Short circuit of JPG and JPS on the indoor electronic control P.C. board enables self-check to be displayed in 3 seconds.

    w 1 Set the switch(SW2-2) on indoor electronic control P.C. board to MU or MUX type, when the outdoor unit is MU or MUX type. If the setting is MUH or MXZ type, the unit does not work.

    Is there 5V DC between J205 + –J101 - on the deicer P.C. board?

    Refer to outdoor unit service manual.

    When OPERATION INDICATOR lamp flashes 0.5-second intervals or 1-time.Outdoor unit does not operate.

    OB385B.qxp 07.5.21 4:41 PM Page 16

  • 17

    MSC-GA20VBMSC-GA25VBMSC-GA35VBIndoor electronic control P.C. board

    CN302

    Indoor coil thermistor (RT12)Room temperature thermistor (RT11)

    Temperature (:)

    Res

    ista

    nce

    (k"

    )

    SW2(Refer to 8-4.)1sets the Auto restart

    function ON/OFF.2switches over MU&MUX type/

    MUH & MXZ type.

    Power supply input230V AC

    Varistor(NR11)

    Fuse F11 250V AC 3.15A

    Room temperaturethermistor RT11Indoor coilthermistor RT12

    Timer short modepoint JPG, JPS(Refer to 8-1.)

    Emergencyoperation switch

    }

    } Indoor fan motor 230V AC}

    5V DC

    +–

    {12V DC +– }

    Safety device offan by horizontalvane CN1R1

    R132

    J23J33

    J33

    J12

    Power monitor, receiver P.C. board

    9-6. Test point diagram and voltage

    OB385B.qxp 07.5.21 4:41 PM Page 17

  • 18

    DISASSEMBLY INSTRUCTIONS10

    MSC-GA20VB MSC-GA25VB MSC-GA35VB

    (1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism.

    1Slide the sleeve.2Pull the terminal while pushing the locking lever.

    1Hold the sleeve, and pull out the terminal slowly.

    The terminal which has the locking mechanism can be detached as shown below.There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.The terminal without locking mechanism can be detached by pulling it out.Check the shape of the terminal before detaching.

    Connector

    Sleeve

    Locking lever

    OPERATING PROCEDURE PHOTOS

    1. Removing the front panel(1) Remove the screw caps of the front panel.

    Remove the screws.(2) Pull the panel down to your side slightly and unhook the

    catches at the top.

    2. Removing the electronic control P.C. board and thepower monitor, receiver P.C. boardNOTE : In case of removing only indoor electronic control

    P.C. board, work (3) is not necessary.(1) Remove the front panel. (Refer to 1.)(2) Remove the power monitor, receiver P.C. board holder

    from the bottom of electrical box.(3) Open the power monitor, receiver P.C. board holder and

    remove the power monitor, receiver P.C. board.(4) Remove the screw of the electrical cover and the electrical

    cover.(5) Remove the screw of the V.A. clamp and the V.A. clamp.(6) Remove the screw of the cord clamp and the cord clamp.(7) Remove the screw of the terminal block.(8) Remove the screw of the earth wire.(9) Pull out indoor electronic control P.C. board slightly.(10) Disconnect all (except CN101) the connectors on the elec-

    tronic control P.C. board.(11) Remove the electronic control P.C. board.(12) Disconnect the connector of power monitor, receiver P.C.

    board (CN101) on the electronic control P.C. board.

    Photo 2

    Photo 1

    Terminal blockfixing screw

    Screw of the V.A.clamp

    Indoor electroniccontrol P.C. board

    Screws of the front panel

    Screw of theearth wire

    Power monitor, receiver P.C. board holder

    Screw of theelectrical cover

    Cord clamp fixingscrew

    OB385B.qxp 07.5.21 4:41 PM Page 18

  • 19

    OPERATING PROCEDURE PHOTOS

    3. Removing the electrical box(1) Remove the front panel. (Refer to 1.)(2) Remove the electrical cover. (Refer to 2.)(3) Remove the V.A. clamp. (Refer to 2.)(4) Remove the cord clamp. (Refer to 2.)(5) Remove the terminal block. (Refer to 2.)(6) Remove the screw of earth wire. (Refer to 2.)(7) Disconnect the connector of the indoor coil thermistor

    (CN112), the fan motor connector (CN211 and CN121) andthe vane motor connector (CN151) on the electronic con-trol P.C. board.

    (8) Remove the fan motor lead wire and indoor coil thermistorfrom the electrical box.

    (9) Remove the lead wire of vane motor from the bottom of electrical box.

    (10) Remove the screw fixing the electrical box, remove the electrical box.

    4. Removing the nozzle assembly and the vane motor(1) Remove the front panel. (Refer to 1.)(2) Remove the electrical box. (Refer to 3.)(3) Pull out the drain hose from the nozzle assembly, remove

    the nozzle assembly.(4) Remove the screws of the vane motor, disconnect the

    vane motor connector.(5) Remove the vane motor.

    5. Removing the indoor fan motor and the line flow fan (1) Remove the front panel. (Refer to 1.)(2) Remove the electrical box. (Refer to 3.)(3) Pull out the drain hose from the nozzle assembly, remove

    the nozzle assembly. (Refer to 4.)(4) Remove the screw of the lead cover and lead cover.(5) Release the hooks to open the motor band slightly.(6) Loosen the hexagon socket set screw from the line flow

    fan.(7) Remove the screws fixing the motor bed, remove the fan

    motor with motor band and the motor bed.(8) Remove the screws fixing the left side of the heat

    exchanger.(9) Lift the left side of the heat exchanger.(10) Remove the line flow fan.

    Photo 5

    Photo 3

    Photo 4

    Photo 7

    Screw of theelectrical box

    Drain hose

    Screws of theleft side of theheat exchanger

    Screws of the vane motor

    Screws of the motorbed

    Photo 6

    Indoor coil thermistorconnector

    Fan motor connector

    Vane motor connector

    Hooks of themotor band

    Screw of the leadcover

    Hexagon socket set screw

    OB385B.qxp 07.5.21 4:41 PM Page 19

  • 20

    PARTS LIST (non-RoHS compliant)11

    1

    2345

    6

    7

    8

    E02 763 234E02 764 234E02 959 000E02 763 067E02 959 010E02 408 142E02 763 100E02 764 100E02 763 975E02 408 970E02 751 970

    BOXBOXPANEL ASSEMBLYSCREW CAPFRONT PANELCATCHCATECHIN AIR FILTERCATECHIN AIR FILTERCORNER BOX (RIGHT)INSTALLATION PLATEINSTALLATION PLATE

    Symbol

    in Wiring

    Diagram

    Q'ty/unit

    1

    12122

    11

    Including No.3,4,52PCS/SET

    2PCS/SET1PCE/SET1PCE/SET

    RemarksPart No.No. Part Name MSC-GA20VB-E1

    11212

    21

    1

    1

    12122

    11

    11

    11

    11

    E02 749 426E02 527 083

    910

    REMOTE CONTROLLERREMOTE CONTROLLER HOLDER

    MSC-GA25VB-E1

    MSC-GA35VB-E1

    KP1A, KM04F

    1 (W)

    72

    4

    MSC-GA20VBMSC-GA25VBMSC-GA35VB

    3

    8 (W)

    11-2. ACCESSORY AND REMOTE CONTROLLER

    11-1. INDOOR UNIT STRUCTURAL PARTS

    11-1. INDOOR UNIT STRUCTURAL PARTS

    5 6 (W)

    10

    11-2. ACCESSORY AND REMOTE CONTROLLER

    9

    Optional parts(See 13. Optional parts.)

    (W) These figures show about MSC-GA35VB.

    OB385B.qxp 07.5.21 4:41 PM Page 20

  • 21

    Part No.No. Part Name

    20

    21

    22

    INDOOR HEAT EXCHANGERINDOOR HEAT EXCHANGERUNION(GAS)UNION(GAS)UNION(LIQUID)

    1

    1

    1

    1

    11

    {9.52{9.52{6.35

    1

    1

    1

    E02 001 504E02 661 702E02 A59 235E02 781 040E02 781 041E02 127 382E02 829 385E02 763 034E02 815 468E02 962 452E02 963 452E02 964 452E02 749 303E02 151 308E02 749 333E02 691 375E02 749 300E02 751 300E02 749 307E02 749 302E02 408 509E02 751 509E02 749 385

    123456789

    10

    11121314

    15

    1617

    18

    19

    SLEEVE BEARINGDRAIN HOSENOZZLE ASSEMBLYVANE UPPER VANE LOWER FUSEVARISTORVANE CRANK SETPOWER MONITOR, RECEIVER P.C. BOARDELECTRONIC CONTROL P.C.BOARDELECTRONIC CONTROL P.C.BOARDELECTRONIC CONTROL P.C.BOARDVANE MOTORROOM TEMPERATURE THERMISTORMOTOR BANDTERMINAL BLOCKINDOOR FAN MOTOR(RC4V19- )INDOOR FAN MOTOR(RC4V19- )INDOOR COIL THERMISTORLINE FLOW FANBEARING MOUNTBEARING MOUNTVARISTOR

    3.15A

    AUTO RESTARTAUTO RESTARTAUTO RESTART

    3P

    F11NR11

    MVRT11

    TBMFMF

    RT12

    NR12

    111111111

    1

    11111

    111

    1

    1111111111

    11111

    111

    1

    111111111

    11111

    111

    11

    Symbolin WiringDiagram

    Q'ty/unit

    RemarksMSC-GA20VB-E1

    MSC-GA25VB-E1

    MSC-GA35VB-E1

    Including fan motor rubber mount 2PCS/SETIncluding fan motor rubber mount 2PCS/SET

    E02 A59 620E02 964 620E02 151 666E02 815 666E02 151 667

    11-3. INDOOR UNIT ELECTRICAL PARTSAND FUNCTIONAL PARTS

    20 (W)

    21

    22

    10

    12

    4

    2

    5

    11

    15

    3

    1718 16

    14

    6 87

    11-4. INDOOR UNIT HEAT EXCHANGER

    11-3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS

    11-4. INDOOR UNIT HEAT EXCHANGER

    MSC-GA20VB MSC-GA25VB MSC-GA35VB

    1

    13

    9

    Part number that is circled is not shown in the illustration.

    (W) This figure shows MSC-GA35VB.

    PARTS LIST (non-RoHS compliant)

    OB385B.qxp 07.5.21 4:41 PM Page 21

  • 22

    ROHS PARTS LIST (RoHS compliant)12

    1

    2345

    6

    7

    8

    GGGGGGGGGGG

    GG

    E12 763 234E12 764 234E12 959 000E12 763 067E12 959 010E12 408 142E12 763 100E12 764 100E12 763 975E12 408 970E12 751 970

    BOXBOXPANEL ASSEMBLYSCREW CAPFRONT PANELCATCHCATECHIN AIR FILTERCATECHIN AIR FILTERCORNER BOX (RIGHT)INSTALLATION PLATEINSTALLATION PLATE

    Symbol

    in Wiring

    Diagram

    Q'ty/unit

    1

    12122

    11

    Including No.3,4,52PCS/SET

    2PCS/SET1PCE/SET1PCE/SET

    RemarksPart No.No.

    Ro

    HS

    Part Name MSC-GA20VB-E1

    11212

    21

    1

    1

    12122

    11

    11

    11

    11

    E12 749 426E12 527 083

    910

    REMOTE CONTROLLERREMOTE CONTROLLER HOLDER

    MSC-GA25VB-E1

    MSC-GA35VB-E1

    KP1A, KM04F

    1 (W)

    72

    4

    MSC-GA20VBMSC-GA25VBMSC-GA35VB

    3

    8 (W)

    12-2. ACCESSORY AND REMOTE CONTROLLER

    12-1. INDOOR UNIT STRUCTURAL PARTS

    12-1. INDOOR UNIT STRUCTURAL PARTS

    5 6 (W)

    10

    12-2. ACCESSORY AND REMOTE CONTROLLER

    9

    (W) These figures show about MSC-GA35VB.

    Optional parts(See 13. Optional parts.)

    OB385B.qxp 07.5.21 4:41 PM Page 22

  • 23

    Part No.No.

    RoH

    S

    Part Name

    20

    2122

    GGGG

    INDOOR HEAT EXCHANGERINDOOR HEAT EXCHANGERUNION(GAS)UNION(LIQUID)

    1

    11

    111

    {9.52{6.35

    1

    11

    E12 001 504E12 897 702E12 A59 235E12 781 040E12 781 041E12 A49 382E12 829 385E12 763 034E12 815 468E12 962 452E12 963 452E12 964 452E12 749 303E12 151 308E12 749 333E12 691 375E12 749 300E12 751 300E12 749 307E12 A59 302E12 408 509E12 751 509E12 749 385

    123456789

    10

    11121314

    15

    1617

    18

    19

    GGGGGGGGGGGGGGGGGGGGGGG

    SLEEVE BEARINGDRAIN HOSENOZZLE ASSEMBLYVANE UPPER VANE LOWER FUSEVARISTORVANE CRANK SETPOWER MONITOR, RECEIVER P.C. BOARDELECTRONIC CONTROL P.C.BOARDELECTRONIC CONTROL P.C.BOARDELECTRONIC CONTROL P.C.BOARDVANE MOTORROOM TEMPERATURE THERMISTORMOTOR BANDTERMINAL BLOCKINDOOR FAN MOTOR(RC4V19- )INDOOR FAN MOTOR(RC4V19- )INDOOR COIL THERMISTORLINE FLOW FANBEARING MOUNTBEARING MOUNTVARISTOR

    3.15A

    AUTO RESTARTAUTO RESTARTAUTO RESTART

    3P

    F11NR11

    MVRT11

    TBMFMF

    RT12

    NR12

    111111111

    1

    11111

    111

    1

    1111111111

    11111

    111

    1

    111111111

    11111

    111

    11

    Symbolin WiringDiagram

    Q'ty/unit

    RemarksMSC-GA20VB-E1

    MSC-GA25VB-E1

    MSC-GA35VB-E1

    Including fan motor rubber mount 2PCS/SETIncluding fan motor rubber mount 2PCS/SET

    E12 A59 620E12 964 620E12 151 666E12 151 667

    12-3. INDOOR UNIT ELECTRICAL PARTSAND FUNCTIONAL PARTS

    20 (W)

    21

    22

    10

    12

    4

    2

    5

    11

    15

    3

    1718 16

    14

    6 87

    12-4. INDOOR UNIT HEAT EXCHANGER

    12-3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS

    12-4. INDOOR UNIT HEAT EXCHANGER

    MSC-GA20VB MSC-GA25VB MSC-GA35VB

    1

    13

    9

    Part number that is circled is not shown in the illustration.

    (W) This figure shows MSC-GA35VB.

    ROHS PARTS LIST (RoHS compliant)

    OB385B.qxp 07.5.21 4:55 PM Page 23

  • OPTIONAL PARTS13

    CC Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTDDistributed in May 2007. No.OB385 REVISED EDITION-B 6Distributed in May 2006. No.OB385 REVISED EDITION-A 6Distributed in Jan. 2005. No.OB385 6Made in Japan

    New publication, effective May 2007Specifications subject to change without notice.

    HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

    Air cleaning filter(White bellows type)

    AIR CLEANING FILTER● AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.● Normal life of AIR CLEANING FILTER is 4 months. However, when it becomes dirty, replace it as soon as possible.● Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.● DO NOT reuse AIR CLEANING FILTER even if it is washed.● DO NOT remove or attach AIR CLEANING FILTER during unit operation.

    Model Part No.

    MAC-1300FTMSC-GA20VBMSC-GA25VBMSC-GA35VB

    OB385B.qxp 07.5.21 4:41 PM Page 24