Printed in U.S.A. 440 04 7101 07 10/17/2014 SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual for future reference. Safety Labeling and Signal Words DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manual that may apply to the product. DANGER Immediate hazards which will result in severe personal injury or death. WARNING Hazards or unsafe practices which could result in severe personal injury or death. CAUTION Hazards or unsafe practices which may result in minor personal injury or product or property damage. NOTE Used to highlight suggestions which will result in enhanced installation, reliability, or operation. ! WARNING Signal Words in Manuals The signal word CAUTION is used throughout this manual in the following manner: ! CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and/or pictures or product labels. The signal word WARNING is used throughout this manual in the following manner: Safetyalert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. TABLE OF CONTENTS STARTUP, ADJUSTMENT, AND SAFETY CHECK 3 ........... GENERAL 3 ............................................... PRIME CONDENSATE TRAP WITH WATER 3 ................. PURGE GAS LINES 3 ...................................... ADJUSTMENTS 3 ......................................... CHECK INLET GAS PRESSURE 4 ........................... ADJUST MANIFOLD PRESSURE 4 .......................... ADJUST TEMPERATURE RISE 6 ............................ ADJUST BLOWER OFF DELAY (HEAT MODE) 6 .............. BLOWER OFF DELAY JUMPER POSITIONS 6 ................ ADJUST COOLING AIRFLOW 6 ............................. ADJUST THERMOSTAT HEAT ANTICIPATOR 6 ............... CHECK SAFETY CONTROLS 6 ............................. CHECKLIST 7 ............................................. ALTITUDE DERATE MULTIPLIER FOR U.S.A. 7 ............... GAS RATE (CU FT./HR) 8 ................................... ORIFICE SIZE AND MANIFOLD PRESSURE 10 ................ SERVICE AND MAINTENANCE PROCEDURES 12 ............. CLEANING HEAT EXCHANGERS 18 .......................... SEQUENCE OF OPERATION 22 ............................. PARTS REPLACEMENT INFORMATION GUIDE 26 ............. MODELS WFSR040A030A WFSR060B042A WFSR080B048A WFSR080C060A WFSR100C042A WFSR100C060A WFSR120D060A Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org .

Upload: others

Post on 19-Aug-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

Printed in U.S.A. 440 04 7101 07 10/17/2014

SERVICE AND TECHNICALSUPPORT MANUAL

Single Stage, PSC Blower Motor35” Tall, High Efficiency Condensing Gas Furnace

WFSRSave this manual for future reference.

Safety Labeling and Signal WordsDANGER, WARNING, CAUTION, and NOTEThe signal words DANGER, WARNING,CAUTION, and NOTE are used to identify levels ofhazard seriousness. The signal word DANGER isonly used on product labels to signify an immediatehazard. The signal words WARNING, CAUTION,and NOTE will be used on product labels andthroughout this manual and other manual that mayapply to the product.

DANGER − Immediate hazards which will result insevere personal injury or death.

WARNING − Hazards or unsafe practices whichcould result in severe personal injury or death.

CAUTION − Hazards or unsafe practices whichmay result in minor personal injury or product orproperty damage.

NOTE − Used to highlight suggestions which willresult in enhanced installation, reliability, oroperation.

! WARNING

Signal Words in Manuals

The signal word CAUTION is used throughoutthis manual in the following manner:

! CAUTIONSignal Words on Product LabelingSignal words are used in combination withcolors and/or pictures or product labels.

The signal word WARNING is used throughoutthis manual in the following manner:

Safety−alert symbolWhen you see this symbol on the unit and ininstructions or manuals, be alert to thepotential for personal injury.

TABLE OF CONTENTSSTART−UP, ADJUSTMENT, AND SAFETY CHECK 3. . . . . . . . . . .GENERAL 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PRIME CONDENSATE TRAP WITH WATER 3. . . . . . . . . . . . . . . . .PURGE GAS LINES 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ADJUSTMENTS 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .CHECK INLET GAS PRESSURE 4. . . . . . . . . . . . . . . . . . . . . . . . . . .ADJUST MANIFOLD PRESSURE 4. . . . . . . . . . . . . . . . . . . . . . . . . .ADJUST TEMPERATURE RISE 6. . . . . . . . . . . . . . . . . . . . . . . . . . . .ADJUST BLOWER OFF DELAY (HEAT MODE) 6. . . . . . . . . . . . . .BLOWER OFF DELAY JUMPER POSITIONS 6. . . . . . . . . . . . . . . .ADJUST COOLING AIRFLOW 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . .ADJUST THERMOSTAT HEAT ANTICIPATOR 6. . . . . . . . . . . . . . .CHECK SAFETY CONTROLS 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . .CHECKLIST 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ALTITUDE DERATE MULTIPLIER FOR U.S.A. 7. . . . . . . . . . . . . . .GAS RATE (CU FT./HR) 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ORIFICE SIZE AND MANIFOLD PRESSURE 10. . . . . . . . . . . . . . . .SERVICE AND MAINTENANCE PROCEDURES 12. . . . . . . . . . . . .CLEANING HEAT EXCHANGERS 18. . . . . . . . . . . . . . . . . . . . . . . . . .SEQUENCE OF OPERATION 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . .PARTS REPLACEMENT INFORMATION GUIDE 26. . . . . . . . . . . . .

MODELSWFSR040A030AWFSR060B042AWFSR080B048AWFSR080C060AWFSR100C042AWFSR100C060AWFSR120D060A

Use of the AHRI Certified TM Mark indicates amanufacturer’s participation in the program.For verification of certification for individualproducts, go to www.ahridirectory.org .

Page 2: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07Specifications are subject to change without notice.2

SAFETY CONSIDERATIONSImproper instal lat ion, adjustment, a l terat ion, serv ice,maintenance, or use can cause explosion, fire, electrical shock,or other conditions which may cause death, personal injury, orproperty damage. Consult a qualified installer, service agency,or your distributor or branch for information or assistance. Thequalified installer or agency must use factory−authorized kits oraccessories when modifying this product. Refer to the individualinstructions packaged with the kits or accessories wheninstalling.

Follow all safety codes. Wear safety glasses, protective clothing,and work gloves. Use quenching cloth for brazing operations.Have fire extinguisher available. Read these instructionsthoroughly and follow all warnings or cautions included inliterature and attached to the unit. Consult local building codes,the current editions of the National Fuel Gas Code (NFCG)NFPA 54/ANSI Z223.1, and the National Electrical Code (NEC)NFPA 70.

In Canada refer to the current editions of the National standardsof Canada CAN/CSA−B149.1 and .2 Natural Gas and PropaneInstallation Codes, and Canadian Electrical Code CSA C22.1.Recognize safety information. This is the safety−alert symbol

. When you see this symbol on the unit and in instructions ormanuals, be alert to the potential for personal injury.Understand these signal words; DANGER, WARNING, andCAUTION. These words are used with the safety−alert symbol.DANGER identifies the most serious hazards which will result insevere personal injury or death. WARNING signifies hazardswhich could result in personal injury or death. CAUTION is usedto identify unsafe practices which may result in minor personalinjury or product and property damage. NOTE is used tohighlight suggestions which will result in enhanced installation,reliability, or operation.

! WARNINGPERSONAL INJURY, AND/OR PROPERTY DAMAGEHAZARDFailure to carefully read and follow this warning couldresult in equipment malfunction, property damage,personal injury and/or death.Installation or repairs made by unqualified persons couldresult in equipment malfunction, property damage,personal injury and/or death.The information contained in this manual is intended foruse by a qualified service technician familiar with safetyprocedures and equipped with proper tools and testinstruments.Installation must conform with local building codes andwith the Natural Fuel Gas Code (NFCG) NFPA 54/ANSIZ223.1, and National standards of CanadaCAN/CSA−B149.1 and .2 Natural Gas and PropaneInstallation Codes.

! WARNINGELECTRICAL SHOCK HAZARD

Failure to follow this warning could cause personalinjury or death.

Before performing service or maintenance operationson unit, always turn off main power switch to unit andinstall lockout tag. Unit may have more than one powerswitch.

! WARNINGCARBON MONOXIDE POISONING AND FIREHAZARD

Failure to follow safety warnings could result in personalinjury, death, and/or property damage.

This furnace is not designed for use in mobile homes,trailers or recreational vehicles.

! CAUTIONCUT HAZARD

Failure to follow this caution may result in damagepersonal injury.

Sheet metal parts may have sharp edges or burrs. Usecare and wear appropriate protective clothing, safetyglasses and gloves when handling parts and servicingfurnaces.

Page 3: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07 3Specifications subject to change without notice.

START−UP, ADJUSTMENT, AND SAFETYCHECK

NOTICEIMPORTANT INSTALLATION AND START−UPPROCEDURES

Failure to follow this procedure may result in a nuisancesmoke or odor complaint.

The manifold pressure, gas rate by meter clocking,temperature rise and operation must be checked afterinstallation. Minor smoke and odor may be presenttemporarily after start−up from the manufacturing process.Some occupants are more sensitive to this minor smoke andodor. It is recommended that doors and windows be openduring the first heat cycle.

General1. Furnace must have a 115-v power supply properly

connected and grounded.NOTE: Proper polarity must be maintained for 115-v wiring.Control status indicator light flashes rapidly and furnacedoes not operate if polarity is incorrect or if the furnace is notgrounded.

2. Thermostat wire connections at terminals R, W, G,and Y must be made at 24-v terminal block onfurnace control.

3. Natural gas service pressure must not exceed 0.5psig (14- in. w.c., 1125 Pa), but must be no less than0.16 psig (4.5-in. w.c., 350 Pa).

4. Blower door must be in place to complete 115-v elec-trical circuit and supply power to the furnacecomponents.

UNIT OPERATION HAZARD

Failure to follow this caution may result in intermittentunit operation or performance satisfaction.

These furnaces are equipped with a manual reset limitswitch in burner assembly. This switch opens andshuts off power to the gas valve if an overheatcondition (flame rollout) occurs in the burnerassembly/enclosure. Correct inadequatecombustion−air supply, improper gas pressure setting,improper burner or gas orifice positioning, or improperventing condition before resetting switch. DO NOTjumper this switch.

CAUTION!

Before operating furnace, check flame rollout manual resetswitch for continuity. If necessary, press button to resetswitch.EAC-1 (115vac) terminal is energized whenever bloweroperates. HUM (24vac) terminal is only energized when thelow pressure switch (LPS) is closed on a call for heat.

Prime Condensate Trap with Water

CARBON MONOXIDE POISONING HAZARD

Failure to follow these warnings could result inpersonal injury or death.

Failure to use a properly configured trap or NOTwater-priming trap before operating furnace may allowpositive pressure vent gases to enter the structurethrough drain tube. Vent gases contain carbonmonoxide which is tasteless and odorless.

! WARNING

1. Remove upper and middle collector box drain plugsopposite of the condensate trap. (See Fig. 10)

2. Connect field-supplied 5/8-in. (16 mm) ID tube with at-tached funnel (see Fig. 10) to upper collector boxdrain connection.

3. Pour one quart (liter) of water into funnel/tube. Watershould run through collector box, overfill condensatetrap, and flow into open field drain.

4. Remove funnel; replace collector box drain plug.5. Connect field-supplied 5/8-in. (16 mm) ID tube to

middle collector box drain port.6. Pour one quart (liter) of water into funnel/tube. Water

should run through collector box, overfill condensatetrap, and flow into open field drain.

7. Remove funnel and tube from collector box andreplace collector box drain plug.

Purge Gas LinesIf not previously done, purge the lines after all connectionshave been made and check for leaks.

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personalinjury, death, and/or property damage.

Never purge a gas line into a combustion chamber.Never test for gas leaks with an open flame. Use acommercially available soap solution madespecifically for the detection of leaks to check allconnections. A fire or explosion may result causingproperty damage, personal injury or loss of life.

! WARNING

Adjustments

FIRE HAZARD

Failure to follow this warning could result in personalinjury, death and/or property damage.

DO NOT bottom out gas valve regulator adjustingscrew. This can result in unregulated manifoldpressure and result in excess overfire and heatexchanger failures.

! WARNING

Page 4: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

4 440 04 7101 07Specifications subject to change without notice.

FURNACE DAMAGE HAZARD

Failure to follow this caution may result in reducedfurnace life.

DO NOT redrill orifices. Improper drilling (burrs,out−of−round holes, etc.) can cause excessive burnernoise and misdirection of burner flames. This canresult in flame impingement of heat exchangers,causing failures. (See Fig. 1)

CAUTION!

BURNER ORIFICE

A93059

Fig. 1 − Orifice HoleFor proper operation and long term reliability the furnaceinput rate must be within +/−2 percent of input rate onfurnace rating plate, or as adjusted for altitude.The gas input rate on rating plate is for installations ataltitudes up to 2000 ft. (610 M).

NOTICEThe NATURAL GAS manifold pressure adjustments in Table4 compensate for BOTH altitude AND gas heating value. DONOT apply an additional de−rate factor to the pressuresshown in Table 4. The values in this Table and NOTreferenced to sea level; they are AS−MEASURED ATALTITUDE.

The heating content of natural gas at altitude may alreadyprovide for a reduction in capacity or altitude. Refer to Table4. No adjustments to the furnace may be necessary ataltitude for certain gas heating values.

Refer to the instructions provided in the factory-specifiedPropane conversion kit for instructions for setting gasmanifold pressures for Propane applications.

In the USA, the input rating for altitudes above 2000 ft. (610M) must be reduced by 2 percent for each 1000 ft. (305 M)above sea level refer to Table 2. The natural gas manifoldpressures in Table 4 adjust for BOTH altitude and naturalgas heating value.In Canada, the input rating must be reduced by 5 percent foraltitudes of 2000 ft. to 4500 ft. (610 to 1372 M) above sealevel. The natural gas manifold pressures in Table 4 adjustfor BOTH altitude and natural gas heating value.NOTE: For Canadian altitudes of 2000 to 4500 ft. (610 to1372 M), use USA altitudes of 2001 to 3000 ft. (611 to 914M) in Table 4.To adjust manifold pressure to obtain the proper input rate,first, determine if the furnace has the correct orifice installed.At higher altitudes or different gas heat contents, it may benecessary to change the factory orifice to a different orifice.Tables have been provided in the furnace installation

instructions to match the required orifice to the manifoldpressure to the heat content and specific gravity of the gas.To do this:

1. Obtain average yearly gas heat value (at installedaltitude) from local gas supplier.

2. Obtain average yearly gas specific gravity from localgas supplier.

3. Find installation altitude range for your installation inthe manifold pressure tables in Table 4.

4. Find closest natural gas heat value and specific grav-ity in Table 4. Follow heat value and specific gravitylines to point of intersection to find orifice size andlow-and high-heat manifold pressure settings forproper operation.

5. Check and verify burner orifice size in furnace.NEVER ASSUME ORIFICE SIZE. ALWAYS CHECKAND VERIFY.

NOTICEIf orifice hole appears damaged or it is suspected to havebeen redrilled, check orifice hole with a numbered drill bit ofcorrect size. Never redrill an orifice. A burr−free and squarelyaligned orifice hole is essential for proper flamecharacteristics.

6. Replace orifice with correct size, if required by Table4. Use only factory−supplied orifices. See EXAMPLE1.

EXAMPLE 1:0 - 2000 ft. (0 - 609.6M) altitudeHeating value = 1050 Btu/cu ft.Specific gravity = 0.62Therefore: Orifice No. 44

(Furnace is shipped with No. 44 orifices. In this example, allmain burner orifices are the correct size and do not need tobe changed to obtain proper input rate.)Manifold pressure: 3.4-in. w.c. (847 Pa).NOTE: To convert gas manifold Table pressures to Pascals,multiply the in.w.c. value by 249.1 Pa/in. w.c. (1 in. wc. =249.1 Pa).

Check Inlet Gas PressureThe inlet gas pressure must be checked with the furnaceoperating in maximum heat. This is necessary to make surethe inlet gas pressure does not fall below the minimumpressure of 4.5 in. w.c.

1. Make sure the gas supply is turned off to the furnaceand at the electric switch on the gas valve.

2. Remove the 1/8 in. NPT plug from the inlet pressuretap on the gas valve.

3. Connect a manometer to the inlet pressure tap on gasvalve.

4. Turn on furnace power supply.5. Turn gas supply manual shutoff valve to ON position.6. Turn furnace gas valve switch to ON position.7. Jumper R and W thermostat connections at the

furnace control board.8. When main burners ignite, confirm inlet gas pressure

is between 4.5 in. w.c. (1125 Pa) and 13.6 in. w.c.(3388 Pa).

9. Remove jumper across thermostat connections toterminate call for heat. Wait until the blower off delayis completed.

10. Turn furnace gas valve electric switch to OFFposition.

Page 5: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07 5Specifications subject to change without notice.

11. Turn gas supply manual shutoff valve to OFFposition.

12. Turn off furnace power supply.13. Remove manometer from the inlet pressure tap of the

gas valve.

FIRE HAZARDFailure to follow this warning could result in personalinjury, death, and/or property damage.Re−install manifold pressure tap plug in gas valve toprevent gas leak.

! WARNING

14. Apply pipe dope sparingly to end of inlet gas pipeplug and re−install in the gas valve.

Adjust Manifold Pressure1. Adjust manifold pressure to obtain proper gas input

rate. (See Fig. 3)a. Turn gas valve ON/OFF switch to OFF.b. Remove manifold pressure tap plug from gas valve.c. Connect a water column manometer or similar

device to manifold pressure tap.d. Turn gas valve ON/OFF switch to ON.e. Manually close blower door switch.f. Jumper R and W thermostat connections on control

to start furnace. (See Fig. 2)g. Remove regulator adjustment cap from gas valve

pressure regulator (See Fig. 3) and turn adjustingscrew (3/16 or smaller flat−tipped screwdriver)counterclockwise (out) to decrease input rate orclockwise (in) to increase input rate.

NOTICEDO NOT set low−heat manifold pressure less than 2.8−in.w.c. (697 Pa) or more than 3.8−in. w.c. (947 Pa) for naturalgas. If required manifold pressure is outside this range,change main burner orifices.

h. When correct input is obtained, replace cap thatconceals gas valve regulator adjustment screws.Main burner flame should be clear blue, almosttransparent (See Fig. 12)

i. Remove jumper R to W.j. Reinstall manifold pressure tap plug from gas valve.

2. Verify natural gas input rate by clocking meter.NOTE: Contact your HVAC distributor or gas supplier formetric gas meter Tables, if required.

a. Turn off all other gas appliances and pilots served bythe meter.

b. Jumper R to W.c. Run furnace for 3 minutes.d. Measure time (in sec) for gas meter to complete 1

revolution and note reading. The 2 or 5 cubic feet dialprovides a more accurate measurement of gas flow.

e. Refer to Table 3 for cubic ft. of gas per hr.f. Multiply gas rate cu ft./hr by heating value (Btuh/cu

ft.) to obtain input. If clocked rate does not matchrequired input from Step 1, increase manifoldpressure to increase input or decrease manifoldpressure to decrease input. Repeat steps b throughe until correct input is achieved. Re−install regulatorseal cap on gas valve.

g. If clocked rate does not match required input fromStep 1, increase manifold pressure to increaseinput or decrease manifold pressure to decreaseinput. Repeat steps b through e of Step 1 untilcorrect heat input is achieved. Re--install regulatorseal cap on gas valve.

3. Restore furnace to normal operating condition.

a. Turn gas valve ON/OFF switch to OFF.b. Remove water column manometer or similar

device from manifold pressure tap.c. Replace manifold pressure tap plug to gas valve.d. Turn gas valve ON/OFF switch to ON.e. Check for gas leaks and verify furnace operation

FIRE HAZARD

Failure to follow this warning could result in personalinjury, death, and/or property damage.

Reinstall manifold pressure tap plug in gas valve toprevent gas leak.

! WARNING

Page 6: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

6 440 04 7101 07Specifications subject to change without notice.

BLW

NU

ET

RA

LS

TATU

S C

OD

E LE

D

SEC-2 SEC-1

EAC-2 L2

FUSE 3-AMP

0.5 AMP@24VAC

HUM

TEST/TWIN

G C

om W

Y R

24V

120 180

90 150

BLOWER OFF-DELAY

CO

OL H

EAT

SPARE-1 SPARE-2 PR-1

L1

PL2 1

24-V THERMOSTATTERMINALS

3-AMP FUSE

LED OPERATION &DIAGNOSTIC LIGHT

115-VAC(L2)NEUTRALCONNECTIONS

COOLHEAT

SPARE-1

SPARE-2BLOWER SPEED

SELECTION TERMINALS

EAC-1 TERMINAL(115-VAC 1.0 AMP MAX.)

115 VAC (L1) LINEVOLTAGE CONNECTION

PL2-HOT SURFACEIGNITER & INDUCERMOTOR CONNECTOR

PL1-LOW VOLTAGE MAINHARNESS CONNECTOR

TRANSFORMER 24-VACCONNECTIONS

HUMIDIFIER TERMINAL(24-VAC 0.5 AMP MAX.)

TWINNING AND/ORCOMPONENT TEST

TERMINALBLOWER OFF-DELAY

J2

J2 JUMPER

PLT

PL1

SPARE-3

SPARE-3

1

A11619

Fig. 2 − Example of Single Stage Furnace ControlAdjust Temperature RiseNOTE: Blower door must be installed when takingtemperature rise reading. Leaving blower door off will resultin incorrect temperature measurements, due to possiblechanges in duct static pressure and airflow.

FURNACE DAMAGE HAZARD

Failure to follow this caution may result in:� Overheating the heat exchangers or

condensing flue gases in heat exchangerareas not designed for condensate.

� Shortened furnace life.� Component damage.

Temperature rise must be within limits specified onfurnace rating plate. Recommended operation is atmidpoint of rise range or slightly above.

CAUTION!

Jumper R to W to check gas-heat temperature rise. Do notexceed temperature rise ranges specified on unit ratingplate.This furnace must operate within the temperature riseranges specified on the furnace rating plate. Determine theair temperature as follows:

1. Place duct thermometers in return and supply ductsas close to furnace as possible. Be surethermometers do not “see” heat exchangers so thatradiant heat does not affect thermometer readings.This is particularly important with straight−run ducts.

2. When thermometer readings stabilize, subtractreturn−air temperature from supply−air temperature todetermine temperature rise.

If the temperature rise is outside this range, check thefollowing:

1. Gas input rate.2. Derate for altitude if applicable.3. Return and supply ducts for excessive restrictions

causing static pressures greater than 0.50−in. w.c.(125 Pa)

4. Adjust temperature rise by adjusting blower speed.� Increase blower speed to reduce temperature rise.� Decrease blower speed to increase temperature

rise.

Page 7: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07 7Specifications subject to change without notice.

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personalinjury or death.

Disconnect 115vac electrical power before changingspeed tap.

! WARNING

(Read following caution before changing taps).

UNIT DAMAGE HAZARD

To avoid operating outside the rise range and avoidcomponent damage:

Refer to the Air Delivery Tables to determine whichairflows and settings are allowed for proper heatingairflow. DO NOT use the highlighted settings forHeating airflow. The highlighted settings are to be usedfor Cooling and Continuous Fan ONLY.

CAUTION!

Change the blower speed taps as required to maintainproper temperature rise for Heating and Cooling asdescribed above. To change blower motor speed selectionsfor heating mode, remove blower motor lead from controlHEAT terminal(s). (See Fig. 2) Select desired blower motorspeed lead(s) from the other motor leads and relocateit/them to HEAT (heating blower tap) terminal(s). Reconnectoriginal lead on SPARE terminal.Adjust Blower Off Delay (Heat Mode)If desired, the main blower off time delay period may belengthened or shortened when operating in the heatingmode to provide greater comfort. For position and locationof jumpers on control center. (See Fig. 2 and Fig. 16)The blower off-delay has four adjustable settings from 90sec to 180 sec. (See Table 1) To change the blower offdelay setting, move the jumper from one set of pins on thecontrol to the pins used for the desired blower off delay.Factory blower off-delay setting is 120 sec.

Table 1 – Blower Off Delay Jumper PositionsPINS 1 AND 2 2 AND 3 3 AND 4 4 AND 5

Time (in sec.) 90 120 150 180

Adjust Cooling AirflowThe cooling airflow can be set from the remaining blowerspeed taps. Refer to the Air Delivery Tables in theseinstructions.

FURNACE OVERHEATING HAZARD

Failure to follow this caution may result in reducedfurnace life.

Recheck temperature rise. It must be within limitsspecified on the rating plate. Recommended operation isat the mid--point of rise range or slightly above.

CAUTION!

Adjust Thermostat Heat AnticipatorMechanical thermostat: Set thermostat heat anticipator tomatch the amp. draw of the electrical components in theR-W circuit. Accurate amp. draw readings can be obtainedat the wires normally connected to thermostat sub-baseterminals, R and W. The thermostat anticipator should NOTbe in the circuit while measuring current.

1. Remove thermostat from sub-base or from wall.2. Connect an amp. meter across the R and W

sub-base terminals or R and W wires at wall.3. Record amp. draw across terminals when furnace is

in low heat and after blower starts.

4. Set heat anticipator on thermostat per thermostatinstructions and install on sub-base or wall.

5. Install blower access door.Electronic thermostat: Set cycle rate for 3 cycles per hr.Check Safety ControlsThe flame sensor, gas valve, and pressure switch were allchecked in the Start−up procedure section as part of normaloperation.

1. Check Main Limit Switch This control shuts off combustion system andenergizes air−circulating blower motor, if furnaceoverheats. By using this method to check the temper-ature limit control, it can be established that the limit isfunctioning properly and that the limit will operate ifthere is a restricted return−air supply or motor failure.If the limit control does not function during this test,the cause must be determined and corrected.a. Run furnace for at least 5 minutes.b. Gradually block off return air with a piece of

cardboard or sheet metal until the limit trips.c. Unblock return air to permit normal circulation.d. Burners will re−light when furnace cools down.

2. Check Pressure Switch(es) This control proves operation of the draft inducerblower.a. Turn off 115−v power to furnace.b. Disconnect inducer motor lead wires from wire

harness.c. Turn on 115−v power to furnace.d. Set thermostat to “call for heat” and wait 1 minute.

When low pressure switch is functioning properly, hotsurface igniter should NOT glow and controldiagnostic light flashes a status code 31. If hotsurface igniter glows when inducer motor isdisconnected, shut down furnace immediately.

e. Determine reason low pressure switch did notfunction properly and correct condition.

f. Turn off 115−v power to furnace.g. Reconnect inducer motor wires, replace door, and

turn on 115−v power.h. Blower will run for 90 sec before beginning the call

for heat again.i. Furnace should ignite normally.

Checklist1. Put away tools and instruments. Clean up debris.2. Verify that the jumper is removed from the TEST/

TWIN terminal. Verify that there is nothing plugged in-to the PLT connector.

NOTE: If there is a jumper connector plugged into PLT,remove it and discard. (See Fig. 2)

3. Verify that the Blower/Heat Off Delay jumpers are setas desired. (See Fig. 2 and Fig. 16)

4. Verify that the blower (lower door in upflow position)and control (“Main” or upper door in upflow position)doors are properly installed.

5. Verify that the Status LED glows. If not, check that thepower supply is energized and that the blower door issecure. See Fig. 5 to interpret diagnostic codes.

6. Cycle test furnace with room thermostat to be surethat it operates properly with the room thermostat.Check all modes including Heat, Cool and Fan.

7. Check operation of accessories per manufacturer’sinstructions.

8. Review Owner’s Manual with owner.9. Attach literature packet to furnace.

Page 8: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

8 440 04 7101 07Specifications subject to change without notice.

Table 2 – Altitude Derate Multiplier for U.S.A.ALTITUDE PERCENT

OFDERATE

DERATEMULTIPLIER

FACTOR*FT. M

0–2000 0−610 0 1.002001–3000 610−914 4−6 0.953001–4000 914−1219 6−8 0.934001–5000 1219−1524 8−10 0.915001–6000 1524−1829 10−12 0.896001–7000 1829−2134 12−14 0.877001–8000 2134−2438 14−16 0.858001–9000 2438−2743 16−18 0.83

9001–10,000 2743−3048 18−20 0.81*Derate multiplier factors are based on midpoint altitude for altitude range.

ON/OFF Switch

Regulator Seal Cap

Regulator AdjustmentRegulator Seal Cap under Cap

1/2” NPT Outlet

1/8” NPT ManifoldPressure Tap

1/8” NPT InletPressure Tap

1/2” NPT Inlet

SINGLE-STAGE

A11153Fig. 3 − Gas Valve

R Y W G

10 TURNS

THERMOSTAT SUBBASETERMINALS WITHTHERMOSTAT REMOVED(ANITICIPATOR, CLOCK, ETC.,MUST BE OUT OF CIRCUIT.)

HOOK-AROUNDAMMETER

EXAMPLE: 5.0 AMPS ON AMMETER10 TURNS AROUND JAWS

= 0.5 AMPS FOR THERMOSTAT ANTICIPATOR SETTING

FROM UNIT 24-VCONTROL TERMINALS

A96316Fig. 4 − Amp. Draw Check with Ammeter

Table 3 – Gas Rate (CU ft./hr)SECONDS

FOR 1 REVOLUTIONSIZE OF TEST DIAL SECONDS

FOR 1 REVOLUTIONSIZE OF TEST DIAL

1 Cu Ft. 2 Cu Ft. 5 Cu Ft. 1 Cu Ft. 2 Cu Ft. 5 Cu Ft.10 360 720 1800 50 72 144 36011 327 655 1636 51 71 141 35512 300 600 1500 52 69 138 34613 277 555 1385 53 68 136 34014 257 514 1286 54 67 133 33315 240 480 1200 55 65 131 32716 225 450 1125 56 64 129 32117 212 424 1059 57 63 126 31618 200 400 1000 58 62 124 31019 189 379 947 59 61 122 30520 180 360 900 60 60 120 30021 171 343 857 62 58 116 29022 164 327 818 64 56 112 28123 157 313 783 66 54 109 27324 150 300 750 68 53 106 26525 144 288 720 70 51 103 25726 138 277 692 72 50 100 25027 133 267 667 74 48 97 24328 129 257 643 76 47 95 23729 124 248 621 78 46 92 23130 120 240 600 80 45 90 22531 116 232 581 82 44 88 22032 113 225 563 84 43 86 21433 109 218 545 86 42 84 20934 106 212 529 88 41 82 20535 103 206 514 90 40 80 20036 100 200 500 92 39 78 19637 97 195 486 94 38 76 19238 95 189 474 96 38 75 18839 92 185 462 98 37 74 18440 90 180 450 100 36 72 18041 88 176 439 102 35 71 17842 86 172 429 104 35 69 17343 84 167 419 106 34 68 17044 82 164 409 108 33 67 16745 80 160 400 110 33 65 16446 78 157 391 112 32 64 16147 76 153 383 116 31 62 15548 75 150 375 120 30 60 15049 73 147 367

Page 9: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07 9Specifications subject to change without notice.

338309-201 Rev. E

A11602

Fig. 5 − Service Label Information

Page 10: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

10 440 04 7101 07Specifications subject to change without notice.

Table 4 – Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate

SAGLARUTANFOYTIVARGCIFICEPSSAG.GVAHEAT VALUE 0.58 0.60 0.62 0.64AT ALTITUDE Orifice Manifold Orifice Manifold Orifice Manifold Orifice Manifold

(Btu/cu ft) No. Pressure No. Pressure No. Pressure No. Pressure

900 43 3.8 42 3.2 42 3.3 42 3.4

0 925 43 3.6 43 3.7 43 3.8 42 3.2

(0) 950 43 3.4 43 3.5 43 3.6 43 3.7

975 44 3.7 44 3.8 43 3.4 43 3.6

to 1000 44 3.5 44 3.6 44 3.8 43 3.4

1025 44 3.3 44 3.5 44 3.6 44 3.72000 1050 44 3.2 44 3.3 44 3.4 44 3.5(610) 1075 45 3.7 45 3.8 44 3.3 44 3.4

1100 46 3.7 46 3.8 45 3.8 44 3.2U.S.A. 800 42 3.4 42 3.5 42 3.6 42 3.7

2001 (611) 825 43 3.8 42 3.3 42 3.4 42 3.5

to 850 43 3.6 43 3.7 42 3.2 42 3.3

3000 (914) 875 43 3.4 43 3.5 43 3.7 43 3.8

900 44 3.7 44 3.8 43 3.5 43 3.6

Canada 925 44 3.5 44 3.6 44 3.8 43 3.4

2001 (611) 950 44 3.3 44 3.4 44 3.6 44 3.7to 975 44 3.2 44 3.3 44 3.4 44 3.5

4500 (1372) 1000 44 3.0 44 3.1 44 3.2 44 3.3775 42 3.3 42 3.4 42 3.5 42 3.6

3001 800 43 3.8 42 3.2 42 3.3 42 3.4

(915) 825 43 3.6 43 3.7 43 3.8 42 3.2

850 44 3.8 43 3.5 43 3.6 43 3.7

875 44 3.6 44 3.7 43 3.4 43 3.5

4000 900 44 3.4 44 3.5 44 3.7 44 3.8(1219) 925 44 3.2 44 3.4 44 3.5 44 3.6

950 44 3.1 44 3.2 44 3.3 44 3.4750 42 3.3 42 3.4 42 3.5 42 3.6

4001 775 43 3.7 43 3.8 42 3.3 42 3.4

(1220) 800 43 3.5 43 3.6 43 3.7 43 3.8

825 44 3.8 43 3.4 43 3.5 43 3.6

850 44 3.5 44 3.7 44 3.8 43 3.4

5000 875 44 3.3 44 3.5 44 3.6 44 3.7(1524) 900 44 3.2 44 3.3 44 3.4 44 3.5

925 44 3.0 44 3.1 44 3.2 44 3.3725 42 3.2 42 3.3 42 3.4 42 3.5

5001 750 43 3.7 43 3.8 42 3.2 42 3.3

(1525) 775 43 3.4 43 3.5 43 3.7 43 3.8

800 44 3.7 44 3.8 43 3.4 43 3.5

825 44 3.5 44 3.6 44 3.7 44 3.86000 850 44 3.3 44 3.4 44 3.5 44 3.6

(1829) 875 44 3.1 44 3.2 44 3.3 44 3.4900 44 2.9 44 3.0 44 3.1 44 3.2675 42 3.4 42 3.5 42 3.6 42 3.8

6001 700 42 3.2 42 3.3 42 3.4 42 3.5

(1830) 725 43 3.6 43 3.7 43 3.8 42 3.3

750 43 3.4 43 3.5 43 3.6 43 3.7

775 44 3.6 44 3.7 43 3.4 43 3.5

7000 800 44 3.4 44 3.5 44 3.6 44 3.7(2133) 825 44 3.2 44 3.3 44 3.4 44 3.5

850 44 3.0 44 3.1 44 3.2 44 3.3

to

to

to

to

ALTITUDERANGE

ft (m)

U.S

.A.a

ndC

anad

a

SINGLE-STAGE FURNACE(TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL)

U.S

.A.O

nly

U.S

.A.O

nly

U.S

.A.O

nly

U.S

.A.O

nly

U.S

.A.a

ndC

anad

a

A11253A

Page 11: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07 11Specifications subject to change without notice.

Table 4 − Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate (Cont.)

SAGLARUTANFOYTIVARGCIFICEPSSAG.GVAHEAT VALUE 0.58 0.60 0.62 0.64AT ALTITUDE Orifice Manifold Orifice Manifold Orifice Manifold Orifice Manifold

(Btu/cu ft) No. Pressure No. Pressure No. Pressure No. Pressure

ALTITUDERANGE

ft (m)

SINGLE-STAGE FURNACE(TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL)

650 42 3.4 42 3.5 42 3.6 42 3.7

7001 675 43 3.8 42 3.2 42 3.3 42 3.4

(2134) 700 43 3.5 43 3.7 43 3.8 42 3.2

725 44 3.8 43 3.4 43 3.5 43 3.6

750 44 3.5 44 3.7 44 3.8 43 3.4

8000 775 44 3.3 44 3.4 44 3.5 44 3.7(2438) 800 44 3.1 44 3.2 44 3.3 44 3.4

825 44 2.9 44 3.0 44 3.1 44 3.2625 42 3.4 42 3.5 42 3.6 42 3.7

8001 650 43 3.8 42 3.2 42 3.3 42 3.4

(2439) 675 43 3.5 43 3.6 43 3.7 42 3.2

700 44 3.7 43 3.4 43 3.5 43 3.6

725 44 3.5 44 3.6 44 3.7 44 3.89000 750 44 3.3 44 3.4 44 3.5 44 3.6

(2743) 775 44 3.0 44 3.2 44 3.3 44 3.49001 600 42 3.3 42 3.4 42 3.6 42 3.7

(2744) 625 43 3.7 42 3.2 42 3.3 42 3.4

650 43 3.5 43 3.6 43 3.7 43 3.8

675 44 3.7 44 3.8 43 3.4 43 3.5

10000 700 44 3.4 44 3.5 44 3.7 44 3.8(3048) 725 44 3.2 44 3.3 44 3.4 44 3.5

* Orifice numbers shown in BOLD are factory-installed.

to

to

to

U.S

.A.O

nly

U.S

.A.O

nly

U.S

.A.O

nly

A11253B

Page 12: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

12 440 04 7101 07Specifications subject to change without notice.

SERVICE AND MAINTENANCEPROCEDURESUntrained personnel can perform basic maintenance func-tions such as cleaning and replacing air filters. All other opera-tions must be performed by trained service personnel. A quali-fied service person should inspect the furnace once a year.

FIRE, INJURY OR DEATH HAZARDFailure to follow this warning could result in personalinjury, death and/or property damage.The ability to properly perform maintenance on thisequipment requires certain knowledge, mechanicalskills, tools, and equipment. If you do not possessthese, do not attempt to perform any service andmaintenance on this equipment other than thoseprocedures recommended in the Owner’s Manual.

! WARNING

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmentalpollution.

Remove and recycle all components or materials (i.e. oil,refrigerant, control board, etc.) before unit final disposal.

CAUTION!

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personalinjury or death, or property damage.

Before installing, modifying, or servicing system, mainelectrical disconnect switch must be in the OFF positionand install a lockout tag. There may be more than onedisconnect switch. Lock out and tag switch with asuitable warning label. Verify proper operation afterservicing.

! WARNING

ELECTRICAL OPERATION HAZARD

Failure to follow this caution may result in improperfurnace operation or failure of furnace.

Label all wires prior to disconnection when servicingcontrols. Wiring errors can cause improper anddangerous operation.

CAUTION!

GeneralThese instructions are written as if the furnace is installed inan upflow application. An upflow furnace application iswhere the blower is located below the combustion andcontrols section of the furnace, and conditioned air isdischarged upward. Since this furnace can be installed inany of the 4 positions shown in Fig. 6, you must revise yourorientation to component location accordingly.Electrical Controls and WiringPressure SwitchesEach pressure switch is labeled with the reference location(noted as “COLLECTOR BOX−LPS” or “HOUSING−HPS”ON THE SWITCH). The nominal break point of each switchis shown on the label below the reference location in inchesof water column, “W.C.” The maximum and minimum breakpoint of the switch is +/− 0.05 inches of water column fromthe nominal break point of the switch. The maximum makepoint of the switch is 0.10 inches of water above themaximum break point of the switch

Example: Nominal break point on pressure switch is0.68−in. W.C. The minimum break point of the switch is0.63−in. W.C. The maximum break point of the switch is0.73−in. W.C. The maximum make point of the switch is0.83−in. W.C.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personalinjury or death.

There may be more than one electrical supply to thefurnace. Check accessories and cooling unit foradditional electrical supplies that must be shut offduring furnace servicing. Lock out and tag switch witha suitable warning label.

! WARNING

The electrical ground and polarity for 115−v wiring must beproperly maintained. Refer to Fig. 7 for field wiringinformation and to Fig. 16 for furnace wiring information.NOTE: If the polarity is not correct, the STATUS LED on thecontrol will flash rapidly and prevent the furnace fromheating. The control system also requires an earth groundfor proper operation of the control and flame−sensingelectrode.The 24−v circuit contains an automotive−type, 3−amp. fuselocated on the control. (See Fig. 2) Any shorts of the 24−vwiring during installation, service, or maintenance will causethis fuse to blow. If fuse replacement is required, use ONLYa 3−amp. fuse. The control LED will display status code 24when fuse needs to be replaced.TroubleshootingRefer to the service label. (See Fig. 5—Service Label)The Troubleshooting Guide (See Fig. 15) can be a usefultool in isolating furnace operation problems. Beginning withthe word “Start,” answer each question and follow theappropriate arrow to the next item.The Guide will help to identify the problem or failedcomponent. After replacing any component, verify correctoperation sequence.Proper instrumentation is required to service electricalcontrols. The control in this furnace is equipped with aStatus Code LED (Light−Emitting Diode) to aid ininstallation, servicing, and troubleshooting. Status codescan be viewed at the indicator in blower door. The amberfurnace control LED is either ON continuously, rapidflashing, or a code composed of 2 digits. The first digit is thenumber of short flashes, the second digit is the number oflong flashes.For an explanation of status codes, refer to service labellocated on control door or Fig. 5, and the troubleshootingguide which can be obtained from your distributor.Retrieving Stored Fault CodesNOTE: Fault codes cannot be retrieved if a thermostatsignal (24-v on W, Y, G, etc) is present, or if any delays suchas blower off-delays are active.The stored status codes will NOT be erased from the controlmemory when 115- or 24-v power is interrupted. See theService Label (Fig. 5) for more information. The most recentfault code may be retrieved as follows:

1. Leave 115-v power connected to furnace.2. Observe the status LED through the blower door (the

lower door on upflow applications) indicator. Refer tothe Service Label (Fig. 5) to interpret the LED.

3. Remove the Main/Control door (the upper door onupflow installations).

4. BRIEFLY (2−3 seconds) disconnect and reconnectONE of the main limit wires.

5. The LED will flash the last stored fault code. Refer tothe Service Label (Fig. 5) to interpret the LED.

6. A component test sequence will follow.7. Reinstall the Main/Control door.

Page 13: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07 13Specifications subject to change without notice.

THE BLOWER IS LOCATEDTO THE RIGHT OF THE

BURNER SECTION, ANDAIR CONDITIONED AIR IS

DISCHARGED TO THE LEFT.

THE BLOWER ISLOCATED BELOW THE

BURNER SECTION, ANDCONDITIONED AIR IS

DISCHARGED UPWARD.

THE BLOWER ISLOCATED ABOVE THE

BURNER SECTION, ANDCONDITIONED AIR IS

DISCHARGED DOWNWARD

THE BLOWER ISLOCATED TO THE LEFT

OF THE BURNER SECTION,AND CONDITIONED AIR IS

DISCHARGED TO THE RIGHT.

A02097

Fig. 6 − Multipoise Orientations

115-V FIELD-SUPPLIED

DISCONNECT

AUXILIARYJ-BOX

24-VTERMINAL

BLOCK

THREE-WIREHEATING-ONLY

FIVE WIRE

NOTE 1

NOTE 2FIELD-SUPPLIEDDISCONNECT

CONDENSINGUNIT

TWOWIRE

FURNACE

CONTROL

R

G

COM

W C R G Y

GND

GND

FIELD 24-V WIRINGFIELD 115-, 208/230-, 460-V WIRINGFACTORY 24-V WIRINGFACTORY 115-V WIRING

208/230- OR460-VTHREEPHASE

208/230-VSINGLEPHASE

BLOWER DOOR SWITCH

WHT

BLK

WHT

BLK

NOTES: Connect Y-terminal in furnace as shown for proper blower operation.Some thermostats require a "C" terminal connection as shown.If any of the original wire, as supplied, must be replaced, usesame type or equivalent wire.

W

Y

GND

THERMOSTATTERMINALS

1.2.3.

A11387

Fig. 7 − Typical Single−Stage Wiring Diagram

Component Self-TestNOTE: The furnace control component test allows allcomponents to run for a short time; except the gas valveand humidifier terminal HUM are not energized. The EAC-1terminal is energized when the blower is energized. Thisfeature helps diagnose a system problem in case of acomponent failure. The component test feature will notoperate if any thermostat signal is present at the control andnot until all time delays are completed.To Begin Component Self-Test:

1. Remove blower access door.2. Disconnect the thermostat R lead from furnace

control.3. Manually close blower door switch.

Caution must be taken when manually closing this switch forservice purposes.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personalinjury, or death.

Blower door switch opens 115−v power to furnacecontrol. No component operation can occur unlessswitch is closed. Exercise caution to avoid electricalshock from exposed electrical components whenmanually closing this switch for service purposes.

! WARNING

Page 14: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

14 440 04 7101 07Specifications subject to change without notice.

4. For approximately 2 sec, short (jumper) the COM-24vterminal on control to the TEST/TWIN 3/16—in. (5mm) quick-connect terminal on control until the LEDgoes off. Remove jumper from terminals. (See Fig. 2)

NOTE: If TEST/TWIN and COM-24v terminals arejumpered longer than 2 sec, LED will flash rapidly andignore component test request.Component test sequence is as follows:

a. LED will display previous status code 4 times.b. Inducer motor starts and continues to run until Step

f of component test sequence.c. After 7 sec the hot surface igniter is energized for

15 sec., then off.d. Blower motor operates on HEAT speed for 10 sec.e. Blower motor operates on COOL speed for 10 sec.f. Inducer motor stops.

5. Reconnect R lead to furnace control, remove tapefrom blower door switch, and re-install blower door.

6. Verify furnace shut down by lowering thermostatsetting below room temperature.

7. Verify that furnace restarts by raising thermostatsetting above room temperature.

Checklist1. Put away tools and instruments. Clean up debris.2. Verify that the jumper is removed from the TEST/

TWIN terminal. Verify that there is nothing pluggedinto the PLT connector. (Note: If there is a jumperconnector plugged into PLT, remove it and discard.)(See Fig. 2)

3. Verify that the Blower/Heat Off Delay jumpers are setas desired. (See Fig. 2)

4. Verify that the blower and control (“Main”) doors areproperly installed.

5. Verify that the Status LED glows. If not, check that thepower supply is energized and that the blower door issecure. (See Fig. 5)

6. Cycle test furnace with room thermostat to be surethat it operates properly with the room thermostat.Check all modes including Heat, Cool and Fan.

7. Check operation of accessories per manufacturer’sinstructions.

8. Review Owner’s Manual with owner.9. Attach entire literature packet to furnace.

Care and Maintenance

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personalinjury, death and/or property damage.

Never store flammable or combustible materials on,near, or in contact with the furnace, such as:

1. Spray or aerosol cans, rags, brooms, dustmops, vacuum cleaners, or other cleaningtools.

2. Soap powders, bleaches, waxes or othercleaning compounds, plastic or plasticcontainers, gasoline, kerosene, cigarette lighterfluid, dry cleaning fluids, or other volatile fluids.

3. Paint thinners and other painting compounds,paper bags, or other paper products. Exposureto these materials could lead to corrosion of theheat exchangers.

! WARNING

For continuing high performance and to minimize possiblefurnace failure, periodic maintenance must be performed on

this furnace. Consult your local dealer about properfrequency of maintenance and the availability of amaintenance contract.

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personalinjury, death, and/or property damage.

Turn off the gas and electrical supplies to the furnaceand install lockout tag before performing anymaintenance or service. Follow the operatinginstructions on the label attached to the furnace.

! WARNING

CARBON MONOXIDE POISONING AND FIREHAZARD

Failure to follow this warning could result in personalinjury, death and/or property damage.

Never operate furnace without a filter or filtrationdevice installed. Never operate a furnace with filter orfiltration device access doors removed.

! WARNING

CUT HAZARD

Failure to follow this caution may result in personalinjury.

Sheet metal parts may have sharp edges or burrs.Use care and wear appropriate protective clothing,safety glasses and gloves when handling parts, andservicing furnaces.

CAUTION!

The minimum maintenance on this furnace is as follows:1. Check and clean air filter each month or more

frequently if required. Replace if torn.2. Check blower motor and wheel for cleanliness each

heating and cooling season. Clean as necessary.3. Check electrical connections for tightness and

controls for proper operation each heating season.Service as necessary.

4. Inspect burner compartment before each heatingseason for rust, corrosion, soot or excessive dust. Ifnecessary, have furnace and burner serviced by aqualified service agency.

5. Inspect the vent pipe/vent system before eachheating season for water leakage, sagging pipes orbroken fittings. Have vent pipes/vent system servicedby a qualified service agency.

6. Inspect any accessories attached to the furnace suchas a humidifier or electronic air cleaner. Perform anyservice or maintenance to the accessories asrecommended in the accessory instructions.

Cleaning and/or Replacing Air FilterThe air filter type may vary depending on the application ororientation. The filter is external to the furnace casing. Thereare no provisions for an internal filter with this furnace. See“Filter Arrangement” under the “Installation” section of thismanual.

Page 15: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07 15Specifications subject to change without notice.

CARBON MONOXIDE POISONING AND FIREHAZARD

Failure to follow this warning could result in personalinjury, death and/or property damage.

Never operate furnace without a filter or filtrationdevice installed. Never operate a furnace with filter orfiltration device access doors removed.

! WARNING

NOTE: If the filter has an airflow direction arrow, the arrowmust point toward the blower. To clean or replace filters, proceed as follows:

ELECTRICAL SHOCK, FIRE OR EXPLOSIONHAZARD

Failure to follow this warning could result in personalinjury or death, or property damage.

Before installing, modifying, or servicing system, mainelectrical disconnect switch must be in the OFFposition and install a lockout tag. There may be morethan one disconnect switch. Lock out and tag switchwith a suitable warning label. Verify proper operationafter servicing.

! WARNING

1. Turn off electrical supply to furnace.2. Remove filter cabinet door.3. Slide filter out of cabinet.4. If equipped with permanent, washable filter, clean

filter by spraying cold tap water through filter inopposite direction of airflow. Rinse filter and let dry.Oiling or coating of the filter is not recommended.

5. If equipped with factory specified disposable mediafilter, replace only with a factory specified media filterof the same size.

6. Slide filter into cabinet.7. Replace filter cabinet door.8. Turn on electrical supply to furnace.

Blower Motor and Wheel MaintenanceTo ensure long life, economy, and high efficiency, cleanaccumulated dirt and grease from blower wheel and motorannually.The inducer and blower motors are pre−lubricated andrequire no additional lubrication. These motors can beidentified by the absence of oil ports on each end of themotor.The following items should be performed by a qualifiedservice technician. Clean blower motor and wheel asfollows:

1. Turn off electrical supply to furnace.2. Remove blower door.3. All factory wires can be left connected, but field

thermostat and accessory wiring may need to bedisconnected depending on their length and routing.

4. If the vent and combustion air pipe passes throughthe blower compartment, it will be necessary toremove the pipes from the blower compartment.

Disconnect the vent and combustion air pipe by:a. Loosen the clamps on the vent couplings and

combustion air pipe external to the furnace.

b. Separate the pipes from the couplings and movethem aside.

c. Loosen the clamps on the vent couplings andcombustion air pipe located on the blower shelf.

d. Separate the pipes from the blower compartmentand set aside.

e. Remove the couplings from the pipe adapters andset aside.

f. After servicing the blower, reverse steps a throughe.

g. Tighten all clamps 15 lb −in.See Fig. 13 for steps 5 through 14.

5. Remove screws securing blower assembly to blowershelf and slide blower assembly out of furnace.Detach ground wire and disconnect blower motorharness plugs from blower motor.

NOTE: Blower wheel is fragile. Use care.6. Clean blower wheel and motor by using a vacuum

with soft brush attachment. Be careful not to disturbbalance weights (clips) on blower wheel vanes. Donot bend wheel or blades as balance will be affected.

7. If greasy residue is present on blower wheel, removewheel from the blower housing and wash it with anappropriate degreaser. To remove wheel:a. Mark blower wheel location on shaft before

disassembly to ensure proper reassembly.b. Loosen setscrew holding blower wheel on motor

shaft.NOTE: Mark blower mounting arms and blower housing soeach arm is positioned at the same hole location duringreassembly.

c. Mark blower wheel orientation and cutoff platelocation to ensure proper reassembly.

d. Remove screws securing cutoff plate and removecutoff plate from housing.

e. Remove bolts holding motor mounts to blowerhousing and slide motor and mounts out of housing.

f. Remove blower wheel from housing.g. Clean wheel per instructions on degreaser cleaner.

Do not get degreaser in motor.8. Reassemble motor and blower wheel by reversing

items 7b through 7f. Ensure wheel is positioned forproper rotation.

9. Torque motor mounting bolts to 40 +/− 10 lb−in. whenreassembling.

10. Torque blower wheel set screw to 160 +/− 20 lb−in.when reassembling.

11. Verify that blower wheel is centered in blower housingand set screw contacts the flat portion of the motorshaft. Loosen set screw on blower wheel andreposition if necessary.

12. Spin the blower wheel by hand to verify that the wheeldoes not rub on the housing.

13. Reinstall blower assembly in furnace.14. Reinstall 2 screws securing blower assembly to

blower deck.15. Reconnect blower leads to furnace control. Refer to

furnace wiring diagram, and connect thermostat leadsif previously disconnected.

NOTE: Be sure to attach ground wire and reconnect blowerharness plugs to blower motor.

Page 16: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

16 440 04 7101 07Specifications subject to change without notice.

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personalinjury or death.

Blower door switch opens 115−v power to control. Nocomponent operation can occur unless switch is closed.Caution must be taken when manually closing thisswitch for service purposes.

! WARNING

16. Downflow or horizontal furnaces with vent pipethrough furnace only:a. Install and connect short piece of vent pipe inside

furnace to existing vent.b. Connect vent connector to vent elbow.

17. Turn on electrical supply. Manually close blower doorswitch. Use a piece of tape to hold switch closed.Check for proper rotation and speed changesbetween heating and cooling by jumpering R to G andR to Y/Y2 on furnace control thermostat terminals. Ifoutdoor temperature is below 70�F (21�C), turn offcircuit breaker to outdoor unit before running furnacein the cooling cycle. Turn outdoor circuit breaker onafter completing cooling cycle. (See Fig. 2)

NOTE: If R−W/W1 thermostat terminals are jumpered at thetime blower door switch is closed, blower will run for 90 secbefore beginning a heating cycle.

a. Perform component self−test as shown at the bottomof the SERVICE label, located on the control door.

b. Verify blower is rotating in the correct direction18. If furnace is operating properly, RELEASE BLOWER

DOOR SWITCH. Remove any jumpers or reconnectany disconnected thermostat leads. Replace blowerdoor.

19. Turn on gas supply and cycle furnace through onecomplete heating cycle. Verify the furnacetemperature rise as shown in Adjustments Section.Adjust temperature rise as shown in AdjustmentsSection.

Cleaning Burners and Flame SensorThe following items must be performed by a qualifiedservice technician. If the burners develop an accumulationof light dirt or dust, they may be cleaned by using thefollowing procedure:NOTE: Use a back-up wrench on the gas valve to preventthe valve from rotating on the manifold or damaging themounting to the burner assembly.

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personalinjury, death, and/or property damage.

Turn off the gas and electrical supplies to the furnaceand install lockout tag before performing anymaintenance or service. Follow the operatinginstructions on the label attached to the furnace.

! WARNING

Refer to Fig. 14.1. Disconnect power at external disconnect, fuse or

circuit breaker.2. Turn off gas at external shut-off or gas meter.3. Remove control door and set aside.4. Turn electric switch on gas valve to OFF.

5. Disconnect the gas pipe from gas valve and removepipe from the furnace casing.

6. Remove individual wires from terminals on gas valve.7. Disconnect Hot Surface Igniter (HSI) wires from HSI.8. Disconnect Flame Sensor wire from Flame Sensor.9. Support the manifold and remove the 4 screws that

secure the manifold assembly to the burner assemblyand set aside. Note the location of the green/yellowwire and ground terminal.

10. Inspect the orifices in the manifold assembly forblockages or obstructions. Remove orifice and cleanor replace orifice.

11. Remove the four screws that attach the top plate ofthe casing to the furnace.

12. Raise top plate up slightly and prop it up with a smallpiece of wood or folded cardboard.

13. Support the burner assembly and remove the screwsthat attach the burner assembly to the heatexchanger cell panel.

14. Remove wires from both rollout switches.15. Slide one--piece burner out of slots on sides of burner

assembly.16. Remove the flame sensor from the burner assembly.17. (Optional) Remove the Hot Surface Igniter (HSI) and

bracket from the burner assembly.18. Check igniter resistance. Nominal resistance is 40 to

70 ohms at room temperature and is stable over thelife of the igniter.

19. Clean burner with a brush and a vacuum.20. Clean the flame sensor with fine steel wool (0000

grade). Do not use sand paper or emery cloth.To reinstall burner assembly:

1. Install the Hot Surface Igniter (HSI) and bracket inburner assembly.

2. Install flame sensor on burner.3. Align the edges of the one-piece burner with the slots

in the burner assembly and slide the burners forwarduntil they are fully seated in the burner assembly.

4. Align the orifices in the manifold assembly with thesupport rings on the end of the burner.

5. Insert the orifices in the support rings of the burners.NOTE: If manifold does not fit flush against the burner, donot force the manifold on the burner assembly. The burnersare not fully seated forward in the burner assembly. Removethe manifold and check burner positioning in the burnerassembly assembly before re-installing the manifold.

6. Attach the green/yellow wire and ground terminal toone of the manifold mounting screws.

7. Install the remaining manifold mounting screws.8. Check the igniter alignment. See Fig. 8, 9 and 14.9. Attach the wires to the roll-out switches.

10. Align the burner assembly with the openings in theprimary cell inlet panel and attach the burnerassembly to the cell panel.

11. Connect the wire for the flame sensor.12. Connect the wire for the Hot Surface Igniter.

NOTE: Use propane-resistant pipe dope to prevent leaks.Do not use Teflon tape.

13. Install the gas pipe to the gas valve.

Page 17: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07 17Specifications subject to change without notice.

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personalinjury, death, and/or property damage.

Never purge a gas line into a combustion chamber.Never test for gas leaks with an open flame. Use acommercially available soap solution madespecifically for the detection of leaks to check allconnections. A fire or explosion may result causingproperty damage, personal injury or loss of life.

! WARNING

14. Check for gas leaks with a commercially availablesoap solution made specifically for the detection ofleaks.

15. Turn gas on at electric switch on gas valve and atexternal shut-off or meter

16. Turn power on at external disconnect, fuse or circuitbreaker.

17. Run the furnace through two complete heating cyclesto check for proper operation

18. Install control door when complete.Servicing Hot Surface IgniterThe igniter does NOT require annual inspection. Checkigniter resistance before removal. Refer to Fig. 8, 9 and 14.

1. Turn off gas and electrical supplies to furnace.2. Remove control door.3. Disconnect igniter wire connection.4. Check igniter resistance. Igniter resistance is affected

by temperature. Only check resistance when theigniter is at room temperature.a. Using an ohm meter, check resistance across both

igniter leads in connector.b. Cold reading should be between 40 ohms and 70

ohms.5. Remove igniter assembly.

a. Using a 1/4−in. driver, remove the two screwssecuring the igniter mounting bracket to the burnerassembly (See Fig. 14 )

b. Carefully withdraw the igniter and bracket assemblythrough the front of the burner assembly withoutstriking the igniter on surrounding parts.

c. Inspect igniter for signs of damage or failure.d. If replacement is required, remove the screw that

secures the igniter on igniter bracket and remove theigniter.

6. To replace igniter and bracket assembly, reverseitems 5a through 5d.

7. Reconnect igniter harness to the igniter, dressing theigniter wires to ensure there is no tension on theigniter itself. (See Fig. 14)

8. Turn on gas and electrical supplies to furnace.9. Verify igniter operation by initiating control board self−

test feature or by cycling thermostat.10. Replace control door.

Flushing Collector Box and Drainage System

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personalinjury, death, and/or property damage.

Turn off the gas and electrical supplies to the furnaceand install lockout tag before performing anymaintenance or service. Follow the operatinginstructions on the label attached to the furnace.

! WARNING

1. Turn off gas and electrical supplies to furnace.2. Remove control door.3. Disconnect pressure switch tube from pressure

switch port.NOTE: Ensure the pressure switch tube disconnected fromthe pressure switch is higher than the collector box openingor water will flow out of tube.

4. Remove the collector box plug from the top port onthe upper corner of the collector box. (See Fig. 10)

5. Attach a funnel with a flexible tube to port on thecollector box.

6. Flush inside of collector box with water until dischargewater from condensate trap is clean and runs freely.

7. Repeat steps 4 thru 6 with middle plug on uppercorner of collector box.

8. Remove the pressure switch tube from the collectorbox.

NOTE: Do NOT blow into tube with tube connected to thepressure switch.

9. Clean pressure switch port on collect box with a smallwire. Shake any water out of pressure switch tube.

10. Reconnect tube to pressure switch and pressureswitch port.

11. Remove the relief tube from the port on the collectorbox and the trap.

12. Clean the relief port on collect box and the trap with asmall wire. Shake any water out of the tube.

13. Reconnect relief tube to trap and collector box ports.Cleaning Condensate Drain and TrapNOTE: If the condensate trap is removed, a new gasketbetween the trap and collector box is required. Verify acondensate trap gasket is included in the service kit orobtain one from your local distributor.

1. Disconnect power at external disconnect, fuse orcircuit breaker.

2. Turn off gas at external shut-off or gas meter.3. Remove control door and set aside.4. Turn electric switch on gas valve to OFF.5. Disconnect external drain from condensate drain

elbow or drain extension pipe inside the furnace andset aside.

6. Disconnect the condensate trap relief hose fromcollector box port and condensate trap.

NOTE: If condensate has a heat pad attached to the trap,trace the wires for the pad back to the connection point anddisconnect the wires for the heat pad.

7. Remove the screw that secures the condensate trapto the collector box, remove the trap and set aside.

8. Remove the trap gasket from the collector box if it didnot come off when the trap was removed.

9. Discard the old trap gasket.10. Rinse condensate trap in warm water until trap is

clean.

Page 18: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

18 440 04 7101 07Specifications subject to change without notice.

11. Flush condensate drain lines with warm water.Remember to check and clean the relief port on thecollector box.

12. Shake trap dry.13. Clean port on collector box with a small wire.

To re-install Condensate Drain and Trap:1. Remove adhesive backing from condensate trap

gasket2. Install gasket on collector box3. Align the condensate trap with the drain opening on

the collector box and secure the trap with the screw4. Attach the relief hose to the relief port on the

condensate trap and collector box.5. Secure tubing to prevent any sags or traps in the

tubing.6. Connect condensate drain elbow or drain extension

elbow to the condensate trap7. Connect the leads of the condensate heat pad (if

used)8. Connect external drain piping to the condensate drain

elbow or drain extension pipe.9. Turn gas on at electric switch on gas valve and at

external shut-off or meter10. Turn power on at external disconnect, fuse or circuit

breaker.11. Run the furnace through two complete heating cycles

to check for proper operation12. Install control door when complete.

Checking Heat Pad Operation (If Applicable)In applications where the ambient temperature around thefurnace is 32�F (0�C) or lower, freeze protection measuresare required. If this application is where heat tape has beenapplied, check to ensure it will operate when lowtemperatures are present.NOTE: The Heat Pad, when used, should be wrappedaround the condensate drain trap. There is no need to useheat tape within the furnace casing. Most heat tapes aretemperature activated, and it is not practical to verify theactual heating of the tape. Check the following:

1. Check for signs of physical damage to heat tape suchas nicks, cuts, abrasions, gnawing by animals, etc.

2. Check for discolored heat tape insulation. If anydamage or discolored insulation is evident, replaceheat tape.

3. Check that heat tape power supply circuit is on.

Cleaning Heat ExchangersThe following items must be performed by a qualifiedservice technician.

Primary Heat ExchangersIf the heat exchangers get an accumulation of light dirt ordust on the inside, they may be cleaned by the followingprocedure:NOTE: If the heat exchangers get a heavy accumulation ofsoot and carbon, both the primary and secondary heatexchangers should be replaced rather than trying to cleanthem thoroughly due to their intricate design. A build−up ofsoot and carbon indicates that a problem exists whichneeds to be corrected, such as improper adjustment ofmanifold pressure, insufficient or poor quality combustionair, improper vent termination, incorrect size or damagedmanifold orifice(s), improper gas, or a restricted heatexchanger (primary or secondary). Action must be taken tocorrect the problem.

1. Turn off gas and electrical supplies to furnace.

ELECTRICAL SHOCK, FIRE OR EXPLOSIONHAZARD

Failure to follow this warning could result in personalinjury or death, or property damage.

Before installing, modifying, or servicing system, mainelectrical disconnect switch must be in the OFFposition and install a lockout tag. There may be morethan one disconnect switch. Lock out and tag switchwith a suitable warning label. Verify proper operationafter servicing.

! WARNING

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personalinjury, death, and/or property damage.

Turn off the gas and electrical supplies to the furnaceand install lockout tag before performing anymaintenance or service. Follow the operatinginstructions on the label attached to the furnace.

! WARNING

2. Remove control door.3. Disconnect wires or connectors to flame rollout

switch, gas valve, igniter, and flame sensor.4. Using backup wrench, disconnect gas supply pipe

from furnace gas control valve.5. Remove two screws attaching top filler plate and

rotate upwards to gain access to screws attachingburner assembly to cell panel.

6. Remove screws attaching burner assembly to cellpanel. (See Fig. 14)

NOTE: Burner cover, manifold, gas valve, and burnerassembly should be removed as one assembly.

7. Clean heat exchanger openings with a vacuum and asoft brush. (See Fig. 11)

NOTE: After cleaning, inspect the heat exchangers toensure they are free of all foreign objects that may restrictflow of combustion products.

8. Reverse items 6 through 1 for reassembly.9. Refer to furnace wiring diagram and reconnect wires

to flame rollout switch, gas valve, igniter, and flamesensor.

10. Turn on gas and electrical supplies to furnace.11. Check furnace operation through 2 complete heat

operating cycles. Look at burners. Burner flamesshould be clear blue, almost transparent. (See Fig.12)

12. Check for gas leaks.

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personalinjury, death, and/or property damage.

Never purge a gas line into a combustion chamber.Never test for gas leaks with an open flame. Use acommercially available soap solution madespecifically for the detection of leaks to check allconnections. A fire or explosion may result causingproperty damage, personal injury or loss of life.

! WARNING

13. Replace main furnace door.

Page 19: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07 19Specifications subject to change without notice.

Secondary Heat ExchangersThe condensing side (inside) of the secondary heatexchanger CANNOT be serviced or inspected withoutcomplete removal of the heat exchanger assembly. Detailedinformation on heat exchanger removal can be obtainedfrom your Distributor.

WINTERIZATION

UNIT AND PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in unitcomponent or property damage.

If the furnace is installed in an unconditioned spacewhere the ambient temperatures may be 32� F (0� C) orlower, freeze protection measures must be taken toprevent minor property or product damage.

CAUTION!

Since the furnace uses a condensing heat exchanger, somewater will accumulate in the unit as a result of the heattransfer process. Therefore, once it has been operated, itcannot be turned off and left off for an extended period oftime when temperatures will reach 32�F (0�C) or lowerunless winterized. Follow these procedures to winterize yourfurnace:

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in damage to thefurnace and other property damage.

Do not use ethylene glycol (automotive antifreezecoolant or equivalent). Failure of plastic componentsmay occur.

CAUTION!

1. Obtain propylene glycol (RV/swimming poolantifreeze or equivalent).

2. Turn off gas and electrical supplies to your furnace.3. Remove furnace control door.4. Remove the top unused rubber plug from the port on

the collector box opposite the condensate trap. SeeFig. 10.

5. Connect a field supplied 3/8−in. (9.5−mm) ID tube tothe open port on the collector box.

6. Insert a field supplied funnel into the tube.7. Pour 1 quart of anti−freeze solution into the funnel/

tube. Antifreeze should run through the inducerhousing, overfill condensate trap and flow to an opendrain.

8. Replace the rubber plug in the port on the collectorbox.

9. Remove the middle unused rubber plug from the porton the collector box opposite the condensate trap.See Fig. 10.

10. Repeat Steps 5 through 8.11. If a condensate pump is used, check with pump

manufacturer to verify pump is safe for use withantifreeze used. Allow pump to start and pump anti−freeze to open drain.

12. Replace main door.13. When furnace is re−started, flush condensate pump

with clear water to check for proper operation beforere−starting furnace.

14. Propylene glycol need not be removed beforere−starting furnace.

2-1/2-in.

(64.4)

1-1/4-in.(31.8)

A11405

Fig. 8 − Igniter Position − Top View

L12F041

2 in.

2.5 mm

3/8 in.

3/16 in.

+0.81.5 mm

50 mm

9.6 mm

4.6 mm

1/10 in.+ 1/32

1/16 in.

Fig. 9 − Igniter Position − Side View

A11392

Fig. 10 − Priming Condensate Trap

Page 20: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

20 440 04 7101 07Specifications subject to change without notice.

A11273

Fig. 11 − Cleaning Heat Exchanger Cell

Burner Flame

Burner

Manifold

A11461

Fig. 12 − Burner Flame

SET SCREW

MOTOR WHEEL HUB

MOTOR SHAFT FLAT

SCREW

MOTOR ARM

GROMMET

SCREW LOCATION

BLO HSG ASSY

BRACKET

BRACKET

ENGAGEMENT

SEE DETAIL A

CAPACITOR

OR POWER CHOKE

(WHEN USED)

BRACKET

SCREW

(GND)

BLOWER HSG ASSY

MOTOR, BLOWER

WHEEL, BLOWER

CUTOFF, BLOWER

DETAIL A

A11584

Fig. 13 − Blower Assembly

Page 21: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07 21Specifications subject to change without notice.

FLAME SENSOR(BELOW BURNER)

FLAME ROLLOUTSWITCH

BRACKET, IGNITERIGNITERBURNER SUPT. ASSY

BURNER ASSY

A11403

Fig. 14 − Burner Assembly

Page 22: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

22 440 04 7101 07Specifications subject to change without notice.

SEQUENCE OF OPERATIONNOTE: Furnace control must be grounded for properoperation or control will lock out. Control is groundedthrough green/yellow wire routed to gas valve and manifoldbracket screw. Using the schematic diagram in Fig. 16,follow the sequence of operation through the differentmodes. Read and follow the wiring diagram very carefully.NOTE: If a power interruption occurs during a call for heat(W), the control will start a 90−sec blower−only ON periodtwo sec after power is restored, if the thermostat is stillcalling for gas heating. The Amber LED light will flash code12 during the 90−sec period, after which the LED will be ONcontinuous, as long as no faults are detected. After the90−sec period, the furnace will respond to the thermostatnormally.

The blower door must be installed for power to beconducted through the blower door interlock switch ILK tothe furnace control CPU, transformer TRAN, inducer motorIDM, blower motor BLWM, hot−surface igniter HSI, and gasvalve GV.

1. Heating (See Fig. 2 for thermostat connections.) The wall thermostat “calls for heat,” closing theR−to−W circuit. The furnace control performs a self−check, verifies the pressure switch contacts collectorbox−LPS and housing pressure switch−HPS areopen, and starts the inducer motor IDM.a. Inducer Prepurge Period− As the inducer motor

IDM comes up to speed the collector box pressureswitch contacts LPS close to begin a 15 second pre-purge period. The inducer housing pressure switchcontacts HPS are ignored until one minute after thegas valve closes.

b. Igniter Warm−Up− At the end of the prepurgeperiod, the Hot−Surface igniter HSI is energized fora 17−sec igniter warm−up period.

c. Trial−for−Ignition Sequence− When the igniterwarm−up period is completed, the main gas valverelay contacts GVR close to energize the gas valveGV, the gas valve opens. The gas valve GV permitsgas flow to the burners where it is ignited by the HSI.Five sec after the GVR closes, a 2−sec flame provingperiod begins. The HSI igniter will remain energizeduntil the flame is sensed or until the 2−sec flameproving period begins.

d. Flame−Proving− When the burner flame is provedat the flame−proving sensor electrode FSE, thefurnace control CPU begins the blower−ON delayperiod and continues to hold the gas valve GV open.If the burner flame is not proved within two sec, thecontrol CPU will close the gas valve GV, and thecontrol CPU will repeat the ignition sequence for upto three more Trials−For−Ignition before going toIgnition−Lockout. Lockout will be resetautomatically after three hours or by momentarilyinterrupting 115 vac power to the furnace, or byinterrupting 24 vac power at SEC1 or SEC2 to thefurnace control CPU (not at W, G, R, etc.).If flame is proved when flame should not be present,the furnace control CPU will lock out of Gas−Heatingmode and operate the inducer motor IDM until flameis no longer proved.

e. Blower−On Delay− If the burner flame is proven, theblower motor is energized on HEAT speed 25 secafter the gas valve GV is energized. Simultaneously, the electronic air cleaner terminal

EAC−1 is energized and remains energized as longas the blower motor BLWM is energized.

f. Blower−Off Delay− When the thermostat issatisfied, the R−to−W circuit is opened, de−energizing the gas valve GV, stopping gas flow to theburners, and de−energizing the humidifier terminalHUM. The inducer motor IDM will remain energizedfor a 15−sec post−purge period. The blower motorBLWM and air cleaner terminal EAC−1 will remainenergized for 90, 120, 150, or 180 sec (dependingon the blower−OFF delay selection). The furnacecontrol CPU is factory−set for a 120−sec blower−OFF delay.

2. Cooling ModeThe thermostat “calls for cooling.”(See Fig. 2 for thermostat connections) The thermostat closes the R−to−G−and−Y circuits. TheR−to−Y circuit starts the outdoor unit, and theR−to−G−and−Y circuits start the furnace blower motorBLWM on COOL speed. The electronic air cleaner terminal EAC−1 is energized with115 vac when the blower motor BLWM is operating. Whenthe thermostat is satisfied, the R−to−G−and−Y circuits areopened. The outdoor unit will stop, and the furnace blowermotor BLWM will continue operating on the COOL speed foran additional 90 sec.

3. Continuous Blower Mode When the R−to−G circuit is closed by the thermostat,the blower motor BLWM will operate on HEAT speed.Terminal EAC−1 is energized as long as the blowermotor BLWM is energized. During a call for heat, theblower BLWM will stop during igniter warm−up (17sec), ignition (7 sec), and blower−ON delay (25 sec),allowing the furnace heat exchangers to heat up morequickly, then restarts at the end of the blower−ONdelay period at HEAT speed. When the thermostat “calls for cooling”, the blowermotor BLWM will operate at COOL speed. When thethermostat is satisfied, the blower motor BLWM willoperate an additional 90 sec on COOL speed beforereverting back to continuous−blower (HEAT speed). When the R−to−G circuit is opened, the blower motorBLWM will continue operating for an additional 5 sec,if no other function requires blower motor BLWMoperation.

4. Heat Pump When installed with a heat pump, the furnace controlautomatically changes the timing sequence to avoidlong blower off times during demand defrost cycles.When the R−to−Wand− Y or R−to−W−and−Y−and−Gcircuits are energized the furnace control CPU willcontinue to turn on the blower motor BLWM at HEATspeed, and begin a heating cycle. The blower motorBLWM will remain on until the end of the prepurgeperiod, then shut off for 24 sec then come back on atHEAT speed. When the W input signal disappears,the furnace control begins a normal inducer post−purge period and the blower switches to COOL speedafter a 3 sec delay. If the R−to−W−and−Y−and−Gsignals disappear at the same time, the blower motorBLWM will remain on for the selected blower− OFFdelay period. If the R−to−W−and−Y signals disappear,leaving the G signal, the blower motor BLWM willcontinue running the blower motor at HEAT speedafter the selected blower−OFF delay period iscompleted.

Component Self-TestRefer to page 13 for instructions.

Page 23: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07 23Specifications subject to change without notice.

Is L

ED

sta

tus lig

ht

on

?

Is th

ere

24V

at

SE

C-1

and S

EC

-2?

Is th

ere

115V

at

L1 a

nd L

2?

Repla

ce f

urn

ace c

ontr

ol.

Is d

oor

sw

itch c

losed

?

Repla

ce t

ransfo

rmer.

Repla

ce d

oor

sw

itch

.

Is th

ere

115V

goin

g t

o s

witch

?

Is d

oor

sw

itch c

losed

?

Is c

ircuit b

reaker

clo

se

d?

Check fo

r co

ntinuity in w

ire f

rom

cir

cuit

bre

aker

to f

urn

ace

.

Clo

se c

ircuit b

reaker

and g

o b

ack to

ST

AR

T.

Is L

ED

sta

tus lig

ht

blin

kin

g r

apid

ly w

ith

out

a p

ause?

Check fo

r co

rrect line v

oltage

pola

rity

. If

units a

re t

win

ned,

ch

eck for

pro

per

low

-

volta

ge (

24V

) tr

ansfo

rmer

phasin

g.

Is L

ED

sta

tus lig

ht

blin

kin

g O

N/O

FF

slo

wly

with a

com

bin

ation o

f sho

rt a

nd

long

fla

shes?

Dete

rmin

e s

tatu

s c

od

e. T

he s

tatu

s c

od

e

is a

2 d

igit n

um

be

r w

ith th

e fir

st

dig

it

dete

rmin

ed b

y t

he n

um

ber

of sho

rt

flash

es a

nd

th

e s

eco

nd d

igit b

y t

he

num

be

r o

f lo

ng f

lashes?

To r

ecall

sta

tus c

ode b

riefly r

em

ove a

nd r

eco

nne

ct

one

RE

D w

ire f

rom

the

dra

ft s

afe

gu

ard

sw

itch t

o d

ispla

y s

tore

d s

tatu

s c

od

e. Y

ou c

an a

lso

recall

the p

revio

us s

tatu

s c

ode

by m

om

enta

rily

sho

rtin

g t

he T

ES

T/T

WIN

term

inal to

Com

24V

te

rmin

al un

til th

e L

ED

go

es o

ut.

LE

D w

ill fla

sh t

he

sta

tus c

ode

of

the p

revio

us f

ault o

r sta

tus c

ode

#1

1 (

1 s

ho

rt a

nd

1 lon

g

flash

) if t

he

re w

as n

o p

revio

us f

ault. A

fter

the c

on

trol re

pe

ats

th

e c

ode

4

tim

es, th

e c

ontr

ol w

ill g

o th

roug

h a

bri

ef

com

po

ne

nt te

st seq

ue

nce

. T

he

inducer

will

sta

rt a

nd r

un f

or

the e

ntire

com

pon

ent

test. T

he H

SI, b

low

er

moto

r F

AN

spe

ed (

when e

quip

ped)

HE

AT

sp

ee

d,

an

d C

OO

L

spe

ed w

ill r

un f

or

10 –

15 s

eco

nds e

ach. G

as v

alv

e a

nd h

um

idifie

r w

ill n

ot

be t

urn

ed o

n.

Was there

a p

revio

us s

tatu

s c

od

e o

ther

tha

n #

11

?

Go t

o s

ectio

n b

elo

w fo

r th

e s

tatu

s c

od

e

that

was f

lashe

d.

Does t

he

co

ntr

ol re

sp

on

d t

o W

, Y

1 (

if

pre

sen

t),

Y/Y

2,

an

d G

(2

4V

) th

erm

osta

t

sig

nals

?

Run s

yste

m t

hro

ugh a

heating

or

co

olin

g

cycle

to c

heck o

pera

tio

n. S

tatu

s c

od

es

are

era

se

d a

fte

r 7

2 h

ou

rs.

Is 2

4V

pre

sent

at W

, Y

1 (

if p

resen

t),

Y/Y

2

or

G th

erm

osta

t te

rmin

als

on t

he fu

rnace

contr

ol?

Check r

oom

th

erm

osta

t or

inte

rco

nne

ctin

g c

able

.

Dis

con

nect all

the

th

erm

osta

t w

ire

s fro

m

the f

urn

ace c

ontr

ol.

Does t

he

pro

ble

m r

epe

at

whe

n u

sin

g a

jum

per

wire

?

Repla

ce f

urn

ace c

ontr

ol.

The th

erm

osta

t is

not com

patible

with t

he

furn

ace c

ontr

ol.

Eithe

r in

sta

ll a b

alla

st

resis

tor,

co

nn

ect th

e C

om

24V

th

erm

osta

t

term

inal to

th

e t

herm

osta

t, o

r re

pla

ce t

he

the

rmosta

t.

YE

S

NO

YE

S

YE

S

YE

S

YE

S

YE

S

YE

S

YE

S

YE

S

YE

S

ST

AR

T

YE

S

YE

S

NO

NO

NO

NO

N

O

NO

NO

N

O

NO

NO

NO

Trou

bles

hoot

ing

Gui

de

A11622

Fig. 15 − Troubleshooting Guide

Page 24: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

24 440 04 7101 07Specifications subject to change without notice.

11

N

O P

RE

VIO

US

CO

DE

– S

tore

d c

ode

s a

re

era

sed

aft

er

72

hours

.

Run

syste

m

thro

ug

h a

heating o

r coolin

g c

ycle

to

check s

yste

m.

12

B

LO

WE

R O

N A

FT

ER

PO

WE

R U

P –

(11

5V

OR

24V

) –

No

rmal o

pe

ration.

Blo

wer

runs f

or

90

secon

ds, if u

nit is

po

we

red u

p d

uri

ng a

call

for

hea

t (R

-W

clo

se

d)

or

wh

en (

R-W

opens)

duri

ng t

he

blo

we

r on-d

ela

y p

eri

od.

13

L

IMIT

CIR

CU

IT L

OC

KO

UT

– L

ockout

occu

rs if

the lim

it o

r flam

e r

ollout

is o

pe

n

long

er

tha

n 3

min

ute

s.

Co

ntr

ol w

ill a

uto

-

rese

t a

fte

r 3 h

ours

. S

ee c

od

e 3

3.

14

IG

NIT

ION

LO

CK

OU

T –

Syste

m f

aile

d t

o

ignite

gas a

nd p

rove

fla

me in 4

att

em

pts

.

Contr

ol w

ill a

uto

-reset

aft

er

3 h

ou

rs.

See

sta

tus c

ode

34

.

21

G

AS

HE

AT

ING

LO

CK

OU

T –

Turn

off

po

we

r and

wait 5

min

ute

s to

re

try.

Ch

eck

for:

-

Stu

ck c

lose

d g

as v

alv

e r

ela

y o

n c

on

trol.

-

Mis

wir

e o

r short

to g

as v

alv

e w

ire

.

22

A

BN

OR

MA

L F

LA

ME

-PR

OV

ING

SIG

NA

L

Fla

me is p

roved w

hile

gas v

alv

e is d

e-

ene

rgiz

ed.

Indu

cer

will

run u

ntil fa

ult is

cle

are

d. C

heck fo

r:

-

Stu

ck o

pe

n o

r le

aky g

as v

alv

e.

23

P

RE

SS

UR

E S

WIT

CH

DID

NO

T O

PE

N –

Check fo

r:

- O

bstr

ucte

d p

ressure

tu

be.

- P

ressure

sw

itch s

tuck c

lose

d.

24

S

EC

ON

DA

RY

VO

LT

AG

E F

US

E IS

OP

EN

Check fo

r:

-

Short

circuit in s

econ

da

ry v

olta

ge (

24V

)

wir

ing

inclu

din

g t

he

rmosta

t le

ads.

Dis

con

nect th

erm

osta

t le

ads t

o isola

te

short

cir

cuit.

31

LP

S o

r H

PS

PR

ES

SU

RE

SW

ITC

H D

ID

NO

T C

LO

SE

OR

RE

OP

EN

ED

– I

f o

pe

ns

duri

ng b

low

er

on

-dela

y p

erio

d, blo

we

r w

ill

com

e o

n f

or

the

sele

cte

d b

low

er

off-d

ela

y.

Check fo

r:

- P

rop

er

ven

t siz

ing

.

- A

ir leak b

etw

een

vestibule

and

blo

wer

com

pa

rtm

ent.

- Lo

w inle

t ga

s p

ressure

(if L

GP

S u

sed).

- D

iscon

necte

d o

r o

bstr

ucte

d p

ressu

re

tubin

g.

- D

efe

ctive o

r m

isw

ire

d p

ressure

sw

itch

es

- E

xcessiv

e w

ind.

- P

lugg

ed c

on

de

nsa

te d

rain

- W

ate

r in

ve

nt pip

ing, p

ossib

le s

ag

gin

g

pip

e

- R

estr

icte

d v

ent.

- D

efe

ctive I

nd

ucer

moto

r.

- Lo

w ind

uce

r voltag

e (

11

5 V

AC

)

33

L

IMIT

CIR

CU

IT F

AU

LT

– In

dic

ate

s t

he

limit, flam

e r

ollo

ut is

op

en.

Blo

wer

will

run

for

4 m

in.

or

un

til o

pen

sw

itch r

em

akes

whic

heve

r is

long

er.

If

op

en

lon

ge

r th

an 3

min

, cod

e c

ha

ng

es t

o lockou

t #

7. I

f o

pen

less t

han

3 m

in. sta

tus c

ode #

4 c

on

tin

ues

to fla

sh u

ntil blo

wer

sh

uts

off.

Fla

me

rollo

ut sw

itch r

equir

es m

anu

al re

se

t.

Check fo

r:

-

Loo

se b

low

er

whe

el.

- D

efe

ctive s

witch

or

co

nn

ectio

ns.

- D

irty

filt

er

or

restr

icte

d d

uct syste

m.

- Im

pro

per

gas in

put

adju

stm

ent.

- Im

pro

per

limit s

witch o

r n

o g

asket unle

ss

no

ted

on

sw

itch

.

34

IG

NIT

ION

PR

OV

ING

FA

ILU

RE

– If

fla

me

is n

ot

se

nse

d d

uri

ng t

he

tri

al fo

r ig

nitio

n

peri

od,

the c

ontr

ol w

ill r

epe

at th

e ignitio

n

seq

uen

ce 3

more

tim

es b

efo

re lockout

#14

occu

rs. I

f flam

e s

ignal is

lost d

uri

ng t

he

blo

we

r on-d

ela

y p

eri

od,

blo

wer

will

com

e

on f

or

the

sele

cte

d b

low

er

off

-dela

y.

Check th

e f

ollo

win

g ite

ms first b

efo

re

pro

cee

din

g t

o th

e n

ext

ste

p.

-

Gas v

alv

e tu

rned o

ff.

- M

an

ual sh

ut-

off v

alv

e.

- G

reen/Y

ello

w w

ire

MU

ST

be c

on

necte

d

to f

urn

ace

sh

eet

meta

l.

- F

lam

e s

en

sor

must

not

be

gro

und

ed.

To d

ete

rmin

e w

heth

er

the p

roble

m is in

th

e g

as v

alv

e, ig

niter,

or

flam

e s

en

so

r th

e

syste

m c

an b

e o

pera

ted in t

he c

om

pon

ent

test m

ode t

o c

heck th

e igniter.

F

irst

rem

ove th

e R

the

rmosta

t con

nection

fro

m

the c

on

trol a

nd initia

te t

he c

om

po

ne

nt te

st

seq

uen

ce.

Do

es t

he igniter

glo

w

ora

ng

e/w

hite b

y t

he e

nd o

f th

e 1

5 s

eco

nd

warm

-up p

eri

od

?

Check c

onn

ectio

ns a

nd

retr

y.

If c

urr

ent is

near

typic

al valu

e

(4.0

-6.0

nom

inal) a

nd b

urn

ers

will

not

sta

y o

n, re

pla

ce

contr

ol.

Cle

an

fla

me s

enso

r w

ith fin

e s

teel w

ool

and

re

che

ck c

urr

en

t. N

om

inal curr

ent is

4.0

to 6

.0 m

icro

am

ps.

Is c

urr

ent

ne

ar

typic

al valu

e?

Repla

ce e

lectr

ode.

Will

main

burn

ers

ig

nite a

nd s

tay o

n?

R

epla

ce f

urn

ace c

ontr

ol.

Fix

ed.

NO

YE

S

YE

S

YE

S

YE

S

NO

NO

45

C

ON

TR

OL C

IRC

UIT

RY

LO

CK

OU

T A

uto

-reset

afte

r 1

ho

ur

lockout

due

to:

- F

lam

e c

ircuit failu

re.

- G

as v

alv

e r

ela

y s

tuck

ope

n.

- S

oft

wa

re c

he

ck e

rror.

R

eset

po

wer

to c

lear

lo

ckou

t. R

epla

ce

co

ntr

ol if c

ode r

epea

ts.

Unplu

g ig

niter

harn

ess f

rom

co

ntr

ol and

initia

te a

noth

er

com

pon

en

t te

st

seq

uen

ce.

Ch

eck for

11

5V

betw

een

pin

1 a

nd N

EU

TR

AL

-L2 o

n t

he c

on

trol. W

as

115V

pre

se

nt fo

r th

e 1

5 s

eco

nd p

eriod

?

Repla

ce f

urn

ace c

ontr

ol.

Check fo

r co

ntinuity in t

he

harn

ess a

nd igniter.

R

epla

ce

defe

ctive

com

pon

ent.

Re

co

nn

ect th

e R

th

erm

osta

t le

ad a

nd

set

the

rmosta

t to

call

for

heat.

C

onn

ect

voltm

ete

r acro

ss g

as v

alv

e c

onn

ections.

Does g

as v

alv

e r

eceiv

e 2

4V

?

Do

es g

as v

alv

e o

pe

n a

nd

allo

w g

as t

o

flo

w?

Do th

e m

ain

burn

ers

ig

nite

?

Do th

e m

ain

burn

ers

sta

y o

n?

Allo

w b

low

er

to c

om

e o

n a

nd

rep

eat

test to

ch

eck for

inte

rmitte

nt o

pe

ration.

Check th

at

all

gas v

alv

es a

re

turn

ed

on. R

epla

ce v

alv

e.

Check c

onn

ectio

ns.

If

OK

,

repla

ce

co

ntr

ol.

Repe

at call

for

he

at

and

ch

eck fla

me

sensor

curr

ent

duri

ng t

rial fo

r ig

nitio

n

peri

od.

Is t

he

DC

mic

roam

ps b

elo

w 0

.5?

YE

S

YE

S

YE

S

YE

S

YE

S

NO

NO

NO

NO

NO

NO

Check fo

r:

- In

adeq

ua

te fla

me c

arr

yover

or

rou

gh ignitio

n.

- Lo

w inle

t ga

s p

ressure

.

- P

rop

er

firin

g r

ate

.

If L

PS

opens longer

than 5

min

ute

s,

inducer

shuts

off for

15 m

inute

s b

efo

re

retr

y. If H

PS

rem

ain

s o

pen for

one m

inute

aft

er

ga

s v

alv

e c

lose

s th

e fu

rna

ce

will

sh

ut

dow

n a

nd r

etr

y. If H

PS

fails

to c

lose o

n

thre

e s

ucce

ssiv

e c

ycle

s th

e fu

rna

ce

will

lockout fo

r 3 h

rs b

efo

re r

etr

y.

A12421

Troubleshooting Guide (Cont)

Page 25: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

440 04 7101 07 25Specifications subject to change without notice.

339236−2 Rev A

Fig. 16 − Wiring Diagram

Page 26: SERVICE AND TECHNICAL SUPPORT MANUAL · SERVICE AND TECHNICAL SUPPORT MANUAL Single Stage, PSC Blower Motor 35” Tall, High Efficiency Condensing Gas Furnace WFSR Save this manual

26 440 04 7101 07Specifications subject to change without notice.

PARTS REPLACEMENT INFORMATION GUIDECasing GroupBlower doorBottom plateControl doorDoor knob assemblyTop filler plateElectrical Group3−Amp fuseCircuit boardControl boxDoor switchJunction boxLimit switch(es)TransformerBlower GroupBlower housingBlower motorBlower wheelCapacitor (when used)Capacitor strap (when used)Cut−off platePower choke (where used)Filter GroupFilter(s)

Gas Control GroupBurnerFlame sensorGas valveHot surface igniterManifoldOrificeHeat Exchanger GroupContainment plateCoupling boxHeat exchanger assemblyPrimary HX cell panelSecondary HX assemblyTubing gasketsInducer GroupCollector boxCondensate trapCondensate trap elbowGasketsInducerInducer assemblyInducer motor capacitor (when used)Inducer motor module (when used)Pressure switch(es)

FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARDFailure to follow this warning could result in dangerous operation, personal injury, death or property damage.Improper installation, adjustment, alteration, service, or maintenance can cause personal injury, property damage, ordeath. Consult a qualified installer, service agency, or your local gas supplier for information or assistance. Thequalified installer or service agency must use only factory−authorized replacement parts, kits, or accessories whenmodifying this product.

! WARNING

TO OBTAIN INFORMATION ON PARTS: Consult your installing dealer or the classified section of your local telephone directoryunder the “Heating Equipment“ or “Air Conditioning Contractors and Systems” headings for dealer listing by brand name, orcontact:

International Comfort ProductsConsumer Relations Department

P.O. Box 128Lewisburg, TN 37091, USA

931−270−4100

NOMENCLATURE1, 2 3 4 5, 6, 7 8 9, 10 11 12WF S R 040 A 24 A 1

WF = Gas FurnaceA = 92.5S = 95.5 EFFICIENCYR = RegularL = Low NOx FEATURE040 = 40,000060 = 60,000

080 = 80,000

100 = 100,000

120 = 120,000 HEATING INPUT, MBTUHA= 14−3/16”B = 17−1/2”C = 21”D = 24−1/2” CABINET WIDTH, Inches24 = 24,000 BTU/hr, 2 Ton30 = 30,000 BTU/hr, 2−1/2 Ton36 = 36,000 BTU/hr, 3 Ton48 = 48,000 BTU/hr, 4 Ton60 = 60,000 BTU/hr, 5 Ton COOLING SIZESALES DIGITEXTRA DIGIT

Have available the product/model number and the serial number located on the unit rating plate to ensure correct replacement parts.