service and maintenance instructions for sizes 040--120 ...€¦ · fig. 1 -- furnace in upflow...
TRANSCRIPT
1
350AAVDeluxe 4--WayMultipoise Fixed--CapacityCondensing Gas Furnace
Service and Maintenance InstructionsFor Sizes 040--120, Series B & C
NOTE: Read the entire instruction manual before starting theinstallation.
TABLE OF CONTENTSPAGE
SAFETY CONSIDERATIONS 1. . . . . . . . . . . . . . . . . . . . . . . . .
GENERAL 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS 2. . .
CARE AND MAINTENANCE 3. . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning and/or Replacing Air Filter 3. . . . . . . . . . . . . . . . . . . .
Blower Motor and Wheel Maintenance 5. . . . . . . . . . . . . . . . . .
Cleaning Burners 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning Heat Exchangers 7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Primary Heat Exchangers 7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Secondary Heat Exchangers 8. . . . . . . . . . . . . . . . . . . . . . . . . .
Flushing Collector Box and Drainage System 8. . . . . . . . . . . . .
Servicing Hot Surface Igniter 9. . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Controls and Wiring 11. . . . . . . . . . . . . . . . . . . . . . . .
Checking Heat Tape Operation (If Applicable) 11. . . . . . . . . . .
Winterizing 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WIRING DIAGRAM 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status Codes 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Component Tests 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL SHOCK, FIRE, OR EXPLOSIONHAZARD
Failure to follow safety warnings exactly could result indangerous operation, personal injury, death, or propertydamage.
-- Before servicing, disconnect all electrical power to furnace.-- When servicing controls, label all wires prior todisconnecting. Reconnect wires correctly.-- Verify proper operation after servicing.
! WARNING
SAFETY CONSIDERATIONSRecognize safety information. This is the safety--alert symbol .When you see this symbol on the furnace and in instructions ormanuals, be alert to the potential for personal injury.Understand the signal words DANGER, WARNING, andCAUTION. These words are used with the safety--alert symbol.DANGER identifies the most serious hazards which will result insevere personal injury or death. WARNING signifies a hazardwhich could result in personal injury or death. CAUTION is usedto identify unsafe practices which may result in minor personalinjury or product and property damage. NOTE is used to highlightsuggestions which will result in enhanced installation, reliability, oroperation.Installing and servicing heating equipment can be hazardous due togas and electrical components. Only trained and qualified serviceagency personnel should install, repair, or service heatingequipment.
ELECTRICAL SHOCK, FIRE, OR EXPLOSIONHAZARD
Failure to follow this warning could result in possibledamage to this equipment, personal injury, or death.
The ability to properly perform maintenance on thisequipment requires certain expertise, mechanical skills,tools, and equipment. If you do not possess these, do notattempt to perform any maintenance on this equipmentother than those procedures recommended in the User’sManual.
! WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could property damage,personal injury, or death.
Never store anything on, near, or in contact with the furnace,such as:1. Spray or aerosol cans, rags, brooms, dust mops, vacuumcleaners, or other cleaning tools.2. Soap powders, bleaches, waxes or other cleaningcompounds, plastic or plastic containers, gasoline, kerosene,cigarette lighter fluid, dry cleaning fluids, or other volatilefluids.3. Paint thinners and other painting compounds, paper bags,or other paper products.
! WARNING
2
A05085
Fig. 1 -- Furnace in Upflow Orientation
ama
REGISTERED
ISO 9001:2000
CERTIFIED
Installing and servicing heating equipment can be hazardous due togas and electrical components. Only trained and qualifiedservice agency personnel should install, repair, or serviceheating equipment. Untrained personnel can perform basicmaintenance functions described in User’s InformationManual such as cleaning and replacing air filters. All otheroperations must be performed by trained service personnel. Whenworking on heating equipment, observe precautions in theliterature, on tags, and on labels attached to or shipped with theunit and other safety precautions that may apply.Follow all safety codes including the National Fuel Gas Code(NFGC) NFPA 54--2006/ANSI Z223.1--2006 in the USA, CSAB149.1--05 National Standard of Canada, Natural Gas and PropaneInstallation Codes (NSCNGPIC) in Canada, and the InstallationStandards, Warm Air Heating and Air Conditioning Systems(NFPA 90B) ANSI/NFPA 90B. Wear safety glasses and workgloves. Have a fire extinguisher available during start--up andadjustment procedures and service calls.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage tofurnace.
Label all wires prior to disconnection when servicingcontrols. Wiring errors can cause improper and dangerousoperation.
CAUTION!
GENERALThis furnace can be installed as a direct vent (2--pipe) or non--directvent (1--pipe) condensing gas furnace. These instructions arewritten as if the furnace is installed in an upflow application. Anupflow furnace application is where the blower is located belowthe combustion and controls section of the furnace, andconditioned air is discharged upward. Since this furnace can beinstalled in any of the 4 positions shown in Fig. 2, you may need torevise your orientation to component location accordingly.
UPFLOW
DOWNFLOW
HORIZONTALLEFT
AIRFLOW AIRFLOW
AIRFLOW
AIRFLOW
HORIZONTALRIGHT
A93041
Fig. 2 -- Multipoise Orientation
ELECTROSTATIC DISCHARGE (ESD)PRECAUTIONS
UNIT DAMAGE HAZARD
Failure to follow this caution may damage furnacecomponents.
Electrostatic discharge can affect electronic components.Take precautions during furnace installation and servicingto protect the furnace electronic control. Precautions willprevent electrostatic discharges from personnel and handtools which are held during the procedure. Theseprecautions will help to avoid exposing the control toelectrostatic discharge by putting the furnace, the control,and the person at the same electrostatic potential.
CAUTION!
1. Disconnect all power to the furnace. DO NOT TOUCHTHE CONTROL OR ANY WIRE CONNECTED TO THECONTROL PRIOR TO DISCHARGING YOUR BODY’SELECTROSTATIC CHARGE TO GROUND.
350AAV
3
2. Firmly touch a clean, unpainted, metal surface of thefurnace chassis which is close to the control. Tools held in aperson’s hand during grounding will be satisfactorilydischarged.
3. After touching the chassis, you may proceed to service thecontrol or connecting wires as long as you do nothing thatrecharges your body with static electricity (for example; DONOT move or shuffle your feet, DO NOT touchungrounded objects, etc.).
4. If you touch ungrounded objects (recharge your body withstatic electricity), firmly touch furnace again beforetouching control or wires.
5. Use this procedure for installed and uninstalled(ungrounded) furnaces.
6. Before removing a new control from its container, dischargeyour body’s electrostatic charge to ground to protect thecontrol from damage. If the control is to be installed in afurnace, follow items 1 through 5 before bringing thecontrol or yourself into contact with the furnace. Put allused AND new controls into containers before touchingungrounded objects.
7. An ESD service kit (available from commercial sources)may also be used to prevent ESD damage.
CARE AND MAINTENANCEFor continuing high performance and to minimize possible furnacefailure, it is essential that maintenance be performed annually.Consult your local dealer for maintenance and maintenancecontract availability.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personalinjury or death.
Turn off the gas and electrical supplies to the unit beforeperforming any maintenance or service. Follow theoperating instructions on the label attached to the furnace.
! WARNING
The minimum maintenance that should be performed on thisequipment is as follows:
1. Check and clean or replace air filter each month as needed.2. Check blower motor and wheel for cleanliness annually.3. Check electrical connections for tightness and controls forproper operation each heating season. Service as necessary.
4. Check for proper condensate drainage. Clean as necessary.5. Check for blockages in combustion--air and vent pipesannually.
6. Check burners for cleanliness annually.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Be careful of sharp metal edges, etc. Use care and wearprotective clothing, gloves, and safety glasses whenremoving parts.
CAUTION!
Step 1 — Cleaning and/or Replacing Air FilterThe air filter arrangement may vary depending on the applicationor orientation. See Tables 1 or 2 for filter size and typeinformation.
FILTER
FILTERSUPPORT
FILTERRETAINER
WASHABLE FILTER ORDISPOSABLE MEDIA FILTERIN FILTER CABINET
A08588
Fig. 3 -- Bottom Filter Arrangement
FILTERRETAINER
FILTERIN FURNACE
WASHABLE FILTER ORDISPOSABLE MEDIAFILTER IN FILTER CABINET
A08589
Fig. 4 -- Filter Installed for Side Inlet
FIRE, CARBON MONOXIDE POISONINGHAZARD
Failure to follow this warning could result in personalinjury, death or property damage.
Never operate unit without a filter or with the blower accesspanel removed. Operating a unit without a filter or with theblower access door removed could cause damage to thefurnace blower motor. Dust and lint on internal parts offurnace can cause a loss of efficiency.
! WARNING
NOTE: If the filter has an airflow direction arrow, the arrow mustpoint toward the blower.
To clean or replace filters, proceed as follows:If filter is installed in filter cabinet adjacent to furnace:
1. Turn off electrical supply to furnace.2. Remove filter cabinet door.3. Slide filter out of cabinet.
350AAV
4
Table 1 – Furnace Air Filter Table
FURNACE CASING WIDTHIN (MM)
FILTER QUANTITY AND SIZE *FILTER TYPE*SIDE RETURN*
IN (MM)BOTTOM RETURN*
IN (MM)
17---1/2 (445) (1) 16 x 25 x 3/4(406 x 635 x 19)
(1) 16 x 25 x 3/4(406 x 635 x 19) 3/4” (19 mm) thick washable
21 (533 ) (1) 16 x 25 x 3/4(406 x 635 x 19)
(1) 20 x 25 x 3/4(508 x 635 x 19) 3/4” (19 mm) thick washable
24---1/2 (610) (1) 16 x 25 x 3/4(406 x 635 x 19)
(1) 24 x 25 x 3/4(610 x 635 x 19) 3/4” (19 mm) thick washable
Table 2 – Air Filter Located in Filter CabinetFILTER CABINET HEIGHT --- IN (MM) FILTER SIZE --- IN (MM) FILTER TYPE
16 (406)
(1) 16 x 25 x 3/4*(406 x 635 x 19) or(1) 16 x 25 x 4---5/16(406 x 635 x 110)
washable
20 (508)
(1) 20 x 25 x 3/4*(508 x 635 x 19) or(1) 20 x 25 x 4---5/16(508 x 635 x 110)
washable
24 (610)
(1) 24 x 25 x 3/4*or(610 x 635 x 19) or(1) 24 x 25 x 4---5/16(610 x 635 x 110)
washable
* Filters with a side return--air may have a different filter size. Measure the filter to obtain the correct size.
350AAV
5
COLLECTOR BOXTUBE (PINK)
COLLECTOR BOXTUBE (GREEN)
INDUCER HOUSING(MOLDED) DRAIN
TUBE (BEHINDCOLLECTOR BOX
DRAIN TUBE)
COLLECTOR BOXDRAIN TUBE (BLUE)
FIELD-INSTALLEDFACTORY-SUPPLIED
DRAIN TUBECOUPLING (LEFT
DRAIN OPTION)
FIELD-INSTALLEDFACTORY-SUPPLIED
DRAIN TUBE
FIELD-INSTALLEDFACTORY-SUPPLIED1⁄2-IN. CPVC STREET
ELBOWS (2) FORLEFT DRAIN OPTION
FIELD-INSTALLEDFACTORY-SUPPLIED
DRAIN TUBECOUPLING (RIGHT
DRAIN OPTION)
CAP
COLLECTOR BOXDRAIN TUBE (BLUE& WHITE STRIPED)
PLUG
CONDENSATETRAP
A05110
Fig. 5 -- Factory--Shipped Upflow Tube Configuration(Shown with Blower Access Panel Removed)
4. Furnaces with a washable filter, clean filter by spraying coldtap water through filter in opposite direction of airflow.Rinse filter and let dry. Oiling or coating of the filter is notrecommended.
5. If equipped with factory specified disposable media filter,replace only with a factory specified media filter of the samesize.
6. Slide filter into cabinet.7. Replace filter cabinet door.8. Turn on electrical supply to furnace.
If filter is installed in furnace blower compartment:1. Turn off electrical supply to furnace.2. Remove main furnace door and blower access panel.3. Release filter retainer wire. (See Fig. 3 or 4.)
NOTE: Filters shown in Fig. 3 and 4 can be in furnace blowercompartment or in filter cabinet, but not in both.
4. Slide filter out of furnace.5. Furnaces with washable filter(s), clean filter by sprayingcold tap water through filter in opposite direction of airflow.
6. Rinse filter and let dry. Oiling or coating filter is notrecommended.
7. Slide filter into furnace.8. Recapture filter retaining wire.9. Replace blower access panel and main furnace door.
10. Turn on electrical supply to furnace.
Step 2 — Blower Motor and Wheel MaintenanceTo ensure long life, economy, and high efficiency, cleanaccumulated dirt and grease from blower wheel and motorannually.The inducer and blower motors are pre--lubricated and require noadditional lubrication. These motors can be identified by theabsence of oil ports on each end of the motor.The following items should be performed by a qualified servicetechnician.Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.2. Remove main furnace door and blower access panel.3. Disconnect wiresAll factory wires can be left connected, but field thermostatconnections may need to be disconnected depending ontheir length and routing.
4. Position control box, transformer, and door switch assemblyto right side of furnace casing.
5. If condensate trap is located in left-- or right--hand side offurnace casing, proceed to item 6. Otherwise remove trapand tubing as described below (See Fig. 5.):a. Disconnect field drain connection from condensate trap.b. Disconnect drain and relief port tubes from condensatetrap.
c. Remove condensate trap from blower shelf.6. Remove screws securing blower assembly to blower shelfand slide blower assembly out of furnace. Detach groundwire and disconnect blower motor harness plugs fromblower motor.
NOTE: Blower wheel is fragile. Use care.7. Clean blower wheel and motor by using a vacuum with softbrush attachment. Be careful not to disturb balance weights(clips) on blower wheel vanes. Do not bend wheel or bladesas balance will be affected.
8. If greasy residue is present on blower wheel, remove wheelfrom the blower housing and wash it with an appropriatedegreaser. To remove wheel:a. Mark blower wheel location on shaft before disassemblyto ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.NOTE: Mark blower mounting arms and blower housing so eacharm is positioned at the same hole location during reassembly.
c. Mark blower wheel orientation and cutoff plate locationto ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoffplate from housing.
e. Remove bolts holding motor mounts to blower housingand slide motor and mounts out of housing.
f. Remove blower wheel from housing.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in noise or furnacecomponent failure.
The blower wheel should not be dropped or bent as balancewill be affected.
CAUTION!
g. Clean wheel per instructions on degreaser cleaner. Donot get degreaser in motor.
350AAV
6
9. Reassemble motor and blower wheel by reversing items 8bthrough 8f. Ensure wheel is positioned for proper rotation.
NOTE: Be sure to attach ground wire to blower housing.10. Reinstall blower assembly in furnace.11. Reinstall condensate trap and tubing if previously removed.
a. Reinstall condensate trap in hole in blower shelf.b. Connect condensate trap drain tubes. See Fig. 5 ortubing diagram on main furnace door for proper tubelocation.
NOTE: Ensure tubes are not kinked or pinched, as this will affectoperation.
(1.) Connect 1 tube (blue or blue and white striped)from collector box.
(2.) Connect 1 tube (violet or unmarked) from inducerhousing.
(3.) Connect 1 tube (relief port, green or pink) fromcollector box.
c. Connect field drain to condensate trap.NOTE: Ensure tubes are not kinked or pinched, as this will affectoperation.12. Reinstall control box, transformer, and door switch
assembly on blower shelf.13. Reconnect wires. Refer to furnace wiring diagram and
connect thermostat leads if previously disconnected. (SeeFig. 21.)
NOTE: Refer to Table 3 for motor speed lead reconnection ifleads were not identified before disconnection.
UNIT DAMAGE HAZARD
Failure to adjust the heating speed may shorten heatexchanger life.
Heating speed selection MUST be adjusted to provideproper temperature rise as specified on the rating plate.
CAUTION!
Table 3 – Speed Selection
COLOR SPEED FACTORYATTACHED TO
Black High CoolYellow (When Present) Medium High Spare
Blue Medium Low HeatRed Low FanWhite Common Com
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personalinjury or death.
Blower access panel door switch opens 115--v power tofurnace control. No component operation can occur.Caution must be taken when manually closing thisswitch for service purposes.
! WARNING
14. Turn on electrical supply. Manually close blower accesspanel door switch. Use a piece of tape to hold switch closed.Check for proper rotation and speed changes betweenheating and cooling by jumpering R to G and R to Y/Y2 onfurnace control thermostat terminals. (See Fig. 15.)
15. If furnace is operating properly, release blower access paneldoor switch, replace blower access panel, and replace mainfurnace door.
MANIFOLDMOUNTINGSCREWS
MANIFOLD
GAS VALVEREGULATORFITTING
GASCONTROLVALVE
CELLPANEL
GASKET
A02312
Fig. 6 -- Burner Box Assembly
Step 3 — Cleaning BurnersThe following items should be performed by a qualified servicetechnician. If the burners develop an accumulation of light dirt ordust, they may be cleaned by using the following procedure:
1. Turn off gas and electrical supplies to furnace.2. Remove main furnace door.3. Remove burner box cover.4. Using backup wrench, disconnect gas supply pipe fromfurnace gas control valve.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in furnacecomponent damage.
Label all wires prior to disconnection when servicingcontrols. Wiring errors can cause improper and dangerousoperation.
CAUTION!
5. Remove wires from gas valve. Note location for reassembly.6. Remove burner box pressure tube from gas valve regulatorfitting.
7. Unplug igniter from harness.8. Remove igniter leads from slot in manifold grommet.9. Remove screws that secure manifold to burner box. (SeeFig. 6.)
NOTE: Do not remove burner box from cell panel.
10. Remove manifold, orifices, and gas valve as 1 assembly.11. Remove screws attaching burner assembly in burner box.
NOTE: Use care when removing and reinstalling burners not tostrike the hot surface igniter.
350AAV
7
IGNIT ER WIRES MUST BE PLACED IN THIS SLOT
A05074
Fig. 7 -- Igniter Wire Placement
12. Remove burner assembly from burner box.NOTE: All burners are attached to burner bracket and can beremoved as 1 assembly.13. Clean burners with soft brush and vacuum.14. Reinstall manifold, orifice, and gas valve assembly in
burner box. Ensure manifold seal grommet is installedproperly and burners fit over orifices.
15. Reinsert the igniter wires in the slot in the manifoldgrommet, dressing the wires to ensure there is no tension onthe igniter itself. (See Fig. 7.)
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personalinjury or death.
Igniter wires must be securely placed in slot in manifoldgrommet or else they could become pinched or severedand electrically shorted.
! WARNING
16. Reconnect wires to gas valve and igniter. Refer to furnacewiring diagram for proper wire location.
17. Reinstall burner box pressure tube to gas valve regulatorfitting.
18. Reinstall gas supply pipe to furnace gas control valve usingbackup wrench on gas valve to prevent rotation andimproper orientation.
NOTE: Use propane gas resistant pipe dope to prevent gas leaks.DO NOT use Teflon tape.
FIRE, EXPLOSION, UNIT DAMAGE HAZARD
Failure to follow this warning could result in personalinjury, death, or property damage.
Gas valve switch MUST be facing forward or tiltedslightly.
! WARNING
19. Replace burner box cover.20. Turn on gas and electrical supplies to furnace.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personalinjury, death or property damage.
Never test for gas leaks with an open flame. Use acommercially available soap solution made specificallyfor the detection of leaks to check all connections.
! WARNING
21. Check for gas leaks.22. Replace main furnace door.
Step 4 — Cleaning Heat ExchangersThe following items should be performed by a qualified servicetechnician.
Primary Heat ExchangersIf the heat exchangers get an accumulation of light dirt or dust onthe inside, they may be cleaned by the following procedure:NOTE: If the heat exchangers get a heavy accumulation of sootand carbon, both the primary and secondary heat exchangersshould be replaced rather than trying to clean them thoroughly dueto their intricate design. A build--up of soot and carbon indicatesthat a problem exists which needs to be corrected, such as improperadjustment of manifold pressure, insufficient or poor qualitycombustion air, improper vent termination, incorrect size ordamaged manifold orifice(s), improper gas, or a restricted heatexchanger (primary or secondary). Action must be taken to correctthe problem.
1. Turn off gas and electrical supplies to furnace.2. Remove main furnace door.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in furnacecomponent damage.
Label all wires prior to disconnection when servicingcontrols. Wiring errors can cause improper and hazardousoperation.
CAUTION!
3. Disconnect wires or connectors to flame rollout switch, gasvalve, igniter, and flame sensor.
4. Disconnect combustion--air intake pipe from intakehousing.
5. Remove the pressure switch tube from intake housing.6. Remove screws attaching intake housing to burner box, androtate intake housing away from burner box for removal.
7. Using backup wrench, disconnect gas supply pipe fromfurnace gas control valve.
8. Disconnect pressure tubing from gas valve.9. Remove 2 screws attaching top filler panel and rotateupwards to gain access to screws attaching burner box tocell panel.
10. Remove screws attaching burner box to cell panel. (See Fig.6.)
NOTE: Burner box, cover, manifold, gas valve, and burnerassembly should be removed as 1 assembly.
11. Clean heat exchanger openings with a vacuum and a softbrush. (See Fig. 8.)
NOTE: After cleaning, inspect the heat exchangers to ensure theyare free of all foreign objects that may restrict flow of combustionproducts.
350AAV
8
PRIMARY HXINLET OPENINGS
A96305
Fig. 8 -- Cleaning Inlet Openings of PrimaryHeat Exchangers
UNIT MAY NOT OPERATE
Failure to follow this caution may result in improper orintermittent unit operation.
The ground wire from the gas valve MUST be attached tothe burner box attachment screw.
CAUTION!
12. Reverse items 3 through 10 for reassembly.NOTE: Be sure burner box gasket is installed between burner boxand cell panel. (See Fig. 6.) If gasket is damaged, replace it.NOTE: Inspect combustion--air intake housing. If foamed gasketwas removed, check for any damage. If gasket is damaged in anyway, it must be repaired. To repair, remove damaged gasketsection, apply sealant releasing agent such as PAM cooking sprayor equivalent (must not contain corn nor canola oil, halogenatedhydrocarbons nor aromatic content, to prevent inadequate sealfrom occurring) to burner box and apply a small bead of G.E. RTV162, G.E. RTV 6702, or Dow--Corning RTV 738 sealant to edgeof combustion--air intake housing. (See Fig. 9.)13. Refer to furnace wiring diagram and reconnect wires to
flame rollout switch, gas valve, igniter, and flame sensor.14. Reconnect pressure switch tubes to gas valve and intake
housing. Refer to tube routing label on main furnace doorfor proper tube location. (See Fig. 10.) Be sure tubes are notkinked.
15. Turn on gas and electrical supplies to furnace.16. Check furnace operation through 2 complete heat operating
cycles. Look through sight glass in burner enclosure tocheck burners. Burner flames should be clear blue, almosttransparent. (See Fig. 11.)
17. Check for gas leaks.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personalinjury, death or property damage.
Never test for gas leaks with an open flame. Use acommercially available soap solution made specificallyfor the detection of leaks to check all connections.
! WARNING
18. Replace main furnace door.
Secondary Heat ExchangersNOTE: The condensing side (inside) of the secondary heatexchangers CANNOT be serviced or inspected. A small number ofbottom outlet openings can be inspected by removing the inducerassembly. See Flushing Collector Box and Drainage Systemsection for details on removing inducer assembly.
Step 5 — Flushing Collector Box and DrainageSystem
1. Turn off gas and electrical supplies to furnace.2. Remove main furnace door.3. Disconnect inducer motor and pressure switch wires orconnectors.
4. Disconnect pressure switch tubes.5. Disconnect vent pipe from inducer housing outlet byloosening coupling clamp on inducer outlet.
PAM
RTV
A93087
Fig. 9 -- Combustion--Air Intake HousingGasket Repair
6. Disconnect drain tube from inducer housing. (See Fig. 10.)NOTE: Ensure the drain tube disconnected from the inducerhousing is higher than the collector box opening or water will flowout of tube.
7. Remove inducer housing assembly by removing 4 boltsattaching assembly to cell panel.
8. Flush inside of collector box with water until dischargefrom condensate trap is clean and runs freely.
9. Inspect inside area of collector box for any pieces of foreignmaterials and remove them if present.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in furnacecomponent damage.
DO NOT use wire brush or other sharp object to inspect ordislodge materials in secondary heat exchangers as cuttingof the secondary heat exchanger protective coating mayoccur. Flush with water only.
CAUTION!
350AAV
9
Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.
Tube location when used in DOWNFLOW application
Tube location when used onHORIZONTAL - RIGHT application
PLUG
CAP
COLLECTOR BOX DRAIN TUBE(BLUE & WHITE STRIPED)
COLLECTOR BOX TUBE(PINK)
COLLECTOR BOX DRAIN TUBE(BLUE)
INDUCER HOUSING DRAIN TUBE(VIOLET)
COLLECTOR BOX TUBE(PINK)
COLLECTOR BOX DRAINTUBE
(BLUE & WHITE STRIPED)
COLLECTOR BOX DRAIN TUBE(BLUE)
INDUCER HOUSING (MOLDED) DRAIN TUBE(BEHIND COLLECTOR BOX DRAIN TUBE)
FIELD-INSTALLEDFACTORY-SUPPLIED DRAIN TUBECOUPLING (LEFT DRAIN OPTION)
FIELD-INSTALLED FACTORY-SUPPLIEDDRAIN TUBE
FIELD-INSTALLEDFACTORY-SUPPLIED 1/2-IN.CPVC STREET ELBOWS (2)FOR LEFT DRAIN OPTION
COLLECTOR BOX TUBE(GREEN)
CONDENSATE TRAP
CAP
Condensate Trap; Factory Installedin Blower Shelf
CONDENSATE TRAP
COLLECTOR BOX TUBE (GREEN)
Condensate Trap on LEFTSide Optional
CAP
PLUGCOLLECTOR BOX
DRAIN TUBE (BLUE)PLUGGED END
COLLECTOR BOX DRAIN TUBE(BLUE & WHITE STRIPED)
COLLECTOR BOXTUBE (GREEN)
COLLECTOR BOXTUBE (PINK)
COLLECTOR BOXEXTENSION TUBECONDENSATE TRAP
INDUCER HOUSING DRAIN TUBE (VIOLET)
COLLECTOR BOXEXTENSION TUBE
COLLECTOR BOX TUBE(PINK)
COLLECTOR BOX DRAIN TUBE(BLUE)
COLLECTOR BOX TUBE(GREEN)
CONDENSATE TRAP
INDUCER HOUSING DRAINTUBE (VIOLET)
COLLECTOR BOX EXTENSION TUBE
COLLECTOR BOX DRAINTUBE
(BLUE & WHITE STRIPED)
Condensate Trap onRIGHT Side
COLLECTOR BOXEXTENSION DRAIN TUBE
DRAIN TUBE COUPLING
GAS VALVE
DRAIN TUBES ROUTED INFRONT OF GAS VALVE
PLUG
CAP
COLLECTOR BOX DRAIN TUBE(BLUE & WHITE STRIPED)
CONDENSATE TRAP
COLLECTOR BOXEXTENSION TUBE
COLLECTOR BOXTUBE (GREEN)
INDUCER HOUSINGDRAIN TUBE
(VIOLET)
COLLECTOR BOX TUBE (PINK)RELOCATE TUBE BETWEEN BLOWERSHELF AND INDUCER HOUSING FOR
040,060, AND 080 HEATING INPUTFURNACES
CAP
PLUG
COLLECTOR BOX DRAIN TUBE(BLUE)
COLLECTOR BOX EXTENSION TUBECOLLECTOR BOX TUBE (PINK)
COLLECTOR BOXTUBE (GREEN)
COLLECTOR BOX DRAIN TUBE(BLUE AND WHITE STRIPED)
INDUCER HOUSING DRAIN TUBE (VIOLET)
CONDENSATE TRAP
Condensate Trap onLEFT Side
COLLECTOR BOXDRAIN TUBE (BLUE)
PLUG
Tube location when used in UPFLOW application
Tube location when used onHORIZONTAL - LEFT application
CAP
PLUG
COLLECTOR BOXEXTENSION TUBE
DRAIN TUBECOUPLINGCOLLECTOR BOX EXTENSION DRAIN TUBE
(Blower access panel removed)
1. All tubing must be connected securely and routed to avoid kinks and traps.2. Pressure tubing must always slope away from pressure switch to collector box connection as shown.3. HORIZONTAL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to
prevent a trap.Refer to the Installation Instructions for further details.
NOTE:
324999-201 REV. C
FIELD-INSTALLEDFACTORY-SUPPLIED
DRAIN TUBE COUPLING(RIGHT DRAIN OPTION)
BURNER ENCLOSUREPRESSURE REFERENCE
TUBE ASSEMBLY
BURNER ENCLOSUREPRESSURE REFERENCE
TUBE ASSEMBLY
BURNER ENCLOSURE PRESSUREREFERENCE TUBE ASSEMBLY
BURNER ENCLOSUREPRESSURE REFERENCE
TUBE ASSEMBLY
BURNER ENCLOSUREPRESSURE REFERENCE
TUBE ASSEMBLY
BURNER ENCLOSURE PRESSUREREFERENCE TUBE ASSEMBLY
TUBE ROUTING
AUXILIARY "J" BOX RELOCATED HERE
A00308
Fig. 10 -- Furnace Pressure and Drain Tubing Diagram
10. Reassemble inducer assembly by reversing items 3--7.Tighten the vent coupling clamp screw(s) to 15 in.--lb oftorque.
NOTE: If seal between the inducer housing and the collector boxis damaged in any way, it must be repaired. To repair, apply sealantreleasing agent such as PAM cooking spray or equivalent (must notcontain corn nor canola oil, halogenated hydrocarbons noraromatic content, to prevent inadequate seal from occurring) toinducer housing. (See Fig. 12.) Apply a small bead of G.E. RTV162, G.E. RTV 6702, or Dow--Corning RTV 738 sealant to groovein collector box.11. Refer to furnace wiring diagram and reconnect wires to
inducer motor and pressure switches or connectors.12. Reconnect pressure tubes to pressure switches. See diagram
on main furnace door for proper location of tubes. Be suretubes are not kinked. (See Fig. 10.)
13. Turn on gas and electrical supplies to furnace.14. Check furnace operation through 2 complete heat operating
cycles. Check area below inducer housing, vent pipe, andcondensate trap to ensure no condensate leaks occur. If leaksare found, correct the problem.
15. Check for gas leaks.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personalinjury, death or property damage.
Never test for gas leaks with an open flame. Use acommercially available soap solution made specifically forthe detection of leaks to check all connections.
! WARNING
16. Replace main furnace door.
Step 6 — Servicing Hot Surface IgniterThe igniter does NOT require annual inspection. Check igniterresistance before removal.
1. Turn off gas and electrical supplies to furnace.
BURN HAZARD
Failure to follow this caution may result in personal injury.
Allow igniter to cool before removal. Normal operatingtemperatures exceed 2000_F (1093_C).
CAUTION!
350AAV
10
2. Remove main furnace door.3. Disconnect igniter wire connection.4. Check igniter resistance. Igniter resistance is affected bytemperature. Only check resistance when the igniter is atroom temperature.a. Using an ohm meter, check resistance across both ig-niter leads in connector.
b. Cold reading should be between 40 ohms and 70 ohms.5. Remove igniter assembly.
a. Remove burner box cover.b. Remove igniter wires from slot in manifold grommet.(See Fig. 7.)
c. Using a 1/4--in. driver, remove the single screw securingthe igniter bracket to the burner box bracket (See Fig.13.) and carefully withdraw the igniter and bracket as-sembly through the front of the burner box withoutstriking the igniter on surrounding parts. Note that theigniter bracket has a handle that extends to the front ofthe burner box to aid in handling. (See Fig. 13.)
d. Inspect igniter for signs of damage or failure.
����BURNER FLAME
BURNER
MANIFOLD
A89020
Fig. 11 -- Burner Flame
RTV
PAM
A93081
Fig. 12 -- Gasket on Collector Box
BRACKET
IGNITER
9/16˝
11/16˝
EXTENDED IGNITERBRACKET HANDLE
IGNITER BRACKETMOUNTING SCREW
A05075
Fig. 13 -- Igniter Bracket
UNIT DAMAGE HAZARD
Failure to follow this caution may result in prematurefailure of the igniter.
The igniter is fragile. DO NOT allow it to hit burner boxparts while removing or replacing it.
CAUTION!
e. If replacement is required, replace igniter on igniterbracket and then install assembly into burner box toavoid damage to the igniter.
6. To replace igniter and bracket assembly, reverse items 5athrough 5c.
7. Reconnect igniter wire connection and insert the igniterwires in the slot in the manifold grommet, dressing theigniter wires to ensure there is no tension on the igniteritself. (See Fig.7.)
2-5/32˝(55 mm)
A04181
Fig. 14 -- Burner Flame
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personalinjury or death.
Igniter wires must be securely placed in slot in manifoldgrommet or else they could become pinched or severed andelectrically shorted.
! WARNING
350AAV
11
115-V FIELD-SUPPLIED
DISCONNECT
AUXILIARYJ-BOX
24-VTERMINAL
BLOCK
THREE-WIREHEATING-ONLY
FIVE WIRE
NOTE 1
NOTE 2FIELD-SUPPLIEDDISCONNECT
CONDENSINGUNIT
TWOWIRE
FURNACE
CONTROL
R
G
COM
W C R G Y
GND
GND
FIELD 24-V WIRINGFIELD 115-, 208/230-, 460-V WIRINGFACTORY 24-V WIRINGFACTORY 115-V WIRING
208/230- OR460-VTHREEPHASE
208/230-VSINGLEPHASE
BLOWER DOOR SWITCH
WHT
BLK
WHT
BLK
NOTES: Connect Y-terminal in furnace as shown for proper blower operation.Some thermostats require a "C" terminal connection as shown.If any of the original wire, as supplied, must be replaced, usesame type or equivalent wire.
W
Y/Y2
GND
THERMOSTATTERMINALS
1.2.3.
A99440
Fig. 15 -- Field Wiring
8. Reinstall burner box cover.9. Turn on gas and electrical supplies to furnace.10. Verify igniter operation by initiating control board self--test
feature or by cycling thermostat.11. Replace main furnace door.
Step 7 — Electrical Controls and Wiring
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personalinjury or death.
There may be more than one electrical supply to the unit.Check accessories and cooling unit for additional electricalsupplies.
! WARNING
The electrical ground and polarity for 115--v wiring must bemaintained properly. Refer to Fig. 15 for field wiring informationand to Fig. 21 for unit wiring information.NOTE: If the polarity is not correct or furnace is not properlygrounded, the STATUS LED on the furnace control will flashrapidly and prevent the furnace from operating. The control systemalso requires an earth ground for proper operation of the furnacecontrol and flame sensor.
The 24--v circuit contains an automotive--type, 3--amp fuse locatedon the furnace control. (See Fig. 16.) Any direct shorts of the 24--v
wiring during installation, service, or maintenance will cause thisfuse to blow. If fuse replacement is required, use ONLY a fuse ofidentical size. The furnace control LED will flash status code 24when fuse needs to be replaced.With power to the unit disconnected, check all electricalconnections for tightness. Tighten all screws on electricalconnections. If any smoky or burned connections are found,disassemble the connection, clean all parts, strip wire, andreassemble properly and securely.Reconnect electrical supply to unit and observe unit through 1complete operating cycle and check for proper operation.
Step 8 — Checking Heat Tape Operation(If Applicable)In applications where the ambient temperature around the furnaceis 32_F (0_C) or lower, freeze protection measures are required. Ifthis application is where heat tape has been applied, check toensure it will operate when low temperatures are present.NOTE: Heat tape, when used, should be wrapped around thecondensate drain trap and drain line. There is no need to use heattape within the furnace casing. Most heat tapes are temperatureactivated, and it is not practical to verify the actual heating of thetape. Check the following:
1. Check for signs of physical damage to heat tape such asnicks, cuts, abrasions, gnawing by animals, etc.
2. Check for discolored heat tape insulation. If any damage ordiscolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
350AAV
12
BLW
NU
ET
RA
LS
TATU
S C
OD
E LE
D
SEC-2 SEC-1
EAC-2 L2
FUSE 3-AMP
0.5 AMP@24VAC
HUM
TEST/TWIN
Y1 D
HU
M G
CO
M W
/W1 Y
/Y2 R
24V
PLT
120 180
90 150
BLOWER OFF-DELAY
PLT
1
CO
OL H
EAT
SPARE-1 SPARE-2FAN
EAC-1
1-AMP@
115VAC PR-1
L1
PL2 1
24-V THERMOSTATTERMINALS
3-AMP FUSE
LED OPERATION &DIAGNOSTIC LIGHT
115-VAC(L2)NEUTRALCONNECTIONS
COOLHEAT
SPARE-1
SPARE-2 FANBLOWER SPEED
SELECTION TERMINALS
EAC-1 TERMINAL(115-VAC 1.0 AMP MAX.)
115 VAC (L1) LINEVOLTAGE CONNECTION
PL2-HOT SURFACEIGNITER & INDUCERMOTOR CONNECTOR
PL1-LOW VOLTAGE MAINHARNESS CONNECTOR
TRANSFORMER 24-VACCONNECTIONS
HUMIDIFIER TERMINAL(24-VAC 0.5 AMP MAX.)
TWINNING AND/ORCOMPONENT TEST
TERMINALBLOWER OFF-DELAY
A02142
Fig. 16 -- Control Center
UNIT AND PROPERTY DAMAGE
Failure to follow this caution may result in furnacecomponent failures or water property damage.
If this furnace is to be operated in an unconditioned spacewhere the ambient temperatures may be 32_F (0_C)orlower, freeze protection measures must be taken. SeeCONDENSATE DRAIN PROTECTION section ofInstallation, Start--up, and Operating Instructions. (See Fig.17.)
CAUTION!
Step 9 —Winterizing
UNIT DAMAGE HAZARD
Failure to follow this caution may result in furnacecomponent damage.
Freezing condensate left in the furnace may damage thefurnace.
CAUTION!
If the furnace will be off for an extended period of time in astructure where the temperature will drop to 32_F (0_C)or below,winterize as follows:
1. Turn off electrical supply to furnace.2. Remove main furnace door.3. Disconnect upper inducer housing drain connection capfrom inducer housing. (See Fig. 18.)
4. Connect field--supplied 1/2--in. I.D. inducer housing tube toupper inducer housing drain connection.
5. Insert funnel in tube and pour one quart of antifreeze,propylene glycol (RV, swimming pool antifreeze, orequivalent) into funnel/tube until it is visible at point wherecondensate enters open drain. (See Fig. 19.)
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit componentdamage.
Do not use ethylene glycol (Prestone II antifreeze/coolant orequivalent automotive type).
CAUTION!
6. Replace drain connection cap and clamp to inducer housing.7. Replace main furnace door.8. Propylene glycol need not be removed before restartingfurnace.
350AAV
13
A07911
Fig. 17 -- Freeze Protection
WIRING DIAGRAMSSee Fig. 15, 16 and 21 for the Deluxe 4--Way Multipoise Furnacewiring diagrams.
TROUBLESHOOTINGUse the troubleshooting guide, the status code LED on the furnacecontrol and the component test to isolate furnace operationproblems.STATUS CODESFor an explanation of status codes, refer to service label located onback of main furnace door or Fig. 20 and the TroubleshootingGuide. The stored status code will NOT be erased from the controlmemory if 115-- or 24--v power is interrupted.NOTE: Removing the blower access door will open the bloweraccess door switch and terminate 115--v power to the control.To read current status code, remove main furnace door. The statuscode LED can be viewed through the sight glass on the bloweraccess door.NOTE: NO thermostat signals may be present at control and allblower off delays must be completed to view previous codes.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unitcomponents.
Make sure limit switch or flame rollout switch wire doesnot contact any metal component, such as gas valve. If wireis shorted, 3--amp fuse on furnace control board will openand unit will not operate.
CAUTION!
To retrieve previous codes, remove 1 of the red main limit or flamerollout switch wires for 1 to 4 sec until the LED light goes out,then reconnect it. (Do not leave red wire disconnected for longerperiods of time as the control will assume an overtemperaturecondition exists and will respond with blower operation.) Thisplaces the control in the status recall mode and displays the lastcode stored in memory.Record the code. After the last code is displayed the control willperform the component test, and then return to normal standbymode.
COMPONENT TEST
ELECTRICAL SHOCK AND UNIT MAY NOTOPERATE HAZARD
Failure to follow this warning could result in electrical shock,personal injury, or death.
Blower access panel door switch opens 115--v power tocontrol board. No component operation can occur. Cautionmust be taken when manually closing this switch for servicepurposes.
! WARNING
Use the Component Test to check furnace components for properoperation. To initiate the component self--test sequence, shut off theroom thermostat or disconnect the “R” thermostat lead. Briefly(approximately 2 sec) short the TWIN/TEST terminal to the COM24V terminal. The status LED will turn off. The test sequence willbe as follows:
1. LED flashes last status code, or code 11, 4 times. Recordthis status code for further troubleshooting.
2. The inducer will start and continue to run until test is over.3. Hot surface igniter (HSI) is energized for 15 sec, thende--energized.
4. Blower operates on continuous FAN speed for 10 sec, thenturns off.
5. The blower motor operates on HEATING speed for 10 sec,then turns off.
6. The blower motor operates on COOLING speed for 10 sec,then turns off.
7. Inducer turns off.8. The gas valve and humidifier terminal HUM are notenergized for safety reasons.
350AAV
14
A99118
Fig. 18 -- Inducer Housing Drain TubeA99119
Fig. 19 -- Funnel in Drain Tube and AntifreezeRunning Through Trap
350AAV
15
SERVICE
To initiate the component test sequence, shut OFF the room thermostat or disconnectthe "R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" ter-minal. Status LED will flash code and then turn ON the inducer motor. The inducermotor will run for the entire component test. The hot surface ignitor, blower motorFAN speed (AMBER LED boards only) blower motor HEAT speed, and blower motorCOOL speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifierwill not be turned on.
CONTINUOUS OFF - Check for 115VAC at L1 & L2, & 24VAC at SEC-1 & SEC-2.CONTINUOUS ON - Control has 24VAC power.RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned,
refer to twinning kit instructions.
LED CODE
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRSTDIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BYTHE NUMBER OF LONG FLASHES.
STATUS
11 NO PREVIOUS CODE - Stored status code is erased automatically after 72hours. On RED LED boards stored status codes can also be erased when power(115 VAC or 24 VAC) to control is interrupted.
12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90seconds, if unit is powered up during a call for heat (R-W closed) or R-W opensduring blower on-delay.
13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit or flame rollout switch isopen longer than 3 minutes.- Control will auto reset after three hours. - Refer to #33.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.21 GAS HEATING LOCKOUT - Control will NOT auto reset.
Check for: - Mis-wired gas valve -Defective control (valve relay)22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is
de-energized. Inducer will run until fault is cleared. Check for:- Leaky gas valve - Stuck-open gas valve
23 PRESSURE SWITCH DID NOT OPEN Check for:- Obstructed pressure tubing. - Pressure switch stuck closed.
24 SECONDARY VOLTAGE FUSE IS OPEN Check for:- Short circuit in secondary voltage (24VAC) wiring.
31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer thanfive minutes, inducer shuts off for 15 minutes before retry. Check for:- Excessive wind - Proper vent sizing - Defective inducer motor- Low inducer voltage (115VAC) - Defective pressure switch- Inadequate combustion air supply - Restricted vent- Disconnected or obstructed pressure tubing- Low inlet gas pressure (if LGPS used)If it opens during blower on-delay period, blower will come on for the selectedblower off-delay.
33 LIMIT CIRCUIT FAULT - Indicates a limit, or flame rollout is open. Blower willrun for 4 minutes or until open switch remakes whichever is longer. If openlonger than 3 minutes, code changes to lockout #13. If open less than 3 minutesstatus code #33 continues to flash until blower shuts off. Flame rollout switchrequires manual reset. Check for: - Restricted vent- Proper vent sizing - Loose blower wheel - Excessive wind- Dirty filter or restricted duct system.- Defective blower motor or capacitor. - Defective switch or connections.- Inadequate combustion air supply (Flame Roll-out Switch open).
34 IGNITION PROVING FAILURE - Control will try three more times before lockout#14 occurs. If flame signal lost during blower on-delay period, blower will comeon for the selected blower off-delay. Check for: - Control ground continuity- Flame sensor must not be grounded- Oxide buildup on flame sensor (clean with fine steel wool).- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).- Gas valve defective or gas valve turned off - Manual valve shut-off- Defective Hot Surface Ignitor
- Low inlet gas pressure- Inadequate flame carryover or rough ignition- Green/Yellow wire MUST be connected to furnace sheet metal
45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure- Software check error Reset power to clear lockout. Replace control if status code repeats.
If status code recall is needed, briefly remove then reconnect one main limit wire to displaystored status code. On RED LED boards do not remove power or blower door before initiat-ing status code recall. After one status code recall is completed component test will occur.
COMPONENT TEST
327884-101 REV. B
A02270
Fig. 20 -- Service Label
350AAV
16
PC
B
TRAN
FRS
NO
TE #
11
LS
PR
S(W
HE
N U
SE
D)
LGP
S
FUS
ED
OR
CIR
CU
IT B
RE
AK
ER
DIS
CO
NN
EC
T S
WIT
CH
(WH
EN
RE
Q’D
)N
OTE
#2
JB
L1 L1 BLW
RH
I/LO
TO 1
15VA
C F
IELD
DIS
CO
NN
ECT
NO
TE #
2EQ
UIP
MEN
T G
RO
UN
D
SPAR
E-1
HEA
T
FAN
CO
OL
HSI
REA
C-1
STAR
TO
L
HI
MED
HI
ME
D L
OLO
BLW
M
SCH
EMAT
IC D
IAG
RAM
(NAT
UR
AL G
AS &
PR
OPA
NE)
11
HSI
2PL
32
PL2
115V
AC
PR1
TRAN
24VA
C
M
IDR
TEST
/TW
IN F U
1N
OTE
#6
IDM
OL AU
X
CAP
- 2
CAP
-1
L2
FRS
LS
LGPS
(WH
EN U
SED
)
NO
TE #
11P
RS
FSE
915
CPU
PC
B
Y1 G CR W
SEC
-1
GV
R-1
NO
TES:
3267
96-1
01 R
EV. A
OM
1046 2PL4
231
NEU
TRA
L
ILK
FU2
L1
ILK
GN
D
RE
D
BLU OR
N
WH
T
RE
DR
ED
OR
N
RE
D
RE
DG
RN
/YE
L
YE
L
BLU
BLU
RE
DW
HT
BLK
LED
1
12345678910
BLO
WE
R O
FF D
ELA
Y
JUM
PE
R S
ELE
CT
YE
L
OL
STA
RT
BLK
WH
T
WH
T
BR
N
IDM
BR
N
CA
P -2 AU
X
OL
M
HSI
WH
T
BLK
BLK
WH
TW
HT
(C
OM
)
BLK
BLK
WH
TW
HT
21
PL2
WH
T
BLK
BLK
BLW
M
CA
P -1
SPA
RE
1S
PAR
E 2
EAC
-1P
R1
SE
C-2
SE
C-1
EAC
-2
SEC
-2
8 7 3
PL1
2 1
PL3
3 2 1
PL4
BR
N
BR
N
RE
D (L
O)
WH
T(C
OM
)
YE
L
BLU
(ME
D L
O)
CO
M
HU
MG
VR-2
DH
UM
Y/Y
2
(ME
D H
I)
FAN
11
WH
T
PL1 11
L2
GR
N/Y
EL
GR
N/Y
EL
GR
N/Y
EL
GN
DN
OTE
#3
GV
M
C
NO
TE #
3
GV
M
CG
RN
/YE
L
GR
N/Y
EL
FSE
NO
TE #
10
WH
T
Y1 R
Y/Y
2
WC
HU
M
om
TES
T/TW
IN
24V
FU1
J1180
150
120
90
G
DH
UM
NO
TE #
6 EAC
-2L2
NEUTRAL
NOTE #8
BLW
L1FA
N
BH
T/C
LRB
FAN
RB
LWR
CO
OL
HE
AT
BLK
(HI)
L E G E N D
BFAN
RCO
NTIN
UOUS
-FAN
SEL
ECT
RELA
Y, SP
DT
BHT/
CLR
BLO
WER
MOT
OR
SPEE
D C
HANG
E RE
LAY,
SPD
TBL
WR
BLO
WER
MOT
OR
RELA
Y, SP
ST-(N
.O.)
BLW
MBL
OW
ER M
OTO
R, PE
RMAN
ENT-
SPLI
T-CA
PACI
TOR
CAP
1, 2
CAPA
CITO
RCP
UM
ICRO
PRO
CESS
OR
AND
CIR
CUIT
RYEA
C-1
ELEC
TRO
NIC
AIR
CLEA
NER
CON
NECT
ION
(115
VAC
1.0
AMP
MAX
.)EA
C-2
ELEC
TRO
NIC
AIR
CLEA
NER
CON
NECT
ION
(CO
MM
ON)
FRS
FLAM
E RO
LLO
UT S
W. -
MAN
UAL
RESE
T, SP
ST-(N
.C.)
FSE
FLAM
E-PR
OVIN
G EL
ECTR
OD
EFU
1FU
SE, 3
AM
P, AU
TOM
OTI
VE B
LAD
E TY
PE, F
ACTO
RY IN
STAL
LED
FU 2
FUSE
OR
CIRC
UIT
BRE
AKER
CUR
RENT
INTE
RRUP
T D
EVIC
E(F
IELD
INST
ALLE
D &
SU
PPLI
ED)
GND
EQUI
PMEN
T GR
OUN
DGV
GAS
VALV
E-RE
DUN
DAN
TGV
R 1,
2GA
S VAL
VE R
ELAY
, DPS
T-(N
.O.)
HSI
HOT
SURF
ACE
IGN
ITER
(115
VAC)
HSIR
HOT
SURF
ACE
IGN
ITER
REL
AY, S
PST-
(N.O
.)HU
M24
VAC
HUM
IDIF
IER
CONN
ECTI
ON
(0.5
AM
P. M
AX.)
IDM
IND
UCE
D D
RAFT
MOT
OR,
PSC
IDR
IND
UCE
D D
RAFT
MOT
OR
RELA
Y, SP
ST-(N
.O.)
ILK
BLO
WER
ACC
ESS
PANE
L IN
TERL
OCK
SW
ITCH
, SPS
T-(N
.O.)
J1BL
OW
ER -
OFF
DEL
AY JU
MPE
R SE
LECT
OR
JBJU
NCTI
ON
BO
XLE
DLI
GHT
-EM
ITTI
NG D
IOD
E FO
R ST
ATUS
CO
DES
- AM
BER
LGPS
LOW
GAS
PRE
SSUR
E SW
ITCH
, SPS
T-(N
.O.)
LSLI
MIT
SW
ITCH
, AUT
O-R
ESET
, SPS
T (N
.C.)
OL
AUTO
-RES
ET IN
TERN
AL M
OTO
R OV
ERLO
ADTE
MPE
RATU
RE S
WIT
CH (N
.C.)
PCB
PRIN
TED
CIR
CUIT
BO
ARD
CO
NTRO
LPL
111
-CIR
CUIT
PCB
CO
NNEC
TOR
PL2
2-CI
RCUI
T CO
NNEC
TOR
PL3
2-CI
RCUI
T HS
I, C
ONN
ECTO
RPL
43-
CIRC
UIT
IDM
EXT
ENSI
ON
CO
NNEC
TOR
PRS
PRES
SURE
SW
ITCH
, SPS
T-(N
.O.)
TEST
/TW
INCO
MPO
NENT
TES
T &
TWIN
TER
MIN
ALTR
ANTR
ANSF
ORM
ER-1
15VA
C/24
VAC
JUNC
TIO
N
UNM
ARKE
D T
ERM
INAL
PCB
CON
TRO
L TER
MIN
AL
FACT
ORY
WIR
ING
(115
VAC)
FACT
ORY
WIR
ING
(24V
AC)
FIEL
D W
IRIN
G (1
15VA
C)
FIEL
D W
IRIN
G (2
4VAC
)
COND
UCTO
R O
N CO
NTRO
L PC
B
FIEL
D W
IRIN
G SC
REW
TER
MIN
AL
FIEL
D E
ARTH
GRO
UND
EQUI
PMEN
T GR
OUN
D
FIEL
D S
PLIC
E
PLUG
REC
EPTA
CLE
1.If
any
of th
e or
igin
al e
quip
men
t wire
is re
plac
ed u
se w
ire ra
ted
for 1
05°C
.2.
Use
onl
y co
pper
wire
bet
wee
n th
e di
scon
nect
sw
itch
and
the
furn
ace
junc
tion
box
(JB)
.3.
This
wire
mus
t be
conn
ecte
d to
furn
ace
shee
t met
al fo
r con
trol t
o pr
ove
flam
e.4.
Sym
bols
are
ele
ctric
al re
pres
enta
tion
only.
5.So
lid li
nes
insi
de P
CB
are
prin
ted
circ
uit b
oard
con
duct
ors
and
are
not i
nclu
ded
in le
gend
.6.
Rep
lace
onl
y w
ith a
3 a
mp
fuse
.7.
Indu
cer (
IDM
) and
blo
wer
(BLW
M) m
otor
s co
ntai
n in
tern
al a
uto-
rese
t the
rmal
ove
rload
sw
itche
s (O
L).
8.N
eutra
l con
nect
ions
are
inte
rcha
ngea
ble
with
in th
e N
EUTR
AL c
onne
ctor
blo
ck.
9.Bl
ower
mot
or s
peed
sel
ectio
ns a
re fo
r ave
rage
con
ditio
ns, s
ee in
stal
latio
n in
stru
ctio
ns fo
r det
ails
on
optim
um s
peed
sel
ectio
n.10
.YE
LLO
W le
ad n
ot o
n al
l mot
ors.
11.
Fact
ory
conn
ecte
d w
hen
LGPS
is n
ot u
sed.
12.
Igni
tion-
lock
out w
ill oc
cur a
fter f
our c
onse
cutiv
e un
succ
essf
ul tr
ials
-for-i
gniti
on. C
ontro
l will
auto
-rese
t afte
r thr
ee h
ours
.13
.Bl
ower
-on
dela
y: g
as h
eatin
g 60
sec
onds
, coo
ling
or h
eat p
ump
2 se
cond
s.14
.Bl
ower
-off
dela
y: g
as h
eatin
g se
lect
ions
are
90,
120
, 150
or 1
80 s
econ
ds, c
oolin
g or
hea
t pum
p90
sec
onds
or 5
sec
onds
whe
n de
hum
idify
cal
l is
activ
e.
NO
TE #
10
PRINTED CIRCIUT BOARD
PRINTED CIRCIUT BOARD
NO
TE #
5
A02157
Fig. 21 -- Wiring Diagram
350AAV
17
Is L
ED
sta
tus
light
on?
Is L
ED
sta
tus
light
blin
king
rap
idly
with
out a
paus
e?
Is L
ED
sta
tus
light
blin
king
ON
/OF
F s
low
lyw
ith a
com
bina
tion
of s
hort
and
long
flas
hes?
Det
erm
ine
stat
us c
ode.
The
sta
tus
code
is a
2 di
git n
umbe
r w
ith th
e fir
st d
igit
dete
rmin
edby
the
num
ber o
f sho
rt fl
ashe
s an
d th
e se
cond
digi
t by
the
num
ber
of lo
ng fl
ashe
s?
Go
to s
ectio
n be
low
for
the
stat
us c
ode
that
was
flas
hed.
Is th
ere
115V
at L
1 an
d L2
?
Is th
ere
24V
at S
EC
-1 a
nd S
EC
-2?
Rep
lace
furn
ace
cont
rol.
Che
ck fo
r co
rrec
t lin
e vo
ltage
pol
arity
and
gro
und-
ing.
If u
nits
are
twin
ned,
che
ck fo
r pr
oper
low
-
volta
ge (
24V
) tr
ansf
orm
er p
hasi
ng.
To r
ecal
l sta
tus
code
brie
fly r
emov
e an
d re
conn
ect o
ne R
ED
wire
from
the
Lim
itS
witc
h or
Fla
me
Rol
lout
sw
itch
to d
ispl
ay s
tore
d st
atus
cod
e. O
n R
ED
LE
Dco
ntro
l do
not r
emov
e po
wer
or
blow
er a
cces
s pa
nel b
efor
e in
itiat
ing
stat
usco
de re
call.
You
can
als
o re
call
the
prev
ious
sta
tus
code
by
mom
enta
rily
shor
ting
the
TE
ST
/TW
IN te
rmin
al to
Com
24V
term
inal
unt
il th
e LE
D g
oes
out.
LE
D w
illfla
sh th
e pr
evio
us s
tatu
s co
de o
r st
atus
cod
e #1
1 (1
sho
rt a
nd 1
long
flas
h) if
ther
e w
as n
o pr
evio
us c
ode.
Afte
r th
e co
ntro
l rep
eats
the
code
4 ti
mes
, the
cont
rol w
ill g
o th
roug
h a
brie
f com
pone
nt te
st s
eque
nce.
The
indu
cer
will
sta
rtan
d ru
n fo
r th
e en
tire
com
pone
nt te
st.
The
HS
I, bl
ower
mot
or F
AN
spe
ed(A
MB
ER
LE
D b
oard
s on
ly)
HE
AT s
peed
, and
CO
OL
spee
d w
ill r
un fo
r 10
– 1
5se
cond
s ea
ch.
Gas
val
ve a
nd h
umid
ifier
will
not
be
turn
ed o
n.
Was
ther
e a
prev
ious
sta
tus
code
othe
r th
an #
11?
Is d
oor
switc
h cl
osed
?
Is th
ere
115V
goi
ng to
sw
itch?
Rep
lace
doo
r sw
itch.
Rep
lace
tran
sfor
mer
.
Doe
s th
e co
ntro
l res
pond
to W
, Y1
(if p
rese
nt),
Y/Y
2, a
nd G
(24
V)
ther
mos
tat s
igna
ls?
Run
sys
tem
thro
ugh
a he
atin
g or
coo
ling
cycl
eto
che
ck o
pera
tion.
Sta
tus
code
s ar
e er
ased
afte
r 72
hou
rs.
On
RE
D L
ED
boa
rds
stor
edst
atus
cod
es c
an a
lso
be e
rase
d w
hene
ver
(115
V o
r 24
V)
is in
terr
upte
d.
Rep
lace
furn
ace
cont
rol.
Clo
se d
oor
switc
h an
d go
bac
k to
STA
RT.
Is c
ircui
t bre
aker
clo
sed?
Che
ck fo
r con
tinui
ty in
wire
from
circ
uit b
reak
erto
furn
ace.
Clo
se c
ircui
t bre
aker
and
go
back
to S
TAR
T.
Che
ck r
oom
ther
mos
tat o
rin
terc
onne
ctin
g ca
ble.
Is 2
4V p
rese
nt a
t W, Y
1 (if
pre
sent
), Y
/Y2
orG
ther
mos
tat t
erm
inal
s on
the
furn
ace
cont
rol?
Dis
conn
ect a
ll th
e th
erm
osta
t wire
s fr
om th
efu
rnac
e co
ntro
l.
Doe
s th
e pr
oble
m r
epea
t whe
n us
ing
a ju
mpe
r w
ire?
The
ther
mos
tat i
s no
t com
patib
le w
ith th
efu
rnac
e co
ntro
l. E
ither
inst
all a
bal
last
resi
stor
,co
nnec
t the
Com
24V
ther
mos
tat t
erm
inal
toth
e th
erm
osta
t, or
rep
lace
the
ther
mos
tat.
NO
YE
S
YE
S
NO
NO
YE
S
YE
S
YE
S
YE
S
NO
YE
S
YE
S
NO
YE
S
NO
YE
S
NO
NO
NO Y
ES
NO YE
S
NO
STA
RT
TR
OU
BLE
SH
OO
TIN
G G
UID
E
NO
A05107
350AAV
18
11N
O P
RE
VIO
US
CO
DE
– S
tore
d co
des
are
eras
ed a
fter 7
2 ho
urs.
On
RE
D L
ED
boar
ds s
tore
d st
atus
cod
es c
an a
lso
beer
ased
whe
neve
r po
wer
(11
5V o
r 24
V)
is in
terr
upte
d. R
un s
yste
m th
roug
h a
heat
ing
or c
oolin
g cy
cle
to c
heck
sys
tem
.
12B
LOW
ER
ON
AF
TE
R P
OW
ER
UP
–(1
15V
OR
24V
) –
Nor
mal
ope
ratio
n.B
low
er r
uns
for
90 s
econ
ds, i
f uni
t is
pow
ered
up
durin
g a
call
for
heat
(R
-Wcl
osed
) or
whe
n (R
-W o
pens
) du
ring
the
blow
er o
n-de
lay
perio
d.
13LI
MIT
CIR
CU
IT L
OC
KO
UT
– L
ocko
utoc
curs
if th
e lim
it or
flam
e ro
llout
sw
itch
isop
en lo
nger
than
3 m
inut
es.
Con
trol w
illau
to-r
eset
afte
r 3 h
ours
. S
ee c
ode
33.
14IG
NIT
ION
LO
CK
OU
T –
Sys
tem
faile
d to
igni
te g
as a
nd p
rove
flam
e in
4 a
ttem
pts.
Con
trol
will
aut
o-re
set a
fter
3 ho
urs.
See
sta
tus
code
34.
21G
AS
HE
ATIN
G L
OC
KO
UT
– T
urn
off
pow
er a
nd w
ait 5
min
utes
to r
etry
.C
heck
for:
-S
tuck
clo
sed
gas
valv
e re
lay
on c
ontro
l.-
Mis
wire
or
shor
t to
gas
valv
e w
ire.
22A
BN
OR
MA
L F
LAM
E-P
RO
VIN
G S
IGN
AL
Fla
me
is p
rove
d w
hile
gas
val
ve is
de-
ener
gize
d. I
nduc
er w
ill r
un u
ntil
faul
t is
clea
red.
Che
ck fo
r:-
Stu
ck o
pen
or le
aky
gas
valv
e.
23P
RE
SS
UR
E S
WIT
CH
DID
NO
T O
PE
NC
heck
for:
-O
bstr
ucte
d pr
essu
re tu
be.
-P
ress
ure
switc
h st
uck
clos
ed.
24S
EC
ON
DA
RY
VO
LTA
GE
FU
SE
IS O
PE
NC
heck
for:
-S
hort
circ
uit i
n se
cond
ary
volta
ge (2
4V)
wiri
ng in
clud
ing
ther
mos
tat l
eads
.D
isco
nnec
t the
rmos
tat l
eads
to is
olat
esh
ort c
ircui
t.
31P
RE
SS
UR
E S
WIT
CH
DID
NO
T C
LOS
EO
R R
EO
PE
NE
D –
If o
pen
long
er th
an 5
min
utes
, ind
ucer
shu
ts o
ff fo
r 15
min
utes
befo
re r
etry
. If
open
s du
ring
blow
er o
n-de
lay
perio
d, b
low
er w
ill c
ome
on fo
r th
ese
lect
ed b
low
er o
ff-de
lay.
Che
ck fo
r:-
Pro
per
vent
siz
ing.
-Lo
w in
duce
r vo
ltage
(11
5V).
-Lo
w in
let g
as p
ress
ure
(if L
GP
S u
sed)
.-
Inad
equa
te c
ombu
stio
n ai
r su
pply
.-
Dis
conn
ecte
d or
obs
truc
ted
pres
sure
tubi
ng.
-D
efec
tive
indu
cer
mot
or.
-D
efec
tive
pres
sure
sw
itch.
-E
xces
sive
win
d.-
Res
tric
ted
vent
.
33LI
MIT
CIR
CU
IT F
AU
LT –
Indi
cate
s th
elim
it or
flam
e ro
llout
sw
itch
is o
pen.
Blo
wer
will
run
for 4
min
utes
or u
ntil
open
sw
itch
rem
akes
whi
chev
er is
long
er.
If op
enlo
nger
than
3 m
inut
es, c
ode
chan
ges
tolo
ckou
t #13
. If
open
less
than
3 m
in.
stat
us c
ode
#33
cont
inue
s to
flas
h un
tilbl
ower
shu
ts o
ff. F
lam
e ro
llout
sw
itch
requ
ires
man
ual r
eset
. C
heck
for:
-D
irty
filte
r or
res
tric
ted
duct
sys
tem
.-
Loos
e bl
ower
whe
el.
-D
efec
tive
switc
h or
con
nect
ions
.-
Def
ectiv
e bl
ower
mot
or o
r ca
paci
tor.
-In
adeq
uate
com
bust
ion
air
supp
ly(f
lam
e ro
llout
sw
itch
open
).-
Res
tric
ted
vent
.-
Pro
per
vent
siz
ing.
-E
xces
sive
win
d.-
Blo
wer
mot
or o
n in
corr
ect s
peed
tap.
- In
put r
ate
to fu
rnac
e se
t too
hig
h.
34IG
NIT
ION
PR
OV
ING
FA
ILU
RE
– If
flam
eis
not
sen
sed
durin
g th
e tr
ial f
or ig
nitio
npe
riod,
the
cont
rol w
ill r
epea
t the
igni
tion
sequ
ence
3 m
ore
times
bef
ore
lock
out
#14
occu
rs.
If fla
me
sign
al is
lost
dur
ing
the
blow
er o
n-de
lay
perio
d, b
low
er w
illco
me
on fo
r the
sel
ecte
d bl
ower
off-
dela
y. C
heck
the
follo
win
g ite
ms
first
bef
ore
proc
eedi
ng to
the
next
ste
p.-
Gas
val
ve tu
rned
off.
-M
anua
l shu
t-of
f val
ve.
-G
reen
/Yel
low
wire
MU
ST
be
conn
ecte
dto
furn
ace
shee
t met
al.
-F
lam
e se
nsor
mus
t not
be
grou
nded
.To
det
erm
ine
whe
ther
the
prob
lem
is in
the
gas
valv
e, ig
nite
r, or
flam
e se
nsor
the
syst
em c
an b
e op
erat
ed in
the
com
pone
ntte
st m
ode
to c
heck
the
igni
ter.
Firs
tre
mov
e th
e R
ther
mos
tat c
onne
ctio
n fro
mth
e co
ntro
l and
initi
ate
the
com
pone
ntte
st s
eque
nce.
Doe
s th
e ig
nite
r gl
owor
ange
/whi
te b
y th
e en
d of
the
15 s
econ
dw
arm
-up
perio
d?
Unp
lug
igni
ter h
arne
ss fr
om c
ontro
l and
initi
ate
anot
her
com
pone
nt te
st s
eque
nce.
Che
ckfo
r 115
V b
etw
een
pin
1 an
d N
EU
TR
AL-
L2 o
nth
e co
ntro
l. W
as 1
15V
pre
sent
for
the
15se
cond
per
iod?
Rec
onne
ct th
e R
ther
mos
tat l
ead
and
set
ther
mos
tat t
o ca
ll fo
r hea
t. C
onne
ct v
oltm
eter
acro
ss g
as v
alve
con
nect
ions
. D
oes
gas
valv
ere
ceiv
e 24
V?
Doe
s ga
s va
lve
open
and
allo
w g
as to
flow
?
Do
the
mai
n bu
rner
s ig
nite
?
Do
the
mai
n bu
rner
s st
ay o
n?
Rep
eat c
all f
or h
eat a
nd c
heck
flam
e se
nsor
curr
ent d
urin
g tr
ial f
or ig
nitio
n pe
riod.
Is
the
DC
mic
roam
ps b
elow
0.5
?
Is c
urre
nt n
ear
typi
cal v
alue
?
Will
mai
n bu
rner
s ig
nite
and
sta
y on
?
Fix
ed.
Cle
an fl
ame
sens
or w
ith fi
ne s
teel
woo
l and
rech
eck
curr
ent.
Nom
inal
cur
rent
is 4
.0 to
6.0
mic
roam
ps.
45C
ON
TR
OL
CIR
CU
ITR
Y L
OC
KO
UT
Aut
o-re
set a
fter
1 ho
ur lo
ckou
t due
to:
-F
lam
e ci
rcui
t fai
lure
.-
Gas
val
ve r
elay
stu
ck o
pen.
-S
oftw
are
chec
k er
ror.
Res
et p
ower
to c
lear
lock
out.
Rep
lace
cont
rol i
f cod
e re
peat
s.
Rep
lace
furn
ace
cont
rol.
Che
ck fo
r con
tinui
ty in
the
harn
ess
and
igni
ter.
Rep
lace
def
ectiv
e co
mpo
nent
.
Che
ck c
onne
ctio
ns.
If O
K, r
epla
ce c
ontr
ol.
Che
ck th
at a
ll ga
s va
lves
are
turn
ed o
n.R
epla
ce v
alve
.
Che
ck fo
r:-
Inad
equa
te fl
ame
carr
yove
r or
rou
ghig
nitio
n.-
Low
inle
t gas
pre
ssur
e.-
Pro
per
firin
g ra
te.
Allo
w b
low
er to
com
e on
and
rep
eat t
est t
och
eck
for
inte
rmitt
ent o
pera
tion.
Che
ck c
onne
ctio
ns a
nd r
etry
. If
curr
ent i
sne
ar ty
pica
l val
ue (
4.0-
6.0
nom
inal
) an
dbu
rner
s w
ill n
ot s
tay
on, r
epla
ce c
ontr
ol.
Rep
lace
ele
ctro
de.
Rep
lace
furn
ace
cont
rol.
YE
S
YE
S
YE
S
YE
S
NO
YE
S
YE
S
YE
S
NO
YE
S
NO
NO
NO
YE
S
NO
NO
NO
NO
A05096
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
E2009 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 09/09
Replaces: SM350AAV---01
Catalog No. SM350AAV---02
350AAV