The materials included in this compilation are for the use of Dwyer Instruments, Inc. potential customers and current employees as a resource only. They may not be reproduced, published, or transmitted electronically for commercial purposes. Furthermore, the Company’s name, likeness, product names, and logos, included
within these compilations may not be used without specific, written prior permission from Dwyer Instruments, Inc. ©Copyright 2011 Dwyer Instruments, Inc
ULT BasicsULT- Ultrasonic Level Transmitter
Non-contact continuous level monitoring
Operation:Ultrasonic level transmitter is installed above the fluidAn ultrasonic signal is transmitted to the fluid level and reflected back to the sensor
SpecificationsMedia: Fluids OnlyRanges:
7.5 m10 m
Accuracy: ±0.2% of maximum range
+/- 1.5 cm for 7.5m range
Blind Zone: Under 20 cmBeam Width: 7.6 cm diameterOutput Signal: 4 to 20 mA or 20 to 4 mA
ULT Advantages7.62 cm Beam Technology
Allows for:Stand pipe mountingRiser MountingConfined location mounting
Conic beam technology:Limit use in confined areasCannot be used in:
StandpipesRiser
Prone to false readings
ULT AdvantagesWeatherproof & Explosion Proof
Weather-proof meets IP 67
FM Approved Explosion-proof Housing
Rated Class I, Div. 1, Groups B, C, D; Class II/III, Div. 1, Groups E, F, G.
6 digit local LCD display w/ Push Buttons
NO HANDHELD or LAPTOP REQUIRED
Units selectionTank dimensionsEasy Programming
ULT AdvantagesFail safe setting in case of loss of echo
Settable output: 3mA21 mA22 mA
Alerts management system if level: enters dead zone or greater than allowable range
ULT Advantages
2 wire deviceNo Additional power supply needed
And of Course-
Very Competitively Priced!!!
Applications
Continuous Level Monitoring for:Fuel Tank LevelDigester Tank LevelPump Lift StationsWet Well Level Chemical Tank LevelCooling Tower Level
Cooling Tower Make UpApplication
InstallationLiquid applications onlyDo not use with:
High Temperatures (60°C +)Vacuum ApplicationsPressures above 2 BarWater Vapor atmospheres
Can be installed 7.62 cm or more away from side wallCan be installed within a riser or 7.62 cm stand pipeObjects in beam path will give false readings
Beam path
Button Operation
INDEXAdvances the display to the next menu item
ENTERPress for two seconds to enter Operating/Programming modeAlso stores changes when programming
UP/DownIncreases/Decreases value when programming
Base Menus
DisplaySelect Units, Air or Liquid Level, Distance or % displayed
Tank Enter Tank Dimensions
OutputSet Safe mode and analog output direction
Base Menus
Target CalManual Calibration through liquid level adjustment
ValuesAllows user to scroll through setup parameters
ULT Adjusting Units
Hold ENTER Press ENTER Press ENTER
Press INDEX until you see UNITS
ULT Adjusting Units
Press INDEX
Once “Meter” is displayed, press ENTER
“saved” confirms selection
ULT Adjusting Units
Press INDEX until “Exit” appears then press ENTER
Press INDEX until “Run” appears then ENTER
ULT Tank Dimensions
Hold ENTER
Press INDEX
1 time
Press ENTER
ULT Tank Dimensions
Press ENTER Use UP/DOWN
Arrows to adjust tank Height, then press ENTER
“saved” confirms selection
ULT Tank Setting
Press INDEX until “Fill Height” appears then ENTER
Adjust Height Then Press ENTER
“saved” confirms selection
ULT Tank Dimensions
Press INDEX until “Exit” Appears
Press INDEX Until “Run” Appears then ENTER
ULT Output Settings
Hold ENTER
Press INDEX
2 time
Press ENTER
ULT Output Settings
Press INDEX until “Safe mode” appears, then ENTER
Adjust fail safe setting then press ENTER
“Saved” confirms selection
ULT Output Settings
Press INDEX until “Norm” appears then ENTER
Use INDEX to select Norm or Reverse acting
Press ENTER to select
ULT Output Settings
“Saved” confirms selection
Press INDEX until “EXIT” appears then ENTER
Press INDEX until “RUN” appears then ENTER
ULF/ULC SeriesULF/ULC
Ultra Sonic Flow TransmitterNon-contact continuous flow monitoring
Operation:Ultrasonic level transmitter is installed above the fluid channelA ultrasonic signal is transmitted to the fluid level and reflected back to the sensorUsing Cross-Sectional Area of the channel & level a flow can be obtained
Applications
Used as a flow monitor for open channels
Designed to be mounted above open channels such as:
FlumesWeirs
Open channel flow construction
Weirs Used for a known dimension to calculate open channel flowCommonly used in irrigation or man-made channels
Open channel flow construction
FlumesUsed for a known dimension to calculate open channel flowCommonly used in natural occurring channels
ULF SpecificationsRanges:
ULF-X1-XXX: 0.25 to 5 mULF-X2-XXX: 0.6 to 15 m
Accuracy: 0.25% of max. range (at 20°C)Blind Zone:
ULF-X1-XXX: .25 mULF-X2-XXX: 0.6 m
Beam Angle: 5°Output Signal: 4 to 20 mAEnclosure Rating: IP65
ULF/ULC Advantages4 Digit Local Display
Push button programming
Pre-Programmed for various sizes of Weirs & Flumes
100+ shapes/sizesMetric & US based sizes
ULF/ULC Advantages
Calibrates up to 6 Interfering SignalsAuto calibration eliminates all possible interfering signals
VibrationUltrasonic Other acoustic signals
Prevents errors in future operation