series connection - rdl hydraulics · d 8086 03-2015-1.2 series connection operating pressure p...
TRANSCRIPT
Proportional directional spool valve type EDL
Product documentation
D 808603-2015-1.2
Series connection
Operating pressure pmax: 320 barFlow rate Qmax: 40(60) lpm
2 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
© by HAWE Hydraulik SE.
The forwarding and reproduction of this document, as well as the use and communication of its contents, are forbidden unless expresse-
ly permitted.
Any breach or infringement will result in liability for damages.
All rights reserved concerning patent or utility model registrations.
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 3
Contents
1 Overview proportional directional spool valve type EDL...................................................................................... 4
2 Type coding, overview.......................................................................................................................................5
3 Available versions, main data............................................................................................................................9
3.1 Connection blocks and end plates........................................................................................................................ 9
3.1.1 Connection blocks for constant pump systems (with integrated 3-way controller) type PSL........................................... 9
3.1.2 Connection blocks for control pumps/constant pressure systems............................................................................. 10
3.1.3 Adapter plates................................................................................................................................................. 11
3.1.4 End plates.......................................................................................................................................................11
3.2 Add-on spool valves......................................................................................................................................... 12
3.2.1 Directional spool valve......................................................................................................................................12
3.2.2 In series intermediate plates............................................................................................................................. 15
4 Parameters..................................................................................................................................................... 16
4.1 General and hydraulic....................................................................................................................................... 16
4.2 Characteristic curves......................................................................................................................................... 18
4.3 Actuations....................................................................................................................................................... 19
5 Dimensions.................................................................................................................................................... 21
5.1 Connection blocks............................................................................................................................................ 21
5.2 In series intermediate plates............................................................................................................................. 23
5.3 Directional spool valve with actuation E, EI........................................................................................................ 24
6 Installation, operation and maintenance information........................................................................................25
6.1 Designated use................................................................................................................................................ 25
6.2 Assembly information........................................................................................................................................25
6.3 Operating instructions.......................................................................................................................................26
6.4 Maintenance information................................................................................................................................... 26
6.5 Planning information........................................................................................................................................ 27
6.5.1 Notes for selection and lay-out..........................................................................................................................27
6.5.2 Circuit examples...............................................................................................................................................30
7 Other information...........................................................................................................................................33
7.1 Note regarding assembly, installation and conversion............................................................................................33
7.1.1 Mounting.........................................................................................................................................................33
7.1.2 Piping.............................................................................................................................................................33
7.1.3 Sealing kits..................................................................................................................................................... 33
4 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
1 Overview proportional directional spool valve type EDL
Proportional directional spool valves are a type of directional valve. They control
the direction of movement and the velocity of individual or multiple hydraulic
consumers actuated simultaneously. Control is independent of the load and
continuous.
The directional spool valve type EDL with series connection is actuated directly.
The flows for the individual consumers can be individually adjusted. By means of
additional functions in the intermediate plates (longitudinal and sandwich valve
combination) and ancillary blocks the proportional directional spool valve can be
flexibly adapted to different control tasks.
The directional spool valve type EDL can be combined directly with the
proportional directional spool valve type PSL and PSV in size 2. It is used in
mobile hydraulics, in particular in civil engineering and hydraulic tools.
Features and benefits:
■ One product for various control functions and small volume quantities
■ Energy-saving closed-centre systems
■ Compact and lightweight design
■ Modular system can be directly combined with type PSL/PSV-2
Intended applications:
■ Construction and construction materials machinery
■ Cranes and lifting equipment
■ Machines for forestry and agricultural purposes
■ Municipal trucks
Figure 1: Proportional directional spool valve type EDL
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 5
2 Type coding, overview
Order coding example:
PSL 3 . 1 Z /D400 -2 -DA
-DA
2
2
L
H
25/16
40/25
/E
/EI
/2
/2 AN300 BN350 -E4 -G24
Solenoid
voltage
Table 15 Solenoid voltage
and design
End plates Table 14 End plates
Ancillary blocks Table 13 Connection blocks
Actuation types Table 12 Actuation types and additives
Volumetric flow key figure Table 11 Volumetric flow key figure
Circuit symbols Table 10 Circuit symbols
Directional spool valve, basic valve Table 9 Directional spool valve, basic valve
Connection Table 8 Connection on the directional spool valve for A and B
Size Table 7 Size
Pressure-limiting valve Table 6 Pressure-limiting valve
2/2-way solenoid valve Table 5 2/2-way solenoid valve
Control oil supply Table 4 Control oil supply
Additional elements Table 3 Additional features
Connection Table 2 Connection on the connection block for P and R
Basic type Table 1 Basic type for connection block
A maximum of 10 directional spool valves can be switched in series in one or more valve manifold(s) via the internal LS line. If more are
required, external wiring is to be provided (see note in Chapter 6.5, "Planning information" ("combination of more than 10 directional
spool valves")).
6 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
Table 1 Basic type for connection block
Coding Description
PSL Hydraulic oil supply via constant pump (open
centre)
PSV Hydraulic oil supply via control pump with load-
sensing controller (closed centre), as 2nd separate
block and for constant pressure systems
ZPL 52 Adapter plate for transition from PSL(V) size 5 (acc.
to D 7700-5) to EDL 2
ZPL 32 Adapter plate for transition from PSL(V) size 3 (acc.
to D 7700-3) to EDL 2
PSV E0 Initial plate without separate ports. Can only be
used in combination with the middle input block
ZPL 22 P6R6, see Chapter 3.2.2, "In series interme-
diate plates"
Operating pressure max = 250 bar!
Table 2 Connection on the connection block for P and R
Coding Connection Standard
3 G 1/2 (BSPP) (ISO 228/1)
UNF 2 3/4-16 UNF-2B (SAE-8, SAE J 514)
Table 3 Additional features
Coding Description
No designation Standard version
S
W
Additional damping element in the LS gallery
B
B 4...7
Orifice in LS line
G Restrictor check valve
Z Restrictor check valve + release valve (type PSL)
H Increased circulation pressure of the 3-way
controller approx. 14 bar(only PSL)
U
UH
Automatic reduction of the pump circulation
pressure due to bypass valve
N Integrated pump gallery locking (type PSV)
Table 4 Control oil supply
Coding Description
No designation Without pressure-reducing valve, e.g. for external
control oil supply (min. 20 bar up to max. 40 bar)
1 With integrated pressure-reducing valve for internal
control oil supply (control pressure approx. 20 bar)
2 With integrated pressure-reducing valve for internal
control oil supply (control pressure approx. 40 bar)
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 7
Table 5 Optional 2/2-way solenoid valve for random pump
direction switching
Coding Description
No designation Without directional valve, however an option for
flange mounting is available
Z
ZMDe-
energised
open
Pump direction switching for de-
energised valve
V De-
energised
closed
Pump direction switching with
energised valve
F..
or D..
For pressure-limiting valve for second pressure stage
(e.g. F50)
PA
PB
PD
Proportional pressure-limiting valve with different
pressure ranges
Table 6 Pressure-limiting valve (main pressure-limiting valve)
in the connection block (only fixed)
Coding Description
/D... Pressure-limiting valve set to ... bar
/... for type PSL...U
Table 7 Size
Coding Description
2 Size 2
Table 8 Connection on the directional spool valve for A and B
Coding Description
DA To attach ancillary blocks, see Table 13
Table 9 Directional spool valve, basic valve
Coding Description
2 Directional spool valve with input controller for
individual volumetric flow metering
5 Input controller with reinforced spring for higher
volumetric flow
R 2, R 5 like A 2, A 5 but with check valve function
Table 10 Circuit symbols
Coding L H
Table 11 Volumetric flow key figure for outlets A and B
(see Table 5 Chapter 3.2.1)
Coding Description
.../... Coding for outlet A or B (can be selected separate-
ly) 3, 6, 10, 16, 25, 40, 50
Table 12 Actuation types
Coding Description
/E Electrical actuation with stroke limitation
/EI Electrical actuation with manual override
8 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
Table 13 Ancillary blocks
Coding Description
/2
/3
/UNF 2
Ancillary blocks without additional functions
/2 AS.. BS.. Ancillary blocks with shock valves at A and B
(mutual spraying), with pressure specification (bar)
/2 AN... BN...
/UNF 2 AN..
BN..
Ancillary blocks with shock and servo-suction valves
at A and B, with pressure specification (bar)
/UNF 2 AN..
/UNF 2 BN..
Ancillary blocks with shock and servo-suction valves
at A or B, with pressure specification (bar)
/2 AL.. BL..
/UNF 2 AL..
BL..
Ancillary blocks with load-holding valves at A and
B, with pressure specification (bar)
/2 AL..
/2 BL..
/UNF 2 AL..
/UNF 2 BL..
Ancillary blocks with load-holding valves at A or B,
with pressure specification (bar)
/2 DRH
/UNF 2 DRH
Ancillary blocks with releasable check valves
/32 DFA
/32 DFB
Ancillary blocks for differential circuit
/3 AVT
/3 BVT
Check valve for A or B with emergency function
/2 A(B) HN Ancillary blocks with emergency drain
Table 13a Intermediate plates
Coding Description
/ZSS
/ZVV
Intermediate plates with bypass valves
/ZDR
/ZDS
Short-circuit valve between A and B
/ZAL.. BL.. Intermediate plates with load-holding valves at A
and B, with pressure specification (bar)
/Z 2 A(B).. Intermediate plates with additional port
/ZDRH Intermediate plates with releasable check valves
/Z 40 Spacer plate
/ZANBN Intermediate plates with servo-suction valves
/ZVX
/ZXV
Intermediate plates with check valves in A or B
Table 14 End plates
Coding Description
E. With thread acc. to ISO 228/1
E. UNF With thread acc. to SAE-4, acc. to SAE J 514
E0 End plate without additional function, not in
combination with valve sections SL2, SL3 or SL5
Operating pressure max. 250 bar!
E1 With control oil return line T external to tank
(standard version)
E2 Like E1, with additional connection Y for connection
to the LS outlet of another one, separate
E4 Like E1, however control oil return line is internal,
maximum return pressure of 10 bar!
E5 Like E2, however control oil return line is internal,
maximum return pressure of 10 bar!
E17... E20
E17 UNF... E20
UNF
For variants see D 7700-2, Table 10
Table 15 Solenoid voltage and solenoid design
Coding Description
G 12 12V DC, connection acc. to DIN EN 175 301-803 A
G 24 24V DC, connection acc. to DIN EN 175 301-803 A
AMP 12 K 4 12V DC, connection with AMP Junior Timer
AMP 24 K 4 24V DC, connection with AMP Junior Timer
DT 12 12V DC, connection with Deutsch connector
DT 24 24V DC, connection with Deutsch connector
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 9
3 Available versions, main data
3.1 Connection blocks and end plates
There are two basic variants of connection blocks:
■ Connection blocks with integrated 3-way controller when using a constant pump system (open centre) - type PSL (Chapter 3.1.1,
"Connection blocks for constant pump systems (with integrated 3-way controller) type PSL ")
■ Connection blocks for use with control pump systems (closed centre), constant pressure systems or for parallel oil supply of
multiple physically separate directional spool valve banks in the second and all further valve blocks - type PSV (Chapter 3.1.2,
"Connection blocks for control pumps/constant pressure systems ")
Order coding of one connection block as an individual section (examples):
PSL 31 Z/250 - 2 - G24
Note
Size specification absolutely necessary, here -2!
3.1.1 Connection blocks for constant pump systems (with integrated 3-way controller) type PSL
The EDL valve sections can be easily combined with all type PSL(V) connection blocks, size 2. For a detailed overview of the available
variants, see D 7700-2.
10 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
3.1.2 Connection blocks for control pumps/constant pressure systems
Order coding example:
PSV 3X . - 2 -...- E1
Additional element Table 2 Coding for additional features
Connection blocks Table 1 Connection blocks
Table 1 Connection blocks
Coding Connection (BSPP) Description
PSV 3X-2 G 1/2 Connection blocks for control pumps
PSV 3X B.-2 G 1/2 Connection blocks for control pumps with damping orifices, see Table 2
PSV E0 -- Initial plate without separate ports. Can only be used in combination with the
middle input block ZPL 22 P6R6, see Chapter 3.2.2, "In series intermediate plates"
Operating pressure max = 250 bar!
Circuit symbols
PSV 3X-2 PSV 3X B.-2 PSV E0-2
For additional connection blocks for control pumps/constant pressure systems, see D 7700-2.
The EDL valve sections can be easily combined with all type PSL(V) connection blocks, size 2.
Table 2 Coding for features in the LS signal duct for the damping of pump controllers
(For notes and explanation see Chapter 6.5, "Planning information" ("About the connection block"))
Additional features only suitable where control pumps are used (limitation of the control oil flow).
Coding Description
No designation Standard, without additional feature
B 4, B 5, B 6, B 7, B 8 With orifice # 0.4 mm, 0.5 mm, 0.6 mm, 0.7 mm or 0.8 mm in the LS duct (to limit control oil flow)
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 11
3.1.3 Adapter plates
Order coding example:
PSL 41/D250-3 - 42 H 80/63 /E
- ZPL 32
- DA2 L 25/16 /E/2 - E4 - G 24
Coding Port Description Circuit symbol
ZPL 32 -- Adapter plate for transition from proportional directional spool valves,
type PSL(V) size 3 to EDL 2.
ZPL 52 -- Adapter plate for transition from proportional directional spool valves,
type PSL(V) size 5 to EDL 2
3.1.4 End plates
The EDL valve sections can be easily combined with all type PSL(V) end plates, size 2. For a detailed overview of the available versions,
see D 7700-2.
Coding Connection Description Circuit symbol
E0 -- End plate without additional function, not in combination with valve
sections SL2, SL3 or SL5
Operating pressure max. 250 bar!
12 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
3.2 Add-on spool valves
3.2.1 Directional spool valve
Order coding example:
PSV 31/D250 - 2 - DA 2 L 25/40 /E /2 - E1 - G 24
Ancillary blocks Table 7 Ancillary blocks
Actuation types Table 6 Actuation types
Flow Table 5 Maximum flow
Circuit symbols Table 4 Circuit symbols
Directional spool valve, basic valve Table 3 Directional spool valve, basic valve
Order coding of the individual sections (examples) Directional spool valve
Valve spool (single)
EDL 2 - DA2 L 25/40 F 2/EI-G 24
EDL 2 - L 25/40
Note
Size specification absolutely necessary, here EDL 2!
The valve spools are subsequently interchangeable, e.g. if a different volumetric flow rating than initially planned becomes
necessary.
Table 3 Directional spool valve, basic valve
Coding Description
DA 2 Standard, with input controller, for simultaneous load compensated moving of several consumers (4/3-way directional
spool valve, standard version, control pressure approx. 6 bar)
DA 5 With input controller (for circuit symbol, see coding 2) but with reinforced 2-way control spring (control pressure approx.
9 bar ).
Only usable in conjunction with connection blocks type PSL.H../... or type PSV or the middle input block type ZPL 22
P6R6, see Chapter 6.5 "Planning information"
DAR 2
DAR 5
Like coding 2, 5, but with additional check valve function (spool valve = slight leakage)
Only usable in conjunction with connection blocks type PSL.H../... or type PSV or the middle input block type ZPL 22
P6R6, see Chapter 6.5 "Planning information"
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 13
Circuit symbol
With respect to main flow and
actuation, the circuit symbols are
neutral and must be supplemented by
the corresponding circuit symbols given
in Tables 5, 6 or 7, see also examples in
Table 7 and Chapter 6.
Ancillary block and intermediate block acc. to
D 7700-2
4/3-way directional
spool valve with input
controller DA2... (DA5...,
DA7...)
Table 4 Circuit symbols
L H
Table 5 Maximum flow P d A(B) in accordance with coding
Coding for volumetric flow QA, B (lpm)
at consumer ports A and B
Coding for spool valve
acc. to Table 4
3 6 10 16 25 40 50
2 3 6 10 16 25 40 50
5 4 9 14 22 34 54 --
Note
The flows for the consumer ports A and B can be selected freely, e.g. 25/40, 6/16. This enables optimal adaptation to the
respective consumer while exploiting the full functional lift. In addition there is the possibility of stroke limitation.
The maximum reflux volumetric flow must not exceed 80 lpm.
Spool valves with coding 50 may only be used at cylinder ratio 1:1.
14 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
Table 6 Actuation types
Actuation Electrical actuation
Electrical actuation with stroke
limitation
Electrical actuation with manual
override
Coding
E EI
Circuit symbol
Correcting variables Control current ratio I/IN
min. approx. 0.2
max. approx. 1
Note
■ For reference values for start of flow at A or B (= min) up to max. usable volume flow in accordance with the volumetric flow
coding Tables , see characteristic curves, Chapter 4.2 "Characteristic curves ".
Table 7 Ancillary blocks
The EDL valve sections can be easily combined with all type PSL(V) connection blocks, size 2. For a detailed overview of the available variants,
see D 7700-2.
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 15
3.2.2 In series intermediate plates
The EDL valve sections can be easily combined with all type PSL(V) connection blocks, size 2. For a detailed overview of the available
variants, see D 7700-2.
PSV E0-2 - DA2 L 40/40 /EI
- ZPL 22 P6R6
- DA2 H 25/16 /EI/2 - E0 - G 24
Coding Connection Description Circuit symbol
ZPL 22 P6R6 P and R = G 1 1/4
(BSPP)
Middle input block for installation of EDL 2 sections on both sides.
Hydraulic oil supply via control pump with load-sensing controller, as
2nd separate block or for constant pressure systems.
Only possible in combination with initial plate PSV E0 - 2.
16 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
4 Parameters
4.1 General and hydraulic
General information
Description Proportional directional spool valves EDL
Design Spool valve in block construction, up to 10 spool valves, all-steel design
Material Steel; nitrided valve housing, electrogalvanised sealing nuts and connection block, hardened
and ground functional inner parts
Steel; valve housing galvanized zinc plated; hardened and ground functional inner parts
Surface treatment (solenoid): DIN 50979-Fe ZnNi 8
Mounting Valve bank M8 Chapter 5, "Dimensions"
Tightening torques See Chapter 5, "Dimensions"
Installation position As desired
Ports P Hydraulic oil inlets (pump) or lead-on
R Return lines
A, B Consumer ports
LS Load-signal outlet, e.g. port for pump controller on PSV.
Caution
No pressure line!
M Pressure gauge port (pump side)
Z Pilot pressure connection
(inlet: 20...40 bar; outlet: 20 or 40 bar )
T Control oil tank line
Y Load-signal inlet (end plates E 2, E 5, E 18, E 18 UNF, E 20 and E 20
UNF)
Surface treatment All surfaces corrosion-inhibiting, gas nitrided
Solenoid at actuation E.. Zinc galvanised and passivated
Hydraulic fluid Hydraulic oil conforming DIN 51 524 part 1 to 3; ISO VG 10 to 68 conforming DIN 51 519
Viscosity limits: min. approx. 4, max. approx. 1500 mm2/s
opt. operation approx. 10... 500 mm2/s.
Also suitable are biologically degradable pressure fluids types HEPG (Poly-alkylenglycol) and
HEES (Synth. Ester) at service temperatures up to approx. +70°C.
Recommended purity class ISO 4406
20/17/14...18/15/12
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 17
Temperatures Ambient: approx. -40 ... +80°C, Fluid: -25 ... +80°C, Note the viscosity range!
Permissible temperature during start: -40°C (observe start-viscosity!), as long as the service
temperature is at least 20K higher for the following operation.
Biologically degradable pressure fluids: Observe manufacturer's specifications. By considera-
tion of the compatibility with seal material not over +70°C.
Note
Note restrictions on explosion-proof solenoid!
Pressure and volumetric flow
operating pressure ■ pmax = 320 bar; connections P, A, B, LS, M, Y
■ The achievable pressure on the consumer side of the directional spool valves is lower by an
amount equal to the fall in internal control pressure at the 3-way valve PSL (see character-
istic curve) or the pump controller (PSV).
■ Return connection R(R1) ≤ 50 bar
volumetric flow Max. consumer volumetric flow in accordance with Table 5 Chapter 3.2.1, "Directional spool
valve"
Weight
Connection block
PSV 3X = 1.7 kg
PSV E0 = 0.3 kg
For other connection blocks, see D 7700-2
Valve section
DA.. E, EI = 1.6 kg
For other ancillary blocks, see D 7700-2
18 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
4.2 Characteristic curves
Characteristic curves
Viscosity during measurements
approx. 60 mm2/s
Δp-Q characteristic curves
Pressure-limiting valve in the middle input
block, type
ZPL 22 P6R6
Directional spool valve
PdA(B), A(B)dR
Figure 2: Q volumetric flow (lpm);
p pressure setting (bar)Figure 3: Q volumetric flow (lpm);
/p pressure setting (bar)
2-way input controller
Figure 4: Q volumetric flow (lpm);
p load pressure (bar)
Control characteristic curve for consumer volumetric flow
(guidelines, example for directional spool valve variant with input controller type EDL 2 - D.
2...)
Figure 5: Q consumer volumetric flow (lpm), I
control current (A)
Figure 6: Q consumer volumetric flow (lpm), I
control current (A)
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 19
4.3 Actuations
For other data, such as coding, circuit symbols, etc. see Chapter 3.2, " Add-on spool valves"
General information
Actuation E, EI Proportional solenoid, manufactured and tested acc. to DIN VDE 0580
single-action solenoid with anchor chambers sealed on the outside and connected to the
return duct. The anchors are thereby maintenance-free lubricated by the hydraulic fluid and
protected against corrosion.
Specifications apply to all solenoid versions, unless specified otherwise
Nominal voltage UN 24V DC 12V DC
Coil resistance R20 22 Ω 5.5 Ω
Current, cold I20 1.10 A 2.18 A
Limit current IG (Ilim) 0.78 A 1.56 A
Power, cold P20 = UN x I20 26 W 26 W
Limit power PG = UN x IG 19 W 19 W
Cut-off energy WA Ò 0.3 Ws Ò 0.3 Ws
Rel. duty cycle (reference temperature δ11 =
50°C)
S1 S1
Required dither frequency 40...70 Hz (recommended value: 55 Hz)
Dither amplitude 20% Ò AD Ò 50%
Characteristic curves
Viscosity during measurements
approx. 60 mm2/s
I stroke characteristic curve
Figure 7: Control current (I,IG); Spool stroke (%)
20 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
Electrical connection
Circuitry for coding
-X 12, -X 24
DIN EN 175 301-803 A
Coil a (1) Coil b (2) IP 65 (IEC 60529)
-AMP 12, -AMP 24 -DT 12, -DT 24
AMP Junior Timer
IP 65 (IEC 60529) IP 67 (IEC 60529)
The specifications regarding the IP protection class apply for versions featuring a properly
assembled plug
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 21
5 Dimensions
All dimensions in mm, subject to change!
5.1 Connection blocks
Connection blocks
PSV 3X.-2 PSV E0-2
1 End plate
2 Directional spool valve, see Chapter 5.3
1 End plate
2 Directional spool valve, see Chapter 5.3
Ports
P, R LS, M
PSV 3X.-2 G 1/2 G 1/4 (ISO 228/1)
22 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
Adapter plates
ZPL 32 ZPL 52
1 Add-on spool valves, size 3
2 Add-on spool valves, size 2 acc. to D 7700-2 1 Add-on spool valves, size 5
2 Add-on spool valves, size 2 acc. to D 7700-2
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 23
5.2 In series intermediate plates
In series intermediate plates
ZPL 22 P6R6
24 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
5.3 Directional spool valve with actuation E, EI
Actuation type E Actuation type EI
1 Plug may be mounted offset by 180°
2 Ancillary blocks
1 Plug may be mounted offset by 180°
2 Ancillary blocks
Additional solenoid versions
Coding -AMP 12, -AMP 24 Coding -DT 12, -DT 24
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 25
6 Installation, operation and maintenance information
6.1 Designated use
This fluid-power product has been designed, manufactured and tested acc. to standards and regulations generally applicable in the
European Union and left the plant in a safe and fault-free condition.
To maintain this condition and ensure safe operation, operators must observe the information and warnings in this documentation.
This fluid-power product must be installed and integrated in a hydraulic system by a qualified staff who is familiar with and observes
the general engineering principles and relevant applicable regulations and standards.
In addition, application-specific features of the system or installation location must be taken into account if relevant.
This product may only be used within oil-hydraulic systems.
The product must be operated within the specified data. This documentation contains the technical parameters for various product
versions.
Note
Non-compliance will void any warranty claims made against HAWE Hydraulik.
6.2 Assembly information
The hydraulic accumulator must be integrated in the system via state of the art connection components (screw fittings, hoses, pipes,
etc.). The hydraulic system must be shut down as a precautionary measure prior to dismounting; this applies in particular to systems
with hydraulic accumulators.
26 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
6.3 Operating instructions
Product, pressure and/or flow settings
All statements in this documentation must be observed for all product, pressure and/or flow settings on or in the hydraulic system.
Caution
Risk of injury on overloading components due to incorrect pressure settings!
■ Always monitor the pressure gauge when setting or changing the pressure.
Filtering and purity of the hydraulic fluid
Soiling in the fine range, e.g. abraded material and dust, or in the macro range, e.g. chips, rubber particles from hoses and seals, can
cause significant malfunctions in a hydraulic system. It is also to be noted that new hydraulic fluid “from the drum” does not necessari-
ly meet the highest purity requirements.
For trouble-free operation pay attention to the purity of the hydraulic fluid (see also purity class in Chapter 4, "Parameters").
6.4 Maintenance information
This product is largely maintenance-free.
Conduct a visual inspection to check the hydraulic connections for damage at regular intervals, but at least once per year. If external
leaks are found, shut down and remedy.
Check the device surfaces for dust deposits at regular intervals (but at least annually) and clean the device if required.
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 27
6.5 Planning information
6.5.1 Notes for selection and lay-out
a) Connection block
■ Additional damping options for the connection blocks type PSL and PSV are described in the D 7700 ++ publications.
Caution
The load pressure must be at least 20 bar.
b) Control blocks
Coding 2 (example EDL 2-DA 2 L 25/16...)
■ The standard version of the load-compensated directional spool valve is fitted with an input controller (coding 2). Thanks to the
control pressure (approx. 6 bar ), the consumer volumetric flow is regulated depending on the spool valve elevation (spool valve
edges are designed as metering orifices) regardless of the system pressure and other consumers:
Coding 5 (example EDL 2-DA 2 H 40/40...)
■ If the control pressure is changed, the maximum possible volumetric flow of the individual consumer may be influenced (see
statements on codings 1 and 2 above). The control pressure is approx. 9 bar for coding 5. This results in a usable volumetric flow
that is approx. 1.3 times higher than for directional spool valve variants with coding 2 (standard).
Coding DAR 2 and DAR 5
■ In addition to its control function, the pressure compensator also acts as a check valve. This prevents a possible flow reversal in the
event of a shortage in supply on the pump side.
28 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
c) Use of control pumps
■ For load-sensing controls in combination with control pumps, the LS signal duct to the (load-sensing controller) of the pump is
limited to minimise circulation losses when in neutral position (i.e. when no hydraulic oil is dispensed to the consumer). This
limiting takes place via the proportional directional spool valves. Without this limiting the pump would have to work in the no-lift
position with its remaining delivery flow against the maximum pressure setting of the pressure controller. As there are directional
spool valves without this limiting possibility, some brands of (load-sensing controllers) have an internal bypass orifice from the LS
signal inlet to a decompressed leakage outlet. Thanks to the internal limiting of proportional directional spool valves of type EDL,
this bypass channel is not necessary and it can even cause malfunctions due to lost control oil. For functional reasons, the control
oil flow must be consciously limited (approx. 2 lpm) (creeping of the consumer).
Note
Care must therefore be taken to ensure that a possible bypass orifice in the pressure delivery flow controller is sealed.
d) Combination with load-holding valves
■ If three control elements, the 3-way controller in the pump or in the connection block, the 2-way controller in the directional valve
and load-holding valve insert are switched in series, oscillations may occur due to external variations of load and resonance effects.
These effects can be effectively suppressed by systematic use of a bypass orifice and throttle-, check-, pre-load valve combination
connected in parallel within the control oil circuit at the load-holding valve type LHDV acc. to D 7770. Similar behaviour can be
achieved using load-holding valves of type LHT acc. to D 7918.
e) Combination of more than 10 directional spool valves
■ By switching the load-sensing line in series, a total of max. 10 directional spool valves can be linked. If more than 10 directional
spool valves are required, these must be arranged in separate valve banks.
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 29
f) Additional components
For electro-hydraulic actuations
1. Male connector MSD 3-309 Standard, included in the delivery
SVS 296107 Male connector with LEDs for function deactivation acc. to
Chapter 3.2, " Add-on spool valves" Table (for more details see
D 7163)
2. Electric amplifier EV 22 K 2-12(24) acc. to D 7817/1
One board can control 2 directional valves
3. Electric amplifier EV 1 M3 acc. to D 7831/2
EV 1 D acc. to D 7831 D
A remote control potentiometer with direction switches is also required
(see detailed information in D 7831/2 Chapter 6.2)
4. Programmable logic valve control PLVC acc. to D 7845 ff
5. Electric joystick EJ 1, EJ 2 or EJ 3 acc. to D 7844
6. Radio controls are accepted if they fulfil the requirements acc. to Sk 7814
(Approved brands: Co. HBC-ELEKTRONIK in D-74564 Crailsheim, Germany; Co. HETRONIK Steuer-Systeme in D-84085 Langquaid, Germany; Co.
NBB-Nachrichtentechnik in D-75248 Ölbronn-Dürrn, Germany; Co. SCANRECO Industrieelektronik AB, Box 19144, S-5227 Södertälje, Sweden)
Load-holding valves
■ Load-holding valves type LHT in accordance with D 7918 or type LHDV in accordance with D 7770 corresponding to note Chapter 6.5,
"Planning information" ("Combination with load-holding valves"), type LHK in accordance with D 7100 only for particularly “stiff”
complete systems and for directional spool valves without input controller (coding 1 in accordance with Table , Chapter 3.2.1,
"Directional spool valve")
Other valves
■ Proportional directional spool valve type PSL(V) size 2 acc. to D 7700-2 (combinable without intermediate plate with EDL 2)
■ Proportional directional spool valve type PSL(V) size 3 acc. to D 7700-3 (combinable via intermediate plate ZPL 32 with EDL 2)
■ Proportional directional spool valve type PSL(V) size 5 acc. to D 7700-5 (combinable via intermediate plate ZPL with EDL 2)
■ Proportional directional spool valve type PSL(V)F size 3 acc. to D 7700-3F (directional spool in flange design)
■ Proportional directional spool valve type PSL(V)F size 5 acc. to D 7700-5F (directional spool in flange design)
■ Connection blocks type HMPL and HMPV acc. to D 7700 H
30 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
6.5.2 Circuit examples
Order coding example 1: PSL control for hydraulic oil supply via constant pump
PSL 3U/250 - 2 - DA 2
- DA 2
- DA 2
- DA 2
L
L
H
H
40/25
25/16
16/16
40/40
/E/2 AN 200 BN 200
/E/2 AN 250 BN 250
/E/2
/E/2 E0-G24
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 31
Order coding example 2: PSV control for hydraulic oil supply via control pump
PSV 551/300 - 3 - 3 2
- ZPL 32
- A 2
- DA 2
- DA 2
O
J
L
L
80/80
40/25
25/16
25/16
C200
A200 B150
/EI
/EI/2
/EI/2
/EI/2 E1-AMP 24 K4
32 03-2015-1.2 - D 8086 - EDL www.hawe.de | 2015
Order coding example 3: PSV control for hydraulic oil supply via control pump
PSV E0 - 2 - DA 2
- DA 2
- ZPL 22 P6R6/250
- DA 2
- DA 2
H
H
L
L
50/50
25/25
16/10
6/3
/EI/2 AS 180 BS 100
/EI/2 AS 200 BS 200
/EI/2
/EI/2 E0-AMP 24
www.hawe.de | 2015 03-2015-1.2 - D 8086 - EDL 33
7 Other information
7.1 Note regarding assembly, installation and conversion
All installation, set-up, maintenance and repairs must be performed by authorised, qualified and trained staff. The use of this product
beyond the specified performance limits, operation with non-specified fluids and/or use of non-genuine spares will invalidate the
warranty.
7.1.1 Mounting
The valve bank must be mounted to the frame or base of the machine in such a way that no stress is induced. Three screws and elastic
washers between the bank and the frame are recommended for mounting.
7.1.2 Piping
All fittings used must utilise deformable seals. The recommended torque values must not be exceeded.
7.1.3 Sealing kits
Connection block DS 7700-21
Valve section DS 7700-22
ZPL 32 DS 7700-22Intermediate plate
ZPL 52 DS 7700-52
D 8
086 -
EDL_
03-2
015-1
.2
HAWE Hydraulik SE
Streitfeldstraße 25 | 81673 München | Postfach 80 08 04 | 81608 München | Germany
Tel +49 89 379100-1000 | Fax +49 89 379100-9100 | [email protected] | www.hawe.com
Additional versions
■ Proportional directional spool valve, type PSL and PSV size 2: D 7700-2
■ Proportional directional spool valve, type PSL, PSM and PSV size 3: D 7700-3
■ Proportional directional spool valve, type PSL, PSM and PSV size 5: D 7700-5
■ Proportional directional spool valve type PSLF, PSVF and SLF size 3: D 7700-3F
■ Proportional directional spool valve type PSLF, PSVF and SLF size 5: D 7700-5F
■ Proportional directional spool valve banks, type PSLF, PSVF and SLF size 7: D 7700-7F
■ Directional spool valve bank type SWS: D 7951