series 14r installation instructions and field service checklist · 2016. 5. 4. · optional: etd-1...
TRANSCRIPT
1© 2013 Maxitrol Company, All Rights Reserved
DESCRIPTION
Selectra Series 14R electronic gas flame modulation systems are designed primarily for make-up air heating, as components of direct fired equipment. They may be field installed on existing equipment or specified for new equipment installation.
The system uses Modulator or Modulator-Regulator valves, amplifiers which include low-fire start, and integral or remote temperature selection and a discharge air temperature sensor that is mounted within a mixing tube.
SYSTEM COMPONENTS
A1014R AmplifierA1014R (all remote temperature ranges)
Included Integral Ranges:40º to 80ºF 55º to 90ºF
90º to 140ºF110º to 160ºF 160º to 210ºF
Remote Temperature SelectorsTD114...................55° to 90°F w/override
0° to 40°F over set pointTD114A................................ 80° to 130°FTD114A-1...........80° to 130°F w/override
0° to 40°F over set pointTD114B................................120 to 170°FTD114C..............................160° to 210°FTD114D..............................200° to 250°FTD114E..............................100° to 250°FTD114F..............40° to 80°F w/override
0° to 40°F over set point TD114G...............................90° to 140°FTD114-1........55° to 90°F w/120° to 170°F override, use w/TS114TD114-2...........55° to 90°F w/two outputsTD114G-2........90° to 140°F w/two outputs
Remote Temperature Selectors Continued
IMPORTANT: The A1014R integral or remote temperature selector’s (TD114) temperature range must match the temperature sensor’s (TS114) temperature range. See page 7 for available integral dial ranges.
Optional: ETD-1 enclosure, EFP-1 cover plate only - no enclosure
Discharge Air Temperature Sensors: use with Mixing Tube
TS114..........................................................................55° to 90°FTS114A.....................................................................80° to 130° FTS114B....................................................................120° to 170° FTS114C....................................................................160° to 210° FTS114D..................................................................200° to 250° FTS114E..................................................................100° to 250° FTS114F.....................................................................40° to 80° FTS114G....................................................................90° to 140° FTS114J.................................110° to 160° F, use w/ AD1014-1116, TS214__...........................dual sensor - any combination of 2 standard ranges available
Example 1 - TS214G....................55° to 90° F and 90° to 140° F, use w/TD114 & TD114G, or TD214G (selector w/switch).
Example 2 - TS214AD..................80° to 130° F and 200° to 250° F, use w/TD114A & TD114D, or TD214AD (selector w/ switch).
Mixing Tubes: (and sensor)
Lengths:MT1-9 or 2-9............................9” MT1-12 or 2-12......................12” MT1-23 or 2-23......................23” MT1-28 or 2-28......................28” MT1-57...................................57”
Valves
Pipe Sizes:M411........................... 3/8” & 1/2”M511...........................1/2” & 3/4”M611 ............................3/4” & 1”MR212D...................1”, 1¼”, 1½”MR212E.........................1½” & 2”MR212G....................... 2½” & 3”MR212J.......................4” flanged
2 Speed Blower or Dual Fuel Operation:MR212D-2................1”, 1¼”, 1½”MR212E-2.....................1½” & 2”MR212G-2.....................2½” & 3”MR212J-2....................4” flangedNOTE: M (Modulator) valve requires an
upstream pressure regulator for low fire & high fire settings. MR (Modulator/Regulator) valve requires no upstream pressure regulator up to 5 psi inlet.
TABLE OF CONTENTSSystem Components....................................................................1Dimensions..................................................................................2Specifications................................................................................3Installation of Components............................................................3Wiring Diagrams............................................................................4Settings..........................................................................4-5Valve Adjustments.........................................................................5 Field Service Checklist.................................................................6Preliminary Circuit Analysis.........................................................7Label Instructions..........................................................................7
Read these instructions carefully and completely before installing or operating. Failure to follow them could result in a fire or explosion causing property damage, personal injury, or loss of life. The product must be installed and operated according to all local regulations.
Service and installation must be performed by a trained/experienced service technician.
Series 14R Installation Instructions and Field Service Checklist
2© 2013 Maxitrol Company, All Rights Reserved
2.96(75)
4.13 (105)
2.62(67)
4.51 (115)
2.25(57)
1.34
(34)
0.5(13)
1.03 (26)
MOUNTING HOLE4-PLACES
3 (76)REF.
4.19(106)
2.5 (63)REF.
1.25 (32)
1.5 (38)
MOUNTING HOLE4-PLACES
4.19(106)
4.19(106)
3 (76) REF.
1.88
(48)
#10-12 X 1/2” LG.BINDING HD. SHEET
METAL SCREWS (2-REQ’D.)
#10-16 X 1/2” LG.BINDING HD. SHEET METAL SCREW (2-REQ’D.)
1 (25) DIA.
LENGTH SEE PAGE 1)
1.56(40)
DIMENSIONS
OPTIONAL SYSTEM COMPONENTS
Dual Temperature SelectorTD214_ or _X*, or AD1214_,TD114HD (use w/TS114): door closed 55° to 90°F; open 90° to 140°F, TD214__: dual selector w/switch (any combination of 2 standard ranges available): Provides dual control for door heaters, or other applications such as paint spray booths.Example 1: TD214G: 55°-90°F (spray) and 90°-140°F (dry), use with TS214G. Example 2: TD214AD: 80°-130°F and 200°-250°F, use with TS214AD. *NOTE: In model numbers TD214__X , “X” denotes no enclosure.
Inlet Air Temperature Sensors: use with Mixing TubeTS10765A (8:1 ratio), TS10765B (5:1 ratio), TS10765C (3.5:1 ratio):Provides inverse change in discharge air for each degree change in inlet air - when installed in a convenient duct location upstream of the burner.
Room Override Thermostat
T115 (40° to 90° F): Provides space temperature control by raising the discharge air temperature to a pre-selected point when used in conjunction with the remote temperature selectors TD114, TD114F, TD114-1, or TD114A-1.
Figure 1: A1014R (front and side)
Figure 2: ETD-1
Figure 3: Mixing Tubes
Figure 4: T114 Figure 5: TD114
© 2
013
Max
itrol
© 2
013
Max
itrol
© 2
013
Max
itrol
© 2
013
Max
itrol
© 2
013
Max
itrol
1.5 (38)
4.19 (106)
1.25
(32)
2.5 (63)REF.
4.69
(119)
1.69
(43)1.41 (36)
2.56 (65)
3.46 (88)3.25 (83) 3
(76)1.5
(38)
0.19
(4.8)
2.25 (57)
2.62 (67)
2.62
(67)
1.75(44)
inches (millimeters)
inches (millimeters)
inches (millimeters)
inches (millimeters) inches (millimeters)
3© 2013 Maxitrol Company, All Rights Reserved
SPECIFICATIONS Power Requirements24 VAC, 50/60 Hz Class II transformer
GasesSuitable for natural, manufactured, mixed gases, liquefied petroleum gases, and LP gas-air mixtures.
Ambient LimitsOperating.............................................-40o to 125o F (-40o to 52o C) Non-operating......................................-50o to 185o F (-46o to 85o C)
Vent M411, 511, 611: vertical vent outlet 1/8” NPT - 12A06 installed. MR212: two vents located in upper housing, both equipped with vent limiting means
Pressure Limits Maximum Discharge PressureM411, 511, 611.......................................................7” w.c. (1.7 kPa)
Static Pressure Rating M411, 511, 611......................................................5.0 psi (34.5 kPa)
Maximum Operating Inlet PressureM411, 511, 611........................................................1.0 psi (7.0 kPa) MR212..................................................................5.0 psi (34.5 kPa)
Maximum Emergency Exposure*M411, 511, 611....................................................3.0 psi (21.0 kPa) MR212...............................................................12.5 psi (86.2 kPa) * May not function properly at this pressure, but will suffer no internal damage
INSTALLATION OF COMPONENTS
Amplifier / Amplifier-Selector: Contains the wiring terminals and sensitivity adjustment - install in any convenient location that is protected from the weather and contaminated atmosphere.
Remote (or Dual) Selector: Install in control cabinet or other chosen location. NOTE: Suffix letters must match, e.g. TS114A must be used with TD114A. For wiring runs longer than 200 ft. substitute ES261-1/ES261-2 for TD114. The ES261s are a 2-piece version of the TD114. ES261-1 is a temperature setting dial only, ES261-2 must be mounted at furnace location.
Discharge Temperature Sensor / Mixing Tube Assembly: Sensor housed in mixing tube, install in discharge air stream.
Dual Temp. Selector (optional): See preceding Remote/Dual Selector.
Room Override Stat (optional): Mount in heated area not in direct path of discharge air stream.
Inlet Air Sensor (optional): Install in convenient location upstream of burner, in intake air duct.
GAS TRAINS Modulator (M) or Modulator-Regulator (MR) ValveMount in upright position in horizontal run of pipe, downstream of other controls. A separate gas pressure regulator must be used with any modulator (M) valve.
AUTOMATIC SAFETY SHUT-OFF VALVE
AUTOMATIC SAFETY SHUT-OFF VALVE
NOTICE
Wiring Run: Control wires connected to the Override Stat, Discharge Air Sensor, or Remote Temperature Selector must not be run close to or inside conduit with power or ignition wires. Doing so may cause the unit to function erratically or may destroy the amplifier. If shielded wires are used, shield must be insulated and grounded at the amplifier location only. If control wiring is inside conduit with line voltage wiring, use shielded cable up to 100 ft. For best results up to 200 ft., run control wiring in separate conduit. For longer runs see Remote Selector below.
NOTICE
Transformer secondary must not be grounded in any portion of the circuit external to a Maxitrol amplifier. If existing transformer is grounded, a separate, independent transformer must be used. Electrical interference may affect performance and/or damage equipment.
Figure 6: MR Valve - Modulator-regulator valve
Figure 7: M Valve - Regulator upstream of modulator valve
© 2
013
Max
itrol
© 2
013
Max
itrol
WIRING DIAGRAMS
SETTINGS
Sensitivity Adjustment
The sensitivity control will allow the user to control the response of the system. Caution should be exercised in the use of this adjustment. Under normal usage the pointer should be in line with the mark on the label.
If hunting (oscillation) is encountered, rotating the sensitivity adjustment counter-clockwise will dampen the oscillation - stabilizing the flame (see Figure 11).
DO NOT adjust unless necessary. Decreasing the sensitivity can increase the temperature “DROOP” of the system.
Integeral or Remote Temperature Dial Selection (TDS): The desired discharge temperature can be selected using the amplifiers integral temperature dial or connecting a TD114 Remote Temperature Selector to terminals 1 & 2.
Set dipswitch #1 to the desired temperature setting selection mode (see Figure 12, page 5). Placing dipswitch #1 in the “UP” position enables the integral dial. Placing dipswitch #1 in the “DOWN” position enables the remote dial. The amplifier will only respond to the dipswitch’s selected temperature setting method, integral or remote.
IMPORTANT: The A1014R integral or remote temperature selector’s (TD114) temperature range must match the temperature sensor’s (TS114) temperature range. See page 7 for available integral dial ranges.
Sensitivity Adjustment
Integral Discharge Temperature Dial
Power Indicator
© 2013 Maxitrol Company, All Rights Reserved 4
TDS Dipswitch LFS Dipswitch
TRANSFORMER
TS114& MIXING TUBE
T115 OVERRIDE
TD114 SELECTOR
VALVE
TD114 SELECTOR(OPTIONAL)
TS114& MIXING TUBE
TS10765 & MIXING
TUBE
VALVE
TRANSFORMER
TS114& MIXING TUBETD114
SELECTOR(OPTIONAL)
VALVE
Figure 8: A1014R Figure 9: A1014R W/ Room Override Figure 10: A1014R W/ Inlet Air Sensor
Figure 11: A1014R Model Amplifier
Enlarged View, see Figure 12, page 5
© 2013 Maxitrol© 2013 Maxitrol© 2013 Maxitrol
© 2013 Maxitrol
1 1 1 1 1 12 2 2 2 2 23 3 3 3 3 3
© 2013 Maxitrol Company, All Rights Reserved 5
Low Fire Start (LFS) Time Adjustment
The low fire start duration can be set to 0 or approximately 10 seconds and begins timing after the amplifier has been energized.
The time is set by placing DIP Switch #2 to the appropriate position. LFS: Up = 10 Seconds, Down = 0 Seconds.
The M/MR valve remains in the low fire setting position during the low fire start time period.
B
A
1
2
MODULATOR
A B
D
C
VALVE ADJUSTMENTS
See bulletin MMR_MT_EN for additional M/MR valve information
NOTE: Low fire adjustment should be checked whenever the high fire adjustment is changed.
MR 212 VALVERefer to Figure 13 for the following procedures.High Fire Manifold Adjustments:
1. Disconnect wires from amplifier terminal 4 (see Figure 11, page 4). This causes the valve to call for continuous high fire.
2. Remove seal cap (A), and turn regulator pressure adjusting screw to obtain desired manifold pressure. (Clockwise rotation increases pressure.)
3. Reconnect the wires to amplifier terminal 4.
NOTE: If low fire bypass is on maximum, the desired high fire outlet pressure may not be achieved.
Low Fire or Bypass Adjustments
1. Disconnect wire from amplifier terminal 8 (see Figure 11, page 4). This causes the valve to call for continuous low fire.
2. Remove cap (B), and loosen lock screw (C). Turn (D) to desired low fire adjustment. (Clockwise rotation reduces minimum flow rate.)
3. Tighten set screw (C), replace cap (B) and reconnect wire to amplifier terminal 8.
M411, 511, 611 VALVERefer to Figure 14 for the following procedures.High Fire Manifold Adjustments: 1. Disconnect wires from amplifier terminal 4 (see Figure 11,
page 4). This causes the valve to call for continuous high fire.2. Adjust the pressure regulator to obtain the desired manifold
pressure (7” w.c. maximum).3. Reconnect the wires to amplifier terminal 4.
Low Fire or Bypass Adjustments:1. Disconnect wire from amplifier terminal 8, this causes the valve
to call for continuous low fire.2. Remove cap (A), and turn adjusting screw (B) to desired low fire
adjustment. (Clockwise rotation reduces minimum flow rate.)3. Replace cap (A), and reconnect wire to amplifier terminal 8.
Figure 13: MR212 Valve Adjustments
Figure 14: M411, 511, 611 Valve Adjustments
UP DOWN
TDS Dipswitch LFS Dipswitch
Figure 12: A1014R Englarged View: DIP Switch Setting
© 2
013
Max
itrol
© 2013 Maxitrol
© 2013 Maxitrol
FIE
LD S
ERVI
CE
CH
ECK
LIST
© 2013 Maxitrol Company, All Rights Reserved 6
SYM
PTO
MPO
SSIB
LE C
AU
SEFI
ELD
TES
TR
EMED
YA
.N
o ga
s flo
w.
1. M
odul
atin
g va
lve
impr
oper
ly in
stal
led.
1. A
rrow
on
side
of v
alve
sho
uld
poin
t in
dire
ctio
n of
gas
flow
.1.
Inst
all p
rope
rly.
B.
Con
tinuo
us L
ow F
ire
(ele
ctro
nics
pro
blem
).2.
Sho
rt ci
rcui
t or n
o vo
ltage
to th
e am
plifi
er.
3. O
pen
circ
uit i
n TD
114
Rem
ote
Tem
pera
ture
S
elec
tor c
ircui
t or w
iring
.
4. S
hort
circ
uit i
n TS
114,
Dis
char
ge A
ir S
enso
r ci
rcui
t or
wiri
ng.
5. A
mpl
ifier
is n
ot o
pera
ting
prop
erly.
6. In
corr
ectly
set
to e
xter
nal d
ial.
2. C
heck
for
pow
er li
ght
or 2
4VA
C a
t am
plifi
er t
erm
inal
s 7
and
8.3.
Ins
pect
for
loo
se o
r br
oken
wire
s be
twee
n am
plifi
er
term
inal
s 1
and
2, a
nd T
D11
4 te
rmin
als
1 an
d 2,
and
TD
114
term
inal
s 1
and
3.4.
Con
nect
test
res
isto
r as
des
crib
ed in
“P
relim
inar
y C
ircui
t A
naly
sis”
, pag
e 7.
Fol
low
pro
cedu
re o
utlin
ed.
5. C
heck
“Fie
ld T
est”
2, 3
and
4.
6. V
isua
lly e
xam
ine
dial
pos
ition
.
2. P
rove
the
pow
er s
ourc
e.
3. T
ight
en c
onne
ctio
ns o
r rep
lace
wiri
ng.
4. I
f m
odul
atin
g vo
ltage
s ar
e ob
tain
ed,
Che
ck T
S11
4 ci
rcui
t fo
r sh
orts
. R
epla
ce
TS11
4 if
nece
ssar
y.5.
If “F
ield
Tes
t” 2,
3, a
nd 4
che
ck o
ut a
nd m
odul
atin
g vo
ltage
s ar
e st
ill n
ot o
btai
ned,
am
plifi
er m
ay b
e as
sum
ed fa
ulty
. Rep
lace
.6.
Set
Dip
switc
h #1
to In
tegr
al.
C.
Con
tinuo
us L
ow F
ire
(val
ve p
robl
em).
7. S
hort
circ
uit o
r ope
n ci
rcui
t in
mod
ulat
or c
oil.
8. P
lung
er m
issi
ng, j
amm
ed, o
r im
prop
erly
inst
alle
d.
7. M
easu
re r
esis
tanc
e ac
ross
mod
ulat
or t
erm
inal
s w
ith
conn
ectin
g w
ires
deta
ched
.8.
Insp
ect.
Plu
nger
sho
uld
be s
moo
th,
clea
n, a
nd o
pera
te
freel
y in
sol
enoi
d sl
eeve
, see
Fig
ure
7, p
age
3. In
stal
l with
al
umin
um ti
p do
wn.
7. R
epla
ce m
odul
ator
hea
d if
not
appr
oxim
atel
y 45
-55
ohm
s fo
r M
611
Valv
e an
d 60
-80
ohm
s fo
r MR
212
Valv
e.8.
Cle
an, o
r if n
eces
sary
, rep
lace
plu
nger
.
D.
Cor
rect
Low
Fire
Err
atic
or
Puls
atin
g Fl
ame.
9.
Inco
rrec
t by-
pass
met
erin
g va
lve
adju
stm
ent.
10. E
xces
sive
neg
ativ
e bu
rner
pre
ssur
e.
9.
See
“Val
ve A
djus
tmen
ts”,
page
5.
10. C
lose
mai
n ga
s su
pply
and
mea
sure
man
ifold
pre
ssur
e
with
blo
wer
ope
ratin
g. R
eadi
ng s
houl
d be
less
than
1.
5” w
.c. n
egat
ive
pres
sure
.
9.
Adj
ust t
o pr
oper
low
fire
.10
. If r
eadi
ng is
gre
ater
than
1.5
” neg
ativ
e pr
essu
re, c
heck
for c
logg
ed fi
lters
or
othe
r inl
et a
ir re
stric
tions
. Con
sult
Max
itrol
Tec
hnic
al S
uppo
rt fo
r oth
er
solu
tions
.
F.C
ontin
uous
Hig
h Fi
re
(ele
ctro
nics
pro
blem
).11
. S
hort
circ
uit
in T
D11
4 R
emot
e Te
mpe
ratu
re S
elec
tor
circ
uit o
r wiri
ng.
12. O
pen
circ
uit i
n TS
114/
TS10
765.
Dis
char
ge o
r Inl
et A
ir S
enso
r Circ
uit o
r wiri
ng.
11. I
nspe
ct fo
r sho
rts a
t or b
etw
een
ampl
ifier
term
inal
s 1
and
2 or
TD
114
term
inal
s 1
and
3.
12. C
heck
TS
114/
TS10
765
for o
pen
inte
rnal
circ
uit.
Con
nect
te
st re
sist
or a
s de
scrib
ed in
“Pre
limin
ary
Circ
uit A
naly
sis”
, pa
ge 7
. Fol
low
pro
cedu
re o
utlin
ed.
11. C
orre
ct w
iring
if s
horts
exi
st.
12.
If m
odul
atin
g vo
ltage
s ar
e ob
tain
ed,
chec
k TS
114/
TS10
765
for
open
circ
uits
. R
epla
ce T
S11
4/TS
1076
5.
GC
ontin
uous
Hig
h Fi
re
(val
ve p
robl
em).
13.
Fore
ign
obje
ct h
oldi
ng v
alve
ope
n.14
. P
lung
er ja
mm
ed.
13. R
emov
e bo
ttom
pla
te a
nd in
spec
t val
ve a
nd s
eat.
14. I
nspe
ct. P
lung
er s
houl
d be
sm
ooth
, cle
an, a
nd o
pera
te
freel
y in
sol
enoi
d sl
eeve
, see
Fig
ure
7, p
age
3. In
stal
l with
al
umin
um ti
p do
wn.
13. C
lean
sea
t. C
lean
val
ve o
r rep
lace
if n
eces
sary
.14
. Cle
an, o
r if n
eces
sary
, rep
lace
plu
nger
.
H.
Inco
rrec
t Hig
h Fi
re.
15. I
nlet
pre
ssur
e to
o lo
w.
16.
Inco
rrec
t ou
tlet
pres
sure
adj
ustm
ent
of p
ress
ure
regu
lato
r.
15. R
ead
pres
sure
at
inle
t to
mod
ulat
ing
valv
e us
ing
a m
anom
eter
with
uni
t op
erat
ing
at h
igh
fire.
Pre
ssur
e sh
ould
be
equa
l to
the
sum
of o
utle
t pre
ssur
e se
tting
plu
s pr
essu
re d
rop
of th
e va
lve
(see
Max
itrol
Cap
acity
Cha
rt).
16. R
ead
man
ifold
pre
ssur
e us
ing
man
omet
er a
nd c
ompa
re
with
reco
mm
enda
tion
of e
quip
men
t man
ufac
ture
r.
15. I
ncre
ase
inle
t pre
ssur
e if
poss
ible
.
16. S
ee “V
alve
Adj
ustm
ents
”, pa
ge 5
.
E.
Erra
tic o
r Pul
satin
g Fl
ame
17.
Hun
ting.
18.
Err
atic
air
patte
rns
or im
prop
er T
S11
4 lo
catio
n.
19.
Wiri
ng is
run
nex
t to
hig
h vo
ltage
sw
itchi
ng c
ircui
ts
caus
ing
indu
ced
volta
ges.
20. A
mpl
ifier
not
ope
ratin
g pr
oper
ly o
r erra
tic v
olta
ge s
uppl
y.
17.
Adj
ust s
ensi
tivity
con
trol c
ount
er-c
lock
wis
e.18
. Con
nect
test
resi
stor
as
desc
ribed
in “P
relim
inar
y C
ircui
t An
alys
is”,
page
7. T
urn
TD11
4 se
lect
or d
ial s
o he
ater
goe
s th
roug
h its
ent
ire m
odul
atin
g ra
nge.
19. T
empo
raril
y w
ire e
ach
of T
D11
4, T
S11
4, a
nd M
R21
2 ex
tern
ally
and
obs
erve
hea
ter/e
quip
men
t ope
ratio
n.20
. W
ith t
est
resi
stor
con
nect
ed (
per
“Fie
ld T
est”
18)
and
TD11
4 lo
cally
con
nect
ed (p
er “F
ield
Tes
t” 19
), tu
rn T
D11
4 se
lect
or d
ial t
hrou
gh e
ntire
mod
ulat
ing
rang
e. O
bser
ve
DC
vol
tage
acr
oss
mod
ulat
or te
rmin
als.
17. A
djus
t sen
sitiv
ity c
ontro
l to
mai
ntai
n an
eve
n fla
me.
18. I
f the
flam
e is
ste
ady
thro
ugho
ut th
e en
tire
mod
ulat
ing
rang
e, th
e TS
114
mus
t be
mov
ed.
19. I
f sm
ooth
ope
ratio
n re
sults
, iso
late
affe
cted
wiri
ng fr
om s
ourc
e of
indu
ced
volta
ge.
20. I
f err
atic
or u
nsta
ble
DC
vol
tage
s ar
e ob
tain
ed th
roug
hout
the
mod
ulat
ing
rang
e,
the
ampl
ifier
may
be
assu
med
faul
ty. R
epla
ce. I
f err
atic
ope
ratio
n is
not
ed o
nly
over
a s
mal
l ran
ge o
f 2 o
r 3 v
olts
, the
vol
tage
sou
rce
may
con
tain
sur
ges.
Con
sult
Max
itrol
Tec
hnic
al S
uppo
rt.
I.In
corr
ect D
isch
arge
Air
Tem
pera
ture
.21
. Inl
et A
ir S
enso
r is
used
.
22. I
ncor
rect
Wiri
ng.
23. S
yste
m o
ut o
f cal
ibra
tion.
24. I
mpr
oper
TS
114
loca
tion.
25. R
oom
Ove
rrid
e Th
erm
osta
t circ
uit c
lose
d.
21. I
nlet
Air
Sen
sor c
hang
es 1
° for e
ach
3.5°
, 5°,
or 8
° out
side
te
mpe
ratu
re c
hang
e fro
m 6
0° (p
rede
term
ined
– tu
rndo
wn
varie
s w
ith m
odel
use
d).
22. C
heck
“Wiri
ng D
iagr
ams”
, pag
e 4.
23. S
ense
d te
mpe
ratu
re (t
herm
omet
er n
ext t
o TS
114)
doe
s no
t cor
resp
ond
to T
D11
4 se
tting
.24
. Sen
sed
tem
pera
ture
(the
rmom
eter
nex
t to
TS11
4) d
oes
not r
epre
sent
ave
rage
dis
char
ge a
ir te
mpe
ratu
re.
25.
Rem
ove
Ove
rrid
e Th
erm
osta
t le
ad f
rom
ter
min
al 2
of
TD11
4.
21. S
ense
d te
mpe
ratu
re w
ill v
ary
from
TD
114
dial
set
tings
. Thi
s is
inte
ntio
nal.
22. C
orre
ct w
iring
as
show
n in
“Wiri
ng D
iagr
ams”
, pag
e 4.
23. C
onsu
lt M
axitr
ol T
echn
ical
Sup
port.
24. M
ove
TS11
4 to
loca
tion
whe
re a
vera
ge re
pres
enta
tive
tem
pera
ture
can
be
sens
ed.
25. T
D11
4 di
al s
ettin
g, th
en c
heck
ther
mos
tat s
ettin
g an
d/or
che
ck w
iring
for s
horts
.
J.B
urne
d ou
t Tra
nsfo
rmer
.26
. Sho
rt ci
rcui
t in
mod
ulat
or c
oil.
27. S
hort
circ
uit b
etw
een
ampl
ifier
and
mod
ulat
or v
alve
.
26. M
easu
re re
sist
ance
acr
oss
mod
ulat
or te
rmin
als
with
red
lead
wire
s di
scon
nect
ed.
27. I
nspe
ct w
iring
.
26. R
epla
ce m
odul
ator
hea
d if
less
than
40
ohm
s.
27. C
orre
ct w
iring
if s
hort
is fo
und.
K.
Dis
char
ge A
ir Te
mpe
ratu
re
too
Low
whe
n T1
15 is
O
pera
tive.
28. T
oo lo
w a
n ov
errid
e te
mpe
ratu
re s
ettin
g.29
. Bur
ner c
apac
ity m
ay b
e in
suffi
cien
t.28
. Che
ck “O
verr
ide
Tem
pera
ture
Sel
ecto
r” o
f TD
114.
29
. Che
ck fo
r hig
h fir
e (m
axim
um m
anifo
ld p
ress
ure
spec
ified
fo
r hea
ter)
.
28. R
eset
to c
orre
ct te
mpe
ratu
re.
29. I
f on
high
fire
, con
trol c
an d
o no
mor
e. H
eate
r una
ble
to fu
rnis
h ad
ditio
nal h
eat
to ra
ise
tem
pera
ture
.
© 2013 Maxitrol Company, All Rights Reserved 7
PRELIMINARY CIRCUIT ANALYSIS
For ease in troubleshooting, it is advisable to wire the system as follows (this differs from the normal connection). Disconnect the Discharge Air Sensor and replace it with a 10,000 ohm, 1/2 watt test resistor (terminals 3 and 4). If inlet air sensor is being used, disconnect and replace with a jumper. On units where the Remote Temperature Selector is located a considerable distance from the heater, it may be advantageous to use the selector at the heater location or use the integral selector.
Connect a DC volt meter (capable of reading 0-24 VDC) on the Modulator or Modulator-Regulator Valve terminals. Set the temperature to the minimum dial setting. The DC voltage should read 0 volts. The DC voltage should gradually increase to at least 20 volts as you slowly rotate the dial to the maximum dial setting. If these voltages are obtained, the valve function can now be checked out.
The operation of the valve with regard to voltage is as follows: from 0 volts to approximately 5 volts, the modulating valve should be on bypass flow with the heater operating on low or minimum fire. From approximately 5 volts to 15 volts DC, the valve should be performing its modulating function, and the heater should be firing at a modulated flow rate between low and high fire, depending upon the voltage. Above approximately 15 volts DC, the valve should be delivering full flow to the heater and the unit should be on full fire. If the DC voltage is obtained on the valve terminals, but the heater does not respond as described, the problem can be isolated to the valve itself or to the gas control manifold of the heater (see “Field Service Checklist”, page 6).
In the event proper voltages are obtained, and the valve responds correctly to these DC voltages, the problem could well be in the wiring leading to the Discharge Air Sensor or the Discharge Air Sensor itself. This should be also reviewed in the Field Service Checklist.
If the proper voltages are not obtained when wired as instructed, the problem can be isolated to the electronics and this may once again be reviewed in the Field Service Checklist.
After the troubleshooting test, remove the test resistor and reconnect the Discharge Air Sensor to terminals 3 and 4. If Remote Temperature Selector has been moved or disconnected return it to its original position.
INTEGRAL TEMPERATURE DIAL LABEL
IMPORTANT: Temperature range on dial must match sensor temperature range.
The A1014R comes with the 40ºF - 80ºF label factory installed.
Following labels are shipped loose with the amplifier and can be field installed:
Label Range Matching Sensor40º-80ºF TS114F55º-90ºF TS114
90º-140ºF TS114G110º-160ºF TS114J160º-210ºF TS114C
* Label factory installed.
Installation Instructions• Locate desired label (to match sensor)• DO NOT remove existing dial label.• Make sure label surface is clean and dry.• Remove adhesive backing from desired label.• Carefully place label on top of range being replaced, lining up with the locating mark. • Set desired temperature by using adjustment pointer to point
to desired temperature.
*
Maxitrol Company23555 Telegraph Rd., PO Box 2230Southfield, MI 48037-2230
SEL14R_MI_EN_09.2013
www.maxitrol.com© 2013 Maxitrol Company
All Rights Reserved
8