see sheet 3 for minimum clearance requirements

3
SWN 1.0 SUBMITTAL SHEET SIZE D SHEET 1 OF 3 PD-000000086 B 6-FAN PROTOAIRE WITH PULL OFF PANELS DOC REV THIRD ANGLE PROJECTION DIMENSIONS ARE IN INCHES. DATE DRAWN: 2017/09/14 R INFORMATION SUBJECT TO CHANGE NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 187.0 L X 53.0 W X 57.5 H SEE SHEET 3 FOR MINIMUM CLEARANCE REQUIREMENTS 185.0 187.0 39.5 56.5 57.5 MAXIMUM TOTAL UNIT WEIGHT (POUNDS) SHIPPING OPERATING 145 POUND RECEIVER 3487 3737 OPTIONAL 200 POUND RECEIVER 3510 3780 RECEIVER SIZES SHOWN ARE BASED UPON 80% CAPACITY AIR DISCHARGE AIR INTAKE PULL-OFF ACCESS PANELS (3 SIDES) WEIGHT OF EACH ACCESS PANEL IS APPROX. 20 lbs. 9.0 MAX PIPING EXTENSION 53.0

Upload: others

Post on 28-May-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SEE SHEET 3 FOR MINIMUM CLEARANCE REQUIREMENTS

SW

N 1

.0 S

UBM

ITTAL

SHEE

T S

IZE

D

SHEET 1 OF 3 PD-000000086 B

6-FAN PROTOAIREWITH PULL OFFPANELSDOC REV

THIRD ANGLE

PROJECTION

DIMENSIONS ARE IN INCHES.DATE DRAWN: 2017/09/14

R

INFORMATION SUBJECT TO CHANGE

NOTES:1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS.2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION.3. OVERALL DIMENSIONS: 187.0 L X 53.0 W X 57.5 H

SEE SHEET 3 FOR MINIMUM CLEARANCE REQUIREMENTS

185.0

187.0

39.5

56.5 57.5

MAXIMUM TOTAL UNIT WEIGHT (POUNDS) SHIPPING OPERATING

145 POUND RECEIVER 3487 3737

OPTIONAL 200 POUND RECEIVER 3510 3780

RECEIVER SIZES SHOWN ARE BASED UPON 80% CAPACITY

AIR DISCHARGE

AIR INTAKE

PULL-OFF ACCESSPANELS (3 SIDES)WEIGHT OF EACH ACCESSPANEL IS APPROX. 20 lbs.

9.0 MAX

PIPING EXTENSION

53.0

Page 2: SEE SHEET 3 FOR MINIMUM CLEARANCE REQUIREMENTS

SW

N 1

.0 S

UBM

ITTAL

SHEE

T S

IZE

D

SHEET 2 OF 3 PD-000000086 B

6-FAN PROTOAIREWITH PULL OFFPANELSDOC REV

THIRD ANGLE

PROJECTION

DIMENSIONS ARE IN INCHES.DATE DRAWN: 2017/09/14

R

INFORMATION SUBJECT TO CHANGE

NOTES:1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS.2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION.3. OVERALL DIMENSIONS: 187.0 L X 53.0 W X 57.5 H

GENERAL UNIT SPECIFICATIONS :MATERIAL : GALVANIZED G90U STEELFINISH : POWDER-COATED BEIGECONDENSER COIL : COPPER TUBING, ALUMINUM FINSOPTIONAL COIL/FIN COATINGS : ELECTROFIN OR POLYFINNOMINAL FAN SPEED : 1140 RPMOPTIONAL VFD AVAILABLE

EACH UNIT ACCOMODATES UPTO SIX COMPRESSORS,ILLUSTRATION SHOWN FOR REPRESENTATION ONLY.ACTUAL PRODUCT MAY VAY DEPENDING UPON UNITCONFIGURATION.OPTIONAL DOOR HOLD-OPEN HARDWARE AVAILABLE

FAN CONTROLPANEL

COMPRESSORS

MAIN SYSTEM ELECTRICALCONTROL PANEL

ELECTRICALDISCONNECT PANEL

SUBCOOLER AND / OR WINTER CONTROL VALVESARE MOUNTED HERE, IF SUPPLIED

6 X LIFTING LUGS

RAIN GUARD

CONDENSERCOIL

SUCTION STUB 2-1/8"

SPLIT SUCTION STUB 2-1/8"

ELECTRIC POWERSUPPLY 2" NIPPLE

SATELLITESUCTION 7/8"

SUBCOOLEDLIQUID 7/8"

NON - SUBCOOLEDLIQUID 7/8"

GAS DEFROST5/8"

4.8

6.645.5

54.5

118.2

164.0

170.0

176.0

LIQUID RECEIVERLIQUID DRIER

OIL SEPARATOR

Page 3: SEE SHEET 3 FOR MINIMUM CLEARANCE REQUIREMENTS

SW

N 1

.0 S

UBM

ITTAL

SHEE

T S

IZE

D

SHEET 3 OF 3 PD-000000086 B

6-FAN PROTOAIREWITH PULL OFFPANELSDOC REV

THIRD ANGLE

PROJECTION

DIMENSIONS ARE IN INCHES.DATE DRAWN: 2017/09/14

R

INFORMATION SUBJECT TO CHANGE

NOTES:1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS.2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION.3. OVERALL DIMENSIONS: 187.0 L X 53.0 W X 57.5 H

MINIMUM CLEARANCE REQUIREMENTS:ACTUAL CLEARANCE REQUIREMENTS AREDEPENDENT UPON AUTHORITY HAVINGJURISDICTION, AND MAY EXCEEDDIMENSIONS SHOWN.

PROVIDE CLEARANCES AS SHOWN TO ENSUREADEQUATE AIRFLOW, REDUCE THE POTENTIALFOR AIR RECIRCULATION, FACILITATE SERVICEACCESSIBILITY, AND TO MAINTAIN COMPLIANCEWITH ELECTRICAL CODE REQUIREMENTS

SUGGESTED RIGGING SETUP IS ILLUSTRATED.BE SURE THAT LIFTING CABLES/STRAPS DO NOTDAMAGE PIPING STUBS, COIL SURFACE, OR RAIN GUARD.FULL PERIMETER SUPPORT FOUNDATION REQUIRED

3 SPREADERBARS

SPREADERBAR

59.1 59.1 44.9

66" MINIMUM

42.0

48.048.0

48.0

48.0

42'' CLEARANCE BETWEEN CONTROL PANEL AND ANY WALL

48'' CLEARANCE BETWEEN CONTROL PANEL AND ANY LIVE PANEL