S O F T S T A R T E R S

Page 2: Sedecal_descargas_28

Stop

Time

Start up Running SlowDowm

Curr

ent

Motor Thermal Protection

Programmations

Sedecal Group

Sedecal Control, S.A. was founded in March 1995.The Company was intended for designing andmanufacturing of medium and high power softstarters, frequency converters and power systems fordifferent applications in the field of heavy industry.

Sedecal Control is located in Algete (Madrid), and itis part of Sedecal Group.

Soft Starter Concept• On the squirrel cage motors, the start up current can

be up to 5 - 10 IN.

• The start up current is proportional to the appliedvoltage.

• 50 % of applied voltage leads to 50% and 25% ofcurrent and torque respectively.

• The start up time is a function of the motor - machineinertial characteristics. (Big fans need about 60seconds, and pumps 20 seconds approximately).

Industries• Paper mill Pulpers, refinders, pumps and fans• Steel mill Big fans, compressors, pumps and fans• Petrol Big fans, compressors, pumps and fans• Chemistry Fermentation stations, compressors,

pumps and fans• Water Desalination stations, compressors, pumps

Page 3: Sedecal_descargas_28

AdvantagesSAP 600 and SAP 6000 soft starter controllersensure the “soft” starting and stopping of largethree-phase induction motors without excessivepeak currents, motor heating or mechanicalshocks.

This has a particular importance in large machi-nes due to the power consumption in themegawatt range. The energy adsorbed by themotor winding and the shock torque have bothand important impact in the mechanical partsand consequently, influences the equipment life-time.

SAP 600 and SAP 6000 allow the reduction ofcable section and the energy peak power fromthe electricity supplier.

SAP 600 and SAP 6000 compensate the voltagedrop on the power cables. The soft startercontrollers apply the pre-set current values.

SAP 600 and SAP 6000 use current control. Thepre-set current value is not affected by the linevoltage or the specific motor start-up currents.

The power and control circuits are communica-ted through optical fibre.

SOFT STAR TER

S A P

SAP - 6000

SAP - 600

Main Referent• Papelera Penínsular Paper mill• Siemens Disperser• Aceralia Steel mill• Europac Paper mill• Cadasa Waters treatments• Pridesa Waters treatments• Eléctricas Centro Waters treatments

Page 4: Sedecal_descargas_28

S O F T S T A R T E R S

Supply voltage 200 - 3.300 V, 6.600 V - 13.000 V 220 to 690 VPower range 220 kW to 20.000 kW 50 kW to 1.000 kWFrequency 50 - 60 Hz 50 - 60 HzOverload 120” 3,5 IN. 3,5 IN.Overload 60” 4 IN. 4 IN.Overload 10” 5 IN. 5 IN.Overload 5” 6 IN. 6 IN.Continues overload 1,2 IN. 1,2 IN.Control system Programmable current control Programmable current controlOvervoltage protection RC network (Snubber) and VDR RC network (Snubber)Motor overload electronic protection Programmable CEI 655 - 8 Programmable CEI 655 - 8Soft stop Optional OptionalSoft start Programmable from control panel Programmable from control panelUnderload Programmable from control panel Programmable from control panelUnderload time Programmable from control panel Programmable from control panelQuick-start Programmable from control panel Programmable from control panelStart Stop per hour (1 - 10) Programmable from control panel Programmable from control panelPhase lose protection Programmable between (10÷900 mseg.) Programmable between (10÷900 mseg.)Instantaneous overcurrent Included IncludedThyristor detector failure Included NoPhase rotation detector Included IncludedRAM memory failure Included IncludedFuse detector failure Included Included4 - 20 mA motor current Included OptionalMain phases fast fuses Included OptionalMotor digital current Included IncludedLine digital voltage Included IncludedSelf diagnostic (50 error) Included IncludedBypass control Included IncludedPerpetual calendars Included IncludedHeatsinks temperature detector Included IncludedLeakage current detector Optional OptionalCooling system By forced air By forced airAmbient temperature -10º ÷ + 40ºC -10º ÷ + 40ºC

Output - Interfase Input - Interfase Input - Interfase

Fault Acknowledgement contactor bypass Acknowledgement contactor bypassRunning Acknowledgement fans failure detector Acknowledgement fans failure detectorOrder to close bypass contactor Heatsinks overtemperature Heatsinks overtemperatureMotor overload (1,2 IN.) Thyristors overtemperature failure detector Thyristors overtemperature failure detectorOrder to open bypass contactor Fuse failure detector Fuse failure detectorSoft starter active Remote start-up (pulse) Remote start-up (pulse)Start-up completed Stop (pulse) demanded by the user Stop (pulse) demanded by the user

Remote reset (pulse) Remote reset (pulse)Thyristor failure signal External ConditionsRemote on - of Remote on - ofSignal for user purposes Signal for user purposes

E L E C T R I C A L S P E C I F I C A T I O N S

S A P 6 0 0 0 S A P 6 0 0