secondary refrigerants maintaining condition and ... · secondary refrigerants: maintaining...

9
SECONDARY REFRIGERANTS: MAINTAINING CONDITION AND PERFORMANCE The Ontario Recreation Facilities Association Inc. (ORFA) regularly researches and writes about issues that could affect our members. These documents provide an opinion on key risk management issues but are not meant to provide any form of legal opinion or official interpretation. No one should act on such information without appropriate professional advice after a thorough examination of the particular situation. All rights reserved. ©2013 Ontario Recreation Facilities Association Inc. October 2013 Ontario Recreation Facilities Association Inc. T. 416.426.7062 F.416.426.7385 1 Introduction Maintaining all liquid levels in the refrigeration plant room is an important part of the inspection and upkeep of the system. Proper liquid levels help to ensure optimum performance thus reducing equipment wear and energy consumption. The most common cycle in an ice rink uses two (2) refrigerants: 1. Primary 2. Secondary The most common primary refrigerants found in North America are ammonia and Freon. Both are installed in the refrigeration system as a liquid and will go through a “change of state” (liquid to gas and back to liquid) during the refrigeration cycle. The primary refrigerant will not lose any of its stability; it remains constant regardless of use or age. The refrigeration technician must maintain the manufacturer’s recommended level to ensure optimum performance of the secondary refrigerant. Member Tips: Freon "We change our filter dryers every year and have found this to be a key preventative maintenance function in older plants. If we have problems with shaft seals we will take Freon sample for analysis." Ammonia “We are currently experimenting with our refrigeration contractor with a new ammonia filter dryer system. We will continue to keep the ORFA in tune with the results of this project.” Secondary refrigerants generally consist of antifreeze solutions, corrosion inhibitors and at times biocides. Secondary refrigerants are available in two (2) categories – aqueous (water based) and nonaqueous solutions. Aqueous secondary refrigerant solutions are most often mixtures of compounds such as calcium chloride or ethylene glycol and water. An example of a nonaqueous solution would be carbon dioxide. Our discussions will focus on aqueous secondary refrigerants only. For an example of a nonaqueous solution see http://www.ashrae.org/File%20Library/docLib/ eNewsletters/FPearson‐‐102013‐‐ 08222013feature.pdf. Aqueous secondary refrigerants are installed as a liquid and do not change state. Brine as a secondary refrigerant may lose some of its stability through use, age or contamination while glycol secondary refrigerants are considered to have a higher state of stability yet contamination is still a great concern. Both the primary and secondary refrigerants are held within “sealed” systems and when properly maintained loss from either of these elements should not occur. Any loss or fluctuation should be closely monitored, recorded and acted upon. Choosing a Secondary Refrigerant Secondary refrigerants are also referred to as “heat transfer fluids”. This fluid is cooled by the primary refrigerant then cycled through a series of pipes to the cooling load location (ice) and back to the refrigeration system to repeat the cycle. In an indirect system, the process includes a “heat exchanger” (chiller), a condenser, compressor and pump. All of these parts will have some resistance therefore it is important that the selected secondary

Upload: doannguyet

Post on 08-Apr-2018

229 views

Category:

Documents


2 download

TRANSCRIPT

SECONDARY REFRIGERANTS: MAINTAINING CONDITION AND PERFORMANCE

The Ontario Recreation Facilities Association Inc. (ORFA) regularly researches and writes about issues that could affect our

members. These documents provide an opinion on key risk management issues but are not meant to provide any form of legal opinion or official interpretation. No one should act on such information without appropriate professional advice after a thorough

examination of the particular situation. All rights reserved. ©2013 Ontario Recreation Facilities Association Inc. October 2013

Ontario Recreation Facilities Association Inc. T. 416.426.7062 F.416.426.7385 1 

Introduction Maintaining all liquid levels in the refrigeration plant room is an important part of the inspection and upkeep of the system. Proper liquid levels help to ensure optimum performance thus reducing equipment wear and energy consumption.  The most common cycle in an ice rink uses two (2) refrigerants:  

1. Primary  2. Secondary 

 The most common primary refrigerants found in North America are ammonia and Freon. Both are installed in the refrigeration system as a liquid and will go through a “change of state” (liquid to gas and back to liquid) during the refrigeration cycle. The primary refrigerant will not lose any of its stability; it remains constant regardless of use or age. The refrigeration technician must maintain the manufacturer’s recommended level to ensure optimum performance of the secondary refrigerant.   Member Tips: Freon "We change our filter dryers every year and have found this to be a key preventative maintenance function in older plants. If we have problems with shaft seals we will take Freon sample for analysis."  Ammonia “We are currently experimenting with our refrigeration contractor with a new ammonia filter dryer system. We will continue to keep the ORFA in tune with the results of this project.”  Secondary refrigerants generally consist of anti‐freeze solutions, corrosion inhibitors and at 

times biocides.  Secondary refrigerants are available in two (2) categories – aqueous (water based) and non‐aqueous solutions.  Aqueous secondary refrigerant solutions are most often mixtures of compounds such as calcium chloride or ethylene glycol and water. An example of a non‐aqueous solution would be carbon dioxide. Our discussions will focus on aqueous secondary refrigerants only. For an example of a non‐aqueous solution see http://www.ashrae.org/File%20Library/docLib/eNewsletters/F‐Pearson‐‐102013‐‐08222013feature.pdf.  Aqueous secondary refrigerants are installed as a liquid and do not change state. Brine as a secondary refrigerant may lose some of its stability through use, age or contamination while glycol secondary refrigerants are considered to have a higher state of stability yet  contamination is still a great concern.  Both the primary and secondary refrigerants are held within “sealed” systems and when properly maintained loss from either of these elements should not occur. Any loss or fluctuation should be closely monitored, recorded and acted upon.  Choosing a Secondary Refrigerant Secondary refrigerants are also referred to as “heat transfer fluids”. This fluid is cooled by the primary refrigerant then cycled through a series of pipes to the cooling load location (ice) and back to the refrigeration system to repeat the cycle. In an indirect system, the process includes a “heat exchanger” (chiller), a condenser, compressor and pump. All of these parts will have some resistance therefore it is important that the selected secondary 

Ontario Recreation Facilities Association Inc. T. 416.426.7062 F.416.426.7385 2

refrigerant provide a cost‐effective and energy efficient application.   Secondary refrigerants will be required to meet some basic  requirements (not all identified):   Positive thermal conductivity  High specific heat  Low viscosity  Quality chemical corrosion inhibitor  Stability with no separation or 

degrading  Non‐toxic  Non‐Flammable 

 Freezing point is best described as the crystal formation when a liquid turns from a fluid into a solid state. The common practice is to choose a secondary refrigerant with a freezing point of no less than 5‐10°C below the system’s normal operating temperature.  Viscosity of a fluid describes the state of being thick, sticky, and semifluid in consistency thus raising the internal friction of the system as it goes about cycling. Viscosity plays a key role in piping size and pump selection during the construction phase. Proper selection will help to ensure a cost effective day‐to‐day operation.  Density is the concentration level of the secondary refrigerant fluid. Checking density is the most effective way of determining secondary refrigerant condition.  The majority of aqueous secondary refrigerants found in ice rinks are salt based and are corrosive by nature. To reduce system corrosion it is imperative to select and maintain a quality corrosion inhibitor or chemical stabilizer.  Equipment Inspections Ongoing equipment inspection is the responsibility of the owner as set out in the Operating Engineer Regulation. Persons permitted entry into a refrigeration plant room in order to perform work must be “competent” 

as set out in the Ontario Occupational Health and Safety Act to do so.   Inspection of secondary refrigerant levels will help to quickly identify operational issues of the plant. Slight fluctuation of secondary refrigerant levels should be considered normal. However, ongoing reduction in level or dramatic fluctuations may be an indication of a system leak and should be recorded in the registered plant room log book, investigated and repaired.  Regular off‐season inspection of the plant room is also an important part of maintaining the system. During the shutdown period it is important to continue to monitor the condition of the plant. It is not uncommon for the secondary refrigerant pump to be turned on for a day each month of shutdown to circulate the fluid to ensure seals in the system remain lubricated. Inspecting the plant room weekly during shutdown is strongly recommended.  Member Tip: "Our solution was to install a float in the expansion tank that is tied into a BAS system to monitor the fluid level of the secondary refrigerant loop. The BAS system can be set up to allow for level fluctuation on startup and shut down of the pump, send an alarm and even shut down the plant or pump for a specific rink in a multi pad facility."  Air in the System Another enemy to the system is the introduction of air. Air contains moisture which will contribute to internal deterioration of the system; it may also reduce the effectiveness through blockage of the refrigeration cycle. Air must be removed from the system.  Refrigerant Leaks in the Plant Room Aqueous secondary refrigerants are water based and therefore present a worker slip hazard if they escape from the system and on to the plant room floor. Use of proper PPE as outlined in the Material Safety Data Sheet is 

Ontario Recreation Facilities Association Inc. T. 416.426.7062 F.416.426.7385 3

also considered essential worker protection when dealing with leaks.  System Maintenance Plant owners should design and maintain a comprehensive refrigeration maintenance program specific to each registered refrigeration plant room. A contractual working relationship with an accredited refrigeration contractor is a legal obligation under the Operator Engineer Regulation (OER). This contractual obligation does not lessen the responsibility of the owner to maintain a safe registered refrigeration plant room.   For a maintenance plan to be effective the owner must have a qualified internal representative (responsible person) that understands the legislative obligations that must be met, the on‐site refrigeration equipment and what investment must be made to keep the registered plant room safe and serviceable.  Although there may be some human risks associated with secondary refrigerants use and contact they should be viewed as being manageable. Maintaining concentration levels as well as corrosion protection will help ensure maximum energy efficiency and equipment life‐cycle.  Maintaining fluid density ensures maximum operational capability while reducing the chance of a system freeze‐up. Secondary refrigerants must have the density checked no less than once per‐year. This test can most likely be performed by the refrigeration contractor but there should be no assumption that it will be conducted without direction from the owner.   When “topping up” any secondary refrigerant it is important to note that not all inhibitors can be mixed with “hard water”. It must also be noted that propylene and ethylene glycol refrigerants are susceptible to bacterial 

contamination; a biocide must be added and properly maintained in these types of systems.  Corrosion problems can escalate within a short period of time (months vs. years). The lack of inhibitor use will result in excessive corrosion and premature equipment failure. An additional inspection of the inhibitor must also be planned. Determining how often this test must be performed (1 ‐3 times per year) will be based on the age, ongoing maintenance program and an evaluation of the system.   Simple evaluation of plant room condition can be performed by viewing control valves. Valves that are corroded are indicators of poor maintenance. Refrigeration equipment can be maintained through low cost methods. Regularly turning valves to ensure smooth operation, cleaning away dirt and rust and painting as required will all serve to prolong function and life of the equipment. 

Member Tip: “We used to do secondary refrigerant testing annually on our calcium chloride systems but from past experiences and with equipment failure we now do our testing semiannually. With this change we still have to make adjustments to the secondary refrigerant each time we test. This indicates that the breakdown of refrigerant can happen quite quickly.”  Mechanics Tips: “When sampling brine, a steady clean stream or sample should be taken.  Sampling streams should be flushed enough to get a representative sample from the system and not the entrapped line which does not represent the system. Sample bottle must be clean and dry or it is new.   Side stream filtration is recommended to trap sediment, dirt and debris. However, this may interfere with dosing of certain additives and may depleted their charge along with the brine system's debris. Filtration before dosing may be preferred. If the CaCl brine system is maintained 

Ontario Recreation Facilities Association Inc. T. 416.426.7062 F.416.426.7385 4

well without any ups and down, organic inhibitors tend to stabilize.  Adding a new organic inhibitor charge to a brine system for the first time or when the system is new may see the inhibitor "consumed" as it makes it's protective layers within the system. Chemists suggest that organic inhibitors will deplete until a stage comes when it is stabilizes. Consumption of inhibitor in a stabilized system is not supposed to be as aggressive. When the system has ups and down like sudden change in the system, pH up or down, adding any additional chemical into the system etc. may also consume the inhibitor. It is always hard to predict what any new additive may do to organic inhibitors.”  Conclusion The condition and performance of secondary refrigerants is necessary for quality refrigeration plant operations. Plant operators must be able to identify the type of secondary refrigerant used and all of its elements. This is best accomplished by maintaining up to date Material Safety Data Sheets (MSDS). It is essential to keep on site records that state operational levels, concentration and fluid quality reports.  

Training staff to inspect equipment and to safely take appropriate action for minor problems will help to prevent the potential of major problems. Further, staff must be trained to deal with spills and leaks in a safe and environmentally friendly manner.   Creating and maintaining a comprehensive program for secondary refrigerant inspection is the most essential element of preserving its overall condition and performance.  Disclaimer ©Ontario Recreation Facilities Association Inc., 2013 The information contained in this reference material is distributed as a guide only; it is generally current to the best of our knowledge as to the revision date, having been compiled from sources believed to be reliable and to represent the best current opinion on the subject. No warranty, guarantee or representation is made by ORFA as to the absolute correctness or sufficiency of any representation contained in this reference material and ORFA assumes no responsibility in connection therewith; nor can it be assumed that all acceptable safety and health measures are contained in this reference material, or that other or additional measures may not be required in particular or exceptional conditions or circumstances. 

While ORFA does not undertake to provide a revision service or guarantee accuracy, we shall be pleased to respond to your individual requests for information at any time. Reference to companies and products are not intended by the publisher as an endorsement of any kind. 

ORFA EDITORIAL NOTE: Member/Contractor Tips are provided for information only.  Members should always research and investigate all options that meet their currents needs as part of an internal review process. 

   

Ontario Recreation Facilities Association Inc. T. 416.426.7062 F.416.426.7385 5

               

Appendix   •  Brine Analysis Report •  Calcium Chloride Table •  DOWFLAKE™ Xtra 83‐87% Calcium Chloride product information sheet 

Brinemastercimco.doc Rev. Date Feb. 19/03 Rev # 0

CIMCO BRINE ANALYSIS REPORT P.O.#: 4500214014 SHIPPER NO:34663

DATE PROCESSED: 05/29/07 LABORATORY NO: 07-164E

DATE RECEIVED: 04/27/07 RECEIVED FROM: Toronto

BRINE TYPE: Calcium Chloride FACILITY:004 Rink #4

DESCRIPTION ACTUAL PREVIOUS TYPICAL Colour/Clarity: Light green after

filtration

Clear/Yellow Chromate

Clear/Blue (575)

Ammonia Check Test:

Nil Nil

Odour:

Nil Nil

Supernatant:

Nil Nil

Sediment:

4 lb/1000 gal Nil

pH: 7.9 8.5 – 9.5 (Chromate)

9.0 – 9.5 (575)

Specific Gravity at 60 F:

1.193 1.21 – 1.22

Percent Calcium Chloride:

20.9 % 22.4 – 23.3 %

Freeze Point:

-3.1 F -10 deg. F

Inhibitor Concentration: Nil

27 ppm

1600 ppm (Chromate)

100 ppm (575)

PH adjust: Add 100 milliliters of 50 % Sodium Hydroxide solution per 1000 US Gal of brine

Freeze point adjust:Add 7.1x50 lb of 77 % Calcium Chloride flakes or 6.1x50 lb of 90 % Calcium

Chloride pellets per 1000 Gal of brine

Inhibitor adjust: Add 20 L of Ancobrand inhibitor 575 per 1000 Gal of brine

Filtration adjust: Recommended filtration

COMMENTS: Please follow the sequence as 1. Add Sodium Hydroxide and let it dissolve completely,

2. Filter, 3. Add the rest

Thanks; any questions, please don’t hesitate to call us.

E-mailed to: John McAllister, Tony Roehrig

Chief Chemist: Sat Anand Date: 05/29/07 Cimco makes no warranties or representations whatsoever, either express or implied, oral or written, in fact or by operation of law or

otherwise, regarding any measurements and recommendations and disclaims all liability in connection with or arising as a result of

providing any services, measurements and recommendations. Cimco accepts no liability or responsibility for any service,

measurement or recommendation and does not and shall not be deemed to approve the design, use or function of, any item, material,

article or product in connection with the services, measurements or recommendations provided..

1.0071.0141.0211.0281.0351.0431.0501.0581.0651.0731.0811.0891.0971.1051.1141.1221.1311.1401.1491.1581.1671.1761.1861.1961.2051.2151.2251.2361.2461.2571.2681.2791.2901.3021.313

1234567891011121314151617181920212223242526272829303132333435

4812162024283236404448525660646872768084889296100104108112116120

-----

0.9431.8862.8293.7724.7155.6586.6017.5448.4879.430

10.37311.31612.25913.20214.14515.08816.03116.97417.91718.86019.80320.74621.68922.63223.57524.51825.46126.40427.34728.29029.23330.17631.11932.06233.000

+31.20+30.40+29.60+28.80+28.00+26.89+25.78+24.67+23.56+22.09+20.62+19.14+17.67+15.75+13.82+11.89+ 9.96+ 7.68+ 5.40+ 3.12- 0.84- 4.44- 8.03

- 11.63- 15.23- 19.56- 24.43- 29.29- 35.30- 41.32- 47.66- 54.00- 44.32- 34.66- 25.00

48454443424140383735.53432.530.529272523.521.520181512.510.58641.5

1” vacuum5” vacuum8.5” vacuum

12” vacuum15” vacuum10” vacuum4” vacuum1.5 pounds

SpecificGravity at 64Degrees F.

DegreeBeaume at 64

Degrees F.

DegreeSalometer at 64

Degrees F.Per CentOf CaC12

FreezingPoint in

Degrees F.

AmmoniaGauge Pressure

Pounds perSquare Inch

CALCIUM CHLORIDE TABLE

ApplicationDOWFLAKE™ Xtra 83-87% Calcium Chloride possesses distinctive properties that make it the ideal choice for ice melting, dust control, concrete acceleration and many other applications. Its higher concentration provides a lower application rate than conventional 77-80% calcium chloride flake.

DOWFLAKE™ Xtra releases heat to melt snow and ice faster and across a wider range of temperatures than other materials. Mix it with rock salt, sand and gravel to improve their performance.

It reduces dust on unpaved surfaces by absorbing moisture from its surroundings, keeping the surface damp and binding dust particles to the gravel.

Adding it to concrete results in reduced time for initial and final set, increased early strength and protection in cold weather.

When put into solution, DOWFLAKE™ Xtra is effective in many other applications, including tire weighting and brine refrigeration. (See tables on reverse.)

DescriptionDOWFLAKE™ Xtra is a purified inorganic salt produced by removing water from a naturally occurring brine solution. Unlike other processes used to produce calcium chloride, the brine process does not involve reactions with chemicals such as hydrochloric acid or ammonia. The National Organic Standards Board noted this distinction when it classified the brine process as “non-synthetic.”

DOWFLAKE™ Xtra meets or exceeds ASTM D98 and AASHTO M144 requirements for calcium chloride purity. ASTM classification for DOWFLAKE™ Xtra is Type S, Grade 1, Class A.

StorageSolid calcium chloride is both hygroscopic and deliquescent. This means that the product can absorb moisture from the air, even to the point of converting to liquid brine. For this reason, solid calcium chloride should be protected from excessive exposure to moisture to maintain product quality while in storage. Store in a dry area. Opened packages should be tightly resealed after each use.

For full safety and handling details, refer to the current Material Safety Data Sheet for this product, available at www.oxycalciumchloride.com.

AvailabilityDOWFLAKE™ Xtra is available in various package sizes, and in bulk truck and bulk rail.

DOWFLAKE™ Xtra 83-87% Calcium ChlorideUnique Properties for “Xtra” Advantage

Product Information

™Trademark of The Dow Chemical Company

CharacteristicCalcium chloride assay

Flake size distribution Larger than 4.8 mm From 0.6 to 4.8 mm Smaller than 0.6 mm

>83%

Typical Value

<20%>75%<5%

ASTM D98 purity requirements(1)

Total alkali chlorides (as NaCl) Total magnesium (as MgCl2) Calcium hydroxide

<6%>0.5%>0.2%

Properties

(1) On an active ingredient basis.

Important: The information presented herein, while not guaranteed, was prepared by technical personnel and is true and accurate to the best of our knowledge. NO WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE, OR WARRANTY OR GUARANTY OF ANY OTHER KIND, EXPRESS OR IMPLIED, IS MADE REGARDING PERFORMANCE, SAFETY, SUITABILITY, STABILITY OR OTHERWISE. This information is not intended to be all-inclusive as to the manner and conditions of use, handling, storage, disposal and other factors that may involve other or additional legal, environmental, safety or performance considerations, and OxyChem assumes no liability whatsoever for the use of or reliance upon this information. While our technical personnel will be happy to respond to questions, safe handling and use of the product remains the responsibility of the customer. No suggestions for use are intended as, and nothing herein shall be construed as, a recommendation to infringe any existing patents or to violate any Federal, State, local or foreign laws.

Form No. 173-01713-0909P&M

For more information or to find an authorized distributor of OxyChem’s calcium chloride products, please call or visit our website.

(888) 293-2336www.oxycalciumchloride.com

Printed in U.S.A.

Making Calcium Chloride Solutions From DOWFLAKE™ XtraCalcium chloride releases heat when it is dissolved. Make sure that the dissolving vessel is appropriately constructed for handling hot solutions. Fill the vessel with cool water (less than 80ºF/26ºC), then slowly add calcium chloride while continuously stirring. Solids kept in motion will dissolve quickly; however, solids that sit motionless on the vessel bottom may form a hard cake that will dissolve more slowly.

.

.

.

.

.

.

.

.

.

Making 100 Liters of Solution From DOWFLAKE™ Xtra Calcium Chloride(1) % CaCl2 Target

262830323436384042

Specific Gravity(26ºC)

1.2511.2751.2981.3221.3451.3691.3921.4161.439

Density @ 25ºC(kg/L)

1.2471.2711.2941.3181.3411.3651.3881.4121.435

Weight of Product to

Dissolve (kg)

384246505458626771

Water Volume

(L)

878684828179777573

Expected Temp.

Rise (ºC)

343740434449484949

Solution Freeze

Point (ºC)

-35-43-47-27-12 -1 +9+16+21

(1) To make up solution volumes different from those used as the basis above (100 gallons or 100 liters), simply adjust the “Weight of Product to Dissolve” and the “Water Volume” numbers in the tables by the ratio of the desired solution volume to 100. For example, to make 2000 gallons of 32% solution: Weight of Product to Dissolve = 415 x (2000/100) = 8300 lbs; Water Volume = 82 x (2000/100) = 1640 gals

Making 100 Gallons of Solution From DOWFLAKE™ Xtra Calcium Chloride(1)

% CaCl2 Target

262830323436384042

Specific Gravity (77ºF)

1.2511.2751.2981.3221.3451.3691.3921.4161.439

Density @ 77ºF (lb/gal)

10.5010.6010.7910.9911.1811.3811.5711.7711.96

Weight of Product to

Dissolve (lb)

319350382415448483518555592

Water Volume

(gal)

878684828179777573

Expected Temp.

Rise (ºF)

626772778084878889

Solution Freeze

Point (ºF)

-31-46-52-17+10+30+48+61+69

.

.

.

.

.

.

.

.