schedule of work i/c. installation of 7x16 kva, sub-stations for electrification of 7(seven) nos. of...

6
Ch to: Deposit work with the TTAADC. Sl No Description of Items Qty. Unit Rate/Unit (₹) Amount (₹) A. Erection of the following items. 1 Erection of 9.0 mtr. Long Steel Tubular Poles (Designation 410: SP-54) conforming to ISS: 2713 (P-I & II)-1980 with base plate direct in earth including excavation, refilling and ramming etc. as required (1/6th length of the pole to be embedded in earth) and grouting with CC of ratio 1:2:4 (1 cement : 2 river sand : 4 jhama brick aggregate of 20 mm. nominal size) ilc supply of cement, sand and brick aggregate complete with excavation, refilling of earth, ramming alongwith centering and shuttering as required (@ 0.273 Cum per Steel Tubular Pole as per TSECL specification ) etc. and applying paints with ready mixed primer (two or more coats) and aluminium paint of approved quality to give an even shade etc. as required as per direction of the Engineer-in-Charge. 431 No 2 Erection of 8 mtr. long Steel Tubular Poles (Designation 410: SP-54) conforming to ISS: 2713 (P-I & II)-1980 with base plate direct in earth including excavation, refilling and ramming etc. as required (1/6th length of the pole to be embedded in earth) and grouting with CC of ratio 1:2:4 (1 cement : 2 river sand : 4 jhama brick aggregate of 20 mm. nominal size) ilc supply of cement, sand and brick aggregate complete with excavation, refilling of earth, ramming alongwith centering and shuttering as required (@ 0.273 Cum per Steel Tubular Pole as per TSECL specification ) etc. and applying paints with ready mixed primer (two or more coats) and aluminium paint of approved quality to give an even shade etc. as required as per direction of the Engineer-in-Charge. 381 No Name of work: Extension of HT line with ACSR Conductor and LT line with 25 mm2 Aerial Bunched Cable i/c. installation of 7x16 KVA, Sub-Stations for electrification of 7(seven) nos. of un-electrified habitations having population below 100 at Ataram para habitation of Kakracherra VC, Jugendra para habitation of Haludia VC, Hadukalak para habitation of Kakracherra V.C., Bangaisi para habitation of Haludia VC, Rabi para habitation of Kakracherra VC, Biswamani para habitation of Nunacherra VC and Samprai Bahadur para habitation of Nunacherra VC located under the jurisdiction of Nunacherra Census Village of Mungiakami R.D. Block covered by ESD-Mungiakami. (Revised Estimate) SCHEDULE OF WORK Signature of Bidder/Condractor Page No 1 of 6

Upload: hathien

Post on 14-Mar-2018

217 views

Category:

Documents


1 download

TRANSCRIPT

  • Ch to: Deposit work with the TTAADC.

    Sl No

    Description of Items Qty. Unit Rate/Unit () Amount ()

    A. Erection of the following items.

    1

    Erection of 9.0 mtr. Long Steel Tubular Poles(Designation 410: SP-54) conforming to ISS:2713 (P-I & II)-1980 with base plate direct inearth including excavation, refilling andramming etc. as required (1/6th length of thepole to be embedded in earth) and groutingwith CC of ratio 1:2:4 (1 cement : 2 river sand: 4 jhama brick aggregate of 20 mm. nominalsize) ilc supply of cement, sand and brickaggregate complete with excavation, refillingof earth, ramming alongwith centering andshuttering as required (@ 0.273 Cum perSteel Tubular Pole as per TSECLspecification ) etc. and applying paints withready mixed primer (two or more coats) andaluminium paint of approved quality to givean even shade etc. as required as perdirection of the Engineer-in-Charge.

    431 No

    2

    Erection of 8 mtr. long Steel Tubular Poles(Designation 410: SP-54) conforming to ISS:2713 (P-I & II)-1980 with base plate direct inearth including excavation, refilling andramming etc. as required (1/6th length of thepole to be embedded in earth) and groutingwith CC of ratio 1:2:4 (1 cement : 2 river sand: 4 jhama brick aggregate of 20 mm. nominalsize) ilc supply of cement, sand and brickaggregate complete with excavation, refillingof earth, ramming alongwith centering andshuttering as required (@ 0.273 Cum perSteel Tubular Pole as per TSECLspecification ) etc. and applying paints withready mixed primer (two or more coats) andaluminium paint of approved quality to givean even shade etc. as required as perdirection of the Engineer-in-Charge.

    381 No

    Name of work: Extension of HT line with ACSR Conductor and LT line with 25 mm2 Aerial BunchedCable i/c. installation of 7x16 KVA, Sub-Stations for electrification of 7(seven) nos. of un-electrifiedhabitations having population below 100 at Ataram para habitation of Kakracherra VC, Jugendrapara habitation of Haludia VC, Hadukalak para habitation of Kakracherra V.C., Bangaisi parahabitation of Haludia VC, Rabi para habitation of Kakracherra VC, Biswamani para habitation ofNunacherra VC and Samprai Bahadur para habitation of Nunacherra VC located under thejurisdiction of Nunacherra Census Village of Mungiakami R.D. Block covered by ESD-Mungiakami.(Revised Estimate)

    SCHEDULE OF WORK

    Signature of Bidder/Condractor Page No 1 of 6

  • 3

    Erection of painted Stay Set complete directin earth with 16 mm. dia. 1.8 mtr. longpainted stay rod, anchor plate of size 300 X300 X 8 mm. thick, turn buckle of length 356mm. with 300 mm. long threaded adjustable16 mm. dia. MS rod , thimble, guy insulatoras per IS specification, hot dip (heavy duty)galvanized stay stranded wire of size 7/2.5mm. fastened with stay clamps as required. (including supply of MS clamp & Nuts & Boltsas reqd) and Grouting of stay set with CC ofratio 1 :2:4 (1 cement: 2 river sand: 4 jhamabrick aggregate of 20 mm. nominal size) ilcsupply of cement, sand and brick aggregatecomplete with excavation, refilling of earth,ramming alongwith centering and shutteringas required ( @ 0.119 Cum per stay set asper TSECL Specification)

    650 Set

    4

    Erection of 2.8 mtr. long made of 75 X 40 X40 X 6 mm. MS Channel for Sub-StationGOS, DOF bracket as per direction of theEngineer-in-Charge.

    28 No

    5Erection of .3 mtr. long S/P top bracket madeof 75 X 40 X 40 X 6 mm. MS Channel as perdirection of the Engineer-in-Charge.

    127 No

    6Erection of 1.2 mtr. long S/P bottom bracketmade of 75 X 40 X 40 X 6 mm. MS Channelas per direction of the Engineer-in-Charge.

    127 No

    7Erection of 2.2 mtr. long D/P bracket made of75 X 40 X 40 X 6 mm. MS Channel as perdirection of the Engineer-in-Charge.

    136 No

    8

    Erection of 2.8 mtr long made of100x50x50x6 mm. MS Channel fortransformer base as per direction of theEngineer-in-Charge.

    21 Nos

    9

    Erection of 0.8 mtr long made of100x50x50x6 mm. MS Channel fortransformer base as per direction of theEngineer-in-Charge.

    14 Nos

    10

    Erection of 2.8 mtr long made of 65x65x6mm. MS Angle for cross arm for GOShandle bracket as per direction of theEngineer-in-Charge.

    7 No

    11Erection of 3.2 mtr. long Sub-Station guardbracket by 65x65x6 mm MS Angle as perdirection of the Engineer-in-Charge.

    7 Nos

    12Erection of 1.5 mtr. long single pole guardbracket by 65x65x6 mm MS Angle as perdirection of the Engineer-in-Charge.

    127 Nos

    13Erection of 2.5 mtr. long double pole guardbracket by 65x65x6 mm MS Angle as perdirection of the Engineer-in-Charge.

    136 Nos

    Signature of Bidder/Condractor Page No 2 of 6

  • 14

    Erection of Polimerik Disc Insulator Ball andSocket type for 11 KV system (EMS-45 KN)conforming to ISS:731/1971 in angle anddead end locations including tension fittingsof EMS-45 KN to accommodate the relevantACSR conductor size along with nuts andbolts, washer etc. as required in complete asper direction of the Engineer-in-Charge.

    768 No

    15

    Erection of Polimerik Pin Insulator includingG.I Pin for 11 KV system with mechanicalstrength of 10 KN conforming toISS:731/1971 with hot dip galvanized M.Sforged 11 KV G.I pin alongwith galvanizedhexagonal nuts, G.I flat washer and G.Ispring washer conforming to ISS: 2486(P-II)/1974 etc. as required in complete as perdirection of the Engineer-in-Charge.

    786 No

    16

    Erection of 11 KV, 200 Amps. 1-phase GOSwitch complete i/c fixing horizontally &vertically operating pipe & operating handlewith nuts & bolts etc. as required.

    14 Set

    17Erection of 11 KV 1-phase DO Fusecomplete with nuts & bolts etc. as required.

    7 Set

    18

    Erection of 9 KV, 5 KA single pole metaloxide gapless type Lightening Arrestor i/c.necessary connection complete as perdirection of the Engineer-in Charge.

    77 Set

    19

    Laying, hoisting & stringing of ACSR(6/1/2.59 mm) Weasel Conductor includingbinding, jumpering, etc. as reqduired & as per direction of the Engineer-in-Charge.

    52 Km

    20

    Laying, hoisting & stringing of 8 SWG G.I.wire as per ISS : 280/1978 amended latestwith heavy coating as per ISS : 4826 I 1968of tensile strength 55 to 95 Kgf/mm i/cfastening with cross arm & metallic parts forearth continuity wire and metal parts to earthelectrode as per direction of the Engineer-in-Charge.

    33.5 Km

    21

    Laying, hoisting and stringing of 1.1 KVClass, LT , Aerial Bunched Cable of size1CX25+1CX16+1X25 sqmm for LT Overhead line on existing pole as required as perdirection of the Engineer-in-Charge.

    15 Ckm

    22

    Erection and fitting fixing of LT InsulationPiercing Connectors (IPC) for makingTee/Tap-off/Service connectors to anABC/Bare Overhead Line suitable for LT ABCable 25 sq mm to 95 sq mm

    496 Nos

    Signature of Bidder/Condractor Page No 3 of 6

  • 23

    Erection & fitting fixing of SuspensionAssembly Comprising of 'suspensionbracket', movable connecting links,galvanised suspension clamp, bracket clamp,nuts & bolts (Suitable for 25-95 sq mm baremessenger wire) on existing pole with thehelp of galvanised clamp (made of 2nos,50X6mm Flat) and nuts & bolts includingsupply of galvanised clamp, nuts & bolts etc.for LT AB Cable.

    304 Nos

    24

    Erection & fitting fixing of DeadEnd/Anchoring Assembly comprising oftension bracket wedge type, galvanisedtension clamp, flexible stain steel rope forfixing of tension clamp (Suitable for 25-95 sqmm bare messenger wire) on existing polewith the help of galvanised Clamp (made of2nos, 50X6mm Flat) and nuts & boltsincluding supply of galvanised clamp, nuts &bolts etc. (For LT AB Cable)

    420 Nos

    25

    Erection & Fitting Fixing of galvanised steelmade 'Eye Hook' with hot dip galvanised nuts& bolts.(Suitable for all size cable) for LT ABCable.

    730 Nos

    26

    Erection & Commissioning of pole mounted 1-phase, 200 Amps all weather proof FRP multiconnection LT SERVICE MAINDISTRIBUTION BOXES

    124 Nos

    27Erection of Pre-Insulated Jointing sleeve for25 sqmm LT AB Cable.

    156 Nos

    28Erection of Pre-Insulated Bi-metallic Socketfor 25 sqmm LT AB Cable.

    156 Nos

    29

    Supply and erection of Earthing Set as perISS : 3043 of 1966 and with latestamendment if any, 2.5 mtr long G.I. pipe (ISImarked) of 40 mm diameter with suitableholes on pipe circumference including a pairof clamps (made of 50 X 6 mm M.S. flat),galvanized nuts & bolts along with alternatelayers of salt & charcoal including supply of4.0 mtr long, 12mm dia PVC pipe for eachearthing set etc. as required and as perdirection of the Engineer-in-Charge.

    184 Set

    30

    Erection & commissioning of 16 KVA, 50 HZ,outdoor type 11/0.433 KV AC DistributionTransformer on Sub-Station Channel base ata height of 2440 mm (approx) above GroundLevel with required connection by ACSR from11 KV line to Transformer via GOS & DOFfastened straining screw, clamp, nuts & boltsas required as per Technical Specification.

    7 Nos

    Signature of Bidder/Condractor Page No 4 of 6

  • 31

    Erection of PVC Cable 70 sqmm i/c fittingfixing 100 Ampere cut out on wooden plankmaking connection from Transformer LT sideto overhead LT Line via fuse unit ofunarmored PVC cable 1100-V gradeconforming to ISS: 1554 (P-I) /1988 of thefollowing sizes and the cables shall beproperly crimped by bi-metallic lugs atcontact areas as per direction of the Engineer-in-Charge. ( Wooden Plank 500X300X25 mmwill be supplied by the Contractor)

    7 Job

    32

    Providing BPL Service Connection along witherection and supply of 1.1KV PVC 2.5 Sq.mm., 1 Core or two 1Core Cable (ServiceWire), GI Wire 10SWG (for ServiceConnection), GI Wire 8SWG (for CoilEarthing), Real Insulator, Single PhaseEnergy Meter, 5-20 Amps (To be Suppliedby TSECL), Cut out 16 Amps., 16 AmpsICDP Main Switch/ Main Switch make Bajaj,Crompton and Havells, 8x12 WoodenBoard, 4x4 Wooden Board, 5 Amps. Switch,5 Amps. Angle Holder, Retrofit LED Lamp 9Watts, Wooden batton 1/PVC Casing (8 MtrLump sum), Wooden Plank etc. as required10 (1 Mtr Lump sum), 1.5 sq. mm. PVC Wire(Single Core 650 Volt grade) with link clip &nails etc. as required, Coil earthing includingmaking of pit, refilling, fabrication, erection,connection etc. as required with supply ofsalt, charcoal & PVC pipe 3 mtr. long to coverearth wire above ground level excludingsupply of G.I. Wire as per direction of theEngineer-in-Charge.

    124 No

    33

    Providing of Sub-Station protective fencing ofsize 2X3 mtr. And height 1.5 mtr. as perengineer requirement by 65X65X6 mm MSAngle post of height 2 mtr. Horizontal bar2X3 mtr and 2X2 mtr. And top angle posts by50X50X6 mm MS angle and two part MSGrill door of size 1.2X1.4 mtr with lockingarrangement i/c necessary grouting andpainted aluminium paint over red oxidepriming of approved quality as required asper Technical Specification.

    7 Job

    34

    Cutting, clearing & disposal of jungle/tree ofany girth from 3(three) meter either side ofHT/LT line of providing required vertical andhorizontal clearance as per provision of I.E.Rule.

    62 KM

    B Supply of the following materials

    1Fabricated bracket clamps 50x6 mm MS Flat(assorted sizes) i/c. holes as per requirementby Drill Machine.

    1051 Nos

    Signature of Bidder/Condractor Page No 5 of 6

  • 2Stay Clamps 50x6 mm MS Flat i/c Nuts &Bolts etc as required.

    650 Pair

    3 70/95 sq. mm. Bi-metallic Lugs 70 Nos

    4 Nuts & Bolts (Assorted Size) 600 Kg

    5 Polythin Pipe 1/2" dia. for Pipe Earthing 736 mtr

    6 Reel Insulator (4-10 sqmm) 2500 Nos

    7Galvanized Steel made Eye Hook with hotdip galvanized nuts & bolts for LT AB Cable

    730 Nos

    C

    Carrying of the following steel tubularPole from Electrical Store Sub-Division,A.D. Nagar, Agartala to work site withinthe administrative jurisdiction ofMungiakami R.D. Block by mechanicaltransport, hand cart & manual labour etcas required i/c. loading, unloading &stacking (i/c. river / cherra crossing ifrequired) etc. as per direction of theEngineer-in-Charge.

    1 9 mtr long steel tubular pole 431 nos

    2 8 mtr long Steel tubular pole 381 nos

    D

    Carrying of the Line Materials andTransformer etc from Electrical Store Sub-Division, AD Nagar, Agartala to work sitevia. ESD-Mungiakami storeyard within theadministrative jurisdiction of MungiakamiR.D. Block by mechanical transport,hand cart & manual labour etc. asrequired i/c. loading, unloading, stackingetc as required.

    1 Line Materials, Transformer etc. 15 Trips

    E

    Numbering of Pole/DT with black Japperpaint after applying priming coats by redoxide primer followed by a painting 2 ormore coats with synthetic enamel paint(Yellow Colour) of approved quality withina area of 8"X14" on pole /DT as requiredas per direction of the Engineer-in-Charge.

    a 8 mtr Long Steel Tubular Pole 381 Nos

    b16 KVA, 1-phase 11/0.433 KV DistributionTransformer

    7 Nos

    Manager Deputy General ManagerESD-Mungiakami Electrical Division, Teliamura

    TSECL, Khowai District TSECL, Khowai District

    Total =

    Signature of Bidder/Condractor Page No 6 of 6

    Sheet3

    Comparative Statement

    ABSTRACT

    Name of work: Extension of 11 KV line by under ground XLPE cable for emergency power connection to the Intake well and treatment plant under Khowai Electrical Sub-division

    Ch to : Deposit work

    NIT No : DGM/ED-X/KH/12-13/04 dated, 24.04.2013 (Sl. No.: 1)

    Estimated Cost Put to the Tender: Rs. 23, 11, 027/-

    Tender form sold : 3 (Three)

    Tender form received : 2 (Two)

    Tender form found formal : 2 (Two)

    Tender form found informal : Nil

    Sl. No.DescriptionAs per EstimateSri Dilip Kumar Kar [1/2]Sri Sudhangshu Bhattacharjee [2/2]

    1Amount of Carrying of PART -'A'000

    2Amount of Supply of PART -'B'000

    3Amount of Erection of PART-'B'000

    4Taxes and dutiesIncludedIncludedIncluded

    GRAND TOTAL000

    Say,Rs.23, 11, 027/-Rs.25, 25, 994/-Rs.26, 48, 797/-

    1st Lowest2nd Lowest

    Remarks: With a view to extension of 11 KV line by under ground XLPE cable for emergency power connection to the Intake well and treatment plant under Khowai Electrical Sub-division, a tender vide NIT No: DGM/ED-X/KH/12-13/04 dated, 24.04.2013 (Sl. No.: 1) was invited. After that, 3 (three) numbers of bid documents were sold to the intended bidders namely, 1] Sri Dilip Kumar Kar, 2] Sri Ashish Debnath, and 3] Sri Sudhangshu Bhattacharjee, against receipt of required cost. But only 2 (two) bidders namely, Sri Dilip Kumar Kar and Sri Sudhangshu Bhattacharjee have submitted the filled-in bid document within the stipulated date and time with required documents. On scrutiny, bid documents of both the bidders were found formal. Thereafter, a Comparative Statement (C.S.) has been prepared. From the C. S., it may be seen that Sri Dilip Kumar Kar has become the 1st lowest bidder and his tender value is Rs.25, 25, 994/- (Rupees twenty five lacs twenty five thousand nine hundred and ninety four only) inclusive of all taxes and duties which is 9.302% (approx.) higher than the estimated cost put to the tender. Now, the matter is submitted before the authority for decision please.

    Draft Prepared byChecked by

    (Er. S. Debnath)(Er. N. Debbarma)(Er. K.L. Das)

    Manager (Electrical), Gr. ASr. Manager (Electrical)Deputy General Manager

    Electrical Division No-X, KhowaiElectrical Division No-X, KhowaiElectrical Division No-X, Khowai

    Sheet2 (2)

    Name of work: Extension of HT line with ACSR Conductor and LT line with 25 mm2 Aerial Bunched Cable i/c. installation of 7x16 KVA, Sub-Stations for electrification of 7(seven) nos. of un-electrified habitations having population below 100 at Ataram para habitation of Kakracherra VC, Jugendra para habitation of Haludia VC, Hadukalak para habitation of Kakracherra V.C., Bangaisi para habitation of Haludia VC, Rabi para habitation of Kakracherra VC, Biswamani para habitation of Nunacherra VC and Samprai Bahadur para habitation of Nunacherra VC located under the jurisdiction of Nunacherra Census Village of Mungiakami R.D. Block covered by ESD-Mungiakami. (Revised Estimate)

    Ch to: Deposit work with the TTAADC.

    SCHEDULE OF WORK

    Sl NoDescription of ItemsQty.UnitRate/Unit ()Amount ()

    A.Erection of the following items.

    1Erection of 9.0 mtr. Long Steel Tubular Poles (Designation 410: SP-54) conforming to ISS: 2713 (P-I & II)-1980 with base plate direct in earth including excavation, refilling and ramming etc. as required (1/6th length of the pole to be embedded in earth) and grouting with CC of ratio 1:2:4 (1 cement : 2 river sand : 4 jhama brick aggregate of 20 mm. nominal size) ilc supply of cement, sand and brick aggregate complete with excavation, refilling of earth, ramming alongwith centering and shuttering as required (@ 0.273 Cum per Steel Tubular Pole as per TSECL specification ) etc. and applying paints with ready mixed primer (two or more coats) and aluminium paint of approved quality to give an even shade etc. as required as per direction of the Engineer-in-Charge.431No

    2Erection of 8 mtr. long Steel Tubular Poles (Designation 410: SP-54) conforming to ISS: 2713 (P-I & II)-1980 with base plate direct in earth including excavation, refilling and ramming etc. as required (1/6th length of the pole to be embedded in earth) and grouting with CC of ratio 1:2:4 (1 cement : 2 river sand : 4 jhama brick aggregate of 20 mm. nominal size) ilc supply of cement, sand and brick aggregate complete with excavation, refilling of earth, ramming alongwith centering and shuttering as required (@ 0.273 Cum per Steel Tubular Pole as per TSECL specification ) etc. and applying paints with ready mixed primer (two or more coats) and aluminium paint of approved quality to give an even shade etc. as required as per direction of the Engineer-in-Charge.381No

    3Erection of painted Stay Set complete direct in earth with 16 mm. dia. 1.8 mtr. long painted stay rod, anchor plate of size 300 X 300 X 8 mm. thick, turn buckle of length 356 mm. with 300 mm. long threaded adjustable 16 mm. dia. MS rod , thimble, guy insulator as per IS specification, hot dip (heavy duty) galvanized stay stranded wire of size 7/2.5 mm. fastened with stay clamps as required. ( including supply of MS clamp & Nuts & Bolts as reqd) and Grouting of stay set with CC of ratio 1 :2:4 (1 cement: 2 river sand: 4 jhama brick aggregate of 20 mm. nominal size) ilc supply of cement, sand and brick aggregate complete with excavation, refilling of earth, ramming alongwith centering and shuttering as required ( @ 0.119 Cum per stay set as per TSECL Specification)650Set

    4Erection of 2.8 mtr. long made of 75 X 40 X 40 X 6 mm. MS Channel for Sub-Station GOS, DOF bracket as per direction of the Engineer-in-Charge.28No

    5Erection of .3 mtr. long S/P top bracket made of 75 X 40 X 40 X 6 mm. MS Channel as per direction of the Engineer-in-Charge.127No

    6Erection of 1.2 mtr. long S/P bottom bracket made of 75 X 40 X 40 X 6 mm. MS Channel as per direction of the Engineer-in-Charge.127No

    7Erection of 2.2 mtr. long D/P bracket made of 75 X 40 X 40 X 6 mm. MS Channel as per direction of the Engineer-in-Charge.136No

    8Erection of 2.8 mtr long made of 100x50x50x6 mm. MS Channel for transformer base as per direction of the Engineer-in-Charge.21Nos

    9Erection of 0.8 mtr long made of 100x50x50x6 mm. MS Channel for transformer base as per direction of the Engineer-in-Charge.14Nos

    10Erection of 2.8 mtr long made of 65x65x6 mm. MS Angle for cross arm for GOS handle bracket as per direction of the Engineer-in-Charge.7No

    11Erection of 3.2 mtr. long Sub-Station guard bracket by 65x65x6 mm MS Angle as per direction of the Engineer-in-Charge.7Nos

    12Erection of 1.5 mtr. long single pole guard bracket by 65x65x6 mm MS Angle as per direction of the Engineer-in-Charge.127Nos

    13Erection of 2.5 mtr. long double pole guard bracket by 65x65x6 mm MS Angle as per direction of the Engineer-in-Charge.136Nos

    14Erection of Polimerik Disc Insulator Ball and Socket type for 11 KV system (EMS-45 KN) conforming to ISS:731/1971 in angle and dead end locations including tension fittings of EMS-45 KN to accommodate the relevant ACSR conductor size along with nuts and bolts, washer etc. as required in complete as per direction of the Engineer-in-Charge.768No

    15Erection of Polimerik Pin Insulator including G.I Pin for 11 KV system with mechanical strength of 10 KN conforming to ISS:731/1971 with hot dip galvanized M.S forged 11 KV G.I pin alongwith galvanized hexagonal nuts, G.I flat washer and G.I spring washer conforming to ISS: 2486(P-II)/1974 etc. as required in complete as per direction of the Engineer-in-Charge.786No

    16Erection of 11 KV, 200 Amps. 1-phase GO Switch complete i/c fixing horizontally & vertically operating pipe & operating handle with nuts & bolts etc. as required.14Set

    17Erection of 11 KV 1-phase DO Fuse complete with nuts & bolts etc. as required.7Set

    18Erection of 9 KV, 5 KA single pole metal oxide gapless type Lightening Arrestor i/c. necessary connection complete as per direction of the Engineer-in Charge.77Set

    19Laying, hoisting & stringing of ACSR (6/1/2.59 mm) Weasel Conductor including binding, jumpering, etc. as reqduired & as per direction of the Engineer-in-Charge.52Km

    20Laying, hoisting & stringing of 8 SWG G.I. wire as per ISS : 280/1978 amended latest with heavy coating as per ISS : 4826 I 1968 of tensile strength 55 to 95 Kgf/mm i/c fastening with cross arm & metallic parts for earth continuity wire and metal parts to earth electrode as per direction of the Engineer-in-Charge.33.5Km

    21Laying, hoisting and stringing of 1.1 KV Class, LT , Aerial Bunched Cable of size 1CX25+1CX16+1X25 sqmm for LT Overhead line on existing pole as required as per direction of the Engineer-in-Charge.15Ckm

    22Erection and fitting fixing of LT Insulation Piercing Connectors (IPC) for making Tee/Tap-off/Service connectors to an ABC/Bare Overhead Line suitable for LT AB Cable 25 sq mm to 95 sq mm496Nos

    23Erection & fitting fixing of Suspension Assembly Comprising of 'suspension bracket', movable connecting links, galvanised suspension clamp, bracket clamp, nuts & bolts (Suitable for 25-95 sq mm bare messenger wire) on existing pole with the help of galvanised clamp (made of 2nos, 50X6mm Flat) and nuts & bolts including supply of galvanised clamp, nuts & bolts etc. for LT AB Cable.304Nos

    24Erection & fitting fixing of Dead End/Anchoring Assembly comprising of tension bracket wedge type, galvanised tension clamp, flexible stain steel rope for fixing of tension clamp (Suitable for 25-95 sq mm bare messenger wire) on existing pole with the help of galvanised Clamp (made of 2nos, 50X6mm Flat) and nuts & bolts including supply of galvanised clamp, nuts & bolts etc. (For LT AB Cable)420Nos

    25Erection & Fitting Fixing of galvanised steel made 'Eye Hook' with hot dip galvanised nuts & bolts.(Suitable for all size cable) for LT AB Cable.730Nos

    26Erection & Commissioning of pole mounted 1-phase, 200 Amps all weather proof FRP multi connection LT SERVICE MAIN DISTRIBUTION BOXES124Nos

    27Erection of Pre-Insulated Jointing sleeve for 25 sqmm LT AB Cable.156Nos

    28Erection of Pre-Insulated Bi-metallic Socket for 25 sqmm LT AB Cable.156Nos

    29Supply and erection of Earthing Set as per ISS : 3043 of 1966 and with latest amendment if any, 2.5 mtr long G.I. pipe (ISI marked) of 40 mm diameter with suitable holes on pipe circumference including a pair of clamps (made of 50 X 6 mm M.S. flat), galvanized nuts & bolts along with alternate layers of salt & charcoal including supply of 4.0 mtr long, 12mm dia PVC pipe for each earthing set etc. as required and as per direction of the Engineer-in-Charge.184Set

    30Erection & commissioning of 16 KVA, 50 HZ, outdoor type 11/0.433 KV AC Distribution Transformer on Sub-Station Channel base at a height of 2440 mm (approx) above Ground Level with required connection by ACSR from 11 KV line to Transformer via GOS & DOF fastened straining screw, clamp, nuts & bolts as required as per Technical Specification.7Nos

    31Erection of PVC Cable 70 sqmm i/c fitting fixing 100 Ampere cut out on wooden plank making connection from Transformer LT side to overhead LT Line via fuse unit of unarmored PVC cable 1100-V grade conforming to ISS: 1554 (P-I) /1988 of the following sizes and the cables shall be properly crimped by bi-metallic lugs at contact areas as per direction of the Engineer-in-Charge. ( Wooden Plank 500X300X25 mm will be supplied by the Contractor)7Job

    32Providing BPL Service Connection along with erection and supply of 1.1KV PVC 2.5 Sq. mm., 1 Core or two 1Core Cable (Service Wire), GI Wire 10SWG (for Service Connection), GI Wire 8SWG (for Coil Earthing), Real Insulator, Single Phase Energy Meter, 5-20 Amps (To be Supplied by TSECL), Cut out 16 Amps., 16 Amps ICDP Main Switch/ Main Switch make Bajaj, Crompton and Havells, 8x12 Wooden Board, 4x4 Wooden Board, 5 Amps. Switch, 5 Amps. Angle Holder, Retrofit LED Lamp 9 Watts, Wooden batton 1/PVC Casing (8 Mtr Lump sum), Wooden Plank etc. as required 10 (1 Mtr Lump sum), 1.5 sq. mm. PVC Wire (Single Core 650 Volt grade) with link clip & nails etc. as required, Coil earthing including making of pit, refilling, fabrication, erection, connection etc. as required with supply of salt, charcoal & PVC pipe 3 mtr. long to cover earth wire above ground level excluding supply of G.I. Wire as per direction of the Engineer-in-Charge.124No

    33Providing of Sub-Station protective fencing of size 2X3 mtr. And height 1.5 mtr. as per engineer requirement by 65X65X6 mm MS Angle post of height 2 mtr. Horizontal bar 2X3 mtr and 2X2 mtr. And top angle posts by 50X50X6 mm MS angle and two part MS Grill door of size 1.2X1.4 mtr with locking arrangement i/c necessary grouting and painted aluminium paint over red oxide priming of approved quality as required as per Technical Specification.7Job

    34Cutting, clearing & disposal of jungle/tree of any girth from 3(three) meter either side of HT/LT line of providing required vertical and horizontal clearance as per provision of I.E. Rule.62KM

    BSupply of the following materials

    1Fabricated bracket clamps 50x6 mm MS Flat (assorted sizes) i/c. holes as per requirement by Drill Machine.1051Nos

    2Stay Clamps 50x6 mm MS Flat i/c Nuts & Bolts etc as required.650Pair

    370/95 sq. mm. Bi-metallic Lugs70Nos

    4Nuts & Bolts (Assorted Size)600Kg

    5Polythin Pipe 1/2" dia. for Pipe Earthing736mtr

    6Reel Insulator (4-10 sqmm)2500Nos

    7Galvanized Steel made Eye Hook with hot dip galvanized nuts & bolts for LT AB Cable730Nos

    CCarrying of the following steel tubular Pole from Electrical Store Sub-Division, A.D. Nagar, Agartala to work site within the administrative jurisdiction of Mungiakami R.D. Block by mechanical transport, hand cart & manual labour etc as required i/c. loading, unloading & stacking (i/c. river / cherra crossing if required) etc. as per direction of the Engineer-in-Charge.

    19 mtr long steel tubular pole431nos

    28 mtr long Steel tubular pole381nos

    DCarrying of the Line Materials and Transformer etc from Electrical Store Sub-Division, AD Nagar, Agartala to work site via. ESD-Mungiakami storeyard within the administrative jurisdiction of Mungiakami R.D. Block by mechanical transport, hand cart & manual labour etc. as required i/c. loading, unloading, stacking etc as required.

    1Line Materials, Transformer etc.15Trips

    ENumbering of Pole/DT with black Japper paint after applying priming coats by red oxide primer followed by a painting 2 or more coats with synthetic enamel paint (Yellow Colour) of approved quality within a area of 8"X14" on pole /DT as required as per direction of the Engineer-in-Charge.

    a8 mtr Long Steel Tubular Pole381Nos

    b16 KVA, 1-phase 11/0.433 KV Distribution Transformer7Nos

    Total =

    ManagerDeputy General Manager

    ESD-MungiakamiElectrical Division, Teliamura

    TSECL, Khowai DistrictTSECL, Khowai District

    &LSignature of Bidder/Condractor&CPage No &P of 6