Salem Saleh Balobaid ID: 213203284 Deakin University PRINCIPLES OF THERMODYNAMICS SEM314 (2013) LAB REPORT Due Date 27 th SEPT 2013

Upload: others

Post on 21-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Salem Saleh Balobaid

ID: 213203284

Deakin University

PRINCIPLES OF THERMODYNAMICS

SEM314

(2013)

LAB REPORT

Due Date

27th SEPT 2013

Experiment 1

Determination of heat capacity ratio

Objective

To determine the heat capacity ratio ⁄ for air near standard temperature and

pressure

Method

The experiment involves a two-step process. In the first step a pressurised vessel is

depressurised briefly by opening then closing a large bore valve very quickly. The gas inside

the vessel expands from to - a process that can be assumed as adiabatic and reversible

( ⁄⁄ is constant)

The volume of the gas inside the vessel is then allowed to return thermal equilibrium,

attaining a final pressure . The second step is therefore a constant volume process (P/T is

constant)

Theory

For a perfect gas,

Where = molar heat capacity at constant pressure, and

= molar heat capacity at constant volume.

For a real gas a relationship may be defined between the heat capacities, which are

dependent on the equation of state, although it is more complex than that for a perfect gas.

The heat capacity ratio may then be determined experimentally using a two-step process:

1. An adiabatic reversible expansion from the initial pressure P, to an intermediate

pressure Pi

{Ps, Volls, Ts} {Pi, Volli, Ti}

2. A return of the temperature to its original value Ts at constant volume Volli

For a reversible adiabatic expansion

From the First Law of Thermodynamics,

Therefore during the expansion process

or

At constant volume the heat capacity relates the change in temperature to the change in

internal energy

Substituting in to equation x,

Substituting in the ideal gas law and then integrating gives

(

) (

)

Now, for an ideal gas

Therefore,

(

)

Rearranging and substituting in from equation x,

During the return of the temperature to the starting value,

Thus

Rearranging gives the relationship in its required form:

Experimental Data

Observations 1 2 3

Atmospheric Pressure (absolute), Patm (N/m2)

Starting Pressure (measured), Ps(N/m2)

Starting Pressure (absolute), Pabss(N/m2)

Intermediate Pressure (measured), Pi (N/m2)

Intermediate Pressure (measured), Pabsi

(N/m2)

Final Pressure (measured), Pf (N/m2)

Final Pressure (absolute), Pabsf (N/m2)

Result and Calculation

For observation 1:

Following same calculation procedure,

for observation 2,

for observation 3,

Conclusions

In this experiment, the heat capacity ration or adiabatic index of air have been measured

three times at near standard temperature and pressure. The result obtained was quiet close

to the value expected. There were some errors came out after calculation which shows slight

difference from the actual value. This experiment allows us to understand the adiabatic

process and the steps to determine the heat capacity ratio of air.

Questions and Answers

1. Why can the initial expansion process be considered adiabatic?

An adiabatic process is a process where no thermal energy is transferred from or to

the system ( . It is possible is the system is completely isolated or is the time

taken to undergo change in the system is very negligible. Rapid change is the system

does not allow any heat to be transferred from or to the system thus creates adiabatic

process. In this experiment the pressure released from the initial state to intermediate

state so quickly that there were no chance of heat to be escaped or added from the

surroundings.

2. How well does the result obtained compare to the expected result? Give possible

reason for any difference.

The heat capacity ratio or adiabatic index of air at standard pressure and

temperature of dry air was found three different values (1.383, 1.457, and 1.451) from

three observations. The actual value of heat capacity ratio of dry air at 20oC is 1.40

(source: Wikipedia). The average value from this experiment comes up with 1.43. This

variation is mainly due to inaccuracy in measuring pressure from the apparatus.

Pressure readings were taken manually hence deviation from accuracy generated. It can

be improved by taking all those pressure values more precisely by using data logger

during the experiment.

Experiment: 2

Simple Refrigeration cycle

Objective

To determine the average thermal output and refrigeration capacity of a simple compression

refrigeration cycle;

Theory

An ideal refrigeration cycle essentially consist of (i) an isentropic compression process

(compressor) (ii) heat rejection at constant pressure (isobaric) using condenser (iii) an

isenthalpic expansion (throttling) and (iv) heat gain at constant pressure (evaporator). Figure

1 and 2 shows the experimental rig and thermodynamics cycle.

Figure 1 Experimental Setup

1 Evaporator 6 High pressure manometer

2 Condenser 7 High pressure switch

3 Sight glass 8 Main switch

4 Low pressure manometer 9 Compressor service valve

5 Thermoelectric expansion valve 10 Compressor

Figure 2 Schematic representation of Thermodynamic process

Another diagram frequently used in the analysis of vapour compression refrigeration cycles

is P-h diagram as shown in figure 3. In industry, P-h diagram is commonly used as

enthalpies at different states can be directly obtained from P-h chart

Figure 3 Schematic representation of P-h diagram

Process 1-2: Isentropic compression (work is done on the system, compressor)

In an reversible isentropic compression (without any heat loss) the work is done by the

compressor can be calculated as

(1)

Figure 4a Isentropic process

Process 2-3: Isobaric heat rejection (Condenser)

Heat is rejected to the atmosphere

(2)

Figure 4b Isobaric Condensation

Process3-4: Isenthalpic expansion (Expansion valve or throttling process)

Isenthalpic mean that neither thermal energy nor work is exchanged with the environment.

Therefore the change of state appears as a vertical line from 3-4 in the log P-h diagram.

(3)

Figure 4c Isenthalpic expansion

Process 4-1: Isobaric evaporation (Evaporator coil)

Heat is gained by the evaporator

(4)

Figure 4c Isobaric evaporation

Determining the average thermal output and refrigeration capacity

This experiment is designed to determine the average refrigeration capacity and the average

thermal output of the system. Since the system does not have a flow meter for refrigerant,

the experiment uses a caloric evaluation by means of the change in temperature of the water

in both tanks.

The approximate refrigerant mass flow will also be determined from the measured capacities.

When determining the refrigerant mass flow, the thermodynamic cycle is assumed to be

ideal.

Following equations can be used to calculate the energy and rate of energy transfer

(5)

(6)

Measurements

Time (min) P1 in bar P2 in bar Twc Twh

0 6.8 6.5 20.5 25

2 1 7.25 18 26

4 1.0 7.0 18.2 24.3

6 1.1 7.75 15 28

8 1.2 8.0 13.5 29.7

10 1.2 8.5 13 31

12 1.2 9.0 12 31

14 1.3 9.5 10 36

16 1.3 10.0 9 39

18 1.4 10.5 7 40

20 1.5 11.25 5 41

The averaged values between an experiment duration of 4 to 8 minutes is 1.1(~1 bar) and

7.5 bars.

Calculation

Determining the average thermal output and refrigeration capacity

The specific thermal capacity of water is used to determine the average power

introduced or extracted between an experiment duration of 4-8 minutes. Using the

thermal capacity, the mass and the temperature change it is possible to determine

the energy change of the water, which corresponds to the energy of ET 101 if

considered without loss. The energy change per unit of time is then equal to the

capacity of the system.

A sample calculation for refrigeration capacity

For thermal capacity:

The procedure to calculate thermal capacity is similar,

Determining the refrigerant mass flow

To determine the refrigerant mass flow, we have to use the log p-h diagram for help. In

addition, we need either the previously calculated refrigeration capacity or thermal output. In

this example we have used the refrigeration capacity to determine the mass flow. This can

be determined using the log p-h diagram as follows

h4 corresponds to the specific enthalpy of the refrigerant at the evaporator inlet and h1 at the evaporator outlet. These can be determined from the log p-h diagram.

Determining Coefficient of Performance (COP) of the refrigeration system

The coefficient of performance (COP) is a term which is used to quantify the performance of

refrigeration cycle. It is the ratio of cooling effect over the work done on the system. The

work done on the system can be determined from the difference in heat rejected to the

atmosphere and heat gained in the evaporator

Conclusion

In this experiment a simple vapour compression refrigeration cycle has been studied and

different types of process associated with it have also been discussed. The refrigeration

effect or cooling effect and thermal capacity is calculated using the formula. Furthermore, the

performance of the refrigeration system was determined by calculating COP and the mass

flow rate is also measured from the P-h diagram of the refrigerant. The COP of the system

was found as 6.714 which is greater than 1 according to our expectation.

Question and Answer

1. In general which is greater: the capacity of the condenser or the capacity of the

evaporator? Justify your answer. (hint: refer to p-h diagram of a refrigeration cycle)

The capacity of the condenser is always greater than the capacity of evaporator. When

the refrigerant is compressed, it gains some heat which comes out from the mechanical

work done on it by the compressor. After being compressed it is then cooled to the

temperature from which it starts expanding and then creating cooling effect by taking

away heat from evaporator. Therefore in the condenser it has to remove heat gained in

the evaporator as well as heat gained from the mechanical work done upon it in

compressor.

Experiment: 3

Simple heat pump

Objective

To determine the average thermal output and heating capacity of a simple heat pump;

Theory

A heat pump is, in its terms of its function, identical to a cooling system. The basis for the

operation of heat pump is a cyclic thermodynamic process. In a cyclic thermodynamic

process a working medium flows through a set sequence of changes of state. The changes

of state are repeated cyclically, the working medium

thus repeatedly returns to its initial state. The term

change of state refers to compression (volume

reduction) involves the absorption of mechanical

energy, expansion (volume increase) involves the

discharge of mechanical energy, heating involves the

absorption of thermal energy (heat) and cooling

involves the discharge of thermal energy.

Figure 1 Heat pump cyclic process

Figure 2 Schematic representation of Thermodynamic process

Another diagram frequently used in the analysis of heat pump cycles is P-h diagram as

shown in figure 3. In industry, P-h diagram is commonly used as enthalpies at different

states can be directly obtained from P-h chart

Figure 3 Schematic representation of P-h diagram

Process 1-2: Isentropic compression (work is done on the system, compressor)

In an reversible isentropic compression (without any heat loss) the work is done by the

compressor can be calculated as

(1)

Figure 4a Isentropic process

Process 2-3: Isobaric heat rejection (Condenser)

Heat is rejected to the atmosphere

(2)

Figure 4b Isobaric Condensation

Process3-4: Isenthalpic expansion (Expansion valve or throttling process)

Isenthalpic mean that neither thermal energy nor work is exchanged with the environment.

Therefore the change of state appears as a vertical line from 3-4 in the log P-h diagram.

(3)

Figure 4c Isenthalpic expansion

Process 4-1: Isobaric evaporation (Evaporator coil)

Heat is gained by the evaporator

(4)

Figure 4c Isobaric evaporation

Determining the Output coefficient (or

coefficient of performance, COP)

In order to be able to make a judgement as to the effectiveness of a heat pump, an output

coefficient is used. This corresponds to the efficiency of thermal power plants and is

determined from the relationship of benefit to work. The benefit comprises the heat flow

discharged, the work the power input Pin or the mechanical energy expended.

Contrary to the efficiency of other machines and systems, the output coefficient is in general

larger than 1. The output coefficient can therefore not be termed efficiency.

The quantities of energy converted in the cyclic process can be taken directly from the p-h

diagram as differences in the enthalpies. Thus the output coefficient for the ideal process

can be derived in a very straight forward manner

(5)

Obviously this equation goes for an ideal cycle but in actual case the process slightly differ.

For the real process with suction gas superheating and liquid supercooling the following

applies

(6)

The output coefficient can also be calculated from the actual amount of heat drawn off from

the condenser using the water circuit and the actual power input by the compressor.

Here all the losses due to radiation, heat conduction friction, etc. are also taken into account.

The benefit, that is the heat flow, is calculated from the flow of the water, the temperature

difference between the inlet and the outlet, and the specific heat capacity of water.

(7)

The lower the temperature differences between the absorption side and the suction side, the

larger the output coefficient.

Measurements

Time (min) 1 2 3 4 5

T1 in oC 12 18.5 12.1 11.4 11.7

T2 in oC 66.8 66 66.4 66.8 67.1

T3 in oC 37.6 37.4 37.6 38.2 37.7

T4 in oC 6.4 6.4 6.5 6.5 6.5

T5 in oC 33.6 33.4 33.7 33.8 33.7

T6 in oC 52.3 52.2 52.4 52.3 52.4

F1 in ltr/min 20.4 20.44 18.9 19.5 19.3

F2 in ltr/hr 20 20 20 20 20

Pel in W 213 213 213 213 213

P1/4 in bar 3.43 3.44 3.38 3.38 3.44

P2/3 in bar 14.78 14.92 14.64 14.76 14.86

h1 in kJ/kg 402.7 402.3 402.4 402.8 402.3

h2 in kJ/kg 442.4 441.6 442.0 447.8 441.8

h3 in kJ/kg 254 253.7 254 254.1 254

h4 in kJ/kg 254 253.7 254 254.1 254

Calculation

Determining the ideal and real output coefficient

Here the output coefficient is determined from the differences in the enthalpies on the log p-h

diagram. To do this the cyclic process must be plotted on the log p-h diagram.

The pressures read from observation 1 at the inlet and outlet of the compressor are now

plotted on the p-h diagram

P1/4=3.43+1 bar abs. =4.43 bar abs

P2/3=14.78+1 bar abs. =15.78 bar abs

Enthalpy values

h1 = 405.8 kJ/kg

h2 = 432 kJ/kg

h3 = h4= 217.2 kJ/kg

Compressor compression ratio

The output coefficient for the ideal cyclic process can now be calculated using the

differences in the enthalpies.

To determine the output coefficient for the real cyclic process, the cyclic process is plotted

on the p-h diagram taking the temperatures into account.

T1 = 12 oC

T2 = 66 oC

T3 = 37.6 oC

T4 = 6.4 oC

Enthalpy values:

h1* = 402.7 kJ/kg

h2* = 442.4 kJ/kg

h3* = h4

*= 254 kJ/kg

The output coefficient for the real cyclic process then has the following value

Experimental Determination of the Actual Output Coefficient

The actual output coefficient is calculated from the amount of heat extracted from the

condenser using the hot water circuit and the power input at the compressor. Here all the

losses due to radiation, heat conduction, friction, etc. are also taken into account.

The benefit, that is the heat flow, is calculated from the water flow rate, the temperature

difference between the inlet and outlet and the specific heat capacity of the water (cp =

4.19kJ/kg K).

= Flow rate in m3/s =

m3/s =5.67X10-6 m3/s

= Density in Kg/m3 = 996 Kg/m3

= Compressor output in kW = 0.213 kW

Conclusion

In this experiment a heat pump system has been thoroughly studied and the output

coefficient measured with different method. The theoretical performance numbers obtained

from the enthalpies are always slightly higher than those determined from the measured

output. This is because of the thermal output power dissipated through the compressor

housing. This heat dissipation results in removal of heat from the hot gas before the

compressor outlet. The actual output coefficient is considerably lower than the ideal/real

output coefficient due to heat losses resulting from radiation and conduction.

The output coefficient for a heat pump is dependent on the temperature gradients between

the hot medium on the hot side and the heat source on the cold side. The higher this

temperature difference, the lower the output coefficient. This effect is comparable with the

behaviour of a normal pump: the higher the pump head, the lower the capacity.

Experiment: 4

Methods of pressure and temperature measurement

Objective

To familiarize with different pressure and temperature measurement

Theory

There are various method available to measure pressure and temperature In this experiment

pressure measurement are to be carried out on a U-tube manometer, an inclined U-tube

manometer and a Bourdon gauge for positive and negative applied pressures. Temperature

measurements are to carried out using a thermocouple, resistance thermometer and a

thermistor (NTC). The temperature of water undergoing a phase change will be measure

using these measurement device mentioned above and compared. The experimental

devices are shown below:

Figure 1 Pressure measurement setup

Figure 2 Temperature measurement setup

Temperature measurement procedures:

Temperature measurement using liquid thermometers

In a glass thermometer, the relative expansion of a liquid compared to the contents of the

bulb is measured. The majority of the liquid is in a spherical or cylindrical-shaped bulb that

forms the thermometer’s actual sensing element (1). The bulb opens into the long, thin glass

capillary tube (2). Practically all liquids can be used in thermometers. Here a differentiation is

made between wetting (e.g. organic) and non-wetting liquids (e.g. mercury). Wetting liquids

cause additional errors as the temperature drops. An organic liquid must be coloured so that

it is visible in the capillary tube and the reading of the temperature made easier. Liquid

containers for mercury are larger than for other liquids due to the smaller coefficient of

expansion. The volume of the medium in liquid thermometers changes in accordance with

the following law:

Vt Volume at Temperature t

V0 Volume at 0°C

Coefficient of linear expansion in 1/K

Difference in temperature from °C to K

Temperature measurement using bimetallic thermometers

Bimetallic thermometers exploit the differential expansion of two different materials to

indicate the temperature. Two or more layers of different materials are rolled together.

During this process, different shapes can be manufactured depending on the application.

One end of the sensor is firmly anchored, the other is coupled to a transmission gear or

directly to a display device.

Contrary to rod type thermometers, bimetallic sensors have only a low capacity to perform

work. They are thus practically limited to usage for indicating equipment, and are less

suitable for remote indication. Over wide measuring ranges, the nonlinear relationship of the

specific deflection to temperature becomes detrimentally apparent. Due to the relatively

large surface areas, bimetallic thermometers that are exposed to the surrounding medium

without heavy protective housings, react comparatively quickly.

The length of the individual metals changes inaccordance with

the following formula

Vt Volume at Temperature t

V0 Volume at 0°C

Coefficient of linear expansion in 1/K

Difference in temperature from °C to K

Figure 3 Principle of

operation of a bimetallic

thermometer

Temperature measurements using gas thermometers

The thermodynamic temperature scale forms the theoretical basis of thermometry. As the

scale is very involved to reproduce, a number of fixed points are defined for use in the

engineering measurement field, these are considerably easier to depict. The gas

thermometer is one of the most important devices used to realise the thermodynamic

temperature scale over a very wide temperature range almost down to absolute zero.

Using this method, the change in the pressure or volume of a gas is measured as a function

of temperature in accordance with the ideal gas equation:

Here the mass m and the gas constant R are constant. All approximately ideal gases can be

used (helium, nitrogen, argon). The lowest measurable temperature is just above the critical

point of the respective charge gas (nitrogen -147°C).

The following relationship exists between the gas states at two different temperatures:

p Pressure in N/mm2

V Volume in m3

T Temperature in K

Temperature measurement using temperature measuring strips

Alongside the classic temperature measuring equipment described, which can be classified

in the mechanical contact thermometer category, there is a series of further methods that are

based on totally different physical or chemical effects. They mostly have serious

disadvantages, which is why they have not become commonly adopted in practice, but are

only used in very specific applications. One type is temperature indicating films that change

colour from light to dark at a specific temperature as a result of a chemical reaction. A heat

sensitive layer is vapour deposited on small self-adhesive pieces of plastic. The colour

change is irreversible. The error on the indication is between 1% and 2% of the printed

value. These films are suitable for a measuring range from 29°C to 290°C.

Temperature measurement using resistor thermometers

The electrical resistance of the majority of materials varies significantly with temperature.

This effect, often regarded as a problem in other areas, is exploited here for a temperature

measuring principle. The cause of this temperature dependency in metallic conductors is the

unattached bonding electrons in the metal lattice: at the temperature drops, the electrical

resistance also drops. In semiconductors there is normally a lack of conduction electrons. It

only through the addition of thermal energy (temperature increase) that electrons for the

conduction of current become free: the electrical resistance drops with increasing

temperature.

Contrary to thermocouples, using which only temperature differences compared to a known

temperature can be measured, the absolute temperature can be determined using resistive

sensor elements. Resistive sensor elements require an auxiliary power supply that is often

not used in thermocouple circuits. The measuring range of resistive sensor elements is

limited, particularly at high temperatures, the linearity of the temperature characteristic is in

some circumstances poor, depending on the material used for the sensor.

The dependency of the resistance of metallic conductors on the temperature can be very

precisely described using a cubic equation. For normal accuracy requirements, it is usual to

limit the calculation to the use of quadratic or even linear functions:

Or

R, R0 and Rt[ ] are resistors in their initial state at 0°C and at t [°C]. [1/K] is the linear

temperature coefficient of the resistor. As the linear equation does not apply exactly for the

majority of materials, that is is not constant, a mean relative change in resistance per

degree between 0°C and 100°C is defined:

R100 and R0 are measured at the boiling and freezing point of water

Metallic substances with good electrical conductivity are used for the resistor materials, such

as

Platinum

Nickel

Copper

In the selection process, the nominal resistance at t0 = 0°C is defined as being R0 = 100 .

Nickel and platinum are used exclusively for temperature measurement.

Temperature measurement using thermistors

These special resistive elements are manufactured from semiconductor materials. There are

two different types,

• NTC thermistors

• PTC thermistors.

Thermistors or NTC (negative temperature coefficient) resistors are conductive materials

that conduct current more effectively at high temperatures than at low temperatures. This

means that as the temperature increases, their electrical resistance falls. They have a

negative temperature coefficient. The opposite of thermistors are posistors (PTC resistors),

which conduct better at lower temperatures and have a positive temperature coefficient.

All semiconductor elements are ideal insulators at very low temperatures. Their increase in

conductivity is described approximately by the following law:

(

) ⇔

(

)

RT Resistance in at absolute temperature T

RN Resistance in at nominal temperature

T Operating temperature

TN Nominal temperature, normaly 25°C (298,16 K)

b Material constant 2000 to 6000 K

The material constant b and the nominal resistance are specified by the manufacturer in the

data sheet.

The normal operating range is between -80°C and +250°C.

Temperature measurement using thermocouples

The technical exploitation of the thermoelectric effect for temperature measurement began

with Seebeck and Peltier. The development and testing of new materials for thermocouples

is still not complete.

In general, any combination of two conductor materials can be utilised to manufacture a

thermocouple.

The sensitivity of the thermocouple is the algebraic sum of the thermal electromotive forces

of the two conductors. The sensitivity is very high if the thermal electromotive forces are very

different. If two different materials are welded into a thermocouple and this joint is heated, an

electromotive force (e.m.f.) is generated. With the aid of the e.m.f. the temperature becomes

a measured parameter.

The following thermocouples are standardised in terms of their e.m.f. and their tolerance:

Iron constantan (Fe-CuNi) code letter "J" up to 750°C

Copper constantan (Cu-CuNi) code letter "T" up to 350°C

Nickel-chromium nickel (NiCr-Ni) code letter "K" up to 1200°C

Nickel-chromium constantan (NiCr-CuNi) code letter "E" up to 900°C

Nicrosil nisil (NiCrSi-NiSi) code letter "N" up to 1200°C

Platinum-rhodium platinum (Pt10Rh-Pt) code letter "S" up to 1600°C

Platinum-rhodium platinum (Pt13Rh-Pt) code letter "R" up to 1600°C

Platinum-rhodium platinum (Pt30Rh-Pt6Rh) code letter "B" up to 1700°C

Experimental data

Experiment 1: Positive pressure measurement with U-tube manometer and Bourdon

tube manometer

Consecutive

no.

Positive

/negative

pressure

applied with

the syringe

Tube manometer: U-tube manometer Inclined manometer

Bourdon

tube

manometer

for :

Positive

pressure

Negative

pressure

In mbar

Reading Calculation

Left

branch:

h1

In mm WC

Right

branch: h2

In mm WC

Inclined

tube

mano-

meter:

h2corr

In mm WC

or

In mm WC

or

In mbar

a No pressure

- -46 -46 0 0 0

b With pressure

5 -160 56 216 20.91 22

C =b-a

- -114 102 216 20.91 22

Experiement 2: Negative pressure measurement with inclined tube manometer and

Bourdon tube manometer

Consecutive

no.

Positive

/negative

pressure

applied with

the syringe

Tube manometer: U-tube manometer Inclined manometer

Bourdon

tube

manometer

for :

Positive

pressure

Negative

pressure

In mbar

Reading Calculation

Left

branch:

h1

In mm WC

Right

branch: h2

In mm WC

Inclined

tube mano-

meter:

h2corr

In mm

WC

or

In mm WC

or

In mbar

a No pressure

- -53 -53 0 0 0

b With pressure

5 -171 59 -230 -22.27 -22

C =b-a

- -118 112 -230 -22.27 -22

Experiment 3: Testing the Pt100, NTC and thermocouple sensor with the phase

transition temperatures of water

Test: Electronic temperature sensor

0 Ice water

Temperature sensor Quantity Unit Measured Setpoint Variance

Pt100 Temperature 0.2 0 0.2

Resistance Ohm 101.3 100.0 1.3

NTC Temperature Too low 0 -

Resistance Ohm 1300 2614 1314

Thermocouple Temperature -2.6 0 2.6

Voltage Out of range 0 -

100 Boilling water

Temperature sensor Quantity Unit Measured Setpoint Variance

Pt100 Temperature 100.2 100 0.2

Resistance Ohm 139 138.5 0.5

NTC Temperature 71.8 100 28.2

Resistance Ohm 81 84.06 3.06

Thermocouple Temperature 99.8 100 0.2

Voltage 3200 4095 895

Conclusion

This experiment created a thorough understanding of different pressure and temperature

measuring devices and methods. Both of these properties are very important in any process,

especially in thermodynamics. Accuracy of measuring pressure and temperature depends

on well calibration of the instrument. The pressure measurement was found quite well with

different device and method. From the above study of temperature measurement, it is

apparent that among three sensors, with the NTC, the measured values are outside the

measuring range.

Question and Answer

2. If you noticed, two pressure gauges when connected together were always

connected in parallel. Why? What would happen if they are connected in series?

In a pressure gauge the hydrostatic force of the fluid is interpreted into displacement to

get the pressure reading from the gauge. Since this force acts uniformly in all direction

therefore, to get the same reading all the pressure gauges should be connected in

parallel. If the gauges were connected in series, some amount of pressure drop would

have occurred in the first gauge which would create a wrong reading from another.