sakashita underground cosmic ray telescope1975–1977) to study solar modulation of cosmic rays in...
TRANSCRIPT
1
SAKASHITA UNDERGROUND COSMIC
RAY TELESCOPE
Cosmic-Ray Research Section,
Solar-Terrestrial Environment Laboratory,
Nagoya University
Nagoya 464-8601 JAPAN
Sakashita Tunnel
2
I. INTRODUCTION
II. SAKASHITA UNDERGROUND OBSERVATORY
Sakashita Underground Multi-directional
Telescope was planned as one of projects of Japan
program for International Magnetospheric Study (IMS,
1975–1977) to study solar modulation of cosmic rays
in high energy region. For the Telescope Sakashita
Underground Cosmic Ray Observatory, Nagoya
University was constructed in 1976 in a disused railway
tunnel of Japan National Railways (now Central Japan
Railway Co.) at Sakashita-cho, Gifu prefecture, about
100 km north-east of Nagoya. The Underground
Telescope was built, extending detectors with three steps
in 1977 to 1979 to 4 x 15 m2 upper and 3 x 14 m2 lower
finally, and full observations of 10 directional cosmic
ray intensities started in Dec. 1979.
The observatory was constructed in the middle of
a tunnel at Sakashita (35°35’N and 137°32’E in
geographic coorditnates, 334 m above sea level), which
runs 14° westward from the north as shown in Fig. 1.
Topography above the observatory is fairly flat as can
be seen from the vertical cross sections of the soil in
Fig. 2. The vertical depth is estimated at 80 mwe from
the topography and also from a comparison between
cosmic ray fluxes inside and outside the tunnel (Ueno
et al., 1976; Fujii and Jacklyn, 1979).
The detector room is 3.6 x 33 m2 in floor area and
has a cross-section of horseshoe shape as shown in Fig.
3. Inside the room, there constructed two layers, upper
and lower, with iron-frame and plate to lay out detectors.
Thin plastic plate was built along with the coved ceiling
of tunnel to protect detector room from water drop out
of the brick wall. The humidity is kept 70% by seven
300 W dehumidifiers. The seasonal change of the room
temperature is about 1°C from the average 22°C and its
daily variation is about 0.2°C.
Fig.1 Map near Sakashita Observatory
Fig.2 Vertical cross section of the ground
3
III. MULTI-DIRECTIONAL UNDERGROUND TELESCOPE
a. Detectors and their arrangements
The multi-directional telescope consists of two
layers of detectors as shown in Fig. 3. Each of detectors
is composed of plastic scintillators of 1 x 1 m2 in area
and 10 cm in thickness, which is set at the bottom of a
pyramid shaped box of 1.6 mm iron plate and is viewed
by a 5" photomultiplier (Hamamatsu Photonics R877).
These detectors are set respectively on the upper and
lower layers separated by 1.75 m in height without
absorber. Configuration of the detector layout was
designed in considering the maximum availability of
space in the tunnel. Centre of each detector on the lower
layer is placed just right under one of the corners of
each detector on the upper layer. Each detector is called
by the number with initial U or L for the upper or lower
layer, as U1, 02, …, U60 and L1. L2, … , L42.
b. Detectors and the adjustments
Pulses from each photomultiplier are amplified by
about 500 times, and then discriminated from noises at
a fixed voltage of 0.5 V by an amplifier/comparator
installed in each detector box. These signal pulses are
sent to a coincidence circuit board by a coaxial cable
(25 m), and reshaped to uniform pulses (5 volts and
200 nsec) to trigger the coincidence circuits. Fig. 4
shows one of plateau curves of detectors, i.e., the
dependence of counting rate of the detector on high
voltage supplied to the photomultiplier. A plateau is seen
at around 850 to 900 volts with a counting rate of about
350 counts per minute, indicating a clear separation of
cosmic ray signals from background noises. Based on
this character, high voltage of each photomultiplier is
adjusted so that the counting rate of every detector is
nearly equal to 400 counts per minute. These
adjustments are made by inserting a proper resister in
series between the photomultiplier and the high voltage
supply set at 950 volts.
Fig.3 Setting of Telescope in the tunnel. Fig.4 Plateau curve (variation of counting rate with
high volate)
4
c. Directional telescopes and their counting rates
Directional telescopes are composed of selected
2-fold coincidences of signals from upper and lower
layer detectors. The selection of the coincidences is
illustrated in the top view of the telescope in Fig. 5,
where the upper and lower layer detectors are shown
by squares of thin solid and thin broken lines
respectively. Coincidences for the directional telescopes
are indicated by the relative position of the upper layer
detectors (thick solid lines) to one representative lower
detector or detectors. Central viewing directions and
average counting rates of these directional telescopes
are summarized in Table I. Two directional telescopes
V1 and V2 in the Table are a sum of (NE, SE, SW and
WN) and that of (N, E, S and W) respectively. Effective
depth and effective median primary rigidity were
calculated by Fujimoto et al. (1977) from the yield
function of cosmic rays (Murakami et al., 1979) in
considering the geometrical configuration of detectors
and particle’s path length in the rock with a mean density
of 2.5 g/cm3.
Table 1. Viewing directions, effective depths, median rigidities and counting rates for multi-
directional telescopes at Sakashita
Fig.5 Configuration of upper and lower layer detec-
tors showing two-fold coincidences for directional
telescopes.
5
d. Recording system
The output pulses from the coincidence system are
fed into 24 channel recorder. Each channel of the
recorder consists of 12 bits binary counter with 12-bit
gate and 4 digits decimal counter with 4 digits buffer
memory. Each binary counter is designed as a sacling
factor of 1 to 4096 for decimal counter and is set so
that hourly count of the decimal counter becomes about
5000/hour. The accumulated counts in the decimal
counter are transferred to the buffer memory once every
hour and then the counter is cleared up for the next
hour. The contents of the buffer memories as well as
the time code are punched every hour on a paper tape.
The atmospheric pressure and the room temperature are
measured by a digital barograph and thermometers with
V-F converters, and are recorded also on paper tape by
the recorder.
e. Power supplies
In order to avoid interruption of observations due
to AC power line failure, an AC-DC-AC converter
system with a deck of floating batteries (96V, 35AH) is
used for the AC power supply. This system can supply
500 W power to the telescope for 3 hours without AC
power input. High voltage supply and DC power
supplies are highly stabilized against changes of AC
voltage and room temperature. The conventional
stabilized power supplies are used for the coincidence
system and the recording system, as they are not
sensitive to the change of the supply voltage,.
Fig.6 Plateau curves of various telescopes
f. Stability of the telescope
All the instrumental gain drift due to the variations
of the power supply voltage and room temperature are
reflected in the counting rate through slopes of the
plateau curve. Fig. 6 shows the plateau curves for five
representative coincidence components together with
those for total single components of upper and lower
layers. Slopes of the plateaus for coincidence
components are less than 0.2 % counts per 1 volt at
∼950 volts. The change of high voltage due to that of
AC power line voltage has negligible effect to the
counting rate. The main instrumental drift is due to the
variation of room temperature. The room temperature
causes gain changes of the photomultiplier and
amplifier-discriminator system of ∼-0.1 % Gain/°C.
Change of 0.1% gain is equivalent to change of -0.1 V
of high voltage, and the room temperature effect of the
Telescope is estimated to be -0.02 % counts/°C. As the
temperature variation is kept within 0.2°C on daily basis
and 2°C on yearly basis, the instrumental drift of the
coincidence rate is less than -0.004 % in a day and -
0.04 % in a year. The other instrumental drift is due to
the fatigue of the photomultiplier. The local rainfall has
also effect on counting rate by the change of effective
ground mass. As no correction for these effects was
made, the long term drift of about 1 %/year were
observed in the counting rate.
g. Automatic check systems
To check the malfunction of the Telescope and the
long term gain change due to fatigue of photomultiplier,
the automatic check system by a PC records daily means
of single and coincidence counting rates from each
6
detector. This system measure also differential pulse
height distribution of each detector by a built-in 256
channel pulse height analyzer, automatically scanning
all detectors once every day. Some of the data are
checked once every day in Nagoya through a telephone
line to the observatory. This automatic check system
has been operated since the middle of 1980.
IV. REDUCTION OF DATA
The paper tape is collected once a month and the
hourly outputs on paper tape are processed by a
computer system in the Institute, to derive the relative
cosmic ray intensity variation. Hourly counts N’s in the
paper tape are converted into the barometer corrected
relative intensity (Wp) using the Natural Logarithmic
Representation (Wada, 1957) as follows,
WP = 104 x (In N - In N
0 + WL) - β(P-P
0)
in unit of 0.01 %
where N0 is average counting rate divided by the scaling
factor and WL is artificially added to make the values
of Wp around 50.00 (%). P is the atmospheric pressure,
P0 is 980 hPa and β is the barometric pressure effect
coefficient (-0.03 %/hPa for all components).
Hourly values of Wp, daily sum and average as well as
the 1st, 2nd and 3rd harmonics coefficients of the daily
variation of each component are computed and tabulated
on daily basis. In the same table, the residual dispersion
of the cosmic ray intensities for one day after removing
the daily variation (up to 3rd harmonics) is tabulated.
Further, these hourly values of Wp are used to produce
hourly value plot for every solar rotation period using
the X-Y plotter attached to the computer system. Check
of the processed data is made, utilizing the hourly data
table and inspecting visually the plotting diagrams. The
final data are written into a magnetic tape and used as
the input to the data processing for final tabulation and
plotting for the publication at NAGOYA University
Computation Center.
REFERENCES
Fuji, Z., and R. M. Jacklyn
Proc. 16th Coemic Ray Conf. Kyoto 4 336 (1979)
Fujimto, K., K. Murakami, I. Kondo, and K. Nagashitna
Proc. 15th Cosmic kay Conf. Plovdiv 4 321
(1977)
Murakami, K., K. Nagasbima, S. Sagisaka, Y. Mishima,
and A. Inoue
Nuovo Cimento 1-2C 635 (1979)
Sagisaka, S., K. Murakami. A. Inoue, Y. Mishima, and
K. Nagashima
Proc. 16th Int. Cosmic Ray Conf., Kyoto 4 235
(1979)
Ueno, H., K. Fujinroto, Z. Fujii, I. Kondo, and K.
Nagashima
Proc. Cosmic Ray Symp. of High Energy C.R.
Modulation 91, (1976)
Wada M.
J. Sci. Res. Inst. 51, 201 (1957)
7
Appendix 1 EPILOGUE
Cosmic-Ray Research Laboratory, Nagoya Univer-
sity found in 1958 as a research institute with cosmic
ray telescopes, was reorganized with Research Insti-
tute of Atmospherics, Nagoya University to Solar-Ter-
restrial Environment Laboratory (STEL) in June, 1990.
Sakashita multi-directional underground telescope con-
tinued observations by cosmic ray research section of
STEL until closing of observations of about 23 years in
March, 2000.
Appendix 2 FOR USE OF DATA
Hourly value data of SAKASHITA Multi-directional
underground telescope are available from Web Site of
Solar-Terrestrial Environment Laboratory (http://
www.stelab.nagoya-u.ac.jp) via network . One record
of the hourly value files (92 bytes) consist of 24 data of
4 digits each, WP in 0.01% and Pressure in 0.1 hPa,
shown below.
Digit content
1 - 4 Last digit of year + Day of Year
5 – 8 Hour and minute (start time of record)
9 - 12 Upper Single + Lower Single
13-16 none (for monitoring Telescope)
17-20 V1
21-24 V2
25-28 NE
29-32 ES
33-36 SW
37-40 WN
41-44 N
44-48 E
49-52 S
53-56 W
57-60 NN
61-64 SS
65-68 none
69-72 none
73-76 NNN
77-80 SSS
81-84 none
85-88 Pressure
89-92 Z (=N-S)