Safety Manual SH 8384-2 EN Translation of original instructions Edition December 2016 Series 3730 Type 3730-2 Electropneumatic Positioner

Upload: phungtruc

Post on 05-Jun-2018

244 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

Safety Manual

SH 8384-2 EN

Tran

slatio

n of

orig

inal

instr

uctio

ns

Edition December 2016

Series 3730Type 3730-2 Electropneumatic Positioner

Page 2: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

2 SH 8384-2 EN

Definition of signal words

Hazardous situations which, if not avoided, will result in death or serious injury

Hazardous situations which, if not avoided, could result in death or serious injury

Property damage message or malfunction

Additional information

Recommended action

DANGER!

WARNING!

NOTICE!

Note

Tip

The mounting and operating instructions for all supplied devices are included in the delivery. The latest versions of the documents are available on our website at www.samson.de > Product documentation. You can enter the document number or type number in the [Find:] field to look for a document.

Page 3: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

SH 8384-2 EN 3

Purpose of this manualThe Safety Manual SH 8384-2 contains information relevant for the use of the Type 3730-2 Positioner in safety-instrumented systems according to IEC 61508 and IEC 61511. The safety manual is intended for planners, constructors, and operators of safety-instrumented systems.

Risk of malfunction due to incorrect mounting, connection or start-up of the device.Refer to the Mounting and Operating Instructions EB 8384-2 on how to mount the positioner, perform the electric and pneumatic connections as well as start up the positioner.Observe the warnings and safety instructions written in the Mounting and Operating Instructions EB 8384-.

Further documentationThe documents listed below contain descriptions of the start-up, functioning, and operation of the positioner. You can download these documents from the SAMSON website. The docu-ments marked with an asterisk (*) are supplied with the positioner either in printed or elec-tronic form.

Type 3730-2 Positioneru T 8384-2: Data sheetu EB 8384-2*: Mounting and operating instructionsu KA 8384-2/3*: Quick guideEXPERTplus diagnostics (Type 3730-2 Positioner in firmware version 1.50 and higher)u T 8389: Data sheetu EB 8389*: Operating instructions

EXPERT+ diagnostics (Type 3730-2 Positioner up to firmware version 1.49)u T 8388: Data sheetu EB 8388: Operating instructions

In addition to the positioner documentation, observe the documentation for the pneumatic actuator, valve, and other valve accessories.

NOTICE!

Note

Page 4: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

4 SH 8384-2 EN

Contents

1 Scope ...........................................................................................................52 Technicaldata(excerptfromEB 8384-2) ........................................................63 Safety-related functions .................................................................................84 Mounting, connection, and start-up ..............................................................105 Required conditions .....................................................................................116 Proof testing ................................................................................................137 Repairs .......................................................................................................15

Page 5: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

SH 8384-2 EN 5

Scope

1 ScopeGeneralThe Type 3730-2 Electropneumatic Positioner is a single-acting, venting positioner for attach-ment to pneumatic rotary and linear actuators with spring-return mechanism. The positioner is used to position control valves.

Use in safety-instrumented systemsObserving the requirements of IEC 61508, the systematic capability of the pilot valve for emergency venting as a component in safety-instrumented systems is given.Use of the positioner is possible on observing the requirements of IEC 61511 and the re-quired hardware fault tolerance in safety-instrumented systems up to SIL 2 (single device/HFT = 0) and SIL 3 (redundant configuration/HFT = 1).The individual safety functions of the positioner are to be regarded as Type A elements in ac-cordance with IEC 61508-2.

The architecture and the interval between proof tests must be changed accordingly for a higher safety integrity level.

Versions and ordering dataAll versions of the Type 3730-2 Positioner are suitable for use in safety-instrumented systems. However, the optional equipment affects the safety-related behavior of the positioner. These options are the inductivelimitcontact SJ2-SN and the solenoid valve.The article code written on the nameplate provides details on the optional equipment of the positioner:

Note

Page 6: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

6 SH 8384-2 EN

Technicaldata(excerptfromEB 8384-2)

Type 3730-2 Positioner x x x x x x x x 0 x 0 0 x 0 x x

Option(additionalequipment)

Without inductive limit contactWith inductive limit contact SJ2-SN (NAMUR NC contact)

01

Without solenoid valveWith 24 V DC solenoid valve

04

AttachmentThe positioner is suitable for the following types of attachment in combination with various mounting parts: − Direct attachment to SAMSON Type 3277 Actuators − Attachment to linear actuators according to IEC 60534-6 (NAMUR) − Attachment to linear actuators according to VDI/VDE 3847 − Attachment to SAMSON Type 3510 Micro-flow Valve − Attachment to rotary actuators according to VDI/VDE 3845, fixing levels 1 and 2

2 Technicaldata(excerptfromEB 8384-2)Type 3730-2 Positioner: the technical data for the explosion-protected devices may be restricted by the limits speci-fiedinthetestcertificates.

Reference variable w

Signal range 4 to 20 mA · Two-wire device, reverse polarity protection · Minimum span 4 mA

Static destruction limit

100 mA

Minimum current 3.6 mA for display · 3.8 mA for operation

Load impedance Without explosion protection: ≤6 V (corresponding to 300 Ω at 20 mA) · Explosion protection: ≤7 V (corresponding to 350 Ω at 20 mA)

Supply airSupply air 1.4 to 7 bar (20 to 105 psi)

Air quality acc. to ISO 8573-1

Max. particle size and density: Class 4 · Oil content: Class 3 · Pressure dew point: Class 3 or at least 10 K below the lowest ambient temperature to be expected

Signal pressure (output) 0 bar up to the supply pressure · Can be limited to 1.4 bar/2.4 bar/3.7 bar ± 0.2 bar by software

Hysteresis ≤0.3 %

Sensitivity ≤0.1 %

Page 7: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

SH 8384-2 EN 7

Technicaldata(excerptfromEB 8384-2)

Type 3730-2 Positioner: the technical data for the explosion-protected devices may be restricted by the limits speci-fiedinthetestcertificates.

Transit time Venting or filling with air adjustable separately up to 240 s by software

Air output capacity

To fill actuator with air

At Δp = 6 bar: 8.5 mn³/h · At Δp = 1.4 bar: 3.0 mn³/h · KVmax (20 °C) = 0.09

To vent actuator At Δp = 6 bar: 14.0 mn³/h · At Δp = 1.4 bar: 4.5 mn³/h · KVmax (20 °C) = 0.15

Permissible ambient tem-perature

–20 to +80 °C (all versions) –45 to +80 °C with metal cable glandThe temperature limits for the explosion-protected devices may be further restricted bythelimitsspecifiedinthetestcertificates.

Use in safety-instrumented systems (SIL)

Observing the requirements of IEC 61508, the systematic capability of the pilot valve for emergency venting as a component in safety-instrumented systems is given.

Use is possible on observing the requirements of IEC 61511 and the required hard-ware fault tolerance in safety-instrumented systems up to SIL 2 (single device/HFT = 0) and SIL 3 (redundant configuration/HFT = 1).

Safety-relevant optionsSolenoidvalve·ApprovalaccordingtoIEC 61508/SIL·Emergencyventingfunction

Input

24 V DC · Galvanically isolated and reverse polarity protection · Static destruction limit 40 V

Current consumption I = U – 5.7 V3840 Ω

(corresponding to 4.8 mA at 24 V/114 mW)

Signal '0' (no response) <12 V (emergency shutdown at 0 V)

Signal '1' (response) > 19 V

Service life >5 x 10 6 switching cycles

KV coefficient 0.15

Use in safety-instrumented systems acc. to IEC 61508/SIL

Same as positioner pneumatics

Inductive limit contact by Pepperl+Fuchs · Function: safety-related end position monitoring

For connection to switching amplifier according to EN 60947-5-6. Can be used in combination with a software limit contact.

SJ2-SN proximity switch Measuring plate not detected: ≥3 mA · Measuring plate detected: ≤1 mA

Page 8: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

8 SH 8384-2 EN

Safety-related functions

3 Safety-related functions1. Emergencyventingoverthei/pconverter(Fig. 1 path )

In automatic operation, the PD controller (3) compares the actual value to the DC control signal from 4 to 20 mA coming from the microcontroller. In case of a system deviation, the activation of the i/p converter is changed so that the actuator (1) is either vented or filled with air. Fail-safe action is triggered when no signal (0 mA) is applied to terminals 11/12 and, as a result, to the i/p converter.

2. Emergency venting over the optional solenoid valve (Fig. 1 path )The solenoid valve (12) is energized by a 24 V DC voltage signal. Fail-safe action is trig-gered when no signal (0 mA) is applied to terminals 81/82. This causes the solenoid valve (12) to vent the output of the i/p converter to the atmosphere. The actuator is vent-ed as well.

3. Safety-related end position monitoring over the optional inductive limit contact (Fig. 1 path )The inductive limit contact SJ2-SN (NAMUR NC contact) indicates the adjusted end posi-tion in a safety-instrumented system at terminals 41/42. See u EB 8384-2 for adjusting the limit contacts.

Fail-safe actionFail-safe action is triggered by the i/p converter or solenoid valve and upon supply air fail-ure. The positioner fully discharges its pneumatic output to the atmosphere, causing the mounted actuator to be vented. As a result, the valve moves to the fail-safe position. The fail-safe position depends on how the springs are arranged in the pneumatic actuator (air-to-close or air-to-open).When the air supply fails and the optional solenoid valve is de-energized, all positioner functions, except open/closed loop control, remain active (including diagnostics, position and, status feedback).

The pneumatic output of the positioner can also be vented to the atmosphere over the soft-ware, e.g. by entering a suitable set point. This procedure is not a safety-instrumented func-tion.

ProtectionagainstunauthorizedchangestotheconfigurationA change to the configuration cannot affect the safety function nor cause it to be deactivated.

Note

Page 9: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

SH 8384-2 EN 9

Safety-related functions

Q

%mm

G

PD

SerialInterface 16

13

22

15

A2

A3

BE

2

4

20

195

3

7

8

10

14

14

9

17 18

8182

1112

4241

5152

8384

3132

3132

A1

Q

%mmmm

G

PD

SerialInterface 16

13

22

15

A2

A3

BE

2

4

20

195

3

7

8

10

14

14

9

17 18

A1

G12 6

xy

1

11

w

w

x

24 V DC

1 Control valve 13* Analog position transmitter2 Travel sensor 14 Software limit contact, alarm 1/23 PD controller 15 Fault alarm output, alarm 34 A/D converter 16 Display5 Microcontroller 17* Actuation of solenoid valve6 i/p converter 18* Electrical insulation7 Air capacity booster 19 D/A converter8 Pressure regulator 20 Communication interface10 Volume restriction 22 Binary input BE*11* Inductive limit contact12* Solenoid valve * Options

Fig. 1: Functional diagram of the positioner

Page 10: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

10 SH 8384-2 EN

Mounting, connection, and start-up

4 Mounting, connection, and start-upRefer to Mounting and Operating Instructions u EB 8384-2 on how to mount, perform the electric and pneumatic connections as well as start up the positioner.Only use the specified original mounting parts and accessories.

G

+81 -82 +11 -12 +83 -84 +51 -52

A2A3 A1

+41 -42 +31 -32

A

+31 -32

24 V DCSolenoid valve

(optional)

mA control signal

Not Ex: Binary input of a PLC acc. to IEC 61131-2 (Pmax = 400 mW) or switch-ing amplifier acc. to EN 60947-5-6Ex: Sw. amplifier acc. to EN 60947-5-6

A3Fault alarm

Limit contacts

A2Software

A1Softwareoptionally inductive

Position transmitter with

two-wire transmitter supply unit

Leakage sensor Binary input

Fig. 2: Electrical connection

Page 11: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

SH 8384-2 EN 11

Required conditions

5 Required conditions

Risk of malfunction due to incorrect selection or wrong installation and operating conditions.Only use control valves in safety-instrumented systems after the necessary conditions in the plant have been fulfilled. The same applies to the mounted positioner.

Selection Î The required transit times of the control valve are kept.The transit times to be implemented are determined by the process engineering require-ments.

The minimum OPEN and CLOSE transit times can be read in Codes 40 and 41 after the positioner has been initialized.

Î The positioner is suitable for the prevailing ambient temperature.

Versions Temperature range

All –20 to +80 °C

With metal cable gland –45 to +80 °C

The temperature limits for the explosion-protected devices may be further restricted by the lim-itsspecifiedinthetestcertificates.

Î The temperature limits are observed.

Mechanical and pneumatic installation Î The positioner is mounted properly as described in the mounting and operating instruc-tions and connected to the air supply.

Error codes 50 to 58 indicate incorrect attachment. For safety-instrumented systems, we recommend assigning the 'Maintenance alarm' status to these errors to quickly recognize them when they occur (indicated by on the display).

Î The maximum supply pressure does not exceed 7 bar.

WARNING!

Tip

Tip

Page 12: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

12 SH 8384-2 EN

Required conditions

Î The pneumatic air supply meets the instrument air specifications.

Particle size and quantity Oil content Pressure dew pointClass 4 Class 3 Class 3≤ 5 µm and 1000/m³ ≤ 1 mg/m³ –20 °C or at least 10 K below the lowest ambi-

ent temperature to be expected

We recommend installing a supply pressure regulator/filter upstream of the positioner. For example, the SAMSON Type 4708 Supply Pressure Regulator with 5 µm filter car-tridge can be used.

Î The supply air line has a minimum inside diameter of 4 mm.Select the cross section and length of the line to ensure that the supply pressure at the po-sitioner on filling the actuator with air does not fall below the minimum limit.

Î The positioner is mounted as prescribed. Î The vent opening at the back of the positioner remains open when the positioner is in-stalled on site.

Electrical installation Î The positioner is connected to the electric power supply properly as described in the mounting and operating instructions.

Î Only cables whose outside diameters are suitable for the cable glands are used. Î The electrical cables in Ex i circuits comply with the data that planning was based on. Î The cable glands and cover screws are fastened tightly to ensure that the degree of pro-tection is met.

Î The installation requirements for the applicable explosion protection measures are ob-served.

Î The special conditions specified in the explosion protection certificates are observed.

Operation Î When the optional inductive limit contact is used, Code 38 is set to YES. Î The inductive limit contact is adjusted mechanically to meet the specifications.

Tip

Page 13: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

SH 8384-2 EN 13

Proof testing

6 Proof testingThe proof test interval and the extent of testing lie within the operator's responsibility. The operator must draw up a test plan, in which the proof tests and the interval between them arespecified.Werecommendsummarizingtherequirementsoftheprooftestinacheck-list.

Risk of dangerous failure due to malfunction in the event of emergency (actuator is not vented or the valve does not move to the fail-safe position).Only use devices in safety-instrumented systems that have passed the proof test according to the test plan drawn up by the operator.

Regularly check the safety-instrumented function of the entire SIS loop. The test intervals are determined, for example on calculating each single SIS loop in a plant (PFDavg).

Function testingRegularly check the safety function according to the test plan drawn up by the operator.

Record any faults in the positioner and inform SAMSON of them in writing.

− Emergencyventingbyapplyinga0 mAsignaltoterminals11/12(controlsignal):1. Apply supply air within the permissible range (max. 7 bar) to the positioner which al-

lows the valve to move to the maximum travel/angle of rotation.2. Apply an electric input signal ≥3.6 mA to the positioner (terminals 11/12).3. Switch the positioner to automatic mode (if it has not already been done).4. Apply the input signal (terminals 11/12) over a local current source or over the con-

trol system in such a way that the valve moves to 50 % of its travel/opening angle.

The travel in automatic mode can be read at the positioner in Code 0.

5. Set the electric input signal to 0 mA or disconnect it.This must cause the valve to move to its fail-safe position (terminals 11/12).

WARNING!

Note

Tip

Page 14: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

14 SH 8384-2 EN

Proof testing

6. Check whether the actuator is fully vented within the demanded time.

Connect a pressure gauge to check that the actuator has completely vented.

− Emergencyventingbyapplyinga0 Vsignaltoterminals81/82(solenoidvalve):1. Apply supply air within the permissible range (max. 7 bar) to the positioner which al-

lows the valve to move to the maximum travel/angle of rotation.2. Apply an electric input signal ≥3.6 mA to the positioner (terminals 11/12).3. Supply the solenoid valve with a voltage >19 V DC (terminals 81/82).4. Apply the input signal (terminals 11/12) over a local current source or over the con-

trol system in such a way that the valve moves to 50 % of its travel/opening angle.

The travel in automatic mode can be read at the positioner in Code 0.

5. Set the voltage to 0 V DC (terminals 81/82).6. Check whether the actuator is fully vented within the demanded time.

Connect a pressure gauge to check that the actuator has completely vented.

− Safety-related end position monitoring1. Apply supply air within the permissible range (max. 7 bar) to the positioner which al-

lows the valve to move to the maximum travel/angle of rotation.2. Apply an electric input signal ≥3.6 mA to the positioner (terminals 11/12).3. Switch the positioner to automatic mode (if it has not already been done).4. Apply the input signal (terminals 11/12) over a local current source or over the con-

trol system in such a way that the valve moves to 50 % of its travel/opening angle.5. Apply the input signal (terminals 11/12) over a local current source or over the con-

trol system in such a way that the valve moves to the end position.6. Check whether a signal exists at terminals 41/42 when the valve has reached the

end position.

Tip

Tip

Tip

Page 15: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

SH 8384-2 EN 15

Repairs

Visual inspection to avoid systematic failureTo avoid systematic failure, inspect the positioner regularly. The frequency and the scope of the inspection lie within the operator's responsibility. Take application-specific influences into account, such as: − Dirt blocking the pneumatic connections − Corrosion (destruction primarily of metals due to chemical and physical processes) − Material fatigue − Aging (damage caused to organic materials, e.g. plastics or elastomer, by exposure to

light and heat) − Chemical attack (organic materials, e.g. plastics or elastomer, which swell, leach out or

decompose due to exposure to chemicals)

Risk of malfunction due to the use of unauthorized parts.Only use original parts to replace worn parts.

7 RepairsOnly perform the work on the positioner described in u EB 8384-2.

Fail-safe action impaired due to incorrect repair.Service and repair work must only be performed by trained staff.

NOTICE!

NOTICE!

Page 16: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism
Page 17: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

Manufacturer's Declaration Changed on: 2014-06-23 2014-07-30 2014-08-21 V/HE-1142-3 DE-EN Changed by: V31/Bhk/V74/Tny V31/Bhk/V74/Tny V31/Bhk/V74/Tny SAMSON AKTIENGESELLSCHAFT · Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany · Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 · [email protected]

Herstellererklärung Manufacturer's Declaration Für folgende Produkte For the following products

Stellungsregler Typ 3730-0XXXXXXXXXX00... Typ 3730-1XXXXXXXXXX00... Typ 3730-2XXXXXXXXXX00... Typ 3730-3XXXXXXXXXX00... Typ 3730-4XXXXXXXXXX00... Typ 3730-5XXXXXXXXXX00...

Type 3730-0XXXXXXXXXX00... Type 3730-1XXXXXXXXXX00... Type 3730-2XXXXXXXXXX00... Type 3730-3XXXXXXXXXX00... Type 3730-4XXXXXXXXXX00... Type 3730-5XXXXXXXXXX00... Positioner

Hiermit wird bestätigt, dass das Steuerventil in den o. g. Stellungsreglern gemäß IEC 61508 für den Einsatz in sicherheitsgerichteten Krei-sen geeignet ist.

Die Stellungsregler haben eine HFT von 0 und können nach IEC 61511 bis SIL 2 (einzelnes Gerät, HFT = 0) und SIL 3 (redundante Ver-schaltung, HFT = 1) eingesetzt werden. Die Geräte sind nach Typ A eingestuft.

We hereby certify that the pilot valve installed in the positioners mentioned above is suitable for use in safety-instrumented systems accord-ing to IEC 61508.

The positioners have an HFT of 0 and can be used up to SIL 2 (single device, HFT = 0) and SIL 3 (redundant configuration, HFT = 1) ac-cording to IEC 61511. The devices are classified as type A.

Die Konformität des Entwicklungsprozesses, der durchgeführten FMEDA und der Aussa-gen dieser Herstellererklärung sind von der TÜV Rheinland Industrie Service durch das Zertifikat V60 2012 C8 vom Dezember 2012 zertifiziert.

The conformity of the development process and the performed FMEDA as well as the statements in this Manufacturer’s Declaration are certified by TÜV Rheinland Industrie Ser-vice GmbH in the Certificate V60 2012 C8 of December 2012.

Sicherheitstechnische Annahmen Safety-related assumptions

Unter Verwendung des i/p-Wandlers und/oder des optionalen Magnetventils schaltet der ein-fachwirkende Stellungsregler seinen pneuma-tischen Ausgang gegen Atmosphäre durch und entlüftet dadurch den angeschlossenen Ventilantrieb.

When the i/p converter and/or the optional so-lenoid valve are used, the single-acting posi-tioner discharges its pneumatic output to the atmosphere, causing the mounted actuator to be vented.

Sicherheitstechnische Kenndaten Safety-related data

λsafe, undetected 9 FIT λsafe, detected 0 FIT λdangerous, undetected 1 FIT λdangerous, detected 0 FIT PFDavg. bei jährlicher Prüfung 4,2 · 10-6 HFT 0 Gerätetyp A SFF (Safe Failure Fraction) 90 % MTBFgesamt 11940 Jahre MTBFdangerous, undetected 119530 Jahre

λsafe, undetected 9 FIT λsafe, detected 0 FIT λdangerous, undetected 1 FIT λdangerous, detected 0 FIT PFDavg. with annual test 4.2 · 10-6 HFT 0 Device type A Safe failure fraction (SFF) 90 % MTBFtotal 11940 years MTBFdangerous, undetected 119530 years

1 FIT = 1 Ausfall pro 109 Stunden 1 FIT = 1 failure per 109 hours

Page 18: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

Manufacturer's Declaration Changed on: 2014-06-23 2014-07-30 2014-08-21 V/HE-1142-3 DE-EN Changed by: V31/Bhk/V74/Tny V31/Bhk/V74/Tny V31/Bhk/V74/Tny SAMSON AKTIENGESELLSCHAFT · Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany · Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 · [email protected]

Nutzbare Gebrauchsdauer Useful lifetime

Nach IEC 61508-2 Abschnitt 7.4.9.5 können acht bis zwölf Jahre angenommen oder ein Wert benutzt werden, der sich durch Betriebs-bewährung des Anwenders ergibt.

According to IEC 61508-2, section 7.4.9.5, a useful lifetime of eight to twelve years can be assumed. Other values can be used based on the user’s previous experience (prior use/ proven-in-use).

Bestimmungsgemäße Verwendung Intended use

– Bedienungsanleitung

– Sicherheitshandbuch + TV-SK 9838

– Anforderung an Instrumentenluft-Qualität

– Operating instructions

– Safety manual + TV-SK 9838

– Quality requirements for instrument air

Das sicherheitsgerichtete Entlüften kann wie folgt ausgelöst werden:

– Der elektrische Eingang des Stellungsreg-lers wird energielos gesetzt. o Typen 3730-0/-1/-2/-3: 0 mA an den

Klemmen 11/12 o Typen 3730-4/-5: Spannungspegel 0 V

an den Klemmen: IEC 1158-2

– Der elektrische Eingang des optionalen Magnetventils wird energielos gesetzt. o Typen 3730-2/-3/-4/-5: Spannungspegel

0 V DC an den Klemmen: 81/82

Emergency venting can be triggered as fol-lows:

– The electrical input of the positioner is de-energized. o Types 3730-0/-1/-2/-3: 0 mA at terminals

11/12 o Types 3730-4/-5: 0 V voltage level at

terminals "IEC 1158-2"

– The electrical input of the optional solenoid valve is de-energized. o Types 3730-2/-3/-4/-5: 0 V DC voltage

level at terminals 81/82

Hinweis! Note!

Die Stellungsregler der Typen 3730-2/-3/-4/-5 sind mit umfangreichen Mitteln zur Diagnose ausgestattet. Diese Diagnose bewertet den Zustand des Stellungsreglers und der ange-bauten Armatur. Die sicherheitstechnischen Kennwerte können sich durch Einsatz der Di-agnose verbessern. Die Diagnose dient auch der Aufdeckung unerkannter systematischer Fehler (siehe VDI 2180 Blatt 5).

The Types 3730-2/-3/-4/-5 Positioners come with extensive diagnostic functions. They as-sess the condition of the positioner as well as of the control valve it is mounted on. The safe-ty-related data can be improved by using the diagnostics. Diagnostics also serve to reveal undetected systematic failures (refer to VDI 2180, sheet 5).

Voraussetzungen Requirements

Die Reparaturzeit ist klein gegenüber der mitt-leren Anforderungsrate. Durchschnittliche Be-anspruchung in industrieller Umgebung durch Medien und Umgebungsbedingungen wird vo-rausgesetzt. Der Anwender ist für den be-stimmungsgemäßen Gebrauch verantwortlich.

Short mean time to repair compared to the av-erage rate of demand. Normal exposure to in-dustrial environment and fluids is assumed. The user is responsible for ensuring that the device is used as intended.

Page 19: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

Manufacturer's Declaration Changed on: 2014-06-23 2014-07-30 2014-08-21 V/HE-1142-3 DE-EN Changed by: V31/Bhk/V74/Tny V31/Bhk/V74/Tny V31/Bhk/V74/Tny SAMSON AKTIENGESELLSCHAFT · Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany · Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 · [email protected]

SAMSON AG SAMSON AG

Guido König Zentralabteilungsleiter Produktmanagement und -marketing Mess- und Regeltechnik SAMSON GROUP

Stephan Michalik Zentralabteilungsleiter Qualitätsmanagement

Director Product Management and Marketing Instrumentation and Controls SAMSON GROUP

Head of Central Department Quality Management

Page 20: Safety Manual SH 8384-2 EN - SAMSON · Safety Manual SH 8384-2 EN ... Quick guide EXPERTplus ... ment to pneumatic rotary and linear actuators with spring-return mechanism

SAMSON AG · MESS- UND REGELTECHNIKWeismüllerstraße 3 · 60314 Frankfurt am Main, GermanyPhone: +49 69 4009-0 · Fax: +49 69 [email protected] · www.samson.de SH 8384-2 EN 20

17-0

1-25

· En

glish