SACSe A REAL CASE OF SELF HEALING DISTRIBUTION NETWORK Regulatory demands on SAIFI and SAIDI drives the need for automotive substation capable of re- energizing customers within 1 minute, without the need for fast communication and advanced DMS. SACSe(Sectionalizing And Changeover System enhanced) uses logic, relays, circuit breakers, motor drives and only local information to deliver this functionality. 2 SACSe substations applied to a feeder yield a dramatic decrease in SAIDI and SAIFI for the feeder. Current SACSe consists of a Xiria RMU from Eaton Holec and a T200P RTU from Schneider. 2 SACSe substations divides the feeder into 4 fault sections. SACSe switching with 2 substations on a feeder with a the fault downstream. 1800 1600 1400 1200 1000 800 600 400 200 0 0 20 40 60 80 100 120 140 160 Average outage profile Time (minutes) Field staff arrives to area Without automation Customers deenergized With automation SACSe2 SACSe1 H SACSe2 SACSe1 H SACSe2 SACSe1 H SACSe2 SACSe1 H SACSe2 SACSe1 H H Substation feeder SACSe SACSe Fault section 1 Fault section 2 Fault section 3 Fault section 4 Neighbor feeder Substation on neighbor(backup) feeder SACSe substation Kåre Seest Rasmussen [email protected] DONG Energy A/S – Denmark

Upload: others

Post on 23-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SACSe - neplan.ch · Current SACSe consists of a Xiria RMU from Eaton Holec and a T200P RTU from Schneider. 2 SACSe substations divides the feeder into 4 fault sections. SACSe switching

SACSe

A REAL CASE OF SELF HEALING DISTRIBUTION NETWORKRegulatory demands on SAIFI and SAIDI drivesthe need for automotive substation capable of re-energizing customers within 1 minute, without the need for fast communication and advanced DMS.

SACSe(Sectionalizing And Changeover System enhanced) uses logic, relays, circuit breakers, motor drives and only local information to deliver this functionality.

2 SACSe substations applied to a feeder yield a dramatic decrease in SAIDI and SAIFI for the feeder.

Current SACSe consists of a Xiria RMU from Eaton Holec and a T200P RTU from Schneider.

2 SACSe substations divides the feeder into 4 fault sections.

SACSe switching with 2 substations on a feeder with a the fault downstream.

1800

1600

1400

1200

1000

800

600

400

200

0

0 20 40 60 80 100 120 140 160

Average outage profile

Time (minutes)

Field staff arrives to area

Without automation

Cus

tom

ers

deen

ergi

zed

With automation

SACSe2SACSe1

H

SACSe2SACSe1

H

SACSe2SACSe1

H

SACSe2SACSe1

H

SACSe2SACSe1

H

H

Substation feeder

SACSe

SACSe

Fault section 1Fault section 2Fault section 3Fault section 4Neighbor feeder

Substation on neighbor(backup) feeder

SACSe substation

1800

1600

1400

1200

1000

800

600

400

200

0

0 20 40 60 80 100 120 140 160

Average outage profile

Time (minutes)

Field staff arrives to area

Without automation

Cus

tom

ers

deen

ergi

zed

With automation

SACSe2SACSe1

H

SACSe2SACSe1

H

SACSe2SACSe1

H

SACSe2SACSe1

H

SACSe2SACSe1

H

H

Substation feeder

SACSe

SACSe

Fault section 1Fault section 2Fault section 3Fault section 4Neighbor feeder

Substation on neighbor(backup) feeder

SACSe substation

1800

1600

1400

1200

1000

800

600

400

200

0

0 20 40 60 80 100 120 140 160

Average outage profile

Time (minutes)

Field staff arrives to area

Without automation

Cus

tom

ers

deen

ergi

zed

With automation

SACSe2SACSe1

H

SACSe2SACSe1

H

SACSe2SACSe1

H

SACSe2SACSe1

H

SACSe2SACSe1

H

H

Substation feeder

SACSe

SACSe

Fault section 1Fault section 2Fault section 3Fault section 4Neighbor feeder

Substation on neighbor(backup) feeder

SACSe substation

Kåre Seest Rasmussen [email protected] Energy A/S – Denmark

Page 2: SACSe - neplan.ch · Current SACSe consists of a Xiria RMU from Eaton Holec and a T200P RTU from Schneider. 2 SACSe substations divides the feeder into 4 fault sections. SACSe switching

CONTINUOUS NETWORK STATE ESTIMATION

From the information imported into SmartPIT, a full network model including loads and generators is built.

• Approx. 7,000 secondary substations are modelled in this phase

• Calculation ‘engine’ is the planning tool NEPLAN from BCP

• State estimation uses load balancing

• The simultaneity factors of the synthetic load curves are adjusted to meet power or current measurements

Calculated flows and voltages are returned to SmartPIT and stored as ‘virtual’ measure-ments. Now, the network can be analyzed, planned and operated on basis of the actual 10 minute loading of individual components.

0

1000

2000

3000

4000

5000

P2

Q2

0

1000

2000

3000

4000

5000

P

Q

0

1000

2000

3000

4000

5000

P

Q

0

1000

2000

3000

4000

5000

P

Q

USINg CONTINUOUS STATE ESTIMATION IN GRID PLANNING

In 2008 DONG Energy implemented the IT solution ‘SmartPIT’ that determines all line flows, transformer loads and bus voltages in the entire MV network every 10 minutes – allowing for analysis, planning and operation on actual hour-by-hour values rather than peak estimates.

Figure 1: Solution components and overview.

DATA AQUISITION FROM PRIMARY SUBSTATIONS

Primary substations are monitored with a traditional SCADA system.

Data imported into SmartPIT every 10 minutes are:

• Bus configuration and voltage at primary substations

• Load currents at feeder head

• Switching state (topology) in MV network

FROM PEAK LOADS TO SYNTHETIC LOAD CURVES P(t)

In DONG Energy’s case, 22 different seasons are used instead of weeks and months; some several weeks long, other just a few days, e.g. Christmas, to give the best possible representation. This gives actual load of:

P(t) = Pmax•Profileday(t)•Profileseason(t)•Profileyear(t)

By analyzing a large number of actual load curves, synthetic curves are defined for workdays, Saturdays and Sundays in all seasons; see example below:

‘High’ curves represent workdays; ‘low’ curves are Saturdays and Sundays.

Profiles show a clear variation over hours, weekdays and seasons.

Figure 2: Synthetic load profiles for

‘Bank & Insurance’

FROM ANNUAL ENERgY TO PEAK LOADS Pmax

All non-telemetered customers are divided into 27 unique categories, giving a fine discrimination between different load patterns. For each category, annual energy sales Q are converted into to peak load Pmax, using Velander’s formula:

Pmax [kW] = A * Q [MWh] + B * √Q

Parameters A and B have been determined for all 27 categories, using up-to-date load measurements.

NETWORK DATA

In order to build an exact network model for the conti-nuous calculations, network data are imported once every 24 hours from two sources, SAP PM and GIS:

• MV lines

• HV/MV and MV/LV transformers

• Generators

• Network structure and line lengths

LOAD DATA, EMBEDDED gENERATION

Embedded generation is quite common in Danish MV grids.

The most usual types are:

• CHP (Cogeneration Heat & Power) plants; typically in the 100 - 5,000 kW range

• Wind turbines; typically in the 100 - 2,000 kW range

• Wind farms; typically in the range of several MW

Data is handled like AMR data.

DATA AQUISITION FROM SECONDARY SUBSTATIONS

Secondary substations are monitored using the distribution automation system Discos from PowerSense.

Data imported into SmartPIT every 10 minutes via gPRS are:

• Phase currents

• Active and reactive power on MV lines and transformers

• LV voltages

TEST RESULTS

Good estimates of loads and voltagesThe synthetic load curves and the calculation methodology has been

validated by comparing estimated and real loads on two feeders,

densely equipped with Discos units.

The figure below shows estimated and actual current [A] on MV feeder GHOA3 from 7th December 2007 to 14th January 2008:

Figure 4: Calculated and measured MV feeder current.

Blue and red curve is estimated and actual current; green curve shows an

abnormal switching state on 11th December. In general, estimates proved

quite fair with a MAPE value (Mean Absolute Percentage Error) at approx.

9 % before supportive Discos measurements.

The absolute deviations over the period are:

Next step is to include Discos

power flow measurements on

feeder branches to improve

these figures.

LOAD DATA, CUSTOMERS WITH AMR

In Denmark, automatic meter reading (AMR) is mandatory for customers with an annual consumption above 100,000 kWh:

• Readings are retrieved once a day via SMS or dial-up lines

• Measurements are checked for validity and sent to SmartPIT after 72 hours

• Data contain hourly sales; i.e. kWh/h and is used as an estimate for the mean load in that specific hour.

LOAD DATA, ‘SMALL’ CUSTOMERS

For customers consuming less than 100,000 kWh/year, the only information known is expected energy sales for the next year.

From SAP IS-U, the following information on more than 900,000 customers is retrieved once every 24 hours:

• Expected annual consumption

• Load Category

• Topological connection to network

Energy sales are then converted into synthetic load curves.

VALIDATION OF MEASUREMENTS

Incoming measurements are validated with the ILog rules tool. The purpose is to:

• Protect state estimation calculations against implausible measurements

• Notify the operator so ‘bad’ measurements can be found and rectified

• Scale measurands to correct units

• Other logical rules

Peter Vinter [email protected]

DONG Energy A/S – Denmark

Hans Knudsen

[email protected]

DONG Energy A/S – Denmark

y [p.u.]

x [hour]

z [season]

0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

0,8

0,9

1

0

20

40

60

80

100

120

140

160

1 17 33 49 65 81 97 113

129

145

161

177

193

209

225

241

257

273

289

305

321

337

353

369

385

401

417

433

449

465

481

497

513

529

545

561

577

593

609

625

641

657

673

689

705

721

737

753

769

785

801

817

833

849

865

881

897

913

929

Iest

I [A]

Normalk.

0%

5%

10%

15%

20%

25%

-30% -20% -10% 0% 10% 20% 30%

BUSINESS PERSPECTIVES

Dimensioning MV feeders where the only information available is energy

sales and peak load at feeder head is a well-known challenge.

The traditional approach based on energy sales has several shortcomings:

• Empirical corellations are rarely updated and do not reflect changes in e.g.

load utilization time over the years

• Solution will satisfy feeder peak load, but not true line and substation peak

load

• In networks with embedded generation, line loads may be severely under-

and overestimated

• Load variation over time is not available, meaning that assets must be

dimensioned to carry peak load ‘for ever’

Historically, utility companies have had either to build in enough network capacity

to handle the uncertainties above leading to higher investment costs or to accept

the risk of compromising network safety and power quality.

With the help of the SmartPIT solution from IBM:

• Real peak load data for individual components have become available

• Voltage levels may be monitored continuously

• Synthetic load curves permits a reliable MV network state estimation even with

a low number of live measurements

• Capital expenditures can now be optimized and directed to the real bottlenecks of

the network.

By taking this step towards the Intelligent Utility Network, DONG Energy becomes

able to make more efficient use of existing electrical infrastructure and avoid unne-

cessary grid reinforcements plan more intelligently for the future.

The expected reductions in grid investments provides a good business case in it-self

for the SmartPIT system, but the SmartPIT system is at the same time a necessary

first step and an integral part of DONG Energys SmartGrid vision for a grid with an

increased amount of embedded generation and flexible demand including a high

penetration of electric vehicles

SOLUTION OVERVIEW

Network Topology

Consumption Enterprise Service Bus

Production PANDA

SAP & PANDA

SCADA

DMS

DISCOS Presentation Planning

Calculation Engine Rules Engine Monitoring &

Alerting

SmartPIT DB

0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

0,8

0,9

1

0

20

40

60

80

100

120

140

160

1 17 33 49 65 81 97 113

129

145

161

177

193

209

225

241

257

273

289

305

321

337

353

369

385

401

417

433

449

465

481

497

513

529

545

561

577

593

609

625

641

657

673

689

705

721

737

753

769

785

801

817

833

849

865

881

897

913

929

Iest

I [A]

Normalk.

0%

5%

10%

15%

20%

25%

-30% -20% -10% 0% 10% 20% 30%

Figure 5: Error distribution curve, feeder GHO A3.

Figure 3State estimation on MV feeder.