  • Introduction

    The purpose of this

    information paper is

    to provide a publicly

    available document for

    professionally informed

    decisions regarding

    the running costs of

    various conventional

    electric heating systems

    installed in UK homes,

    and their running costs.

    The report has been prepared

    by Dr John Counsell who is an

    independent researcher with

    over 20 years of experience in

    the design, development and

    performance assessment of

    electric heating systems and

    their controls. The running

    costs used in the comparison

    study described in this paper

    have been estimated using the

    UK Government’s calculation

    method: Standard Assessment

    Procedure 2012 (SAP). SAP is a

    compulsory calculation required

    to comply with Part L of the

    England & Wales and Section

    6 of the Scotland & Northern

    Ireland building regulations.

    The study uses the full SAP

    calculation and the latest BRE

    published revision SAP2012

    (2012 Edition rev Feb2014) [1].

    The fuel costs used are also from

    SAP published in Table 12 [1].

    SAP has expanded its

    coverage of energy

    use in homes since its

    introduction to Part L

    in 1994 to cover the

    whole house energy

    use including the use of

    renewable energy sources.

    The energy prediction

    method/calculations for

    Space and Domestic Hot

    Water heating energy

    consumption have been

    calculated in SAP based

    on the BRE Domestic

    Energy Model (BREDEM).

    In the comparison of

    electric heating system

    running costs in this paper,

    only space heating (i.e.

    excluding Domestic Hot

    Water) energy running

    costs are used. The type of

    electric heating systems

    to be compared in their

    running cost performances

    have been confined to

    conventional types of

    electric heating. These

    systems are based on

    resistive heating elements

    and do not include more

    complex electric heating

    systems such as heat

    pumps and underfloor

    electric heating systems.

    The SAP/BREDEM

    modelling parameters

    for the heating systems

    used are given and fully

    explained in the report and

    the attached Appendix A.

    A typical High Heat Retention Heater made by Dimplex.

    4

    Running cost report_Inside Pages.indd 4 27/11/2014 15:44

  • Running Cost

    Estimation using SAP

    BREDEM which is the core

    estimation method for predicting

    the energy consumption in

    UK homes is, still to date the

    only known energy prediction

    method that has been extensively

    calibrated across the UK with a

    wide range of real occupied homes.

    This calibration was carried out with accurately

    monitored annual and minute-by-minute data

    from real occupied homes. The data from

    the monitoring contained information on;

    occupancy times, house temperatures, space

    heating and hot water energy use and outside

    weather conditions.

    This unique calibration has

    established BREDEM and thus SAP

    as the Government and Building

    industry’s trusted de facto standard

    for predicting energy use in a UK

    home. The BREDEM method is a

    combination of empirically derived

    standard occupancy patterns in two

    zones in the home; the first for the

    main living area and secondly the

    rest of the home.

    The SAP calculation procedure in

    this study uses outside weather

    conditions specified monthly and also

    allows the UK regional weather to be

    specified if required. In this study the

    SAP region used is the “UK Average”

    [1] as it fairly represents the average

    weather conditions for space heating

    energy use calculations in the UK.

    5

    Running cost report_Inside Pages.indd 5 27/11/2014 15:44

  • Home 1

    The first home type used

    is a 1 Bedroom, 40m2 in

    with an originally designed

    minimum SAP space heating

    energy requirement

    of 6840kWh.

    Home 2

    The second home used is a 2

    Bedroom, 65m2

    originally designed minimum

    SAP space heating energy

    consumption of 10610kWh.

    Home 3

    The third home type used is

    a 3 Bedroom, 90m2

    area, semi-detached home

    with an originally designed

    SAP minimum space heating

    energy consumption

    of 15910kWh.

    For all three types of

    property two types of

    construction were assumed;

    first the originally built

    based on 1960s building

    regulation levels of

    insulation and air tightness

    (Tables 1 to 3) and secondly

    a refurbished level of

    insulation typical of building

    regulations in the 1990s

    (Tables 3 to 6).

    The physical parameters

    used for these constructions

    are described in Appendix

    A and were taken from the

    Energy Saving Trust’s report

    “Northern Ireland: assessing

    U-values of existing

    housing” [2].

    The BREDEM method

    uses these outside weather

    conditions to calculate the

    monthly space heating

    energy required to meet the

    empirically derived standard

    occupancy times and comfort

    temperatures of 21°C in the

    main living area and 18°C in

    the rest of the rooms. The

    energy use calculation is

    based on the conservation

    of energy principle that

    requires the average internal

    temperatures for the

    house to be derived for the

    different heating systems

    whilst satisfying the required

    comfort temperatures during

    the standard (on average)

    occupancy times.

    The running costs of electric

    heating systems in this paper

    are calculated using energy

    consumptions derived

    using SAP2012 energy use

    estimation methods. This

    energy use is combined with

    a standard electric heating

    tariff and an Economy 7 tariff

    with kWh use unit rates as

    stated in SAP2012 Table 12

    [1]. With these assumptions

    the SAP2012 calculation

    procedure has been used

    in the comparison study

    described in this paper to

    predict the space heating

    running costs for 3 types

    of homes with two levels

    of insulation.

    The three types of home considered are typical of

    homes where electric heating is commonly used.

    6

    Running cost report_Inside Pages.indd 6 27/11/2014 15:44

  • Different Types of

    Electric Heating and their

    SAP performance models

    Direct acting heating in SAP is defined

    as an electric heating system that has a

    responsiveness of 1 and perfect tracking of

    room temperature. A responsiveness of 1

    usually describes a heating system that can

    go from zero heat output to maximum heat

    output with time constant response of less

    than 5 minutes.

    Perfect tracking of room temperature

    requires a room by room thermostat, i.e.

    a thermostat fitted to each heater. The

    heaters that SAP considers to be of Direct

    acting type include, but are not confined

    to; Panel convector heaters, radiant panel

    heaters (oil or ceramic filled), fan heaters

    and aluminium/oil filled radiators. In

    SAP modelling all these heaters have the

    same responsiveness and controllability

    and there is NO variation in running cost

    predictions in SAP2012 between

    these systems.

    In the study three types

    of 100% efficient electric

    heating systems have been

    modelled using SAP2012,

    they are as follows:

    Direct Acting (Direct):

    Manually Charged Storage

    and Secondary Direct

    Acting Heaters (Storage):

    This heating system is defined

    in SAP2012 and consists of

    the modern high heat retention,

    digitally controlled fan assisted

    storage heaters with secondary

    direct acting heating

    (such as panel convector heaters).

    High Heat Retention

    Storage and Secondary

    Direct Acting Heaters

    (High Ret):

    This heating system consists of

    traditional manually charged

    (i.e. no automatic charging of

    the store) static storage heaters

    (i.e. no fan or integrated radiant

    panel heater) in the home with

    secondary direct acting heaters

    (such as panel convector heaters)

    in, for example, bedrooms

    and bathrooms.

    7

    Running cost report_Inside Pages.indd 7 27/11/2014 15:44

  • Heating System Type

    Electric heating system types and examples used in this SAP2012 comparative study

    Direct Acting

    using Standard

    Rate Tariffs

    [1] (Direct)

    High heat retention

    Storage Heaters &

    Secondary Direct

    Acting using E7

    Tariff [1] (HHRS)

    Manual Storage &

    Secondary Direct

    Acting Heaters

    using an E7 Tariff

    [1] (Storage)

    8

    Running cost report_Inside Pages.indd 8 27/11/2014 15:45

  • Relative Heating

    Systems’ Performances

    The SAP results for the three heating systems described in Table 1 were calculated

    assuming; SAP standard occupancy and thermal comfort requirements; “UK Average”

    regional weather conditions and electricity tariffs described in SAP2012 Table 12 [1].

    For the three case study homes as originally built these results are shown in the

    following tables:

    The original homes have been assumed to be

    of a fabric and glazing typical of the 1960s

    building standards. This was when many of

    Within a reasonable budget it is feasible

    to upgrade these homes with new UPVc

    double glazed windows, draught proofing

    and internal or external insulation to bring

    homes up to insulation standards typical of

    the 1990s building fabric standards.

    All the key parameters for areas and

    insulation for the original and refurbished

    homes used in this comparative study are

    given in Appendix A. The same three homes

    assumed to be refurbished to the equivalent

    of 1990s insulation levels according to SAP

    calculations again using tariffs described in

    SAP2012 [1] gave the following SAP results

    in Tables 4 to 6:

    Heating System Tariff Running Cost (£)

    Direct Acting Convectors or Electric Radiators Standard £902

    Manual Charge Storage & Convectors E7 £664

    High Heat Retention storage & Convectors E7 £494

    Table 1 - 40m2 1 Bed Flat as built with typical 1960s Building Regulations (refer Appendix A)

    Heating System Tariff Running Cost (£)

    Direct Acting Convectors or Electric Radiators Standard £1399

    Manual Charge Storage & Convectors E7 £985

    High Heat Retention storage & Convectors E7 £745

    Table 2 - 65m2 2 Bed Flat as built with typical 1960s Building Regulations (refer Appendix A)

    Heating System Tariff Running Cost (£)

    Direct Acting Convectors or Electric Radiators Standard £2099

    Manual Charge Storage & Convectors E7 £1542

    High Heat Retention storage & Convectors E7 £1124

    Table 3 - 90m2 3 Bed Semi-detached Home with 1960s Building Regulations (refer Appendix A)

    9

    Running cost report_Inside Pages.indd 9 27/11/2014 15:45

  • Heating System Tariff Running Cost (£)

    Direct Acting Convectors or Electric Radiators Standard £523

    Manual Charge Storage & Convectors E7 £371

    High Heat Retention storage & Convectors E7 £291

    Table 4 - 40m2 1 Bed Flat as refurbished with typical 1990s Building Regulations (refer Appendix A)

    Heating System Tariff Running Cost (£)

    Direct Acting Convectors or Electric Radiators Standard £849

    Manual Charge Storage & Convectors E7 £575

    High Heat Retention storage & Convectors E7 £455

    Table 5 - 65m2 2 Bed Flat as refurbished with typical 1990s Building Regulations (refer Appendix A)

    Heating System Tariff Running Cost (£)

    Direct Acting Convectors or Electric Radiators Standard £1248

    Manual Charge Storage & Convectors E7 £857

    High Heat Retention storage & Convectors E7 £663

    Table 6 - 90 m2 3 Bed Semi-detached with typical 1990s Building Regulations (refer Appendix A)

    In both the original and the refurbished case studies it can be observed from Tables 1 to 6

    that the High Heat Retention Storage (HHRS) heating system achieves a running cost on

    an Economy 7 (E7) tariff almost half that of direct acting heating on a standard tariff.

    10

    Running cost report_Inside Pages.indd 10 27/11/2014 15:45

  • Potential Impact of Electric Heating

    Choices on Fuel Poverty

    The running costs for the three homes as they were built

    (assumed to be in the 1960s) for the three heating systems as

    estimated by SAP are shown in the column chart Figure 1 below:

    £500.00

    £0.00

    £1,000.00

    £1,500.00

    £2,000.00

    £2,500.00

    1 BED FLAT 2 BED FLAT 3 BED SEMI

    Direct (Standard)

    Storage (E7)

    HHRS (E7)

    Figure 1: Annual space heating running costs (£) for all

    heating systems in the three original homes

    The advantage of the HHRS heating system

    running costs is achieved by utilising 90%

    of the electricity at the E7 off-peak rate.

    SAP2012 and other price research such as

    the Sutherland tables (April 2014 SE England)

    which is a reputable and established source

    of independent and impartial information on

    domestic heating costs, state that the E7

    off-peak electricity unit price to be less than

    40% of the standard electricity tariff unit price.

    The HHRS heating system is a revolution in

    storage heating as it achieves 90% E7

    off-peak electricity use without

    over-heating the home which results from

    poor temperature control normally associated

    with older storage heating systems. Even

    more modern storage convectors with manual

    charging shown in this comparison study

    overheat according to SAP by an average of

    0.7°C. According to SAP, the results shown in

    Tables 1 to 6 indicate that modern convective

    storage heating systems typically use 25%

    more energy than HHRS heating systems and

    cost over 35% more to run in some poorly

    insulated homes.

    11

    Running cost report_Inside Pages.indd 11 27/11/2014 15:45

  • It is clear from both Figures 1 and 2 that the

    most cost effective of the heating systems

    in this study in terms of running costs is

    the HHRS heating systems operating on an

    Economy 7 tariff. With its vastly improved

    controllability and its superior running costs

    the modern HHRS heating system using

    Economy 7 [1] compared with the Direct

    acting system using a Standard Electricity

    tariff [1] presents the best conventional

    electric heating solution for homes aiming

    to reduce running cost and fuel poverty.

    These running costs are also predicted

    by assuming that the SAP’s standard

    occupancy comfort conditions are achieved

    (e.g. The average expected comfort

    conditions of a UK homes) and thus present

    a high level of confidence that the running

    costs will be achieved with thermal comfort

    conditions at levels expected by all in a

    modern UK society.

    The relative percentage savings by

    HHRS heating systems improves slightly as

    a home is refurbished with better glazing,

    draught proofing, building fabric and roof

    insulation. There is a lot of confusion with

    government bodies, architects, heating

    system designers, installers and users to

    why storage based heating systems can

    deliver much lower running costs whilst

    using more energy, improve thermal

    comfort and reduce building fabric and

    glazing condensation.

    The energy increase especially from

    modern HHRS heating systems is very

    small compared with the benefit of using

    90% of the heating energy required using

    electricity which is less than half the price

    of that of Standard Rate electricity, i.e. off-

    peak electricity generally available between

    midnight and 7am in the morning every day

    of the week and throughout the year.

    The running costs for the homes refurbished to insulation standards

    typical of 1990s building regulations for the three heating systems

    are shown in column chart Figure 2 below.

    1 BED FLAT 2 BED FLAT 3 BED SEMI

    £200.00

    £400.00

    £600.00

    £800.00

    £1,000.00

    £1,200.00

    £1,400.00

    £0.00

    Direct (Standard)

    Storage (E7)

    HHRS (E7)

    Figure 2: Annual space heating running costs (£) for all

    heating systems in the three refurbished homes

    12

    Running cost report_Inside Pages.indd 12 27/11/2014 15:45

  • Author’s Biography

    Dr John Counsell is the Managing Director of Advanced Control Partnerships Limited

    and a BRE Trust Fellow sponsored by BRE at the University of Liverpool where he is an

    active member of BRE’s and DECC’s SAP scientific integrity group. He was previously

    the R&D group manager for advanced domestic electric heating for the electricity

    industry at EA Technology and the holder of the BRE. Chair in Energy Utilisation at the

    University of Strathclyde.

    Author’s signature.

    Advanced Control Partnerships Limited

    54 Grange Cross Lane

    Wirral

    CH48 8BQ

    Email: [email protected]

    Any claims of significant energy saving due to more accurate digital control of room

    temperatures by direct acting heating is considered negligible (i.e. less than 1 or 2%)

    in the SAP2012 model.

    In SAP2012 the energy waste due to poor temperature control using Direct acting

    systems and HHRS heating systems is modelled as being identical, i.e. Zero!

    Conclusion

    In conclusion using the de facto model SAP2012 for prediction of space heating energy

    consumption in UK homes, this comparison study showed that HHRS heating systems

    using an E7 tariff [1] on average reduce running costs compared with Direct Acting

    systems using a Standard Rate tariff [1] by between 45 and 47%.

    13

    Running cost report_Inside Pages.indd 13 27/11/2014 15:45

  • House Parameter / Description Value / Units

    Wall Fabric U value 0.55 W/K/m2

    Roof U value 0.35 W/K/m2

    Suspended sealed Floor U value 0.45 W/K/m2

    Non sealed, Wooden Frame Single Glazing U value 3.1 W/K/m2

    Living area fractions 1 bed = 0.5

    2 bed = 0.4

    3 bed = 0.3

    House Parameter / Description Value / Units

    Wall Fabric U value 1.7 W/K/m2

    Roof U value 1.5 W/K/m2

    Suspended sealed Floor U value 0.6 W/K/m2

    Non sealed, Wooden Frame Single Glazing U value 4.84 W/K/m2

    Living area fractions 1 bed = 0.5

    2 bed = 0.4

    3 bed = 0.3

    Table A1 - Home SAP parameters as originally built, assumed to be in the 1960s [2]

    Table A2 - Home SAP parameters as refurbished to 1990s insulation levels [2]

    Heating System Type and Control SAP Parameters Value

    Direct Acting using Standard Rate

    Tariffs [1] (Direct)

    SAP Heating Type:

    SAP Responsiveness (R):

    SAP Percentage from Secondary Direct-acting heaters

    1

    1

    0%

    Manual Storage & Secondary

    Direct Acting Heaters using an

    E7 Tariff [1] (Storage)

    SAP Heating Type:

    SAP Responsiveness (R):

    SAP Percentage from Secondary Direct-acting heaters

    5

    0.2

    15%

    High heat retention Storage Heaters

    & Secondary Direct Acting using

    E7 Tariff [1] (High Ret)

    SAP Heating Type:

    SAP Responsiveness (R):

    SAP Percentage from Secondary Direct-acting heaters

    2

    0.8

    10%

    Table A1 - Heaters’ SAP2012 Parameters

    References

    1. BRE (Published on behalf of DECC), “SAP2012, The Government’s Standard

    Assessment Procedure for Energy Rating of Dwellings”, 2012 Edition,

    rev February 2014.

    2. Energy Savings Trust, “Energy Efficiency Best Practice in Housing, Northern

    Ireland: assessing U-values of existing housing”, March 2005, CE127.

    14

    Running cost report_Inside Pages.indd 14 27/11/2014 15:45

  • 15

    Running cost report_Inside Pages.indd 15 27/11/2014 15:45

  • Running Costs of Conventional

    Electric Space Heating Systems

    Dr John Counsell

    Advanced Control Partnerships Limited

    A

    B

    CD