INDIVIDUALINNOVATIVEENERGY-SAVING

FOR REVOLVING AND CURVED SLIDING DOORS

RONDELL EC

RONDELL ECRONDELL ECRONDELL EC

RONDELL EC

RONDELL EC

Page 2: RONDELL EC - TEKADOOR

Discharge support always in the radius of the revolving doorswith discharge fins for optimum air distribution, powder coated with RAL colours

+

Heating connectionsat the side (left or right), optional also possible on the intake side

+Self-supporting, industrially-galvanised sheet steel housingpowder-coated on request

+

+ Discharge ductwith connection flange

ApplicationsRondell EC is "The" door air curtain for revolving doors. The unit is delivered complete with a discharge duct and support, including discharge fins, in three installation variants. These variants can be installed on top of, integrated into or in front of the door.

Special designWith every rotation, revolving doors bring in cold external air. Particularly for highly-frequented doors, a "cold patch" forms on the floor directly behind the revolving door. By using our door air curtain system "TEKADOOR Rondell EC", with an integrated air outlet especially adapted to the door radius, the spread of cold air is prevented and the recirculating air is warmed up to room temperature. This results in a pleasant indoor climate in the entry area. The design of the Rondell EC air curtain is always individual, corresponding to the existing or planned revolving door, whereby the discharge support with integrated fins is adapted to the door radius.

The housingThis consists of an industrially-galvanised self-supporting sheet steel housing with intake grille and duct connection flange, discharge duct with support and integrated discharge fins. All the visible parts can be powder coated in standard RAL colours, depending on the wishes of the client. Fascia covers can be manufactured in RAL colours or, optionally, in stainless steel.Inspection panel optionally from above or below.

Heating mediaHeat exchangers for different heating mediaLPHW: for normal temperature LPHW 70/50°C and low-temperature LPHW 60/40°C, other temperatures available on request. DX: DX register soldered under nitrogen for operation with heat pumps (only heating modus possible). High-quality heat exchanger made from copper tubes, with pressed-on, extra-strong aluminium fins.ELECTRO: 3-stage heat exchanger 400V, spiral form, corrosion resistant, with thermal overheating protection and switch-off delay.

DESIGN AIR CURTAINRONDELL EC

2

Page 3: RONDELL EC - TEKADOOR

Advantages at a glanceMade in Germany

ErP conform / EC fans

Certified by TÜV-Süd

Individual solutions / custom-made depending on the revolving door

Different heating media possible

Service-friendly thanks to filterless intake grille

Individual colours – standard RAL colours available

Low noise, optimum shielding

+

+

+

+

++

+

EC fansThe efficiency of the EC fans used by TEKADOOR is > 90% under partial load operation. This is 30–35% higher than for conventional AC fans. This does not just increase the efficiency, but also reduces the operating costs. The individually-driven EC fans with integrated motor protection can intake air in both directions. They have vibration-free bearings and are controlled using a PWM signal (pulse width modulation) – and with 0-10 V for the DX. They do not just comply with Directive ErP, but actually exceed this standard.

MountingSimple mounting thanks to the incorporated M8 rivet nuts on the top or at the sides of the unit (4 on each side).Accessories for mounting on the revolving door (top mounted unit) consist of two rectangular tubes and a set of bolts.

Maintenance Easy to clean without opening the unit by simply vacuuming the intake grille. The inspection panel can be removed completely for maintenance work.

Control Electronic TEKADOOR GTC EC control unit, multifunctional with touch display, including an optional ModBus interface A GTC 1 EC control unit is used as standard for models with LPHW heating. A GTC E EC control unit is used for models with electrical heating. The units come with 20 m preassembled and shielded data cable. The GTC 1 EC 5-stage control unit includes the ability to switch from manual to automatic and from summer mode to winter mode as standard. A solenoid valve of up to 2.5 A can be connected as an option for the winter mode. With the standard GTC E EC control unit, the airflow can be selected manually in 5 stages and the heating capacity – de-pending on the fan level – can be selected manually in 3 stages. Each control unit includes a manual to automatic mode switch and a potential-free contact for enabling via any on-site BMS or BEMS. A choice of 5-stage or stepless fan operation is offered as standard.A maximum of 10 units can be connected in parallel.

Intake grille+

+Inspection panel can be removed completely, optionally from above or below.

+

Electrical connectionsat the side, left or right

+

3

Page 4: RONDELL EC - TEKADOOR

Connections

Heating connections – flow and return –for easy connection to the on-site heating system. (Internal thread dimensions depend on the model series)

Connection box (LPHW)

Simple electrical connection via connection box (voltage supply 230V/50 Hz at the side of the unit).

Exception:Electrical units with a heating capacity greater than 22,5kW.

DETAILSRONDELL EC

4

Page 5: RONDELL EC - TEKADOOR

Data cable connection/interface

Simple, standard plug and play connection of the data cable and an optional solenoid valve.

Control:Input for the data cable to the control unit.

Auxiliary:Output for parallel operation with other units.

Discharge duct

Discharge duct with guide plates (corresponding to the number of fans installed) consisting of a support adapted to the radius of the revolving door and vertically arranged fixed fins. All surfaces of the parts visible from below are powder coated in standard RAL colours according to the customer's wishes.

5

Page 6: RONDELL EC - TEKADOOR

RONDELL EC

Rondell, Top mounted type AB

For use on revolving doors: installed on top of the door system body. Mounting of the air curtain system with discharge duct on top of the doors; the recirculating air is sucked in through the front of the unit. The discharge support – adapted to the door's outer radius – with integrated fins, is situated in front of the door's fascia. An additional cover can be mounted in front of the discharge support for architectural reasons. Covers and surfaces of all the parts visible from below are powder coated in standard RAL colours according to the customer's wishes. Heating and electrical connections can be made either from above or from the side. Inspection panel optionally from above or below.

Rondell, Integrated type EB

For use on revolving doors: integrated in the door system body. Mounting of the air curtain system with discharge duct within the door system; the recirculating air is sucked in through suitable air replacement grilles provided on-site by the client. The discharge support – adapted to the door's inner radius – with integrated fins, is installed within the door system. The surfaces of all the parts visible from below are powder coated in standard RAL colours according to the customer's wishes. Heating and electrical connections can be made either from above or from the side. Inspection panel optionally from above or below.

Rondell, Front mounted type VB

For use on revolving doors: installed in front of the doors. Mounting of the air curtain system with discharge duct in front of the door (inside the building), e.g. in the suspend-ed ceiling. The recirculating air intake is either from the suspended ceiling or from below via an additional intake chamber. The discharge support – adapted to the door's outer radius – with integrated fins, is situated outside the door system, in front of the door's fascia. An additional cover can be mounted in front of the discharge support for architectural reasons. Covers and surfaces of all the parts visible from below are powder coated in standard RAL colours according to the customer's wishes.Heating and electrical connections can be made either from above or from the side. Inspection panel optionally from above or below.

TYPESRONDELL EC

6

Page 7: RONDELL EC - TEKADOOR

RONDELL EC

The design

We need the following principal data to design the door air curtain system:

Important for the size of the unit are

Drum diameter: DT =

Entrance width: DB =

Fascia height: HA =

Please name the responsible contact person with whom we can agree the design.

Name:

Company:

Telephone:

Telefax:

e-mail:

Type of installation: Integrated (EB) Top mounted (AB) Front mounted (VB)

For the calculation of the air volume

Headroom/discharge height HT =

Number of door leaves FZ =

Passage angle =

Drum speed / min. dZ =Standard 3 to 4 rotations/min

For the configuration of the heatertA Reference outside temperature(depends on installation location)

e.g. -14 °C for Berlin but -10 °C for Düsseldorf

Available heating mediaLow-pressure hot water LPHW =

Electrical energy =

If known

Door manufacturer:

Type:

Surface / RAL colour:

Additional covers:(across the entire internal area (approximate total 180°))

mm

°

rpm

°C

°C

V

mm

mm

mm

Air curtain

Revolving door

DT

HA

HT

DBDB

7

Page 8: RONDELL EC - TEKADOOR

Connection-ready door air curtain system with intake at the front and discharge support fitted to the door radius.

TOP VIEW

Rondell, Top mounted type AB

Rondell, Integrated type EB

SECTION A–A

SECTION A–A

AA + 200

D

TD

A

AD

EH

100

40160

H

D 50D

B

Z

A

A - A

AA + 200

D

TD

A

AD

EH

100

40160

H

D 50D

B

Z

A

A - A

AA + 200

D

AAD

E

H

100

D 50D

B

Z

DT

A - A

ID

TD

AA + 200

D

AAD

E

H

100

D 50D

B

Z

DT

A - A

ID

TD

TOP VIEW

8

Page 9: RONDELL EC - TEKADOOR

Basic unit / total length Supply air support design

A (mm) = Length A-50 (mm) = Width supply air support E (mm) = Height DT (mm) = Drum diameterD (mm) = Depth DA (mm) = External duct diameter DI (mm) = Internal air duct diameter DZ (mm) = Max. depth supply air support HA (mm) = Fascia height HB (mm) = Cover height

Connection-ready door air curtain system with intake at the front and discharge support fitted to the door radius.Unit to be installed in the suspended ceiling in front of the door.

Rondell, Front mounted type VB

SECTION A–ATOP VIEW

100

A - A

D

240 D 50

A

D

A - 50

T

TD

100

A - A

D

240 D 50

A

D

A - 50

T

TD

9

Page 10: RONDELL EC - TEKADOOR

10

OPTIONAL ACCESSORIESRONDELL EC

Thermostatic 3-way valve

(Setting range from +20°C to +35°C)Limits the discharge temperature (constant supply air temperature limitation).Also available as a straight-way valve.

Flexible heating connections

Flexible heating connections with threaded connections for flow and return.

Length approx. 1 metre each

Control unit GTC 2 ECincluding an optional ModBus interface

Possibility of combination of various automatic operations. A constant discharge temperature can be set via an optional electronic control valve, and a week timer is incorporated as standard, enabling up to 12 different switching times to be programmed per week.

Page 11: RONDELL EC - TEKADOOR

11

Frost protection thermostat

For monitoring LPHW heat exchangers exposed to the risk of frost. As soon as the temperature falls below +7 °C, the fans are switched off and an optional solenoid valve is opened.

Solenoid valve

Opens or closes the heating water circuit in the summer/winter setting of the control unit, to close the heating water circuit during summer operation or when the air curtain is not working (normally closed).

Caution: If solenoid valves or thermo-electric shut-off valves are used, it is expressly recommended to install a frost protection thermostat (automatically actuated) and a strainer.

Electronic control valve

Electronic valve with 0-10V impulse and blow-out tem-perature sensor completely installed and wired. In combi-nation with the GTC 2 control, a preselected blow-out tem-perature is kept constant.

Cable temperature sensor

Cable sensor for detecting the actual temperature combined with the GTC 1 EC and GTC E EC control units. Includes 10 metres connection cable.

Page 12: RONDELL EC - TEKADOOR

STANDARD CIRCUIT DIAGRAM FOR LPHWRONDELL EC

230V/ 50Hz

3

CONTROL

F 16 AT

L N PE

Platine EC

Anschlußbox

bauseitig

Erdung, Nullung oderSchutzschaltung nachden Vorschriften desVDE und des zuständ.EVU ausführen.

Technische Änderungen vorbehalten

Störun

g pot.

-frei

Betrie

b pot.

-frei

1 211 12 133 4 514 15

0

zum Steuerteil (CONTROL)Adresse 1-9

8

AUXILIARNL2 PE

230V / 50Hz

Magnetventil(OPTIONAL)

L PEN

8

PENL2

internAUX MON

07.03.2017lagezeichnet/signet

TeileGruppevonPos.

Werkstoff Maßstab

Blatt

Erstelldatum

GTM EC MOD Bus 170307Kunde

BenennungName

Kundenzeichnung Nr.:

DatumName

1 von 1

6 716 17 8 9 10 1918 20

CPU

AdressSchalter0 = MASTER1 - 9 = SLAVE

5

1 23

4

9

87 6

nicht

beleg

t

nicht

beleg

t

nicht

beleg

t

nicht

beleg

t

Fros

tschu

tzthe

rmos

tatop

tiona

l

Standard Anschlusskabel(20 m) mitRJ-45 Stecker

1M

PENL1

zu weiterenVentilatoren

blau/blue

gelb/yellow

weiss/white

rot/red

4

321

RJ 45

MOD Bus 1 2 3 4

ON

optio

nal

ext. S

ignalg

eber

DDC-

Fre

igab

e op

tiona

l

Y PWM

0 V

+10 V

imp.

ModBusinterface(optional)

230V/ 50Hz

3

CONTROL

F 16 AT

L N PE

PCB EC

Connecting box

Main switch and fusesto be installed by thirdparties must complyto all applicable rules andrequirements!

Technical changes reserved

1 211 12 133 4 514 15

0

to input (CONTROL) next PCBAddress 1-9

8

AUXILIARNL2 PE

230V / 50Hz

Magnetic valve(OPTIONAL)

L PEN

8

PENL2

internAUX MON

02.01.2019lagezeichnet/signet

TeileGruppevonPos.

Werkstoff Maßstab

Blatt

Erstelldatum

GTC I EC 190102Kunde

BenennungName

Kundenzeichnung Nr.:

DatumName

1 von 1

6 716 17 8 9 10 1918 20

CPU

Addressswitch0 = MASTER1 - 9 = SLAVE

5

1 23

4

9

87 6

ext. C

ontac

t

fault

Opera

tion

Fros

t prot

ectio

n the

rmos

tat

not u

sed

not u

sed

nicht

beleg

t

optio

nal

optio

nal

Standard suppledshielded datacable(20 m) withRJ-45 connectors

1M

PENL1

next Fan

blau/blue

gelb/yellow

weiss/white

rot/red

4

Room

temp.

sens

orop

tiona

l

Room temperature. Sensor installed

q

BMS

On/O

ff

Y 0-10 V

0 V

+10 V

imp.

Timeroff

Fr 21.09.201807:52

Heat level0 / 0

AutomaticHand

Room Temp10°C

Fan level0 / 0

CONTROL UNIT GTC 1 ECMultilingual, menu-driven electronic control unit for TEKADOOR air curtains with LPHW heating and energy-saving EC fans. A standard feature of the control unit with touch display is a choice between 5-stage or stageless fan control, which can be selected individually by the operator. The relevant operating modes and symbols are arranged clearly on the colour display. The date, time and room temperature are shown as standard. The room temperature is monitored via an internal temperature sensor in the control unit as standard.

An easy-to-navigate menu offers a selection of different operating modes:Hand – manual operationAuto AS – automatic operation via cool down protectionAuto RT – automatic operation via room temperatureAuto TK – automatic operation via door contactAuto Kombi – option to combine all individual automatic modes

An enabling contact and potential-free operation and malfunction signals are provided for control via an on-site BMS or BEMS. Errors and faults are displayed with a red „warning“ sign. By coding the control boards differently, up to 10 door air curtains can also be operated in parallel with 1 control unit, using the Master/Slave principle. The control board is preinstalled in the door air curtain unit and 20 m of preassembled data cable (connection between the door air curtain and control unit) are included as standard.

* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES

12

Page 13: RONDELL EC - TEKADOOR

CIRCUIT DIAGRAM ELECTRICAL HEAT EXCHANGERRONDELL EC

* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES

230V/ 50Hz

3

CONTROL

F 16 AT

L N PE

Platine EC

Anschlußbox

bauseitig

Erdung, Nullung oderSchutzschaltung nachden Vorschriften desVDE und des zuständ.EVU ausführen.

Technische Änderungen vorbehalten

Störun

g pot.

-frei

Betrie

b pot.

-frei

1 211 12 133 4 514 15

0

zum Steuerteil (CONTROL)Adresse 1-9

8

AUXILIARNL2 PE

230V / 50Hz

Magnetventil(OPTIONAL)

L PEN

8

PENL2

internAUX MON

07.03.2017lagezeichnet/signet

TeileGruppevonPos.

Werkstoff Maßstab

Blatt

Erstelldatum

GTM EC MOD Bus 170307Kunde

BenennungName

Kundenzeichnung Nr.:

DatumName

1 von 1

6 716 17 8 9 10 1918 20

CPU

AdressSchalter0 = MASTER1 - 9 = SLAVE

5

1 23

4

9

87 6

nicht

beleg

t

nicht

beleg

t

nicht

beleg

t

nicht

beleg

t

Fros

tschu

tzthe

rmos

tatop

tiona

l

Standard Anschlusskabel(20 m) mitRJ-45 Stecker

1M

PENL1

zu weiterenVentilatoren

blau/blue

gelb/yellow

weiss/white

rot/red

4

321

RJ 45

MOD Bus 1 2 3 4

ON

optio

nal

ext. S

ignalg

eber

DDC-

Fre

igab

e op

tiona

l

Y PWM

0 V

+10 V

imp.

ModBusinterface(optional)

Blow

out T

emp s

enso

r

CONTROL

PCB EC

Technical changes reserved

1 211 12 133 4 514 15

0

to inputCONTROLnext PCB

8

AUXILIAR

8

AUX MON

02.01.2019Sagezeichnet/signet

TeileGruppevonPos.

Werkstoff Maßstab

Blatt

Erstelldatum

GTC E EC UK 190201Kunde

BenennungName

Kundenzeichnung Nr.:

DatumName

1 von 1

6 716 17 8 9 10 1918 20

CPU

Adressswitch0 = MASTER1 - 9 = SLAVE

5

1 23

4

9

87 6

Failu

re

Oper

ation

free

Standard supplied shielded datacable (20 m)1:1 straight wired RJ-45 Stecker

S 50°K1

K1 K2 K3

S 80°

S 60°

q q

q

q

K1

Connecting box

Mains switch and fusesto be installed by thirdparties must complyto all applicable rules andrequirements!

BMS

On/O

ff

1M

PENL1

nextFan

blau/blue

gelb/yellow

weiss/white

rot/red

optio

nal

4

free

step 2step 3 = step 1 + step 2

step 1

NL2 PE

PENL2intern

230V / 50Hz

K3 K2

230V/ 50Hz

3

3~400V/ 50Hz4

K0

q

ext.

Sign

alop

tiona

l

Fros

t the

rmos

tat

optio

nal

Room

Tem

p se

nsor

q q

Room temperature. Sensor installed

S 45°

YPWM

0 V

+10 V

imp.

L N PE31 2

S 100°

F 16 AT

Timeroff

Fr 21.09.201807:52

Heat level0 / 0

AutomaticHand

Room Temp10°C

Fan level0 / 0

CONTROL UNIT GTC E EC Multilingual, menu-driven electronic control unit for TEKADOOR air curtains with LPHW heating and energy-saving EC fans. 5-stage fan operation or stageless fan control – easy to adjust on the control unit using the touch display. The electric heater can be activated in 3 stages.The relevant operating modes and symbols are arranged clearly on the colour display. The date, time and room temperature are shown as standard. The room temperature is monitored via an internal temperature sensor in the control unit as standard. An easy-to-navigate menu offers a selection of different operating modes: Hand – manual operation Auto AS – automatic operation via cool down protection Auto RT – automatic operation via room temperature Auto TK – automatic operation via door contact Auto AT – automatic operation via constant discharge temperature Auto Kombi – option to combine all individual automatic modes An enabling contact and potential-free operation and malfunction signals are provided for control via an on-site BMS or BEMS. A constant discharge temperature can be set via an optional cable temperaturesensor. This enables optimisation of the shielding performance. A week timer is incorporated as standard, enabling up to 12 different switching times to be programmed per week. Errors and faults are displayed with a red „warning“ sign. By coding the control boards differently, up to 10 door air curtains can also be operated in parallel with 1 control unit, using the Master/Slave principle.The control board is preinstalled in the door air curtain unit and 20 m of preassembled data cable (connection between the door air curtain and control unit) are included as standard. 13

Page 14: RONDELL EC - TEKADOOR

RONDELL ECSTANDARD CIRCUIT DIAGRAM FOR LPHW (OPTIONAL)

230V/ 50Hz

3

CONTROL

F 16 AT

L N PE

Platine EC

Anschlußbox

bauseitig

Erdung, Nullung oderSchutzschaltung nachden Vorschriften desVDE und des zuständ.EVU ausführen.

Technische Änderungen vorbehalten

Störun

g pot.

-frei

Betrie

b pot.

-frei

1 211 12 133 4 514 15

0

zum Steuerteil (CONTROL)Adresse 1-9

8

AUXILIARNL2 PE

230V / 50Hz

Magnetventil(OPTIONAL)

L PEN

8

PENL2

internAUX MON

07.03.2017lagezeichnet/signet

TeileGruppevonPos.

Werkstoff Maßstab

Blatt

Erstelldatum

GTM EC MOD Bus 170307Kunde

BenennungName

Kundenzeichnung Nr.:

DatumName

1 von 1

6 716 17 8 9 10 1918 20

CPU

AdressSchalter0 = MASTER1 - 9 = SLAVE

5

1 23

4

9

87 6

nicht

beleg

t

nicht

beleg

t

nicht

beleg

t

nicht

beleg

t

Fros

tschu

tzthe

rmos

tatop

tiona

l

Standard Anschlusskabel(20 m) mitRJ-45 Stecker

1M

PENL1

zu weiterenVentilatoren

blau/blue

gelb/yellow

weiss/white

rot/red

4

321

RJ 45

MOD Bus 1 2 3 4

ON

optio

nal

ext. S

ignalg

eber

DDC-

Fre

igab

e op

tiona

l

Y PWM

0 V

+10 V

imp.

interface(optional)

230V/ 50Hz

3

CONTROL

F 16 AT

L N PE

1 211 12 133 4 514 15

0

8

AUXILIARNL2 PE

230V / 50Hz

L PEN

8

PENL2

internAUX MON

02.01.2019segezeichnet/signet

TeileGruppevonPos.

Werkstoff Maßstab

Blatt

Erstelldatum

GTC II EC 190102Kunde

BenennungName

Kundenzeichnung Nr.:

DatumName

1 von 1

6 716 17 8 9 10 1918 20

CPU

5

1 23

4

9

87 6

q

optio

nal

optio

nal

1M

PENL1

blau/blue

gelb/yellow

weiss/white

rot/red

4

Blow

Out

Sens

or

q

230V

Analo

g Si

gnal

0-10 V

M 24V

7 17

LNG0

Y

G

optional

Siemens 2-WayValve optional

PE

PCB EC

Connecting box

Mains switch and fusesto be installed by thirdparties must comply to all applicable rules andrequirements!

Technical changes reserved

to inputCONTROLnext PCB

Magnetic valve(OPTIONAL)

Adressswitch0 = MASTER1 - 9 = SLAVE

ext. C

ontac

t

BMS

On/O

ff

Room

temp.

sens

or

Falilu

re

Opera

tion

Fros

t prot

ectio

n the

rmos

tat

free

Standard suppled shielded datacable(20 m) 1:1 straight wiredRJ-45 connectors next

Fan

Room temperature. Sensor installed

Y PWM

0 V

+10 V

imp.

Timeroff

Fr 21.09.201807:52

Heat level0 / 0

AutomaticHand

Room Temp10°C

Fan level0 / 0

EASY-TO-USE CONTROL UNIT GTC 2 EC Multilingual, menu-driven electronic control unit for TEKADOOR air curtains with LPHW heating and ener-gy-saving EC fans. A standard feature of the control unit with touch display is a choice between 5-stage or stageless fan control, which can be selected individually by the operator. The relevant operating modes and symbols are arranged clearly on the colour display. The date, time and room temperature are shown as standard. The room temperature is monitored via an internal temperature sensor in the control unit as standard. An easy-to-navigate menu offers a selection of different operating modes:Hand – manual operationAuto AS – automatic operation via cool down protectionAuto RT – automatic operation via room temperatureAuto TK – automatic operation via door contactAuto AT – automatic operation via constant discharge temperature (opt. electronic control valve required)Auto Kombi – option to combine all individual automatic modesAn enabling contact and potential-free operation and malfunction signals are provided for control via an on-site BMS or BEMS. A constant discharge temperature can be set via an optional cable temperaturesensor. This enables optimisation of the shielding performance. A week timer is incorporated as standard, enabling up to 12 different switching times to be programmed per week. Errors and faults are displayed with a red „warning“ sign. By coding the control boards differently, up to 10 door air curtains can also be operated in parallel with 1 control unit, using the Master/Slave principle.The control board is preinstalled in the door air curtain unit and 20 m of preassembled data cable (connection between the door air curtain and control unit) are included as standard.

* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES

ModBus

14

Page 15: RONDELL EC - TEKADOOR

TECHNICAL DATA

RONDELL EC 2000

RONDEL EC 2000 2001-2 2001.5-3 2002-5 2002.5-6 2003-8

Outside diameter m 2.5 2.5 4.8 3.6 6.0

Discharge height m 2.6 2.4 2.6 3.0 3.0

Passage angle ° 60 90 60 90 60

Air quantity max. m3/h 1800 2700 4500 5400 7200

Heating capacity rated1 LPHW 70 / 50 °C kW 8.5 12.7 21.2 25.5 34.0

LPHW 60 / 40 °C kW 8.5 12.7 21.2 25.5 34.0

Flow rate LPHW 70 / 50 °C m3/h 0.37 0.56 0.93 1.11 1.49

LPHW 60 / 40 °C m3/h 0.37 0.55 0.92 1.11 1.49

Water resistance LPHW 70 / 50 °C kPa 0.5 5.7 3.2 3.7 7.2

LPHW 60 / 40 °C kPa 3.8 7.0 3.2 4.2 7.2

Nominal connection sizes

Internal thread Inches 2 x 3/4" 2 x 3/4" 2 x 3/4" 2 x 3/4" 2 x 3/4"

Flow/return DN 20 20 20 20 20

EC fans Voltage V 230 / 1 / N / PE

Frequency Hz 50

Current consumption A 2.1 3.1 5.1 6.2 8.2

Motor power kW 0.3 0.5 0.8 0.9 1.2

Electric heater 3-stage

Voltage V 400 / 3 / N / PE

Frequency Hz 50

Heating capacity kW 3/6/9 4/8/12 6/12/18 10/20/30 10.7/21.4/32

Sound pressure level 2 Highest setting dB(A) 58 59 61 62 64

Dimensions of the basic unit without duct

Unit width mm 1000 1500 2000 2500 3000

Unit height mm 240 240 240 240 240

Unit depth mm 390 390 390 390 390

Weight of the basic unit without duct kg 45 60 80 102 125

Design based on: recommended operating pointintake temperature tLE = +20 °C

discharge temperature tLA = +34 °CSince the design and calculation of the air curtain is always individual,

corresponding to the existing or planned revolving door, a few examples are shown below.

1. Rated operation based on operating point (see above), discharge temperature control recommended. 2. Measured at a lateral distance of 3 m. Sound pressure level may very depending on surrounding conditions.

[DX-H available on request (only heating mode possible)]

A well-balanced pressure ratio is one of the prerequisites for perfect function.

* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES

15