robust decentralized approach to interactionmitigation in

14
CONPRA: 104346 Model 5G pp. 1โ€“14 (col. ๏ฌg: NIL) Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedance minimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346. Control Engineering Practice xxx (xxxx) xxx Contents lists available at ScienceDirect Control Engineering Practice journal homepage: www.elsevier.com/locate/conengprac Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedance minimization Adedotun J. Agbemuko a,b,โˆ— , Josรฉ Luis Domรญnguez-Garcรญa a , Oriol Gomis-Bellmunt b a IREC Catalonia Institute for Energy Research, Jardins de les Dones de Negre 1, 2a. 08930 Sant Adriร  de Besรฒs, Barcelona, Spain b Department of Electrical Engineering, Universitat Politรจcnica de Catalunya UPC, Av. Diagonal, 647, Pl. 2. 08028 Barcelona, Spain ARTICLE INFO Keywords: VSC-HVDC Transmission Multivariable control Impedance-based analysis Robust control H-infinity ABSTRACT An interconnection of independently designed voltage source converters (VSCs) and their control in high voltage DC grids can result in network-level detrimental interactions and even instability. In many cases, vendors are not willing to share proprietary information about their designs in a manner that allows the entire system to be designed considering the collective dynamics. Besides, such an endeavour is not realistic. In this paper, robust network-level global controllers are proposed to decouple interacting VSCs through an impedance shaping technique. Particularly, the global controllers are designed without any need to establish the internal controller structure of any VSC which is often proprietary. Rather, the global controllers rely on the externally measurable feedback impedance of each VSC in stand-alone and the rest of the system. It is demonstrated how robust convex optimization framework can be exploited to robustly shape global feedback impedances to obtain a decoupled network. The synthesized controllers are validated through nonlinear simulations of the physical model. 1. Introduction 1 Over the last decade, the electric power system has witnessed a re- 2 markable proliferation of power electronic converters in all areas of the 3 system (Bose, 2013). Particularly is the increasing adoption of voltage 4 source converter (VSC) interfaced DC circuits and systems (Flourent- 5 zou, Agelidis, & Demetriades, 2009; Hertem & Ghandhari, 2010; Schet- 6 tler, Huang, & Christl, 2000). Currently, the number of VSC-based 7 point-to-point high voltage DC (VSC-HVDC) links from different manu- 8 facturers and vendors is rapidly increasing. Progressively, it is expected 9 that these links will be interconnected to form multi-terminal DC 10 (MTDC) grids (Haileselassie & Uhlen, 2013; Staudt et al., 2014; Tour- 11 goutian & Alefragkis, 2017). On the alternative, multi-terminal grids 12 are also expected to be developed completely from the beginning; 13 desirably with control systems from multi-vendors. 14 An expected challenge is the issue of interoperability and coordi- 15 nation of independently designed and tuned converters after intercon- 16 nection. An immediate consequence of these is unintended interactions 17 between these converters at the network-level (Rault, 2019). Therefore, 18 from an external view, a network operator would have to determine 19 how to securely operate such independently designed systems, without 20 access to information that could be classified as proprietary. Such 21 include the internal structure, interconnection, and architecture of 22 control, and/or controller parameters among other information. Then, 23 โˆ— Corresponding author at: IREC Catalonia Institute for Energy Research, Jardins de les Dones de Negre 1, 2a. 08930 Sant Adriร  de Besรฒs, Barcelona, Spain. E-mail address: [email protected] (A.J. Agbemuko). there is a requirement to determine if network-level interactions war- 24 rant additional control actions. The subsequent step is the identification 25 of the mechanism of interaction and mitigation. 26 Literature is extensive on network-scale interaction studies (Beerten, 27 Dโ€™Arco, & Suul, 2016; Cole, Beerten, & Belmans, 2010; Kalcon, Adam, 28 Anaya-Lara, Lo, & Uhlen, 2012; Pinares, Tjernberg, Tuan, Breitholtz, & 29 Edris, 2013; Prieto-Araujo, Egea-Alvarez, Fekriasl, & Gomis-Bellmunt, 30 2016). However, many efforts at understanding these interactions are 31 based on the traditional stateโ€“space approach for which complete 32 knowledge of all states (network and converters) is implicitly assumed. 33 Moreover, stateโ€“space methods do not support independent design 34 philosophy (Amin, Rygg, & Molinas, 2016). In reality, a manufacturer 35 will often only provide black-box models of their devices. However, 36 during the design phase of each converter, it is impossible to know 37 the characteristics of all other devices that would be interconnected in 38 the future. Hence, it is impossible to design the converter for uncertain 39 scenarios. 40 In a multi-vendor HVDC grid, there are two broad perspectives 41 for control: the converter itself in stand-alone (vendor), and the in- 42 terconnected network of converters (operator) (Qoria et al., 2019). 43 From the view of the vendor, the main control objectives are tracking 44 and regulation, stand-alone stability, performance, and control channel 45 availability for additional control actions. Alternatively, from the view 46 of the operator, the main objectives are the stabilization of network 47 https://doi.org/10.1016/j.conengprac.2020.104346 Received 7 February 2019; Received in revised form 17 December 2019; Accepted 16 February 2020 Available online xxxx 0967-0661/ยฉ 2020 Elsevier Ltd. All rights reserved.

Upload: others

Post on 03-Apr-2022

3 views

Category:

Documents


0 download

TRANSCRIPT

CONPRA: 104346 Model 5G pp. 1โ€“14 (col. fig: NIL)

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

Control Engineering Practice xxx (xxxx) xxx

Contents lists available at ScienceDirect

Control Engineering Practice

journal homepage: www.elsevier.com/locate/conengprac

Robust decentralized approach to interaction mitigation in VSC-HVDC gridsthrough impedance minimizationAdedotun J. Agbemuko a,b,โˆ—, Josรฉ Luis Domรญnguez-Garcรญa a, Oriol Gomis-Bellmunt b

a IREC Catalonia Institute for Energy Research, Jardins de les Dones de Negre 1, 2a. 08930 Sant Adriร  de Besรฒs, Barcelona, Spainb Department of Electrical Engineering, Universitat Politรจcnica de Catalunya UPC, Av. Diagonal, 647, Pl. 2. 08028 Barcelona, Spain

A R T I C L E I N F O

Keywords:VSC-HVDC TransmissionMultivariable controlImpedance-based analysisRobust controlH-infinity

A B S T R A C T

An interconnection of independently designed voltage source converters (VSCs) and their control in highvoltage DC grids can result in network-level detrimental interactions and even instability. In many cases,vendors are not willing to share proprietary information about their designs in a manner that allows the entiresystem to be designed considering the collective dynamics. Besides, such an endeavour is not realistic. In thispaper, robust network-level global controllers are proposed to decouple interacting VSCs through an impedanceshaping technique. Particularly, the global controllers are designed without any need to establish the internalcontroller structure of any VSC which is often proprietary. Rather, the global controllers rely on the externallymeasurable feedback impedance of each VSC in stand-alone and the rest of the system. It is demonstratedhow robust convex optimization framework can be exploited to robustly shape global feedback impedances toobtain a decoupled network. The synthesized controllers are validated through nonlinear simulations of thephysical model.

1. Introduction1

Over the last decade, the electric power system has witnessed a re-2

markable proliferation of power electronic converters in all areas of the3

system (Bose, 2013). Particularly is the increasing adoption of voltage4

source converter (VSC) interfaced DC circuits and systems (Flourent-5

zou, Agelidis, & Demetriades, 2009; Hertem & Ghandhari, 2010; Schet-6

tler, Huang, & Christl, 2000). Currently, the number of VSC-based7

point-to-point high voltage DC (VSC-HVDC) links from different manu-8

facturers and vendors is rapidly increasing. Progressively, it is expected9

that these links will be interconnected to form multi-terminal DC10

(MTDC) grids (Haileselassie & Uhlen, 2013; Staudt et al., 2014; Tour-11

goutian & Alefragkis, 2017). On the alternative, multi-terminal grids12

are also expected to be developed completely from the beginning;13

desirably with control systems from multi-vendors.14

An expected challenge is the issue of interoperability and coordi-15

nation of independently designed and tuned converters after intercon-16

nection. An immediate consequence of these is unintended interactions17

between these converters at the network-level (Rault, 2019). Therefore,18

from an external view, a network operator would have to determine19

how to securely operate such independently designed systems, without20

access to information that could be classified as proprietary. Such21

include the internal structure, interconnection, and architecture of22

control, and/or controller parameters among other information. Then,23

โˆ— Corresponding author at: IREC Catalonia Institute for Energy Research, Jardins de les Dones de Negre 1, 2a. 08930 Sant Adriร  de Besรฒs, Barcelona, Spain.E-mail address: [email protected] (A.J. Agbemuko).

there is a requirement to determine if network-level interactions war- 24

rant additional control actions. The subsequent step is the identification 25

of the mechanism of interaction and mitigation. 26

Literature is extensive on network-scale interaction studies (Beerten, 27

Dโ€™Arco, & Suul, 2016; Cole, Beerten, & Belmans, 2010; Kalcon, Adam, 28

Anaya-Lara, Lo, & Uhlen, 2012; Pinares, Tjernberg, Tuan, Breitholtz, & 29

Edris, 2013; Prieto-Araujo, Egea-Alvarez, Fekriasl, & Gomis-Bellmunt, 30

2016). However, many efforts at understanding these interactions are 31

based on the traditional stateโ€“space approach for which complete 32

knowledge of all states (network and converters) is implicitly assumed. 33

Moreover, stateโ€“space methods do not support independent design 34

philosophy (Amin, Rygg, & Molinas, 2016). In reality, a manufacturer 35

will often only provide black-box models of their devices. However, 36

during the design phase of each converter, it is impossible to know 37

the characteristics of all other devices that would be interconnected in 38

the future. Hence, it is impossible to design the converter for uncertain 39

scenarios. 40

In a multi-vendor HVDC grid, there are two broad perspectives 41

for control: the converter itself in stand-alone (vendor), and the in- 42

terconnected network of converters (operator) (Qoria et al., 2019). 43

From the view of the vendor, the main control objectives are tracking 44

and regulation, stand-alone stability, performance, and control channel 45

availability for additional control actions. Alternatively, from the view 46

of the operator, the main objectives are the stabilization of network 47

https://doi.org/10.1016/j.conengprac.2020.104346Received 7 February 2019; Received in revised form 17 December 2019; Accepted 16 February 2020Available online xxxx0967-0661/ยฉ 2020 Elsevier Ltd. All rights reserved.

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

parameters, disturbance rejection, tolerance, network characterization,1

and robustness. From the traditional stateโ€“space modelling and analy-2

sis, assuming all the states are known, each perspective above could be3

classified into local and interaction behaviours (Beerten et al., 2016).4

A vendor will always ensure that local objectives are met and local5

modes are at least stable across the expected operating range. However,6

local stability does not necessarily translate to global stability or a non-7

interactive network (Agbemuko, Domรญnguez-Garcรญa, Prieto-Araujo, &8

Gomis-Bellmunt, 2019).9

This article deals with the aforementioned objectives from the10

perspectives of the operator. Specifically, robust mitigation of network-11

level interactions between VSCs through impedance minimization. In12

essence, this implies a disturbance rejection problem where additional13

controllers decouple the network of converters (from any arbitrary14

interfaces) from an external view. Other methods to decouple interac-15

tions include shaping impedances by retuning controller parameters of16

existing local control (Amin & Molinas, 2019). However, this assumes17

that the internal structure of local control is known, and there are18

no complex inter-dependencies of control loops such that changing19

the parameters of one loop requires modifying others. Therefore, in20

this paper, an external view is taken where existing local controllers21

are assumed unchangeable and only black-box models are available.22

Importantly, the local behaviour as established by the manufacturerโ€”23

tracking, stand-alone stability, etc. are not adversely affected by the ad-24

ditional decoupling controllers. Hence, local behaviour is maintained.25

Besides, such a view allows the development of scalable solutions.26

Impedance minimization techniques among many others fall under27

a large class of impedance shaping techniques. Many research efforts28

have exploited the modularity and scalability of impedance shaping29

approach from viewpoints of active damping, virtual impedance con-30

trol, to methods for passivating VSCs (Cรฉspedes & Sun, 2012; Freijedo,31

Rodriguez-Diaz, Golsorkhi, Vasquez, & Guerrero, 2017; Harnefors, Bon-32

giorno, & Lundberg, 2007; Harnefors, Yepes, Vidal, & Doval-Gandoy,33

2015; He & Li, 2012; Pea-Alzola, Liserre, Blaabjerg, Ordonez, & Yang,34

2014; Wang et al., 2014; Wang, Li, Blaabjerg, & Loh, 2015; Xin, Loh,35

Wang, Blaabjerg, & Tang, 2016; Yang, Ruan, & Wu, 2014). More36

recently, impedance shaping approaches have been fitted to exploit37

the superiority of existing robust control methods through convex38

optimization (Cobreces, Bueno, Rodriguez, Pizarro, & Huerta, 2010;39

Cรณbreces, Wang, Pรฉrez, Griรฑรณ, & Blaabjerg, 2018; Gabe, Montagner, &40

Pinheiro, 2009; Kammer, Dโ€™Arco, Endegnanew, & Karimi, 2019; Pรฉrez,41

Cobreces, Gri, & Sรกnchez, 2017). However, except in Kammer et al.42

(2019) where a multi-converter system is studied, the focus of existing43

research is often a single converter-grid interface, and a disproportion-44

ate share of research is focused on the AC side of the VSC. In such cases,45

the previously described perspectives and objectives easily overlap46

into one with an assumption of complete knowledge of the system47

states. Therefore, research into network-scale impedance shaping in48

a multi-converter meshed DC grid is relatively unknown, even less49

for interaction decoupling considering independently designed local50

controllers. More so using only grid available measurements.51

This paper presents a tractable and scalable methodology for robust52

decoupling of converters in VSC-HVDC grids of arbitrary structures,53

through impedance minimization. The method combines the inputโ€“54

output impedance responses of the converter and a multi-variable55

aggregation, and characterization of the interconnected network to56

determine if additional control action is required. Subsequently, inter-57

action analysis is done to determine the mechanism of interactions, and58

physical objectives are transformed into frequency domain specifica-59

tions. Finally, a decentralized โˆž fixed structure convex algorithm is60

exploited for the robust shaping of closed-loop impedances. This paper61

is an extension of the initial modelling and interaction analysis ef-62

forts presented in Agbemuko, Domรญnguez-Garcรญa, and Gomis-Bellmunt63

(2018) and Agbemuko et al. (2019). The main contributions of this64

paper are summarized below:65

Fig. 1. Schematic terminal-level diagram of a generic VSC.

Table 1System parameters.

Parameter Value Parameter Value

Rated power 800 MVA ๐ฟ 42 mHDC voltage 400 kV ๐ถ๐‘“ 10 ฮผFAC voltage 220 kV (p-p) ๐‘…๐‘” 0.048 ฮฉ๐ถ๐‘‘๐‘ 150 ฮผF ๐ฟ๐‘” 15 mH๐‘… 0.242 ฮฉ

1. Application of inputโ€“output frequency responses of the converter 66

and interconnected network to design coordinated decentralized 67

network controllers. 68

2. Tractable formulation of the overall problem from an external 69

view of the system with scalability to an arbitrary HVDC grid, 70

with applicability to any system including multi-vendor systems. 71

3. Design of low order parametrized robust controllers with a 72

simple structure to decouple network-scale interactions. 73

4. A method that incorporates flexibility for different approaches 74

from a multi-variable point of view. 75

This paper is organized as follows. Section 2 presents the numerically 76

estimated inputโ€“output impedance of a controlled VSC assuming black- 77

box models and verified with analytical derivations. Section 3 presents 78

the network aggregation and reformulation of the system into two 79

partitions for control design and the generalized procedures. Then, 80

Sections 4 and 5 applies the procedure to design global controllers for 81

a meshed HVDC grid. 82

2. Simplified inputโ€“output impedance response of a controlled 83

VSC 84

From a black-box overview, the terminal-level block diagram of a 85

synchronous reference frame VSC (Yazdani & Iravani, 2010), is shown 86

in Fig. 1. The system parameters of the VSC as shown in Fig. 1 87

is provided in Table 1. The aim here is to obtain the inputโ€“output 88

feedback impedance transfer function of the converter on the DC side 89

in the form 90

๐‘๐‘œ๐‘,๐‘–(๐‘ ) =๐›ฅ๐‘‰๐‘‘๐‘,๐‘–๐›ฅ๐ผ๐‘–

=๐‘๐‘š๐‘ ๐‘š +โ‹ฏ + ๐‘1๐‘  + ๐‘0

๐‘Ž๐‘›๐‘ ๐‘› + ๐‘Ž๐‘›โˆ’1๐‘ ๐‘›โˆ’1 +โ‹ฏ + ๐‘Ž1๐‘  + ๐‘Ž0(1) 91

where ๐‘๐‘œ๐‘,๐‘– is the feedback impedance and equivalent inputโ€“output 92

response of the VSC,1 ๐›ฅ๐‘‰๐‘‘๐‘,๐‘– is the DC-bus voltage response to local 93

disturbance (without interconnection), ๐›ฅ๐ผ๐‘– is the bus current changes 94

during disturbance, and the coefficients of ๐‘๐‘œ๐‘,๐‘– may be arbitrary. In 95

this paper, a numerically estimated transfer function from inputโ€“output 96

time-domain simulation responses given the pre-defined local control 97

strategy is compared to an analytical derivation. To facilitate the ana- 98

lytical derivations, Fig. 2 shows the control block layout and internal 99

interconnections of the generic VSC. However, these interconnections 100

1 In practice, ๐‘๐‘œ๐‘,๐‘– is a set of transfer functions rather than one function.

2

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

Fig. 2. Local control structure of a VSC-station.

Table 2Control parameters.

Controller Time constant Damping ratio

AC-side current 1.5 ms 0.7071DC-side voltage 15 ms 0.7071AC-side voltage 100 ms 0.7071Active power 20 ms 0.7071Phase-locked loop 20 ms 0.7071

are only for the analytical derivations and a knowledge of this structure1

from a network perspective is not required. The desired time responses2

of each control system as shown is provided in Table 2 and can be used3

in computing the controller parameters. All other passive subsystems4

and components such as lines and cables can be modelled in the same5

manner with transfer functions. Frequency-dependent transfer function6

models for cables are widely available from literature (Beerten, 2016).7

2.1. Impedance response of a direct-voltage controlled VSC8

For a VSC in direct-voltage local control mode, a simplified analyt-9

ical derivation can be obtained given two simplifying assumptions:10

1. The connected AC grid is fairly strong, with SCR > 3. Then, it11

may be assumed that the point of common coupling (PCC) bus-12

voltage magnitude ๐‘ˆ๐‘“ =โˆš

๐‘ข2๐‘“๐‘‘ + ๐‘ข2๐‘“๐‘ž is constant at the defined13

value such that,14

๐‘ข๐‘“๐‘ž โ‰ˆ 0

โŸน ๐‘ˆ๐‘“ โ‰ˆ ๐‘ข๐‘“๐‘‘ , โŸน ๐›ฅ๐‘ข๐‘“๐‘‘ โ‰ˆ 0.(2)15

where ๐‘ข๐‘“๐‘‘ and ๐‘ข๐‘“๐‘ž are the PCC-bus d and q axes alternating16

voltages. That is, the impact of alternating voltage controller17

(AVC) vanishes and the AC side is fairly decoupled from the DC18

side (more details can be found in Agbemuko et al., 2019).19

2. If the above holds, the reactive current reference can be assumed20

constant.21

It is important to note that the above assumptions only allow to22

neglect the impact of AC dynamics on the DC side. However, this23

does not hold if the connected AC grid at the PCC is weak; in which24

case the interaction functions between AC and DC variables must be25

considered in detail. Following this approach, the resultant simplified26

direct-voltage control loop is shown in Fig. 3. The closed-loop expres-27

sion of the ๐‘–th direct-voltage controlled VSC can be derived from the28

block diagram as29

๐‘‰๐‘‘๐‘,๐‘– = ๐ป๐‘ฃ๐‘๐‘™,๐‘–(๐‘ )๐‘‰

โˆ—๐‘‘๐‘,๐‘– +๐‘๐‘ฃ

๐‘œ๐‘,๐‘–(๐‘ )๐ผ๐‘–โŸน ๐›ฅ๐‘‰๐‘‘๐‘,๐‘– = ๐‘๐‘ฃ

๐‘œ๐‘,๐‘–(๐‘ )๐›ฅ๐ผ๐‘–(3)30

Fig. 3. Simplified closed-loop block diagram of the DVC loop.

Fig. 4. Direct-voltage response to step input in bus power for a direct-voltagecontrolled VSC.

where ๐ป๐‘ฃ๐‘๐‘™,๐‘–(๐‘ ) is the closed-loop reference-to-output transfer function, 31

๐‘‰ โˆ—๐‘‘๐‘,๐‘– is the voltage reference obtained from power flow, ๐ผ๐‘– is the total 32

DC-bus current flowing into the converter, ๐พ๐‘ฃ(๐‘ ) the direct-voltage 33

controller (DVC), and ๐‘๐‘ฃ๐‘œ๐‘,๐‘–(๐‘ ) is the inputโ€“output impedance of a direct- 34

voltage controlled converter in the same form as (1). Analytically it can 35

be derived as 36

๐‘๐‘ฃ๐‘œ๐‘,๐‘–(๐‘ ) =

๐‘๐‘๐‘–(๐‘ )1 +๐ป๐‘ฃ

๐‘œ๐‘™,๐‘–(๐‘ )(4) 37

with 38

๐ป๐‘ฃ๐‘œ๐‘™,๐‘–(๐‘ ) = ๐‘๐พ๐‘ฃ(๐‘ )โ„Ž๐‘–๐‘๐‘™๐‘๐‘๐‘–(๐‘ ); ๐‘ =

๐‘ข0๐‘“๐‘‘,๐‘–๐‘˜๐‘‰ 0

๐‘‘๐‘,๐‘–

39

where โ„Ž๐‘–๐‘๐‘™ is the closed-loop reference-to-output transfer function of 40

the inner-loop, ๐‘ข0๐‘“๐‘‘,๐‘– and ๐‘‰ 0๐‘‘๐‘,๐‘– are the operating points of the PCC 41

and DC-bus voltages respectively, and ๐‘๐‘๐‘–(๐‘ ) is the equivalent physical 42

impedance on the DC side of the VSC. It is important to reiterate 43

that the main interest is the final form of the inputโ€“output impedance 44

๐‘๐‘œ๐‘,๐‘–(๐‘ ) and not the structure of internal control blocks or components 45

that make it up. Hence, it is assumed that the inner-loop for instance 46

is properly tuned and fixedโ€”itโ€™s response cannot be changed, and the 47

entire local control including the DVC is stable. 48

The circuit schematic for obtaining inputโ€“output time-domain re- 49

sponses is similar to Fig. 1. For a 150 MW step input in inversion at 50

0.7 s, Fig. 4 shows the time-domain response of the terminal direct- 51

voltage to the step change. Clearly, there is one stable local oscillatory 52

mode around 32.9 Hz from which a transfer function can be estimated. 53

In this work, the spectral analysis of the inputโ€“output time-domain 54

response is applied in estimating the frequency response; other methods 55

are available from literature. A comparison between the analytically de- 56

rived inputโ€“output impedance response and the numerically estimated 57

response from the shown time-domain simulation is shown in Fig. 5. It 58

can be seen that there is a clear match between the numerically esti- 59

mated response from the detailed model and the analytically derived 60

response given the assumptions made. Therefore, this is the nominal 61

feedback impedance equivalent of a direct-voltage controlled VSC as 62

seen from the external terminals. 63

From the analytical derivations, it can be seen that the inputโ€“output 64

impedance depends on the operating point. To establish the impacts, 65

Fig. 6 shows the responses of the analytically derived function across 66

the expected operating range of the VSC from โˆ’800 MWโ€“800 MW. 67

Importantly, it shows that the local oscillatory frequency remains the 68

same, only the magnitude differs across the operating range; differences 69

in phase is limited to the region around the local mode. However, 70

models adopted at the network-level will depend on the exact power 71

flow, but the eventual transfer function will be within the shown set. 72

3

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

Fig. 5. Nominal frequency response of the inputโ€“output impedance of a direct-voltagecontrolled VSC: analytical (solid blue), numerical estimation (circled red).

Fig. 6. Sensitivity of impedance response to varying operating points.

2.2. Impedance response of a droop/active power controlled VSC1

As an alternative to direct-voltage control, a VSC may be equipped2

with droop/active power control. Both modes can be analytically com-3

bined, with the droop gain determining whether the controller is in4

active power or droop modeโ€”๐‘…๐‘‘๐‘,๐‘– = 0 implies active power, and5

๐‘…๐‘‘๐‘,๐‘– โ‰ซ 0 implies droop control. From the perspective of a manu-6

facturer, ? discusses how to design droop gains from an impedance7

viewpoint to meet minimum performance set by an operator. With8

similar assumptions as previously, Fig. 7 shows the simplified block9

diagram of a droop/active power controlled VSC. In addition, if the10

VSC is assumed lossless,11

๐‘ƒ๐‘Ž๐‘ = ๐‘ƒ๐‘‘๐‘ (5)12

where ๐‘ƒ๐‘‘๐‘ is the DC-bus power and ๐‘ƒ๐‘Ž๐‘ is the AC-bus power. Due to13

the presence of the nonlinear power variable, linearization around an14

operating point must be done. Thus, at the ๐‘—th VSC15

๐›ฅ๐‘ƒ๐‘Ž๐‘,๐‘— = ๐›ฅ๐‘ƒ๐‘‘๐‘,๐‘— = ๐‘‰ 0๐‘‘๐‘,๐‘—๐›ฅ๐ผ๐‘‘๐‘,๐‘— + ๐ผ0๐‘‘๐‘,๐‘—๐›ฅ๐‘‰๐‘‘๐‘,๐‘— (6)16

where ๐ผ๐‘‘๐‘,๐‘— is the converter injection current balanced with the AC side.17

Following the block diagram, the closed-loop response can be derived18

Fig. 7. Simplified closed-loop block diagram of the droop/active power loop.

Fig. 8. Direct-voltage response to step input in bus power for a droop/active powercontrolled VSC.

Fig. 9. Nominal frequency response of the inputโ€“output impedance of a droop/activecontrolled VSC: analytical (solid blue), numerical estimation (circled red).

in a similar form to the direct-voltage VSC as 19

๐›ฅ๐‘‰๐‘‘๐‘,๐‘— =๐‘๐‘๐‘— (๐‘ )

1 +๐‘๐‘๐‘— (๐‘ )(

๐‘๐พ๐‘(๐‘ )โ„Ž๐‘–๐‘๐‘™ (๐‘ )(๐ผ0๐‘‘๐‘,๐‘—+๐‘…๐‘‘๐‘,๐‘— )

1+๐‘๐พ๐‘(๐‘ )โ„Ž๐‘–๐‘๐‘™ (๐‘ )๐‘‰0๐‘‘๐‘,๐‘—

)

โŸโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโŸโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโŸ๐‘๐‘‘๐‘๐‘œ๐‘,๐‘— (๐‘ )

๐›ฅ๐ผ๐‘— (7) 20

where ๐‘…๐‘‘๐‘,๐‘— is the droop gain, ๐พ๐‘(๐‘ ) is the active power compensator, 21

and ๐‘๐‘‘๐‘๐‘œ๐‘,๐‘— (๐‘ ) is the imposed DC impedance by a droop/active power 22

controlled VSC. 23

In a similar manner as the direct-voltage VSC, Fig. 8 shows the 24

time-domain response to a similar input power at ๐‘ก = 0.7 s for a 25

droop/active power controlled VSC. The deviation in direct-voltage 26

response following a change in bus power is clear; notably, there is 27

no oscillatory behaviour during the transition. A comparison of the 28

numerically estimated frequency response to the analytically derived 29

response is shown in Fig. 9. Both responses are a close match, there 30

is no oscillatory behaviour, and the steady-state deviation seen the 31

time-domain response is clear in the frequency response. That is, both 32

droop and active power control impose a steady-state impedance on 33

the system; whereas in the case of direct-voltage control, the imposed 34

impedance vanishes in steady-state. In the same manner, Fig. 10 shows 35

the sensitivity of the droop impedance response to variation in oper- 36

ating point across the range of the VSC. Compared to a direct-voltage 37

VSC, the phase differs considerably for a droop VSC across the entire 38

range of operation. 39

4

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

Fig. 10. Sensitivity of impedance response to varying operating points.

Fig. 11. Generic terminal equivalent representation of a controlled VSC.

To summarize, Fig. 11 shows the terminal-level two-port circuit1

equivalent of the controlled VSC with the converter local control re-2

sponse behind (Agbemuko et al., 2018). This is the equivalent repre-3

sentation of the VSC at the network-level.4

3. Network aggregation and two-partition equivalent for control5

design6

3.1. Aggregation of impedance equivalents7

System-level analysis requires interconnection of different convert-8

ers with a network and its topology. In the previous modelling sec-9

tion, each VSC has been represented by their equivalent inputโ€“output10

impedances that dictates their external behaviour. Each cable in the11

network can be represented by its equivalent frequency-dependent12

transfer function model (Beerten, 2016). In this paper, a distributed13

๐›ฑ equivalent model utilized. However, higher-order cable models can14

be integrated as well if a wider range of interaction frequencies are15

expected.16

Subsequent to interconnection in the given topology of the net-17

work (with at least two terminals), an equivalent multi-input multi-18

output (MIMO) dynamic impedance transfer matrix can be obtained19

as (Agbemuko et al., 2019)20

โŽ›

โŽœ

โŽœ

โŽœ

โŽœ

โŽœ

โŽ

๐›ฅ๐‘‰ ๐‘”๐‘™๐‘‘๐‘,๐‘–

๐›ฅ๐‘‰ ๐‘”๐‘™๐‘‘๐‘,๐‘—

โ‹ฎ

๐›ฅ๐‘‰ ๐‘”๐‘™๐‘‘๐‘,๐‘›

โŽž

โŽŸ

โŽŸ

โŽŸ

โŽŸ

โŽŸ

โŽ 

โŸโžโŸโžโŸ๐›ฅ๐•๐‘”๐‘™

๐‘‘๐‘

=

โŽ›

โŽœ

โŽœ

โŽœ

โŽœ

โŽ

๐‘๐‘–๐‘–(๐‘ ) ๐‘๐‘–๐‘— (๐‘ ) โ‹ฏ ๐‘๐‘–๐‘›(๐‘ )๐‘๐‘—๐‘–(๐‘ ) ๐‘๐‘—๐‘— (๐‘ ) โ‹ฏ ๐‘๐‘—๐‘›(๐‘ )โ‹ฎ โ‹ฎ โ‹ฑ โ‹ฎ

๐‘๐‘›๐‘–(๐‘ ) ๐‘๐‘›๐‘— (๐‘ ) โ‹ฏ ๐‘๐‘›๐‘›(๐‘ )

โŽž

โŽŸ

โŽŸ

โŽŸ

โŽŸ

โŽ 

โŸโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโŸโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโžโŸ๐™๐‘๐‘™๐‘‘๐‘ (๐‘ )

โŽ›

โŽœ

โŽœ

โŽœ

โŽœ

โŽ

๐›ฅ๐ผ๐‘–๐›ฅ๐ผ๐‘—โ‹ฎ

๐›ฅ๐ผ๐‘›

โŽž

โŽŸ

โŽŸ

โŽŸ

โŽŸ

โŽ 

โŸโŸโŸ๐›ฅ๐ˆ

(8)21

where ๐•๐‘”๐‘™๐‘‘๐‘ is the global direct-voltage measurements at each terminal22

during disturbances, ๐›ฅ๐ˆ is the vector of bus current changes, and ๐™๐‘๐‘™๐‘‘๐‘ (๐‘ )23

is the closed-loop dynamic MIMO equivalent transfer matrix of the24

network. It consists of the contribution of all devices in the networkโ€”25

passive and active devices as seen from any terminal. Although ๐™๐‘๐‘™๐‘‘๐‘ (๐‘ )26

is a MIMO matrix, its single-input single-output (SISO) responses can27

Fig. 12. Global control design flowchart.

be employed to characterize the network as a first step in determining 28

the overall behaviour. However, MIMO responses are more conclusive 29

in determining if the network meets a pre-defined minimum require- 30

ment. If not, then interaction analysis may be carried out with a view 31

to implementing global controllers in addition to the existing local 32

controllers. 33

3.2. Two-partition equivalent model 34

From the perspective of control, manipulating ๐•๐‘”๐‘™๐‘‘๐‘ to meet network- 35

level objectivesโ€”such as disturbance rejection, requires manipulating 36

๐™๐‘๐‘™๐‘‘๐‘ (๐‘ ). This in turn requires a tractable form of the matrix. One form 37

relies on the inputโ€“output stability based on a two-partition model of 38

the network as seen from any controllable terminal. That is, at any 39

controllable terminal ๐‘–, ๐›ฅ๐‘‰ ๐‘”๐‘™๐‘‘๐‘,๐‘– from (8) can be re-written as (Agbemuko, 40

Domรญnguez-Garcรญa, Prieto-Araujo, & Gomis-Bellmunt, 2020) 41

๐›ฅ๐‘‰ ๐‘”๐‘™๐‘‘๐‘,๐‘– = ๐›ฅ๐‘‰๐‘‘๐‘,๐‘– + ๐›ฅ๐‘‰๐‘›๐‘’๐‘ก,๐‘–

= ๐‘๐‘œ๐‘,๐‘–(๐‘ )1

1 +๐‘๐‘œ๐‘,๐‘–(๐‘ )๐‘๐‘›๐‘’๐‘ก,๐‘–(๐‘ )

๐›ฅ๐ผ๐‘– (9) 42

43

๐‘๐‘›๐‘’๐‘ก,๐‘–(๐‘ ) =๐‘๐‘–๐‘–(๐‘ )๐‘๐‘œ๐‘,๐‘–(๐‘ )

๐‘๐‘œ๐‘,๐‘–(๐‘ ) โˆ’๐‘๐‘–๐‘–(๐‘ )(10) 44

where ๐›ฅ๐‘‰๐‘‘๐‘,๐‘– is the local response as derived in Sections 2.1 and 2.2, 45

๐›ฅ๐‘‰๐‘›๐‘’๐‘ก,๐‘– is the contribution of the rest of the interconnection as seen from 46

terminal ๐‘–, represented by ๐‘๐‘›๐‘’๐‘ก,๐‘–(๐‘ ). Since ๐‘๐‘œ๐‘,๐‘–(๐‘ ) is based on the existing 47

local control, ๐‘๐‘›๐‘’๐‘ก,๐‘–(๐‘ ) becomes the tractable component which can take 48

on two possible limiting values: ๐‘๐‘›๐‘’๐‘ก,๐‘– โ†’ 0 and ๐‘๐‘›๐‘’๐‘ก,๐‘– โ†’ โˆž. The former 49

is an impedance minimization problem and the latter is an impedance 50

matching problem. The impedance minimization may apply to a case 51

where the local response based on ๐‘๐‘œ๐‘,๐‘–(๐‘ ) is not acceptableโ€”it has one 52

or more poorly damped local oscillatory modes (but strictly stable). 53

Hence, it is desired to minimize these oscillatory modes in addition 54

to any global interaction mode. This article deals with impedance 55

minimization, whereas ? discusses the case of impedance matching. 56

5

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

Fig. 13. Three terminal VSC-HVDC grid.

Broadly speaking, in both cases the stability margin as seen from1

each terminal is being manipulated. The generalized steps for analysis2

and design of global controllers (if required) are depicted in Fig. 12. The3

optimization formulation is discussed in more detail in later sections.4

4. Application example: Network characterization and interaction5

analysis6

This section presents the first step in determining if additional7

control action is required. For a three-terminal masterโ€“slave controlled8

HVDC grid shown in Fig. 13, the characterization, and interaction9

analysis are presented given the local impedance responses derived in10

Section 2โ€”direct-voltage and active power. Data for the HVDC grid is11

presented in Table 1. The HVDC interconnects two AC grid with an12

isolated power systemโ€”such as a wind farm, with VSC-1 being the13

direct-voltage controlling terminal and, VSC-2 and 3 in active power14

control modes.15

Given the network-level control strategy and the corresponding16

inputโ€“output frequency response of all subsystems, the next step is to17

obtain the network transfer matrix and characterize the network.18

4.1. Equivalent transfer matrix and SISO network characterization19

For the three terminal network shown in Fig. 13 the equivalent20

transfer matrix can be symbolically written as21

๐™๐‘๐‘™๐‘‘๐‘ (๐‘ ) =

โŽ›

โŽœ

โŽœ

โŽ

๐‘11(๐‘ ) ๐‘12(๐‘ ) ๐‘13(๐‘ )๐‘12(๐‘ ) ๐‘22(๐‘ ) ๐‘23(๐‘ )๐‘13(๐‘ ) ๐‘23(๐‘ ) ๐‘33(๐‘ )

โŽž

โŽŸ

โŽŸ

โŽ 

. (11)22

Given the nominal power flow, the isolated SISO frequency re-23

sponses of the network transfer matrix are shown in Fig. 14 (elements24

in similar colours are equivalent). The diagonal elements predict the25

behaviour of each subsystem (VSCs) relative to the network for dis-26

turbances close to them; whereas off-diagonal elements indicate the27

transfers from other subsystemsโ€”in which case they predict the in-28

teractions between terminals. As shown, there appear to be multiple29

resonant frequencies. There are three dominant interaction frequencies30

at 17 Hz, 41 Hz, and 56 Hz respectively. However, some elements show31

all three frequencies with different magnitudes, and others show only32

two. Hence, the SISO frequency response gives a first impression of33

potential resonances during disturbances. Each element predicts the34

dynamic amplification for isolated disturbances from the corresponding35

terminal or between terminals.36

4.2. MIMO network characterization37

The SISO frequency response of ๐™๐‘๐‘™๐‘‘๐‘ (๐‘ ) provides rich information on38

the oscillatory behaviour and resonances as contributed by each VSC.39

Particularly, the SISO frequency response gives the isolated behavioural40

responses even though physical responses are often coupled. That is, a41

disturbance at one VSC elicits a reaction from that VSC and other VSCs42

that could go back and forth; this is a MIMO behaviour. Essentially, the 43

๐™๐‘๐‘™๐‘‘๐‘ (๐‘ ) transfer matrix should instead be considered as a MIMO transfer 44

matrix rather than a collection of SISO transfer functions. On the other 45

hand, it is important to determine if oscillatory behaviour does indeed 46

warrant additional control action. In this case, the collective response 47

(rather than isolated SISO responses) with respect to defined network 48

specifications indicates the true characterization of the network con- 49

sidering a MIMO behaviour. Specifications can be defined by imposing 50

limits on the maximum singular value of the transfer matrix. For a 51

maximum allowed voltage deviation of ๐›ฅ๐‘‰ and expected bus current 52

change of ๐›ฅ๐ผ , a limit can be defined as 53

๏ฟฝฬ„๏ฟฝ(๐™๐‘๐‘™๐‘‘๐‘ ) โ‰ค 20 log10

โ€–๐›ฅ๐‘‰ โ€–2โ€–๐›ฅ๐ผโ€–2

dB. (12) 54

For a maximum allowed voltage deviation of 40 kV (equivalent to 10% 55

overvoltage), and bus current change of 500 A (equivalent to 200 MW), 56

the limit of maximum singular value is โ‰ˆ 40 dB. Fig. 15 shows the cor- 57

responding MIMO responses based on the singular value decomposition 58

(SVD) of the matrix indicating the principal components of responses 59

considering the potential direction of inputs (in this case currents). It 60

shows that the maximum singular value breached the established limits 61

indicated below the grey area. Hence, additional control is required to 62

keep the system within established limits, which may not be possible 63

with existing local control. Therefore, the area below the grey shading 64

in Fig. 15 establishes the benchmark for potential improvements with 65

external controllers. 66

4.3. Interaction analysis 67

The SVD response plot still does not provide information about how 68

the VSCs are contributing to each frequency if there is indeed any 69

interaction. While the SVD response may identify a resonant frequency 70

as dominant, this may not hold from an interaction contribution per- 71

spective. More so, it is important to isolate the different combinations 72

of terminals contributing to an interaction mode to allow efficient tar- 73

geting. The frequency-dependent relative gain array (RGA) defined for 74

MIMO systems is an extraordinary tool for indication of combinations 75

of interactions in MIMO systems (Bristol, 1966). Let ๐‘(๐‘ ), evaluated at 76

each frequency denote the corresponding RGA of ๐™๐‘๐‘™๐‘‘๐‘ (๐‘ ) such that, 77

๐‘(๐‘ ) = ๐™๐‘๐‘™๐‘‘๐‘ (๐‘ )โŠ—

(

๐™๐‘๐‘™๐‘‘๐‘ (๐‘ )

)โˆ’๐‘‡ (13) 78

where โŠ— is the Hadamard product (element-wise multiplication). Since 79

๐‘(๐‘ ) is frequency-dependent, the general criterion that guarantees a 80

non-interacting system at a specified frequency ๐‘  = ๐‘—๐œ” is 81

๐‘(๐‘—๐‘ค) = ๐ˆ (14) 82

where ๐ˆ is the identity matrix. That is, VSCs are not interacting at 83

a specified frequency if ๐‘(๐‘ ) is unity. On the other hand, they are 84

interacting at a specified frequency if corresponding elements in ๐™๐‘๐‘™๐‘‘๐‘ (๐‘ ) 85

show magnitude peaks (โ‰ซ 1). For example, if all elements of ๐™๐‘๐‘™๐‘‘๐‘ (๐‘ ) 86

show magnitude peaks at a certain frequency, then all VSCs are in- 87

teracting at that frequency. Additionally, RGA also allows determining 88

how inherent coordination could be applied in design when the number 89

of controllers to be designed is less than the number of VSCs in the 90

network. 91

For the studied example, Fig. 16 shows the frequency-dependent 92

RGA magnitude plot based on the network transfer matrix ๐™๐‘๐‘™๐‘‘๐‘ (๐‘ ). The 93

combination of terminals contributing to each interaction frequency is 94

shown in the zoomed response. Several observations can be directly 95

made: Observe the first peak where all distinct elements of the matrix 96

show significant peaks; at this frequency, all VSCs are interacting or 97

otherwise contributing to that frequency at different magnitudes. This 98

is due to the interaction between the direct-voltage control and the total 99

capacitance of the DC grid which was not considered in local control. 100

Nevertheless, observation of the first peak is contrary to the SVD plot in 101

Fig. 15 that suggest the most dominant mode as the resonance at 56 Hz 102

6

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

Fig. 14. SISO frequency response of the global disturbance transfer matrix.

Fig. 15. SVD plot of the global closed-loop disturbance response matrix.

(third peak). At the second peak, VSCs 1 and 2 are interacting with VSC-1

3 as indicated by the magnitudes of 13, 23, and 33 elements. Whereas,2

at the slightly higher third peak, only VSC-1 and 2 are interacting3

with a relatively higher magnitude than the previous peak (VSC-3 does4

not seem to participate at all this frequency). Further, at steady-state5

and high frequency, diagonal elements approach 1 and off-diagonal6

elements approach 0โ€”non-interacting system in these spectra. From7

this plot, it can be hypothesized that only two controllers at VSC-1 and8

2 are necessary to decouple the system. It makes no sense to have three9

controllers since for each frequency VSC-3 is contributing, either one10

of VSC-1 and/or VSC-2 are also contributing.11

To verify these frequencies from a detailed nonlinear time-domain12

model, Fig. 17 depicts the time-domain responses of direct-voltages for13

a step change at 2.5 s at VSC-3 and the corresponding fast Fourier trans-14

form (FFT). Firstly, the frequencies of resonances match the identified15

frequencies in Fig. 15 at 17 Hz, 41 Hz, and 56 Hz respectively. Secondly,16

for the change in VSC-3, the first two frequencies are more dominant as17

expected from the interaction analysis since the contribution of VSC-318

to the 56 Hz resonance is low. To further demonstrate the effectiveness19

Fig. 16. Frequency-dependent RGA plot.

of the RGA plot in the detection of interactions, Fig. 18 depicts the 20

time-domain response of direct-voltages for a step-change in power 21

reference at VSC-2, with the corresponding FFT of signals. From the 22

RGA response, for changes at VSC-2, VSC-1 contributes significantly to 23

7

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

Fig. 17. Non-linear time-domain simulation of system responses and FFT of signals for step change in power from VSC-3.

Fig. 18. Non-linear time-domain simulation of system responses and FFT of signals for step change in power at VSC-2.

the first and third peaks; this is confirmed by the FFT with relatively1

similar magnitudes to the RGA response. At VSC-2 all three peaks can2

be seen and at VSC-3 only the first and second peaks can be seen since3

it does not contribute to the third peak that only involves VSC-1 and 2.4

5. Application example: Control formulation and design of decen-5

tralized global controllers6

The network analysis in the previous section established the need to7

implement global controllers independent of the existing local control.8

The next step from Fig. 12 is to partition the system into two from each9

controllable terminal according to (9). In this case, an impedance min-10

imization problem is desired due to the presence of a poorly damped11

local oscillatory mode in the direct-voltage controlled VSC. That is, it is12

desired to transfer some local responsibilities to the global controller, in13

addition to mitigating interactions with the rest of the network. Hence,14

it is desired that ๐‘๐‘›๐‘’๐‘ก,๐‘– โ†’ 0 and according to (10) this is equivalent to15

forcing ๐‘๐‘–๐‘–(๐‘ ) โ†’ 0 from each terminal since there is no access to local16

control based on ๐‘๐‘œ๐‘,๐‘–(๐‘ ). Therefore, the goal of global control from the17

network view is to minimize the existing transfer matrix ๐™๐‘๐‘™๐‘‘๐‘ (๐‘ ) subject18

to constraints.19

5.1. Objectives of design20

First, the objectives are stated, and a description of how the problem21

fits into the โˆž mixed sensitivity framework follows. It is important to22

remark again that this is a disturbance rejection problem. The following23

objectives are paramount:24

1. Reduce the effect of feedback coupling (interaction) between ter-25

minals and dormant network oscillations not considered during26

the individual design of local controllers.27

2. Synthesized controllers must not interact with local controllers. 28

Particularly, it is ideally desired that synthesized controllers van- 29

ish in steady-state. That is, the controllers are only active during 30

transients and disturbances of pre-defined frequency spectrum 31

identified based on ๐™๐‘๐‘™๐‘‘๐‘ (๐‘ ). 32

3. More importantly, the controller must not in any manner inter- 33

act with the inner AC control loop which is often the fastest loop 34

and the bandwidth limit of the VSC. 35

In the following subsections, these objectives are translated into 36

frequency domain requirements. 37

5.2. Mixed sensitivity framework 38

Considering that tracking is not an issue as each local controller 39

ensures this, the problem becomes that of minimizing ๐›ฅ๐•๐‘”๐‘™๐‘‘๐‘ = ๐™๐‘๐‘™

๐‘‘๐‘ (๐‘ )๐›ฅ๐ˆ 40

due to the interconnection with other VSCs, subject to constraints. 41

Constraints include the maximum allowed control effort to minimize 42

๐›ฅ๐•๐‘”๐‘™๐‘‘๐‘ . Therefore, the overall problem is a mixed-sensitivity problem of 43

disturbance and control input. 44

Fig. 19 describes the problem in the generalized framework of 45

โˆž (Skogestad & Postlethwaite, 2007). ๐™๐‘ = ๐›ผ๐ผ is a fictitious plant 46

model (๐›ผ is determined by iteration and to prevent the synthesis of 47

a large gain controller); in this work, ๐›ผ = [1โ€“500]. This ensures that 48

the minimization problem is wholly dominated by ๐™๐‘๐‘™๐‘‘๐‘ (๐‘ ). ๐–๐‘(๐‘ ) is 49

the output weighting matrix that determines by how much ๐›ฅ๐•๐‘”๐‘™๐‘‘๐‘ is 50

minimized (objective 1), ๐–๐‘ข(๐‘ ) is the control output weighting matrix 51

(objectives 2 and 3), and ๐Š(๐‘ ) is a diagonal matrix of synthesized 52

controllers (Gahinet & Apkarian, 2011). It must be noted that this is 53

a MIMO problem and all matrices are MIMO matrices with lengths 54

equal to the number of subsystems. The closed-loop expressions of 55

the augmented system can be derived from Fig. 19. Starting with the 56

8

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

Fig. 19. Block diagram of plant interconnections.

inner-most structure (dashed red box)1

๐‘ง1(๐‘ ) = ๐–๐‘ข(๐‘ )๐›ฅ๐ˆ๐‘ ๐‘ง2(๐‘ ) = ๐–๐‘(๐‘ )๐™๐‘๐‘™

๐‘‘๐‘ (๐‘ )๐›ฅ๐ˆ +๐–๐‘(๐‘ )๐™๐‘(๐‘ )๐›ฅ๐ˆ๐‘ ๐›ฅ๐• = ๐™๐‘๐‘™

๐‘‘๐‘ (๐‘ )๐›ฅ๐ˆ + ๐™๐‘(๐‘ )๐›ฅ๐ˆ๐‘ .(15)2

The above expressions can be written compactly as3

[

๐ณ๐›ฅ๐•

]

=[

๐‘ƒ11 ๐‘ƒ12๐‘ƒ21 ๐‘ƒ22

]

โŸโžโžโžโžโŸโžโžโžโžโŸ๐

[

๐›ฅ๐ˆ๐›ฅ๐ˆ๐‘ 

]

, ๐ณ =[

๐‘ง1๐‘ง2

]

(16)4

where ๐ is the augmented plant with target weights ๐–๐‘ and ๐–๐‘ข, ๐‘ง1 and5

๐‘ง2 are the outputs to be minimized, ๐›ฅ๐• is the input to controller, ๐›ฅ๐ˆ is6

the disturbance, and ๐›ฅ๐ˆ๐‘  as the control input. The (s) term for transfer7

functions is henceforth neglected. The ๐ matrix can be expanded as8

๐ =

โŽก

โŽข

โŽข

โŽข

โŽฃ

0๐–๐‘๐™๐‘๐‘™

๐‘‘๐‘

๐–๐‘ข๐–๐‘๐™๐‘

๐™๐‘๐‘™๐‘‘๐‘ ๐™๐‘

โŽค

โŽฅ

โŽฅ

โŽฅ

โŽฆ

. (17)9

After interconnection with the controller(s) to be synthesized, then10

the controller outputs ๐›ฅ๐ˆ๐‘  = โˆ’๐Š๐›ฅ๐• can be eliminated to obtain11

๐‘ง1 = โˆ’๐–๐‘ข๐Š๐›ฅ๐•๐‘ง2 = ๐–๐‘๐™๐‘๐‘™

๐‘‘๐‘๐›ฅ๐ˆ โˆ’๐–๐‘๐™๐‘๐Š๐›ฅ๐•๐›ฅ๐• = ๐™๐‘๐‘™

๐‘‘๐‘๐›ฅ๐ˆ โˆ’ ๐™๐‘๐Š๐›ฅ๐•

โŸน ๐›ฅ๐• = ๐ˆ๐ˆ + ๐™๐‘๐ŠโŸโžโŸโžโŸ

๐’

๐™๐‘๐‘™๐‘‘๐‘

โŸโžโžโžโžโžโŸโžโžโžโžโžโŸ๐™๐‘๐‘™๐‘‘๐‘,๐‘›๐‘’๐‘ค

๐›ฅ๐ˆ (18)12

where ๐’ is the sensitivity transfer matrix of the synthesized controllers,13

๐™๐‘๐‘™๐‘‘๐‘,๐‘›๐‘’๐‘ค is the modified transfer matrix of the network, and ๐›ฅ๐• can be14

eliminated from ๐‘ง1 and ๐‘ง2 to obtain15

๐‘ง1 = โˆ’๐–๐‘ข๐Š๐’๐™๐‘๐‘™๐‘‘๐‘๐›ฅ๐ˆ

๐‘ง2 = ๐–๐‘๐’๐™๐‘๐‘™๐‘‘๐‘๐›ฅ๐ˆ.

(19)16

The above expressions can be written compactly as17

๐ณ = ๐(๐Š)๐›ฅ๐ˆ. (20)18

The optimization problem becomes that of minimizing the โˆž norm of19

the closed loop transfer function ๐ subject to a given stable controller20

such that21

min๐พ

โ€–๐(๐พ)โ€–โˆž โ‰ค ๐›พ, ๐(๐พ) =[

๐–๐‘ข๐Š๐’๐†๐‘‘๐–๐‘๐’๐†๐‘‘

]

(21)22

where ๐›พ is the desired closed-loop gain.23

5.3. Design preliminaries24

5.3.1. Scaling25

A key priority for a successful implementation is proper scaling to26

prevent potential skewing of the mixed-sensitivity problem. Scaling is27

Table 3Scaling factors.

Parameter Value Comments

๐›ฅ๐‘‰๐‘š๐‘Ž๐‘ฅ 40 kV Allowed voltage deviation๐›ฅ๐ผ๐‘ ,๐‘š๐‘Ž๐‘ฅ 0.8 kA Allowed control input๐›ฅ๐ผ๐‘š๐‘Ž๐‘ฅ 0.5 kA Expected disturbance

Table 4Design weights.

๐‘Š๐‘ ๐‘Š๐‘ข

VSC-1 0.5 ๐‘ +2๐œ”๐‘1

๐‘ +๐œ”๐‘1500

0.75 ๐‘ +2๐‘ +๐œ”๐‘ข1

VSC-2 0.45 ๐‘ +2๐œ”๐‘2

๐‘ +๐œ”๐‘2450

0.65 ๐‘ ๐‘ +๐œ”๐‘ข2

VSC-3 0.45 ๐‘ +2๐œ”๐‘3

๐‘ +๐œ”๐‘3450

0.65 ๐‘ ๐‘ +๐œ”๐‘ข3

done according to the recommendations in Skogestad and Postlethwaite 28

(2007) by determination of maximum expected change in inputs, max- 29

imum allowed control input to correct output error, and maximum 30

allowed output for each subsystem. Scalings at each subsystem can 31

emphasize the priority or role of each subsystem. For example, a 32

maximum of 20 kV may be allowed at one subsystem, while only 10 kV 33

may be allowed at another subsystem. However, for simplicity in this 34

paper, the scaling is similar at all subsystems as given in Table 3. The 35

fictitious plant model ๐™๐‘ and transfer matrix ๐™๐‘๐‘™๐‘‘๐‘ are scaled according 36

to 37

๐™๐‘ ๐‘ = ๐›ฅ๐•โˆ’1

๐‘š๐‘Ž๐‘ฅ๐™๐‘๐›ฅ๐ˆ๐‘ ,๐‘š๐‘Ž๐‘ฅ๐™๐‘๐‘™,๐‘ ๐‘‘๐‘ = ๐›ฅ๐•โˆ’1

๐‘š๐‘Ž๐‘ฅ๐™๐‘๐‘™๐‘‘๐‘๐›ฅ๐ˆ๐‘š๐‘Ž๐‘ฅ

(22) 38

where ๐ˆ๐‘ ,๐‘š๐‘Ž๐‘ฅ is the maximum allowed control input to minimize output, 39

and ๐ˆ๐‘š๐‘Ž๐‘ฅ is the maximum expected disturbance. 40

5.3.2. Model reduction 41

To keep the problem as tractable as possible by preventing nu- 42

merical artefacts, a low order equivalent model is sought for the key 43

transfer matrix ๐™๐‘๐‘™๐‘‘๐‘ . The Hankel balanced reduction method is applied 44

for reduction. In this paper, the total order of ๐™๐‘๐‘™๐‘‘๐‘ is 35 before reduction 45

and 7 after reduction. Fig. 20 shows the comparison of the original 46

model and the equivalent reduced model, whereas, Fig. 21 depicts the 47

Hankelโ€™s singular value plot showing the dominant states. 48

5.3.3. Order and structure of controller 49

A key priority is to obtain adoptable low-order fixed structure 50

controllers. It is well known that the order of synthesized controller 51

with standard โˆž is quite high while assuming a centralized structure. 52

Several methods to reduce the order have been suggested in literature. 53

However, in this paper, decentralized controllers, with a maximum 54

order of three was preferred for transparency and to eliminate any 55

communication requirements of the centralized structure. The real- 56

ized third-order structure is reducible to two without any change in 57

performance if desired. 58

5.3.4. Weight selection and justification 59

The choice of weights ๐–๐‘ and ๐–๐‘ข are influenced by the actual 60

frequency domain responses, and iteration may be required to obtain 61

the best weights. 62

โ€ข ๐–๐‘ is a diagonal matrix of frequency-dependent weights that 63

determine the target sensitivity of control. For the impedance 64

minimization problem, a simple choice of a high gain low-pass 65

filter with a bandwidth equal to the frequency of disturbances 66

to be rejected can be selected. Bandwidth and magnitude of 67

weights can be chosen to reflect the priority of each subsystem or 68

coordination as obtained from the RGA plot. The chosen weights 69

for the base case can be found in Table 4 with a bandwidth of 70

๐œ”๐‘1 = ๐œ”๐‘2 = ๐œ”๐‘3 = 2๐œ‹ร—65 (rad/s) respectively for each subsystem. 71

9

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

Fig. 20. Comparison plot between original and reduced disturbance model.

Fig. 21. Hankel singular value plot.

โ€ข ๐–๐‘ข is also a diagonal matrix of frequency-dependent weights to1

constrain the controller action. The weights in ๐–๐‘ข, in general,2

are high pass filters. The chosen bandwidth of weights should3

limit the bandwidth of control to be less than that of the inner4

current loop (based on generic knowledge) and slightly higher5

than the disturbance (but not necessarily). Each decentralized6

controller can have different bandwidths to prioritize and force7

coordination among them. Table 4 list the weights and corre-8

sponding bandwidths of ๐œ”๐‘ข1 = 2๐œ‹ ร— 90, ๐œ”๐‘ข2 = 2๐œ‹ ร— 75, ๐œ”๐‘ข3 =9

2๐œ‹ร—60 (rad/s) respectively. Subsystem 1 is given a slight priority10

(being the master terminal) by having a slightly higher gain in11

the low-frequency region.12

5.4. Proposed decentralized controller design13

Decentralized controllers of fixed order are synthesized by solving14

the โˆž optimization problem of (21) subject to a stabilizing controller15

with ๐›พ โ‰ค 1. The control design is implemented with MATLABยฎโ€™s16

hinfstruct algorithm (Gahinet & Apkarian, 2011). The pseudocode17

shown in Algorithm 1 depicts an overview of the controller synthesis18

procedure as implemented. The order of each controller is fixed at19

three. After the analysis in the previous section, only two controllers20

are required to decouple the system. Moreover, VSC-3 integrates an21

intermittent source and may not be suitable as a controllable terminal.22

Fig. 22. Block diagram of the modified control structure.

Nevertheless, both two and three decentralized controllers are synthe- 23

sized while including information about the entire grid. In the physical 24

structure the grid, the global controllers accept bus voltage deviations 25

as inputs and outputs current signals to mitigate interaction oscillations 26

as shown in Fig. 22. Therefore, the global controllers are additional 27

feed-forward terms external to the local control. In addition, the global 28

controllers reduce the initial magnitude of voltage deviations at the 29

instant of disturbances. 30

For the case of three synthesized controllers, the maximum gain 31

achieved for ๐›พ(โ€–๐โ€–โˆž) = 0.655 which is less than the target ๐›พ๐‘š๐‘Ž๐‘ฅ. Fig. 23 32

shows the frequency response of the three synthesized controllers. For 33

this case, VSC-2 and VSC-3 are prioritized equally. However, this is ar- 34

bitrary and flexibility can be employed with specifics. The synthesized 35

controllers are bandpass filters with active regions around the specified 36

range of frequencies, and very low gain outside this range. As expected, 37

the controllers do not contribute to steady-state behaviour (< 1 Hz) 38

where local controllers are most active. For the case of two controllers 39

designed for VSC-1 and 2, while including the model of the network 40

including VSC-3, the maximum gain achieved for ๐›พ(โ€–๐โ€–โˆž) = 0.9 which 41

is also less than the target. Fig. 24 shows the frequency response. Note 42

that the magnitude of response is nearly a decade higher to compensate 43

for the lack of a controller at VSC-3. 44

Based on two decentralized controllers, Fig. 25 shows the modified 45

SISO response of the network transfer matrix in comparison to that 46

with only local controllers. Remarkable improvements can be seen in 47

both magnitude and phase difference. Most importantly, the peaks have 48

been shaved despite having implemented only two controllers. The new 49

network characterization based on MIMO responses is shown in Fig. 26. 50

It shows that the maximum singular value is within the pre-defined 51

10

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

Fig. 23. Frequency responses of the three fixed order controllers.

Fig. 24. Frequency responses of the two fixed order controllers.

limits and the smallest singular value is several orders lower than that1

in Fig. 15. To establish the modified interaction profile, Fig. 27 shows2

the modified frequency-dependent RGA. It can be seen that the system3

has been decoupled in nearly the entire range of disturbance spectrum4

as diagonal elements approach 1 and off-diagonal elements approach 0.5

However, a slight interaction between VSC-2 and 3 can be seen around6

10 Hz, but the gain is significantly lower compared to the original7

system without the global controllers.8

Fig. 26. SVD MIMO frequency response with global controllers.

Fig. 27. Frequency-dependent relative gain array with supplementary control.

6. Validation and time-domain results 9

This section presents time-domain results with the developed global 10

controllers for both cases of two and three decentralized controllers. 11

For the first analysed case in Fig. 17 with a 50% sudden change in 12

active power at VSC-3, Fig. 28 shows the comparison of direct-voltage 13

responses with two global controllers and with only local control. As 14

can be seen, the global controllers were able to quickly damp out the 15

oscillations and stabilize grid parameters within a short time frame. In 16

Fig. 25. SISO frequency responses: existing local control (bold blue), global control (dash dotted red).

11

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

Fig. 28. Performance of two synthesized controllers in comparison to case without global controllers for changes at VSC-3.

Algorithm 1 Decentralized global controller synthesis1: Definitions and model preliminaries:

๐›ฅ๐•๐‘š๐‘Ž๐‘ฅ = diag(๐›ฅ๐‘‰๐‘š๐‘Ž๐‘ฅ,๐‘–,โ‹ฏ , ๐›ฅ๐‘‰๐‘š๐‘Ž๐‘ฅ,๐‘›);๐›ฅ๐ˆ๐‘ ,๐‘š๐‘Ž๐‘ฅ = diag(๐›ฅ๐ผ๐‘ ๐‘š๐‘Ž๐‘ฅ,๐‘–,โ‹ฏ , ๐›ฅ๐ผ๐‘ ๐‘š๐‘Ž๐‘ฅ,๐‘›);๐›ฅ๐ˆ๐‘š๐‘Ž๐‘ฅ = diag(๐›ฅ๐ผ๐‘š๐‘Ž๐‘ฅ,๐‘–,โ‹ฏ , ๐›ฅ๐ผ๐‘š๐‘Ž๐‘ฅ,๐‘›)

2: Process/Disturbance Models:๐‘ง๐‘๐‘–๐‘– = ๐›ผ๐‘–๐‘– โˆ— tf(1, 1); โ‹ฏ ๐‘ง๐‘๐‘›๐‘› = ๐›ผ๐‘›๐‘› โˆ— tf(1, 1);๐™๐‘ = blckdiag(๐‘ง๐‘๐‘–๐‘–,โ‹ฏ ๐‘ง๐‘๐‘›๐‘›); ๐™๐‘๐‘™

๐‘‘๐‘ = tf(โ‹ฏ);3: Model reduction:

[๐™๐‘๐‘™๐‘‘๐‘,๐‘Ÿ๐‘’๐‘‘ ] = reduce(๐™๐‘๐‘™

๐‘‘๐‘ ,order);4: Scaling:

๐™๐‘ ๐‘ = ๐›ฅ๐•โˆ’1๐™๐‘๐›ฅ๐ˆ๐‘ ;

๐™๐‘๐‘™,๐‘ ๐‘‘๐‘ = ๐›ฅ๐•โˆ’1๐™๐‘๐‘™

๐‘‘๐‘,๐‘Ÿ๐‘’๐‘‘๐›ฅ๐ˆ; % goto 1 for scaling parameters5: Weighting Matrices:

๐‘ค๐‘ข๐‘– = tf(โ‹ฏ); โ‹ฏ ๐‘ค๐‘ข๐‘› = tf(โ‹ฏ);๐–๐‘ข = blkdiag(๐‘ค๐‘ข๐‘–,โ‹ฏ๐‘ค๐‘ข๐‘›);๐‘ค๐‘๐‘– = tf(โ‹ฏ); โ‹ฏ ๐‘ค๐‘๐‘› = tf(โ‹ฏ);๐–๐‘ = blkdiag(๐‘ค๐‘๐‘–,โ‹ฏ๐‘ค๐‘๐‘›);

6: Controller order specification:๐‘˜๐‘–๐‘– = tf([๐‘๐‘›โˆ’1, ๐‘๐‘›โˆ’2,โ‹ฏ ๐‘0], [๐‘Ž๐‘›, ๐‘Ž๐‘›โˆ’1,โ‹ฏ ๐‘Ž0]); % ๐‘› is the order ofcontroller, ๐‘Ž and ๐‘ are free parameters๐Š = blkdiag(๐‘˜๐‘–๐‘–,โ‹ฏ ๐‘˜๐‘›๐‘›);

7: ๐ assembly and interconnection:๐™๐‘๐‘™๐‘‘๐‘,๐‘Ÿ๐‘’๐‘‘ .u = โ€˜๐‘‘๐ผโ€™; ๐™๐‘๐‘™

๐‘‘๐‘,๐‘Ÿ๐‘’๐‘‘ .y = โ€˜๐‘คโ€™;๐–๐‘ข.u = โ€˜๐‘‘๐ผ๐‘ โ€™; ๐–๐‘ข.y = โ€˜๐‘ง1โ€™;๐–๐‘.u = โ€˜๐‘‘๐‘‰ โ€™; ๐–๐‘.y = โ€˜๐‘ง2โ€™;๐Š.u = โ€˜๐‘‘๐‘‰ โ€™; ๐Š.y = โ€˜๐‘‘๐ผ๐‘ โ€™;๐™๐‘ ๐‘.u = โ€˜๐‘‘๐ผ๐‘ โ€™; ๐™๐‘ 

๐‘.y = โ€˜๐‘œ๐‘ข๐‘ก๐‘๐‘ข๐‘กโ€™;sumoutput = sumblk(โ€˜๐‘‘๐‘‰ = ๐‘ค + ๐‘œ๐‘ข๐‘ก๐‘๐‘ข๐‘กโ€™, ๐‘›); % ๐‘› is thedimension of the MIMO system

8: ๐ assembly:connect(โ‹ฏ); % make the interconnection

9: Controller synthesis:[๐Š, ๐›พ,info] = hinfstruct(๐);

10: if ๐›พ > ๐›พ๐‘š๐‘Ž๐‘ฅ then11: goto 5 % adapt weighting matrices12: end if13: Transfer function of synthesized controllers:

showTunable(๐Š);

the second case of Fig. 18 for a similar step-change in active power1

at VSC-2, Fig. 29 shows the grid direct-voltage responses. It can be2

seen that despite the higher distortion across several frequencies as in3

case with only local control, the global controllers are able to quickly4

mitigate the oscillatory behaviour. The only oscillatory behaviour is 5

that due to the interaction between VSC-2 and VSC-3 at 10.3 Hz as 6

shown in the RGA in Fig. 27. However, this damps out within 200 ms. 7

In a severe case of sudden simultaneous changes at both VSC-2 and 8

3 (50% and 30% steps changes respectively), Fig. 30 shows a comparison 9

between only local control and two global controllers. Despite a lack of 10

global controller at VSC-3 at a cost of a slightly degraded response, sim- 11

ilar performance as in previous cases demonstrate the improvements 12

from the global control. 13

To further demonstrate the robustness of synthesized controllers 14

(two decentralized) in a more stringent scenario, Fig. 31 depicts the 15

direct-voltage responses across varying operating points. It can be 16

seen that in the case with only local control, the system lost after 17

a sudden disconnection of VSC-3 initially supplying power into the 18

network. However, with the two synthesized global controllers, the 19

network maintained its robust stability facilitated by the controllers, 20

while mitigating detrimental oscillations. As expected for VSC-3, the 21

response is slightly degraded. Nevertheless, the performance is quite 22

better and acceptable than with only local control. 23

7. Conclusion 24

In summary, this paper proposed the formulation and design of 25

decentralized global controllers to decouple converters in a VSC-HVDC 26

grids through network impedance shaping. First, it was determined if 27

the characterization of the network through MIMO treatment meets 28

pre-defined minimum requirements. In the case the network does not 29

meet this requirement, then RGA can be applied to identify cross- 30

interactions between VSCs and the mechanism of these interactions. 31

Then, robust controllers are synthesized by fitting the problem into 32

an โˆž convex optimization framework. Importantly, these controllers 33

can be designed and implemented using only measurable input-out 34

impedances of VSCs and the availability of an additional control chan- 35

nel. Overall, it can be seen that despite the order of the system, the 36

designed low order controllers were able to robustly decouple the 37

system as demonstrated. Therefore, the method presented offer network 38

operators a flexible and scalable approach in securely interconnecting 39

independently designed converters. 40

Declaration of competing interest 41

The authors declare that they have no known competing finan- 42

cial interests or personal relationships that could have appeared to 43

influence the work reported in this paper. 44

12

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

Fig. 29. Performance of two synthesized controllers in comparison to case without global controllers for changes at VSC-2.

Fig. 30. Performance of two synthesized controllers in comparison to case without global controllers for multiple simultaneous changes.

Fig. 31. Test of robustness (a) step disturbances at VSC-3 (b) direct-voltage response of the network.

Acknowledgements1

This work was financially supported by the European Unionโ€™s Hori-2

zon 2020 research and innovation programme under Marie-3

Sklodowska-Curie action INCITE (grant agreement No. 675318).4

References 5

Agbemuko, A. J., Domรญnguez-Garcรญa, J. L., & Gomis-Bellmunt, O. (2018). An integrated 6

approach to understanding the impact of network resonances and control on 7

dynamic responses in VSC-HVdc networks. IFAC-PapersOnLine, 51(28), 344โ€“349. 8

13

CONPRA: 104346

Please cite this article as: A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt, Robust decentralized approach to interaction mitigation in VSC-HVDC grids through impedanceminimization. Control Engineering Practice (2020) 104346, https://doi.org/10.1016/j.conengprac.2020.104346.

A.J. Agbemuko, J.L. Domรญnguez-Garcรญa and O. Gomis-Bellmunt Control Engineering Practice xxx (xxxx) xxx

http://dx.doi.org/10.1016/j.ifacol.2018.11.726, 10th IFAC Symposium on Control1

of Power and Energy Systems CPES 2018.2

Agbemuko, A. J., Domรญnguez-Garcรญa, J. L., Prieto-Araujo, E., & Gomis-Bellmunt, O.3

(2019). Dynamic modelling and interaction analysis of multi-terminal VSC-HVDC4

grids through an impedance-based approach. International Journal of Electrical Power5

& Energy Systems, 113, 874โ€“887. http://dx.doi.org/10.1016/j.ijepes.2019.06.029.6

Agbemuko, A. J., Domรญnguez-Garcรญa, J. L., Prieto-Araujo, E., & Gomis-Bellmunt, O.7

(2020). Advanced impedance-based control design for decoupling multi-vendor8

converter hvdc grids. IEEE Transactions on Power Delivery, [ISSN: 1937-4208] 1โ€“1.9

http://dx.doi.org/10.1109/TPWRD.2020.2968761.10

Amin, M., & Molinas, M. (2019). A gray-box method for stability and controller11

parameter estimation in HVDC-connected wind farms based on nonparametric12

impedance. IEEE Transactions on Industrial Electronics, 66(3), 1872โ€“1882. http:13

//dx.doi.org/10.1109/TIE.2018.2840516.14

Amin, M., Rygg, A., & Molinas, M. (2016). Impedance-based and eigenvalue based15

stability assessment compared in VSC-HVDC system. In 2016 IEEE energy conversion16

congress and exposition (ECCE) (pp. 1โ€“8). http://dx.doi.org/10.1109/ECCE.2016.17

7855185.18

Beerten, J. (2016). Frequency-dependent cable modelling for small-signal stability19

analysis of vsc-hvdc systems. IET Generation, Transmission & Distribution, 10(11),20

1370โ€“1381.21

Beerten, J., Dโ€™Arco, S., & Suul, J. A. (2016). Identification and small-signal analysis22

of interaction modes in VSC MTDC systems. IEEE Transactions on Power Delivery,23

31(2), 888โ€“897. http://dx.doi.org/10.1109/TPWRD.2015.2467965.24

Bose, B. K. (2013). Global energy scenario and impact of power electronics in 21st25

century. IEEE Transactions on Industrial Electronics, 60(7), 2638โ€“2651. http://dx.26

doi.org/10.1109/TIE.2012.2203771.27

Bristol, E. (1966). On a new measure of interaction for multivariable process control.28

IEEE Transactions on Automatic Control, 11(1), 133โ€“134. http://dx.doi.org/10.1109/29

TAC.1966.1098266.30

Cรฉspedes, M., & Sun, J. (2012). Impedance shaping of three-phase grid-parallel voltage-31

source converters. In 2012 twenty-seventh annual IEEE applied power electronics32

conference and exposition (APEC) (pp. 754โ€“760). http://dx.doi.org/10.1109/APEC.33

2012.6165904.34

Cobreces, S., Bueno, E. J., Rodriguez, F. J., Pizarro, D., & Huerta, F. (2010).35

Robust loop-shaping ๐ปโˆž control of LCL-connected grid converters. In 2010 IEEE36

international symposium on industrial electronics (pp. 3011โ€“3017). http://dx.doi.org/37

10.1109/ISIE.2010.5637614.38

Cรณbreces, S., Wang, X., Pรฉrez, J., Griรฑรณ, R., & Blaabjerg, F. (2018). Robust admittance39

shaping approach to grid current harmonic attenuation and resonance damping.40

IEEE Transactions on Industry Applications, 54(5), 5039โ€“5053. http://dx.doi.org/10.41

1109/TIA.2018.2845358.42

Cole, S., Beerten, J., & Belmans, R. (2010). Generalized dynamic VSC MTDC model43

for power system stability studies. IEEE Transactions on Power Systems, 25(3),44

1655โ€“1662. http://dx.doi.org/10.1109/TPWRS.2010.2040846.45

Flourentzou, N., Agelidis, V. G., & Demetriades, G. D. (2009). Vsc-based hvdc power46

transmission systems: An overview. IEEE Transactions on Power Electronics, 24(3),47

592โ€“602. http://dx.doi.org/10.1109/TPEL.2008.2008441.48

Freijedo, F. D., Rodriguez-Diaz, E., Golsorkhi, M. S., Vasquez, J. C., & Guerrero, J. M.49

(2017). A root-locus design methodology derived from the impedance/admittance50

stability formulation and its application for lcl grid-connected converters in wind51

turbines. IEEE Transactions on Power Electronics, 32(10), 8218โ€“8228. http://dx.doi.52

org/10.1109/TPEL.2016.2645862.53

Gabe, I. J., Montagner, V. F., & Pinheiro, H. (2009). Design and implementation of a54

robust current controller for VSI connected to the grid through an LCL filter. IEEE55

Transactions on Power Electronics, 24(6), 1444โ€“1452. http://dx.doi.org/10.1109/56

TPEL.2009.2016097.57

Gahinet, P., & Apkarian, P. (2011). Decentralized and fixed-structure Hโˆž control in58

matlab. In 2011 50th IEEE conference on decision and control and european control59

conference (pp. 8205โ€“8210). http://dx.doi.org/10.1109/CDC.2011.6160298.60

Haileselassie, T., & Uhlen, K. (2013). Power system security in a meshed North Sea61

HVDC grid. Proceedings of the IEEE, 101(4), 978โ€“990. http://dx.doi.org/10.1109/62

JPROC.2013.2241375.63

Harnefors, L., Bongiorno, M., & Lundberg, S. (2007). Input-admittance calculation and64

shaping for controlled voltage-source converters. IEEE Transactions on Industrial65

Electronics, 54(6), 3323โ€“3334. http://dx.doi.org/10.1109/TIE.2007.904022.66

Harnefors, L., Yepes, A. G., Vidal, A., & Doval-Gandoy, J. (2015). Passivity-based 67

controller design of grid-connected vscs for prevention of electrical resonance 68

instability. IEEE Transactions on Industrial Electronics, 62(2), 702โ€“710. http://dx. 69

doi.org/10.1109/TIE.2014.2336632. 70

He, J., & Li, Y. W. (2012). Generalized closed-loop control schemes with embedded 71

virtual impedances for voltage source converters with LC or LCL filters. IEEE 72

Transactions on Power Electronics, 27(4), 1850โ€“1861. http://dx.doi.org/10.1109/ 73

TPEL.2011.2168427. 74

Hertem, D. V., & Ghandhari, M. (2010). Multi-terminal VSC HVDC for the european 75

supergrid: Obstacles. Renewable & Sustainable Energy Reviews, 14(9), 3156โ€“3163. 76

http://dx.doi.org/10.1016/j.rser.2010.07.068, URL http://www.sciencedirect.com/ 77

science/article/pii/S1364032110002480. 78

Kalcon, G. O., Adam, G. P., Anaya-Lara, O., Lo, S., & Uhlen, K. (2012). Small- 79

signal stability analysis of multi-terminal VSC-based DC transmission systems. 80

IEEE Transactions on Power Systems, 27(4), 1818โ€“1830. http://dx.doi.org/10.1109/ 81

TPWRS.2012.2190531. 82

Kammer, C., Dโ€™Arco, S., Endegnanew, A. G., & Karimi, A. (2019). Convex optimization- 83

based control design for parallel grid-connected inverters. IEEE Transactions 84

on Power Electronics, 34(7), 6048โ€“6061. http://dx.doi.org/10.1109/TPEL.2018. 85

2881196. 86

Pea-Alzola, R., Liserre, M., Blaabjerg, F., Ordonez, M., & Yang, Y. (2014). Lcl-filter 87

design for robust active damping in grid-connected converters. IEEE Transactions 88

on Industrial Informatics, 10(4), 2192โ€“2203. http://dx.doi.org/10.1109/TII.2014. 89

2361604. 90

Pรฉrez, J., Cobreces, S., Gri, R., & Sรกnchez, F. J. R. (2017). ๐ปโˆž current controller for 91

input admittance shaping of VSC-based grid applications. IEEE Transactions on Power 92

Electronics, 32(4), 3180โ€“3191. http://dx.doi.org/10.1109/TPEL.2016.2574560. 93

Pinares, G., Tjernberg, L. B., Tuan, L. A., Breitholtz, C., & Edris, A. A. (2013). 94

On the analysis of the dc dynamics of multi-terminal VSC-HVDC systems using 95

small signal modeling. In PowerTech (POWERTECH), 2013 IEEE grenoble (pp. 1โ€“6). 96

http://dx.doi.org/10.1109/PTC.2013.6652303. 97

Prieto-Araujo, E., Egea-Alvarez, A., Fekriasl, S., & Gomis-Bellmunt, O. (2016). DC 98

voltage droop control design for multiterminal HVDC systems considering AC 99

and DC grid dynamics. IEEE Transactions on Power Delivery, 31(2), 575โ€“585. http: 100

//dx.doi.org/10.1109/TPWRD.2015.2451531. 101

Qoria, T., Prevost, T., Denis, G., Gruson, F., Colas, F., & Guillaud, X. (2019). Power 102

converters classification and characterization in power transmission systems. EPEโ€™19 103

ICCE EUROPE. 104

Rault, P. (2019). Implementation of a dedicated control to limit adverse interaction in 105

multi-vendor HVDC systems. IET Conference Proceedings, (1), 7(6 pp.). 106

Schettler, F., Huang, H., & Christl, N. (2000). HVDC transmission systems using voltage 107

sourced converters design and applications. In 2000 power engineering society summer 108

meeting (Cat. No.00CH37134), Vol. 2 (pp. 715โ€“720). http://dx.doi.org/10.1109/ 109

PESS.2000.867439. 110

Skogestad, S., & Postlethwaite, I. (2007). Multivariable feedback control: analysis and 111

design, Vol. 2. Wiley New York. 112

Staudt, V., Steimel, A., Kohlmann, M., Jรคger, M. K., Heising, C., Meyer, D., et al. 113

(2014). Control concept including validation strategy for an AC/DC hybrid link 114

(ultranet). In 2014 IEEE energy conversion congress and exposition (ECCE) (pp. 115

750โ€“757). http://dx.doi.org/10.1109/ECCE.2014.6953471. 116

Tourgoutian, B., & Alefragkis, A. (2017). Design considerations for the COBRAcable 117

HVDC interconnector. In IET international conference on resilience of transmission and 118

distribution networks (RTDN 2017) (pp. 1โ€“7). http://dx.doi.org/10.1049/cp.2017. 119

0332. 120

Wang, X., Blaabjerg, F., Liserre, M., Chen, Z., He, J., & Li, Y. (2014). An active damper 121

for stabilizing power-electronics-based ac systems. IEEE Transactions on Power 122

Electronics, 29(7), 3318โ€“3329. http://dx.doi.org/10.1109/TPEL.2013.2278716. 123

Wang, X., Li, Y. W., Blaabjerg, F., & Loh, P. C. (2015). Virtual-impedance-based 124

control for voltage-source and current-source converters. IEEE Transactions on Power 125

Electronics, 30(12), 7019โ€“7037. http://dx.doi.org/10.1109/TPEL.2014.2382565. 126

Xin, Z., Loh, P. C., Wang, X., Blaabjerg, F., & Tang, Y. (2016). Highly accurate 127

derivatives forlcl-filtered grid converter with capacitor voltage active damping. IEEE 128

Transactions on Power Electronics, 31(5), 3612โ€“3625. http://dx.doi.org/10.1109/ 129

TPEL.2015.2467313. 130

Yang, D., Ruan, X., & Wu, H. (2014). Impedance shaping of the grid-connected 131

inverter with lcl filter to improve its adaptability to the weak grid condition. IEEE 132

Transactions on Power Electronics, 29(11), 5795โ€“5805. http://dx.doi.org/10.1109/ 133

TPEL.2014.2300235. 134

Yazdani, A., & Iravani, R. (2010). Voltage-sourced converters in power systems: modeling, 135

control, and applications. John Wiley & Sons. 136

14