Matas Dijokas, DTU
RMS vs EMT: the need for new
simulation tools
![Page 2: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/2.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Offshore AC grid and HVDC links
218 September 2019
• 5 wind power parks (Psum = 3.5 GW)
• Hub configuration: 220kV AC
• 5 HVDC links
• Hub connected to 3 synchronous
areas
![Page 3: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/3.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
VSC modelComponents and phasors
3
• Converter of MMC type
• Phase reactor – leakage inductance and series resistance of transformer
• Unity transformer ratio assumed
• Two converter control strategies:
– Grid following control
– Grid forming control
18 September 2019
![Page 4: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/4.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Grid following control (Onshore VSC)
418 September 2019
![Page 5: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/5.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Grid following control (Onshore VSC)
5
• Converter controls DC link voltage and
reactive power exchange at onshore station
• Outer and inner control loops use PI control
• Decoupled current control
18 September 2019
![Page 6: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/6.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Grid forming control (Offshore VSC)
618 September 2019
![Page 7: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/7.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Grid forming control (Offshore VSC)
7
• Converter controls AC hub voltage and
active power sharing
• Two P-f control strategies:
– Different frequency droop values
– Same frequency droop values
• The frequency droop value kf selected
considering:
– Capability available on VSC
– Inertia of the onshore grids
• Converter equipped with Virtual
Impedance Control
18 September 2019
𝑃𝑖 = 𝑃𝑖𝑜 +
𝑘𝑓𝑖σ𝑗=1𝑛 𝑘𝑓𝑗
∙ ∆𝑃𝑤
Converter
Virtual Impedance Controller
Active Power Controller
![Page 8: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/8.jpg)
Is RMS still good enough to
analyse the dynamics of
zero-inertia systems?
![Page 9: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/9.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Time domain simulationsStudy case introduction
9
Active power change:
1. Power request from onshore station
2. Wind power increase
Fault:
3. DC-link outage
18 September 2019
![Page 10: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/10.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Case 1: Power request from onshore station
10
• Good match of RMS and EMT simulation regarding active power and frequency responses
• Slight mismatch between RMS and EMT model regarding hub voltage. EMT is able to detect high frequency
oscillations in hub voltage
• Overall, RMS model is appropriate when it comes to power exchange between the different onshore grids.
No need to consider the transmission cable dynamics
18 September 2019
Frequency VoltageActive power
![Page 11: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/11.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Case 2: Wind power increase
11
• Good match of RMS and EMT simulations regarding the active power and frequency responses
• RMS model is unable to detect the maximum voltage deviation and high frequency oscillations in Hub-
voltage
• Overall, for wind power variation RMS model is appropriate when the focus is on active power and frequency
response. However, it fails to detect the maximum Hub-voltage deviation
18 September 2019
Frequency VoltageActive power
![Page 12: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/12.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Case 3: DC-link outage
12
• The active power from the wind is exported from the hub
18 September 2019
![Page 13: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/13.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Case 3: DC-link outage
13
• The active power from the wind is exported from the hub
• DC-link outage simulated and isolated with two breakers
18 September 2019
![Page 14: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/14.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Case 3: DC-link outage
14
• The active power from the wind is exported from the hub
• DC-link outage simulated and isolated with two breakers
• Power redirected to remaining VSC links and determined by
frequency droop values kf
18 September 2019
![Page 15: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/15.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Case 3: DC-link outage
15
• No visible frequency mismatch between RMS and EMT models
• RMS model is unable to detect the maximum deviation and high frequency oscillations in Hub-voltage/active
power
• overall, for large disturbances (link-outage), RMS model fails to capture the dominant modes that
characterize the power and voltage responses
18 September 2019
Frequency VoltageActive power
![Page 16: RMS vs EMT: the need for new simulation tools€¦ · RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU Case 1: Power request from onshore station 10 • Good match](https://reader034.vdocuments.site/reader034/viewer/2022052023/6038fc1c1e34593ac7379bb2/html5/thumbnails/16.jpg)
RMS vs EMT: the need for new simulation tools / Matas Dijokas ,DTU
Main takeaways
For the :
1. The simulations are able to to
capture the after a
2. The simulation reflects power changes and faults accurately, but requires
1618 September 2019
Need for new tools to capture the dynamics of zero-inertia
systems under fault, but remain computationally efficient
for large scale systems