    Introduction

    Sharing of RIICs Findings

    Conclusion

    SCOPE OF PRESENTATION

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    3/27

    A chairman 2 external & 2 SCDF members 2-year term To provide neutrality in investigatingcomplaints and hearing cases against RIs

    RI INQUIRY COMMITTEE (RIIC)INTRODUCTION

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    4/27

    Complaint Received

    IO

    Conducts priorinvestigation

    IO

    Constitutes RI

    Inquiry Committee

    and follow-up

    NO

    YES

    START

    ENDIO

    Closes case

    PROCEDURES FOR ACTIVATING RIIC

    IO

    Any case againstRI ?

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    5/27

    IC

    Requests for RIs explanation,present the case

    Commissioner

    Makes final decision

    END

    IC

    Submits report to

    Commissioner SCDF (CED)

    Institutes

    appropriate

    action against RI

    REGISTERED INSPECTOR INQUIRY COMMITTEE (RIIC)

    IO

    Constitutes RI

    Inquiry Committeeand follow-up

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    6/27

    FINDINGSNon compliances RIs Explanation

    Non provision of dry

    riser for a 6-storey

    building, premises

    greater than 10m.

    RI admitted he overlooked and did not detect this

    irregularity on-site.

    The building was only 6 storeys, he was of the view

    that the fire engine could reach all levels of the

    building.

    RIIC

    He should have noted the omission of dry riser provision and

    reported accordingly.

    The assumption that the fire engine could reach all levels of the

    building is unacceptable.

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    7/27

    FINDINGSNon-compliances RIs Explanation

    Non provision of

    automatic alarm system

    for building more than

    4 storeys.

    As the RI (Arch), he is responsible for the

    architectural aspects .

    The automatic alarm system was under RI (M&E).

    RIICRI (Arch) holds the duty to point out any form of deficiencies in fire safety

    provisions.

    He should have known that a 6-storey building has to be equipped with an

    automatic alarm system.

    He demonstrated bad practice.

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    8/27

    FINDINGSNon-compliances RIs Explanation

    Ventilation to

    staircase not

    provided.

    Since the staircase was enclosed, he assumed that it was

    mechanically-ventilated.

    RI (M&E) would always be engaged and be responsible to

    check on the ventilation requirements to staircase.

    RIIC FINDINGS

    Not to assume that mechanical ventilation would be provided to

    the staircase.

    He should communicate and verify with QP.

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    9/27

    NON-COMPLIANCES TO CLAUSE FINDINGS

    Clau se 2.3.3 (b) (ii) Ex tern al Exi t

    Staircase.

    RI did notic e that there were op enings next

    to the staircase but failed to po int ou t and

    issu ed RI fo rm 1.

    FINDINGSRIIC INTERPRETATION

    Not d iffic u lt to p ick up

    RI has no t be tho rough

    in his inspec tion

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    10/27

    Insufficient

    Hydrant

    NON-COMPLIANCES TO CLAUSE FINDINGS

    Prov is ion o f hydr an t d id no t

    com ply with Clause 4.4.1 (b) ofthe Fire Code.

    D id no t occu r to the R I tha t the re was

    sho rtage of hydrants.

    Used direct distance for measurement from

    the hyd rant.

    Actual distance to be taken

    FINDINGS

    RI IC INTERPRETATION

    RI to use the path of fire eng ine accessway

    for measu rement ins tead of direct dis tance.

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    11/27

    FINDINGS Dry risers found at site but not indicated onapproved plan

    RI to check site against approved plan

    RI to advise the QP to make correct the

    situation at site arising from his

    inspections

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    12/27

    Fire doors were not installed

    for electrical risers at the lift

    lobby as indicated on plans

    Inspection certificate form 1

    issued

    FINDINGS

    RI to advise the QP to make correct thesituation

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    13/27

    Store rooms erected at thebasement were not regularised.

    RI informed that these were not installed

    when he inspected the building and

    showed photos as evidence.

    FINDINGS

    RIIC did not

    pursue any

    further.

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    14/27

    Partitions found in hall and kitchenwhich are deviated from approved

    plans.

    FINDINGS

    RI informed that these were not installed

    when he inspected the building.

    RI cannot provide

    any photos but given

    benefit of doubt.

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    15/27

    No fire compartmentationbetween carpark & kitchen

    CarparkKitchen

    RI was told by

    QP that there

    would be no open

    flame cooking

    FINDINGSOpen flame cooking or not, the compartmentation wall must be

    provided as it was designed and approved as a kitchen

    RI cannot just take things in his own hand and accepts the deviation

    and issue form 1

    We cannot foresee its future use and RI should have advised the QP

    to seek waiver

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    16/27

    Exit signs installed at 3.4m high

    Height of exit lights (only at mainhall entrance) were mounted

    higher than 2.5m.

    The hall had much higher ceilingheight and any smoke in the hall

    would not obstruct the exit lights.

    Furthermore, there were

    emergency lights installed

    FINDINGSThere would be previous waiver cases approved for such deviation

    RI cannot just take things in his own hand and accepts the deviation

    and issue form 1

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    17/27

    Home for the aged / sick comprising 3 storey Administration

    Block and 4 storey accommodation block.No emergency lightings& PA system forstaircases at various levelof this 4-storey home.

    Clause 8.2.1(a) (iii)

    For Hotel or health care occupancies of less than 24m in

    habitable height,

    FINDINGS

    loudspeakers for the public address system shall

    be provided in lift lobby, staircase enclosure and

    other strategic positions within audible distance

    of all parts of all storey of the building.

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    18/27

    The measuredairflow velocitywas about 13 m/s(on average)

    Lower than that ofaverage 14.88 m/s

    FINDINGS

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    19/27

    Gap between fire door & floor level more than10mm

    Clause 3.2.2 Clearance between leaf and frame or finished floor

    shall have fitting tolerances of not more than 10mm between the

    bottom of the door leaf or door leaves and the finished floor with

    the door closed

    FINDINGS

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    20/27

    Hosereel not located

    in common area but

    I nside KTV room

    Concealed sprinklerpainted over

    OTHER FINDINGS

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    21/27

    Openings between storeys/rooms werefound not fully compartmented.

    Clause 3.9.3 (a) - Pipes which pass through a

    separating wall, compartment wall or compartmentfloor shall be kept as small as possible and fire-

    stopped around the pipe.

    OTHER FINDINGS

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    22/27

    Part ofenclosure

    constructionbeing cut to fitother services

    OTHER FINDINGS

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    23/27

    Inspect & certify compliance of fire safetystandards professionally

    OTHER FINDINGS

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    24/27

    Inspect & certify compliance of fire safetystandards professionally

    OTHER FINDINGS

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    25/27

    Expired validity

    period & no

    date

    No RI stamp &

    signature

    Project title not

    tally with main

    plan

    Part I/II & PB notdeleted

    accordingly

    Related plans

    not included

    ADMINSITRATIVE

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    26/27

    CONCLUSION

    QPs/RIs to work closely and exercise

    high professionalism to uphold

    fire safety standards

    Notify SCDF if parties involve

    refuse to rectify

  • 7/27/2019 RI Sharing of Findings From Registered Inspector Inquiry Committee (RIIC)

    27/27

    END