rfe-1-ye_-ece-ido-001-revc cálculos eléctricos.pdf
TRANSCRIPT
PLANTA DE RESERVA FRÍA DE GENERACIÓN DE ETEN S.A
PROYECTO PROJECT
RESERVA FRÍA ETEN CONTRATISTA CONTRACTOR
TÍTULO TITLE
CÁLCULOS ELÉCTRICOS
Nº DE DOCUMENTO PROYECTO PROJECT DOCUMENT Nº
RFE-1-YE__-ECE-IDO-001
REV C EDITADO PARA ISSUED FOR
PARA DISEÑO FECHA DATE
09-05-2014
JMM
PRV
JSA
REALIZADO DONE BY
REVISADO CHECKED BY
APROBADO APPROVED BY
ESTE DOCUMENTO CONTIENE INFORMACIÓN PROPIETARIA Y NO PUEDE SER DUPLICADO, PROCESADO O CEDIDO A TERCEROS PARA UN USO DISTINTO AL DE ESTE PROYECTO Y EL OBJETO PARA EL QUE HA SIDO PREVISTO SIN LA AUTORIZACIÓN ESCRITA DE COBRA.
THIS DOCUMENT CONTAINS PROPIETARY INFORMATION AND CAN NOT BE DUPLICATED, PROCESSED OR DISCLOSED TO THIRD PARTIES FOR ANY USE OTHER THAN THIS PROJECT AND THE PURPOSE FOR WHICH IT IS INTENDED FOR WITHOUT THE WRITTEN CONSENT OF COBRA.
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 2 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
CONTROL DE MODIFICACIONES/CHANGE LOG
Revisión
Revision
Fecha
Date
Modificaciones
Modifications
A 14/06/12
EDICIÓN INICIAL
B 28/03/2014 ACTUALIZACIÓN GENERAL
C 09/05/2014 ACTUALIZACIÓN DE ANÁLISIS
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 3 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
ÍNDICE
1. OBJETO ............................................................................................................................. 4
2. REFERENCIAS ................................................................................................................... 5
3. DATOS DE PARTIDA ......................................................................................................... 6
3.1. CARACTERÍSTICAS DE LOS EQUIPOS .............................................................. 6
3.1.1. RED DE 220 KV .................................................................................................... 6
3.1.2. TRANSFORMADOR PRINCIPAL .......................................................................... 6
3.1.3. TRANSFORMADOR AUXILIAR ............................................................................. 7
3.1.4. GENERADORES ................................................................................................... 7
3.1.5. TRANSFORMADORES M.T./M.T. ......................................................................... 8
3.1.6. TRANSFORMADORES M.T./B.T. .......................................................................... 9
3.1.7. MOTORES DE M.T. ............................................................................................... 9
3.1.8. CARGAS DE B.T. ................................................................................................ 10
3.1.9. GENERADOR DIESEL DE EMERGENCIA.......................................................... 11
3.1.10. LÍNEA DE TRANSMISIÓN ................................................................................... 11
3.1.11. CABLES DE MEDIA Y BAJA TENSIÓN ............................................................... 11
3.2. CONSIDERACIONES .......................................................................................... 12
3.2.1. GENERAL ........................................................................................................... 12
3.2.2. CRITERIOS PARTICULARES PARA CADA ANÁLISIS ....................................... 13
4. ANALISIS DE LAS CONDICIONES DE FUNCIONAMIENTO ........................................... 18
4.1. ANÁLISIS DE FLUJO DE CARGAS ..................................................................... 18
4.2. ANÁLISIS DE CORTOCIRCUITO ........................................................................ 18
4.3. ANÁLISIS DE ARRANQUE DE MOTORES ......................................................... 18
5. CONCLUSIONES .............................................................................................................. 19
5.1. ANÁLISIS DE FLUJO DE CARGAS ..................................................................... 19
5.2. ANÁLISIS DE CORTOCIRCUITO ........................................................................ 20
5.3. ANÁLISIS DE ARRANQUE DE MOTORES ......................................................... 20
6. ANEXOS ........................................................................................................................... 22
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 4 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
1. OBJETO
El objeto del presente documento es recoger el estudio de FLUJO DE CARGAS,
CORTOCIRCUITO y ARRANQUE DE MOTORES correspondiente al sistema eléctrico de la
Planta de Reserva Fría de Eten (Perú), a fin de establecer las características que deberán tener
los equipos.
El estudio se ha realizado con el programa de diseño, análisis y simulación de sistemas
eléctricos ETAP Powerstation, de Operation Technology, Inc., versión 12.0.0C.
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 5 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
2. REFERENCIAS
[1] ISA-REP: PE-REQU-ANTE-2011-D230 “Anteproyecto de Ingeniería Subestación Reque
220 kV y obras conexas”
[2] Email RFE-CPI-GE-EML-0070. de 2012-12-13 con datos de la red 220 kV.
[3] Doc. 401A6263 “GE LOAD SUMMARY”
[4] Diagram 105T6742 “ONE LINE DIAGRAM GAS TURBINE”
[5] RFE-1-BAT-EHP-IDO-001 “HOJA DE DATOS TRANSFORMADOR PRINCIPAL”
[6] RFE-1-YE_-ECE-IDO-003 “Cálculo de Cables de Media Tensión”
[7] RFE-1-YE_-ECE-IDO-004 “Cálculo de Cables de Baja Tensión”
[8] RFE-1-YE_-ELC-IDO-001 “Lista de Consumidores Electricos”
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 6 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
3. DATOS DE PARTIDA
3.1. CARACTERÍSTICAS DE LOS EQUIPOS
En el anexo I se incluye el esquema simplificado empleado para la simulación. En él se han
incluido los elementos descritos a continuación.
3.1.1. Red de 220 kV
Se considera la red de 220 kV definida por los siguientes valores:
Tensión nominal ............................................................................................................ 220 kV
Frecuencia nominal ......................................................................................................... 60 Hz
Intensidad de cortocircuito trifásica ................................................................................. 9,3 kA
Intensidad de cortocircuito monofásica ......................................................................... 10,5 kA
3.1.2. Transformador principal
Los parámetros principales del transformador principal son los siguientes:
Potencia nominal ............................................................................................... 225 / 300 MVA
Refrigeración ..................................................................................................... ONAN / ONAF
Relación de transformación .................................................................................... 220 / 18 kV
Regulación: ............................................................................................. en carga, ± 10 x 1,5%
Tensión de cortocircuito ................................................................................... 10% (225 MVA)
Grupo de conexión .......................................................................................................... YNd1
Neutro a tierra .................................................................................................. Conexión sólida
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 7 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
3.1.3. Transformador auxiliar
Los parámetros principales del transformador auxiliar son los siguientes:
Potencia nominal ............................................................................................... 8,5 / 11,5 MVA
Refrigeración ..................................................................................................... ONAN / ONAF
Relación de transformación ..................................................................................... 18 / 6,9 kV
Regulación: .............................................................................................. en vacío, ± 2 x 2,5%
Tensión de cortocircuito .................................................................................... 10% (8,5 MVA)
Grupo de conexión ......................................................................................................... Dyn11
Neutro a tierra ...................................................................... Mediante resist. De 796,74 Ω (5A)
3.1.4. Generadores
Los datos y curvas considerados para el generador de la turbina principal se han incluido en el
anexo II:
Generador Principal
Tensión nominal .............................................................................................................. 18 kV
Potencia aparente nominal ...................................................................................... 279,5 MVA
Potencia activa nominal ............................................................................................ 223,6 MW
Factor de potencia ........................................................................................................ 0,8 p.u.
Capacidad de potencia reactiva con cos φ =0,80 inductivo ....................................... 167 MVAr
Capacidad de potencia reactiva con cos φ =0,95 capacitivo ...................................... -86 MVAr
Reactancia subtransitoria saturada ............................................................................. 0,17 p.u.
Neutro a tierra .......................................................................... Mediante trafo-resist. (10Aprim)
Los datos del generador auxiliar se muestran a continuación:
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 8 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
Generador Auxiliar
Tensión nominal ........................................................................................................... 6.600 V
Potencia aparente nominal .................................................................................... 10,549 MVA
Potencia activa nominal .............................................................................................. 8,44 MW
Factor de potencia ...................................................................................................... 0,80 p.u.
Capacidad de potencia reactiva con cos φ =0,80 inductivo .......................................6,33 MVAr
Capacidad de potencia reactiva con cos φ =0,95 capacitivo ................................... -3,29 MVAr
Reactancia subtransitoria saturada ............................................................................. 0,16 p.u.
Neutro a tierra Mediante resist. de 762Ω (5A)
3.1.5. Transformadores M.T./M.T.
Se han empleado las siguientes características de los transformadores de los motores de MT:
Potencia nominal ......................................................................................................... 600 kVA
Refrigeración ....................................................................................................................... AN
Relación de transformación ................................................................................ 6,6 / 0,505 kV
Regulación de tensión ............................................................................................... En vacío
Regulación en el primario .......................................................................................... 2x2,5%
Tensión de cortocircuito ...................................................................................................... 6 %
Grupo de conexión ............................................................................................................. Yd1
Neutro ............................................................................................................................ Aislado
Se han empleado las siguientes características del transformador del LCI:
Potencia nominal ..................................................................................... 5450-2725/2725 kVA
Configuración........................................................................................................ 3 devanados
Refrigeración ....................................................................................................................... AN
Relación de transformación .......................................................................... 6,6 / 2,08-2.08 kV
Tensión de cortocircuito ...................................................................................................... 6 %
Grupo de conexión ......................................................................................................... Dy1d1
Neutro ............................................................................................................................ Aislado
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 9 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
3.1.6. Transformadores M.T./B.T.
Se han empleado las siguientes características de los transformadores de servicio de MT/BT:
Potencia nominal ....................................................................................................... 3500 kVA
Refrigeración ....................................................................................................................... AN
Relación de transformación ................................................................................ 6,6 / 0,505 kV
Regulación de tensión ............................................................................................... En vacío
Regulación en el primario .......................................................................................... 2x2,5%
Tensión de cortocircuito .................................................................................................... 12 %
Grupo de conexión ......................................................................................................... Dyn11
Neutro a tierra .................................................................................................. Conexión sólida
Se han empleado las siguientes características del transformador de excitación:
Potencia nominal ....................................................................................................... 1500 kVA
Refrigeración .................................................................................................................. ONAN
Relación de transformación .................................................................................. 6,6 / 0,45 kV
Tensión de cortocircuito ...................................................................................................... 6 %
Grupo de conexión ............................................................................................................. Yd1
Neutro ............................................................................................................................ Aislado
3.1.7. Motores de M.T.
Motor Pn
[kW]
Un
[V]
Cos φ
[%]
Rend.
[%]
Utilizac.
[%]
ATOMIZING AIR SYSTEM
COMPRESSOR DRIVE MOTOR 1 375 4000 92 93,22 85
ATOMIZING AIR SYSTEM
COMPRESSOR DRIVE MOTOR 2 375 4000 92 93,22 85
WATER INJECTION PUMP MOTOR 224 4000 92 93 55
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 10 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
Motor Pn
[kW]
Un
[V]
Cos φ
[%]
Rend.
[%]
Utilizac.
[%]
88WN-1
WATER INJECTION PUMP MOTOR
88WN-2 224 4000 92 93 55
Estos motores irán alimentados, cada uno, a través de un transformador reductor de M.T./M.T.
(ver sección 3.1.5).
3.1.8. Cargas de B.T.
Las cargas empleadas para realizar los análisis son los siguientes:
Carga Tipo
(% motor / % estático)
Pn
[kW]
Un
[V]
Cos φ
[%]
Utilizac.
[%]
EXCITACIÓN 0 / 100 1500 480 100 100
LCI 0 / 100 3250 2080 100 0
CARGAS 1BJA76 60 / 40 230 480 85 75
1BJA80 25* / 75 340 480 85 85
MBN50AH010 0 / 100 450 480 100 90
CARGAS 1BNB52 10 / 90 74 380 90 80
CARGAS 1BMB20 75 / 25 200 480 85 83
CARGAS 1BJA11 85 / 15 570 480 80 85
CARGAS 1BJA12 85 / 15 481 480 80 85
CARGAS 1BMB52 50 / 50 190 480 80 67
CARGAS 1BJA51 50 / 50 520 480 80 70
* Indica el porcentaje de motores que no llevan variador de frecuencia.
Los motores empleados para realizar los análisis son los siguientes:
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 11 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
Motor Pn
[kW]
Un
[V]
Cos φ
[%]
Rend.
[%]
Utilizac.
[%]
PCI 200 480 85 90 80
COMPRESOR 1* 37 480 85 90 45
COMPRESOR 2* 37 480 85 90 45
AUX LUBE OIL PUMP MOTOR 1 75 480 85 95 90
AUX LUBE OIL PUMP MOTOR 2 75 480 85 95 90
* Estos motores arrancarán mediante un sistema estrella - triángulo, con el objeto de disminuir la
intensidad de arranque.
3.1.9. Generador Diesel de Emergencia
Los datos principales del generador de emergencia son:
Tensión nominal .............................................................................................................. 480 V
Potencia aparente nominal ........................................................................................ 2500 kVA
Potencia activa nominal .............................................................................................. 2000 kW
Factor de potencia ...................................................................................................... 0,80 p.u.
Reactancia subtransitoria saturada ............................................................................. 0,19 p.u.
3.1.10. Línea de Transmisión
Se considera la línea de transmisión aérea desde la planta ‘Reserva Fría Eten’ hasta S.E.
Reque, situada a 2.92 km mediante cable ‘Narcissus’ (1272 MCM).
3.1.11. Cables de Media y Baja Tensión
Los cables de Media Tensión considerados son:
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 12 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
Carga Configuración Cable Material Aislamiento Longitud [m]
Acometida Tablero M.T. 3x(4x(1x240mm2)) Cu XLPE (6/10 kV) 40
Trafo Excitación 3x(1x150mm2) Cu XLPE (6/10 kV) 40
Trafo LCI 3x(3x(1x240mm2)) Cu XLPE (6/10 kV) 40
Tablero MT Black Start 3x(3x(1x300mm2)) Cu XLPE (6/10 kV) 120
Generador Auxiliar (BS) 3x(3x(1x300mm2)) Cu XLPE (6/10 kV) 20
Trafo Black Start 3x(1x300mm2) Cu XLPE (6/10 kV) 20
Trafo M.T./B.T. (1BFT51) 3x(2x(1x185mm2)) Cu XLPE (6/10 kV) 40
Trafo M.T./B.T. (1BFT53) 3x(2x(1x185mm2)) Cu XLPE (6/10 kV) 40
Trafo Atomizing Air 1 3x70mm2 Cu XLPE (6/10 kV) 100
Motor Atomizing Air 1 3x70mm2 Cu XLPE (6/10 kV) 50
Trafo Atomizing Air 2 3x70mm2 Cu XLPE (6/10 kV) 100
Motor Atomizing Air 2 3x70mm2 Cu XLPE (6/10 kV) 50
Trafo Water Injection 1 3x70mm2 Cu XLPE (6/10 kV) 70
Motor Water Injection 1 3x70mm2 Cu XLPE (6/10 kV) 50
Trafo Water Injection 2 3x70mm2 Cu XLPE (6/10 kV) 70
Motor Water Injection 2 3x70mm2 Cu XLPE (6/10 kV) 50
Además, se han considerado los siguientes cables de Baja Tensión:
Carga Configuración Cable Material Aislamiento Longitud [m]
Generador Diesel Emerg. 3x(6x(1x300mm2)) Cu XLPE (0,6/1kV) 50
Sistema PCI 3x(2x(1x240mm2))+2x(
1x120mm2) Cu XLPE (0,6/1kV) 115
3.2. CONSIDERACIONES
3.2.1. General
Como valores de los parámetros de los equipos eléctricos no especificados en este documento
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 13 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
se han asumido los que aparecen por defecto en el programa de cálculo.
No se ha incluido ningún cable más de Baja Tensión ni embarrado de conexión, despreciando
así las pérdidas que conllevarían estos elementos.
El regulador de tensión en vacío del transformador auxiliar se fija en la toma +2,5%, Los
reguladores de tensión en vacío de los transformadores de MT/BT, se han fijado en su toma
central (0%), salvo el transformador de los servicios auxiliares del Generador Auxiliar que se ha
fijado en la toma +2,5%.
Según la norma IEC 60.076, se ha considerado una tolerancia de ±10% para los
transformadores de Ucc<10%, y de ±7,5% para los de Ucc>=10%.
Todos los consumidores se alimentarán desde un único transformador de M.T./B.T.
Los cálculos de flujo de carga se han realizado con el interruptor del embarrado de 480 V
acoplado, alimentando así desde un único transformador de M.T./ B.T y con el generador diésel
de emergencia parado.
Las cargas combinadas de 480 V se han empleado como equivalentes del conjunto de las
cargas en cada embarrado.
3.2.2. Criterios particulares para cada análisis
Flujo de cargas:
Se estudiarán los siguientes análisis:
Caso de estudio Criterios de cálculo
LF-1 Tensión de red = 220 kV
Generador Principal; Generación a
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 14 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
Caso de estudio Criterios de cálculo
cos φ =0,80 inductivo
Generador Auxiliar; Generación a cos φ =0,80 inductivo
Regulador de tensión de Transformador Principal en Automático para conseguir la tensión nominal en el sistema de 18 kV.
Todas las Cargas Auxiliares operando.
LF-2 Tensión de red = 220 kV
Generador Principal y Auxiliar; Generación a cos φ =0,95 capacitivo
Regulador de tensión de Transformador Principal en Automático para conseguir la tensión nominal en el sistema de 18 kV.
Todas las Cargas Auxiliares operando.
LF-3
(Mínima tensión en barras)
Tensión de red = 220 kV
Generador Principal y Auxiliar; parados
Regulador de tensión de Transformador Principal en Automático para conseguir la tensión nominal en el sistema de 18 kV.
Todas las Cargas Auxiliares operando.
LF-4
(Máxima tensión en barras)
Tensión de red = 220 kV
Generador Principal y Auxiliar; parados
Regulador de tensión de Transformador Principal en Automático para conseguir la tensión nominal en el sistema de 18 kV.
Todas las Cargas Auxiliares fuera de servicio.
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 15 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
Cortocircuito:
El método utilizado para cálculo de las corrientes de cortocircuito es el de la norma IEC 60909.
Para el cálculo de las intensidades máximas de cortocircuito se han aplicado los siguientes
factores:
c=1,10 para M.T.
c=1,05 para B.T.
Según la norma IEC 60909 se definen como:
I"k: la corriente de cortocircuito simétrica inicial
ip: el valor de cresta de la corriente de cortocircuito
ip = (1,02 + 0,98 * e-3*R/X) * 2 * I"k
id.c.: la componente de continua de la corriente de cortocircuito
id.c. = 2 * I"k * e-2**t*R/X
A: valor inicial de la componente de corriente continua id.c.
A = 2 * I"k
Ib: corriente de cortocircuito simétrica de corte (valor eficaz).
tmín: tiempo de retardo mínimo de un interruptor automático (tiempo más corto entre la
aparición de la corriente de cortocircuito y la primera separación de los contactos de un polo
del interruptor)
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 16 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
Ib = tmin * I"k
Ik: corriente de cortocircuito de régimen permanente (valor eficaz).
Para obtener la máxima intensidad de cortocircuito en cada embarrado se estudiarán los
siguientes casos:
Caso de estudio Criterios de cálculo
SC-1 Todas las cargas conectadas
Generador de Emergencia parado
Generador Auxiliar (Black Start)
conectado
SC-2 Todas las cargas conectadas
Generador de Emergencia conectado
Generador Auxiliar (Black Start) parado
Nota: En ningún caso, y con el objetivo de no sobredimensionar los embarrados
auxiliares de la planta, se permitirá que los Generadores de Emergencia y Auxiliar estén
trabajando en paralelo y sincronizados entre sí.
Arranque de motores
Durante el arranque de los motores la caída de tensión no podrá superar el 10% en barras ni el
20% en los terminales del motor arrancado.
El estudio de arranque realizado es estático. En este modo de cálculo, el programa utilizado,
obtiene las caídas de tensión en el momento del arranque (valor máximo) y tanto la caída de
tensión como la posterior recuperación son instantáneas. En cada caso, antes del arranque se
encuentran en funcionamiento todas las cargas a excepción del motor seleccionado (que es la
última carga en entrar en servicio).
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 17 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
Se ha analizado el arranque de los siguientes motores (el arranque de los motores se realiza en
T=1 segundo en ambos estudios):
Casos de estudio Criterios de cálculo
MS-1 Arranque del motor de MT ‘Atomizing
Air System Compressor Drive Motor 1’
(88AK-1).
Generador Principal y Auxiliar; parados
Funcionamiento del regulador en
carga del transformador principal en
automático.
Regulador de tensión del
transformador auxiliar en toma -2,5%.
MS-2 Arranque del motor PCI
Generador Principal y Auxiliar; parados
Funcionamiento del regulador en
carga del transformador principal en
toma -4.5%.
Regulador de tensión del
transformador auxiliar en toma -2,5%.
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 18 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
4. ANALISIS DE LAS CONDICIONES DE FUNCIONAMIENTO
4.1. ANÁLISIS DE FLUJO DE CARGAS
En el anexo III se adjuntan los resultados de los siguientes análisis de flujo de cargas:
LF-1
LF-2
LF-3
LF-4
4.2. ANÁLISIS DE CORTOCIRCUITO
En el anexo IV se adjuntan los resultados de los siguientes análisis de cortocircuito:
SC-1
SC-2
4.3. ANÁLISIS DE ARRANQUE DE MOTORES
En el anexo V se adjuntan los resultados de los siguientes análisis de arranque de motores:
MS-1
MS-2
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 19 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
5. CONCLUSIONES
5.1. ANÁLISIS DE FLUJO DE CARGAS
Las conclusiones extraídas de los casos de estudio realizados son los siguientes:
La carga consumida en los sistemas auxiliares son siempre inferiores a la potencia nominal
de los transformadores que las alimentan, obteniendo así un sistema sin sobrecargas.
Para obtener una tensión en barras comprendida entre 90%÷110% Un, los reguladores de
tensión han de operar de las siguientes maneras:
Transformador Principal: Regulador de tensión en automático para obtener el 100%
de tensión en el sistema de 18 kV.
Transformador Auxiliar: Regulador de tensión en la toma +2,5%.
Transformadores de servicio (1BFT51/53): Regulador de tensión en toma central.
Transformador de servicios auxiliares de Generador Auxiliar (1BFT76): Regulador de
tensión en toma +2,5%.
Teniendo una situación de máxima tensión en barras (caso LF-4), se ha obtenido una tensión
del 112,96% en el embarrado auxiliar 1BNB52 (secundario del transformador 1BNT52). Al no
haber modelado el cableado de Baja Tensión que alimenta dicho panel, se da por sentado
que la tensión será inferior a la obtenida en la simulación. En la Puesta En Marcha se
recomienda realizar una medición de tensión en esta situación antes de cerrar el interruptor
de acometida de la barra 1BNB52 , para en caso de obtener un valor superior al 110%, subir
el regulador de tensión del transformador 1BNT52 a la toma +2,5%. Teniendo en cuenta el
margen existente en el caso de mínima tensión (LF-3), se puede asegurar que aun subiendo
la toma del transformador, la tensión en barras seguirá estando dentro de los límites. Este
comentario es extrapolable a las demás barras de 380-220V alimentados a través de un
transformador de servicio.
Se han considerado las condiciones más desfavorables de funcionamiento. Cualquier otra
situación será más favorable para el flujo de las cargas en el sistema.
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 20 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
5.2. ANÁLISIS DE CORTOCIRCUITO
Las conclusiones extraídas de los casos de estudio realizados son los siguientes:
Las corrientes de cortocircuito trifásico máximas, en los diferentes niveles de tensión, para el
dimensionamiento de los equipos son las indicadas a continuación:
Nivel de tensión Ik”
(kA)
Ib asym
(MT = 50 ms)
(BT = 30 ms)
(kA)
Ip
(kA)
220kV (S.E. GEN) 10,251 10,032 25,637
18kV (BUS GEN) 104,581 91,781 281,154
6,6kV (1BBA51) 16,829 14,709 42,505
48V (Cuadros Generales de BT) 62,417 56,471 144.677
480 V (CCMs) 57,077 52,343 124,789
En ningún momento, y con el objetivo de no sobredimensionar los embarrados auxiliares de
la planta, se permitirá que los Generadores de Emergencia y Auxiliar estén trabajando en
paralelo y sincronizados entre sí.
Cualquier otra situación de funcionamiento será más favorable para el dimensionamiento de
los equipos de los distintos niveles de tensión.
5.3. ANÁLISIS DE ARRANQUE DE MOTORES
Las conclusiones extractadas de los casos de estudio realizados son los siguientes:
En las situaciones analizadas, la tensión en el momento del arranque de los motores se
mantiene por encima del 90% de la nominal en todas las barras.
En el momento de arranque de motores, no se permitirá que los Generadores Principal y
Auxiliar estén trabajando en paralelo, a plena carga y con factor de potencia 0,95 capacitivo,
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 21 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
debido a la caída de tensión resultante en este modo de operación. En caso de estar los dos
generadores en operación, al menos, el Generador Auxiliar deberá estar trabajando con
factor de potencia inductivo (generando reactiva) para no perjudicar el arranque de motores
principales.
Se considera que cualquier otra situación será más favorable para el arranque de motores.
CÁLCULOS ELÉCTRICOS
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 22 de/of 23
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
6. ANEXOS
Anexo I: Esquema Unifilar
Anexo II: Datos Generador Principal
Anexo III: Datos Transformador Principal
Anexo IV: Datos Generador Auxiliar
Anexo V: Datos Transformador Auxiliar
Anexo VI: Reportes del análisis de flujo de cargas
Anexo VII : Reportes del análisis de cortocircuito
Anexo VIII Reportes del análisis de arranque de motores
CÁLCULOS ELÉCTRICOS ANEJO I
Rev. C
RFE-1-YE__-ECE-IDO-001 Pág/Page 1 de/of 3
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
ANEXO I:
ESQUEMA UNIFILAR
One-Line Diagram - OLV1 (Load Flow Analysis)
page 1 11:11:38 may 02, 2014 Project File: Eten
1BFA51
0,48 kV
1BBA51
6,6 kV
1BFA53
0,48 kV
1BMA52
0,48 kV
1BNB52
0,38 kV
CGDE
0,48 kV
1BBA76
6,6 kV
1BJA76
0,48 kV
BUS GEN
18 kV
S.E. Etén
220 kV
S.E. Reque
220 kV
Sistema PCI
200 kW
Red eléctrica Peruana
3022 MVAsc
Narcissus
AL 2,92 km
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
1MKA10
225 MW
Isolated Phase CU
35 m
Isolated Phase CU
35 m
Isolated Phase CU
8 m
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
4-3/C 240
CU 40 m
1MKA76
8,44 MW
3-3/C 300
CU 20 m
Open
CARGAS 1BJA76
270 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1-3/C 300
CU 20 m
3-3/C 300
CU 120 m
Excitación 1MKC10
944 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1-3/C 150
CU 40 m
LCI 1BPA10_1
2725 kVA
LCI 1BPA10_2
2725 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
3-3/C 240
CU 40 m
Open
88WN-1
224 kW
1-3/C 70
CU 50 m
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
88WN-2
224 kW
1-3/C 70
CU 50 m
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
Open
88AK-1
375 kW
1-3/C 70
CU 50 m
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
88AK-2
375 kW
1-3/C 70
CU 50 m
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
Open
W-1BMB20
1XKA52
2000 kW
6-3/C 300
CU 50 m
Open
CARGAS 1BNB52
82,2 kVA
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
W-1BMB52
MBN50 AH010
450 kVA
1BJA80
400 kVA
W-1BJA12
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
2-3/C 185
CU 40 m 2-3/C 185
CU 40 m
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
Open
W-1BJA51W-1BJA11
2-3/C 240
CU 115 m
1BJA76
0,48 kV
1BBA76
6,6 kV
S.E. Reque
220 kV
1BNB52
0,38 kV
CGDE
0,48 kV
1BMA52
0,48 kV
BUS GEN
18 kV
S.E. Etén
220 kV
1BFA51
0,48 kV
1BFA53
0,48 kV
1BBA51
6,6 kV
1MKA10
225 MW
Isolated Phase CU
35 m
Isolated Phase CU
35 m
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
Isolated Phase CU
8 m
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
1MKA76
8,44 MW
Open
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
Open
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
Red eléctrica Peruana
3022 MVAsc
Excitación 1MKC10
944 kVA
LCI 1BPA10_1
2725 kVA
Sistema PCI
200 kW
1XKA52
2000 kW
Open
88WN-1
224 kW
Open
88AK-1
375 kW
88WN-2
224 kW
Open
88AK-2
375 kW
MBN50 AH010
450 kVA
CARGAS 1BNB52
82,2 kVA
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
W-1BJA51W-1BMB20W-1BJA12W-1BJA11
Narcissus
AL 2,92 km
6-3/C 300
CU 50 mW-1BMB52
1BJA80
400 kVA
3-3/C 300
CU 120 m
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVAOpen
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
CARGAS 1BJA76
270 kVA
3-3/C 300
CU 20 m1-3/C 300
CU 20 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 100 m
1-3/C 70
CU 70 m
1-3/C 70
CU 70 m
2-3/C 185
CU 40 m
2-3/C 185
CU 40 m
1-3/C 150
CU 40 m
3-3/C 240
CU 40 m
4-3/C 240
CU 40 m
1-3/C 70
CU 100 m
1-3/C 70
CU 50 m
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
LCI 1BPA10_2
2725 kVA
2-3/C 240
CU 115 m
One-Line Diagram - OLV1 (Load Flow Analysis)
page 2 11:11:38 may 02, 2014 Project File: Eten
RESERVA FRÍA ETEN
1BJA11
0,48 kV
1BJA12
0,48 kV
1BMB52
0,48 kV1BJA51
0,48 kV
1BMB20
0,48 kV
CARGAS 1BMB20
235 kVA
1MBV10AP001-M01
75 kW
1BMA52
4-3/C 240
CU 50 m
Compresor 1
37 kW
CARGAS 1BJA51
650 kVA
1BFA51
4-3/C 240
CU 20 m
1BMA52
2-3/C 150
CU 20 m
Compresor 2
37 kW
Open
CARGAS 1BMB52
231 kVA
CARGAS 1BJA12
592 kVA
6-3/C 240
CU 50 m
1BFA53
CARGAS 1BJA11
695 kVA
1MBV10AP002-M1
75 kW
6-3/C 240
CU 50 m
1BFA51
1BMB20
0,48 kV
1BJA51
0,48 kV
1BMB52
0,48 kV
CARGAS 1BMB20
235 kVA
Compresor 1
37 kW
Compresor 2
37 kW
Open
CARGAS 1BMB52
231 kVA
1BFA51
1BMA52 1BFA53 1BFA51
1MBV10AP001-M01
75 kW
4-3/C 240
CU 50 m
1BJA12
0,48 kV
6-3/C 240
CU 50 m
1BJA11
0,48 kV
6-3/C 240
CU 50 m
4-3/C 240
CU 20 m
2-3/C 150
CU 20 m
1BMA52
CARGAS 1BJA11
695 kVA
CARGAS 1BJA12
592 kVA
CARGAS 1BJA51
650 kVA
1MBV10AP002-M1
75 kW
CÁLCULOS ELÉCTRICOS Rev. C
ANEXO II
RFE-1-YE__-ECE-IDO-001 Pág/Page 1 de/of 13
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
ANEXO II:
DATOS GENERADOR PRINCIPAL
SIZE DWG NO SH REV
A 106T0023 1 -
©COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
SIGNATURES & DATES
GE ENERGY GENERAL ELECTRIC COMPANYGENERATOR
Schenectady, NY, USA
DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26
CHECKED - See PLM
GENERATOR ELECTRICAL DATAUTE Reserva Fria Eten
CHECKED DATE (YYYY-MM-DD) -12/10/26
ENGR - SEE PLM
ENGRG DATE (YYYY-MM-DD) - 12/10/26FIRST MADE FOR: 761X201 MLI/COST CODE: C902
APPLIED PRACTICES
ADDITIONAL APPROVALSSEE PLM SYSTEM FOR REGISTERED
INFORMATION
SIZE CAGE CODE DWG NO
A 106T0023SIM TO: RDO CODE: SHEET 1 of 12
REV ZONE DESCRIPTIONDATE
(YYYY-MM-DD)APPROVED
- N/A Initial Release. ECO0078796 12/10/26 See PLM
ITEM DESCRIPTION DWG. NO.
LIST OF COMPLEMENTARY DOCUMENTS
THIS DRAWING TO BE REVISED IN MICROSOFT WORD ONLY. THE SOURCE FILE IS STORED IN A SECURE DATABASE
THIS DOCUMENT SHALL BE REVISED IN ITS ENTIRETY. ALL SHEETS OF THIS DOCUMENT ARE THE SAME REVISION LEVEL AS INDICATED.
REVISION DESCRIPTION IS FULLY STATED ON FIRST SHEET OF DOCUMENT
DWG Number 106T0023 Rev - Released 11/2/2012 Page 1 of 12
GE Proprietary Information - Class II (Internal) US EAR - NLR
SIZE DWG NO SH REV
A 106T0023 2 -
©COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
GE ENERGY GENERAL ELECTRIC COMPANYGENERATOR
Schenectady, NY, USA
SIZE CAGE CODE DWG NO
A 106T0023DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26 RDO CODE: SHEET 2 of 12
ESTIMATED GENERATOR DATA
Customer: ACS Cobra
Station/Project: UTE Reserva Fria Eten
Generator Number: 761X201
Generator Type: 7FH2B LU
GENERATOR RATING
Data for Proposal No/Electrical Design: 726191G2 Jul 23 2012
ATB 2 281250 kVA 3600 RPM 18000 Volts 0.8 PF 45 psig (310 kPa) 42 °C Gas 225000 kW 9021 Amps410 Field Volts 79 Ft (24.1 m) Alt 0.44 SCR 60 Hz 3 Phase WYE Connection
Exciter Rating
Type Static
875 kW 410 Volts 2134 D.C.Amps Field Amps @ Generator rated Load 2011
Total temperatures are guaranteed not to exceed:
Stator coils: 104 °C by embedded detector
Field coils 120 °C by Resistance
Collector Gas Rise 20 °C by RTD
Insulation Class
Armature F
Field F
Temperature Rise
B
B
COOLING WATER REQUIREMENTS @ GENERATOR RATING
Generator Output: 281250 kVA
Loss to Coolers: 2075 kW
Inlet Water Temperature: 36.4 °C
Outlet Cold Gas Temperature 42 °C
Coolant 100% Water
Maximum Fouling Factor: 0.0005 ft2 hr °F/ Btu (0.0881 m2 °K/ kW)
Total Water Flow Required: 1820 GPM (413.1 m3/hr) (total for all coolers)
Coolant temperature Max 40.7 °C
Head Loss Per Cooler: 12.92 Feet of Water (38.6 kPa)
Maximum Operating Pressure: 125 psig (862 kPa)
DIELECTRIC TESTS (Between coils and ground, 50/60 hertz AC for 1 min)
Stator 37000V
Rotor 3750V
DWG Number 106T0023 Rev - Released 11/2/2012 Page 2 of 12
GE Proprietary Information - Class II (Internal) US EAR - NLR
SIZE DWG NO SH REV
A 106T0023 3 -
©COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
GE ENERGY GENERAL ELECTRIC COMPANYGENERATOR
Schenectady, NY, USA
SIZE CAGE CODE DWG NO
A 106T0023DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26 RDO CODE: SHEET 3 of 12
REACTANCES (Per Unit): Direct Axis Quadrature AxisSaturated Synchronous Xdv 2.39 Xqv 2.27Unsaturated Synchronous Xdi 2.39 Xqi 2.27Saturated Transient X'dv 0.265Unsaturated Transient X'di 0.300 X'q 0.505Saturated Sub transient X"dv 0.170 X"qv 0.170Unsaturated Sub transient X"di 0.220 X"qi 0.220Saturated Negative Sequence X2v 0.170Unsaturated Negative Sequence X2i 0.220Saturated Zero Sequence X0v 0.115Unsaturated Zero Sequence X0i 0.115Saturated Leakage Reactance Xlv 0.150Unsaturated Leakage Reactance Xli 0.170
FIELD TIME CONSTANTS (Seconds @ 125 °C)Open Circuit T'd0 7.7 T'q0 0.62Three Phase Short Circuit Transient T'd3 0.77 T'q 0.14Line To Line Short Circuit Transient T'd2 1.32Line To Neutral Short Circuit Transient T'd1 1.6Short Circuit Sub transient T"d 0.026 T"q 0.026Open Circuit Sub transient T"d0 0.039 T"q0 0.076
ARMATURE DC COMPONENT TIME CONSTANTS (Seconds@ 100 °C)
Three Phase Short Circuit Ta3 0.42Line To Line Short Circuit Ta2 0.42Line To Neutral Short Circuit Ta1 0.32
ARMATURE WINDING SEQUENCE RESISTANCES (Per Unit)
Positive R1 0.0033Negative R2 0.0155Zero R0 0.0067
Reactance, Resistance and Time Constant data may be interpreted per IEEE 115, Part II.
The base reactance (“UNIT”) is calculated by the armature kV squared / MVA.
Base reactance = 1.152 Ohms
Rotor Short-Time Thermal Capacity, (I2)2t 10 s
Turbine-Generator Combined Train Inertia, WR2
389970 lb-ft2
(16433 kg-m2)
Turbine-Generator Combined Inertia Constant, H 4.151 kW-s/kVA
Three Phase Armature Winding Capacitance 0.9651 F
Armature Winding DC Resistance (Per Phase) 0.001472 Ω (100 °C)
Field Winding DC Resistance 0.1804 Ω (125 °C)
Field Current At Rated Kva, Armature Voltage, & PF 2011 A
Field Current At Rated Kva, Armature Voltage, 0 PF Lagging*
2460 A
(*For Systems Study Only - Not Allowable Operating Point)
DWG Number 106T0023 Rev - Released 11/2/2012 Page 3 of 12
GE Proprietary Information - Class II (Internal) US EAR - NLR
SIZE DWG NO SH REV
A 106T0023 4 -
©COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
GE ENERGY GENERAL ELECTRIC COMPANYGENERATOR
Schenectady, NY, USA
SIZE CAGE CODE DWG NO
A 106T0023DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26 RDO CODE: SHEET 4 of 12
MACHINE SATURATION DATA
S/1.0 = 0.0792 Machine saturation may be calculated from the data of curves A and B of
S/1.2 = 0.7214 “ESTIMATED SATURATION AND SYNCHRONOUS IMPEDANCE CURVES”.
“S/1.0” is the field amp difference from B to A divided by the field amp of A at 1.0 pu voltage.
X/R RATIO
X/R = 134 X/R ratio equals “XPP/DV” * base reactance / armature DC resistance at 100 C
DWG Number 106T0023 Rev - Released 11/2/2012 Page 4 of 12
GE Proprietary Information - Class II (Internal) US EAR - NLR
SIZE DWG NO SH REV
A 106T0023 5 -
©COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
GE ENERGY GENERAL ELECTRIC COMPANYGENERATOR
Schenectady, NY, USA
SIZE CAGE CODE DWG NO
A 106T0023DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26 RDO CODE: SHEET 5 of 12
DWG Number 106T0023 Rev - Released 11/2/2012 Page 5 of 12
GE Proprietary Information - Class II (Internal) US EAR - NLR
SIZE DWG NO SH REV
A 106T0023 6 -
©COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
GE ENERGY GENERAL ELECTRIC COMPANYGENERATOR
Schenectady, NY, USA
SIZE CAGE CODE DWG NO
A 106T0023DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26 RDO CODE: SHEET 6 of 12
DWG Number 106T0023 Rev - Released 11/2/2012 Page 6 of 12
GE Proprietary Information - Class II (Internal) US EAR - NLR
SIZE DWG NO SH REV
A 106T0023 7 -
©COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
GE ENERGY GENERAL ELECTRIC COMPANYGENERATOR
Schenectady, NY, USA
SIZE CAGE CODE DWG NO
A 106T0023DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26 RDO CODE: SHEET 7 of 12
DWG Number 106T0023 Rev - Released 11/2/2012 Page 7 of 12
GE Proprietary Information - Class II (Internal) US EAR - NLR
SIZE DWG NO SH REV
A 106T0023 8 -
©COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
GE ENERGY GENERAL ELECTRIC COMPANYGENERATOR
Schenectady, NY, USA
SIZE CAGE CODE DWG NO
A 106T0023DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26 RDO CODE: SHEET 8 of 12
DWG Number 106T0023 Rev - Released 11/2/2012 Page 8 of 12
GE Proprietary Information - Class II (Internal) US EAR - NLR
SIZE DWG NO SH REV
A 106T0023 9 -
©COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
GE ENERGY GENERAL ELECTRIC COMPANYGENERATOR
Schenectady, NY, USA
SIZE CAGE CODE DWG NO
A 106T0023DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26 RDO CODE: SHEET 9 of 12
DWG Number 106T0023 Rev - Released 11/2/2012 Page 9 of 12
GE Proprietary Information - Class II (Internal) US EAR - NLR
SIZE DWG NO SH REV
A 106T0023 10 -
©COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
GE ENERGY GENERAL ELECTRIC COMPANYGENERATOR
Schenectady, NY, USA
SIZE CAGE CODE DWG NO
A 106T0023DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26 RDO CODE: SHEET 10 of 12
DWG Number 106T0023 Rev - Released 11/2/2012 Page 10 of 12
GE Proprietary Information - Class II (Internal) US EAR - NLR
SIZE DWG NO SH REV
A 106T0023 11 -
©COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
GE ENERGY GENERAL ELECTRIC COMPANYGENERATOR
Schenectady, NY, USA
SIZE CAGE CODE DWG NO
A 106T0023DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26 RDO CODE: SHEET 11 of 12
DWG Number 106T0023 Rev - Released 11/2/2012 Page 11 of 12
GE Proprietary Information - Class II (Internal) US EAR - NLR
SIZE DWG NO SH REV
A 106T0023 12 -
©COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
GE ENERGY GENERAL ELECTRIC COMPANYGENERATOR
Schenectady, NY, USA
SIZE CAGE CODE DWG NO
A 106T0023DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26 RDO CODE: SHEET 12 of 12
DWG Number 106T0023 Rev - Released 11/2/2012 Page 12 of 12
GE Proprietary Information - Class II (Internal) US EAR - NLR
CÁLCULOS ELÉCTRICOS Rev. C
ANEXO III
RFE-1-YE__-ECE-IDO-001 Pág/Page 1 de/of 7
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
ANEXO III:
DATOS TRANSFORMADOR PRINCIPAL
I PRV PRV JSA
H PRV PRV JSA
G PRV JMM JSA
F PRV JMM JSA
E PRV AAB JSA
D PRV AAB JSA
C EAM AAB AOP
B EAM AAB AOP
A EAM AAB AOP
REV. PREPARADO REVISADO APROBADO
AOP AOP ESR
VÁLIDO PARA INFORMACIÓN 09/12/2010 09/12/2010 09/12/2010
VÁLIDO PARA APROBACIÓN EDITA
VÁLIDO PARA DISEÑO
VÁLIDO PARA OFERTA / COMPRA X
VÁLIDO PARA CONSTRUCCIÓN
AS BUILT
CLIENTE
FECHA
12/04/2012
15/02/2012
ASÍ COMPRADO (CON DATOS FABRICANTE)
ASÍ COMPRADO (punto 22)
15/10/2012
07/03/2013 PUNTOS 141,142,143, 289, 322 a 330
01/10/2013
12/11/2012
EDICIÓN ORIGINALFIRMA
DESCRIPCIÓN
ADECUACIÓN TURBINA GE
FECHA
EDICIÓN INICIAL
31/10/2012
COMENTARIOS COBRA
02/02/2012
ADECUACIÓN NORMATIVA
FIRMA
REVISADO
FECHA
HOJA DE DATOSTRANSFORMADOR PRINCIPAL
TÍTULO
RFE-1-BAT-EHP-IDO-001
1
SIGUE
2
HOJA DE DATOSTRANSFORMADOR PRINCIPAL
PARA PETICIÓN OFERTA
LINEA DE FUGA
08/10/2013
DOCUMENTO No HOJA
ES
TA
DO
REVISADO COBRA
RESERVA FRIA ETEN
I-FOR INFORMATION X AWC-APPROVED WITH COMMENTSApproval not required Valid for construction. Return back the document
corrected within two weeks
A-APPROVED R-REJECTEDValid for construction Not valid for construction. Return back the document
corrected within one week
RESPONSIBLE & DATE
IMPORTANT NOTE: documentation approval does not relieve the manufacturer of its
responsibility for the adequancy and suitability of the information, equipments and/or
materials included in it for the function that is intended
YOU MUST FILL IN THE DOCUMENT WITH ALT INFORMATION THE DOCUMENT'S TITLE IS: DATA SHEET THE CODE'S TITLE IS: RFE-1-BAT-EHP-ALT-001
ALSTOM
COMPLETE
YOU MUST START ON NUMBER 1 XGR 29.01.2014
Nº CARACTERISTICAS SOLICITADO UD DATOS DE FABRICANTE
12 Nº DE UNIDADES 1 Uds. 1
3
IDENTIFICACION DE EQUIPOS - Three phases, two windings withon-load tap-changer
4 MODELO -
5 TIPO PROTECCIÓN INTEMPERIE - Outdoor
6 NORMA DE DISEÑO IEC 60076 - IEC 60076
7 FRECUENCIA 60 Hz 60
8 Nº DE FASES 3 Uds. 3
9 Nº DE ARROLLAMIENTOS 2 Uds. 2
10 CORRIENTE DE CORTOCIRCUITO:
11 EN PRIMARIO A.T.
12INTENSIDAD MÁXIMA DE CORTOCIRCUITO EFICAZ SIMÉTRICA
50 kA 50
13
INTENSIDAD SIMÉTRICA DE CORTOCIRCUITO EFICAZ SOPORTADA POR EL TRANSFORMADOR DURANTE 2 seg
kA IEC standard
14INTENSIDAD DE CRESTA SOPORTADA POR EL TRANSFORMADOR
kA IEC standard
15 EN SECUNDARIO B.T.
16INTENSIDAD MÁXIMA DE CORTOCIRCUITO EFICAZ SIMÉTRICA
150 kA 150
17
INTENSIDAD SIMÉTRICA DE CORTOCIRCUITO EFICAZ SOPORTADA POR EL TRANSFORMADOR DURANTE 2 seg
kA IEC standard
18INTENSIDAD DE CRESTA SOPORTADA POR EL TRANSFORMADOR
kA IEC standard
19 NIVEL CONTAMINACIÓN S/ IEC 60815 IV (muy alto) - IV (muy alto) Zona desértica
20 LINEA DE FUGA EN EXTERIOR 31 mm/kV 31
21
22
POTENCIAS ASIGNADAS EN SERV. CONTINUO, SIN SOBREPASAR LOS CALENTAMIENTOS MÁXIMOS ADMISIBLES A 40°C AMBIENTE
225/300ONAN/ONAF
MVA 225/300MVA ONAN/ONAF
23
VALORES DE INCREMENTOS MÁXIMOS DE Tª (CALENTAMIENTO) SOBRE LA Tª AMBIENTE SEGÚN IEC 60076-2 A LA POTENCIA ASIGNADA:
IEC 60076-2
24EN EL COBRE (MEDIDO POR VARIACIÓN DE RESISTENCIA) 65 K 65
25EN EL ACEITE (MEDIDO POR TERMÓMETRO EN LA CAPA SUPERIOR DEL ACEITE)
60 K 60
26SOBRETENSIÓN PERMITIDA SOBRE LA ASIGNADA, DURANTE 5 seg
140 % Un Over-excitation at 140% for 5 seconds
27TENSIONES ASIGNADAS EN VACÍO: No-load winding voltage
(nominal voltage)28 ARROLLAMIENTO DE A.T. 220 ± 10x1,5% kV 220 ± 10x1,5 %
29 ARROLLAMIENTO DE B.T. 18 kV 18
30 CORRIENTES ASIGNADAS:
31 ARROLLAMIENTO DE A.T.:
32 NOMINAL INP A Rated current:787.2
33 VACÍO IOP A No-load current: 0.35%pu
34CONEXIÓN ICP (INTENSIDAD MÁXIMA EN LA CONEXIÓN INRUSH)
A Inrush current: 4787A (0.008s)
35 ARROLLAMIENTO DE B.T.:
36 NOMINAL INP A Rated current: 9622.5A
37 VACÍO IOP A No-load current: 0.35%pu
38CONEXIÓN ICP (INTENSIDAD MÁXIMA EN LA CONEXIÓN INRUSH)
A Inrush current: 58700A (0.008s)
39 GRUPO DE CONEXIÓN (PRIMARIO/SECUNDARIO) YNd1 - YNd1
40
CAPACIDAD MÁXIMA DE SOBRECARGA A LA TEMP. AMB. 40ºC, TENSIÓN NOM, CARGA INICIAL 100% Y SIN DISMINUCIÓN DE VIDA APRECIABLE:
41CONTINUA %PN
5% overload of transformer rated power
42DURANTE 4 HORAS %PN
15% overload of transformer rated power
43DURANTE 2 HORAS %PN
25% overload of transformer rated power
44DURANTE 1 HORA %PN
30% overload of transformer rated power
45 CARACTERÍSTICAS DEL NÚCLEO :
46 TIPO DE CHAPA
47SOBREXCITACIÓN SEGÚN CEI 60076-1, EN ARROLLAMIENTO DE B.T.:
48 PLENA CARGA EN PERMANENCIA %VN/FN1,05
49 VACÍO EN PERMANENCIA %VN/FN1,15
50 VACÍO DURANTE 2 min %VN/FN1,20
51 VACÍO DURANTE 2 seg %VN/FN1,50
52 INDUCCIÓN MÁXIMA:
53 A TENSIÓN NOMINAL TESLAS 1,72
54 AL 105% DE LA TENSIÓN NOMINAL TESLAS 1,80
55 AL 110% DE LA TENSIÓN NOMINAL TESLAS 1,90
56 AL 115% DE LA TENSIÓN NOMINAL TESLAS 2,00
57 TENSIÓN DE CORTOCIRCUITO: (ONAN 225 MVA) Based on 225MVA
58 TENSIÓN DE CORTOCIRCUITO: Impedance %
59 TOMA SUPERIOR %UN11.2% (Maximum tap)
OBSERVACIONES
CARACTERÍSTICAS DEL TRANSFORMADOR
GENERAL
VALOR ESTIMADO
VALOR ESTIMADO
RFE-1-BAT-EHP-IDO-001-REVI GSU V00 (2013-12-13) 2 / 6
ALSTOM
COMPLETE WITH ALSTOM INFORMATION
Nº CARACTERISTICAS SOLICITADO UD DATOS DE FABRICANTE OBSERVACIONES
60 TOMA CENTRAL 10 %UN10% (Rated tap)
61 TOMA INFERIOR %UN9.4% (Minimum tap)
62TENSIÓN DE CORTOCIRCUITO HOMOPOLAR: Base en 225MVA (cortocircuito
ZERO SEQ.IMPEDANCIA)
63
TOMA SUPERIOR %UN10.5%
(For reference only, test value will be supplied)
64
TOMA CENTRAL %UN9%
(For reference only, test value will be supplied)
65
TOMA INFERIOR %UN8.5%
(For reference only, test value will be supplied)
66 TENSIÓN RESISTIVA DE CORTOCIRCUITO: Based on 225MVA
67 TOMA SUPERIOR %UN0,15%
68 TOMA CENTRAL %UN0,16%
69 TOMA INFERIOR %UN0,18%
70 TENSIÓN REACTIVA DE CORTOCIRCUITO: Based on 225MVA
71 TOMA SUPERIOR %UN11,20%
72 TOMA CENTRAL %UN10,00%
73 TOMA INFERIOR %UN9,40%
74 IMPEDANCIA DE CORTOCIRCUITO (AT): Based on 225MVA
75 PRIMARIO TOMA SUPERIOR Ω 31,8
76 PRIMARIO TOMA CENTRAL 21,5 Ω 21,5
77 PRIMARIO TOMA INFERIOR Ω 14,6
78SECUNDARIO Ω 0.144
(based on rated voltage position)79 PÉRDIDAS:
80 EN VACÍO: No-load losses
81 90% UNkW 170
82 100% UNkW 180
83 105% UNkW 220
84 110% UNkW 282
85 115% UNkW 300
86 EN CARGA: On-load losses
87 25% Sn kW 40
88 50% Sn kW 158
89 75% Sn kW 355
90 100 Sn kW 630
91 POR REFRIGERACIÓN kW 8 (pérdida auxiliar)
92 PÉRDIDAS TOTALES: (Excluir pérdida auxiliar)
93 80 % Sn kW 583
94 100% Sn kW 810
95 RELACIÓN DE PÉRDIDAS DE DISPERSIÓN Y TOTALES p.u. 1,1
96 RENDIMIENTO COS φ = 0,85: eficiencia @ PF=0.85
97 25% PN% 0,9965
98 50% PN% 0,9973
99 75% PN% 0,9972
100 100% PN% 0,9968
101 ARROLLAMIENTOS:
102 ARROLLAMIENTO PRIMARIO A.T.:103 TENSIÓN MÁS ELEVADA PARA EL MATERIAL 245 kV 245 (Sistema de tensión más
elevada)104 TENSIÓN SOPORTADA A FRECUENCIA INDUSTRIAL 460 kV 460 (A.C)
105 TENSIÓN SOPORTADA A IMPULSO TIPO RAYO (BIL) 1050 kV 1050 (BIL)
106
TENSIÓN DE PRUEBA CON ONDA DE CHOQUE CORTADA / TENSIÓN DE ENSAYO DE IMPULSO DE MANIOBRA
kV 1155
107TENSIÓN DE PRUEBA A TENSIÓN INDUCIDA (LARGA DURACIÓN)
kV 212
108 MATERIAL DE PARTE ACTIVA COBRE De cobre (material de winding)
109 RIGIDEZ ELECTRODINÁMICA kA Corriente de cortocircuito: HV 5.9
110 DENSIDAD DE CORRIENTE A/mm2 HV 3.0 (Normal.tap)
111NEUTRO AT: HV Neutral punto nivel de
aislamiento
112 TENSIÓN MÁS ELEVADA PARA EL MATERIAL 245 kV 123
113 TENSIÓN SOPORTADA A FRECUENCIA INDUSTRIAL 460 kV 230
114 TENSIÓN SOPORTADA A IMPULSO TIPO RAYO (BIL) 1050 kV 550
115 ARROLLAMIENTO SECUNDARIO B.T.:116 TENSIÓN MÁS ELEVADA PARA EL MATERIAL 24 kV 24
117 TENSIÓN SOPORTADA A FRECUENCIA INDUSTRIAL 50 kV 50
118 TENSIÓN SOPORTADA A IMPULSO TIPO RAYO (BIL) 125 kV 125
119 MATERIAL DE PARTE ACTIVA COBRE De cobre (material de winding)
120 RIGIDEZ ELECTRODINÁMICA kA Corriente de cortocircuito: LV:41.6
121 DENSIDAD DE CORRIENTE A/mm2 ~ 3.5
122 AISLADORES PASATAPAS:
123 ARROLLAMIENTO PRIMARIO A.T.:124 FABRICANTE - Trench/CHINA
125
TIPO CONEXIÓN LÍNEA AÉREA - CONDUCTOR
DESNUDO
- Oil-Air Bushings with air side terminal
RFE-1-BAT-EHP-IDO-001-REVI GSU V00 (2013-12-13) 3 / 6
Nº CARACTERISTICAS SOLICITADO UD DATOS DE FABRICANTE OBSERVACIONES
126 CORRIENTE NOMINAL 1000 A 1250
127 TENSIÓN MÁS ELEVADA PARA EL MATERIAL 245 kV 245
128TENSIÓN DE PRUEBA A FRECUENCIA INDUSTRIAL AMBIENTE SECO / 1 min
460 kV 460
129
TENSIÓN DE PRUEBA A FRECUENCIA INDUSTRIAL AMBIENTE LLUVIOSO /1 min
kV 460
130 TENSIÓN DE PRUEBA A IMPULSO TIPO RAYO (BIL) 1050 kV 1050
131 LÍNEA DE FUGA A TENSIÓN COMPUESTA >=7565 mm > =7595
132 TENSIÓN DE ENSAYO A IMPULSO TIPO MANIOBRA 850 kV 850
133 TIPO DE AISLAMIENTO - Oil-Air Bushings 245kV/1250A
134 TIPO DE BORNA - 245kV/1250A
135 TOMA CAPACITIVA - YES
136 COLOR DE LA PORCELANA - Brown
137 NEUTRO AT:138 FABRICANTE - ZhiDa/CHINA
139
TIPO CONEXIÓN CABLE DE COBRE AISLADO
- Oil-Air Bushings with air side terminal
140 CORRIENTE NOMINAL A 1250
141 TENSIÓN MÁS ELEVADA PARA EL MATERIAL 123 kV 123
142TENSIÓN DE PRUEBA A FRECUENCIA INDUSTRIAL AMBIENTE SECO / 1 min
230 kV 230
143
TENSIÓN DE PRUEBA A FRECUENCIA INDUSTRIAL AMBIENTE LLUVIOSO /1 min
kV 230
144 TENSIÓN DE PRUEBA A IMPULSO TIPO RAYO (BIL) 550 kV BIL550
145 LÍNEA DE FUGA A TENSIÓN SIMPLE >=3.813 mm > =3813
146 TENSIÓN DE ENSAYO A IMPULSO TIPO MANIOBRA kV BIL 550
147 TIPO DE AISLAMIENTO - Oil-Air Bushings 123kV/1250A
148 TIPO DE BORNA - 123KV/1250A
149 COLOR DE LA PORCELANA - Brown
150 ARROLLAMIENTO SECUNDARIO B.T.:151 FABRICANTE - ZhiDa/CHINA
152
TIPO CONEXIÓN BARRAS DE FASE AISLADA
- Insulated phase busbars
153 CORRIENTE NOMINAL 10.000 A 16000
154 TENSIÓN MÁS ELEVADA PARA EL MATERIAL 24 kV 24
155TENSIÓN DE PRUEBA A FRECUENCIA INDUSTRIAL AMBIENTE SECO / 1 min
50 kV 50
156
TENSIÓN DE PRUEBA A FRECUENCIA INDUSTRIAL AMBIENTE LLUVIOSO /1 min
kV 50
157 TENSIÓN DE PRUEBA A IMPULSO TIPO RAYO (BIL) 125 kV 125
158 LÍNEA DE FUGA A TENSIÓN COMPUESTA mm 744
159 TENSIÓN DE ENSAYO A IMPULSO TIPO MANIOBRA kV BIL 125
160 TIPO DE AISLAMIENTO - Pure porcelain type bushing
161 TIPO DE BORNA - Oil-Air bushing 24kv/16000A
162 TOMA CAPACITIVA - NA
163 NIVEL DE RADIOINTERFERENCIA µV As per IEC
164NIVEL DE RUIDO (PRESIÓN ACÚSTICA A 1 m, A POTENCIA NOMINAL, CON TODA LA REFRIGERACIÓN FUNCIONANDO)
≤ 85 dB(A) 75dB(A) Nivel de presión
165 CAPACIDAD A TIERRA EN LA TOMA MEDIA:
166
PRIMARIO µF 914pF Capacitance of HV to earth(For reference only, test value will
be supplied)
167
SECUNDARIO µF 8372pF Capacitance of HV to earth (For reference only, test value will
be supplied)168 TIPO REFRIGERACIÓN ONAN/ONAF - ONAN/ONAF
169 EQUIPO REFRIGERACIÓN FORZADA:
170 NÚMERO DE ETAPAS Uds. Two cooling stage, ONAN/ONAF
171 NÚMERO DE RADIADORES Uds. 30
172 NÚMERO DE VENTILADORES POR ETAPA Uds. 15+1(On-line spare fans)
173 POTENCIA DE CADA VENTILADOR kW ~0.5kW Per unit fan
174 TENSIÓN DE LOS VENTILADORES / Hz 480 / 60 V/Hz 480/60
175 TIPO DEL ACEITE MINERAL - mineral
176 CANTIDAD TOTAL DE ACEITE l
177 VELOCIDAD MÁXIMA DEL ACEITE cm/seg
178 GRADO DE PROTECCIÓN VENTILADORES IP IP 55
179 CUBA: Principal tank
180 CUBA PRINCIPAL SI - Yes
181 CUBA SEGREGADA PARA EL REGULADOR NO - No
182 PRESIÓN MÁXIMA kg/cm2 0.1Mpa (presión positiva)
183 PRESIÓN MÍNIMA kg/cm2 133Pa (presión de vacío)
184 DEPÓSITO DE EXPANSIÓN:
185CÁMARA 1 CON BALÓN DE CAUCHO PARA AISLAMIENTO DEL AMBIENTE
SI - Sí (conservador con la bolsa de goma)
186CÁMARA 2 DE LAS MISMAS CARACTERÍSTICAS PARA EL REGULADOR
SI - Sí (para el cambiador)
187188 DIMENSIONES:189 LARGO TOTAL mm Consulte el outline
190 ALTO SIN PASATAPAS mm Consulte el outline
191 ALTO CON PASATAPAS mm Consulte el outline
192 ALTO CON DEPÓSITO DE EXPANSIÓN mm Consulte el outline
193 ALTO CON AUTOVÁLVULAS EN A.T. mm Consulte el outline
CARACTERÍSTICAS FÍSICAS
RFE-1-BAT-EHP-IDO-001-REVI GSU V00 (2013-12-13) 4 / 6
Nº CARACTERISTICAS SOLICITADO UD DATOS DE FABRICANTE OBSERVACIONES
194 ANCHO mm
195 LARGO DE TRANSPORTE mm Consulte el outline
196 ALTO DE TRASNPORTE mm Consulte el outline
197 ANCHO DE TRANSPORTE mm Consulte el outline
198 ANCHO DE VIAS mm Consulte el outline
199 TIPO DE CARRIL kg/m200 PESOS:201 TOTAL kg 276800
202 DEL TRAFO SIN ACEITE kg 212200
203 DEL ACEITE kg 64600
204 DESENCUBADO kg 147000 (Un tanking peso)
205 DEL COBRE kg 23500
206 DE LA CHAPA MAGNÉTICA (NÚCLEO) kg 103000
207 DE LA PIEZA MÁS PESADA DE TRANSPORTE kg 178400
208
CROQUIS ORIENTACIÓN ARMARIO CONTROL Y OLTC
209210 KKS 1BAT10GH002 El cambiador de tomas bajo carga
211FABRICANTE - Huaming Shanghai, China o
equivalente212 TIPO EN CARGA - En carga
213 MARGEN DE REGULACIÓN 220 ± 10x1,5% kV 220 ± 10x1,5 %
214 TENSIÓN EN TOMAS:
215 SUPERIOR 115 %UN115
216 INFERIOR 85 %UN85
217 VALOR DEL PASO 1,5 %UN1,5
218 NUMERO DE TOMAS 21 Uds. 21
219 TENSIONES EN VACIO: Voltaje sin carga
220 EN POSICIÓN SUPERIOR kV 253
221 EN POSICIÓN MEDIA kV 220
222 EN POSICIÓN INFERIOR kV 187
223 CORRIENTES ASIGNADAS EN SERVICIO CONTINUO:
224 EN POSICIÓN SUPERIOR A 685
225 EN POSICIÓN MEDIA A 787
226 EN POSICIÓN INFERIOR A 926
227 TENSIÓN MÁS ELEVADA PARA EL MATERIAL kV 123kV voltage class
228 TENSIÓN DE ENSAYO A FRECUENCIA INDUSTRIAL kV AC230
229 TENSIÓN DE ENSAYO A IMPULSO TIPO RAYO kV BIL550
230 MANDO MOTORIZADO:
231 MOTOR 480 / 60 V / Hz 480/60
232 CONTROL 125 / DC V / Hz 125/DC
233 CALDEO 220 / 60 V / Hz 220/60
234 PROTECCIONES
235 NIVEL (MIN / MAX) SÍ SÍ
236 RELÉ CONTROL FLUJO SÍ SÍ
237 RELÉ SOBREPRESIÓN NO NO
238 ALIVIO SOBREPRESIÓN SÍ SÍ
239 TEMPERATURA SÍ SÍ
240241 KKS 1BAT10GH001 Gabinete de control del ventilador
242 PROTECCIÓN IP65 - IP65
243 MATERIAL - ACERO
244 INDICADORES LOCALES - SI
245 LÁMPARAS INDICADORAS - SI
246 PRUEBA LÁMPARAS - SI
247 CONMUTADORES Y PULSADORES -
248 ALIMENTACIÓN DE BARRAS DE POTENCIA 480 / 60 V / Hz 480/60
249 RESISTENCIA DE CALDEO SI - SI
250 ALUMBRADO Y TOMA DE CORRIENTE SI - SI
251 CONTACTOS DE ALARMA LIBRES DE POTENCIAL SI - SI
252 ALIMENTACIÓN PARA ALUMBRADO Y CALDEO 220 / 60 V / Hz 220/60
253ALIMENTACIÓN PARA DISPOSITIVO DE IMAGEN TÉRMICA Y CONTROL
125 / DC V / Hz 125/DC
254255 TIPO MINERAL - Mineral (Nynas libra)
256 FABRICANTE - Nynas
257 5% RESERVA SI - SI
258259 BORNAS A.T.:
260 CANTIDAD POR FASE NO REQUERIDO Uds. /
261 CORRIENTE P A /
262 CORRIENTE S1 A /
TRANSFORMADORES DE CORRIENTE EN BUSHING (A PARTE DEL DE LA IMAGEN TÉRMICA)
ACEITE
CAMBIADOR DE TOMAS
ARMARIO DE MANIOBRA Y CONTROL
AT
BT
OLTC
Y
CONTR
RFE-1-BAT-EHP-IDO-001-REVI GSU V00 (2013-12-13) 5 / 6
Nº CARACTERISTICAS SOLICITADO UD DATOS DE FABRICANTE OBSERVACIONES
263 POTENCIA S1 - /
264 PRECISIÓN S1 - /
265 CORRIENTE S2 A /
266 POTENCIA S2 A /
267 PRECISIÓN S2 - /
268 INTENSIDAD LIMITE TERMICA kA /
269 INTENSIDAD LIMITE DINAMICA (PICO) kA /
270 FABRICANTE - /
271 MODELO - /
272FACTOR DE SEGURIDAD (PARA TRAFOS DE MEDIDA)
- /
273 BORNA DE NEUTRO AT: Bushing tipo CT
274 CANTIDAD 1 Uds. 1
275 CORRIENTE P 2.000 A 2.000276 CORRIENTE S1 5 A 5
277 POTENCIA S1 100 VA 100
278 PRECISIÓN S1 5P20 - 5P20279 CORRIENTE S2 5 A 5
280 POTENCIA S2 100 A 100
281 PRECISIÓN S2 5P20 - 5P20
282 INTENSIDAD LIMITE TERMICA kA Despues de orden
283 INTENSIDAD LIMITE DINAMICA (PICO) kA Despues de orden
284 FABRICANTE - China
285 MODELO - Proteccion
286FACTOR DE SEGURIDAD (PARA TRAFOS DE MEDIDA)
- 1,3
287 BORNAS DE B.T.:
288 CANTIDAD POR FASE 1 Uds. 1
289 CORRIENTE P 12.000 A 12.000290 CORRIENTE S1 5 A 5
291 POTENCIA S1 100 VA 100
292 PRECISIÓN S1 5P20 - 5P20
293 CORRIENTE S2 5 A 5
294 POTENCIA S2 100 A 100
295 PRECISIÓN S2 5P20 - 5P20
296 INTENSIDAD LIMITE TERMICA kA Despues de orden
297 INTENSIDAD LIMITE DINAMICA (PICO) kA Despues de orden
298 FABRICANTE - China
299 MODELO - Proteccion
300FACTOR DE SEGURIDAD (PARA TRAFOS DE MEDIDA)
- 1,3
301302 CUBA PRINCIPAL:
303 RUEDAS SI - SI
304 CÁNCAMOS DE ELEVACIÓN SI - SI
305 APOYOS PARA GATOS HIDRÁULICOS SI - SI
306CONEXIONES FLEXIBLES ENTRE LA CUBA Y LA TAPA
SI - SI
307 VÁLVULA DE VACIADO SI - SI
308 VÁLVULA DE TOMA DE MUESTRAS SI - SI
309 DEPÓSITO DE EXPANSIÓN SI -
310 DESECADOR DE SILICAGEL SI - SI
311 TERMINALES PARA CONEXIÓN DE P.A.T. AL MENOS 2 - Consulte el outline
312 PLACA DE CARACTERÍSTICAS INOX SI - SI
313 VÁLVULA CONEXIÓN DE FILTRO SI - SI
314315 RELES DE PROTECCION:
316 INDICADOR DE NIVEL SI - SI
317 TERMÓMETRO TEMPERATURA ACEITE SI - SI
318 RELÉ BUCHHOLZ SI - SI
319 DETECCIÓN DE AUMENTO DE PRESION SI SI
320 IMAGEN TÉRMICA. SI SI
321 SISTEMA MONITORIZACIÓN DE GASES SÍ SI
322 PARARRAYOS
323 UNIDADES 3 Uds.
324 FABRICANTE / MODELO325 TECNOLOGÍA MO (Metal-Oxide)326 TENSIÓN NOMINAL (Ur) 198 kV PENDIENTE.
327 INTENSIDAD NOMINAL DE DESCARGA (Ir) 10 kA
328 CLASE LINEA DE DESCARGA 3 -
329 AISLADORES CERAMICOS -
330 NIVEL CONTAMINACIÓN S/ IEC 60815 IV (muy alto) - Zona desértica
ACCESORIOS
RFE-1-BAT-EHP-IDO-001-REVI GSU V00 (2013-12-13) 6 / 6
CÁLCULOS ELÉCTRICOS Rev. C
ANEXO IV
RFE-1-YE__-ECE-IDO-001 Pág/Page 1 de/of 15
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
ANEXO IV:
DATOS GENERADOR AUXILIAR
PLANTA DE RESERVA FRÍADE GENERACIÓN DE ETEN S.A
Wärtsilä Finland Oy
PROYECTO
RESERVA FRÍA ETEN
CONTRATISTA
UTE RESERVA FRÍA ETEN
TÍTULO
Generator Technical Specification
Nº DE DOCUMENTO PROYECTO
RFE-1-MKA-EIP-WRT-001Wärtsilä doc id: DBAC857966 - | Original doc id:
REV 00EDITADO PARA
FECHA 04/02/2014
Daniel Byskata Tuomas Karri Thomas Lönngrén
REALIZADO REVISADO APROBADO
Este documento contiene información privada y no puede ser duplicado, modificado o divulgado a terceros sin el consentimientoescrito de COBRA. La única copia controlada de este documento está en el Sistema Informático de Gestión Documental de COBRA.
Generator Technical Specification
Rev. 00
RFE-1-MKA-EIP-WRT-001
Este documento contiene información privada y no puede ser duplicado, modificado o divulgado a terceros sin el consentimiento
escrito de COBRA. La única copia controlada de este documento está en el Sistema Informático de Gestión Documental de COBRA.
CONTROL DE MODIFICACIONES
Revisión Fecha Modificaciones
00 - 04/02/2014 For review
Status: Approved Internal Document id: DBAC857966 - Page 2 (14)
Status: Approved Internal Document id: DBAC857966 - Page 3 (14)
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. Ó Copyright 2011 ABB
Prep. Helena Krivetz/PGD 19.12.2013 TECHNICAL SPECIFICATION No. of sh.
Appr. PGD 12Resp. dept. PGD
Document identification Lang. Rev. ind. Sheet
ABB Oy / Motors and Generators 3AFP 54306401 en A 1TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;SAVEDATE: 12/19/2013 5:46:00 PM
TECHNICAL SPECIFICATION
Project name: Reserva Fria EtenOur reference number: 5430HG401Customer’s reference number:Customer: WÄRTSILÄ FINLAND OYFinal customer:Application: Diesel/Gas engineType designation: AMG 1120LS10 DSE
NOTES
CONTENTS
SECTION:
1 PERFORMANCE DATA (Calculated values) 2
2 CONFIGURATION AND SCOPE OF SUPPLY 5
3 ACCESSORIES 9
4 P/Q DIAGRAM 11
5 NO LOAD AND SHORT-CIRCUIT CURVE 12
Revision Change Date Updated byA Original 19.12.2013 HEKR
Status: Approved Internal Document id: DBAC857966 - Page 4 (14)
Document identification Lang. Rev. ind. Sheet
ABB Oy / Motors and Generators 3AFP 54306401 en A 2TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;SAVEDATE: 12/19/2013 5:46:00 PM
1 PERFORMANCE DATA (Calculated values)
TYPE
Type designation: AMG 1120LS10 DSE
RATINGS
Output: 10549 kVA Direction of rotationDuty: S1 (Facing drive end): CCWVoltage: 6600 V Weight: 33400 kgCurrent: 923 A Inertia: 3190 kgm^2Power factor: 0,80 Protection by enclosure: IP23Frequency: 60 Hz Cooling method: IC0A1Speed: 720 rpm Mounting arrangement: IM1101Overspeed: 864 rpm
STANDARDS
Applicable standard: IECMarine classification: NoneHazardous area classification: NoneTemperature rise stator / rotor: B/BInsulation class: F
ENVIRONMENTAL CONDITIONS (max. values)
Ambient temperature: 50 °C Altitude: 1000 maslCoolant temperature: °C
ASSUMED DATA
Driving equipment: Wärtsilä 20V34SG/DFApprox. mech. power: 8650 KW
EFFICIENCY in %
load: 110 % 100 % 75 % 50 % 25 %Efficiency @ power factor 0,80 97,64 97,59 97,32 96,60 94,10Efficiency @ power factor 1,00 98,26 98,21 97,99 97,39 95,34
REACTANCES in %
XD (U): 171,3 XD’ (S): 28,5 XQ’’ (S): 18,2 X0 (U): 9,4XQ (U): 86,1 XD’’ (S): 16,0 X2 (S): 17,1 XP (S): 23,5X1 (U): 13,2 (S) = Saturated value, (U) = Unsaturated value
TIME CONSTANTS (SEC.) AT 75 °C
TD0’: 7,713 TD’: 1,410 TQ0’’: 0,1207 TA: 0,182TD0’’: 0,02938 TD’’: 0,01677 TQ’’: 0,0280
Status: Approved Internal Document id: DBAC857966 - Page 5 (14)
Document identification Lang. Rev. ind. Sheet
ABB Oy / Motors and Generators 3AFP 54306401 en A 3TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;SAVEDATE: 12/19/2013 5:46:00 PM
RESISTANCES AT 20 °C
Stator winding: 0,0093 W Field winding: 1,0430 WExcitation winding: 5,7 W
SHORT CIRCUIT
Short circuit ratio: 0,67Sustained short circuit current: 1,7 p.u. (rated excitation)
> 2.5 p.u. (voltage regulator)Sudden short circuit current: 5750 A (symmetric RMS)
14650 A (peak value)
VOLTAGE VARIATION
Maximum allowed amount of starting load:
Maximum voltage drop Power factor Load15 % 0.1 5200 kVA15 % 0.4 5650 kVA15 % 0.8 8800 kVA20 % 0.1 7300 kVA20 % 0.4 7900 kVA
Voltage drop at sudden increase of rated load: 18 %Voltage rise at sudden drop of rated load: 24 %
REACTIVE LOADING
Steady state reactive loading at rated excitation: 8700 KVAR (lagging)Steady state reactive loading at zero excitation: 4650 KVAR (leading)
TORQUE
Rated load torque (Calculated of rated output in kVA): 139900 Nm
The peak values of sudden short circuit air gap torques:2-phase short circuit: 790 % 3-phase short circuit: 560 %
BEARINGS
D-end: Sleeve, self lubricated, locating N.D-end: Sleeve, self lubricated, freeOil viscosity: ISO VG 46
TERMINAL CONNECTIONS (Defined facing drive end)
Direction of main connection: Right downDirection of zero connection: Left down
EXCITATION
Exciter fieldNo load: 3,8 A 27,9 VRated load: 8,1 A 59,3 V
Status: Approved Internal Document id: DBAC857966 - Page 6 (14)
Document identification Lang. Rev. ind. Sheet
ABB Oy / Motors and Generators 3AFP 54306401 en A 4TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;SAVEDATE: 12/19/2013 5:46:00 PM
OTHER
Stored energy constant (rotational energy divided by rated effect): 0,86 sEarth capacitance (1-phase): 0,23 µF
Status: Approved Internal Document id: DBAC857966 - Page 7 (14)
Document identification Lang. Rev. ind. Sheet
ABB Oy / Motors and Generators 3AFP 54306401 en A 5TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;SAVEDATE: 12/19/2013 5:46:00 PM
2 CONFIGURATION AND SCOPE OF SUPPLY
GENERAL
The generator is designed to operate together with a Gas engine.
CONSTRUCTION
The stator frame is a rigid welded steel structure construction. The stator core is built of thinelectric sheet steel laminations which are insulated on both sides with heat-resistant inorganicresin. The radial cooling ducts in the stator core ensure uniform and effective cooling of thestator.
The rotor consists of a shaft and poles fixed on the shaft, exciter and a fan(s). The shaft ismachined of steel forging. The poles are manufactured of 2 mm sheet steel and bolted fromthe top to the shaft. The pole laminations are pressed together with steel bars which arewelded to the end plates. The exciter rotor and the fan are shrink fitted onto the shaft andsecured with a key.
All windings are completely vacuum pressure impregnated with high quality epoxy resin. Thewindings are provided with very strong bracing which withstands all expected mechanical andelectrical shocks and vibrations as well as chemicals. For more information ask for brochure"MICADUR-Compact Industry Insulation System".
The stator frame, core support and end-shields are made of fabricated steel and weldedtogether. The stator frame is closed with steel panels that guide the ventilation air and providethe degree of protection required. The flange mounted bearings are bolted to the end-shields.
According to IM1101 the machine has 2 endshield bearings. The feet are raised. The shaftend is cylindrical.
FOUNDATION
The machine can be mounted using shimming, machined blocks, chock fast or on grouted soleplates or bed plate. Before using other mountings, contact us.
COOLING
The machine has a shaft mounted fan inside. The surrounding air is used for cooling. Thecooling air is drawn in through air filters (self charging electrostatic panels) and blown out tothe surrounding environment.
CONTROL SYSTEMS
A three phase transformer supplies the excitation power to the field winding of the shaft driventhree phase exciter under the control of the digital automatic voltage regulator (AVR) type ABBUNITROL UN1020. A three phase voltage feedback is supplied by the voltage transformer. Acurrent feedback is provided by the current transformer. The transformers are installed in thegenerator.
Thanks to a permanent magnet pole in the exciter no external power source is required forinitial excitation at start-up. The permanent magnet pole is already magnetized by thegenerator manufacturer. Should the re-magnetization of the permanent magnet be necessary,rated values for re-magnetization given on the main connection diagram of the generator are
Status: Approved Internal Document id: DBAC857966 - Page 8 (14)
Document identification Lang. Rev. ind. Sheet
ABB Oy / Motors and Generators 3AFP 54306401 en A 6TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;SAVEDATE: 12/19/2013 5:46:00 PM
used. Thanks to Soft Start function it is possible to avoid over shooting at start-up.
Excitation power at short circuit is supplied by the CTs through rectifier. At nominal voltage thecontactor is shorting the output of CTs (and preventing over excitation from these CTs). At aline short circuit AVR will notice the voltage drop and connect CTs to give full short circuitexcitation. ECL-10 current limiter limits sustained short circuit current approx. 250 - 300 % ofrated current.
The circuit breaker protects the field circuit and the AVR against thermal overload and shortcircuit. The over voltage relay will trip the circuit breaker in excess of pre-set limit of overvoltage and thus interrupt the supply of the excitation power to the AVR.
Auxiliary supply can be 9 to 300 Vac (3-phase), 16 to 300 Vac (1-phase) or 18 to 300 Vdc.
UNITROL 1020 AVR can be operated using digital and analogue I/O signals, from local panelor with CMT1000 PC software. CMT1000 is a commissioning and maintenance tool runningunder Microsoft Windows. With CMT1000 the tuning of the AVR can be done easily, also byusing preset parameter files. The operation of a synchronous machine can be monitored andcontrolled by an on-line power chart, four channel oscilloscope and by several measurementsand status indications with trending and memory functions. Measured data and parameterscan be saved to a file for future use and analysis.
UNITROL 1020 single channel AVR plate (dimensions: 334x570mm) includes:- UNITROL UN1020 AVR- Excitation breaker (ac) and MCB for Upwr supply- Over voltage relay (stator over voltage protection)- Boost circuit with ECL-10 current limiter- Standard software functions as per UNITROL UN1020 brochure, including
- AVR/FCR/PF/VAR- Limiters- Modbus TCP
- Rotating diode monitoring- Voltage matching prior to synchronizing- VDC mode- Synchronization- Event logger- Data logger- Real time clock- PSS (option)
- Interface for I/O signals:Inputs
- Excitation On/Off- Gen CB status- Setpoint Increase- Setpoint Decrease- PF mode enable- VDC (reactive load sharing by digital RS-485 bus)- PWG status- Remote SP enable (for analogue for PF setpoint)- 4..20 mA analogue input for PF setpoint- Line charging- Secondary Net 1- Secondary Net 2
Outputs
Status: Approved Internal Document id: DBAC857966 - Page 9 (14)
Document identification Lang. Rev. ind. Sheet
ABB Oy / Motors and Generators 3AFP 54306401 en A 7TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;SAVEDATE: 12/19/2013 5:46:00 PM
- Synchronize- FRT output
- Diode trip- Close CB command output- Over voltage
- Excitation On/Off Status- Free programmable
- CMT 1000 Commissioning and maintenance tool- PID setting calculation tool
TESTING
Testing is according to Wärtsilä Generator testing instruction 4V64L0037, IEC and ABBinternal requirements. Test items are listed below. The test may be observed by the customerwithout extra charges. The test procedures are described in Machine Description Document8006327, available upon request. Other tests to be agreed separately.
ROUTINE TESTS
1. Visual inspection *2. Air gap measurement and bearing clearance *3. Insulation resistance measurement *4. Resistance measurement of windings and elements *5. Direction of rotation6. First running: checking of bearings *7. No-load curve, U1= f(Im), n = nN8. Short-circuit curve, I1= f(Im), n = nN9. Tests with voltage regulator - adjusting of basic settings - initial voltage build-up and voltage regulation speed at no-load - setting of under frequency limit and function testing - measuring of sustained short-circuit current - measuring of remanence voltage10. Overspeed test, t = 2 min, n = 1.2 * nN11. Vibration measurement at no-load, U1 = U1N, n = nN12. High voltage test:
stator winding rotor winding field winding space heaters Pt-100 (stator) Pt-100 (others)
13. Insulation resistance measurement - polarization index 10/1 min for stator windings
* Tests to be completed before witness tests(Performing order of the tests may differ from the listed above.)
Status: Approved Internal Document id: DBAC857966 - Page 10 (14)
Document identification Lang. Rev. ind. Sheet
ABB Oy / Motors and Generators 3AFP 54306401 en A 8TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;SAVEDATE: 12/19/2013 5:46:00 PM
SURFACE TREATMENT
Colour: RAL 5019 Grade: C3, Special color
Surface treatment C3 according to the ISO 12944 standard, for standard industrialenvironment.
DOCUMENTATION
User's Manual in electronic format. Documentation language is English.
Status: Approved Internal Document id: DBAC857966 - Page 11 (14)
Document identification Lang. Rev. ind. Sheet
ABB Oy / Motors and Generators 3AFP 54306401 en A 9TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;SAVEDATE: 12/19/2013 5:46:00 PM
3 ACCESSORIES
No pc/pcs Item
6 PT100 for stator winding - PYR PT100LG10/3
1 PT100 for cold cooling air - PYR PT100RC0/4L=50 mm
1 PT100 for warm cooling air - PYR PT100RC0/4L=50 mm
2 PT100 for sleeve bearings (radial bearing surface) - PYR PT100A_7/4ZResistance temperature detector for sleeve bearings, insulated, quick connector
1 Varistor - SXV 40K550 C
3 Diode - LNM 260A/2000VABB Stock code: 9877911
1 Automatic Voltage Regulator system - UN 1020 WARTSILA 1CH SYSTEM (FULL)Unitrol 1020 -Wärtsilä system, Product code 3BHE036163R6106
1 1PT - Voltage transformer for exc.power & actual value meas. - KSG 3PU180/63/E6600/110/110 V, 60 HzSecondary 1: 110 V 3200VA for excitationSecondary 2: 110 V 300VA for actual value measurement
3 3CT - Current transformer for short circuit exc.power - KSG KOKM 1EF 10001000/7.5 A, class PX, 60 Hz
1 2CT - Current transformer for actual value measurement - KSG 1000T21000/1A, 5 VA, CL 0.5, 60 Hz
3 4CT - Current transformer for differential protection - KSG D 500/1000 1/1KOFA 1000/1/1 A, 60 HzCore 1: 20VA, 5P10Core 2: 20VA, 5P10
1 Top mounted direct air cooling unit incl. air filter
6 Inlet Air Filters - WJFA 500x1000x24Pliotron CR, Galvanized Steel, 500*1000
2 Anticondensation heater - RER 1-800W/490VVoltage 380-480 V, power 2x500-800 W
1 Auxiliary terminal box B3A - B3A StandStandard auxiliary terminal box for accessories. In stock.
1 Multidiameter cable entry seals (Rox System) for main cables - NLR...
Status: Approved Internal Document id: DBAC857966 - Page 12 (14)
Document identification Lang. Rev. ind. Sheet
ABB Oy / Motors and Generators 3AFP 54306401 en A 10TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;SAVEDATE: 12/19/2013 5:46:00 PM
1 Drive-end sleeve bearing - ZLL EFZLB28-250ASide flange mounted sleeve bearing for AMG/Z 1120 in land application. D-end.Normal end float +/- 2.5 mm or +/- 1/8 inch. Max. axial force 2 kN.Machine seal on machine side IP44. Floating labyrinth seal on outer side IP44.
1 Non-drive-end sleeve bearing - ZLL EFZLQ28-250EPSide flange mounted sleeve bearingInsulation between bearing housing and shell
1 Welding inspection record for the frame
Status: Approved Internal Document id: DBAC857966 - Page 13 (14)
Document identification Lang. Rev. ind. Sheet
ABB Oy / Motors and Generators 3AFP 54306401 en A 11TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;SAVEDATE: 12/19/2013 5:46:00 PM
4 P/Q DIAGRAM
ABB Oy Motors and Generators
Handled by: HEKR 19.12.2013
Type: AMG 1120LS10 DSESn: 10549 kVA cos: 0.80 Tn: 139910 NmUn: 6600 V n: 720 rpm In: 922,8 Af: 60 Hz
-15000 -10000 -5000 0 5000 10000 15000 kVAr
0
2500
5000
7500
10000
12500
15000
17500
20000
22500kW
P / Q -DIAGRAM
1. Stator current at rated load 2. Nominal working point 3. Active power limit 4. Rated rotor current
5. Minimum excitation limit 6. Stability limit 7. Theoretical stability limit
0,40,4
0,60,6
0,80,8
0,90,9 0,950,95
0,25
0,5
0,75
1,2
0,1
1,0
1
2 3
4
5
67
Status: Approved Internal Document id: DBAC857966 - Page 14 (14)
Document identification Lang. Rev. ind. Sheet
ABB Oy / Motors and Generators 3AFP 54306401 en A 12TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;SAVEDATE: 12/19/2013 5:46:00 PM
5 NO LOAD AND SHORT-CIRCUIT CURVE
ABB Oy Motors and Generators
Handled by: HEKR 19.12.2013
Type: AMG 1120LS10 DSE
Sn: 10549 kVA cos: 0.80 Tn: 139910 NmUn: 6600 V n: 720 rpm In: 922,8 Af: 60 Hz
0 50 100 150 200 250 A
0 0
0,2 0,4
0,4 0,8
0,6 1,2
0,8 1,6
1 2
1,2 2,4
1,4 2,8E/Un I/In
Excitation current (A)
1 2
3
1 Air-gap line
2 No load voltage
3 Short-circuit current
CÁLCULOS ELÉCTRICOS Rev. C
ANEXO V
RFE-1-YE__-ECE-IDO-001 Pág/Page 1 de/of 6
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
ANEXO V:
DATOS TRANSFORMADOR AUXILIAR
(DATOS DE LA OFERTA SIEMENS)
Nº CHARACTERISTICS REQUESTED UNIT MANUFACTURER
DATA
1
2 No. OF UNITS 1 Uds. 13 EQUIPMENT IDENTIFICATION 1BBT10 -
4 MODEL - cKOUM 5 TYPE OF PROTECTION INTEMPERIE - INTEMPERIE6 DESIGN NORM IEC 60076 - IEC 600767 FREQUENCY 60 Hz 608 No. OF PHASES 3 Uds. 39 No. OF WINDINGS 2 Uds. 2
10 SHORT-CIRCUIT CURRENT According to IEC11 IN PRIMARY, HV
12
EFFICIENT, SYMMETRIC, MAXIMUM SHORT-CIRCUIT
CURRENT150 kA *
13
EFFICIENT, SYMMETRIC SHORT-CIRCUIT CURRENT
RESISTED BY THE TRANSFORMER FOR 2 seconds
kA *
14 PEAK CURRENT RESISTED BY THE TRANSFORMER kA *15 IN SECONDARY, LV *
16
EFFICIENT, SYMMETRIC, MAXIMUM SHORT-CIRCUIT
CURRENT31,5 kA *
17
EFFICIENT, SYMMETRIC SHORT-CIRCUIT CURRENT
RESISTED BY THE TRANSFORMER FOR 2 seconds
kA *
18 PEAK CURRENT RESISTED BY THE TRANSFORMER kA *19
20
POTENCIAS ASIGNADAS EN SERV. CONTINUO, SIN
SOBREPASAR LOS CALENTAMIENTOS MÁXIMOS ADMISIBLES A
LA TEMPERATURA DE DISEÑO (40°C)
8,5/11,5
ONAN/ONAF
MVA 8,5/11,5
ONAN/ONAF
21
MAXIMUM TEMPERATURE INCREMENT VALUES (HEATING)
OVER AIR TEMPERATURE, AS SPECIFIED FOR ASSIGNED
POWER IN IEC 60076-2:
22 IN COPPER (MEASURED WITH RESISTANCE VARIATION) 65 K 65
23
IN OIL (MEASURED BY MEANS OF A THERMOMETER ON
THE UPPER OIL LAYER)60 K 60
24
ALLOWED OVERVOLTAGE OVER SET OVERVOLTAGE, FOR 5
seconds140 % Un According to IEC
25 SET NO-LOAD VOLTAGE:
26 HV WINDING 18 ± 2x2,5% kV 18 ± 2x2,5%27 LV WINDING 6,6 kV 6,628 SET CURRENTS:
29 HV WINDING:
30 RATED INP A
31 IOP VACUUM A *
32
ICP CONNECTION (MAXIMUM INRUSH CONNECTION
CURRENT)
A *
33 LV WINDING:
34 RATED INP A
35 IOP VACUUM A *
36
ICP CONNECTION (MAXIMUM INRUSH CONNECTION
CURRENT)
A *
37 CONNECTION GROUP (PRIMARY/SECONDARY) Dyn11 - Dyn11
38
MAXIMUM CAPACITY FOR AIR TEMPERATURE OVERLOAD:
40ºC; RATED VOLTAGE, 100% INITIAL LOAD AND NO
NOTICEABLE LIFE REDUCTION:
39 CONTINUOUS %PN According to IEC
40 FOR 4 HOURS %PN According to IEC
41 FOR 2 HOURS %PN According to IEC
42 FOR 1 HOUR %PN According to IEC
43 CORE CHARACTERISTICS:
44 TYPE OF PLATE M4 o similar
45
OVERREPRESENTATION IN THE LP WINDING, AS
SPECIFIED IN CEI 60076-1:According to IEC
46 FULL ENDURANCE LOAD %VN/FN
47 ENDURANCE NO-LOAD %VN/FN
48 NO-LOAD FOR 2 min %VN/FN
49 NO-LOAD FOR 2 seconds %VN/FN
50 MAXIMUM INDUCTION:
51 RATED VOLTAGE TESLAS 1,752 105% OF RATED VOLTAGE TESLAS 1,7853 110% OF RATED VOLTAGE TESLAS 1,8754 115% OF RATED VOLTAGE TESLAS 2,1555 TAP CHANGER
56 TYPE EN VACÍO - EN VACIO57 REGULATION MARGIN 18 ± 2x2,5% kV 18 ± 2x2,5%58 TAP VOLTAGE:
59 UPPER 105 %UN 105
60 LOWER 95 %UN 95
61 STEP VALUE 2,5 %UN 2,5
62 NUMBER OF TAPS 5 Uds. 563 NO-LOAD VOLTAGES:
64 IN UPPER POSITION kV 18,965 IN INTERMEDIATE POSITION kV 1866 IN LOWER POSITION kV 17,167 SET CURRENTS IN CONTINOUS OPERATION:
68 IN UPPER POSITION A 259,6569 IN INTERMEDIATE POSITION A 272,6470 IN LOWER POSITION A 286,98 REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
GENERAL
ON IPBs
TRANSFORMER CHARACTERISTICS
ESTIMATED VALUE
OBSERVATIONS
NLI H1
Página 1 de 5
Nº CHARACTERISTICS REQUESTED UNIT MANUFACTURER
DATA
OBSERVATIONS
NLI H1
71 SHORTCIRCUIT VOLTAGE -72 SHORTCIRCUIT VOLTAGE
73 IN UPPER POSITION %UN *
74 IN INTERMEDIATE POSITION 10 %UN 10
75 IN LOWER POSITION %UN *
76 UNIPOLAR SHORT-CIRCUIT VOLTAGE
77 IN UPPER POSITION %UN *
78 IN INTERMEDIATE POSITION %UN *
79 IN LOWER POSITION %UN *
80 RESISTIVE SHORT-CIRCUIT VOLTAGE:
81 IN UPPER POSITION %UN *
82 IN INTERMEDIATE POSITION %UN *
83 IN LOWER POSITION %UN *
84 REACTIVE SHORT-CIRCUIT VOLTAGE
85 IN UPPER POSITION %UN *
86 IN INTERMEDIATE POSITION %UN *
87 IN LOWER POSITION %UN *
88 SHORT-CIRCUIT IMPEDANCE (HV):
89 PRIMARIO TOMA SUPERIOR Ω *90 PRIMARIO TOMA CENTRAL Ω *91 PRIMARIO TOMA INFERIOR Ω *92 SECUNDARIO Ω *93 LOSSES:
94 IN NO-LOAD CONDITION:
95 90% UNkW 7,2
96 100% UNkW 9,5
97 105% UNkW 11
98 110% UNkW 13
99 115% UNkW 15
100 IN LOAD CONDITIONS:
101 25% Sn kW 2,9102 50% Sn kW 15103 75% Sn kW 29,6104 100 Sn kW 50105 CAUSED BY COOLING kW 1,2106 TOTAL LOSSES:
107 80 % Sn kW 42,5108 100% Sn kW 59,5
109
RELATION BETWEEN SCATTERING LOSSES AND TOTAL
LOSSES
p.u.
110 PERFORMANCE COS φ = 0,85:
111 25% PN% 99,3
112 50% PN% 99,39
113 75% PN% 99,31
114 100% PN% 99,18
115 WINDINGS
116 HV PRIMARY WINDING:117 HIGHEST VOLTAGE FOR THE MATERIAL 24 kV 24118 WITHSTOOD VOLTAGE AT INDUSTRIAL FREQUENCY 50 kV 50
119
WITHSTOOD VOLTAGE AT LIGHTING TYPE IMPULSE
(BIL)125 kV 125
120
TEST VOLTAGE WITH CHOPPED SHOCK WAVE /
TEST VOLTAGE FOR SWITCHING IMPULSE
kV *
121
TEST VOLTAGE AT INDUCED VOLTAGE (LONG
DURATION)
kV *
122 ACTIVE PART MATERIAL COBRE COBRE123 ELECTRODINAMIC RIGIDITY kA *124 CURRENT DENSITY
A/mm2 3,2
125 LV NEUTRAL:126 HIGHEST VOLTAGE FOR THE MATERIAL 7,2 kV 7,2127 WITHSTOOD VOLTAGE AT INDUSTRIAL FREQUENCY 20 kV 20
128
WITHSTOOD VOLTAGE AT LIGHTING TYPE IMPULSE
(BIL)60 kV 60
129 ARROLLAMIENTO SECUNDARIO B.T.:
130 HIGHEST VOLTAGE FOR THE MATERIAL 7,2 kV 7,2
131 WITHSTOOD VOLTAGE AT INDUSTRIAL FREQUENCY 20 kV 20
132
WITHSTOOD VOLTAGE AT LIGHTING TYPE IMPULSE
(BIL)60 kV 60
133 ACTIVE PART MATERIAL COBRE COBRE134 ELECTRODINAMIC RIGIDITY kA *135 CURRENT DENSITY
A/mm2 3,2
136 BUSHING INSULATORS
137 HV PRIMARY WINDING:138 MANUFACTURER - CEDASPE o Similar
139
TYPE OF CONNECTION BARRAS DE FASE
AISLADA
- CUMPLE
140 RATED CURRENT A 1000141 HIGHEST VOLTAGE FOR THE MATERIAL 24 kV 24
142
TEST VOLTAGE AT INDUSTRIAL FREQUENCY IN DRY
ENVIRONMENT / 1 min50 kV 50
143
TEST VOLTAGE AT INDUSTRIAL FREQUENCY IN
RAINY ENVIRONMENT / 1 min
kV *
144 TEST VOLTAGE AT LIGHTING TYPE IMPULSE (BIL) 125 kV 125145 CONTAMINATION LEVEL S/IEC 60815 IV (muy alto) - CUMPLE Desert area
146 LINEA DE FUGA EN EXTERIOR 31 mm/kV 31
147 TEST VOLTAGE AT SWITCHING IMPULSE kV N/A
44 mm/kV According to IEEE C57.19
REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
Página 2 de 5
Nº CHARACTERISTICS REQUESTED UNIT MANUFACTURER
DATA
OBSERVATIONS
NLI H1
148 TYPE OF INSULATION kV 52149 TYPE OF BUSHING - SECO150 CONDENSIVE TAP - N/A151 PORCELAIN COLOR - CAFÉ
152 LV NEUTRAL:
153 MANUFACTURER - CEDASPE o Similar
154
TYPE OF CONNECTION CABLE DE
COBRE AISLADO
- CUMPLE
155 RATED CURRENT A 2000
156
HIGHEST VOLTAGE FOR THE MATERIAL 7,2 kV 7,2
157
TEST VOLTAGE AT INDUSTRIAL FREQUENCY IN DRY
ENVIRONMENT / 1 min20 kV 20
158
TEST VOLTAGE AT INDUSTRIAL FREQUENCY IN
RAINY ENVIRONMENT / 1 min
kV
159 TEST VOLTAGE AT LIGHTING TYPE IMPULSE (BIL) 60 kV 60160 LÍNEA DE FUGA A TENSIÓN SIMPLE mm/KV 31161 TENSIÓN DE ENSAYO A IMPULSO TIPO MANIOBRA kV N/A162 TIPO DE AISLAMIENTO kV 30163 TIPO DE BORNA - SECO164 COLOR DE LA PORCELANA - CAFÉ165 LV SECONDARY WINDING:166 MANUFACTURER - CEDASPE o Similar167 TYPE OF CONNECTION CABLE DE - CUMPLE168 RATED CURRENT A 2000
169
HIGHEST VOLTAGE FOR THE MATERIAL 7,2 kV 7,2
170
TEST VOLTAGE AT INDUSTRIAL FREQUENCY IN DRY
ENVIRONMENT / 1 min20 kV 20
171
TEST VOLTAGE AT INDUSTRIAL FREQUENCY IN
RAINY ENVIRONMENT / 1 min
kV
172 TEST VOLTAGE AT LIGHTING TYPE IMPULSE (BIL) 60 kV 60173 LÍNEA DE FUGA A TENSIÓN COMPUESTA mm/kV 31174 TEST VOLTAGE AT SWITCHING IMPULSE kV N/A175 TYPE OF INSULATION - 30176 TYPE OF BUSHING - SECO177 CONDENSIVE TAP - N/A178 RADIOINTERFERENCE LEVEL µV *
179
NOISE LEVEL (ACOUSTIC PRESSURE AT 1 m, RATED POWER
AND THE COOLING SYSTEM OPERATING FULLY)≤ 85 dB(A) CUMPLE
180 GROUNDING CAPACITY OF MEDIUM TAP:
181 PRIMARY µF *182 SECONDARY µF *183 TYPE OF COOLING ONAN/ONAF - ONAN/ONAF184 FORCED COOLING EQUIPMENT
185 NUMBER OF STAGES 1 Uds. 1186 NUMBER OF RADIATORS Uds. *187 NUMBER OF FANS PER STAGE Uds. *188 POWER OF EACH FAN kW *189 FAN VOLTAGE / Hz 480 V / 60 Hz V/Hz 480 V / 60 Hz 190 TYPE OF OIL - Mineral191 TOTAL AMOUNT OF OIL l
192 MAXIMUM OIL SPEED cm/seg *193 LEVEL OF FAN PROTECTION IP
194 CAGE:
195 MAIN CAGE SI - SI196 MAXIMUM PRESSURE kPa *197 MINIMUM PRESSURE kPa *198 EXPANSION TANK SI SI
199
CHAMBER 1 WITH RUBBER BALL FOR
ENVIRONMENTAL INSULATION
- SI
200
CHAMBER 2 WITH THE SAME FEATURES FOR
THE REGULATOR
- N/A
201
202 DIMMENSIONS:
203 TOTAL LENGTH mm 4100204 HEIGHT WITH NO BUSHINGS mm 2100205 HEIGHT WITH BUSHINGS mm N/A206 HEIGHT WITH EXPANSION TANK mm 3700207 HEIGHT WITH AUTOMATIC VALVES IN HT mm 2500208 WIDTH mm 3550209 LENGTH FOR TRANSPORT mm 4100210 HEIGHT FOR TRANSPORT mm 2500211 WIDTH FOR TRANSPORT mm 2000212 WIDTH OF RAILWAY TRACKS mm *213 TYPE OF RAILWAY TRACKS kg/m *214 WEIGHTS:
215 TOTAL kg 19900216 OF TRANSFORMER (NO OIL) kg 14700217 OF OIL kg 5200218 OUTSIDE THE CAGE kg *219 OF COPPER kg 2450220 OF MAGNETIC PLATE (CORE) kg 5900221 OF THE HEAVIEST PIECE TO TRANSPORT kg 16700222
223 PROTECTION IP65 - CUMPLE224 MATERIAL - COLD ROLLED225 LOCAL INDICATORS - *226 INDICATING LAMPS - *227 TEST LAMPS - *228 SWITCHES AND BUTTONS - *
CONTROL AND OPERATION CABINET
Without EXPANSION TANK
Bushing in side
PHYSICAL CHARACTERISTICS
Página 3 de 5
Nº CHARACTERISTICS REQUESTED UNIT MANUFACTURER
DATA
OBSERVATIONS
NLI H1
229 POWER BUS SUPPLY - *
230 FIRING RESISTANCE Sí 220 VAC - CUMPLE
231 LIGHTING AND ELECTRICAL SOCKETS Sí 220 VAC - CUMPLE
232 POTENTIAL-FREE ALARM CONTACTS SI - SI233 LIGHTING AND AUXILIARY POWER SUPPLY - *234 CONTROL AND THERMAL IMAGE POWER SUPPLY DEVICE - *235
236 TYPE - MINERAL237 MANUFACTURER - NYNAS238 5% RESERVE TANK SI - SI239
240 HV BUSHINGS: PRIMEROS241 AMOUNT PER PHASE 1 Uds. 1242 P CURRENT 2000 A 2000243 S1 CURRENT 5 A 5244 S1 POWER 100 VA 20245 S1 ACCURACY 5P20 - 5P20246 S2 CURRENT 5 A N/A247 S2 POWER 100 VA N/A248 S2 ACCURACY 5P20 - N/A249 THERMAL CURRENT LIMIT kA *250 DYNAMIC CURRENT LIMIT (PEAK) kA *251 MANUFACTURER - SIEMENS252 MODEL -
253
SAFETY FACTOR (FOR INSTRUMENT
TRANSFORMERS)
-
254 HV TERMINALS SEGUNDOS255 AMOUNT PER PHASE 1 Uds. 1256 P CURRENT 1000 A 1000257 S1 CURRENT 5 A N/A258 S1 POWER 100 VA N/A259 S1 ACCURACY 5P20 - N/A260 S2 CURRENT 5 A 5261 S2 POWER 25 VA 20262 S2 ACCURACY CL 0,2 - CL 0,2263 THERMAL CURRENT LIMIT kA *264 DYNAMIC CURRENT LIMIT kA *265 MANUFACTURER - SIEMENS266 MODEL -
267
SAFETY FACTOR (FOR INSTRUMENT
TRANSFORMERS)
-
268 NEUTRAL TERMINAL
269 QUANTITY 1 Uds. 1270 P CURRENT 30 A 300271 S1 CURRENT 5 A 5272 S1 POWER 50 VA 20273 S1 ACCURACY 5P20 - 5P20274 S2 CURRENT A N/A275 S2 POWER A N/A276 S2 ACCURACY - N/A277 THERMAL CURRENT LIMIT kA *278 DYNAMIC CURRENT LIMIT kA *279 FABRICANTE - SIEMENS280 MANUFACTURER - SIEMENS281 MODEL -
282 LV TERMINALS
283 AMOUNT PER PHASE 1 Uds. 2284 P CURRENT 1500 A 1500285 S1 CURRENT 5 A 5286 S1 POWER 50 VA 20287 S1 ACCURACY 5P20 - 5P20288 S2 CURRENT 5 A 5289 S2 POWER 50 VA 20290 S2 ACCURACY CL 0,2 - CL 0,2291 THERMAL CURRENT LIMIT kA *292 DYNAMIC CURRENT LIMIT kA *293 FABRICANTE - SIEMENS294 MANUFACTURER - SIEMENS
295
SAFETY FACTOR (FOR INSTRUMENT
TRANSFORMERS)
-
(NOTE: INCLUDE CURRENT TRANSFORMER FOR THERMAL IMAGE). INCLUDE TC FOR
THERMAL IMAGE
296
297 MAIN CAGE:
298 WHEELS ORIENTABLES 90º SI - SI299 CÁNCAMOS DE ELEVACIÓN EN CUBA Y TAPAS SI - SI300 APOYOS PARA GATOS HIDRÁULICOS SI - SI
301
CONEXIONES FLEXIBLES ENTRE LA CUBA Y
LA TAPA
SI - SI
302 VÁLVULA DE VACIADO SI - SI303 VÁLVULA DE TOMA DE MUESTRAS SI - SI304 DEPÓSITO DE EXPANSIÓN SI - SI
305 DESECADOR DE SILICAGEL SI - SI
306 TERMINALES PARA CONEXIÓN DE P.A.T. minimo 2 - CUMPLE307 PLACA DE CARACTERÍSTICAS INOX SI - SI308 VÁLVULA CONEXIÓN DE FILTRO SI - SI
309
CAJA CUBREBORNAS PARA CONEXIÓN DE
CABLES/BARRAS, EQUIPADA CON
RESISTENCIA DE CALDEO Y TERMOSTATO
SI - SI
310 PROTECCIONES Y ALARMAS
ACCESSORIES
OPPOSITE SIDES
BOTH SIDES (HV Y LV)
OPTIONAL
2 TC PER PHASE, ONE FOR MEASURE Y ONE
FOR PROTECTION
OPTIONAL
PENDING
1 TC PER PHASE FOR MEASURE
BUSHING CURRENT TRANSFORMERSPENDING
1 TC PER PHASE FOR PROTECTION
OIL
Página 4 de 5
Nº CHARACTERISTICS REQUESTED UNIT MANUFACTURER
DATA
OBSERVATIONS
NLI H1
311 RELÉ BUCHHOLZ (ALARMA, 2xDISPARO) SI SI312 INDICADOR DE NIVEL (ALARMA ALTA Y BAJA) SI - SI
313
TERMÓMETRO TEMPERATURA ACEITE
(ALARMA, 2xDISPARO)
SI - SI
314
DETECCIÓN DE AUMENTO DE PRESION
(DISPARO)
SI - SI
315 IMAGEN TÉRMICA (ALARMA, 2xDISPARO) SI - SI
* Dates according to final design and IEC Standard
Página 5 de 5
CÁLCULOS ELÉCTRICOS Rev. C
ANEXO VI
RFE-1-YE__-ECE-IDO-001 Pág/Page 1 de/of 17
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
ANEXO VI:
REPORTES DEL ANÁLISIS DE FLUJO DE CARGAS
One-Line Diagram - OLV1 (Load Flow Analysis)
page 1 10:05:48 may 02, 2014 Project File: Eten
RESERVA FRÍA ETEN
ESTUDIO DE FLUJO DE CARGAS: CASO LF-1 (REV C)
CONDICIONES:-> TENSIÓN DE RED: 220 kV-> GENERADOR PRINCIPAL OPERANDO A PLENA CARGA Y FP=0,8 IND-> GENERADOR AUXILIAR OPERANDO A PLENA CARGA Y FP=0,8 IND-> GENERADOR EMERGENCIA PARADO-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIÓN EN AUTO.-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIÓN EN TOMA CENTRAL.-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN ÚNICO TRAFO MT/BT.
1BFA51
0,48 kV104
,67%
1BBA51
6,6 kV106
,91%
1BFA53
0,48 kV 104,67
% 1BMA52
0,48 kV 104,67
%
1BNB52
0,38 kV108
,21%
CGDE
0,48 kV
1BBA76
6,6 kV 107,02
%
1BJA76
0,48 kV108
,07%
BUS GEN
18 kV
99,95%
S.E. Etén
220 kV 100,46
%
S.E. Reque
220 kV 100%
Sistema PCI
200 kW
173 kW
107 kvar
Red eléctrica Peruana
3022 MVAsc
226624 kW
130683 kvar
Narcissus
AL 2,92 km
0,5 %Vd
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
227721 kW
170959 kvar
1MKA10
225 MW
Isolated Phase CU
35 m
Isolated Phase CU
35 m
223600 kW
167700 kvar
4117 kW
3259 kvar
Isolated Phase CU
8 m
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
4-3/C 240
CU 40 m
0,0 %Vd
1MKA76
8,44 MW
8440 kW
6330 kvar
3-3/C 300
CU 20 m
0,0 %Vd
CARGAS 1BJA76
270 kVA
184 kW
114 kvar
184 kW
114 kvar
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1-3/C 300
CU 20 m
0,0 %Vd
3-3/C 300
CU 120 m
0,1 %Vd
Excitación 1MKC10
944 kVA
815 kW
395 kvar
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1-3/C 150
CU 40 m
0,0 %Vd
LCI 1BPA10_1
2725 kVA
LCI 1BPA10_2
2725 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
3-3/C 240
CU 40 m
Open
88WN-1
224 kW
133 kW
57 kvar
1-3/C 70
CU 50 m
0,0 %Vd
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
0,0 %Vd
88WN-2
224 kW
1-3/C 70
CU 50 m
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
Open
88AK-1
375 kW
342 kW
145 kvar
1-3/C 70
CU 50 m
0,0 %Vd
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
0,0 %Vd
88AK-2
375 kW
1-3/C 70
CU 50 m
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
Open
W-1BMB20
1XKA52
2000 kW
6-3/C 300
CU 50 m
CARGAS 1BNB52
82,2 kVA
68 kW
33 kvar
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
69 kW
34 kvar
W-1BMB52
MBN50 AH010
450 kVA
444 kW
0 kvar
1BJA80
400 kVA
310 kW
192 kvar
W-1BJA12
2749 kW
1575 kvar
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
2-3/C 185
CU 40 m
0,0 %Vd
2-3/C 185
CU 40 m
0,0 %Vd
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
Open
W-1BJA51W-1BJA11
2-3/C 240
CU 115 m
0,6 %Vd
Excitación 1MKC10
944 kVA
LCI 1BPA10_1
2725 kVA
MBN50 AH010
450 kVA
CARGAS 1BNB52
82,2 kVA
W-1BJA51W-1BMB20W-1BJA12W-1BJA11W-1BMB52
1BJA80
400 kVA
CARGAS 1BJA76
270 kVA
LCI 1BPA10_2
2725 kVA
Open
Red eléctrica Peruana
3022 MVAsc
1MKA10
225 MW
1MKA76
8,44 MW
1XKA52
2000 kW
Narcissus
AL 2,92 km
6-3/C 300
CU 50 m
3-3/C 300
CU 120 m
3-3/C 300
CU 20 m1-3/C 300
CU 20 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 100 m
1-3/C 70
CU 70 m
1-3/C 70
CU 70 m
2-3/C 185
CU 40 m
2-3/C 185
CU 40 m
1-3/C 150
CU 40 m
3-3/C 240
CU 40 m
4-3/C 240
CU 40 m
1-3/C 70
CU 100 m
1-3/C 70
CU 50 m
2-3/C 240
CU 115 m
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
1BBA51
6,6 kV
1BFA53
0,48 kV
1BFA51
0,48 kV
S.E. Etén
220 kV
BUS GEN
18 kV
1BMA52
0,48 kV
CGDE
0,48 kV 1BNB52
0,38 kV
S.E. Reque
220 kV
1BBA76
6,6 kV
1BJA76
0,48 kV
Sistema PCI
200 kW
88WN-1
224 kW
88AK-1
375 kW
88WN-2
224 kW
88AK-2
375 kW
8248 kW
6217 kvar
8440 kW
6324 kvar
185 kW
119 kvar
134 kW
59 kvar
0,49 kW
-1 kvar
2793 kW
1948 kvar
820 kW
428 kvar
4138 kW
3632 kvar
350 kW
157 kvar
174 kW
108 kvar
562 kW
397 kvar
409 kW
307 kvar
400 kW
298 kvar
252 kW
142 kvar
130 kW
97 kvar
226860 kW
132202 kvar
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1136 kW
802 kvar
1587 kW
1076 kvar
108,07
%
107,02
%
100%
108,21
%
104,67
%
99,95%
100,46
%
104,67
%104,67
%
106,91
%
Isolated Phase CU
35 m
Isolated Phase CU
35 m
Isolated Phase CU
8 m
4138 kW
3632 kvar
820 kW
428 kvar Open
1587 kW
1076 kvar
Open
227721 kW
170959 kvar
223600 kW
167700 kvar
815 kW
395 kvar
1136 kW
802 kvar
Open
252 kW
142 kvar
2749 kW
1575 kvar
134 kW
59 kvar Open
350 kW
157 kvarOpen
444 kW
0 kvar
400 kW
298 kvar
68 kW
33 kvar
226624 kW
130683 kvar
226860 kW
132202 kvar
4117 kW
3259 kvar
0,5 %Vd
310 kW
192 kvar
2793 kW
1948 kvar
0,49 kW
-1 kvar
409 kW
307 kvar
562 kW
397 kvar
174 kW
108 kvar
69 kW
34 kvar
130 kW
97 kvar
0,1 %Vd
133 kW
57 kvar
8440 kW
6324 kvar
185 kW
119 kvar
184 kW
114 kvar
184 kW
114 kvar
0,0 %Vd
8440 kW
6330 kvar
8248 kW
6217 kvar
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
342 kW
145 kvar
173 kW
107 kvar0,6 %Vd
One-Line Diagram - OLV1 (Load Flow Analysis)
page 2 10:05:48 may 02, 2014 Project File: Eten
1BJA11
0,48 kV 104,37
%1BJA12
0,48 kV 104,45
%
1BMB52
0,48 kV
104,56
%
1BJA51
0,48 kV 104,54
%
1BMB20
0,48 kV 104,49
%
CARGAS 1BMB20
235 kVA
170 kW
105 kvar
1MBV10AP001-M01
75 kW
82 kW
36 kvar
1BMA52
4-3/C 240
CU 50 m
0,2 %Vd
Compresor 1
37 kW
19 kW
11 kvar
CARGAS 1BJA51
650 kVA
381 kW
286 kvar
1BFA51
4-3/C 240
CU 20 m
0,1 %Vd
1BMA52
2-3/C 150
CU 20 m
0,1 %Vd
Compresor 2
37 kW
Open
CARGAS 1BMB52
231 kVA
130 kW
97 kvar
CARGAS 1BJA12
592 kVA
408 kW
306 kvar
6-3/C 240
CU 50 m
0,2 %Vd
1BFA53
CARGAS 1BJA11
695 kVA
479 kW
359 kvar
1MBV10AP002-M1
75 kW
82 kW
36 kvar
6-3/C 240
CU 50 m
0,3 %Vd
1BFA51
CARGAS 1BMB20
235 kVA
CARGAS 1BMB52
231 kVA
1BFA51
1BMA52 1BFA53 1BFA51
1BMA52
CARGAS 1BJA11
695 kVA
CARGAS 1BJA12
592 kVA
CARGAS 1BJA51
650 kVA
4-3/C 240
CU 50 m
6-3/C 240
CU 50 m
6-3/C 240
CU 50 m
4-3/C 240
CU 20 m
2-3/C 150
CU 20 m
1BMB52
0,48 kV1BJA51
0,48 kV
1BMB20
0,48 kV
1BJA12
0,48 kV
1BJA11
0,48 kV
Compresor 1
37 kW
Compresor 2
37 kW
1MBV10AP001-M01
75 kW
1MBV10AP002-M1
75 kW
104,49
%
104,54
%
104,56
%
Open
130 kW
97 kvar
170 kW
105 kvar
82 kW
36 kvar
0,2 %Vd
104,45
%
0,2 %Vd
104,37
%
0,3 %Vd
0,1 %Vd0,1 %Vd
19 kW
11 kvar
479 kW
359 kvar
408 kW
306 kvar
381 kW
286 kvar
82 kW
36 kvar
Ubicación:
Ingeniero:Caso de Estudio: LF-1
12.0.0C
Página: 1
SN: IDOMINGC-3
Archivo: Eten
Proyecto:ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
MW Mvar AmpID %PF
XFMR
%Tap
1BBA51 6.600 9.8 106.915 -0.015 0.006 1BBA76 -8.241 -6.209 844.2 79.90 0
Bus17 0.134 0.059 12.0 91.5
Bus18 0.000 0.001 0.1 -34.4
Bus19 2.793 1.948 278.6 82.0
Bus20 0.820 0.428 75.7 88.7
Bus22 4.138 3.632 450.5 75.2
Bus15 0.350 0.157 31.4 91.3
1BBA76 6.600 9.8 107.022 -0.012 0.008 1BBA51 8.248 6.217 844.2 79.90 0
Bus BS -8.440 -6.324 862.0 80.0
Bus9 0.185 0.119 18.0 84.2
1BFA51 0.480 4.8 104.673 PCI_BUS 0.174 0.108 235.6 84.90 0 0 0
1BJA11 0.562 0.397 790.6 81.7
1BJA51 0.400 0.298 572.7 80.2
1BMA52 -1.136 -0.802 1598.4 81.7
1BFA53 0.480 4.8 104.673 0.192 0.753 1BJA12 0.409 0.307 587.3 80.00 0
Bus19 -2.749 -1.575 3640.5 86.8
1BMA52 1.587 1.076 2203.0 82.8
1BJA11 0.480 4.7 104.372 0.395 0.561 1BFA51 -0.561 -0.395 790.6 81.70 0
1BJA12 0.480 4.7 104.449 0.306 0.408 1BFA53 -0.408 -0.306 587.3 80.00 0
1BJA51 0.480 4.7 104.542 0.297 0.399 1BFA51 -0.399 -0.297 572.7 80.20 0
1BJA76 0.480 9.4 108.074 0.114 0.184 Bus9 -0.184 -0.114 240.5 85.00 0
1BMA52 0.480 4.8 104.673 1BMB20 0.252 0.142 332.2 87.10 0 0 0
1BMB52 0.130 0.097 186.3 80.0
1BNB52 0.069 0.034 88.8 89.5
1BFA51 1.136 0.802 1598.4 81.7
1BFA53 -1.587 -1.076 2203.0 82.8
1BMB20 0.480 4.7 104.486 0.141 0.252 1BMA52 -0.252 -0.141 332.2 87.20 0
1BMB52 0.480 4.8 104.556 0.097 0.130 1BMA52 -0.130 -0.097 186.3 80.00 0
1BNB52 0.380 4.2 108.211 0.033 0.068 1BMA52 -0.068 -0.033 106.6 90.00 0
Bus5 4.000 9.4 109.856 0.057 0.133 Bus10 -0.133 -0.057 19.0 91.90 0
Bus7 4.000 8.7 107.675 0.145 0.342 Bus13 -0.342 -0.145 49.8 92.10 0
Bus9 6.600 9.8 107.021 0.002-0.001 1BBA76 -0.185 -0.119 18.0 84.20 0
2.5001BJA76 0.186 0.117 18.0 84.6
Bus10 4.160 9.4 105.645 Bus5 0.133 0.057 19.0 91.90 0 0 0
Bus17 -0.133 -0.057 19.0 91.9
Bus13 4.000 8.7 107.713 Bus7 0.342 0.145 49.8 92.10 0 0 0
Ubicación:
Ingeniero:Caso de Estudio: LF-1
12.0.0C
Página: 2
SN: IDOMINGC-3
Archivo: Eten
Proyecto:ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
MW Mvar AmpID %PF
XFMR
%Tap
Bus15 -0.342 -0.145 49.8 92.1
Bus15 6.600 9.8 106.886 1BBA51 -0.350 -0.157 31.4 91.30 0 0 0
Bus13 0.350 0.157 31.4 91.3
Bus17 6.600 9.8 106.907 1BBA51 -0.134 -0.059 12.0 91.50 0 0 0
Bus10 0.134 0.059 11.9 91.6
Bus18 6.600 9.8 106.915 0.001 0.000 1BBA51 0.000 -0.001 0.1 -34.40 0
Bus19 6.600 9.8 106.891 0.001 0.000 1BBA51 -2.793 -1.947 278.6 82.00 0
1BFA53 2.793 1.946 278.6 82.0
Bus20 6.600 9.8 106.900 1BBA51 -0.820 -0.428 75.7 88.70 0 0 0
Bus EX 0.820 0.427 75.7 88.7
Bus22 6.900 9.8 102.250 0.008-0.008 1BBA51 -4.138 -3.631 450.5 75.20 0
BUS GEN 4.145 3.623 450.5 75.3
Bus BS 6.600 9.8 107.040 6.330 8.440 0.005-0.001 1BBA76 8.441 6.325 862.0 80.0
Bus EX 0.480 8.1 98.113 0.395 0.815 Bus20 -0.815 -0.395 1110.1 90.00 0
BUS GEN 18.000 7.0 99.953 167.700 223.600 0.000-0.004 S.E. Etén 227.721 170.959 9137.7 80.0
2.500Bus22 -4.117 -3.259 168.5 78.4
PCI_BUS 0.480 4.7 104.060 0.107 0.173 1BFA51 -0.173 -0.107 235.6 85.00 0
S.E. Etén 220.000 0.4 100.462 S.E. Reque 226.860 132.202 685.9 86.40 0 0 0
9.000BUS GEN -226.860 -132.202 685.9 86.4
S.E. Reque* 220.000 0.0 100.000 -130.684-226.624 S.E. Etén -226.624 -130.684 686.5 86.60 0
*
# Indica una barra con un error de convergencia superior a 0,1 MVA
Indica una barra con tensión regulada (con máquinas de tensión controlada o máquinas de referencia conectadas)
One-Line Diagram - OLV1 (Load Flow Analysis)
page 1 10:07:42 may 02, 2014 Project File: Eten
RESERVA FRÍA ETEN
ESTUDIO DE FLUJO DE CARGAS: CASO LF-2 (REV C)
CONDICIONES:-> TENSIÓN DE RED: 220 kV-> GENERADOR PRINCIPAL OPERANDO A PLENA CARGA Y FP=0,95 CAP-> GENERADOR AUXILIAR OPERANDO A PLENA CARGA Y FP=0,95 CAP-> GENERADOR EMERGENCIA PARADO-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIÓN EN AUTO.-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIÓN EN TOMA CENTRAL.-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN ÚNICO TRAFO MT/BT.
1BFA51
0,48 kV91,
6%
1BBA51
6,6 kV94,
92%
1BFA53
0,48 kV 91,6%
1BMA52
0,48 kV 91,6%
1BNB52
0,38 kV94,
65%
CGDE
0,48 kV
1BBA76
6,6 kV 94,96%
1BJA76
0,48 kV95,
65%
BUS GEN
18 kV
100,34
%
S.E. Etén
220 kV 99,76%
S.E. Reque
220 kV 100%
Sistema PCI
200 kW
173 kW
107 kvar
Red eléctrica Peruana
3022 MVAsc
227322 kW
-108616 kvar
Narcissus
AL 2,92 km
0,2 %Vd
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
228156 kW
-79546 kvar
1MKA10
225 MW
Isolated Phase CU
35 m
Isolated Phase CU
35 m
223600 kW
-73494 kvar
4556 kW
-6053 kvar
Isolated Phase CU
8 m
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
4-3/C 240
CU 40 m
0,0 %Vd
1MKA76
8,44 MW
8440 kW
-2774 kvar
3-3/C 300
CU 20 m
0,0 %Vd
CARGAS 1BJA76
270 kVA
166 kW
103 kvar
166 kW
103 kvar
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1-3/C 300
CU 20 m
0,0 %Vd
3-3/C 300
CU 120 m
0,0 %Vd
Excitación 1MKC10
944 kVA
642 kW
311 kvar
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1-3/C 150
CU 40 m
0,0 %Vd
LCI 1BPA10_1
2725 kVA
LCI 1BPA10_2
2725 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
3-3/C 240
CU 40 m
Open
88WN-1
224 kW
133 kW
57 kvar
1-3/C 70
CU 50 m
0,0 %Vd
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
0,0 %Vd
88WN-2
224 kW
1-3/C 70
CU 50 m
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
Open
88AK-1
375 kW
342 kW
145 kvar
1-3/C 70
CU 50 m
0,0 %Vd
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
0,0 %Vd
88AK-2
375 kW
1-3/C 70
CU 50 m
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
Open
W-1BMB20
1XKA52
2000 kW
6-3/C 300
CU 50 m
CARGAS 1BNB52
82,2 kVA
54 kW
26 kvar
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
54 kW
27 kvar
W-1BMB52
MBN50 AH010
450 kVA
340 kW
0 kvar
1BJA80
400 kVA
254 kW
157 kvar
W-1BJA12
2469 kW
1455 kvar
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
2-3/C 185
CU 40 m
0,0 %Vd
2-3/C 185
CU 40 m
0,0 %Vd
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
Open
W-1BJA51W-1BJA11
2-3/C 240
CU 115 m
0,7 %Vd
Excitación 1MKC10
944 kVA
LCI 1BPA10_1
2725 kVA
MBN50 AH010
450 kVA
CARGAS 1BNB52
82,2 kVA
W-1BJA51W-1BMB20W-1BJA12W-1BJA11W-1BMB52
1BJA80
400 kVA
CARGAS 1BJA76
270 kVA
LCI 1BPA10_2
2725 kVA
Open
Red eléctrica Peruana
3022 MVAsc
1MKA10
225 MW
1MKA76
8,44 MW
1XKA52
2000 kW
Narcissus
AL 2,92 km
6-3/C 300
CU 50 m
3-3/C 300
CU 120 m
3-3/C 300
CU 20 m1-3/C 300
CU 20 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 100 m
1-3/C 70
CU 70 m
1-3/C 70
CU 70 m
2-3/C 185
CU 40 m
2-3/C 185
CU 40 m
1-3/C 150
CU 40 m
3-3/C 240
CU 40 m
4-3/C 240
CU 40 m
1-3/C 70
CU 100 m
1-3/C 70
CU 50 m
2-3/C 240
CU 115 m
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
1BBA51
6,6 kV
1BFA53
0,48 kV
1BFA51
0,48 kV
S.E. Etén
220 kV
BUS GEN
18 kV
1BMA52
0,48 kV
CGDE
0,48 kV 1BNB52
0,38 kV
S.E. Reque
220 kV
1BBA76
6,6 kV
1BJA76
0,48 kV
Sistema PCI
200 kW
88WN-1
224 kW
88AK-1
375 kW
88WN-2
224 kW
88AK-2
375 kW
8270 kW
-2882 kvar
8439 kW
-2775 kvar
169 kW
106 kvar
134 kW
59 kvar
0 kW
0 kvar
2517 kW
1852 kvar
647 kW
337 kvar
4615 kW
-5298 kvar
352 kW
160 kvar
175 kW
108 kvar
544 kW
383 kvar
394 kW
295 kvar
353 kW
263 kvar
241 kW
135 kvar
114 kW
85 kvar
227540 kW
-107236 kvar
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1072 kW
754 kvar
1482 kW
1002 kvar
95,65%
94,96%
100%
94,65%
91,6%
100,34
%
99,76%
91,6%91,
6%
94,92%
Isolated Phase CU
35 m
Isolated Phase CU
35 m
Isolated Phase CU
8 m
4615 kW
-5298 kvar
647 kW
337 kvar Open
1482 kW
1002 kvar
Open
228156 kW
-79546 kvar
223600 kW
-73494 kvar
642 kW
311 kvar
1072 kW
754 kvar
Open
241 kW
135 kvar
2469 kW
1455 kvar
134 kW
59 kvar Open
352 kW
160 kvarOpen
340 kW
0 kvar
353 kW
263 kvar
54 kW
26 kvar
227322 kW
-108616 kvar
227540 kW
-107236 kvar
4556 kW
-6053 kvar
0,2 %Vd
254 kW
157 kvar
2517 kW
1852 kvar
0 kW
0 kvar
394 kW
295 kvar
544 kW
383 kvar
175 kW
108 kvar
54 kW
27 kvar
114 kW
85 kvar
0,0 %Vd
133 kW
57 kvar
8439 kW
-2775 kvar
169 kW
106 kvar
166 kW
103 kvar
166 kW
103 kvar
0,0 %Vd
8440 kW
-2774 kvar
8270 kW
-2882 kvar
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
342 kW
145 kvar
173 kW
107 kvar0,7 %Vd
One-Line Diagram - OLV1 (Load Flow Analysis)
page 2 10:07:42 may 02, 2014 Project File: Eten
1BJA11
0,48 kV 91,27%
1BJA12
0,48 kV 91,35%
1BMB52
0,48 kV
91,48%
1BJA51
0,48 kV 91,47%
1BMB20
0,48 kV 91,4%
CARGAS 1BMB20
235 kVA
159 kW
99 kvar
1MBV10AP001-M01
75 kW
82 kW
36 kvar
1BMA52
4-3/C 240
CU 50 m
0,2 %Vd
Compresor 1
37 kW
19 kW
11 kvar
CARGAS 1BJA51
650 kVA
334 kW
251 kvar
1BFA51
4-3/C 240
CU 20 m
0,1 %Vd
1BMA52
2-3/C 150
CU 20 m
0,1 %Vd
Compresor 2
37 kW
Open
CARGAS 1BMB52
231 kVA
114 kW
85 kvar
CARGAS 1BJA12
592 kVA
393 kW
294 kvar
6-3/C 240
CU 50 m
0,2 %Vd
1BFA53
CARGAS 1BJA11
695 kVA
461 kW
346 kvar
1MBV10AP002-M1
75 kW
82 kW
36 kvar
6-3/C 240
CU 50 m
0,3 %Vd
1BFA51
CARGAS 1BMB20
235 kVA
CARGAS 1BMB52
231 kVA
1BFA51
1BMA52 1BFA53 1BFA51
1BMA52
CARGAS 1BJA11
695 kVA
CARGAS 1BJA12
592 kVA
CARGAS 1BJA51
650 kVA
4-3/C 240
CU 50 m
6-3/C 240
CU 50 m
6-3/C 240
CU 50 m
4-3/C 240
CU 20 m
2-3/C 150
CU 20 m
1BMB52
0,48 kV1BJA51
0,48 kV
1BMB20
0,48 kV
1BJA12
0,48 kV
1BJA11
0,48 kV
Compresor 1
37 kW
Compresor 2
37 kW
1MBV10AP001-M01
75 kW
1MBV10AP002-M1
75 kW
91,4%
91,47%
91,48%
Open
114 kW
85 kvar
159 kW
99 kvar
82 kW
36 kvar
0,2 %Vd
91,35%
0,2 %Vd
91,27%
0,3 %Vd
0,1 %Vd0,1 %Vd
19 kW
11 kvar
461 kW
346 kvar
393 kW
294 kvar
334 kW
251 kvar
82 kW
36 kvar
Ubicación:
Ingeniero:Caso de Estudio: LF-2
12.0.0C
Página: 1
SN: IDOMINGC-3
Archivo: Eten
Proyecto:ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
MW Mvar AmpID %PF
XFMR
%Tap
1BBA51 6.600 10.5 94.922 1BBA76 -8.264 2.890 806.8 -94.40 0 0 0
Bus17 0.134 0.059 13.5 91.5
Bus18 0.000 0.000 0.0 -50.1
Bus19 2.517 1.852 288.0 80.5
Bus20 0.647 0.337 67.2 88.7
Bus22 4.615 -5.298 647.5 -65.7
Bus15 0.352 0.160 35.7 91.0
1BBA76 6.600 10.6 94.955 1BBA51 8.270 -2.882 806.8 -94.40 0 0 0
Bus BS -8.439 2.775 818.4 -95.0
Bus9 0.169 0.106 18.4 84.5
1BFA51 0.480 4.7 91.601 PCI_BUS 0.175 0.108 269.8 84.90 0 0 0
1BJA11 0.544 0.383 874.3 81.8
1BJA51 0.353 0.263 578.0 80.3
1BMA52 -1.072 -0.754 1721.4 81.8
1BFA53 0.480 4.7 91.601 0.157 0.594 1BJA12 0.394 0.295 646.1 80.00 0
Bus19 -2.469 -1.455 3763.4 86.2
1BMA52 1.482 1.002 2349.0 82.8
1BJA11 0.480 4.6 91.268 0.382 0.543 1BFA51 -0.543 -0.382 874.3 81.80 0
1BJA12 0.480 4.6 91.354 0.294 0.393 1BFA53 -0.393 -0.294 646.1 80.00 0
1BJA51 0.480 4.7 91.468 0.262 0.353 1BFA51 -0.353 -0.262 578.0 80.30 0
1BJA76 0.480 10.1 95.647 0.103 0.166 Bus9 -0.166 -0.103 246.0 85.00 0
1BMA52 0.480 4.7 91.601 1BMB20 0.241 0.135 363.4 87.20 0 0 0
1BMB52 0.114 0.085 186.9 80.0
1BNB52 0.054 0.027 79.7 89.5
1BFA51 1.072 0.754 1721.4 81.8
1BFA53 -1.482 -1.002 2349.0 82.8
1BMB20 0.480 4.6 91.397 0.135 0.241 1BMA52 -0.241 -0.135 363.4 87.30 0
1BMB52 0.480 4.7 91.484 0.085 0.114 1BMA52 -0.114 -0.085 186.9 80.00 0
1BNB52 0.380 4.0 94.652 0.026 0.054 1BMA52 -0.054 -0.026 95.7 90.00 0
Bus5 4.000 9.9 97.209 0.057 0.133 Bus10 -0.133 -0.057 21.4 91.90 0
Bus7 4.000 9.0 94.714 0.145 0.342 Bus13 -0.342 -0.145 56.6 92.10 0
Bus9 6.600 10.6 94.954 1BBA76 -0.169 -0.106 18.4 84.50 0 0 0
2.5001BJA76 0.169 0.106 18.4 84.6
Bus10 4.160 9.9 93.486 Bus5 0.133 0.057 21.4 91.90 0 0 0
Bus17 -0.133 -0.057 21.4 91.9
Bus13 4.000 9.0 94.756 Bus7 0.342 0.145 56.6 92.10 0 0 0
Ubicación:
Ingeniero:Caso de Estudio: LF-2
12.0.0C
Página: 2
SN: IDOMINGC-3
Archivo: Eten
Proyecto:ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
MW Mvar AmpID %PF
XFMR
%Tap
Bus15 -0.342 -0.145 56.6 92.1
Bus15 6.600 10.5 94.889 1BBA51 -0.352 -0.160 35.7 91.00 0 0 0
Bus13 0.352 0.160 35.7 91.0
Bus17 6.600 10.5 94.913 1BBA51 -0.134 -0.059 13.5 91.50 0 0 0
Bus10 0.134 0.059 13.5 91.5
Bus18 6.600 10.5 94.922 1BBA51 0.000 0.000 0.0 -50.10 0 0 0
Bus19 6.600 10.5 94.898 1BBA51 -2.516 -1.852 288.0 80.50 0 0 0
1BFA53 2.516 1.852 288.0 80.5
Bus20 6.600 10.5 94.909 1BBA51 -0.647 -0.337 67.2 88.70 0 0 0
Bus EX 0.647 0.337 67.2 88.7
Bus22 6.900 10.5 90.797 1BBA51 -4.614 5.299 647.5 -65.70 0 0 0
BUS GEN 4.614 -5.299 647.5 -65.7
Bus BS 6.600 10.6 94.961 -2.774 8.440 1BBA76 8.440 -2.774 818.4 -95.00 0
Bus EX 0.480 8.8 87.108 0.311 0.642 Bus20 -0.642 -0.311 985.5 90.00 0
BUS GEN 18.000 6.4 100.344 -73.494 223.600 S.E. Etén 228.156 -79.546 7723.6 -94.40 0
2.500Bus22 -4.556 6.053 242.2 -60.1
PCI_BUS 0.480 4.6 90.899 0.107 0.173 1BFA51 -0.173 -0.107 269.8 85.00 0
S.E. Etén 220.000 0.4 99.762 S.E. Reque 227.540 -107.236 661.7 -90.50 0 0 0
-4.500BUS GEN -227.540 107.236 661.7 -90.5
S.E. Reque* 220.000 0.0 100.000 108.616-227.322 S.E. Etén -227.322 108.616 661.2 -90.20 0
*
# Indica una barra con un error de convergencia superior a 0,1 MVA
Indica una barra con tensión regulada (con máquinas de tensión controlada o máquinas de referencia conectadas)
One-Line Diagram - OLV1 (Load Flow Analysis)
page 1 10:10:16 may 02, 2014 Project File: Eten
RESERVA FRÍA ETEN
ESTUDIO DE FLUJO DE CARGAS: CASO LF-3 - MÍNIMA TENSIÓN EN BARRAS (REV C)
CONDICIONES:-> TENSIÓN DE RED: 220 kV-> GENERADOR PRINCIPAL PARADO-> GENERADOR AUXILIAR PARADO-> GENERADOR EMERGENCIA PARADO-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIÓN EN AUTO.-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIÓN EN TOMA CENTRAL.-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN ÚNICO TRAFO MT/BT.
1BFA51
0,48 kV94,
63%
1BBA51
6,6 kV97,
67%
1BFA53
0,48 kV 94,63%
1BMA52
0,48 kV 94,63%
1BNB52
0,38 kV97,
79%
CGDE
0,48 kV
1BBA76
6,6 kV 97,67%
1BJA76
0,48 kV98,
45%
BUS GEN
18 kV
99,85%
S.E. Etén
220 kV 99,99%
S.E. Reque
220 kV 100%
Sistema PCI
200 kW
173 kW
107 kvar
Red eléctrica Peruana
3022 MVAsc
3944 kW
2398 kvar
Narcissus
AL 2,92 km
0,0 %Vd
3944 kW
2879 kvar
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
1MKA10
225 MW
Isolated Phase CU
35 m
Isolated Phase CU
35 m
3943 kW
2867 kvar
Isolated Phase CU
8 m
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
4-3/C 240
CU 40 m
0,0 %Vd
1MKA76
8,44 MW
3-3/C 300
CU 20 m
CARGAS 1BJA76
270 kVA
170 kW
105 kvar
170 kW
105 kvar
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1-3/C 300
CU 20 m
0,0 %Vd
3-3/C 300
CU 120 m
0,0 %Vd
Excitación 1MKC10
944 kVA
680 kW
330 kvar
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1-3/C 150
CU 40 m
0,0 %Vd
LCI 1BPA10_1
2725 kVA
LCI 1BPA10_2
2725 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
3-3/C 240
CU 40 m
Open
88WN-1
224 kW
133 kW
57 kvar
1-3/C 70
CU 50 m
0,0 %Vd
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
0,0 %Vd
88WN-2
224 kW
1-3/C 70
CU 50 m
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
Open
88AK-1
375 kW
342 kW
145 kvar
1-3/C 70
CU 50 m
0,0 %Vd
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
0,0 %Vd
88AK-2
375 kW
1-3/C 70
CU 50 m
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
Open
W-1BMB20
1XKA52
2000 kW
6-3/C 300
CU 50 m
CARGAS 1BNB52
82,2 kVA
57 kW
28 kvar
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
58 kW
29 kvar
W-1BMB52
MBN50 AH010
450 kVA
363 kW
0 kvar
1BJA80
400 kVA
266 kW
165 kvar
W-1BJA12
2529 kW
1481 kvar
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
2-3/C 185
CU 40 m
0,0 %Vd
2-3/C 185
CU 40 m
0,0 %Vd
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
Open
W-1BJA51W-1BJA11
2-3/C 240
CU 115 m
0,7 %Vd
Excitación 1MKC10
944 kVA
LCI 1BPA10_1
2725 kVA
MBN50 AH010
450 kVA
CARGAS 1BNB52
82,2 kVA
W-1BJA51W-1BMB20W-1BJA12W-1BJA11W-1BMB52
1BJA80
400 kVA
CARGAS 1BJA76
270 kVA
LCI 1BPA10_2
2725 kVA
Open
Open
Open
Red eléctrica Peruana
3022 MVAsc
1MKA10
225 MW
1MKA76
8,44 MW
1XKA52
2000 kW
Narcissus
AL 2,92 km
6-3/C 300
CU 50 m
3-3/C 300
CU 120 m
3-3/C 300
CU 20 m1-3/C 300
CU 20 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 100 m
1-3/C 70
CU 70 m
1-3/C 70
CU 70 m
2-3/C 185
CU 40 m
2-3/C 185
CU 40 m
1-3/C 150
CU 40 m
3-3/C 240
CU 40 m
4-3/C 240
CU 40 m
1-3/C 70
CU 100 m
1-3/C 70
CU 50 m
2-3/C 240
CU 115 m
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
1BBA51
6,6 kV
1BFA53
0,48 kV
1BFA51
0,48 kV
S.E. Etén
220 kV
BUS GEN
18 kV
1BMA52
0,48 kV
CGDE
0,48 kV 1BNB52
0,38 kV
S.E. Reque
220 kV
1BBA76
6,6 kV
1BJA76
0,48 kV
Sistema PCI
200 kW
88WN-1
224 kW
88AK-1
375 kW
88WN-2
224 kW
88AK-2
375 kW
172 kW
109 kvar
172 kW
109 kvar
134 kW
59 kvar
0,04 kW
0,21 kvar
2576 kW
1870 kvar
685 kW
357 kvar
3918 kW
2552 kvar
352 kW
159 kvar
174 kW
108 kvar
548 kW
387 kvar
397 kW
298 kvar
363 kW
271 kvar
244 kW
137 kvar
117 kW
88 kvar
3944 kW
2398 kvar
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1085 kW
766 kvar
1504 kW
1018 kvar
98,45%
97,67%
100%
97,79%
94,63%
99,85%
99,99%
94,63%94,
63%
97,67%
Isolated Phase CU
35 m
Open
Isolated Phase CU
35 m
Isolated Phase CU
8 m
3918 kW
2552 kvar
172 kW
109 kvar
685 kW
357 kvar Open
1504 kW
1018 kvar
Open
3944 kW
2879 kvar
680 kW
330 kvar
1085 kW
766 kvar
Open
244 kW
137 kvar
2529 kW
1481 kvar
134 kW
59 kvar Open
352 kW
159 kvarOpen
363 kW
0 kvar
363 kW
271 kvar
57 kW
28 kvar
3944 kW
2398 kvar
3943 kW
2867 kvar
0,0 %Vd
3944 kW
2398 kvar
266 kW
165 kvar
2576 kW
1870 kvar
0,04 kW
0,21 kvar
397 kW
298 kvar
548 kW
387 kvar
174 kW
108 kvar
58 kW
29 kvar
117 kW
88 kvar
0,0 %Vd
133 kW
57 kvar
Open
172 kW
109 kvar
170 kW
105 kvar
170 kW
105 kvar
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
342 kW
145 kvar
173 kW
107 kvar0,7 %Vd
One-Line Diagram - OLV1 (Load Flow Analysis)
page 2 10:10:16 may 02, 2014 Project File: Eten
1BJA11
0,48 kV 94,3%
1BJA12
0,48 kV 94,38%
1BMB52
0,48 kV
94,51%
1BJA51
0,48 kV 94,49%
1BMB20
0,48 kV 94,43%
CARGAS 1BMB20
235 kVA
162 kW
100 kvar
1MBV10AP001-M01
75 kW
82 kW
36 kvar
1BMA52
4-3/C 240
CU 50 m
0,2 %Vd
Compresor 1
37 kW
19 kW
11 kvar
CARGAS 1BJA51
650 kVA
345 kW
258 kvar
1BFA51
4-3/C 240
CU 20 m
0,1 %Vd
1BMA52
2-3/C 150
CU 20 m
0,1 %Vd
Compresor 2
37 kW
Open
CARGAS 1BMB52
231 kVA
117 kW
88 kvar
CARGAS 1BJA12
592 kVA
396 kW
297 kvar
6-3/C 240
CU 50 m
0,2 %Vd
1BFA53
CARGAS 1BJA11
695 kVA
465 kW
349 kvar
1MBV10AP002-M1
75 kW
82 kW
36 kvar
6-3/C 240
CU 50 m
0,3 %Vd
1BFA51
CARGAS 1BMB20
235 kVA
CARGAS 1BMB52
231 kVA
1BFA51
1BMA52 1BFA53 1BFA51
1BMA52
CARGAS 1BJA11
695 kVA
CARGAS 1BJA12
592 kVA
CARGAS 1BJA51
650 kVA
4-3/C 240
CU 50 m
6-3/C 240
CU 50 m
6-3/C 240
CU 50 m
4-3/C 240
CU 20 m
2-3/C 150
CU 20 m
1BMB52
0,48 kV1BJA51
0,48 kV
1BMB20
0,48 kV
1BJA12
0,48 kV
1BJA11
0,48 kV
Compresor 1
37 kW
Compresor 2
37 kW
1MBV10AP001-M01
75 kW
1MBV10AP002-M1
75 kW
94,43%
94,49%
94,51%
Open
117 kW
88 kvar
162 kW
100 kvar
82 kW
36 kvar
0,2 %Vd
94,38%
0,2 %Vd
94,3%
0,3 %Vd
0,1 %Vd0,1 %Vd
19 kW
11 kvar
465 kW
349 kvar
396 kW
297 kvar
345 kW
258 kvar
82 kW
36 kvar
Ubicación:
Ingeniero:Caso de Estudio: LF-3
12.0.0C
Página: 1
SN: IDOMINGC-3
Archivo: Eten
Proyecto:ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
MW Mvar AmpID %PF
XFMR
%Tap
1BBA51 6.600 -3.1 97.675 -0.002 0.000 1BBA76 0.172 0.109 18.2 84.60 0
Bus17 0.134 0.059 13.1 91.5
Bus18 0.000 0.000 0.0 19.2
Bus19 2.576 1.870 285.1 80.9
Bus20 0.685 0.357 69.2 88.7
Bus22 -3.918 -2.552 418.8 83.8
Bus15 0.352 0.159 34.6 91.1
1BBA76 6.600 -3.1 97.673 1BBA51 -0.172 -0.109 18.2 84.60 0 0 0
Bus9 0.172 0.109 18.3 84.5
1BFA51 0.480 -8.7 94.625 PCI_BUS 0.174 0.108 261.0 84.90 0 0 0
1BJA11 0.548 0.387 852.4 81.7
1BJA51 0.363 0.271 575.6 80.2
1BMA52 -1.085 -0.766 1688.4 81.7
1BFA53 0.480 -8.7 94.625 0.165 0.629 1BJA12 0.397 0.298 630.6 79.90 0
Bus19 -2.529 -1.481 3725.7 86.3
1BMA52 1.504 1.018 2308.2 82.8
1BJA11 0.480 -8.7 94.301 0.385 0.546 1BFA51 -0.546 -0.385 852.4 81.70 0
1BJA12 0.480 -8.7 94.385 0.297 0.396 1BFA53 -0.396 -0.297 630.6 80.00 0
1BJA51 0.480 -8.7 94.494 0.270 0.363 1BFA51 -0.363 -0.270 575.6 80.20 0
1BJA76 0.480 -3.5 98.449 0.105 0.170 Bus9 -0.170 -0.105 244.4 85.00 0
1BMA52 0.480 -8.7 94.625 1BMB20 0.244 0.137 355.3 87.20 0 0 0
1BMB52 0.117 0.088 186.4 80.1
1BNB52 0.058 0.029 81.8 89.5
1BFA51 1.085 0.766 1688.4 81.7
1BFA53 -1.504 -1.018 2308.2 82.8
1BMB20 0.480 -8.7 94.426 0.136 0.243 1BMA52 -0.243 -0.136 355.3 87.30 0
1BMB52 0.480 -8.7 94.509 0.088 0.117 1BMA52 -0.117 -0.088 186.4 80.00 0
1BNB52 0.380 -9.3 97.790 0.028 0.057 1BMA52 -0.057 -0.028 98.2 90.00 0
Bus5 4.000 -3.6 100.117 0.057 0.132 Bus10 -0.132 -0.057 20.8 91.90 0
Bus7 4.000 -4.5 97.701 0.145 0.342 Bus13 -0.342 -0.145 54.9 92.10 0
Bus9 6.600 -3.1 97.671 1BBA76 -0.172 -0.109 18.3 84.50 0 0 0
2.5001BJA76 0.172 0.109 18.2 84.6
Bus10 4.160 -3.6 96.281 Bus5 0.132 0.057 20.8 91.90 0 0 0
Bus17 -0.132 -0.057 20.8 91.9
Bus13 4.000 -4.5 97.743 Bus7 0.342 0.145 54.9 92.10 0 0 0
Bus15 -0.342 -0.145 54.8 92.1
Ubicación:
Ingeniero:Caso de Estudio: LF-3
12.0.0C
Página: 2
SN: IDOMINGC-3
Archivo: Eten
Proyecto:ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
MW Mvar AmpID %PF
XFMR
%Tap
Bus15 6.600 -3.1 97.643 1BBA51 -0.352 -0.159 34.6 91.10 0 0 0
Bus13 0.352 0.159 34.6 91.1
Bus17 6.600 -3.1 97.667 1BBA51 -0.134 -0.059 13.1 91.50 0 0 0
Bus10 0.134 0.059 13.1 91.5
Bus18 6.600 -3.1 97.675 1BBA51 0.000 0.000 0.0 19.20 0 0 0
Bus19 6.600 -3.1 97.651 1BBA51 -2.576 -1.870 285.1 80.90 0 0 0
1BFA53 2.575 1.870 285.1 80.9
Bus20 6.600 -3.1 97.661 1BBA51 -0.685 -0.357 69.2 88.70 0 0 0
Bus EX 0.685 0.357 69.1 88.7
Bus22 6.900 -3.1 93.442 1BBA51 3.919 2.553 418.8 83.80 0 0 0
BUS GEN -3.919 -2.552 418.8 83.8
Bus EX 0.480 -4.7 89.634 0.330 0.680 Bus20 -0.680 -0.330 1014.1 90.00 0
BUS GEN 18.000 -0.1 99.849 0.000 0.001 S.E. Etén -3.944 -2.867 156.6 80.90 0
2.500Bus22 3.943 2.867 156.6 80.9
PCI_BUS 0.480 -8.8 93.946 0.107 0.173 1BFA51 -0.173 -0.107 261.0 85.00 0
S.E. Etén 220.000 0.0 99.991 S.E. Reque -3.944 -2.879 12.8 80.80 0 0 0
BUS GEN 3.944 2.879 12.8 80.8
S.E. Reque* 220.000 0.0 100.000 2.398 3.944 S.E. Etén 3.944 2.398 12.1 85.40 0
*
# Indica una barra con un error de convergencia superior a 0,1 MVA
Indica una barra con tensión regulada (con máquinas de tensión controlada o máquinas de referencia conectadas)
One-Line Diagram - OLV1 (Load Flow Analysis)
page 1 10:11:32 may 02, 2014 Project File: Eten
RESERVA FRÍA ETEN
ESTUDIO DE FLUJO DE CARGAS: CASO LF-4 - MÁXIMA TENSIÓN EN BARRAS (REV C)
CONDICIONES:-> TENSIÓN DE RED: 220 kV-> GENERADOR PRINCIPAL PARADO-> GENERADOR AUXILIAR PARADO-> GENERADOR EMERGENCIA PARADO-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIÓN EN AUTO.-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIÓN EN TOMA CENTRAL.-> TODAS LAS CARGAS FUERA DE SERVICIO.
1BFA51
0,48 kV107
,31%
1BBA51
6,6 kV102
%
1BFA53
0,48 kV 107,31
% 1BMA52
0,48 kV 107,31
%
1BNB52
0,38 kV112
,96%
CGDE
0,48 kV
1BBA76
6,6 kV 102%
1BJA76
0,48 kV104
,69%
BUS GEN
18 kV
100%
S.E. Etén
220 kV 100%
S.E. Reque
220 kV 100%
Sistema PCI
200 kW
Red eléctrica Peruana
3022 MVAsc
0,1 kW
481 kvar
Narcissus
AL 2,92 km
0,0 %Vd
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
0,1 kW
0,45 kvar
1MKA10
225 MW
Isolated Phase CU
35 m
Isolated Phase CU
35 m
0,13 kW
0,44 kvar
Isolated Phase CU
8 m
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
4-3/C 240
CU 40 m
0,0 %Vd
1MKA76
8,44 MW
3-3/C 300
CU 20 m
CARGAS 1BJA76
270 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1-3/C 300
CU 20 m
0,0 %Vd
3-3/C 300
CU 120 m
0,0 %Vd
Excitación 1MKC10
944 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1-3/C 150
CU 40 m
0,0 %Vd
LCI 1BPA10_1
2725 kVA
LCI 1BPA10_2
2725 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
3-3/C 240
CU 40 m
Open
88WN-1
224 kW
1-3/C 70
CU 50 m
0,0 %Vd
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
0,0 %Vd
88WN-2
224 kW
1-3/C 70
CU 50 m
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
Open
88AK-1
375 kW
1-3/C 70
CU 50 m
0,0 %Vd
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
0,0 %Vd
88AK-2
375 kW
1-3/C 70
CU 50 m
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
Open
W-1BMB20
1XKA52
2000 kW
6-3/C 300
CU 50 m
CARGAS 1BNB52
82,2 kVA
0,001 kW
0 kvar
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
W-1BMB52
0,21 kW
0,1 kvar
MBN50 AH010
450 kVA
1BJA80
400 kVA
W-1BJA12
0,18 kW
0,27 kvar
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
2-3/C 185
CU 40 m
0,0 %Vd
2-3/C 185
CU 40 m
0,0 %Vd
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
Open
W-1BJA51W-1BJA11
2-3/C 240
CU 115 m
0,0 %Vd
Excitación 1MKC10
944 kVA
LCI 1BPA10_1
2725 kVA
MBN50 AH010
450 kVA
CARGAS 1BNB52
82,2 kVA
W-1BJA51W-1BMB20W-1BJA12W-1BJA11W-1BMB52
1BJA80
400 kVA
CARGAS 1BJA76
270 kVA
LCI 1BPA10_2
2725 kVA
Open
Open
Open
Red eléctrica Peruana
3022 MVAsc
1MKA10
225 MW
1MKA76
8,44 MW
1XKA52
2000 kW
Narcissus
AL 2,92 km
6-3/C 300
CU 50 m
3-3/C 300
CU 120 m
3-3/C 300
CU 20 m1-3/C 300
CU 20 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 100 m
1-3/C 70
CU 70 m
1-3/C 70
CU 70 m
2-3/C 185
CU 40 m
2-3/C 185
CU 40 m
1-3/C 150
CU 40 m
3-3/C 240
CU 40 m
4-3/C 240
CU 40 m
1-3/C 70
CU 100 m
1-3/C 70
CU 50 m
2-3/C 240
CU 115 m
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
1BBA51
6,6 kV
1BFA53
0,48 kV
1BFA51
0,48 kV
S.E. Etén
220 kV
BUS GEN
18 kV
1BMA52
0,48 kV
CGDE
0,48 kV
S.E. Reque
220 kV
1BBA76
6,6 kV
1BJA76
0,48 kV
Sistema PCI
200 kW
88WN-1
224 kW
88AK-1
375 kW
88WN-2
224 kW
88AK-2
375 kW
0 kW
0 kvar
0 kW
-0,01 kvar
0 kW
0 kvar
0 kW
-0,01 kvar
0 kW
0,36 kvar
0,001 kW
0 kvar
0,06 kW
0,51 kvar
0,07 kW
0,13 kvar
0 kW
-0,01 kvar
0,03 kW
-0,18 kvar
0,03 kW
-0,18 kvar
0,04 kW
-0,3 kvar
0 kW
0,05 kvar
0,1 kW
0,45 kvar
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
0,07 kW
-0,46 kvar
1BNB52
0,38 kV
104,69
%
102%
100%
112,96
%
107,31
%
100%
100%
107,31
%107,31
%
102%
Isolated Phase CU
35 m
Open
Isolated Phase CU
35 m
Isolated Phase CU
8 m
0,06 kW
0,51 kvar
0,001 kW
0 kvar Open
Open
0,1 kW
0,45 kvar
0,07 kW
-0,46 kvar
Open
0,18 kW
0,27 kvar
0 kW
0 kvar Open
0,07 kW
0,13 kvarOpen
0,04 kW
-0,3 kvar
0,001 kW
0 kvar
0,1 kW
481 kvar
0,1 kW
0,45 kvar
0,13 kW
0,44 kvar
0,0 %Vd
0 kW
0,36 kvar
0 kW
-0,01 kvar
0,21 kW
0,1 kvar
0,03 kW
-0,18 kvar
0,03 kW
-0,18 kvar
0 kW
-0,01 kvar
0 kW
0,05 kvar
0,0 %Vd
Open
0 kW
-0,01 kvar
0 kW
0 kvar
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
One-Line Diagram - OLV1 (Load Flow Analysis)
page 2 10:11:32 may 02, 2014 Project File: Eten
1BJA11
0,48 kV 107,31
%1BJA12
0,48 kV 107,31
%
1BMB52
0,48 kV
107,31
%
1BJA51
0,48 kV 107,31
%
1BMB20
0,48 kV 107,31
%
CARGAS 1BMB20
235 kVA
1MBV10AP001-M01
75 kW
1BMA52
4-3/C 240
CU 50 m
0,0 %Vd
Compresor 1
37 kW
CARGAS 1BJA51
650 kVA
1BFA51
4-3/C 240
CU 20 m
0,0 %Vd
1BMA52
2-3/C 150
CU 20 m
0,0 %Vd
Compresor 2
37 kW
Open
CARGAS 1BMB52
231 kVA
CARGAS 1BJA12
592 kVA
6-3/C 240
CU 50 m
0,0 %Vd
1BFA53
CARGAS 1BJA11
695 kVA
1MBV10AP002-M1
75 kW
6-3/C 240
CU 50 m
0,0 %Vd
1BFA51
CARGAS 1BMB20
235 kVA
CARGAS 1BMB52
231 kVA
1BFA51
1BMA52 1BFA53 1BFA51
1BMA52
CARGAS 1BJA11
695 kVA
CARGAS 1BJA12
592 kVA
CARGAS 1BJA51
650 kVA
4-3/C 240
CU 50 m
6-3/C 240
CU 50 m
6-3/C 240
CU 50 m
4-3/C 240
CU 20 m
2-3/C 150
CU 20 m
1BMB52
0,48 kV1BJA51
0,48 kV
1BMB20
0,48 kV
1BJA12
0,48 kV
1BJA11
0,48 kV
Compresor 1
37 kW
Compresor 2
37 kW
1MBV10AP001-M01
75 kW
1MBV10AP002-M1
75 kW
0,01 kW
-0,05 kvar 107,31
%
107,31
%
107,31
%
Open
0,0 %Vd
107,31
%
0,0 %Vd
107,31
%
0,0 %Vd
0,0 %Vd0,0 %Vd
0,01 kW
-0,05 kvar
Ubicación:
Ingeniero:Caso de Estudio: LF-4
12.0.0C
Página: 1
SN: IDOMINGC-3
Archivo: Eten
Proyecto:ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
MW Mvar AmpID %PF
XFMR
%Tap
1BBA51 6.600 0.0 101.997 1BBA76 0.000 0.000 0.0 10.00 0 0 0
Bus17 0.000 0.000 0.0 0.0
Bus18 0.000 0.000 0.0 -1.8
Bus19 0.000 0.000 0.0 0.6
Bus20 0.000 0.000 0.0 38.9
Bus22 0.000 0.001 0.0 11.7
Bus15 0.000 0.000 0.0 47.6
1BBA76 6.600 0.0 101.997 1BBA51 0.000 0.000 0.0 10.00 0 0 0
Bus9 0.000 0.000 0.0 -16.2
1BFA51 0.480 0.0 107.310 PCI_BUS 0.000 0.000 0.0 -17.90 0 0 0
1BJA11 0.000 0.000 0.2 -14.9
1BJA51 0.000 0.000 0.3 -14.9
1BMA52 0.000 0.000 0.5 -14.8
1BFA53 0.480 0.0 107.310 1BJA12 0.000 0.000 0.2 -14.90 0 0 0
Bus19 0.000 0.000 0.4 55.4
1BMA52 0.000 0.000 0.3 90.8
1BJA11 0.480 0.0 107.310 1BFA51 0.000 0.000 0.2 -14.90 0 0 0
1BJA12 0.480 0.0 107.310 1BFA53 0.000 0.000 0.2 -14.90 0 0 0
1BJA51 0.480 0.0 107.310 1BFA51 0.000 0.000 0.3 -14.90 0 0 0
1BJA76 0.480 0.0 104.692 Bus9 0.000 0.000 0.0 0.00 0 0 0
1BMA52 0.480 0.0 107.310 1BMB20 0.000 0.000 0.1 -17.90 0 0 0
1BMB52 0.000 0.000 0.1 3.7
1BNB52 0.000 0.000 0.0 -43.5
1BFA51 0.000 0.000 0.5 -14.8
1BFA53 0.000 0.000 0.3 90.8
1BMB20 0.480 0.0 107.310 1BMA52 0.000 0.000 0.1 -17.90 0 0 0
1BMB52 0.480 0.0 107.310 1BMA52 0.000 0.000 0.1 3.70 0 0 0
1BNB52 0.380 0.0 112.958 1BMA52 0.000 0.000 0.0 -43.50 0 0 0
Bus5 4.000 0.0 106.077 Bus10 0.000 0.000 0.0 18.70 0 0 0
Bus7 4.000 0.0 106.078 Bus13 0.000 0.001 0.1 6.80 0 0 0
Bus9 6.600 0.0 101.997 1BBA76 0.000 0.000 0.0 -16.20 0 0 0
2.5001BJA76 0.000 0.000 0.0 0.0
Bus10 4.160 0.0 101.997 Bus5 0.000 0.000 0.0 18.70 0 0 0
Bus17 0.000 0.000 0.0 93.5
Bus13 4.000 0.0 106.078 Bus7 0.000 -0.001 0.1 6.80 0 0 0
Bus15 0.000 0.000 0.0 71.1
Ubicación:
Ingeniero:Caso de Estudio: LF-4
12.0.0C
Página: 2
SN: IDOMINGC-3
Archivo: Eten
Proyecto:ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
MW Mvar AmpID %PF
XFMR
%Tap
Bus15 6.600 0.0 101.997 1BBA51 0.000 0.000 0.0 47.60 0 0 0
Bus13 0.000 0.000 0.0 71.1
Bus17 6.600 0.0 101.997 1BBA51 0.000 0.000 0.0 0.00 0 0 0
Bus10 0.000 0.000 0.0 93.5
Bus18 6.600 0.0 101.997 1BBA51 0.000 0.000 0.0 -1.80 0 0 0
Bus19 6.600 0.0 101.997 1BBA51 0.000 0.000 0.0 0.60 0 0 0
1BFA53 0.000 0.000 0.0 55.4
Bus20 6.600 0.0 101.997 1BBA51 0.000 0.000 0.0 38.90 0 0 0
Bus EX 0.000 0.000 0.0 0.0
Bus22 6.900 0.0 97.562 1BBA51 0.000 -0.001 0.0 11.70 0 0 0
BUS GEN 0.000 0.000 0.0 29.0
Bus EX 0.480 0.0 95.622 Bus20 0.000 0.000 0.0 0.00 0 0 0
BUS GEN 18.000 0.0 100.001 S.E. Etén 0.000 0.000 0.0 21.60 0 0 0
2.500Bus22 0.000 0.000 0.0 29.0
PCI_BUS 0.480 0.0 107.310 1BFA51 0.000 0.000 0.0 -17.90 0 0 0
S.E. Etén 220.000 0.0 100.001 S.E. Reque 0.000 0.000 0.0 21.20 0 0 0
BUS GEN 0.000 0.000 0.0 21.6
S.E. Reque* 220.000 0.0 100.000 -0.481 0.000 S.E. Etén 0.000 -0.481 1.3 0.00 0
*
# Indica una barra con un error de convergencia superior a 0,1 MVA
Indica una barra con tensión regulada (con máquinas de tensión controlada o máquinas de referencia conectadas)
CÁLCULOS ELÉCTRICOS Rev. C
ANEXO VI
RFE-1-YE__-ECE-IDO-001 Pág/Page 1 de/of 49
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
ANEXO VII:
REPORTES DEL ANÁLISIS DE CORTOCIRCUITO
One-Line Diagram - OLV1 (Short-Circuit Analysis)
page 1 10:00:39 may 02, 2014 Project File: Eten
RESERVA FRÍA ETEN
ESTUDIO DE CORTOCIRCUITO: CASO SC-1 (REV C)
CONDICIONES:-> TENSIÓN DE RED: 220 kV-> GENERADOR PRINCIPAL OPERANDO-> GENERADOR AUXILIAR OPERANDO-> GENERADOR EMERGENCIA PARADO-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIÓN EN AUTO.-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIÓN EN TOMA CENTRAL.-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN ÚNICO TRAFO MT/BT.
1BFA51
0,48 kV49,7 kA
1BBA51
6,6 kV
16,8 kA
1BFA53
0,48 kV49,7 kA
1BMA52
0,48 kV49,7 kA
1BNB52
0,38 kV5,6 kA
CGDE
0,48 kV
1BBA76
6,6 kV 16,8 kA
1BJA76
0,48 kV
16,3 kA
BUS GEN
18 kV
104,6 kA
S.E. Etén
220 kV10,3 kA
S.E. Reque
220 kV10,8 kA
Sistema PCI
200 kW
Red eléctrica Peruana
3022 MVAsc
220 kV
7,93
Narcissus
AL 2,92 km
2,92
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
44,53
1MKA10
225 MW
18 kV
17 %Xd"
9021 A
Isolated Phase CU
35 m
Isolated Phase CU
35 m
58,48 1,63
Isolated Phase CU
8 m
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
4-3/C 240
CU 40 m
1MKA76
8,44 MW
6,6 kV
16 %Xd"
922,9 A
3-3/C 300
CU 20 m
CARGAS 1BJA76
270 kVA
1,23
15,12
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1-3/C 300
CU 20 m
3-3/C 300
CU 120 m
Excitación 1MKC10
944 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1-3/C 150
CU 40 m
LCI 1BPA10_1
2725 kVA
LCI 1BPA10_2
2725 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
3-3/C 240
CU 40 m
Open
88WN-1
224 kW
1-3/C 70
CU 50 m
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
88WN-2
224 kW
1-3/C 70
CU 50 m
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
Open
88AK-1
375 kW
1-3/C 70
CU 50 m
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
88AK-2
375 kW
1-3/C 70
CU 50 m
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
Open
39,77
W-1BMB20
1XKA52
2000 kW
0,48 kV
3007 A
6-3/C 300
CU 50 m
Open
CARGAS 1BNB52
82,2 kVA
,085
5,56
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
,074
W-1BMB52
36,59
MBN50 AH010
450 kVA
1BJA80
400 kVA
,821
W-1BJA12
31,86
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
2-3/C 185
CU 40 m 2-3/C 185
CU 40 m
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
Open
W-1BJA51W-1BJA11
2-3/C 240
CU 115 m
Excitación 1MKC10
944 kVA
LCI 1BPA10_1
2725 kVA
MBN50 AH010
450 kVA
CARGAS 1BNB52
82,2 kVA
W-1BJA51W-1BMB20W-1BJA12W-1BJA11W-1BMB52
1BJA80
400 kVA
CARGAS 1BJA76
270 kVA
LCI 1BPA10_2
2725 kVA
Red eléctrica Peruana
3022 MVAsc
220 kV
1MKA10
225 MW
18 kV
17 %Xd"
9021 A
1MKA76
8,44 MW
6,6 kV
16 %Xd"
922,9 A
1XKA52
2000 kW
0,48 kV
3007 A
Narcissus
AL 2,92 km
6-3/C 300
CU 50 m
3-3/C 300
CU 120 m
3-3/C 300
CU 20 m1-3/C 300
CU 20 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 100 m
1-3/C 70
CU 70 m
1-3/C 70
CU 70 m
2-3/C 185
CU 40 m
2-3/C 185
CU 40 m
1-3/C 150
CU 40 m
3-3/C 240
CU 40 m
4-3/C 240
CU 40 m
1-3/C 70
CU 100 m
1-3/C 70
CU 50 m
2-3/C 240
CU 115 m
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
1BBA51
6,6 kV
1BFA53
0,48 kV
1BFA51
0,48 kV
S.E. Etén
220 kV
BUS GEN
18 kV
1BMA52
0,48 kV
CGDE
0,48 kV 1BNB52
0,38 kV
S.E. Reque
220 kV
1BBA76
6,6 kV
1BJA76
0,48 kV
Sistema PCI
200 kW
88WN-1
224 kW
88AK-1
375 kW
88WN-2
224 kW
88AK-2
375 kW
7,35
9,39
7,32,092
,1531,05
8,07
,233
2,065,214,08 2,812,24,944
2,84
7,34
10,0613,32
16,3 kA
16,8 kA
10,8 kA
5,6 kA
49,7 kA
104,6 kA
10,3 kA
49,7 kA49,7 kA
16,8 kA
Isolated Phase CU
35 m
Isolated Phase CU
35 m
Isolated Phase CU
8 m
8,07
7,35
Open
13,32
Open
2,92
44,53
58,48
10,06
Open
2,24
31,86
,153
Open
,233
Open
2,81
5,56
,085
7,93
7,34
1,63
2,84
,821
1,05
36,59 39,774,08 5,21 2,06,074,944
7,32,092
15,12
1,23
9,39
One-Line Diagram - OLV1 (Short-Circuit Analysis)
page 2 10:00:39 may 02, 2014 Project File: Eten
1BJA11
0,48 kV44,9 kA
1BJA12
0,48 kV44,6 kA
1BMB52
0,48 kV41,9 kA
1BJA51
0,48 kV46,3 kA
1BMB20
0,48 kV41,7 kA
CARGAS 1BMB20
235 kVA
1,45
1MBV10AP001-M01
75 kW
,82
1BMA52
4-3/C 240
CU 50 m
Compresor 1
37 kW
,153
CARGAS 1BJA51
650 kVA
2,67
1BFA51
4-3/C 240
CU 20 m
1BMA52
2-3/C 150
CU 20 m
Compresor 2
37 kW
Open
CARGAS 1BMB52
231 kVA
,948
CARGAS 1BJA12
592 kVA
4,13
6-3/C 240
CU 50 m
1BFA53
CARGAS 1BJA11
695 kVA
4,48
1MBV10AP002-M1
75 kW
,82
6-3/C 240
CU 50 m
1BFA51
CARGAS 1BMB20
235 kVA
CARGAS 1BMB52
231 kVA
1BFA51
1BMA52 1BFA53 1BFA51
1BMA52
CARGAS 1BJA11
695 kVA
CARGAS 1BJA12
592 kVA
CARGAS 1BJA51
650 kVA
4-3/C 240
CU 50 m
6-3/C 240
CU 50 m
6-3/C 240
CU 50 m
4-3/C 240
CU 20 m
2-3/C 150
CU 20 m
1BMB52
0,48 kV1BJA51
0,48 kV
1BMB20
0,48 kV
1BJA12
0,48 kV
1BJA11
0,48 kV
Compresor 1
37 kW
Compresor 2
37 kW
1MBV10AP001-M01
75 kW
1MBV10AP002-M1
75 kW
39,6140,48
43,5
39,47
40,98
41,7 kA
46,3 kA41,9 kA 40,98
Open
,948
1,45 ,82
44,6 kA44,9 kA
,153
4,484,13
2,67
43,5
39,47 40,48 39,61
,82
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 1
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Cortocircuito
Falta trifásica en barra: 1BBA51
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
6.600
1.10
42.505
15.340
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BBA51 Total 0.00 1.477 -16.764 11.4 16.829
1BBA76 1BBA51 0.81 0.450 -7.339 16.3 7.353
Bus17 1BBA51 0.07 0.041 -0.147 3.6 0.153
Bus18 1BBA51 0.00 0.000 0.000 999.9 0.000
Bus19 1BBA51 0.07 0.303 -1.005 3.3 1.049
Bus20 1BBA51 0.00 0.000 0.000 999.9 0.000
Bus22 1BBA51 0.23 0.619 -8.048 13.0 8.072
Bus15 1BBA51 0.15 0.064 -0.224 3.5 0.233
Bus BS 1BBA76 0.94 0.413 -7.256 17.6 7.268
Bus9 1BBA76 0.81 0.037 -0.083 2.3 0.091
Bus10 Bus17 14.61 0.041 -0.147 3.6 0.153
1BFA53 Bus19 34.11 0.303 -1.005 3.3 1.049
Bus EX Bus20 0.00 0.000 0.000 999.9 0.000
BUS GEN Bus22 95.11 0.619 -8.048 13.0 8.072
Bus13 Bus15 23.23 0.064 -0.224 3.5 0.233
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
17.733 0.01 16.078 23.937
13.779 0.02 15.753 20.929
10.484 0.03 15.414 18.641
7.977 0.04 15.065 17.047
6.436 0.05 14.709 16.055
4.955 0.06 14.562 15.382
3.814 0.07 14.415 14.911
2.937 0.08 14.270 14.569
2.426 0.09 14.122 14.329
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 2
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
(Cont.)
Falta trifásica en barra: 1BBA51
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
6.600
1.10
42.505
15.340
(Definido por el Usuario)
kA Método C
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
1.883 0.10 13.973 14.099
0.530 0.15 13.740 13.751
0.149 0.20 13.509 13.510
0.042 0.25 13.280 13.280
0.012 0.30 13.111 13.111
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 3
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BBA76
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
6.600
1.10
42.389
15.327
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BBA76 Total 0.00 1.483 -16.725 11.3 16.791
1BBA51 1BBA76 1.03 1.057 -9.331 8.8 9.391
Bus BS 1BBA76 0.13 0.389 -7.310 18.8 7.321
Bus9 1BBA76 0.01 0.037 -0.084 2.3 0.092
Bus17 1BBA51 1.10 0.041 -0.146 3.5 0.151
Bus18 1BBA51 1.03 0.000 0.000 999.9 0.000
Bus19 1BBA51 1.10 0.304 -0.994 3.3 1.040
Bus20 1BBA51 1.03 0.000 0.000 999.9 0.000
Bus22 1BBA51 1.21 0.647 -7.969 12.3 7.996
Bus15 1BBA51 1.17 0.064 -0.222 3.4 0.231
1MKA76 Bus BS 100.00 0.389 -7.310 18.8 7.321
1BJA76 Bus9 7.25 0.037 -0.084 2.3 0.092
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
17.678 0.01 16.031 23.864
13.764 0.02 15.703 20.881
10.479 0.03 15.360 18.594
7.978 0.04 15.008 16.997
6.504 0.05 14.649 16.028
5.020 0.06 14.501 15.345
3.875 0.07 14.355 14.869
2.991 0.08 14.206 14.517
2.534 0.09 14.056 14.283
1.976 0.10 13.906 14.045
0.570 0.15 13.672 13.684
0.164 0.20 13.440 13.441
0.047 0.25 13.209 13.209
0.014 0.30 13.038 13.038
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 4
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BFA51
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
111.741
31.702
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BFA51 Total 0.00 10.201 -48.619 4.8 49.677
PCI_BUS 1BFA51 4.52 0.504 -1.997 4.0 2.060
1BJA11 1BFA51 1.66 1.970 -4.823 2.4 5.210
1BJA51 1BFA51 0.53 1.089 -2.586 2.4 2.806
1BMB20 1BMA52 1.07 0.802 -2.095 2.6 2.243
1BMB52 1BMA52 0.47 0.368 -0.870 2.4 0.944
1BNB52 1BMA52 1.45 0.029 -0.068 2.4 0.074
1BJA12 1BFA53 1.30 1.595 -3.755 2.4 4.080
Bus19 1BFA53 78.76 3.525 -31.668 9.0 31.863
1BJA80 1BFA53 100.00 0.318 -0.757 2.4 0.821
Sistema PCI PCI_BUS 100.00 0.504 -1.997 4.0 2.060
1MBV10AP002-M1 1BJA11 104.35 0.242 -0.770 3.2 0.807
CARGAS 1BJA11 1BJA11 100.00 1.728 -4.053 2.3 4.406
Compresor 1 1BJA51 100.00 0.057 -0.141 2.5 0.152
CARGAS 1BJA51 1BJA51 100.00 1.032 -2.445 2.4 2.654
1MBV10AP001-M01 1BMB20 104.35 0.242 -0.775 3.2 0.812
CARGAS 1BMB20 1BMB20 100.00 0.560 -1.320 2.4 1.434
CARGAS 1BMB52 1BMB52 100.00 0.368 -0.870 2.4 0.944
CARGAS 1BNB52 1BNB52 105.26 0.035 -0.082 2.4 0.089
CARGAS 1BJA12 1BJA12 100.00 1.595 -3.755 2.4 4.080
1BBA51 Bus19 78.90 0.270 -2.423 9.0 2.438
1BMA52 1BFA51 0.00 6.637 -39.212 5.9 39.770
1BFA53 1BMA52 0.00 5.438 -36.179 6.7 36.586
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
38.147 0.01 47.777 61.138
24.463 0.02 46.760 52.772
14.435 0.03 45.612 47.842
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 5
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
(Cont.)
Falta trifásica en barra: 1BFA51
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
111.741
31.702
(Definido por el Usuario)
kA Método C
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
8.518 0.04 44.511 45.318
6.061 0.05 43.463 43.884
3.713 0.06 42.958 43.119
2.275 0.07 42.467 42.528
1.393 0.08 41.988 42.012
1.004 0.09 41.524 41.536
0.626 0.10 41.074 41.079
0.059 0.15 40.193 40.193
0.006 0.20 39.365 39.365
0.001 0.25 38.592 38.592
0.000 0.30 38.566 38.566
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 6
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BFA53
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
111.741
31.702
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BFA53 Total 0.00 10.201 -48.619 4.8 49.677
1BJA12 1BFA53 1.30 1.595 -3.755 2.4 4.080
Bus19 1BFA53 78.76 3.525 -31.668 9.0 31.863
1BJA80 1BFA53 100.00 0.318 -0.757 2.4 0.821
1BMB20 1BMA52 1.07 0.802 -2.095 2.6 2.243
1BMB52 1BMA52 0.47 0.368 -0.870 2.4 0.944
1BNB52 1BMA52 1.45 0.029 -0.068 2.4 0.074
PCI_BUS 1BFA51 4.52 0.504 -1.997 4.0 2.060
1BJA11 1BFA51 1.66 1.970 -4.823 2.4 5.210
1BJA51 1BFA51 0.53 1.089 -2.586 2.4 2.806
CARGAS 1BJA12 1BJA12 100.00 1.595 -3.755 2.4 4.080
1BBA51 Bus19 78.90 0.270 -2.423 9.0 2.438
1MBV10AP001-M01 1BMB20 104.35 0.242 -0.775 3.2 0.812
CARGAS 1BMB20 1BMB20 100.00 0.560 -1.320 2.4 1.434
CARGAS 1BMB52 1BMB52 100.00 0.368 -0.870 2.4 0.944
CARGAS 1BNB52 1BNB52 105.26 0.035 -0.082 2.4 0.089
Sistema PCI PCI_BUS 100.00 0.504 -1.997 4.0 2.060
1MBV10AP002-M1 1BJA11 104.35 0.242 -0.770 3.2 0.807
CARGAS 1BJA11 1BJA11 100.00 1.728 -4.053 2.3 4.406
Compresor 1 1BJA51 100.00 0.057 -0.141 2.5 0.152
CARGAS 1BJA51 1BJA51 100.00 1.032 -2.445 2.4 2.654
1BFA51 1BMA52 0.00 3.563 -9.407 2.6 10.059
1BMA52 1BFA53 0.00 4.762 -12.439 2.6 13.320
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
38.147 0.01 47.777 61.138
24.463 0.02 46.760 52.772
14.435 0.03 45.612 47.842
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 7
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
(Cont.)
Falta trifásica en barra: 1BFA53
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
111.741
31.702
(Definido por el Usuario)
kA Método C
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
8.518 0.04 44.511 45.318
6.061 0.05 43.463 43.884
3.713 0.06 42.958 43.119
2.275 0.07 42.467 42.528
1.393 0.08 41.988 42.012
1.004 0.09 41.524 41.536
0.626 0.10 41.074 41.079
0.059 0.15 40.193 40.193
0.006 0.20 39.365 39.365
0.001 0.25 38.592 38.592
0.000 0.30 38.566 38.566
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 8
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BJA11
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
94.635
29.226
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BJA11 Total 0.00 11.720 -43.306 3.7 44.864
1BFA51 1BJA11 12.59 9.745 -38.395 3.9 39.613
1MBV10AP002-M1 1BJA11 104.35 0.242 -0.784 3.2 0.820
CARGAS 1BJA11 1BJA11 100.00 1.734 -4.127 2.4 4.477
PCI_BUS 1BFA51 16.59 0.559 -1.744 3.1 1.831
1BJA51 1BFA51 13.05 1.111 -2.234 2.0 2.495
1BMB20 1BMA52 13.52 0.829 -1.814 2.2 1.994
1BMB52 1BMA52 13.00 0.375 -0.751 2.0 0.839
1BNB52 1BMA52 14.47 0.029 -0.059 2.0 0.066
1BJA12 1BFA53 13.71 1.625 -3.242 2.0 3.627
Bus19 1BFA53 80.63 4.894 -27.898 5.7 28.324
1BJA80 1BFA53 100.00 0.324 -0.654 2.0 0.730
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
26.975 0.01 43.408 51.107
13.412 0.02 42.475 44.542
6.166 0.03 41.505 41.961
2.835 0.04 40.572 40.671
1.559 0.05 39.681 39.712
0.743 0.06 39.251 39.258
0.354 0.07 38.831 38.833
0.169 0.08 38.422 38.423
0.094 0.09 38.025 38.025
0.046 0.10 37.638 37.638
0.001 0.15 36.877 36.877
0.000 0.20 36.159 36.159
0.000 0.25 35.487 35.487
0.000 0.30 35.464 35.464
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 9
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BJA12
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
93.861
29.226
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BJA12 Total 0.00 11.744 -43.001 3.7 44.576
1BFA53 1BJA12 12.86 10.144 -39.193 3.9 40.484
CARGAS 1BJA12 1BJA12 100.00 1.600 -3.808 2.4 4.131
Bus19 1BFA53 80.68 4.906 -27.809 5.7 28.238
1BJA80 1BFA53 100.00 0.324 -0.651 2.0 0.728
1BMB20 1BMA52 13.80 0.828 -1.808 2.2 1.988
1BMB52 1BMA52 13.28 0.374 -0.748 2.0 0.837
1BNB52 1BMA52 14.76 0.029 -0.058 2.0 0.065
PCI_BUS 1BFA51 16.86 0.559 -1.738 3.1 1.825
1BJA11 1BFA51 14.30 2.015 -4.155 2.1 4.617
1BJA51 1BFA51 13.33 1.109 -2.226 2.0 2.487
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
26.657 0.01 43.201 50.764
13.243 0.02 42.282 44.307
6.070 0.03 41.343 41.786
2.782 0.04 40.439 40.534
1.534 0.05 39.576 39.605
0.729 0.06 39.159 39.166
0.347 0.07 38.752 38.753
0.165 0.08 38.355 38.356
0.092 0.09 37.969 37.969
0.045 0.10 37.594 37.594
0.001 0.15 36.855 36.855
0.000 0.20 36.157 36.157
0.000 0.25 35.503 35.503
0.000 0.30 35.481 35.481
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 10
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BJA51
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
99.706
30.178
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BJA51 Total 0.00 11.263 -44.890 4.0 46.282
1BFA51 1BJA51 8.29 10.173 -42.289 4.2 43.495
Compresor 1 1BJA51 100.00 0.057 -0.142 2.5 0.153
CARGAS 1BJA51 1BJA51 100.00 1.033 -2.460 2.4 2.668
PCI_BUS 1BFA51 12.47 0.542 -1.831 3.4 1.909
1BJA11 1BFA51 9.80 2.006 -4.393 2.2 4.829
1BMB20 1BMA52 9.27 0.822 -1.910 2.3 2.079
1BMB52 1BMA52 8.72 0.373 -0.792 2.1 0.875
1BNB52 1BMA52 10.01 0.029 -0.062 2.1 0.068
1BJA12 1BFA53 9.47 1.619 -3.418 2.1 3.782
Bus19 1BFA53 79.99 4.458 -29.196 6.5 29.534
1BJA80 1BFA53 100.00 0.323 -0.689 2.1 0.761
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
30.337 0.01 44.772 54.082
16.604 0.02 43.809 46.850
8.363 0.03 42.823 43.632
4.212 0.04 41.874 42.085
2.563 0.05 40.967 41.047
1.341 0.06 40.529 40.552
0.701 0.07 40.102 40.108
0.367 0.08 39.685 39.687
0.226 0.09 39.279 39.280
0.121 0.10 38.885 38.885
0.005 0.15 38.109 38.109
0.000 0.20 37.377 37.377
0.000 0.25 36.691 36.691
0.000 0.30 36.669 36.669
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 11
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BJA76
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
27.361
15.044
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BJA76 Total 0.00 8.418 -13.999 1.7 16.335
Bus9 1BJA76 91.09 7.943 -12.867 1.6 15.121
CARGAS 1BJA76 1BJA76 100.00 0.476 -1.132 2.4 1.228
1BBA76 Bus9 91.16 0.593 -0.961 1.6 1.129
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
2.480 0.01 16.158 16.348
0.273 0.02 16.066 16.068
0.030 0.03 15.974 15.974
0.003 0.04 15.883 15.883
0.000 0.05 15.794 15.794
0.000 0.06 15.751 15.751
0.000 0.07 15.707 15.707
0.000 0.08 15.664 15.664
0.000 0.09 15.622 15.622
0.000 0.10 15.580 15.580
0.000 0.15 15.498 15.498
0.000 0.20 15.418 15.418
0.000 0.25 15.342 15.342
0.000 0.30 15.340 15.340
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 12
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BMA52
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
111.741
31.702
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BMA52 Total 0.00 10.201 -48.619 4.8 49.677
1BMB20 1BMA52 1.07 0.802 -2.095 2.6 2.243
1BMB52 1BMA52 0.47 0.368 -0.870 2.4 0.944
1BNB52 1BMA52 1.45 0.029 -0.068 2.4 0.074
1BJA12 1BFA53 1.30 1.595 -3.755 2.4 4.080
Bus19 1BFA53 78.76 3.525 -31.668 9.0 31.863
1BJA80 1BFA53 100.00 0.318 -0.757 2.4 0.821
PCI_BUS 1BFA51 4.52 0.504 -1.997 4.0 2.060
1BJA11 1BFA51 1.66 1.970 -4.823 2.4 5.210
1BJA51 1BFA51 0.53 1.089 -2.586 2.4 2.806
1MBV10AP001-M01 1BMB20 104.35 0.242 -0.775 3.2 0.812
CARGAS 1BMB20 1BMB20 100.00 0.560 -1.320 2.4 1.434
CARGAS 1BMB52 1BMB52 100.00 0.368 -0.870 2.4 0.944
CARGAS 1BNB52 1BNB52 105.26 0.035 -0.082 2.4 0.089
CARGAS 1BJA12 1BJA12 100.00 1.595 -3.755 2.4 4.080
1BBA51 Bus19 78.90 0.270 -2.423 9.0 2.438
Sistema PCI PCI_BUS 100.00 0.504 -1.997 4.0 2.060
1MBV10AP002-M1 1BJA11 104.35 0.242 -0.770 3.2 0.807
CARGAS 1BJA11 1BJA11 100.00 1.728 -4.053 2.3 4.406
Compresor 1 1BJA51 100.00 0.057 -0.141 2.5 0.152
CARGAS 1BJA51 1BJA51 100.00 1.032 -2.445 2.4 2.654
1BFA51 1BMA52 0.00 3.563 -9.407 2.6 10.059
1BFA53 1BMA52 0.00 5.438 -36.179 6.7 36.586
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
38.147 0.01 47.777 61.138
24.463 0.02 46.760 52.772
14.435 0.03 45.612 47.842
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 13
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
(Cont.)
Falta trifásica en barra: 1BMA52
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
111.741
31.702
(Definido por el Usuario)
kA Método C
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
8.518 0.04 44.511 45.318
6.061 0.05 43.463 43.884
3.713 0.06 42.958 43.119
2.275 0.07 42.467 42.528
1.393 0.08 41.988 42.012
1.004 0.09 41.524 41.536
0.626 0.10 41.074 41.079
0.059 0.15 40.193 40.193
0.006 0.20 39.365 39.365
0.001 0.25 38.592 38.592
0.000 0.30 38.566 38.566
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 14
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BMB20
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
85.499
28.103
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BMB20 Total 0.00 12.126 -39.926 3.3 41.727
1BMA52 1BMB20 18.81 11.324 -37.807 3.3 39.466
1MBV10AP001-M01 1BMB20 104.35 0.242 -0.784 3.2 0.820
CARGAS 1BMB20 1BMB20 100.00 0.561 -1.336 2.4 1.449
1BMB52 1BMA52 19.20 0.371 -0.692 1.9 0.785
1BNB52 1BMA52 20.94 0.029 -0.054 1.9 0.061
1BJA12 1BFA53 19.87 1.607 -2.988 1.9 3.392
Bus19 1BFA53 81.61 5.330 -25.953 4.9 26.494
1BJA80 1BFA53 100.00 0.321 -0.602 1.9 0.683
PCI_BUS 1BFA51 22.56 0.569 -1.615 2.8 1.713
1BJA11 1BFA51 20.16 1.998 -3.844 1.9 4.332
1BJA51 1BFA51 19.24 1.099 -2.059 1.9 2.333
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
22.339 0.01 40.464 46.220
9.959 0.02 39.694 40.925
4.091 0.03 38.906 39.120
1.681 0.04 38.144 38.181
0.832 0.05 37.414 37.424
0.355 0.06 37.060 37.062
0.151 0.07 36.714 36.714
0.065 0.08 36.376 36.376
0.032 0.09 36.046 36.046
0.014 0.10 35.725 35.725
0.000 0.15 35.092 35.092
0.000 0.20 34.492 34.492
0.000 0.25 33.928 33.928
0.000 0.30 33.913 33.913
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 15
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BMB52
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
82.601
28.515
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BMB52 Total 0.00 13.991 -39.528 2.8 41.931
1BMA52 1BMB52 20.21 13.624 -38.654 2.8 40.984
CARGAS 1BMB52 1BMB52 100.00 0.367 -0.874 2.4 0.948
1BMB20 1BMA52 21.05 0.907 -1.654 1.8 1.886
1BNB52 1BMA52 22.32 0.032 -0.053 1.7 0.062
1BJA12 1BFA53 21.21 1.756 -2.946 1.7 3.430
Bus19 1BFA53 81.57 6.540 -25.976 4.0 26.787
1BJA80 1BFA53 100.00 0.351 -0.594 1.7 0.690
PCI_BUS 1BFA51 23.89 0.647 -1.606 2.5 1.732
1BJA11 1BFA51 21.49 2.190 -3.793 1.7 4.380
1BJA51 1BFA51 20.62 1.202 -2.030 1.7 2.359
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
19.005 0.01 40.782 44.993
7.339 0.02 40.062 40.729
2.582 0.03 39.322 39.407
0.908 0.04 38.608 38.619
0.396 0.05 37.924 37.926
0.145 0.06 37.592 37.593
0.053 0.07 37.268 37.268
0.020 0.08 36.952 36.952
0.009 0.09 36.643 36.643
0.003 0.10 36.342 36.342
0.000 0.15 35.748 35.748
0.000 0.20 35.186 35.186
0.000 0.25 34.659 34.659
0.000 0.30 34.644 34.644
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 16
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BNB52
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.380
1.05
9.416
5.310
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BNB52 Total 0.00 2.945 -4.814 1.6 5.644
1BMA52 1BNB52 86.27 2.912 -4.736 1.6 5.559
CARGAS 1BNB52 1BNB52 100.00 0.033 -0.079 2.4 0.085
1BMB20 1BMA52 86.37 0.137 -0.159 1.2 0.210
1BMB52 1BMA52 86.31 0.060 -0.065 1.1 0.088
1BJA12 1BFA53 86.39 0.259 -0.280 1.1 0.381
Bus19 1BFA53 88.88 1.310 -2.672 2.0 2.976
1BJA80 1BFA53 95.00 0.052 -0.056 1.1 0.077
PCI_BUS 1BFA51 86.69 0.107 -0.160 1.5 0.192
1BJA11 1BFA51 86.42 0.325 -0.362 1.1 0.487
1BJA51 1BFA51 86.32 0.177 -0.193 1.1 0.262
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
0.831 0.01 5.644 5.705
0.091 0.02 5.644 5.644
0.010 0.03 5.644 5.644
0.001 0.04 5.644 5.644
0.000 0.05 5.644 5.644
0.000 0.06 5.644 5.644
0.000 0.07 5.644 5.644
0.000 0.08 5.644 5.644
0.000 0.09 5.644 5.644
0.000 0.10 5.644 5.644
0.000 0.15 5.644 5.644
0.000 0.20 5.644 5.644
0.000 0.25 5.644 5.644
0.000 0.30 5.644 5.644
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 17
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: Bus EX
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
81.675
34.912
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
Bus EX Total 0.00 5.513 -34.947 6.3 35.380
Bus20 Bus EX 91.39 5.513 -34.947 6.3 35.380
1BBA51 Bus20 91.69 0.376 -2.383 6.3 2.412
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
27.787 0.01 35.380 44.987
15.550 0.02 35.380 38.646
8.669 0.03 35.380 36.426
4.833 0.04 35.380 35.708
2.725 0.05 35.380 35.484
1.523 0.06 35.380 35.412
0.851 0.07 35.380 35.390
0.475 0.08 35.380 35.383
0.270 0.09 35.380 35.381
0.151 0.10 35.380 35.380
0.008 0.15 35.380 35.380
0.000 0.20 35.380 35.380
0.000 0.25 35.380 35.380
0.000 0.30 35.380 35.380
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 18
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: BUS GEN
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
18.000
1.10
281.154
63.797
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
BUS GEN Total 0.00 3.765 -104.513 27.8 104.581
S.E. Etén BUS GEN 50.48 3.186 -44.417 13.9 44.531
Bus22 BUS GEN 49.93 0.143 -1.621 11.4 1.628
1MKA10 BUS GEN 100.00 0.436 -58.475 134.0 58.476
S.E. Reque S.E. Etén 54.18 0.261 -3.634 13.9 3.643
1BBA51 Bus22 52.31 0.382 -4.335 11.4 4.352
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
129.681 0.01 99.810 163.644
115.607 0.02 97.992 151.550
102.210 0.03 96.037 140.250
90.365 0.04 93.962 130.364
86.069 0.05 91.781 125.823
77.236 0.06 90.956 119.325
69.310 0.07 90.114 113.686
62.198 0.08 89.258 108.791
69.618 0.09 88.394 112.517
64.027 0.10 87.511 108.433
42.127 0.15 86.158 95.905
27.718 0.20 84.766 89.183
18.237 0.25 83.348 85.320
11.999 0.30 81.917 82.791
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 19
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: S.E. Etén
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
220.000
1.10
25.637
10.247
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
S.E. Etén Total 0.00 0.935 -10.209 10.9 10.251
S.E. Reque S.E. Etén 7.47 0.892 -7.284 8.2 7.339
BUS GEN S.E. Etén 40.52 0.043 -2.925 67.9 2.925
Red eléctrica Peruana S.E. Reque 100.00 0.892 -7.284 8.2 7.339
Bus22 BUS GEN 69.22 0.090 -0.964 10.7 0.968
1MKA10 BUS GEN 100.00 0.437 -34.780 79.6 34.783
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
10.418 0.01 10.169 14.558
7.946 0.02 10.142 12.884
5.882 0.03 10.110 11.696
4.355 0.04 10.073 10.974
4.139 0.05 10.032 10.852
3.221 0.06 10.019 10.524
2.507 0.07 10.006 10.315
1.951 0.08 9.992 10.181
2.870 0.09 9.978 10.382
2.397 0.10 9.963 10.247
0.975 0.15 9.936 9.984
0.396 0.20 9.907 9.914
0.161 0.25 9.874 9.875
0.066 0.30 9.839 9.840
Ubicación:
Ingeniero:Caso de Estudio: SC-1
12.0.0C
Página: 20
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: S.E. Reque
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
220.000
1.10
26.744
10.755
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
S.E. Reque Total 0.00 1.032 -10.710 10.4 10.759
S.E. Etén S.E. Reque 2.89 0.048 -2.840 59.1 2.840
Red eléctrica Peruana S.E. Reque 100.00 0.984 -7.869 8.0 7.931
BUS GEN S.E. Etén 42.24 0.048 -2.840 59.1 2.840
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
10.738 0.01 10.685 15.148
8.042 0.02 10.660 13.353
5.846 0.03 10.631 12.133
4.250 0.04 10.598 11.419
3.970 0.05 10.561 11.283
3.035 0.06 10.550 10.978
2.320 0.07 10.538 10.790
1.773 0.08 10.526 10.674
2.584 0.09 10.513 10.826
2.122 0.10 10.499 10.712
0.792 0.15 10.475 10.505
0.296 0.20 10.448 10.452
0.111 0.25 10.418 10.419
0.041 0.30 10.386 10.387
One-Line Diagram - OLV1 (Short-Circuit Analysis)
page 1 10:02:18 may 02, 2014 Project File: Eten
RESERVA FRÍA ETEN
ESTUDIO DE CORTOCIRCUITO: CASO SC-2 (REV C)
CONDICIONES:-> TENSIÓN DE RED: 220 kV-> GENERADOR PRINCIPAL OPERANDO-> GENERADOR AUXILIAR PARADO-> GENERADOR EMERGENCIA OPERANDO-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIÓN EN AUTO.-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIÓN EN TOMA CENTRAL.-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN ÚNICO TRAFO MT/BT.
1BFA51
0,48 kV62,4 kA
1BBA51
6,6 kV
10,1 kA
1BFA53
0,48 kV62,4 kA
1BMA52
0,48 kV62,4 kA
1BNB52
0,38 kV5,8 kA
CGDE
0,48 kV
58,0 kA
1BBA76
6,6 kV 10,0 kA
1BJA76
0,48 kV
15,7 kA
BUS GEN
18 kV
103,6 kA
S.E. Etén
220 kV10,2 kA
S.E. Reque
220 kV10,7 kA
Sistema PCI
200 kW
Red eléctrica Peruana
3022 MVAsc
220 kV
7,93
Narcissus
AL 2,92 km
2,9
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
44,53
1MKA10
225 MW
18 kV
17 %Xd"
9021 A
Isolated Phase CU
35 m
Isolated Phase CU
35 m
58,48 ,619
Isolated Phase CU
8 m
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
4-3/C 240
CU 40 m
1MKA76
8,44 MW
6,6 kV
16 %Xd"
922,9 A
3-3/C 300
CU 20 m
CARGAS 1BJA76
270 kVA
1,23
14,46
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1-3/C 300
CU 20 m
3-3/C 300
CU 120 m
Excitación 1MKC10
944 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1-3/C 150
CU 40 m
LCI 1BPA10_1
2725 kVA
LCI 1BPA10_2
2725 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
3-3/C 240
CU 40 m
Open
88WN-1
224 kW
1-3/C 70
CU 50 m
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
88WN-2
224 kW
1-3/C 70
CU 50 m
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
Open
88AK-1
375 kW
1-3/C 70
CU 50 m
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
88AK-2
375 kW
1-3/C 70
CU 50 m
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
Open
52,56
W-1BMB20
1XKA52
2000 kW
0,48 kV
3007 A
17,61
6-3/C 300
CU 50 m
CARGAS 1BNB52
82,2 kVA
,085
5,67
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
,074
W-1BMB52
32,56
MBN50 AH010
450 kVA
1BJA80
400 kVA
,821
W-1BJA12
27,83
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
2-3/C 185
CU 40 m 2-3/C 185
CU 40 m
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
Open
W-1BJA51W-1BJA11
2-3/C 240
CU 115 m
Excitación 1MKC10
944 kVA
LCI 1BPA10_1
2725 kVA
MBN50 AH010
450 kVA
CARGAS 1BNB52
82,2 kVA
W-1BJA51W-1BMB20W-1BJA12W-1BJA11W-1BMB52
1BJA80
400 kVA
CARGAS 1BJA76
270 kVA
LCI 1BPA10_2
2725 kVA
Open
Red eléctrica Peruana
3022 MVAsc
220 kV
1MKA10
225 MW
18 kV
17 %Xd"
9021 A
1MKA76
8,44 MW
6,6 kV
16 %Xd"
922,9 A
1XKA52
2000 kW
0,48 kV
3007 A
Narcissus
AL 2,92 km
6-3/C 300
CU 50 m
3-3/C 300
CU 120 m
3-3/C 300
CU 20 m1-3/C 300
CU 20 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 100 m
1-3/C 70
CU 70 m
1-3/C 70
CU 70 m
2-3/C 185
CU 40 m
2-3/C 185
CU 40 m
1-3/C 150
CU 40 m
3-3/C 240
CU 40 m
4-3/C 240
CU 40 m
1-3/C 70
CU 100 m
1-3/C 70
CU 50 m
2-3/C 240
CU 115 m
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
1BBA51
6,6 kV
1BFA53
0,48 kV
1BFA51
0,48 kV
S.E. Etén
220 kV
BUS GEN
18 kV
1BMA52
0,48 kV
CGDE
0,48 kV 1BNB52
0,38 kV
S.E. Reque
220 kV
1BBA76
6,6 kV
1BJA76
0,48 kV
Sistema PCI
200 kW
88WN-1
224 kW
88AK-1
375 kW
88WN-2
224 kW
88AK-2
375 kW
,092
9,89
,092
,1531,54
8,07
,233
2,065,214,08 2,812,24,94416,86
40,62
2,81
7,34
10,0629,88
15,7 kA
10,0 kA
10,7 kA
5,8 kA
58,0 kA
62,4 kA
103,6 kA
10,2 kA
62,4 kA62,4 kA
10,1 kA
Isolated Phase CU
35 m
Isolated Phase CU
35 m
Isolated Phase CU
8 m
8,07
,092
Open
29,88
Open
2,9
44,53
58,48
10,062,24
27,83
,153
Open
,233
Open
2,81
5,67
,085
7,93
7,34
,619
2,81
,821
1,54
32,56 52,5616,864,08 5,21 2,06,074,944
Open
,092
14,46
1,23
9,89
17,61
40,62
One-Line Diagram - OLV1 (Short-Circuit Analysis)
page 2 10:02:18 may 02, 2014 Project File: Eten
1BJA11
0,48 kV54,7 kA
1BJA12
0,48 kV54,4 kA
1BMB52
0,48 kV50,7 kA
1BJA51
0,48 kV57,1 kA
1BMB20
0,48 kV50,2 kA
CARGAS 1BMB20
235 kVA
1,45
1MBV10AP001-M01
75 kW
,82
1BMA52
4-3/C 240
CU 50 m
Compresor 1
37 kW
,153
CARGAS 1BJA51
650 kVA
2,67
1BFA51
4-3/C 240
CU 20 m
1BMA52
2-3/C 150
CU 20 m
Compresor 2
37 kW
Open
CARGAS 1BMB52
231 kVA
,948
CARGAS 1BJA12
592 kVA
4,13
6-3/C 240
CU 50 m
1BFA53
CARGAS 1BJA11
695 kVA
4,48
1MBV10AP002-M1
75 kW
,82
6-3/C 240
CU 50 m
1BFA51
CARGAS 1BMB20
235 kVA
CARGAS 1BMB52
231 kVA
1BFA51
1BMA52 1BFA53 1BFA51
1BMA52
CARGAS 1BJA11
695 kVA
CARGAS 1BJA12
592 kVA
CARGAS 1BJA51
650 kVA
4-3/C 240
CU 50 m
6-3/C 240
CU 50 m
6-3/C 240
CU 50 m
4-3/C 240
CU 20 m
2-3/C 150
CU 20 m
1BMB52
0,48 kV1BJA51
0,48 kV
1BMB20
0,48 kV
1BJA12
0,48 kV
1BJA11
0,48 kV
Compresor 1
37 kW
Compresor 2
37 kW
1MBV10AP001-M01
75 kW
1MBV10AP002-M1
75 kW
49,4550,26
54,3
47,97
49,7
50,2 kA
57,1 kA50,7 kA 49,7
Open
,948
1,45 ,82
54,4 kA54,7 kA
,153
4,484,13
2,67
54,3
47,97 50,26 49,45
,82
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 1
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Cortocircuito
Falta trifásica en barra: 1BBA51
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
6.600
1.10
24.995
9.060
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BBA51 Total 0.00 1.034 -10.019 9.7 10.072
1BBA76 1BBA51 0.01 0.037 -0.084 2.3 0.092
Bus17 1BBA51 0.07 0.041 -0.147 3.6 0.153
Bus18 1BBA51 0.00 0.000 0.000 999.9 0.000
Bus19 1BBA51 0.10 0.273 -1.515 5.5 1.539
Bus20 1BBA51 0.00 0.000 0.000 999.9 0.000
Bus22 1BBA51 0.23 0.619 -8.048 13.0 8.072
Bus15 1BBA51 0.15 0.064 -0.224 3.5 0.233
Bus9 1BBA76 0.02 0.037 -0.084 2.3 0.092
Bus10 Bus17 14.61 0.041 -0.147 3.6 0.153
1BFA53 Bus19 50.03 0.273 -1.515 5.5 1.539
Bus EX Bus20 0.00 0.000 0.000 999.9 0.000
BUS GEN Bus22 95.11 0.619 -8.048 13.0 8.072
Bus13 Bus15 23.23 0.064 -0.224 3.5 0.233
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
10.101 0.01 9.985 14.203
7.505 0.02 9.924 12.443
5.448 0.03 9.862 11.267
3.955 0.04 9.799 10.567
3.043 0.05 9.737 10.202
2.235 0.06 9.709 9.962
1.642 0.07 9.680 9.818
1.206 0.08 9.675 9.750
0.941 0.09 9.660 9.706
0.696 0.10 9.635 9.660
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 2
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
(Cont.)
Falta trifásica en barra: 1BBA51
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
6.600
1.10
24.995
9.060
(Definido por el Usuario)
kA Método C
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
0.154 0.15 9.585 9.586
0.034 0.20 9.536 9.536
0.008 0.25 9.488 9.488
0.002 0.30 9.481 9.481
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 3
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BBA76
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
6.600
1.10
24.610
8.979
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BBA76 Total 0.00 1.069 -9.916 9.3 9.973
1BBA51 1BBA76 1.09 1.032 -9.832 9.5 9.886
Bus9 1BBA76 0.01 0.037 -0.084 2.3 0.092
Bus17 1BBA51 1.15 0.042 -0.146 3.5 0.151
Bus18 1BBA51 1.09 0.000 0.000 999.9 0.000
Bus19 1BBA51 1.19 0.277 -1.499 5.4 1.524
Bus20 1BBA51 1.09 0.000 0.000 999.9 0.000
Bus22 1BBA51 1.27 0.649 -7.966 12.3 7.992
Bus15 1BBA51 1.23 0.065 -0.222 3.4 0.231
1BJA76 Bus9 7.25 0.037 -0.084 2.3 0.092
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
9.832 0.01 9.889 13.945
7.183 0.02 9.829 12.174
5.126 0.03 9.768 11.031
3.659 0.04 9.707 10.373
2.769 0.05 9.646 10.036
1.999 0.06 9.618 9.824
1.444 0.07 9.590 9.698
1.042 0.08 9.595 9.652
0.801 0.09 9.570 9.604
0.582 0.10 9.546 9.564
0.118 0.15 9.497 9.498
0.024 0.20 9.449 9.449
0.005 0.25 9.402 9.402
0.001 0.30 9.395 9.395
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 4
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BFA51
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
144.677
44.263
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BFA51 Total 0.00 11.068 -61.428 5.6 62.417
PCI_BUS 1BFA51 4.52 0.504 -1.997 4.0 2.060
1BJA11 1BFA51 1.66 1.970 -4.823 2.4 5.210
1BJA51 1BFA51 0.53 1.089 -2.586 2.4 2.806
1BMB20 1BMA52 1.07 0.802 -2.095 2.6 2.243
1BMB52 1BMA52 0.47 0.368 -0.870 2.4 0.944
CGDE 1BMA52 4.93 1.327 -16.812 12.7 16.864
1BNB52 1BMA52 1.45 0.029 -0.068 2.4 0.074
1BJA12 1BFA53 1.30 1.595 -3.755 2.4 4.080
Bus19 1BFA53 68.80 3.065 -27.665 9.0 27.834
1BJA80 1BFA53 100.00 0.318 -0.757 2.4 0.821
Sistema PCI PCI_BUS 100.00 0.504 -1.997 4.0 2.060
1MBV10AP002-M1 1BJA11 104.35 0.242 -0.770 3.2 0.807
CARGAS 1BJA11 1BJA11 100.00 1.728 -4.053 2.3 4.406
Compresor 1 1BJA51 100.00 0.057 -0.141 2.5 0.152
CARGAS 1BJA51 1BJA51 100.00 1.032 -2.445 2.4 2.654
1MBV10AP001-M01 1BMB20 104.35 0.242 -0.775 3.2 0.812
CARGAS 1BMB20 1BMB20 100.00 0.560 -1.320 2.4 1.434
CARGAS 1BMB52 1BMB52 100.00 0.368 -0.870 2.4 0.944
1XKA52 CGDE 100.00 1.327 -16.812 12.7 16.864
CARGAS 1BNB52 1BNB52 105.26 0.035 -0.082 2.4 0.089
CARGAS 1BJA12 1BJA12 100.00 1.595 -3.755 2.4 4.080
1BBA51 Bus19 68.92 0.235 -2.117 9.0 2.130
1BMA52 1BFA51 0.00 7.504 -52.022 6.9 52.560
1BFA53 1BMA52 0.00 4.978 -32.177 6.5 32.560
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
52.702 0.01 59.457 79.453
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 5
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
(Cont.)
Falta trifásica en barra: 1BFA51
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
144.677
44.263
(Definido por el Usuario)
kA Método C
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
36.466 0.02 58.048 68.551
23.438 0.03 56.471 61.141
15.064 0.04 54.903 56.932
11.531 0.05 53.357 54.589
7.675 0.06 52.670 53.227
5.109 0.07 51.992 52.242
3.400 0.08 51.323 51.435
2.678 0.09 50.663 50.733
1.816 0.10 50.012 50.045
0.261 0.15 48.811 48.812
0.037 0.20 47.647 47.647
0.005 0.25 46.526 46.526
0.001 0.30 46.141 46.141
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 6
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BFA53
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
144.677
44.263
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BFA53 Total 0.00 11.068 -61.428 5.6 62.417
1BJA12 1BFA53 1.30 1.595 -3.755 2.4 4.080
Bus19 1BFA53 68.80 3.065 -27.665 9.0 27.834
1BJA80 1BFA53 100.00 0.318 -0.757 2.4 0.821
1BMB20 1BMA52 1.07 0.802 -2.095 2.6 2.243
1BMB52 1BMA52 0.47 0.368 -0.870 2.4 0.944
CGDE 1BMA52 4.93 1.327 -16.812 12.7 16.864
1BNB52 1BMA52 1.45 0.029 -0.068 2.4 0.074
PCI_BUS 1BFA51 4.52 0.504 -1.997 4.0 2.060
1BJA11 1BFA51 1.66 1.970 -4.823 2.4 5.210
1BJA51 1BFA51 0.53 1.089 -2.586 2.4 2.806
CARGAS 1BJA12 1BJA12 100.00 1.595 -3.755 2.4 4.080
1BBA51 Bus19 68.92 0.235 -2.117 9.0 2.130
1MBV10AP001-M01 1BMB20 104.35 0.242 -0.775 3.2 0.812
CARGAS 1BMB20 1BMB20 100.00 0.560 -1.320 2.4 1.434
CARGAS 1BMB52 1BMB52 100.00 0.368 -0.870 2.4 0.944
1XKA52 CGDE 100.00 1.327 -16.812 12.7 16.864
CARGAS 1BNB52 1BNB52 105.26 0.035 -0.082 2.4 0.089
Sistema PCI PCI_BUS 100.00 0.504 -1.997 4.0 2.060
1MBV10AP002-M1 1BJA11 104.35 0.242 -0.770 3.2 0.807
CARGAS 1BJA11 1BJA11 100.00 1.728 -4.053 2.3 4.406
Compresor 1 1BJA51 100.00 0.057 -0.141 2.5 0.152
CARGAS 1BJA51 1BJA51 100.00 1.032 -2.445 2.4 2.654
1BFA51 1BMA52 0.00 3.563 -9.407 2.6 10.059
1BMA52 1BFA53 0.00 6.089 -29.251 4.8 29.878
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
52.702 0.01 59.457 79.453
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 7
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
(Cont.)
Falta trifásica en barra: 1BFA53
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
144.677
44.263
(Definido por el Usuario)
kA Método C
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
36.466 0.02 58.048 68.551
23.438 0.03 56.471 61.141
15.064 0.04 54.903 56.932
11.531 0.05 53.357 54.589
7.675 0.06 52.670 53.227
5.109 0.07 51.992 52.242
3.400 0.08 51.323 51.435
2.678 0.09 50.663 50.733
1.816 0.10 50.012 50.045
0.261 0.15 48.811 48.812
0.037 0.20 47.647 47.647
0.005 0.25 46.526 46.526
0.001 0.30 46.141 46.141
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 8
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BJA11
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
116.227
39.589
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BJA11 Total 0.00 13.795 -52.929 3.8 54.697
1BFA51 1BJA11 15.71 11.820 -48.018 4.1 49.452
1MBV10AP002-M1 1BJA11 104.35 0.242 -0.784 3.2 0.820
CARGAS 1BJA11 1BJA11 100.00 1.734 -4.127 2.4 4.477
PCI_BUS 1BFA51 19.59 0.575 -1.681 2.9 1.777
1BJA51 1BFA51 16.16 1.119 -2.146 1.9 2.421
1BMB20 1BMA52 16.62 0.838 -1.744 2.1 1.935
1BMB52 1BMA52 16.11 0.378 -0.722 1.9 0.815
CGDE 1BMA52 19.97 2.328 -14.359 6.2 14.546
1BNB52 1BMA52 17.71 0.030 -0.056 1.9 0.064
1BJA12 1BFA53 16.80 1.637 -3.115 1.9 3.519
Bus19 1BFA53 72.55 4.589 -23.566 5.1 24.009
1BJA80 1BFA53 100.00 0.327 -0.628 1.9 0.708
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
33.621 0.01 52.636 62.457
16.815 0.02 51.505 54.180
7.840 0.03 50.305 50.913
3.655 0.04 49.111 49.247
2.027 0.05 47.931 47.974
0.978 0.06 47.406 47.416
0.472 0.07 46.887 46.889
0.228 0.08 46.374 46.375
0.131 0.09 45.869 45.869
0.064 0.10 45.370 45.370
0.002 0.15 44.425 44.425
0.000 0.20 43.505 43.505
0.000 0.25 42.617 42.617
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 9
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
(Cont.)
Falta trifásica en barra: 1BJA11
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
116.227
39.589
(Definido por el Usuario)
kA Método C
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
0.000 0.30 42.342 42.342
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 10
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BJA12
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
115.299
39.589
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BJA12 Total 0.00 13.824 -52.563 3.8 54.350
1BFA53 1BJA12 15.97 12.224 -48.754 4.0 50.264
CARGAS 1BJA12 1BJA12 100.00 1.600 -3.808 2.4 4.131
Bus19 1BFA53 72.62 4.596 -23.492 5.1 23.938
1BJA80 1BFA53 100.00 0.326 -0.626 1.9 0.706
1BMB20 1BMA52 16.87 0.837 -1.738 2.1 1.929
1BMB52 1BMA52 16.37 0.377 -0.719 1.9 0.812
CGDE 1BMA52 20.21 2.334 -14.314 6.1 14.503
1BNB52 1BMA52 17.98 0.029 -0.056 1.9 0.063
PCI_BUS 1BFA51 19.84 0.574 -1.676 2.9 1.771
1BJA11 1BFA51 17.36 2.032 -3.993 2.0 4.481
1BJA51 1BFA51 16.42 1.118 -2.139 1.9 2.413
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
33.249 0.01 52.389 62.049
16.626 0.02 51.275 53.904
7.733 0.03 50.113 50.706
3.596 0.04 48.955 49.087
2.000 0.05 47.809 47.851
0.964 0.06 47.301 47.311
0.465 0.07 46.798 46.800
0.224 0.08 46.300 46.301
0.129 0.09 45.809 45.810
0.064 0.10 45.325 45.325
0.002 0.15 44.407 44.407
0.000 0.20 43.513 43.513
0.000 0.25 42.648 42.648
0.000 0.30 42.375 42.375
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 11
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BJA51
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
124.789
41.360
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BJA51 Total 0.00 13.004 -55.576 4.3 57.077
1BFA51 1BJA51 10.35 11.913 -52.975 4.4 54.298
Compresor 1 1BJA51 100.00 0.057 -0.142 2.5 0.153
CARGAS 1BJA51 1BJA51 100.00 1.033 -2.460 2.4 2.668
PCI_BUS 1BFA51 14.45 0.555 -1.790 3.2 1.874
1BJA11 1BFA51 11.83 2.023 -4.287 2.1 4.740
1BMB20 1BMA52 11.31 0.830 -1.864 2.2 2.041
1BMB52 1BMA52 10.77 0.376 -0.772 2.1 0.859
CGDE 1BMA52 14.84 2.019 -15.209 7.5 15.343
1BNB52 1BMA52 12.14 0.029 -0.060 2.1 0.067
1BJA12 1BFA53 11.50 1.631 -3.334 2.0 3.712
Bus19 1BFA53 71.24 4.124 -24.985 6.1 25.323
1BJA80 1BFA53 100.00 0.326 -0.672 2.1 0.747
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
39.264 0.01 54.829 67.438
22.176 0.02 53.614 58.019
11.624 0.03 52.343 53.618
6.092 0.04 51.075 51.437
3.828 0.05 49.820 49.967
2.080 0.06 49.263 49.307
1.131 0.07 48.711 48.724
0.614 0.08 48.166 48.170
0.399 0.09 47.627 47.629
0.221 0.10 47.096 47.097
0.012 0.15 46.097 46.097
0.001 0.20 45.124 45.124
0.000 0.25 44.183 44.183
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 12
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
(Cont.)
Falta trifásica en barra: 1BJA51
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
124.789
41.360
(Definido por el Usuario)
kA Método C
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
0.000 0.30 43.874 43.874
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 13
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BJA76
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
26.532
14.320
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BJA76 Total 0.00 7.826 -13.581 1.7 15.674
Bus9 1BJA76 87.09 7.351 -12.449 1.7 14.457
CARGAS 1BJA76 1BJA76 100.00 0.476 -1.132 2.4 1.228
1BBA76 Bus9 87.15 0.549 -0.929 1.7 1.079
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
2.609 0.01 15.498 15.716
0.315 0.02 15.406 15.410
0.038 0.03 15.315 15.315
0.004 0.04 15.225 15.225
0.001 0.05 15.136 15.136
0.000 0.06 15.093 15.093
0.000 0.07 15.050 15.050
0.000 0.08 15.007 15.007
0.000 0.09 14.965 14.965
0.000 0.10 14.923 14.923
0.000 0.15 14.842 14.842
0.000 0.20 14.762 14.762
0.000 0.25 14.686 14.686
0.000 0.30 14.685 14.685
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 14
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BMA52
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
144.677
44.263
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BMA52 Total 0.00 11.068 -61.428 5.6 62.417
1BMB20 1BMA52 1.07 0.802 -2.095 2.6 2.243
1BMB52 1BMA52 0.47 0.368 -0.870 2.4 0.944
CGDE 1BMA52 4.93 1.327 -16.812 12.7 16.864
1BNB52 1BMA52 1.45 0.029 -0.068 2.4 0.074
1BJA12 1BFA53 1.30 1.595 -3.755 2.4 4.080
Bus19 1BFA53 68.80 3.065 -27.665 9.0 27.834
1BJA80 1BFA53 100.00 0.318 -0.757 2.4 0.821
PCI_BUS 1BFA51 4.52 0.504 -1.997 4.0 2.060
1BJA11 1BFA51 1.66 1.970 -4.823 2.4 5.210
1BJA51 1BFA51 0.53 1.089 -2.586 2.4 2.806
1MBV10AP001-M01 1BMB20 104.35 0.242 -0.775 3.2 0.812
CARGAS 1BMB20 1BMB20 100.00 0.560 -1.320 2.4 1.434
CARGAS 1BMB52 1BMB52 100.00 0.368 -0.870 2.4 0.944
1XKA52 CGDE 100.00 1.327 -16.812 12.7 16.864
CARGAS 1BNB52 1BNB52 105.26 0.035 -0.082 2.4 0.089
CARGAS 1BJA12 1BJA12 100.00 1.595 -3.755 2.4 4.080
1BBA51 Bus19 68.92 0.235 -2.117 9.0 2.130
Sistema PCI PCI_BUS 100.00 0.504 -1.997 4.0 2.060
1MBV10AP002-M1 1BJA11 104.35 0.242 -0.770 3.2 0.807
CARGAS 1BJA11 1BJA11 100.00 1.728 -4.053 2.3 4.406
Compresor 1 1BJA51 100.00 0.057 -0.141 2.5 0.152
CARGAS 1BJA51 1BJA51 100.00 1.032 -2.445 2.4 2.654
1BFA51 1BMA52 0.00 3.563 -9.407 2.6 10.059
1BFA53 1BMA52 0.00 4.978 -32.177 6.5 32.560
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
52.702 0.01 59.457 79.453
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 15
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
(Cont.)
Falta trifásica en barra: 1BMA52
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
144.677
44.263
(Definido por el Usuario)
kA Método C
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
36.466 0.02 58.048 68.551
23.438 0.03 56.471 61.141
15.064 0.04 54.903 56.932
11.531 0.05 53.357 54.589
7.675 0.06 52.670 53.227
5.109 0.07 51.992 52.242
3.400 0.08 51.323 51.435
2.678 0.09 50.663 50.733
1.816 0.10 50.012 50.045
0.261 0.15 48.811 48.812
0.037 0.20 47.647 47.647
0.005 0.25 46.526 46.526
0.001 0.30 46.141 46.141
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 16
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BMB20
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
103.029
37.545
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BMB20 Total 0.00 14.447 -48.108 3.3 50.230
1BMA52 1BMB20 22.86 13.644 -45.989 3.4 47.970
1MBV10AP001-M01 1BMB20 104.35 0.242 -0.784 3.2 0.820
CARGAS 1BMB20 1BMB20 100.00 0.561 -1.336 2.4 1.449
1BMB52 1BMA52 23.23 0.372 -0.654 1.8 0.752
CGDE 1BMA52 26.79 2.615 -13.178 5.0 13.435
1BNB52 1BMA52 25.15 0.029 -0.051 1.8 0.059
1BJA12 1BFA53 23.87 1.612 -2.822 1.8 3.250
Bus19 1BFA53 74.38 5.000 -21.603 4.3 22.174
1BJA80 1BFA53 100.00 0.322 -0.569 1.8 0.654
PCI_BUS 1BFA51 26.45 0.585 -1.533 2.6 1.641
1BJA11 1BFA51 24.15 2.008 -3.633 1.8 4.151
1BJA51 1BFA51 23.28 1.102 -1.945 1.8 2.236
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
26.828 0.01 48.529 55.451
11.746 0.02 47.642 49.068
4.776 0.03 46.710 46.954
1.942 0.04 45.777 45.818
0.948 0.05 44.849 44.859
0.400 0.06 44.439 44.440
0.169 0.07 44.031 44.031
0.071 0.08 43.628 43.628
0.036 0.09 43.228 43.228
0.016 0.10 42.834 42.834
0.000 0.15 42.081 42.081
0.000 0.20 41.343 41.343
0.000 0.25 40.626 40.626
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 17
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
(Cont.)
Falta trifásica en barra: 1BMB20
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
103.029
37.545
(Definido por el Usuario)
kA Método C
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
0.000 0.30 40.405 40.405
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 18
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BMB52
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
99.126
38.255
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BMB52 Total 0.00 17.173 -47.650 2.8 50.651
1BMA52 1BMB52 24.51 16.806 -46.776 2.8 49.704
CARGAS 1BMB52 1BMB52 100.00 0.367 -0.874 2.4 0.948
1BMB20 1BMA52 25.30 0.926 -1.559 1.7 1.813
CGDE 1BMA52 28.41 3.356 -13.211 3.9 13.630
1BNB52 1BMA52 26.79 0.032 -0.050 1.6 0.060
1BJA12 1BFA53 25.46 1.784 -2.773 1.6 3.297
Bus19 1BFA53 74.31 6.226 -21.618 3.5 22.497
1BJA80 1BFA53 100.00 0.357 -0.559 1.6 0.663
PCI_BUS 1BFA51 28.02 0.675 -1.522 2.3 1.665
1BJA11 1BFA51 25.73 2.229 -3.573 1.6 4.211
1BJA51 1BFA51 24.90 1.221 -1.911 1.6 2.268
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
22.123 0.01 49.063 53.820
8.124 0.02 48.226 48.905
2.736 0.03 47.344 47.422
0.921 0.04 46.458 46.467
0.385 0.05 45.576 45.578
0.135 0.06 45.188 45.189
0.048 0.07 44.803 44.803
0.017 0.08 44.422 44.422
0.007 0.09 44.044 44.044
0.003 0.10 43.671 43.671
0.000 0.15 42.960 42.960
0.000 0.20 42.262 42.262
0.000 0.25 41.584 41.584
0.000 0.30 41.360 41.360
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 19
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: 1BNB52
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.380
1.05
9.572
5.523
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
1BNB52 Total 0.00 3.027 -4.895 1.6 5.755
1BMA52 1BNB52 88.00 2.994 -4.816 1.6 5.671
CARGAS 1BNB52 1BNB52 100.00 0.033 -0.079 2.4 0.085
1BMB20 1BMA52 88.08 0.115 -0.125 1.1 0.170
1BMB52 1BMA52 88.04 0.050 -0.051 1.0 0.072
CGDE 1BMA52 88.37 0.564 -1.147 2.0 1.278
1BJA12 1BFA53 88.10 0.217 -0.220 1.0 0.309
Bus19 1BFA53 88.46 0.990 -1.863 1.9 2.110
1BJA80 1BFA53 95.00 0.044 -0.044 1.0 0.062
PCI_BUS 1BFA51 88.34 0.091 -0.127 1.4 0.156
1BJA11 1BFA51 88.13 0.274 -0.285 1.0 0.395
1BJA51 1BFA51 88.04 0.149 -0.152 1.0 0.213
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
0.821 0.01 5.755 5.813
0.086 0.02 5.755 5.756
0.009 0.03 5.755 5.755
0.001 0.04 5.755 5.755
0.000 0.05 5.755 5.755
0.000 0.06 5.755 5.755
0.000 0.07 5.755 5.755
0.000 0.08 5.755 5.755
0.000 0.09 5.755 5.755
0.000 0.10 5.755 5.755
0.000 0.15 5.755 5.755
0.000 0.20 5.755 5.755
0.000 0.25 5.755 5.755
0.000 0.30 5.755 5.755
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 20
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: Bus EX
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
74.926
31.580
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
Bus EX Total 0.00 4.951 -31.945 6.5 32.327
Bus20 Bus EX 83.50 4.951 -31.945 6.5 32.327
1BBA51 Bus20 83.78 0.338 -2.178 6.5 2.204
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
25.779 0.01 32.327 41.347
14.715 0.02 32.327 35.518
8.349 0.03 32.327 33.387
4.737 0.04 32.327 32.672
2.730 0.05 32.327 32.442
1.554 0.06 32.327 32.364
0.885 0.07 32.327 32.339
0.503 0.08 32.327 32.330
0.292 0.09 32.327 32.328
0.166 0.10 32.327 32.327
0.010 0.15 32.327 32.327
0.001 0.20 32.327 32.327
0.000 0.25 32.327 32.327
0.000 0.30 32.327 32.327
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 21
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: BUS GEN
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
18.000
1.10
278.448
63.353
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
BUS GEN Total 0.00 3.735 -103.501 27.7 103.568
S.E. Etén BUS GEN 50.48 3.186 -44.417 13.9 44.531
Bus22 BUS GEN 19.00 0.112 -0.609 5.4 0.619
1MKA10 BUS GEN 100.00 0.436 -58.475 134.0 58.476
S.E. Reque S.E. Etén 54.18 0.261 -3.634 13.9 3.643
1BBA51 Bus22 19.90 0.300 -1.628 5.4 1.656
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
128.482 0.01 98.818 162.088
114.676 0.02 97.002 150.200
101.470 0.03 95.050 139.035
89.785 0.04 92.980 129.254
85.670 0.05 90.808 124.841
76.956 0.06 89.982 118.402
69.129 0.07 89.142 112.806
62.098 0.08 88.288 107.939
69.553 0.09 87.420 111.714
64.029 0.10 86.539 107.651
42.335 0.15 85.188 95.127
27.991 0.20 83.799 88.351
18.507 0.25 82.386 84.439
12.236 0.30 80.967 81.886
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 22
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: CGDE
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
0.480
1.05
132.146
43.154
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
CGDE Total 0.00 11.402 -56.823 5.0 57.956
1BMA52 CGDE 11.88 10.477 -39.241 3.7 40.616
1XKA52 CGDE 100.00 0.925 -17.582 19.0 17.606
1BMB20 1BMA52 12.83 0.798 -1.828 2.3 1.995
1BMB52 1BMA52 12.29 0.362 -0.758 2.1 0.840
1BNB52 1BMA52 13.77 0.028 -0.059 2.1 0.066
1BJA12 1BFA53 13.03 1.571 -3.271 2.1 3.629
Bus19 1BFA53 71.76 3.854 -24.454 6.3 24.755
1BJA80 1BFA53 100.00 0.313 -0.659 2.1 0.730
PCI_BUS 1BFA51 15.89 0.530 -1.754 3.3 1.832
1BJA11 1BFA51 13.35 1.947 -4.205 2.2 4.634
1BJA51 1BFA51 12.35 1.073 -2.253 2.1 2.496
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
47.136 0.01 55.457 72.782
33.898 0.02 54.181 63.911
21.800 0.03 52.841 57.161
14.019 0.04 51.491 53.365
13.017 0.05 50.143 51.805
9.009 0.06 49.554 50.366
6.236 0.07 48.969 49.364
4.316 0.08 48.388 48.580
4.803 0.09 47.811 48.052
3.505 0.10 47.240 47.369
0.725 0.15 46.199 46.205
0.150 0.20 45.180 45.181
0.031 0.25 44.189 44.189
0.006 0.30 43.774 43.774
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 23
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: S.E. Etén
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
220.000
1.10
25.559
10.214
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
S.E. Etén Total 0.00 0.934 -10.179 10.9 10.222
S.E. Reque S.E. Etén 7.47 0.892 -7.284 8.2 7.339
BUS GEN S.E. Etén 40.11 0.042 -2.895 69.1 2.895
Red eléctrica Peruana S.E. Reque 100.00 0.892 -7.284 8.2 7.339
Bus22 BUS GEN 50.45 0.069 -0.364 5.3 0.371
1MKA10 BUS GEN 100.00 0.443 -35.019 79.1 35.022
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
10.384 0.01 10.138 14.512
7.920 0.02 10.110 12.843
5.862 0.03 10.077 11.658
4.339 0.04 10.039 10.937
4.129 0.05 9.997 10.816
3.214 0.06 9.984 10.489
2.502 0.07 9.970 10.279
1.947 0.08 9.956 10.145
2.873 0.09 9.941 10.348
2.401 0.10 9.926 10.212
0.979 0.15 9.898 9.947
0.399 0.20 9.868 9.876
0.163 0.25 9.835 9.836
0.066 0.30 9.800 9.800
Ubicación:
Ingeniero:Caso de Estudio: SC-2
12.0.0C
Página: 24
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Falta trifásica en barra: S.E. Reque
kA rms
Nominal kV
Tensión Factor c
Valor Pico
Estado Estable
=
=
=
=
220.000
1.10
26.672
10.724
(Definido por el Usuario)
kA Método C
ID MagnitudCocienteActivaBarra OrigenID Imaginario
Barra Origen Barra Destino % V kA kA X/R kA
Contribución Tensión y Corriente Inicial Simétrica (rms)
S.E. Reque Total 0.00 1.031 -10.682 10.4 10.731
S.E. Etén S.E. Reque 2.86 0.047 -2.812 60.1 2.813
Red eléctrica Peruana S.E. Reque 100.00 0.984 -7.869 8.0 7.931
BUS GEN S.E. Etén 41.82 0.047 -2.812 60.1 2.813
Corriente de Falta e Interrupción en CC (kA)
TD (S) Ib sym Idc
Basada en la Corriente Total de Falta en Bar
Ib asym
10.707 0.01 10.655 15.105
8.019 0.02 10.630 13.315
5.829 0.03 10.600 12.097
4.237 0.04 10.566 11.384
3.963 0.05 10.528 11.249
3.030 0.06 10.516 10.944
2.316 0.07 10.504 10.756
1.771 0.08 10.491 10.640
2.589 0.09 10.478 10.793
2.127 0.10 10.464 10.678
0.796 0.15 10.439 10.470
0.298 0.20 10.411 10.416
0.112 0.25 10.381 10.382
0.042 0.30 10.349 10.349
CÁLCULOS ELÉCTRICOS Rev. C
ANEXO VIII
RFE-1-YE__-ECE-IDO-001 Pág/Page 1 de/of 21
Este documento contiene información propiedad de Cobra y está sujeto a las restricciones detalladas en la página de portada.
La única copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page. The only controlled copy of the document is located on the Cobra intranet.
ANEXO VIII:
REPORTES DEL ANÁLISIS DE ARRANQUE DE MOTORES
One-Line Diagram - OLV1 (Motor Acceleration Analysis)
page 1 09:56:51 may 02, 2014 Project File: Eten
RESERVA FRÍA ETEN
ESTUDIO DE ARRANQUE DE MOTORES: CASO MS-1 - MOTOR DE MT (REV C)
CONDICIONES:-> TENSIÓN DE RED: 220 kV-> GENERADOR PRINCIPAL PARADO-> GENERADOR AUXILIAR PARADO-> GENERADOR EMERGENCIA PARADO-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIÓN EN AUTO.-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIÓN EN TOMA CENTRAL.-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN ÚNICO TRAFO MT/BT.
PCI_BUS
1BFA51
0,48 kV94,
95%
Bus18
1BBA51
6,6 kV97,
97%
Bus19
1BFA53
0,48 kV 94,95%
1BMA52
0,48 kV 94,95%
1BNB52
0,38 kV98,
12%
CGDE
0,48 kV
Bus14
Bus11
Bus8
Bus15
Bus13
Bus7
Bus16
Bus12
Bus6
Bus17
Bus10
Bus5
Bus23
Bus25Bus24
Bus20
Bus EX
1BBA76
6,6 kV 97,97%
Bus9
1BJA76
0,48 kV98,
76%
Bus BS
Bus22
BUS GEN
18 kV
99,86%
S.E. Etén
220 kV 99,99%
S.E. Reque
220 kV 100%
Sistema PCI
200 kW
Red eléctrica Peruana
3022 MVAsc
3600 kW
2196 kvar
Narcissus
AL 2,92 km
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
1MKA10
225 MW
Isolated Phase CU
35 m
Open
Isolated Phase CU
35 m
Isolated Phase CU
8 m
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
4-3/C 240
CU 40 m
1MKA76
8,44 MW
3-3/C 300
CU 20 m
Open
CARGAS 1BJA76
270 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1-3/C 300
CU 20 m
3-3/C 300
CU 120 m
Excitación 1MKC10
944 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1-3/C 150
CU 40 m
LCI 1BPA10_1
2725 kVA
LCI 1BPA10_2
2725 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
3-3/C 240
CU 40 m
Open
88WN-1
224 kW
1-3/C 70
CU 50 m
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
88WN-2
224 kW
1-3/C 70
CU 50 m
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
Open
88AK-1
375 kW
1-3/C 70
CU 50 m
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
88AK-2
375 kW
1-3/C 70
CU 50 m
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
Open
W-1BMB20
1XKA52
2000 kW
6-3/C 300
CU 50 m
Open
CARGAS 1BNB52
82,2 kVA
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
W-1BMB52
MBN50 AH010
450 kVA
1BJA80
400 kVA
W-1BJA12
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
2-3/C 185
CU 40 m 2-3/C 185
CU 40 m
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
Open
W-1BJA51W-1BJA11
2-3/C 240
CU 115 m
Bus25Bus24
Bus23Bus16 Bus14
Bus12 Bus11
Bus BS
Bus8Bus6
CGDE
0,48 kV
1MKA10
225 MW
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
1MKA76
8,44 MW
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
Excitación 1MKC10
944 kVA
LCI 1BPA10_1
2725 kVA
1XKA52
2000 kW
88WN-1
224 kW
88WN-2
224 kW
88AK-2
375 kW
MBN50 AH010
450 kVA
CARGAS 1BNB52
82,2 kVA
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
W-1BJA51W-1BMB20W-1BJA12W-1BJA11
Narcissus
AL 2,92 km
6-3/C 300
CU 50 mW-1BMB52
1BJA80
400 kVA
3-3/C 300
CU 120 m
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
CARGAS 1BJA76
270 kVA
3-3/C 300
CU 20 m1-3/C 300
CU 20 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 100 m
1-3/C 70
CU 70 m
1-3/C 70
CU 70 m
2-3/C 185
CU 40 m
2-3/C 185
CU 40 m
1-3/C 150
CU 40 m
3-3/C 240
CU 40 m
4-3/C 240
CU 40 m
1-3/C 70
CU 100 m
1-3/C 70
CU 50 m
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
LCI 1BPA10_2
2725 kVA
2-3/C 240
CU 115 m
Sistema PCI
200 kW
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
88AK-1
375 kW
Red eléctrica Peruana
3022 MVAsc
1BBA51
6,6 kV
1BBA76
6,6 kV
1BFA51
0,48 kV
1BFA53
0,48 kV
1BJA76
0,48 kV
1BMA52
0,48 kV
1BNB52
0,38 kV
Bus5 Bus7
Bus9
Bus10 Bus13
Bus15Bus17
Bus18
Bus19
Bus20
Bus22
Bus EX
BUS GEN
18 kV
PCI_BUS
S.E. Etén
220 kV
S.E. Reque
220 kV
98,76%
97,97%
100%
98,12%
94,95%
99,86%
99,99%
94,95%94,
95%
97,97%
Isolated Phase CU
35 m
Open
Isolated Phase CU
35 m
Isolated Phase CU
8 m
Open
Open
Open
Open Open
3600 kW
2196 kvar
Open
One-Line Diagram - OLV1 (Motor Acceleration Analysis)
page 2 09:56:51 may 02, 2014 Project File: Eten
1BJA11
0,48 kV 94,63%
1BJA12
0,48 kV 94,71%
1BMB52
0,48 kV
94,83%
1BJA51
0,48 kV 94,82%
1BMB20
0,48 kV 94,75%
CARGAS 1BMB20
235 kVA
1MBV10AP001-M01
75 kW
1BMA52
4-3/C 240
CU 50 m
Compresor 1
37 kW
CARGAS 1BJA51
650 kVA
1BFA51
4-3/C 240
CU 20 m
1BMA52
2-3/C 150
CU 20 m
Compresor 2
37 kW
Open
CARGAS 1BMB52
231 kVA
CARGAS 1BJA12
592 kVA
6-3/C 240
CU 50 m
1BFA53
CARGAS 1BJA11
695 kVA
1MBV10AP002-M1
75 kW
6-3/C 240
CU 50 m
1BFA51
CARGAS 1BMB20
235 kVA
Compresor 1
37 kW
Compresor 2
37 kW
CARGAS 1BMB52
231 kVA
1BFA51
1BMA52 1BFA53 1BFA51
1MBV10AP001-M01
75 kW
4-3/C 240
CU 50 m
6-3/C 240
CU 50 m
6-3/C 240
CU 50 m
4-3/C 240
CU 20 m
2-3/C 150
CU 20 m
1BMA52
CARGAS 1BJA11
695 kVA
CARGAS 1BJA12
592 kVA
CARGAS 1BJA51
650 kVA
1MBV10AP002-M1
75 kW
1BJA11
0,48 kV
1BJA12
0,48 kV
1BJA51
0,48 kV
1BMB20
0,48 kV
1BMB52
0,48 kV
94,75%
94,82%
94,83%
Open
94,71%
94,63%
One-Line Diagram - OLV1 (Motor Acceleration Analysis)
page 1 09:57:10 may 02, 2014 Project File: Eten
RESERVA FRÍA ETEN
ESTUDIO DE ARRANQUE DE MOTORES: CASO MS-1 - MOTOR DE MT (REV C)
CONDICIONES:-> TENSIÓN DE RED: 220 kV-> GENERADOR PRINCIPAL PARADO-> GENERADOR AUXILIAR PARADO-> GENERADOR EMERGENCIA PARADO-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIÓN EN AUTO.-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIÓN EN TOMA CENTRAL.-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN ÚNICO TRAFO MT/BT.
PCI_BUS
1BFA51
0,48 kV91,
39%
Bus18
1BBA51
6,6 kV94,
73%
Bus19
1BFA53
0,48 kV 91,39%
1BMA52
0,48 kV 91,39%
1BNB52
0,38 kV94,
43%
CGDE
0,48 kV
Bus14
Bus11
Bus8
Bus15
Bus13
Bus7
Bus16
Bus12
Bus6
Bus17
Bus10
Bus5
Bus23
Bus25Bus24
Bus20
Bus EX
1BBA76
6,6 kV 94,73%
Bus9
1BJA76
0,48 kV95,
41%
Bus BS
Bus22
BUS GEN
18 kV
99,67%
S.E. Etén
220 kV 99,91%
S.E. Reque
220 kV 99,92%
Sistema PCI
200 kW
Red eléctrica Peruana
3022 MVAsc
4103 kW
4433 kvar
Narcissus
AL 2,92 km
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
1MKA10
225 MW
Isolated Phase CU
35 m
Open
Isolated Phase CU
35 m
Isolated Phase CU
8 m
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
4-3/C 240
CU 40 m
1MKA76
8,44 MW
3-3/C 300
CU 20 m
Open
CARGAS 1BJA76
270 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1-3/C 300
CU 20 m
3-3/C 300
CU 120 m
Excitación 1MKC10
944 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1-3/C 150
CU 40 m
LCI 1BPA10_1
2725 kVA
LCI 1BPA10_2
2725 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
3-3/C 240
CU 40 m
Open
88WN-1
224 kW
1-3/C 70
CU 50 m
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
88WN-2
224 kW
1-3/C 70
CU 50 m
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
Open
88AK-1
375 kW
298 kW
1550 kvar
1-3/C 70
CU 50 m
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
88AK-2
375 kW
1-3/C 70
CU 50 m
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
Open
W-1BMB20
1XKA52
2000 kW
6-3/C 300
CU 50 m
Open
CARGAS 1BNB52
82,2 kVA
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
W-1BMB52
MBN50 AH010
450 kVA
1BJA80
400 kVA
W-1BJA12
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
2-3/C 185
CU 40 m 2-3/C 185
CU 40 m
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
Open
W-1BJA51W-1BJA11
2-3/C 240
CU 115 m
Bus25Bus24
Bus23Bus16 Bus14
Bus12 Bus11
Bus BS
Bus8Bus6
CGDE
0,48 kV
1MKA10
225 MW
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
1MKA76
8,44 MW
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
Excitación 1MKC10
944 kVA
LCI 1BPA10_1
2725 kVA
1XKA52
2000 kW
88WN-1
224 kW
88WN-2
224 kW
88AK-2
375 kW
MBN50 AH010
450 kVA
CARGAS 1BNB52
82,2 kVA
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
W-1BJA51W-1BMB20W-1BJA12W-1BJA11
Narcissus
AL 2,92 km
6-3/C 300
CU 50 mW-1BMB52
1BJA80
400 kVA
3-3/C 300
CU 120 m
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
CARGAS 1BJA76
270 kVA
3-3/C 300
CU 20 m1-3/C 300
CU 20 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 100 m
1-3/C 70
CU 70 m
1-3/C 70
CU 70 m
2-3/C 185
CU 40 m
2-3/C 185
CU 40 m
1-3/C 150
CU 40 m
3-3/C 240
CU 40 m
4-3/C 240
CU 40 m
1-3/C 70
CU 100 m
1-3/C 70
CU 50 m
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
LCI 1BPA10_2
2725 kVA
2-3/C 240
CU 115 m
Sistema PCI
200 kW
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
88AK-1
375 kW
Red eléctrica Peruana
3022 MVAsc
1BBA51
6,6 kV
1BBA76
6,6 kV
1BFA51
0,48 kV
1BFA53
0,48 kV
1BJA76
0,48 kV
1BMA52
0,48 kV
1BNB52
0,38 kV
Bus5 Bus7
Bus9
Bus10 Bus13
Bus15Bus17
Bus18
Bus19
Bus20
Bus22
Bus EX
BUS GEN
18 kV
PCI_BUS
S.E. Etén
220 kV
S.E. Reque
220 kV
95,41%
94,73%
99,92%
94,43%
91,39%
99,67%
99,91%
91,39%91,
39%
94,73%
Isolated Phase CU
35 m
Open
Isolated Phase CU
35 m
Isolated Phase CU
8 m
Open
Open
Open
Open Open
4103 kW
4433 kvar
Open
298 kW
1550 kvar
One-Line Diagram - OLV1 (Motor Acceleration Analysis)
page 2 09:57:10 may 02, 2014 Project File: Eten
1BJA11
0,48 kV 91,05%
1BJA12
0,48 kV 91,14%
1BMB52
0,48 kV
91,27%
1BJA51
0,48 kV 91,25%
1BMB20
0,48 kV 91,18%
CARGAS 1BMB20
235 kVA
1MBV10AP001-M01
75 kW
1BMA52
4-3/C 240
CU 50 m
Compresor 1
37 kW
CARGAS 1BJA51
650 kVA
1BFA51
4-3/C 240
CU 20 m
1BMA52
2-3/C 150
CU 20 m
Compresor 2
37 kW
Open
CARGAS 1BMB52
231 kVA
CARGAS 1BJA12
592 kVA
6-3/C 240
CU 50 m
1BFA53
CARGAS 1BJA11
695 kVA
1MBV10AP002-M1
75 kW
6-3/C 240
CU 50 m
1BFA51
CARGAS 1BMB20
235 kVA
Compresor 1
37 kW
Compresor 2
37 kW
CARGAS 1BMB52
231 kVA
1BFA51
1BMA52 1BFA53 1BFA51
1MBV10AP001-M01
75 kW
4-3/C 240
CU 50 m
6-3/C 240
CU 50 m
6-3/C 240
CU 50 m
4-3/C 240
CU 20 m
2-3/C 150
CU 20 m
1BMA52
CARGAS 1BJA11
695 kVA
CARGAS 1BJA12
592 kVA
CARGAS 1BJA51
650 kVA
1MBV10AP002-M1
75 kW
1BJA11
0,48 kV
1BJA12
0,48 kV
1BJA51
0,48 kV
1BMB20
0,48 kV
1BMB52
0,48 kV
91,18%
91,25%
91,27%
Open
91,14%
91,05%
Ubicación:
Ingeniero:Caso de Estudio: MS-1
12.0.0C
Página: 1
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga @ T = 0.000-
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
% PFMW Mvar AmpID
XFMR
% Tap
6.6001BBA51 -2.8 97.972 84.61BBA76 0.173 0.109 18.200 00
91.5Bus17 0.134 0.059 13.1
0.0Bus18 0.000 0.000 0.0
81.0Bus19 2.584 1.873 284.9
88.7Bus20 0.689 0.359 69.4
83.1Bus22 -3.579 -2.400 384.8
0.0Bus15 0.000 0.000 0.0
6.6001BBA76 -2.8 97.970 84.61BBA51 -0.173 -0.109 18.200 00
84.6Bus9 0.173 0.109 18.2
0.4801BFA51 -8.4 94.948 84.9PCI_BUS 0.174 0.108 260.100 00
81.71BJA11 0.549 0.387 850.3
80.21BJA51 0.365 0.271 575.6
81.81BMA52 -1.088 -0.766 1685.4
0.4801BFA53 -8.4 94.948 0.166 0.633 80.01BJA12 0.397 0.298 629.200
86.3Bus19 -2.537 -1.484 3723.9
82.81BMA52 1.507 1.020 2305.8
0.4801BJA11 -8.4 94.625 0.385 0.547 81.81BFA51 -0.547 -0.385 850.300
0.4801BJA12 -8.4 94.709 0.297 0.396 80.01BFA53 -0.396 -0.297 629.200
0.4801BJA51 -8.4 94.817 0.271 0.364 80.31BFA51 -0.364 -0.271 575.600
0.4801BJA76 -3.3 98.755 0.106 0.170 85.0Bus9 -0.170 -0.106 244.200
0.4801BMA52 -8.4 94.948 87.21BMB20 0.244 0.137 354.400 00
80.01BMB52 0.118 0.088 186.4
89.51BNB52 0.058 0.029 82.0
81.81BFA51 1.088 0.766 1685.4
82.81BFA53 -1.507 -1.020 2305.8
0.4801BMB20 -8.4 94.750 0.136 0.244 87.21BMA52 -0.244 -0.136 354.400
0.4801BMB52 -8.4 94.832 0.088 0.118 80.01BMA52 -0.118 -0.088 186.400
0.3801BNB52 -9.0 98.125 0.028 0.057 90.01BMA52 -0.057 -0.028 98.400
4.000Bus5 -3.3 100.430 0.057 0.133 91.9Bus10 -0.133 -0.057 20.700
4.000Bus7 -2.8 101.891 0.0Bus13 0.000 0.000 0.000 00
6.600Bus9 -2.8 97.969 84.61BBA76 -0.173 -0.109 18.200 00
2.500 84.61BJA76 0.173 0.109 18.2
4.160Bus10 -3.3 96.583 91.9Bus5 0.133 0.057 20.700 00
91.9Bus17 -0.133 -0.057 20.7
4.000Bus13 -2.8 101.891 0.0Bus7 0.000 0.000 0.000 00
0.0Bus15 0.000 0.000 0.0
6.600Bus15 -2.8 97.972 0.01BBA51 0.000 0.000 0.000 00
0.0Bus13 0.000 0.000 0.0
6.600Bus17 -2.8 97.964 91.51BBA51 -0.134 -0.059 13.100 00
91.5Bus10 0.134 0.059 13.1
6.600Bus18 -2.8 97.972 0.01BBA51 0.000 0.000 0.000 00
Ubicación:
Ingeniero:Caso de Estudio: MS-1
12.0.0C
Página: 2
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga @ T = 0.000-
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
% PFMW Mvar AmpID
XFMR
% Tap
6.600Bus19 -2.8 97.948 81.01BBA51 -2.583 -1.872 284.900 00
81.01BFA53 2.583 1.872 284.9
6.600Bus20 -2.8 97.959 88.71BBA51 -0.689 -0.359 69.400 00
88.7Bus EX 0.689 0.359 69.4
6.900Bus22 -2.8 93.726 83.11BBA51 3.580 2.400 384.800 00
83.1BUS GEN -3.580 -2.400 384.8
0.480Bus EX -4.5 89.907 0.332 0.684 90.0Bus20 -0.684 -0.332 1017.200
18.000BUS GEN -0.1 99.860 80.4S.E. Etén -3.600 -2.666 143.900 00
2.500 80.4Bus22 3.600 2.666 143.9
0.480PCI_BUS -8.5 94.272 0.107 0.173 85.01BFA51 -0.173 -0.107 260.100
220.000S.E. Etén 0.0 99.992 80.3S.E. Reque -3.600 -2.676 11.800 00
80.3BUS GEN 3.600 2.676 11.8
* 220.000S.E. Reque 0.0 100.000 85.4S.E. Etén 3.600 2.196 11.100 00
85.4Red eléctrica Peruana -3.600 -2.196 11.1
* 220.000Red eléctrica Peruana 0.1 100.087 2.202 3.601 85.3S.E. Reque 3.601 2.202 11.100
* Indica una barra con tensión regulada (con máquinas de tensión controlada o máquinas de referencia conectadas)
Ubicación:
Ingeniero:Caso de Estudio: MS-1
12.0.0C
Página: 3
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga @ T = 1,000+
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
% PFMW Mvar AmpID
XFMR
% Tap
6.6001BBA51 -3.2 94.728 84.51BBA76 0.168 0.106 18.400 00
91.5Bus17 0.134 0.059 13.5
0.0Bus18 0.000 0.000 0.0
80.5Bus19 2.512 1.851 288.2
88.7Bus20 0.644 0.336 67.1
68.2Bus22 -4.060 -4.349 549.4
28.8Bus15 0.602 1.997 192.6
6.6001BBA76 -3.2 94.726 84.51BBA51 -0.168 -0.106 18.400 00
84.5Bus9 0.168 0.106 18.4
0.4801BFA51 -9.0 91.387 84.9PCI_BUS 0.175 0.108 270.400 00
81.81BJA11 0.544 0.383 875.9
80.31BJA51 0.353 0.262 578.2
81.81BMA52 -1.071 -0.754 1723.9
0.4801BFA53 -9.0 91.387 0.157 0.592 80.01BJA12 0.393 0.295 647.200
86.1Bus19 -2.465 -1.453 3766.2
82.81BMA52 1.480 1.001 2351.9
0.4801BJA11 -9.1 91.054 0.382 0.542 81.81BFA51 -0.542 -0.382 875.900
0.4801BJA12 -9.0 91.140 0.294 0.392 80.01BFA53 -0.392 -0.294 647.200
0.4801BJA51 -9.0 91.255 0.262 0.352 80.31BFA51 -0.352 -0.262 578.200
0.4801BJA76 -3.7 95.411 0.103 0.166 85.0Bus9 -0.166 -0.103 246.100
0.4801BMA52 -9.0 91.387 87.21BMB20 0.241 0.135 364.000 00
80.01BMB52 0.114 0.085 186.9
89.51BNB52 0.054 0.027 79.6
81.81BFA51 1.071 0.754 1723.9
82.81BFA53 -1.480 -1.001 2351.9
0.4801BMB20 -9.1 91.183 0.135 0.241 87.31BMA52 -0.241 -0.135 364.000
0.4801BMB52 -9.0 91.270 0.085 0.113 80.01BMA52 -0.113 -0.085 186.900
0.3801BNB52 -9.6 94.430 0.026 0.053 90.01BMA52 -0.053 -0.026 95.500
4.000Bus5 -3.7 97.004 0.057 0.133 91.9Bus10 -0.133 -0.057 21.500
4.000Bus7 2.7 74.565 1.550 0.298 18.9Bus13 -0.298 -1.550 305.600
6.600Bus9 -3.2 94.725 84.51BBA76 -0.168 -0.106 18.400 00
2.500 84.51BJA76 0.168 0.106 18.4
4.160Bus10 -3.7 93.289 91.9Bus5 0.133 0.057 21.500 00
91.9Bus17 -0.133 -0.057 21.5
4.000Bus13 2.6 74.684 19.1Bus7 0.302 1.552 305.600 00
19.1Bus15 -0.302 -1.552 305.6
6.600Bus15 -3.1 94.622 28.71BBA51 -0.598 -1.996 192.600 00
28.7Bus13 0.598 1.996 192.6
6.600Bus17 -3.2 94.719 91.51BBA51 -0.134 -0.059 13.500 00
91.5Bus10 0.134 0.059 13.5
6.600Bus18 -3.2 94.728 0.01BBA51 0.000 0.000 0.000 00
Ubicación:
Ingeniero:Caso de Estudio: MS-1
12.0.0C
Página: 4
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga @ T = 1,000+
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
% PFMW Mvar AmpID
XFMR
% Tap
6.600Bus19 -3.2 94.704 80.51BBA51 -2.512 -1.850 288.200 00
80.51BFA53 2.512 1.850 288.2
6.600Bus20 -3.2 94.715 88.71BBA51 -0.644 -0.335 67.100 00
88.7Bus EX 0.644 0.335 67.1
6.900Bus22 -3.2 90.629 68.21BBA51 4.061 4.350 549.400 00
68.2BUS GEN -4.061 -4.350 549.4
0.480Bus EX -4.8 86.930 0.310 0.640 90.0Bus20 -0.640 -0.310 983.500
18.000BUS GEN -0.1 99.670 64.3S.E. Etén -4.103 -4.892 205.500 00
2.500 64.3Bus22 4.103 4.892 205.5
0.480PCI_BUS -9.1 90.684 0.107 0.173 85.01BFA51 -0.173 -0.107 270.400
220.000S.E. Etén 0.0 99.909 64.1S.E. Reque -4.103 -4.912 16.800 00
64.1BUS GEN 4.103 4.912 16.8
* 220.000S.E. Reque 0.0 99.924 67.9S.E. Etén 4.103 4.433 15.900 00
67.9Red eléctrica Peruana -4.103 -4.433 15.9
* 220.000Red eléctrica Peruana 0.1 100.087 4.445 4.105 67.8S.E. Reque 4.105 4.445 15.900
* Indica una barra con tensión regulada (con máquinas de tensión controlada o máquinas de referencia conectadas)
Ubicación:
Ingeniero:Caso de Estudio: MS-1
12.0.0C
Página: 5
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga @ T = 2,000+
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
% PFMW Mvar AmpID
XFMR
% Tap
6.6001BBA51 -3.1 97.601 84.61BBA76 0.172 0.109 18.200 00
91.5Bus17 0.134 0.059 13.1
0.0Bus18 0.000 0.000 0.0
80.9Bus19 2.575 1.870 285.3
88.7Bus20 0.684 0.356 69.1
83.9Bus22 -3.981 -2.585 425.4
90.9Bus15 0.416 0.191 41.0
6.6001BBA76 -3.1 97.599 84.61BBA51 -0.172 -0.109 18.200 00
84.6Bus9 0.172 0.109 18.2
0.4801BFA51 -8.8 94.542 84.9PCI_BUS 0.174 0.108 261.300 00
81.71BJA11 0.548 0.386 853.1
80.21BJA51 0.363 0.270 575.8
81.81BMA52 -1.086 -0.765 1689.6
0.4801BFA53 -8.8 94.542 0.165 0.628 80.01BJA12 0.397 0.298 631.200
86.3Bus19 -2.529 -1.481 3728.4
82.81BMA52 1.504 1.018 2310.8
0.4801BJA11 -8.8 94.218 0.385 0.546 81.81BFA51 -0.546 -0.385 853.100
0.4801BJA12 -8.8 94.301 0.297 0.396 80.01BFA53 -0.396 -0.297 631.200
0.4801BJA51 -8.8 94.410 0.270 0.363 80.31BFA51 -0.363 -0.270 575.800
0.4801BJA76 -3.6 98.373 0.105 0.170 85.0Bus9 -0.170 -0.105 244.400
0.4801BMA52 -8.8 94.542 87.21BMB20 0.244 0.137 355.400 00
80.01BMB52 0.117 0.088 186.5
89.51BNB52 0.058 0.029 81.8
81.81BFA51 1.086 0.765 1689.6
82.81BFA53 -1.504 -1.018 2310.8
0.4801BMB20 -8.8 94.343 0.136 0.243 87.21BMA52 -0.243 -0.136 355.400
0.4801BMB52 -8.8 94.426 0.088 0.117 80.01BMA52 -0.117 -0.088 186.500
0.3801BNB52 -9.4 97.703 0.028 0.057 90.01BMA52 -0.057 -0.028 98.100
4.000Bus5 -3.7 100.039 0.057 0.133 91.9Bus10 -0.133 -0.057 20.800
4.000Bus7 -4.8 96.895 0.170 0.402 92.1Bus13 -0.402 -0.170 65.100
6.600Bus9 -3.1 97.598 84.61BBA76 -0.172 -0.109 18.200 00
2.500 84.61BJA76 0.172 0.109 18.2
4.160Bus10 -3.7 96.206 91.9Bus5 0.133 0.057 20.800 00
91.9Bus17 -0.133 -0.057 20.8
4.000Bus13 -4.8 96.944 92.1Bus7 0.402 0.170 65.100 00
92.1Bus15 -0.402 -0.170 65.1
6.600Bus15 -3.1 97.564 90.91BBA51 -0.416 -0.190 41.000 00
90.9Bus13 0.416 0.190 41.0
6.600Bus17 -3.1 97.593 91.51BBA51 -0.134 -0.059 13.100 00
91.5Bus10 0.134 0.059 13.1
6.600Bus18 -3.1 97.601 0.01BBA51 0.000 0.000 0.000 00
Ubicación:
Ingeniero:Caso de Estudio: MS-1
12.0.0C
Página: 6
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga @ T = 2,000+
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
% PFMW Mvar AmpID
XFMR
% Tap
6.600Bus19 -3.1 97.577 80.91BBA51 -2.575 -1.870 285.300 00
80.91BFA53 2.575 1.870 285.3
6.600Bus20 -3.1 97.588 88.71BBA51 -0.684 -0.356 69.100 00
88.7Bus EX 0.684 0.356 69.1
6.900Bus22 -3.1 93.372 83.91BBA51 3.982 2.585 425.400 00
83.9BUS GEN -3.982 -2.585 425.4
0.480Bus EX -4.8 89.566 0.329 0.679 90.0Bus20 -0.679 -0.329 1013.400
18.000BUS GEN -0.1 99.837 80.9S.E. Etén -4.007 -2.911 159.100 00
2.500 80.9Bus22 4.007 2.911 159.1
0.480PCI_BUS -8.8 93.863 0.107 0.173 85.01BFA51 -0.173 -0.107 261.300
220.000S.E. Etén 0.0 99.981 80.8S.E. Reque -4.007 -2.922 13.000 00
80.8BUS GEN 4.007 2.922 13.0
* 220.000S.E. Reque 0.0 99.990 85.4S.E. Etén 4.007 2.442 12.300 00
85.4Red eléctrica Peruana -4.007 -2.442 12.3
* 220.000Red eléctrica Peruana 0.1 100.087 2.450 4.008 85.3S.E. Reque 4.008 2.450 12.300
* Indica una barra con tensión regulada (con máquinas de tensión controlada o máquinas de referencia conectadas)
One-Line Diagram - OLV1 (Motor Acceleration Analysis)
page 1 09:53:38 may 02, 2014 Project File: Eten
RESERVA FRÍA ETEN
ESTUDIO DE ARRANQUE DE MOTORES: CASO MS-2 - MOTOR DE BT (REV C)
CONDICIONES:-> TENSIÓN DE RED: 220 kV-> GENERADOR PRINCIPAL PARADO-> GENERADOR AUXILIAR PARADO-> GENERADOR EMERGENCIA PARADO-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIÓN EN TOMA -4,5%.-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIÓN EN TOMA CENTRAL.-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN ÚNICO TRAFO MT/BT.
PCI_BUS
1BFA51
0,48 kV100
,8%
Bus18
1BBA51
6,6 kV102
,8%
Bus19
1BFA53
0,48 kV 100,8%
1BMA52
0,48 kV 100,8%
1BNB52
0,38 kV104
,2%
CGDE
0,48 kV
Bus14
Bus11
Bus8
Bus15
Bus13
Bus7
Bus16
Bus12
Bus6
Bus17
Bus10
Bus5
Bus23
Bus25Bus24
Bus20
Bus EX
1BBA76
6,6 kV 102,8%
Bus9
1BJA76
0,48 kV103
,73%
Bus BS
Bus22
BUS GEN
18 kV
104,57
%
S.E. Etén
220 kV 99,99%
S.E. Reque
220 kV 100%
Sistema PCI
200 kW
Red eléctrica Peruana
3022 MVAsc
3972 kW
2297 kvar
Narcissus
AL 2,92 km
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
-4,5% TapP
1MKA10
225 MW
Isolated Phase CU
35 m
Open
Isolated Phase CU
35 m
Isolated Phase CU
8 m
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
4-3/C 240
CU 40 m
1MKA76
8,44 MW
3-3/C 300
CU 20 m
Open
CARGAS 1BJA76
270 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1-3/C 300
CU 20 m
3-3/C 300
CU 120 m
Excitación 1MKC10
944 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1-3/C 150
CU 40 m
LCI 1BPA10_1
2725 kVA
LCI 1BPA10_2
2725 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
3-3/C 240
CU 40 m
Open
88WN-1
224 kW
1-3/C 70
CU 50 m
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
88WN-2
224 kW
1-3/C 70
CU 50 m
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
Open
88AK-1
375 kW
1-3/C 70
CU 50 m
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
88AK-2
375 kW
1-3/C 70
CU 50 m
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
Open
W-1BMB20
1XKA52
2000 kW
6-3/C 300
CU 50 m
Open
CARGAS 1BNB52
82,2 kVA
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
W-1BMB52
MBN50 AH010
450 kVA
1BJA80
400 kVA
W-1BJA12
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
2-3/C 185
CU 40 m 2-3/C 185
CU 40 m
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
Open
W-1BJA51W-1BJA11
2-3/C 240
CU 115 m
Bus25Bus24
Bus23Bus16 Bus14
Bus12 Bus11
Bus BS
Bus8Bus6
CGDE
0,48 kV
1MKA10
225 MW
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
-4,5% TapP
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
1MKA76
8,44 MW
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
Excitación 1MKC10
944 kVA
LCI 1BPA10_1
2725 kVA
1XKA52
2000 kW
88WN-1
224 kW
88AK-1
375 kW
88WN-2
224 kW
88AK-2
375 kW
MBN50 AH010
450 kVA
CARGAS 1BNB52
82,2 kVA
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
W-1BJA51W-1BMB20W-1BJA12W-1BJA11
Narcissus
AL 2,92 km
6-3/C 300
CU 50 mW-1BMB52
1BJA80
400 kVA
3-3/C 300
CU 120 m
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
CARGAS 1BJA76
270 kVA
3-3/C 300
CU 20 m1-3/C 300
CU 20 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 100 m
1-3/C 70
CU 70 m
1-3/C 70
CU 70 m
2-3/C 185
CU 40 m
2-3/C 185
CU 40 m
1-3/C 150
CU 40 m
3-3/C 240
CU 40 m
4-3/C 240
CU 40 m
1-3/C 70
CU 100 m
1-3/C 70
CU 50 m
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
LCI 1BPA10_2
2725 kVA
2-3/C 240
CU 115 m
Sistema PCI
200 kW
Red eléctrica Peruana
3022 MVAsc
1BBA51
6,6 kV
1BBA76
6,6 kV
1BFA51
0,48 kV
1BFA53
0,48 kV
1BJA76
0,48 kV
1BMA52
0,48 kV
1BNB52
0,38 kV
Bus5 Bus7
Bus9
Bus10 Bus13
Bus15Bus17
Bus18
Bus19
Bus20
Bus22
Bus EX
BUS GEN
18 kV
PCI_BUS
S.E. Etén
220 kV
S.E. Reque
220 kV
103,73
%
102,8%
100%
104,2%
100,8%
104,57
%
99,99%
100,8%100
,8%
102,8%
Isolated Phase CU
35 m
Open
Isolated Phase CU
35 m
Isolated Phase CU
8 m
Open
Open
Open
Open Open
3972 kW
2297 kvar
Open
One-Line Diagram - OLV1 (Motor Acceleration Analysis)
page 2 09:53:38 may 02, 2014 Project File: Eten
1BJA11
0,48 kV 100,5%
1BJA12
0,48 kV 100,57
%
1BMB52
0,48 kV
100,69
%
1BJA51
0,48 kV 100,67
%
1BMB20
0,48 kV 100,61
%
CARGAS 1BMB20
235 kVA
1MBV10AP001-M01
75 kW
1BMA52
4-3/C 240
CU 50 m
Compresor 1
37 kW
CARGAS 1BJA51
650 kVA
1BFA51
4-3/C 240
CU 20 m
1BMA52
2-3/C 150
CU 20 m
Compresor 2
37 kW
Open
CARGAS 1BMB52
231 kVA
CARGAS 1BJA12
592 kVA
6-3/C 240
CU 50 m
1BFA53
CARGAS 1BJA11
695 kVA
1MBV10AP002-M1
75 kW
6-3/C 240
CU 50 m
1BFA51
CARGAS 1BMB20
235 kVA
Compresor 1
37 kW
Compresor 2
37 kW
CARGAS 1BMB52
231 kVA
1BFA51
1BMA52 1BFA53 1BFA51
1MBV10AP001-M01
75 kW
4-3/C 240
CU 50 m
6-3/C 240
CU 50 m
6-3/C 240
CU 50 m
4-3/C 240
CU 20 m
2-3/C 150
CU 20 m
1BMA52
CARGAS 1BJA11
695 kVA
CARGAS 1BJA12
592 kVA
CARGAS 1BJA51
650 kVA
1MBV10AP002-M1
75 kW
1BJA11
0,48 kV
1BJA12
0,48 kV
1BJA51
0,48 kV
1BMB20
0,48 kV
1BMB52
0,48 kV
100,61
%
100,67
%
100,69
%
Open
100,57
%100
,5%
One-Line Diagram - OLV1 (Motor Acceleration Analysis)
page 1 09:54:33 may 02, 2014 Project File: Eten
RESERVA FRÍA ETEN
ESTUDIO DE ARRANQUE DE MOTORES: CASO MS-2 - MOTOR DE BT (REV C)
CONDICIONES:-> TENSIÓN DE RED: 220 kV-> GENERADOR PRINCIPAL PARADO-> GENERADOR AUXILIAR PARADO-> GENERADOR EMERGENCIA PARADO-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIÓN EN TOMA -4,5%.-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIÓN EN TOMA +2,5%.-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIÓN EN TOMA CENTRAL.-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN ÚNICO TRAFO MT/BT.
PCI_BUS
1BFA51
0,48 kV91,
87%
Bus18
1BBA51
6,6 kV100
,36%
Bus19
1BFA53
0,48 kV 91,87%
1BMA52
0,48 kV 91,87%
1BNB52
0,38 kV94,
93%
CGDE
0,48 kV
Bus14
Bus11
Bus8
Bus15
Bus13
Bus7
Bus16
Bus12
Bus6
Bus17
Bus10
Bus5
Bus23
Bus25Bus24
Bus20
Bus EX
1BBA76
6,6 kV 100,36
%
Bus9
1BJA76
0,48 kV101
,22%
Bus BS
Bus22
BUS GEN
18 kV
104,42
%
S.E. Etén
220 kV 99,93%
S.E. Reque
220 kV 99,94%
Sistema PCI
200 kW
295 kW
1281 kvar
Red eléctrica Peruana
3022 MVAsc
4150 kW
4058 kvar
Narcissus
AL 2,92 km
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
-4,5% TapP
1MKA10
225 MW
Isolated Phase CU
35 m
Open
Isolated Phase CU
35 m
Isolated Phase CU
8 m
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
4-3/C 240
CU 40 m
1MKA76
8,44 MW
3-3/C 300
CU 20 m
Open
CARGAS 1BJA76
270 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
1-3/C 300
CU 20 m
3-3/C 300
CU 120 m
Excitación 1MKC10
944 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
1-3/C 150
CU 40 m
LCI 1BPA10_1
2725 kVA
LCI 1BPA10_2
2725 kVA
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
3-3/C 240
CU 40 m
Open
88WN-1
224 kW
1-3/C 70
CU 50 m
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
88WN-2
224 kW
1-3/C 70
CU 50 m
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 70 m
Open
88AK-1
375 kW
1-3/C 70
CU 50 m
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
88AK-2
375 kW
1-3/C 70
CU 50 m
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1-3/C 70
CU 100 m
Open
W-1BMB20
1XKA52
2000 kW
6-3/C 300
CU 50 m
Open
CARGAS 1BNB52
82,2 kVA
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
W-1BMB52
MBN50 AH010
450 kVA
1BJA80
400 kVA
W-1BJA12
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
2-3/C 185
CU 40 m 2-3/C 185
CU 40 m
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
Open
W-1BJA51W-1BJA11
2-3/C 240
CU 115 m
Bus25Bus24
Bus23Bus16 Bus14
Bus12 Bus11
Bus BS
Bus8Bus6
CGDE
0,48 kV
1MKA10
225 MW
1BAT10
13,33 %Z
220/18 kV
YNd1
300 MVA
-4,5% TapP
1BBT51
13,5 %Z
18/6,9 kV
Dyn11 11,5 MVA
2,5% TapP
1MKA76
8,44 MW
1BFT53
12 %Z
6,6/0,505 kV
Dyn11 3500 kVA
1BFT51
12 %Z
6,6/0,505 kVDyn11 3500 kVA
1MKC20
6 %Z
6,6/0,45 kV
Yd1 1500 kVA
Excitación 1MKC10
944 kVA
LCI 1BPA10_1
2725 kVA
1XKA52
2000 kW
88WN-1
224 kW
88AK-1
375 kW
88WN-2
224 kW
88AK-2
375 kW
MBN50 AH010
450 kVA
CARGAS 1BNB52
82,2 kVA
1BNT52
4 %Z
0,48/0,4 kV
Dyn1
150 kVA
W-1BJA51W-1BMB20W-1BJA12W-1BJA11
Narcissus
AL 2,92 km
6-3/C 300
CU 50 mW-1BMB52
1BJA80
400 kVA
3-3/C 300
CU 120 m
88WN-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88WN-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-1_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
88AK-2_XFR
6 %Z
6,6/4,16 kV
Yd1
600 kVA
1BFT76
4 %Z
6,6/0,505 kV
Dyn11
500 kVA
2,5% TapP
CARGAS 1BJA76
270 kVA
3-3/C 300
CU 20 m1-3/C 300
CU 20 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 50 m
1-3/C 70
CU 100 m
1-3/C 70
CU 70 m
1-3/C 70
CU 70 m
2-3/C 185
CU 40 m
2-3/C 185
CU 40 m
1-3/C 150
CU 40 m
3-3/C 240
CU 40 m
4-3/C 240
CU 40 m
1-3/C 70
CU 100 m
1-3/C 70
CU 50 m
1BPT10
6/6/6 %Z
6,6/2,08/2,08 kV
5450/2725/2725 kVA
LCI 1BPA10_2
2725 kVA
2-3/C 240
CU 115 m
Sistema PCI
200 kW
Red eléctrica Peruana
3022 MVAsc
1BBA51
6,6 kV
1BBA76
6,6 kV
1BFA51
0,48 kV
1BFA53
0,48 kV
1BJA76
0,48 kV
1BMA52
0,48 kV
1BNB52
0,38 kV
Bus5 Bus7
Bus9
Bus10 Bus13
Bus15Bus17
Bus18
Bus19
Bus20
Bus22
Bus EX
BUS GEN
18 kV
PCI_BUS
S.E. Etén
220 kV
S.E. Reque
220 kV
101,22
%
100,36
%
99,94%
94,93%
91,87%
104,42
%
99,93%
91,87%91,
87%
100,36
%
Isolated Phase CU
35 m
Open
Isolated Phase CU
35 m
Isolated Phase CU
8 m
Open
Open
Open
Open Open
4150 kW
4058 kvar
Open
295 kW
1281 kvar
One-Line Diagram - OLV1 (Motor Acceleration Analysis)
page 2 09:54:33 may 02, 2014 Project File: Eten
1BJA11
0,48 kV 91,54%
1BJA12
0,48 kV 91,62%
1BMB52
0,48 kV
91,75%
1BJA51
0,48 kV 91,74%
1BMB20
0,48 kV 91,67%
CARGAS 1BMB20
235 kVA
1MBV10AP001-M01
75 kW
1BMA52
4-3/C 240
CU 50 m
Compresor 1
37 kW
CARGAS 1BJA51
650 kVA
1BFA51
4-3/C 240
CU 20 m
1BMA52
2-3/C 150
CU 20 m
Compresor 2
37 kW
Open
CARGAS 1BMB52
231 kVA
CARGAS 1BJA12
592 kVA
6-3/C 240
CU 50 m
1BFA53
CARGAS 1BJA11
695 kVA
1MBV10AP002-M1
75 kW
6-3/C 240
CU 50 m
1BFA51
CARGAS 1BMB20
235 kVA
Compresor 1
37 kW
Compresor 2
37 kW
CARGAS 1BMB52
231 kVA
1BFA51
1BMA52 1BFA53 1BFA51
1MBV10AP001-M01
75 kW
4-3/C 240
CU 50 m
6-3/C 240
CU 50 m
6-3/C 240
CU 50 m
4-3/C 240
CU 20 m
2-3/C 150
CU 20 m
1BMA52
CARGAS 1BJA11
695 kVA
CARGAS 1BJA12
592 kVA
CARGAS 1BJA51
650 kVA
1MBV10AP002-M1
75 kW
1BJA11
0,48 kV
1BJA12
0,48 kV
1BJA51
0,48 kV
1BMB20
0,48 kV
1BMB52
0,48 kV
91,67%
91,74%
91,75%
Open
91,62%
91,54%
Ubicación:
Ingeniero:Caso de Estudio: MS-2
12.0.0C
Página: 1
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga @ T = 0.000-
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
% PFMW Mvar AmpID
XFMR
% Tap
6.6001BBA51 -2.8 102.798 84.61BBA76 0.180 0.113 18.100 00
91.5Bus17 0.134 0.059 12.4
0.0Bus18 0.000 0.000 0.0
82.1Bus19 2.527 1.758 262.0
88.7Bus20 0.758 0.395 72.8
84.7Bus22 -3.950 -2.483 397.0
91.2Bus15 0.351 0.158 32.7
6.6001BBA76 -2.8 102.796 84.61BBA51 -0.180 -0.113 18.100 00
84.6Bus9 0.180 0.113 18.1
0.4801BFA51 -7.8 100.804 0.0PCI_BUS 0.000 0.000 0.000 00
81.71BJA11 0.557 0.393 812.8
80.21BJA51 0.385 0.287 573.2
81.11BMA52 -0.942 -0.679 1385.9
0.4801BFA53 -7.8 100.804 0.181 0.704 80.01BJA12 0.404 0.303 602.800
86.7Bus19 -2.488 -1.429 3424.1
82.51BMA52 1.380 0.945 1995.8
0.4801BJA11 -7.8 100.495 0.391 0.555 81.71BFA51 -0.555 -0.391 812.800
0.4801BJA12 -7.8 100.575 0.302 0.403 80.01BFA53 -0.403 -0.302 602.800
0.4801BJA51 -7.8 100.673 0.286 0.385 80.21BFA51 -0.385 -0.286 573.200
0.4801BJA76 -3.3 103.725 0.110 0.177 85.0Bus9 -0.177 -0.110 242.000
0.4801BMA52 -7.8 100.804 87.21BMB20 0.249 0.140 340.400 00
80.01BMB52 0.125 0.094 186.2
89.51BNB52 0.065 0.032 86.1
81.11BFA51 0.942 0.679 1385.9
82.51BFA53 -1.380 -0.945 1995.8
0.4801BMB20 -7.8 100.614 0.139 0.248 87.21BMA52 -0.248 -0.139 340.400
0.4801BMB52 -7.7 100.688 0.094 0.125 80.01BMA52 -0.125 -0.094 186.200
0.3801BNB52 -8.4 104.199 0.031 0.064 90.01BMA52 -0.064 -0.031 103.300
4.000Bus5 -3.3 105.520 0.057 0.133 91.9Bus10 -0.133 -0.057 19.700
4.000Bus7 -4.1 103.241 0.145 0.342 92.1Bus13 -0.342 -0.145 51.900
6.600Bus9 -2.8 102.795 84.61BBA76 -0.180 -0.113 18.100 00
2.500 84.61BJA76 0.180 0.113 18.1
4.160Bus10 -3.3 101.476 91.9Bus5 0.133 0.057 19.700 00
91.9Bus17 -0.133 -0.057 19.7
4.000Bus13 -4.1 103.280 92.1Bus7 0.342 0.145 51.900 00
92.1Bus15 -0.342 -0.145 51.9
6.600Bus15 -2.8 102.768 91.21BBA51 -0.351 -0.158 32.700 00
91.2Bus13 0.351 0.158 32.7
6.600Bus17 -2.8 102.790 91.51BBA51 -0.134 -0.059 12.400 00
91.5Bus10 0.134 0.059 12.4
6.600Bus18 -2.8 102.798 0.01BBA51 0.000 0.000 0.000 00
Ubicación:
Ingeniero:Caso de Estudio: MS-2
12.0.0C
Página: 2
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga @ T = 0.000-
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
% PFMW Mvar AmpID
XFMR
% Tap
6.600Bus19 -2.8 102.776 82.11BBA51 -2.527 -1.758 262.000 00
82.11BFA53 2.527 1.758 262.0
6.600Bus20 -2.8 102.784 88.71BBA51 -0.758 -0.395 72.800 00
88.7Bus EX 0.758 0.395 72.8
6.900Bus22 -2.8 98.342 84.71BBA51 3.950 2.483 397.000 00
84.7BUS GEN -3.950 -2.483 397.0
0.480Bus EX -4.5 94.336 0.365 0.753 90.0Bus20 -0.753 -0.365 1067.300
18.000BUS GEN -0.1 104.572 82.1S.E. Etén -3.972 -2.767 148.500 00
2.500 82.1Bus22 3.972 2.767 148.5
0.480PCI_BUS -7.8 100.804 0.01BFA51 0.000 0.000 0.000 00
220.000S.E. Etén 0.0 99.991 82.0S.E. Reque -3.972 -2.777 12.700 00
-4.500 82.0BUS GEN 3.972 2.777 12.7
* 220.000S.E. Reque 0.0 100.000 86.6S.E. Etén 3.972 2.297 12.000 00
86.6Red eléctrica Peruana -3.972 -2.297 12.0
* 220.000Red eléctrica Peruana 0.1 100.092 2.304 3.973 86.5S.E. Reque 3.973 2.304 12.000
* Indica una barra con tensión regulada (con máquinas de tensión controlada o máquinas de referencia conectadas)
Ubicación:
Ingeniero:Caso de Estudio: MS-2
12.0.0C
Página: 3
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga @ T = 1,000+
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
% PFMW Mvar AmpID
XFMR
% Tap
6.6001BBA51 -2.9 100.360 84.61BBA76 0.176 0.111 18.100 00
91.5Bus17 0.134 0.059 12.7
0.0Bus18 0.000 0.000 0.0
63.1Bus19 2.730 3.359 377.3
88.7Bus20 0.723 0.377 71.0
71.1Bus22 -4.113 -4.064 504.0
91.2Bus15 0.351 0.158 33.6
6.6001BBA76 -2.9 100.358 84.61BBA51 -0.176 -0.111 18.100 00
84.6Bus9 0.176 0.111 18.1
0.4801BFA51 -8.5 91.870 25.4PCI_BUS 0.348 1.328 1798.000 00
81.81BJA11 0.545 0.384 872.3
80.31BJA51 0.354 0.263 577.7
53.41BMA52 -1.247 -1.975 3058.6
0.4801BFA53 -8.5 91.870 0.158 0.597 80.01BJA12 0.394 0.296 644.700
70.3Bus19 -2.648 -2.677 4930.5
59.81BMA52 1.658 2.224 3631.1
0.4801BJA11 -8.5 91.539 0.382 0.543 81.81BFA51 -0.543 -0.382 872.300
0.4801BJA12 -8.5 91.624 0.295 0.393 80.01BFA53 -0.393 -0.295 644.700
0.4801BJA51 -8.5 91.738 0.263 0.354 80.31BFA51 -0.354 -0.263 577.700
0.4801BJA76 -3.4 101.215 0.108 0.174 85.0Bus9 -0.174 -0.108 243.000
0.4801BMA52 -8.5 91.870 87.21BMB20 0.242 0.135 362.600 00
80.01BMB52 0.114 0.086 186.8
89.51BNB52 0.055 0.027 79.9
53.41BFA51 1.247 1.975 3058.6
59.81BFA53 -1.658 -2.224 3631.1
0.4801BMB20 -8.5 91.667 0.135 0.241 87.31BMA52 -0.241 -0.135 362.600
0.4801BMB52 -8.5 91.753 0.086 0.114 80.01BMA52 -0.114 -0.086 186.800
0.3801BNB52 -9.1 94.931 0.026 0.054 90.01BMA52 -0.054 -0.026 95.900
4.000Bus5 -3.4 102.950 0.057 0.133 91.9Bus10 -0.133 -0.057 20.200
4.000Bus7 -4.2 100.608 0.145 0.342 92.1Bus13 -0.342 -0.145 53.300
6.600Bus9 -2.9 100.357 84.61BBA76 -0.176 -0.111 18.100 00
2.500 84.61BJA76 0.176 0.111 18.1
4.160Bus10 -3.4 99.005 91.9Bus5 0.133 0.057 20.200 00
91.9Bus17 -0.133 -0.057 20.2
4.000Bus13 -4.2 100.648 92.1Bus7 0.342 0.145 53.300 00
92.1Bus15 -0.342 -0.145 53.3
6.600Bus15 -2.9 100.330 91.21BBA51 -0.351 -0.158 33.600 00
91.2Bus13 0.351 0.158 33.6
6.600Bus17 -2.9 100.352 91.51BBA51 -0.134 -0.059 12.700 00
91.5Bus10 0.134 0.059 12.7
6.600Bus18 -2.9 100.360 0.01BBA51 0.000 0.000 0.000 00
Ubicación:
Ingeniero:Caso de Estudio: MS-2
12.0.0C
Página: 4
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga @ T = 1,000+
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
% PFMW Mvar AmpID
XFMR
% Tap
6.600Bus19 -2.9 100.329 63.11BBA51 -2.728 -3.358 377.300 00
63.11BFA53 2.728 3.358 377.3
6.600Bus20 -2.9 100.347 88.71BBA51 -0.723 -0.377 71.000 00
88.7Bus EX 0.723 0.377 71.0
6.900Bus22 -2.9 96.015 71.11BBA51 4.114 4.065 504.000 00
71.1BUS GEN -4.114 -4.065 504.0
0.480Bus EX -4.6 92.099 0.348 0.718 90.0Bus20 -0.718 -0.348 1042.000
18.000BUS GEN -0.1 104.425 67.6S.E. Etén -4.149 -4.521 188.500 00
2.500 67.6Bus22 4.149 4.521 188.5
0.480PCI_BUS -6.8 87.967 1.281 0.295 22.41BFA51 -0.295 -1.281 1798.000
220.000S.E. Etén 0.0 99.927 67.5S.E. Reque -4.150 -4.538 16.100 00
-4.500 67.5BUS GEN 4.150 4.538 16.1
* 220.000S.E. Reque 0.0 99.941 71.5S.E. Etén 4.150 4.058 15.200 00
71.5Red eléctrica Peruana -4.150 -4.058 15.2
* 220.000Red eléctrica Peruana 0.1 100.092 4.070 4.151 71.4S.E. Reque 4.151 4.070 15.200
* Indica una barra con tensión regulada (con máquinas de tensión controlada o máquinas de referencia conectadas)
Ubicación:
Ingeniero:Caso de Estudio: MS-2
12.0.0C
Página: 5
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga @ T = 2,000+
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
% PFMW Mvar AmpID
XFMR
% Tap
6.6001BBA51 -3.0 102.474 84.61BBA76 0.179 0.113 18.100 00
91.5Bus17 0.134 0.059 12.5
0.0Bus18 0.000 0.000 0.0
81.4Bus19 2.735 1.952 286.8
88.7Bus20 0.754 0.393 72.5
84.1Bus22 -4.152 -2.674 421.6
91.2Bus15 0.351 0.158 32.8
6.6001BBA76 -3.0 102.472 84.61BBA51 -0.179 -0.113 18.100 00
84.6Bus9 0.179 0.113 18.1
0.4801BFA51 -8.4 99.687 84.9PCI_BUS 0.224 0.139 318.100 00
81.71BJA11 0.555 0.391 819.6
80.21BJA51 0.381 0.284 573.5
81.91BMA52 -1.160 -0.814 1710.4
0.4801BFA53 -8.4 99.687 0.178 0.690 80.01BJA12 0.403 0.302 607.600
86.5Bus19 -2.688 -1.558 3748.5
82.91BMA52 1.595 1.078 2322.4
0.4801BJA11 -8.4 99.375 0.390 0.553 81.71BFA51 -0.553 -0.390 819.600
0.4801BJA12 -8.4 99.455 0.301 0.402 80.01BFA53 -0.402 -0.301 607.600
0.4801BJA51 -8.4 99.555 0.283 0.381 80.21BFA51 -0.381 -0.283 573.500
0.4801BJA76 -3.4 103.392 0.110 0.177 85.0Bus9 -0.177 -0.110 242.100
0.4801BMA52 -8.4 99.687 87.21BMB20 0.248 0.139 342.900 00
80.01BMB52 0.123 0.093 186.2
89.51BNB52 0.063 0.031 85.3
81.91BFA51 1.160 0.814 1710.4
82.91BFA53 -1.595 -1.078 2322.4
0.4801BMB20 -8.4 99.494 0.139 0.247 87.21BMA52 -0.247 -0.139 342.900
0.4801BMB52 -8.4 99.570 0.092 0.123 80.01BMA52 -0.123 -0.092 186.200
0.3801BNB52 -9.0 103.040 0.030 0.062 90.01BMA52 -0.062 -0.030 102.400
4.000Bus5 -3.4 105.179 0.057 0.133 91.9Bus10 -0.133 -0.057 19.800
4.000Bus7 -4.2 102.891 0.145 0.342 92.1Bus13 -0.342 -0.145 52.100
6.600Bus9 -3.0 102.471 84.61BBA76 -0.179 -0.113 18.100 00
2.500 84.61BJA76 0.179 0.113 18.1
4.160Bus10 -3.4 101.148 91.9Bus5 0.133 0.057 19.800 00
91.9Bus17 -0.133 -0.057 19.8
4.000Bus13 -4.2 102.930 92.1Bus7 0.342 0.145 52.100 00
92.1Bus15 -0.342 -0.145 52.1
6.600Bus15 -3.0 102.445 91.21BBA51 -0.351 -0.158 32.800 00
91.2Bus13 0.351 0.158 32.8
6.600Bus17 -3.0 102.466 91.51BBA51 -0.134 -0.059 12.500 00
91.5Bus10 0.134 0.059 12.5
6.600Bus18 -3.0 102.474 0.01BBA51 0.000 0.000 0.000 00
Ubicación:
Ingeniero:Caso de Estudio: MS-2
12.0.0C
Página: 6
SN: IDOMINGC-3
Archivo: Eten
Proyecto: ETAP
Contrato:
Fecha: 02-05-2014
Revisión: Base
Config.: Normal
Informe de Flujo de Carga @ T = 2,000+
Barra
ID kV
Tensión
Áng.% Mag.
Generación
MW Mvar
Carga
MW Mvar
Flujo de Carga
% PFMW Mvar AmpID
XFMR
% Tap
6.600Bus19 -3.0 102.450 81.41BBA51 -2.734 -1.952 286.800 00
81.41BFA53 2.734 1.952 286.8
6.600Bus20 -3.0 102.460 88.71BBA51 -0.754 -0.393 72.500 00
88.7Bus EX 0.754 0.393 72.5
6.900Bus22 -3.0 98.033 84.11BBA51 4.152 2.675 421.600 00
84.1BUS GEN -4.152 -2.675 421.6
0.480Bus EX -4.6 94.038 0.363 0.749 90.0Bus20 -0.749 -0.363 1064.000
18.000BUS GEN -0.1 104.552 81.3S.E. Etén -4.177 -2.994 157.700 00
2.500 81.3Bus22 4.177 2.994 157.7
0.480PCI_BUS -8.5 98.859 0.138 0.222 85.01BFA51 -0.222 -0.138 318.100
220.000S.E. Etén 0.0 99.982 81.2S.E. Reque -4.177 -3.006 13.500 00
-4.500 81.2BUS GEN 4.177 3.006 13.5
* 220.000S.E. Reque 0.0 99.992 85.6S.E. Etén 4.177 2.526 12.800 00
85.6Red eléctrica Peruana -4.177 -2.526 12.8
* 220.000Red eléctrica Peruana 0.1 100.092 2.534 4.178 85.5S.E. Reque 4.178 2.534 12.800
* Indica una barra con tensión regulada (con máquinas de tensión controlada o máquinas de referencia conectadas)