With Reference to Undang-undang Kecil 1984 (Pindaan 2012)REVISION TO FIRE FIGHTING REQUIREMENTS

With Reference to Undang-undang Kecil 1984 (Pindaan 2012)

Part 2 : Passive Fire Requirements (Part VII)Part 3 : Active Fire Requirements (Fire alarms, Detection,

Extinguishment & Fire fighting Access) (Part VIII)

Part 5 : Summary

Part 1 : Introduction to Fire Requirements

Part 4 : Part IX - Miscellaneous

REVISION TO FIRE FIGHTING REQUIREMENTS

UBBL 1984 CONTENT

UBBL PARTS

PART I – PrelimBy law1-2

PART II- submission of plan for approval

By law 3-29

PART III- Space, light and ventilation

By law 30-47

PART IV – Temporary works in connection

with building operationsBy law 48-52

PART VI – Constructional requirement

By law 81-132

PART VII – Fire requirements

By law 133-224

PART VIII – Fire alarm, fire detection, fire

extinguishment, & fire access

By law 225-253

PART IX – Miscellaneous By law 254-258

& Schedule 1-10

PART V – Structural requirementsBy law 53-80

1.0 INTRODUCTION TO FIRE REQUIREMENTS

Undang-undang Kecil Bangunan 1984

Undang-undang Kecil 1984 (Pindaan 2012)

1.0 INTRODUCTION TO FIRE REQUIREMENTS

Part VII –

By Law 133 – 224

(92 By Laws)

Part VII –

By Law 133 – 224

(92 By Laws)

Part VIII –

By Law 225 – 253

(29 By Laws)

Part IX –

By Law 254 – 258

(5 By Laws)

FIRE FIGHTING REQUIREMENTS

Part 2 : Passive Fire Requirements (Part VII)Part 3 : Active Fire Requirements (Fire alarms, Detection,

Extinguishment & Fire fighting Access) (Part VIII)

Part 1 : Introduction to Fire Requirements

Part 5 : SummaryPart 4 : Part IX - Miscellaneous

Part VII –

By Law 133 – 224

(92 By Laws)

Part VII –

By Law 133 – 224

(92 By Laws)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

Part VII –

By Law 133 – 224

(92 By Laws)

CONTAINMENT

& PROTECTION

GENERAL & REFERENCE

RESCUE

CONTAINMENT

& PROTECTION

EXITS & EVACUATION

EXITS & EVACUATION

CONTAINMENT

& PROTECTION

Part VII –

By Law 133 – 224

(92 By Laws)

GENERAL & REFERENCE

GENERAL & REFERENCE

CONTAINMENT

& PROTECTION

CONTAINMENT

& PROTECTION

CONTAINMENT

& PROTECTION

CONTAINMENT

& PROTECTION

EXITS & EVACUATION

EXITS & EVACUATION

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

Part VII (Passive Fire Requirements)

1.0 GENERAL AND REFERENCE

2.0 CONTAINMENT & PROTECTION

3.0 EXITS AND EVACUATION

4.0 FIRE RESCUE

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

Heading By Law Description

1.0 GENERAL AND REFERENCE

133 Interpretation

134Designation of Purpose Groups

135 Rules of Measurement

209 Reference to buildings

215 Height of buildings

Reference to 5th Schedule 1) Purpose

Group & 2) Limit of

Compartmentation

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

Heading

2.0 CONTAINMENT &PROTECTION

2.1 COMPARTMENTATION

2.2 ELEMENTS

2.2.1 Separating Wall

2.2.2 External Walls

2.2.3 Structure

2.2.4 Shaft

2.2.5 AC System

2.2.6 Fire Stops

2.2.7 Doors2.2.8 Staircase

2.2.9 Moving walks

2.2.10 Lobbies

2.2.11 Surfaces & materials

2.2.12 Roofing2.3 FIRE RESISTANCE

2.4 DESIGNATED SPACE / SPECIAL PROVISION

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.1 COMPARTMENTATION

136Provisions of compartment walls and compartment floors

137Floor in building exceeding 30m in height to be constructed as compartment floors

138Other walls and floors to be constructed as compartment walls or compartment floors

139 Separation of fire risk areas

148Special requirements as to compartment walls and compartment floors

220Floor area and capacity of buildings and compartments

2.0 CONTAINMENT & PROTECTION

Reference to 5th

Schedule 1) Limit of

Compartmentation

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2.1 Separating Wall

141 Separating Walls

147 Construction of Separating Wall

2.2.2 External Walls

142 External Walls

144 Cladding on External Wall

145 Reference to 6th Schedule

146 Relevant Boundary

149Horizontal & vertical barriers at the external walls

2.2.3 Structure

143 Beams & Columns

2.2.4 Shaft

150 Protected Shafts

151 Ventilation to lift shaft

152 Openings in lift shafts

156 Protected shafts as ventilating duct

157 Protected shafts consisting of staircase

2.2.5 AC System

160 Fire precaution in air-conditioning systems

2.2.6 Fire Stops

161 Fire-stopping

2.2 ELEMENTS

2.0 CONTAINMENT & PROTECTION

Reference to 6th Schedule

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS

2.0 CONTAINMENT & PROTECTION

2.2.7 Doors

162 Fire Doors in compartment walls and separating walls

163 Half hour and one hour doors

164 Door closers for fire doors

193 Power operated doors as means of egress

2.2.8 Staircase

189 Enclosing means of escape in certain buildings

190 External Staircase

191 Openings in adjacent walls not permitted

198 Ventilation of staircase enclosures

199Ventilation of staircase enclosures in buildings not exceeding 18 metres

200Ventilation of staircase enclosures in buildings exceeding 18 metres

201 Staircase enclosures below ground level

202 Pressurized system for staircase

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS

2.0 CONTAINMENT & PROTECTION

2.2.9 Moving walks

192 Moving walks

2.2.10 Lobbies196 Smoke lobbies

197 Protected lobbies

2.2.11 Surfaces & materials

203 Restriction of spread of flame

204Classification of restriction of flame over surfaces of walls and ceilings

205 Classification of interior finish materials

206 Classification surfaces of wall or ceiling

207 Exceptions relating to ceilings

2.2.12 Roofing

208 Reference to Roofs

210 Construction of Roofs

211 Roofing materials

212Category designation for fire penetration and spread of flame on roof surface

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.3 Fire Resistance

213 Fire Resistance

214 Additional requirements

217 Fire Resistance of Structural member

218Compartment wall separating flats and maisonette

219 Application of theses by-laws to floors

221 Test of Fire Resistance

222 Fire Resistance for Walls

223Fire Resistance for Floor Above Ground Floor

224Fire Resistance for Any Elements of Structure

2.0 CONTAINMENT & PROTECTION

2.0 CONTAINMENT & PROTECTION

Reference to 9th

Schedule

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.4 Designated Space / Special Provision

158 Stages in places of assembly

159 Open stages

194 Building with single staircase

216 Single Storey Buildings

2.2 ELEMENTS

2.0 CONTAINMENT & PROTECTION

REVISED PASSIVE FIRE REQUIREMENTS

Reference to Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

Heading By Law Description

1.0 GENERAL AND REFERENCE

133 Interpretation

134Designation of Purpose Groups

135 Rules of Measurement

209 Reference to buildings

215 Height of buildings

Reference to 5th Schedule 1) Purpose

Group & 2) Limit of

Compartmentation

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

1.0 GENERAL AND REFERENCE 134 Designation of Purpose Groups

2.0 CONTAINMENT & PROTECTION

UBBL 1984

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

1.0 GENERAL AND REFERENCE 134 Designation of Purpose Groups

2.0 CONTAINMENT & PROTECTION

Undang-undang Kecil 1984 (Pindaan 2012

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

Heading

2.0 CONTAINMENT &PROTECTION

2.1 COMPARTMENTATION

2.2 ELEMENTS

2.2.1 Separating Wall

2.2.2 External Walls

2.2.3 Structure

2.2.4 Shaft

2.2.5 AC System

2.2.6 Fire Stops

2.2.7 Doors2.2.8 Staircase

2.2.9 Moving walks

2.2.10 Lobbies

2.2.11 Surfaces & materials

2.2.12 Roofing2.3 FIRE RESISTANCE

2.4 DESIGNATED SPACE / SPECIAL PROVISION

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.1 COMPARTMENTATION

136Provisions of compartment walls and compartment floors

137Floor in building exceeding 30m in height to be constructed as compartment floors

138Other walls and floors to be constructed as compartment walls or compartment floors

139 Separation of fire risk areas

148Special requirements as to compartment walls and compartment floors

220Floor area and capacity of buildings and compartments

2.0 CONTAINMENT & PROTECTION

Reference to 5th

Schedule 1) Limit of

Compartmentation

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.1 COMPARTMENTATION 136Provisions of compartment walls and compartment floors

2.0 CONTAINMENT & PROTECTION

UBBL 1984

* No revision to 5th Schedule –Limits of compartmentation

Undang-undang Kecil 1984 (Pindaan 2012

Standards

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.1 COMPARTMENTATION 137Floor in building exceeding 30m in height to be constructed as compartment floors

2.0 CONTAINMENT & PROTECTION

UBBL 1984

Undang-undang Kecil

1984 (Pindaan2012

Addition

Addition

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.1 COMPARTMENTATION 139 Separation of fire risk areas

2.0 CONTAINMENT & PROTECTION

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012

Addition

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2.1 Separating Wall

141 Separating Walls

147 Construction of Separating Wall

2.2.2 External Walls

142 External Walls

144 Cladding on External Wall

145 Reference to 6th Schedule

146 Relevant Boundary

149Horizontal & vertical barriers at the external walls

2.2.3 Structure

143 Beams & Columns

2.2.4 Shaft

150 Protected Shafts

151 Ventilation to lift shaft

152 Openings in lift shafts

156 Protected shafts as ventilating duct

157 Protected shafts consisting of staircase

2.2.5 AC System

160 Fire precaution in air-conditioning systems

2.2.6 Fire Stops

161 Fire-stopping

2.2 ELEMENTS

2.0 CONTAINMENT & PROTECTION

Reference to 6th Schedule

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 141 Separating Walls

2.0 CONTAINMENT & PROTECTION - ELEMENTS

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

Addition

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 144 Cladding on External Wall

2.0 CONTAINMENT & PROTECTION - ELEMENTS

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS

2.0 CONTAINMENT & PROTECTION

2.2.7 Doors

162 Fire Doors in compartment walls and separating walls

163 Half hour and one hour doors

164 Door closers for fire doors

193 Power operated doors as means of egress

2.2.8 Staircase

189 Enclosing means of escape in certain buildings

190 External Staircase

191 Openings in adjacent walls not permitted

198 Ventilation of staircase enclosures

199Ventilation of staircase enclosures in buildings not exceeding 18 metres

200Ventilation of staircase enclosures in buildings exceeding 18 metres

201 Staircase enclosures below ground level

202 Pressurized system for staircase

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 162 Fire Doors in compartment walls and separating walls

2.0 CONTAINMENT & PROTECTION - ELEMENTS

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

Cancelled

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 163 Half hour and one hour doors

2.0 CONTAINMENT & PROTECTION - ELEMENTS

UBBL 1984

Undang-undang Kecil 1984 (Pindaan 2012)

Cancelled

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 189 Enclosing means of escape in certain buildings

2.0 CONTAINMENT & PROTECTION - ELEMENTS

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

Cancelled

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 200Ventilation of staircase enclosures in buildings exceeding 18 metres

2.0 CONTAINMENT & PROTECTION - ELEMENTS

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

Standards

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 202 Pressurized system for staircase

2.0 CONTAINMENT & PROTECTION - ELEMENTS

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

Cancelled

Standards

2.2.8 Moving walks

192 Moving walks

2.2.9 Lobbies

196 Smoke lobbies

197 Protected lobbies

197AMeans of Access & Fire Fighting in buildings over 18m

197B Fire Fighting Access Lobby

2.2.10 Surfaces & materials

203 Restriction of spread of flame

204Classification of restriction of flame over surfaces of walls and ceilings

205 Classification of interior finish materials

206 Classification surfaces of wall or ceiling

207 Exceptions relating to ceilings

2.2.11 Roofing

208 Reference to Roofs

210 Construction of Roofs

211 Roofing materials

211A Construction Materials

212Category designation for fire penetration and spread of flame on roof surface

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS

2.0 CONTAINMENT & PROTECTION

NEW

NEW

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 197A Means of Access & Fire Fighting in buildings over 18m

2.0 CONTAINMENT & PROTECTION - ELEMENTS

Similar to By Law 197 / 229

Undang-undang Kecil 1984 (Pindaan 2012)

NEW

Fire Lift

Pressurize

Fire Fighting Access Lobby

Fire Staircase

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 197B Fire Fighting Access Lobby

2.0 CONTAINMENT & PROTECTION - ELEMENTS

Similar to By Law 242

Undang-undang Kecil 1984 (Pindaan 2012)

NEW

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 204Classification of restriction of flame over surfaces of

walls and ceilings

2.0 CONTAINMENT & PROTECTION - ELEMENTS

UBBL 1984

Cancelled

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 204Classification of restriction of flame over surfaces of

walls and ceilings

2.0 CONTAINMENT & PROTECTION - ELEMENTS

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 207 Exceptions relating to ceilings

2.0 CONTAINMENT & PROTECTION - ELEMENTS

UBBL 1984 Cancelled

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 207 Exceptions relating to ceilings

2.0 CONTAINMENT & PROTECTION - ELEMENTS

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 211 Roofing materials

2.0 CONTAINMENT & PROTECTION - ELEMENTS

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

Cancelled

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.2 ELEMENTS 211A Construction Materials

2.0 CONTAINMENT & PROTECTION - ELEMENTS

Undang-undang Kecil 1984 (Pindaan 2012)

NEW

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.3 Fire Resistance

213 Fire Resistance

214 Additional requirements

217 Fire Resistance of Structural member

218Compartment wall separating flats and maisonette

219 Application of theses by-laws to floors

221 Test of Fire Resistance

222 Fire Resistance for Walls

223Fire Resistance for Floor Above Ground Floor

224Fire Resistance for Any Elements of Structure

2.0 CONTAINMENT & PROTECTION

2.0 CONTAINMENT & PROTECTION

Reference to 9th

Schedule

No discrepancy

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.4 Designated Space / Special Provision

158 Stages in places of assembly

159 Open stages

194 Building with single staircase

216 Single Storey Buildings

2.2 ELEMENTS

2.0 CONTAINMENT & PROTECTION

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

2.4 DESIGNATED SPACE / SPECIAL PROVISION

194 Building with single staircase

2.0 CONTAINMENT & PROTECTION - ELEMENTS

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

3.0 EXITS AND EVACUATION

3.1 DETECTION & FIRE MODE OPERATIONS

3.2 EXITS CONSIDERATION

3.3 CAPACITY EXITS & OCCUPANCY LOAD

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

3.1 DETECTION & FIRE MODE OPERATIONS

153 Smoke detectors for lift lobbies

154Emergency mode of operation in the event of mains power failure

155 Fire Mode of Operation

172 Emergency Exit Signs

187 Notice affixed to door of gate

3.0 EXITS AND EVACUATION

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

3.1 DETECTION & FIRE MODE OPERATIONS

172 Emergency Exit Signs

3.0 EXITS AND EVACUATION

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

3.2 EXITS CONSIDERATION

165 Measurement of Travel Distance to Exits

166 Exits to be accessible at all times167 Storey Exits168 Staircases169 Exit Route

170 Egress through unenclosed openings

171 Horizontal exits173 Exit doors

174 Arrangement of storey exits

178 Exits for institutional and other places of assembly

182 Rate of discharge

183 Exit details for places of assembly

184 Seating

185 Gangway in places of assembly

186 Exit doors in places of assembly188 Travel distance in place of assembly

195 Staircases to reach roof level

3.0 EXITS AND EVACUATION

Reference to 7th

Schedule Part 1

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

3.2 EXITS CONSIDERATION 165 Measurement of Travel Distance to Exits

3.0 EXITS AND EVACUATION

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

3.2 EXITS CONSIDERATION Reference to 7th Schedule

UBBL 1984

3.0 EXITS AND EVACUATION

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

3.2 EXITS CONSIDERATION Reference to 7th Schedule

3.0 EXITS AND EVACUATION

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

3.2 EXITS CONSIDERATION 167 Storey Exits

3.0 EXITS AND EVACUATION

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

3.2 EXITS CONSIDERATION 168 Staircases

3.0 EXITS AND EVACUATION

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

3.2 EXITS CONSIDERATION 169 Exit Route

3.0 EXITS AND EVACUATION

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

3.3 CAPACITY EXITS & OCCUPANCY LOAD

175 Calculation of occupant load

176 Computing storey exit widths

177Computing number of staircases and staircase widths

179 Classification of places of assembly

180Space standards for calculating occupancy loads

181 Width of means of egress

3.0 EXITS AND EVACUATION

Reference to 7th

Schedule Part 2

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

3.3 CAPACITY EXITS & OCCUPANCY LOAD

7th Schedule - Calculations of Occupant Load & capacity Exits

3.0 EXITS AND EVACUATION

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

Heading By Law Description

4.0 FIRE RESCUE 140 Fire Appliances Access

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

4.0 FIRE RESCUE 140 Fire Appliances Access

UBBL 1984

CLASSIFICATION OF PASSIVE FIRE REQUIREMENTS

4.0 FIRE RESCUE 140 Fire Appliances Access

Undang-undang Kecil 1984 (Pindaan 2012)

FIRE FIGHTING REQUIREMENTS

Part 2 : Passive Fire Requirements (Part VII)Part 3 : Active Fire Requirements (Fire alarms, Detection,

Extinguishment & Fire fighting Access) (Part VIII)

Part 1 : Introduction to Fire Requirements

Part 5 : SummaryPart 4 : Part IX - Miscellaneous

Part VIII –

By Law 225 – 253

(29 By Laws)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

By Law Description

225 Detecting and extinguishing fire

226 Automatic system for hazardous occupancy227 Portable extinguishers228 Sprinkler valves

229 Means of Access & Fire Fighting in buildings over 18.3m

230 Installation & testing of dry rising system

231 Installation & testing of wet rising system

232 Wet or drying systems for buildings under construction

233 Foam inlets

234Underground structures & windowless buildings to have foam inlets

235 Fixed installations236 Special hazards

237 Fire alarms

238 Command & control centre239 Voice communication system240 Electrical isolating switch241 Special requirements for fire alarm systems

Reference to 10th

Schedule

By Law Description

242 Fire Fighting access lobbies

243 Fire lifts

244 Standard Required

245 Approval of D.G.F.S.

246 Certification on Completion

247 Water Storage

248 Marking on wet riser, etc.

249 Smoke and heat venting

250 Natural draught smoke vent

251Smoke vents to be adequate to prevent dangerous accumulation of smoke

252Smoke vents to be adequate to be openable by Fire Authority

253 Emergency power system

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

REVISED ACTIVE FIRE REQUIREMENTS

Reference to Undang-undang Kecil 1984 (Pindaan 2012)

By Law Description 225 Detecting and extinguishing fire226 Automatic system for hazardous occupancy

226A Hose Reel227 Portable extinguishers228 Sprinkler valves

229 Means of Access & Fire Fighting in buildings over 18.3m

230 Installation & testing of dry rising system231 Installation & testing of wet rising system

232 Wet or drying systems for buildings under construction

233 Foam inlets

234Underground structures & windowless buildings to have foam inlets

235 Fixed installations236 Special hazards237 Fire alarms238 Command & control centre239 Voice communication system240 Electrical isolating switch241 Special requirements for fire alarm systems

Reference to 10th

Schedule

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

NEW

cancel

By Law Description

242 Fire Fighting access lobbies

243 Fire lifts243A Emergency exits during power failure244 Standard Required

245 Approval of D.G.F.S.

246 Certification on Completion247 Water Storage

248 Marking on wet riser, etc.

249 Smoke and heat venting

250 Natural draught smoke vent

251Smoke vents to be adequate to prevent dangerous accumulation of smoke

252 Smoke vents to be adequate to be openable by Fire Authority

252A Atrium in building

253 Emergency power system

253A Emergency light

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

cancel

NEW

NEW

NEW

cancel

cancel

cancel

225 Detecting and extinguishing fire

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

10th SCHEDULE

REVISED ACTIVE FIRE REQUIREMENTS

Reference to Undang-undang Kecil 1984 (Pindaan 2012)

UBBL 1984

10th Schedule Schedule for Detection Fire, Alarm & Extinguishment System

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

10th Schedule Schedule for Detection Fire, Alarm & Extinguishment System

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

10th Schedule Schedule for Detection Fire, Alarm & Extinguishment System

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

10th Schedule Schedule for Detection Fire, Alarm & Extinguishment System

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

10th Schedule Schedule for Detection Fire, Alarm & Extinguishment System

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

226A Hose reel

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

NEW

UBBL 1984

227 Portable extinguishers

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

228 Sprinkler valves

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

229 Means of Access & Fire Fighting in buildings over 18.3m

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

230 Installation & testing of dry rising system

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

Selangor UBBL 1986 (Revision 2012)UBBL 1984

231 Installation & testing of wet rising system

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

235 Fixed installations

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

236 Special hazards

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

237 Fire alarms

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

238 Command & control centre

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

239 Voice communication system

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

240 Electrical isolating switch

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

243A Emergency exits during power failure

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

NEW

248 Marking on wet riser, etc.

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

251 Smoke vents to be adequate to prevent dangerous accumulation of smoke

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

252A Atrium in building

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

NEW

253 Emergency power system

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

253A Emergency lights

Undang-undang Kecil 1984 (Pindaan 2012)

CLASSIFICATION OF ACTIVE FIRE REQUIREMENTS

NEW

FIRE FIGHTING REQUIREMENTS

Part 2 : Passive Fire Requirements (Part VII)Part 3 : Active Fire Requirements (Fire alarms, Detection,

Extinguishment & Fire fighting Access) (Part VIII)Part 4 : Part IX - Miscellaneous

Part 1 : Introduction to Fire Requirements

Part 5 : Summary

Part IX –

By Law 254 – 258

(5 By Laws)

PART IX - MISCELLANEOUS

By Law Description

254 Buildings to which Parts VII and VIII apply

255 Power of local authority to extend period, etc.

256 Buildings exempted

257Malaysian Standard Specification and Code of Practice to prevail over British Standard Specification and Code of Practice

258 Failure to buildings

PART IX - MISCELLANEOUS

Reference to Undang-undang Kecil 1984 (Pindaan 2012)

PART IX - MISCELLANEOUS

By Law Description

254 Buildings to which Parts VII and VIII apply

255 Power of local authority to extend period, etc.

256 Buildings exempted

257Malaysian Standard Specification and Code of Practice to prevail over British Standard Specification and Code of Practice

258 Failure to buildings

256 Buildings exempted

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

PART IX - MISCELLANEOUS

257Malaysian Standard Specification and Code of Practice to prevail over British

Standard Specification and Code of Practice

UBBL 1984 Undang-undang Kecil 1984 (Pindaan 2012)

PART IX - MISCELLANEOUS

UBBL 1984

258 Failure to buildings

PART IX - MISCELLANEOUS

258 Failure to buildings

Undang-undang Kecil 1984 (Pindaan 2012)

PART IX - MISCELLANEOUS

FIRE FIGHTING REQUIREMENTS

Part 2 : Passive Fire Requirements (Part VII)Part 3 : Active Fire Requirements (Fire alarms, Detection,

Extinguishment & Fire fighting Access) (Part VIII)Part 4 : Part IX - Miscellaneous

Part 1 : Introduction to Fire Requirements

Part 5 : Summary

SUMMARY

Parts of By LawsTotal By Laws Amendment Cancelled New By Laws

1.0Part VII (Passive Fire Requirements)

92 21 1 3

2.0

Part VIII - Active Fire Requirements (Fire alarms, Detection, Extinguishment & Fire fighting Access)

29 14 8 4

3.0 Part IX - Miscellaneous 5 3 0 0

4.0 5th Schedule - Purpose Group amended5th Schedule - Limit of Compartmentation No amendment

5.06th Schedule - Limits of Openings on Unprotected area No amendment

6.0 7th Schedule - Travel Distance amended7th Schedule - Occupancy Load amended

7.010th Schedule - Fire Alarms & Extinguishment System amended

PART VII - PASSIVE FIRE REQUIREMENTS – Amended By Laws

SUMMARY

CONTAINMENT & PROTECTION

136 Provisions of compartment walls and compartment floors

137Floor in building exceeding 30m in height to be constructed as compartment floors

139 Separation of fire risk areas141 Separating Walls144 Cladding on External Wall

162 Fire Doors in compartment walls and separating walls

163 Half hour and one hour doors

189 Enclosing means of escape in certain buildings

200Ventilation of staircase enclosures in buildings exceeding 18 metres

202 Pressurized system for staircase

204Classification of restriction of flame over surfaces of walls and ceilings

207 Exceptions relating to ceilings

211 Roofing materials

222 Fire Resistance for Walls

194 Building with single staircase

PART VII - PASSIVE FIRE REQUIREMENTS – Amended By Laws

SUMMARY

EXITS AND EVACUATION

172 Emergency Exit Signs

165Measurement of Travel Distance to Exits

167 Storey Exits

168 Staircases

169 Exit Route

FIRE RESCUE 140 Fire Appliances Access

PART VII - PASSIVE FIRE REQUIREMENTS – Cancelled By Laws

SUMMARY

154 Emergency mode of operation in the event of mains power failure

PART VII - PASSIVE FIRE REQUIREMENTS – New By Laws

SUMMARY

197AMeans of Access & Fire Fighting in buildings over 18m

197B Fire Fighting Access Lobby

211A Construction Materials

PART VIII - ACTIVE FIRE REQUIREMENTS – Amended By Laws

SUMMARY

By Law Description 225 Detecting and extinguishing fire227 Portable extinguishers228 Sprinkler valves

229Means of Access & Fire Fighting in buildings over 18.3m

230 Installation & testing of dry rising system

231 Installation & testing of wet rising system

235 Fixed installations

236 Special hazards

237 Fire alarms

238 Command & control centre239 Voice communication system240 Electrical isolating switch

251Smoke vents to be adequate to prevent dangerous accumulation of smoke

253 Emergency power system

PART VIII - ACTIVE FIRE REQUIREMENTS – Cancelled By Laws

SUMMARY

By Law Description 233 Fioam inlets

234Underground structures & windowless buildings to have foam inlets

242 Fire Fighting access lobbies

243 Fire lifts

244 Standard Required

246 Certification on Completion

247 Water Storage

252Smoke vents to be adequate to be openable by Fire Authority

PART VIII - ACTIVE FIRE REQUIREMENTS – New By Laws

SUMMARY

By Law Description

226A Hose Reel

243A Emergency exits during power failure

252A Atrium in building

253A Emergency light

PART IX - MISCELLANOUS– Amended By Laws

SUMMARY

By Law Description 225 Detecting and extinguishing fire227 Portable extinguishers228 Sprinkler valves

229Means of Access & Fire Fighting in buildings over 18.3m

230 Installation & testing of dry rising system

231 Installation & testing of wet rising system

235 Fixed installations

236 Special hazards

237 Fire alarms

238 Command & control centre239 Voice communication system240 Electrical isolating switch

251Smoke vents to be adequate to prevent dangerous accumulation of smoke

253 Emergency power system

PART IX - MISCELLANEOUS

By Law Description 256 Buildings exempted

257

Malaysian Standard Specification and Code of Practice to prevail over British Standard Specification and Code of Practice

258 Failure to buildings