review of the station nightclub fire - michigan state … folder/ce 808 fire course... · web...
TRANSCRIPT
A Comparison of the Fire Performance of
Prestressed Concrete Double T-beams
using Design Provisions and SAFIRThe
Station Nightclub Fire Evaluation
CE 808: Structural Fire Engineering
FridayMonday, AprilFebruary 814, 2008
Nickolas Hatinger
Megan Vivian
Table of Contents
I. Introduction .................................................................................................1
II. Literature Review ......................................................................................2
A. General ........................................................................................................2
B. Experimental Studies ...................................................................................2
C. Analytical Studies ........................................................................................6
III. Structural Models ......................................................................................8
IV. Design Codes ............................................................................................10
A. General ......................................................................................................10
B. American ....................................................................................................11
C. Canadian ....................................................................................................12
D. Eurocode ....................................................................................................13
V. SAFIR .......................................................................................................14
VI. Results/Discussion ....……………………………………………………16
VII. Conclusions ...............................................................................................17
VIII. Acknowledgements ..................................................................................18
IX. References ................................................................................................20
APPENDIX A: Sample Calculations .................................................................22
APPENDIX B: SAFIR Input Files .....................................................................40
I. Introduction
II. Literature Review
A. General
B. Experimental Studies
C. Analytical Studies 5
III. Structural Models
IV. Design Codes
A. General
B. American 10
C. Canadian 11
D. EuroCode
V. SAFIR
VI. Results
VII. Conclusions 2
VIII. Acknowledgements 3
IX. References 4
I. Introduction ............................................................................................................1
II. The Station Nightclub Fire ...................................................................................1
A. Structural and Material Features ............................................................................1
B. Ignition of Fire .........................................................................................................2
C. Fire Growth .............................................................................................................2
D. Fire Protection Features .........................................................................................3
E. Fire Service Response ..............................................................................................3
F. Structural Effects Due to Fire ..................................................................................3
G. Aftermath .................................................................................................................4
III. Lessons to be Learned ...........................................................................................4
A. NIST Investigations ..................................................................................................4
B. Human Behavior ......................................................................................................5
C. Recommendations ....................................................................................................5
IV. Conclusions .............................................................................................................6
V. References ................................................................................................................7
2
AbstractThe fire performance of two prestressed concrete double T-beams were assessed
using the tabulated data and simplified calculations under the American, Canadian, and
European design provisions, as well as with a performance-based approach, SAFIR. A
10DT24+2 and 12DT32+2 simply supported beams were selected as representative
beams typically incorporated into retail stores or parking structures, with spans of 40 and
50 ft., respectively. The design provisions coincided well with one another, but the
tabulated data fire ratings under the Canadian code proved to be slightly conservative.
Similarly, the SAFIR results were consistent with the design provisions for the
10DT24+2, but diverged slightly for the 12DT32+2 and were contributed to lack of
available temperature distributions for 90 minutes. Overall the prescriptive-based design
provisions provided reasonable results, but it is been suggested that American and
Canadian codes incorporate an advanced calculation method to promote accurate and
efficient fire safety designs.The purpose of this paper is to present a case study to
compare current structural fire safety design provisions in the United States, Canada, and
Europe to finite elements methods using SAFIR.The purpose of this paper is to present an
overview of The Station nightclub fire that led to death of 100 and injured 200 patrons on
February 20, 2003. The overview consists of a description the building’s features and
materials, fire ignition and growth, fire protection systems, response of emergency units,
and aftermath of the fire. In addition, it highlights the several simulations and tests
conducted by the NIST investigation to identify any negligence in safety of the nightclub
and further work that could be done to ensure safety among similar public structures. It
was conclude that fire severity or the event as whole could have been avoided if proper
building materials, sprinkler systems, and considerations of egress would have been
accounted for in the buildings design.
4
I. IntroductionIntroduction
II.
Fires are among earthquakes, hurricanes, floods, tornadoes, and blasts as one of
the most destructive forces subjected to a structure. In 2006, fire’s caused 3,245 civilian
fatalities, 16,400 civilian injuries, and $11,307,000,000 in property loss throughout the
United States, alone. A total of 524,000 structural fires contributed to $9.6 billion dollars
in property damage (Karter, 2007). The devastation and unpredictability of such
catastrophes is the reason why design provisions demand structures to meet minimal fire
safety requirements.
The philosophy of most design provisions around the world is to ensure life safety
and minimize property damage in the event of a fire. Commonly this is accomplished
through a prescriptive-based approach, which assigns structural elements fire ratings
through tabulated data derived from standard fire tests. Although widely practiced it is
limited in scope and restrictive in application. Therefore, countries such as New Zealand,
United Kingdom, Australia, Japan, Sweden, other European countries have moved
towards a performance-based methodology. The new method is intended to capture the
complexities of the event through the introduction of realistic fire scenarios (variation in
fuel loads and ventilation), loading regimes, and restraint, in attempt to develop a rational
and economic design alternative.
The purpose of this paper is to present a case study to compare the fire
performance of two precast prestressed concrete double T-beams through various
methods. The methods consist of design provisions from American, Canadian, and
European codes, as well as a finite-element methods using SAFIR to predict the
1
members’ fire response. The goals of the study are to illustrate the limitations of the
prescriptive-based approach and to promote the performance-based movement in an
attempt to accurately and efficiently predict the fire response of structural elements.
The following paper consists of seven main sections. First, is the introduction
discussed previously. Second, is the literature review, which identifies similar analytical
studies conducted in the past. In addition, a few experimental studies to explore how the
current provisions were established for the fire performance of prestressed concrete
beams. In the third section, a description of the structural models and loading are
presented. Overviews of the relevant codes are discussed in the fourth section. The
computer program SAFIR, used in the comparison, is detailed in the fifth section. Sixth,
are the results of the comparison. Finally, in the seventh section the relevant conclusions
are addressed.
In the Unites States alone, fires contribute to 3,245 civilian fire fatalities and
approximately $11,307,000,000 in property loss in 2006. Of this, about 524,000 fires
took place in structures; which accounted for $9.6 billion dollars in property damage
(Karter, 2007). A very small percentage of these structural fires typically occur in
nightclubs or similar venues, yet these occurrences lead to remarkably high numbers of
casualties.
One such structural fire, on the evening of February 20, 2003, at The Station
nightclub in Warwick, Rhode Island, took the lives of 100 civilians (FEMA, 2004). The
pyrotechnic display from the nightly entertainment created a spark causing ignition of
surrounding foam insulation and subsequently engulfed the entire building in flames.
Due to overcrowding and panicked egression of The Station, patrons were unable to
evacuate from the quick spreading fire and many perished that evening. Investigations
have been completed to determine any negligence in safety of the nightclub and further
work that can be done to ensure safety among similar public structures.
Literature Review
2
A. General
In the following discussion a series of experimental studies are reviewed to briefly
illustrate how the current prescriptive-based provisions were developed from standard
fire tests for prestressed concrete beams. In conclusion, the similarities among the
studies are highlighted and their limitations are identified. Subsequently, several
analytical studies are presented to provide similar research findings.
B. Experimental Studies
In general, most fire tests of precast prestressed concrete beams have been
performed to establish prescriptive-based codes under standard fire exposure. Most of
the ratings depend on concrete cover, cross-sectional area, reinforcement axis distance,
restraint, or insulation thickness. Many of these investigations were used not only to
establish design provisions, but also to validate models and identify prevalent failure
modes under elevated temperatures. The following are a series of fire test conducted to
establish current prescriptive-based design codes in the United States.
Gustaferro and Carlson (1962) compiled 50 standard fire tests on precast
prestressed concrete building components and conducted tests on a variety beams and
slabs to determine the factors which affect fire resistance. The tests were conducted from
1953 to 1961 collectively by the National Bureau of Standards, Underwriters
Laboratories, Portland Cement Association, and Fire Prevention Research Institute. An
assortment of span lengths, insulation thicknesses, aggregate types and cross sections of
members such as I-shaped, double-tee, and single-tee beams, as well as flat hollow-core,
solid, and stemmed floor assemblies were tested in accordance with ASTM E 119. The
factors which affected the fire resistance of the precast prestressed components were
3
concrete cover, degree of restraint, cross-sectional area, member geometry, aggregate
type, and concrete moisture content. The main factors which affected the strand
temperature were concrete cover, cross-sectional area, member shape, type of aggregate
and insulating protection. Although, all of the details of restraint were not provided for
each study, it proved to significantly increase the member’s fire resistance and typically
failed due to heat transmission. Conversely, the failure mode for unrestrained beams
primarily was due to prestressing strands exceeding their critical temperatures (850 to
950°F). Other key observations were that lightweight aggregates provided better fire
resistance than normal weight aggregates. The moisture content only became an issue
once 70% relative humidity was exceeded. Similarly, the vermiculite insulation has
proven to provide greater fire ratings as long as it remains bonded to the concrete.
Finally, a comparison of one studies results tabulated in Table 1 were deemed consistent
with the other tests, but was considered slightly conservative.
Table 1: Cover for various fire resistances (Gustaferro and Carlson 1962).
4
Selvaggio and Carlson (1964) performed a study on the influence of aggregate
type and load intensity on the fire resistance of twenty two prestressed concrete I-beams.
The beams were tested under standard fire tests with three-sided exposure and spanned
20 ft. Three different normal (dolomitic or siliceous) and lightweight (expanded shale’s)
aggregates were used. Two loading intensities were uniformly applied through different
live and dead load combinations. The results yielded, lightweight aggregates exhibited
the best fire performance and were remarkably similar. The dolomitic aggregates
exhibited the best fire performance of the normal weight aggregates, through delayed
heat transmission affects. Lightweight aggregate beams failed in a compressive manner,
while the normal weight aggregate beams failed in tension. When considering varying
load intensities, the heavier loading regime failed quicker with greater midspan
deflections. A few beams were restrained and revealed a 22% better fire performance
than simply supported beams. In addition, less thrust was observed in the expanded shale
aggregates compared to the normal weight aggregates.
Abrams and Gustaferro (1972) conducted fire endurance tests of four prestressed
concrete double T-beams with spray-applied insulation. Two different cross sections
were tested under the ASTM E119 standard fire with unrestrained support conditions. A
control specimen and two more beams with ½ and 1 in. of vermiculite acoustical plastic
insulation, consisted of one cross section. The other beam section used ½ in. mineral
fiber insulation. Their fire endurances were 1 hr. 2 min., 1 hr. 50 min., 3 hr. 6 min., and 2
hr. 28 min., respectively. Both types of insulation maintained adhesion throughout the
tests. A prescriptive based tabulated approach was suggested for 2 and 3 hr. ratings,
based on stem width, concrete cover, type and thickness of insulation.
5
The majority of the fire tests for the prestressed concrete beams were performed
in the 1960’s and 1970’s. Although these results are invaluable in determining many of
the factors affecting the members’ fire performance they are limited to standard fire
exposure and are not applicable to other potential fire scenarios. Other issues are raised
when considering the variability in size of the test specimens, because full-scale
specimens fail in different mechanisms than large specimens. In addition, although some
of the studies included restraint, it is only vaguely understood to improve the fire
resistance without any rational understanding to quantify such a scenario. Therefore,
crude tabulated fire ratings are assigned to a multitude of beams based on handful of fire
tests. The tabulated data limits a designer’s ability to push the envelope for new designs
and prevents new materials to be used without costly fire tests to assure fire ratings.
C. Analytical Studies
While reviewing the literature, no specific case studies were found that compared
fire ratings among different countries design provisions. However, several papers were
discovered in which finite-element methods were used to accurately estimate the fire
performance of prestressed concrete beams. The methods used in the studies are
examples of the types of procedures that are regularly used in a performance-based
methodology. The following are significant findings of each study.
Anderson and Laurisden (1999) undertook a comparison of prescribed fire ratings
to a series of calculations for prestressed concrete double T-beams roof assemblies. Four
participants (DTI, PJK, DTU, and FSD) used different calculation methods to determine
the fire ratings. Three used finite element programs (FEM), while the other performed
simplified calculation methods. The fire endurance calculations and tests were in
6
accordance with standard fire test method ISO 834. Three beams were tested and
modeled. The beams differed through their location of the prestressing steel from the
bottom flange (57, 73, and 83 mm). However, the second specimen temperature-time
curve was greater than ISO 834; therefore it was excluded from the results. Table 2
illustrates the results.
Table 2: Analysis method and fire test results (Anderson and Laurisden 1999).
All three beams failed initially to bond failure followed by shear fracture.
Spalling was observed in all three tests on the bottom surface of the slab between the
stems. The average fire resistance time calculated for type 1 and 3 beams were 36 and
6% greater than the actual fire tests. Although the moment calculations were similar for
7
DTI, DTU, and PJK, the shear and anchorage failure calculations were scattered. The
variations of the results are attributed to different material property reductions and bond
models incorporated in the different methods.
Franssen and Bruls (1997) performed a state-of-art analysis on a precast
prestressed concrete double-T beam to verify the results of a previous experiment under
the ISO 834 standard fire exposure. The manufacturer prescribed a 2 hr. fire rating for
the beams based solely on its ultimate bending capacity; however the test specimen failed
in 79 min. Therefore, the authors conducted a nonlinear thermo-mechanical analysis,
using a computer program called SAFIR, to validate the test. The bending capacity
analysis resulted in a fire rating of 91 min. and led to the conclusion that the beam failed
in a shear failure mode. The ultimate shear resistance was calculated using the method
proposed in Eurocode 2-Part 1-1. The study considered the contributions of the steel
stirrups, prestressing tendons, and concrete to the beams shear strength. As a result, the
calculations coincided very well with the tests at 80 min. However, the beam did not
satisfy code requirements; therefore the beam was modified in SAFIR to provide a fire
resistance for shear and bending moment of 135 and 130 min., respectively. A
subsequent fire test yielded a fire endurance of 144 min.
These studies proved that advanced calculation methods often used in
performance-based design procedures can yield accurate results. Although, these
methods are not always the best solution to a problem, in time they may minimize cost
associated with expensive fire tests for validation once a certain degree of confidence is
established. The structural models used for the comparison in this paper are discussed
next.
III. The Station Nightclub FireStructural Models
8
Figures 1 and 2 illustrate the two precast prestressed concrete double T-beams
selected arbitrarily to represent a typical floor/roof assembly used in shopping centers or
parking garages. A 12DT32+2 and 10DT24+2 spanning 50 and 40 ft., respectively, were
selected from the PCI Design Handbook (PCI, 2004). All of the relevant dimensions and
material properties are also shown in the figures 1 and 2 below. The beams are assumed
to be simply supported and loaded uniformly. A live load of 100 psf was used to
represent a typical live load for the first floor of a retail store (ASCE, 2005). The load
combinations and other specifics will be determined per code and will be discussed in the
next section.
Figure 1: Dimensions and properties for the 12DT32+2
9
Figure2: Dimensions and properties for the 10DT24+2
IV. Design Codes
A. General
Most countries throughout the world require structures to meet minimal fire safety
requirements. Typically, design provisions offer a hierarchy of design methods, such as
tabulated data, simplified calculations, and advanced methods. The hierarchy varies in
complexity of application, with the tabulated data being the easiest and the advanced
methods being the most arduous. Therefore, most design provisions are typically
established through either tabulated data or simplified calculations. However, in recent
years performance-based methods have come to the fore, offering more flexibility to
designers through a rational approach. Discussed below is an overview of U.S,
Canadian, and European design provisions used.
11
B. American
All concrete structures in the United States are designed in accordance with the
American Concrete Institute standards (ACI 318, 2005). However, this guide references
ACI 216 (2001) for the fire provisions of concrete structural members. The ACI
provisions provided for prestressed concrete beams are similar to the Precast/Prestressed
Concrete Institute Design Handbook (2004) and International Building Code (2006).
These codes offer tabulated data and simplified procedures to establish the fire
performance of a prestressed concrete beam. The ratings are valid for three-sided ASTM
E 119 standard fire exposure. The tabulated fire rating for the beams are based on
minimum concrete cover and depend on restraint, aggregate type, and either beam width
or cross-sectional area, depending on the table used. The restraint is categorized either
as restrained or unrestrained. The aggregate types are classified as either carbonate or
siliceous, lightweight or semi-lightweight, or all. Through these parameters a concrete
cover for fire ratings of 1, 1½, 2, 3, or 4 hours. Similarly, tabulated data is provided for
determining a fire rating based on the heat transmission failure criteria for slab and is
based on its thickness and type of aggregate.
Alternatively, ACI 216 provides guidelines for an analytical approach to
determine the fire resistance of prestressed concrete flexural members based on the
ASTM E119 standard fire condition. The method assumes that flexural tension governs
the design. The fire resistance is determined through curves based on heat transfer
principles to establish the temperatures in the prestressing steel and requires the type of
aggregate, moment intensity, minimum cover and reinforcement index. The temperatures
are used to asses the reduced strength and moment capacity of the section. The
12
remaining moment capacity must be greater than a load combination of 1.2D + 0.5L. It
should be noted that no advanced calculation methods, are currently available.
C. Canadian
The National Building Code of Canada (2004) governs concrete structures and
has very similar provisions as the Americans. The provisions provided for prestressed
concrete beams are prescriptive in nature. The method includes tabulated data to assess
the fire rating of 30, 45, 60, 90, 120, 180, or 240 minutes. The ratings are based on
concrete cover and depend on type of concrete and area of beam. The two types of
concrete are characterized as type S or N gravels, or type L for lightweight aggregates.
The dense aggregates is subdivided into 3 different intervals of area, while the
lightweight aggregates only apply once the area of the member has exceeded 970 mm2 .
The ratings are for unrestrained members and are applicable for either independent or
integral slabs or roof components. It is assumed that the unrestrained condition will
govern and will suffice for the restrained conditions. Subsequent provisions provide
multiplying factors when plaster or other fire proofing materials are present. Similarly,
tabulated data is provided for determining a fire rating based on the heat transmission
failure criteria for slab and is based on its thickness and type of concrete.
Alternatively, a Canadian design guide, CPCI (2007) offers a rational design
approach through simplified calculations using reduced material properties due to
elevated temperatures and is very similar to the Americans. However, it should be noted
that adequate temperature profiles were not available for 1, 3, and 4 hr ratings; therefore
the American temperatures were used. Furthermore, the load combination suggested was
D + L or service loads. Note, that no advanced methods were offered.
13
D. Eurocode
The majority of European countries design concrete structures in accordance with
the European Standards or better known as “Eurocode” (2004). All reinforced concrete
structures are governed by EN 1992-1-1 and the fire provisions are supplied in EN 1992-
1-2. The provisions offer tabulated data, simplified calculations and advanced methods.
The quickest method to crudely determine the fire resistance of a prestressed beam is
through the tabulated data. The tabulated prescriptive method gives fire ratings for 30,
60, 90, 120, 180, and 240 minutes for a three-sided fire exposure of prestressed beams.
The ratings are based on minimum beam width of the exposed flange, average axis
distance of tendon to the exposed surface, and web thickness for rectangular, tapered and
I-section beams. Two primary tables are supplied based on support conditions, either
simply or continuously supported. In addition, provisions suggest an increase in the axis
distance and beam widths for prestressing members. Another provision allows the
previous tables mentioned to be applicable for four-sided fire exposure, if minimum
beam area and height are met. Similarly, tabulated data is provided for determining a fire
rating based on the heat transmission failure criteria for slabs, which is based on its
thickness.
An alternative to the tabulated method is through simplified calculations similar
to the American and Canadian codes. It is incorporated similarly to actual design
procedure, except that reduced properties are applied for given temperature exposures.
However, it should be noted that adequate temperature profiles were not available for
tapered beams; therefore the American temperatures were used. The reduced properties,
such as cross-sectional area, yield strength of prestressing steel, and compressive strength
14
of various types of concrete are tabulated for different temperatures. In addition,
expressions are available for thermal and mechanical properties, as well as stress-strain
relations at elevated temperatures. The load combination suggested was D + 0.9L. The
advanced methods presented suggest requirements for a performance-based design for the
mechanical, thermal, and spalling of concrete, but also require validation of models.
V. SAFIR
SAFIR is a 3D thermal-mechanical analysis program used to assess the fire
performance of structural elements. The finite-element-method (FEM) incorporates
nonlinear temperature dependent properties and stress distributions. The twofold
procedure consists of first creating a thermal model. A thermal model is a 2D cross
section of the member discretized into nodes and elements of different materials, as
shown in figure 3. The model is exposed to a standard fire exposure to produce a The
model is exposed to a standard fire exposure to produce a temperature distribution at a
specific time as shown in figure 4. The second part of the
15
Figure 3: Discretization of model Figure 4: Temperature distributions
temperature distribution at a specific time as shown in figure 4. The second part of the
procedure consists of a structural analysis. Similarly, the structural model is discretized
into a series of nodes and elements to create a beam. The loading and support conditions
are established and the temperature distributions at given time increments are used to
assess the reduced properties at elevated temperatures. These reduced properties are used
in the structural analysis to determine the internal forces and deflections until collapse.
SAFIR was used to incorporate a performance-based approach to determine the
fire endurance of the prestressed concrete double T-beams. An analysis case was
performed for each design provision, since they incorporated different loading
16
VI. Results/Discussion
Tables 3 and 4 show the fire performance of the 10DT24+2 and 12DT32+2
beams, respectively. The tables present the fire ratings per code in hours and the fire
endurance times using SAFIR in minutes. Please refer to appendix A and B for the
sample calculations and SAFIR input files, respectively. In addition, ambient
temperature calculations are provided.
Table 3: 10DT24+2 Fire resistance results
10DT24+2FIRE RESISTANCE (hr.)
Code: American Canadian EuropeanLoad Combination: 1.2D+.5L D+L D+0.9LTabulated: 1 1/2 1 1 1/2Simplified Calculations: 1 1 1SAFIR (min): 64 60 61
Table 3: 10DT24+2 Fire resistance results
12DT32+2FIRE RESISTANCE (hr.)
Code: American Canadian EuropeanLoad Combination: 1.2D+.5L D+L D+0.9LTabulated: 1 1/2 1 1 ½Simplified Calculations: 1 1 1SAFIR (min): 92 86 87
The results for both the tabulated and simplified calculations yield identical
results for both beams. However, minor discrepancies arise when comparing the
tabulated data for each code. The American and European codes are slightly
conservative with a 1 ½ hr fire rating for both beams compared to the 1 hr. rating
prescribed by the Canadian code. When considering the SAFIR results, they vary
slightly among the different codes, due to the various load combinations. Although these
results coincide well with the design provisions for the 10DT24+2, they tend to diverge
for the 12DT32+2. The 12DT32+2 results, show the simplified calculations
18
underestimatinge the fire ratings compared to SAFIR. This may not be the case if 90
min. temperature profiles are provided in the design provisions to accurately asses the fire
rating. In contrast, it may also be due to the assumption that the reduced prestressing
force is based on the temperature acquired at average strand centroid, rather then
developing this relationship for each individual strand. Another factor that may be
affecting the simplified calculations methods used. Overall the results prove to be
consistent and could arguably be claimed that the fire rating for the 10DT24+ and
12DT32+2, are 1 and 1 ½ hrs, respectively.
Figures 5 and 6 illustrate the midspan deflections based on SAFIR for the
10DT24+2 and 12DT32+2 beams, respectively. The deflections for both beams reflect
the loading combinations. They are greatest for the American code and lowest for the
Canadian code.
10DT24+2 Midspan Deflections
0
0.01
0.02
0.03
0.04
0.05
0 480 960 1440 1920 2400 2880 3360 3840
Time (sec)
Def
lect
ions
(m)
AmericanCanadianEuropean
Figure 5: Midspan deflections of a 10DT24+2 versus time
19
12DT32+2 Midspan Deflections
0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0 480 960 1440 1920 2400 2880 3360 3840 4320 4800 5280 5760
Time (sec)
Def
lect
ions
(m)
AmericanCanadianEuropean
Figure 6: Midspan deflections of a 12DT32+2 versus time
Conclusions
20
VII. Conclusions
The fire performance of two prestressed concrete double T-beams were assessed
using the tabulated data and simplified calculations for the American, Canadian, and
European design provisions, as well as with a performance-based approach using SAFIR.
Both design provisions yielded identical results for both beams. However, there were
minor differences in the American and European codes compared Canadian code.
Similarly, the SAFIR results were consistent with the design provisions for the
10DT24+2, but diverged slightly for the 12DT32+2. Therefore, it has been proven that
prescriptive-based design provisions can accurately assess the fire endurance of
prestressed concrete double T-beams. However, circumstances where limitations of
available temperature profiles or tabulated data exist, a performance-based approach
should be adopted to accurately and efficiently assess the fire performance of a member.
Therefore, it is suggested that the American and Canadian codes incorporate similar
advanced calculations methods to their arsenal of accepted analysis methods.
VIII. Acknowledgements
I would first like to thank Lansival Jean-Baptiste for his technical assistance and
mastery of SAFIR. Secondly, I would like thank my advisor and mentor for the
opportunity to help promote a new approach for design provisions in the United States.
21
X.
1) Abrams, M.S. and Gustaferro, A.H. 1972. “Fire Endurance of Prestressed Concrete
Unit Coated with Spray-Applied Insulation”, Prestressed Concrete Institute, V. 17,
No. 1, pp. 82-103.
2) ACI 216. 2001. “Guide for Determining the Fire Endurance of Concrete Elements.”
American Concrete Institute, ACI. Detroit, MI, USA.
3) ACI 318. 2005. “Building code requirements for structural concrete and
Commentary.” American Concrete Institute, ACI. Detroit, MI, USA.
4) Anderson, N.E. and Laurisden, D.H. 1999. “TT-roof slabs.” Technical Report
X52650, Part 1. Danish Institute of Fire Technology, Denmark.
5) ASCE 7-05. 2005. “Minimum Design Loads for Buildings and Other Structures.”
American Society of Civil Engineers, ASCE. Reston, VA, USA.
6) BS EN 1992-1-1. 2004. “Eurocode 2: Design of concrete structures. General rules
and regulations for buildings British-Adopted European Standard.”
7) BS EN 1992-1-2. 2005. “Eurocode 2: Design of concrete structures. General rules –
Structural fire design rules for buildings British-Adopted European Standard.
8) CSA CAN3-D-2.10. 1995. “Code for the design of concrete structures for buildings.”
Canadian Standard Association, CSA. Rexdale, ON, Canada.
9) CPCI. 2007. “CPCI Design Handbook 4th edition.” Canadian Precast/Prestressed
Concrete Institute, CPCI. Ottawa, ON, Canada
10) Franssen, J.M. and Bruls, A. 1997. “Design and Tests of Prestressed Concrete
Beams”, Proceeding of the 5th International Symposium on Fire Safety Science,
IAFSS. Melbourne, Australia. pp. 1081-1092.
23
11) Franssen, J.M., Kodur, V.K.R. & Mason, J. 2002. “User’s Manual for SAFIR2004:
A Computer Program for Analysis of Structures Subjected to Fire.” Liege:
University of Liege, Belgium.
12) Gustaferro, A. H. and Carlson, C. C. 1962. “An Interpretation of Results of Fire
Tests of Prestressed Concrete Building Components.” Prestressed Concrete
Institute Journal. V. 7. pp. 14-43.
13) IBC 7, 2006. “Fire-resistance-rated construction.” International Building Code, IBC.
International Code Council, Falls Church, VA, USA.
14) Karter, M.J. 2007. “Fire Loss in the Untied States During 2006.” National Fire
Protection Association, NFPA. Quincy, MA, USA.
15) PCI MNL 120-04. 2004. “PCI Design Handbook 6th edition.” Precast and Prestressed
Concrete Institute, PCI. Chicago, IL, USA.
16) Selvaggio, S.L. and Carlson, C.C. 1964. “Fire Resistance of Prestressed Concrete Beams Study. Influence of Aggregate and Load Intensity”, Portland Concrete Institute, V. 6, No. 4, pp. 10-25.
24
APPENDIX B
XI. SAFIR Input FilesAcknowledgements
I would first like to thank Lansival Jean-Baptiste for his technical assistance and mastery
of SAFIR. Secondly, I would like thank my advisor and mentor for the opportunity to
help promote a new approach for design provisions in the United States.
26
XII. References
17) Abrams, M.S. and Gustaferro, A.H. 1972. “Fire Endurance of Prestressed Concrete
Unit Coated with Spray-Applied Insulation”, Prestressed Concrete Institute, V. 17,
No. 1, pp. 82-103.
18) ACI 216. 2001. “Guide for Determining the Fire Endurance of Concrete Elements.”
American Concrete Institute, ACI. Detroit, MI, USA.
19) Structural and Material Features
20) The Station, built in 1946, was a conventional wood frame structure with a small
basement that underwent numerous renovations since its initial construction. This
single-story building had an estimated area of 412 m2, with a main floor plan as
shown in Figure 1 (Grosshandler et al., 2005). As indicated in Figure 1, the
nightclub mostly consisted of the main bar, sunroom, and dance floor areas. Four
doors were located in these areas for exits. Windows were located on both sides of
the front entrance door.
21) The building’s interior contained combustibles such as flexible polyurethane foam
lining, ceiling tiles, wood paneling, carpet, gypsum board, and an industrial
polytechnic device (Madrzykowski, 2006).
22)
27
23)
24)
25)
26)
27)
28)
29)
30)
31)
32)
33)
34) Figure 1: Floor Plane of The Station nightclub (Grosshandler et al., 2005)
35) Ignition of Fire
36) Nightclub fires are most frequently caused by incendiary, electrical, cooking, or
smoking (FEMA, 2000). On the evening of February 20, the band performing on
the raised platform incorporated pyrotechnics into their show. These pyrotechnics
caused two ignition locations of the polyurethane foam that lined the walls and
ceiling of the platform and nearby alcove (shown in Figure 1).
37) Fire Growth
38) At first, those inside The Station mistook the ignition for part of the performance and
did not react as the fire spread. Yet within 30 seconds after the ignition time,
patrons of the nightclub had realized the seriousness of the situation at hand and the
rapid growth of the fire around the dance floor. Patrons began to evacuate the
28
building and the band stopped playing. The flames spread from the polyurethane
foam lining to the wood paneling and ceiling tiles and moved beyond the dance
floor into the remaining rooms and hallways. Within five minutes after ignition,
witnesses saw flames reaching out of the building.
39) Fire Protection Features
40) The Station, an unprotected wood frame structure, was not equipped with a sprinkler
system (not required for this building). Fire alarms and emergency strobe lights
were present and alerted patrons 41 seconds after ignition. Several fire
extinguishers were located in the nightclub, yet could not control the growing fire.
Within 90 seconds, a black smoke layer had formed and encompassed the area from
the ceiling to one foot below (Grosshandler et al., 2005).
41) With the lack of sprinkler system and quick formation of a heavy toxic smoke layer,
patrons began overflowing the doorways in a effort to evacuate. Exit signs were
installed above each exit doorway and emergency egress lighting were present.
Approximately, two thirds of the patrons flooded toward the main entrance door in
a large crowd, which caused many to fall in a stampede and prohibited them from
exiting. Therefore, successful egress was not possible and in less than 100 seconds,
patrons clogged the front door (Grosshandler et al., 2005).
42) Fire Service Response
43) The Rhode Island Emergency 911 Center received calls pertaining to The Station
nightclub fire 60 seconds after ignition. The response teams arrived at the site
about 5 minutes after ignition and recorded the first water use within 6 minutes.
These rescue workers were responsible for helping evacuate a few patrons that
29
were stuck in the front entrance. Three triage areas were stationed for injured
civilians and were transported for further medical assistance as needed
(Grosshandler et al., 2005).
44) Structural Effects Due to Fire
45) Despite the fire spread throughout the entire building, no structural effects due to the
fire were evident until about 25 minutes after ignition. At this time, a portion of the
main bars’ roof was showing fire and had partially collapsed. It was not until 45
minutes into the fire when a major portion of the main roof had collapsed. Fifteen
minutes later, the roof above the sunroom also collapsed. In the end, the nightclub
was virtually destroyed; just a few exterior walls remained standing near the front
entrance and kitchen areas (Grosshandler et al., 2005).
46) Aftermath
47) The Station nightclub fire led to largest life loss fire incident in the state’s history. A
total of 100 fatalities and 200 injuries were accounted for, out of the estimated 440
to 458 people in attendance that night (Grosshandler et al., 2005). The flames
destroyed the establishment and multiple cars in the adjacent parking lot. In lieu of
the circumstances, a full blown National Institute of Standards and Technology
(NIST) investigation was commissioned to determine any negligence in safety of
the nightclub and further work that could be done to ensure safety among similar
public structures. In 2006, the two owners of The Station were sentenced to 15
years in prison for pleading no contest to 100 counts of manslaughter (Winograd,
2006).
48) Lessons to be Learned
30
49) NIST Investigations
50) NIST investigated the effects of smoke and fire spread through computer simulation
and a fire test on a mock-up of the nightclub. Both the computer simulation and
fire test estimated that within 90 seconds of ignition the temperatures, heat fluxes
and combustion gasses would have led to severe incapacitation or death to those
immediately around the dance floor. Furthermore, NIST evaluated the impact that
sprinklers would have had on controlling the fire if present. In these tests, no
tenability criteria or other dangerous levels were exceeded in 200 seconds and
flashover was prevented (Grosshandler et al., 2005).
51) NIST investigators also created several egress simulations under different scenarios
using multiple computer programs. The minimal egress time was estimated to be
188 seconds when the main entrance was not clogged from the crowd crush.
However, a maximum egress time of 341 seconds was predicted when the stage
door and main entrance were assumed impassible in 30 and 90 seconds,
respectively (Grosshandler et al., 2005).
31
52) Human Behavior
53) Mixing the occurrence of fire with the pandemonium of The Station’s loud music,
flashing lights, low lighting levels, large crowds, alcohol, smoking, and
entertainment confirmed several basic tenets in fire safety. First, people often wait
for reinforcing clues before acting out. Secondly, occupants will attempt to exit
through the same door in which they entered (Tracey, 2004). This type of human
behavior caused a crowd crush when two thirds of the patrons, all at once,
attempted to exit the nightclub’s main door in which they entered. Figure 2
illustrates these tenets through locations of the bodies recovered after the fire was
extinguished.
54)
55) Figure 2: Locations of bodies recovered after the fire (Grosshandler et al., 2005)
56) Recommendations
57) As a result of The Station nightclub fire, NIST proposed numerous recommendations
for improving the safety of nightclubs. The following is a brief list of the most
32
significant recommendations (FP & FEJ, 2005):
58) Forbid materials which easily ignite and rapidly propagate flames
59) All nightclubs should have sprinkler systems
60) Increasing the factor of safety on egress times
61) Strengthening pyrotechnic device provisions
62) Conclusions
63) The Station Nightclub fire was a tragic event, but may have been avoided or its
severity lessened, if the following considerations were taken into account during
the design of the building. First and foremost, the polyurethane foam lining was an
extremely combustible material that should be forbidden in all structures to prevent
such ultrafast fires. Secondly, the NIST investigations estimated that if sprinkler
systems would have been incorporated into the structure, flashover and loss of life
or injury of innocent people could have been avoided all together. Finally, the
inability of the facility to properly evacuate the majority of the people through the
main entrance led to an increase in fatalities. The egress issue can be contributed to
the patron’s natural tendencies in a fire and the building’s poor design of the main
entrance which lead to a crowd crush in the narrow corridors.
64)
33
65) References
66) Delen, D. May 2004. “Nightclub fires I.” Canadian Consulting Engineering, V.
45,No. 3, pp. 6-7.
67) Federal Emergency Management Agency, FEMA. June 2004. "Nightclub Fires in
2000.” Topical Fire Research Series, V. 3, I – Issue 7. U.S. Fire
Administration/National Fire Data Center.
68) Grosshandler, W., Bryner, N., Madrzykowski, D., and Kuntz, K. June 2005.
“Report of the Technical Investigation of The Station Nightclub Fire.” NIST
NCSTAR 2: Vol. I. National Institute of Standards and Technology, NIST.
Gaithersburg, MD.
69) Karter, M.J. September 2007. “Fire Loss in the Untied States During 2006.”
National Fire Protection Association, NFPA. Quincy, MA.
70) Madrzykowski, D., Bryner, N., and Kerber, S.I. 2006. “The NIST Station Nightclub
Fire Investigation: Physical Simulation of the Fire.” National Institute of Standards
and Technology, NIST. Gaithersburg, MD.
71) Delen, D. and Hershfield, M. May 2004. “Nightclub fires I.” Canadian Consulting
Engineerings, Volume 45, pp. 67-68.
72) FP & FEJ. August 2005. “Action stations.” Fire prevention & Fire Engineers
Journal, pp. 34-36.
73) ACI 318. 2005. “Building code requirements for structural concrete and
Commentary.” American Concrete Institute, ACI. Detroit, MI, USA.
74) Anderson, N.E. and Laurisden, D.H. 1999. “TT-roof slabs.” Technical Report
X52650, Part 1. Danish Institute of Fire Technology, Denmark.
34
75) ASCE 7-05. 2005. “Minimum Design Loads for Buildings and Other Structures.”
American Society of Civil Engineers, ASCE. Reston, VA, USA.
76) BS EN 1992-1-1. 2004. “Eurocode 2: Design of concrete structures. General rules
and regulations for buildings British-Adopted European Standard.”
77) BS EN 1992-1-2. 2005. “Eurocode 2: Design of concrete structures. General rules –
Structural fire design rules for buildings British-Adopted European Standard.
78) CSA CAN3-D-2.10. 1995. “Code for the design of concrete structures for buildings.”
Canadian Standard Association, CSA. Rexdale, ON, Canada.
79) CPCI. 2007. “CPCI Design Handbook 4th edition.” Canadian Precast/Prestressed
Concrete Institute, CPCI. Ottawa, ON, Canada
80) Franssen, J.M. and Bruls, A. 1997. “Design and Tests of Prestressed Concrete
Beams”, Proceeding of the 5th International Symposium on Fire Safety Science,
IAFSS. Melbourne, Australia. pp. 1081-1092.
81) Franssen, J.M., Kodur, V.K.R. & Mason, J. 2002. “User’s Manual for SAFIR2004:
A Computer Program for Analysis of Structures Subjected to Fire.” Liege:
University of Liege, Belgium.
82) Gustaferro, A. H. and Carlson, C. C. 1962. “An Interpretation of Results of Fire
Tests of Prestressed Concrete Building Components.” Prestressed Concrete
Institute Journal. V. 7. pp. 14-43.
83) IBC 7, 2006. “Fire-resistance-rated construction.” International Building Code, IBC.
International Code Council, Falls Church, VA, USA.
84) Karter, M.J. 2007. “Fire Loss in the Untied States During 2006.” National Fire
Protection Association, NFPA. Quincy, MA, USA.
35
85) PCI MNL 120-04. 2004. “PCI Design Handbook 6th edition.” Precast and Prestressed
Concrete Institute, PCI. Chicago, IL, USA.
86) Selvaggio, S.L. and Carlson, C.C. 1964. “Fire Resistance of Prestressed Concrete Beams Study. Influence of Aggregate and Load Intensity”, Portland Concrete Institute, V. 6, No. 4, pp. 10-25.
36