Harmonic Solutions for VFD’s PQ01 Review of Power Control Harmonics, Power Factor, Distortion & Displacement

Upload: nguyenthu

Post on 09-Apr-2018

223 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Harmonic Solutions for VFD’s

PQ01

Review of Power Control Harmonics, Power

Factor, Distortion & Displacement

Page 2: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

PQ02 – Power Quality and Monitoring..

PQ03 – Using Test Eqipment to Detect and

Measure PQ Issues

PQ04 – Understanding Power Monitoring

PD02 – Power Quality and Monitoring

MC04 – Installation Considerations for VFD’s

Related Content at the Expo

Page 3: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What Are Harmonics?

3 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Page 4: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What Are Harmonics?

4 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Ideal

Often seen

Page 5: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What Are Harmonics?

5 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Page 6: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What Are Harmonics? What Are

Waveforms?

6 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Rfund.V =...

0

0

40.00m

40.00m

10.00m

10.00m

20.00m

20.00m

30.00m

30.00m

-150.0 -150.0

150.0

0 0

-100.0 -100.0

-50.0 -50.0

50.0 50.0

100.0 100.0

• A sinusoidal waveform has no harmonics

Page 7: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What Are Harmonics and Waveforms?

Rtotal.V =...

0

0

40.00m

40.00m

10.00m

10.00m

20.00m

20.00m

30.00m

30.00m

-150.0 -150.0

150.0

0 0

-100.0 -100.0

-50.0 -50.0

50.0 50.0

100.0 100.0

7 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

• This non-sinusoidal waveform contains harmonics

Page 8: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Let’s Create a Distorted Waveform

Fundamental (1st harmonic) Only

8 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

• fundamental at 60Hz

Page 9: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Fundamental and 5th Harmonic

9 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

• Some 5th harmonic , 153deg

Page 10: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

1st, 5th and 7th Harmonics

10 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

•A little of 7th harmonic , 282deg

Page 11: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

1st, 5th, 7th and 11th Harmonics

11 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

•A bit of 11th harmonic , 0deg

Page 12: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

1st and Sum of the 5th, 7th and

11th

12 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

• Sum the 5th, 7th and 11th harmonic currents

Page 13: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Fundamental, Harmonics, Total

13 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

• Sum the harmonics with the fundamental

Page 14: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

FFT and How Are Harmonics

Measured?

14

Power Source

AC Drive

Motor M

Harmonic

Power Meter

Performing FFT

A1 Waveform178.67 Arms, 34.40 %THD

0

20

40

60

80

100

1 5 10 15 20 25 30 35 40 45 5010/28/2010 - 1:46:18.297 PM

Page 15: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

FFT, RSS, THD

15 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Harmonic

Number

Frequency

Hz

Amplitude

RMS

Amplitude

RMS^2

Phase

Angle

0 DC 0.00 0.00 0

1 60 70.71 5000.00 357

3 180 0.00 0.00 0

5 300 27.97 782.50 153

7 420 10.85 117.67 282

9 540 0.00 0.00 0

11 660 5.54 30.74 0

13 780 2.79 7.79 81

15 900 0.00 0.00 0

17 1020 2.54 6.44 189

19 1140 1.45 2.09 246

21 1260 0.00 0.00 0

23 1380 1.37 1.88 10

25 1500 0.91 0.84 58

27 1620 0.00 0.00 0

29 1740 0.78 0.61 185

Sum of 3rd to 29th 950.56

Square Root of Sum 30.83 Iharm

Sum of 1st to 29th 5950.56

Square Root of Sum 77.14 Itotal

Iharm = 30.83A

Ifund = 70.71A

Itotal = 77.14A

ITHD = 43.6%

= Iharm / Ifund

Page 16: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What Is I(THD)?

ITHD = Iharm / Ifund

So, Iharm = ITHD * Ifund

16

•ITHD is a ratio between two numbers, it does not stand alone!

We can decrease ITHD

by either decreasing Iharm or increasing Ifund

Page 17: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Frequency, Amplitude, Phase Angle

17 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

•Harmonics are simply integer multiples of the fundamental frequency

– for example, if 60Hz is the fundamental (sometimes referred to as the 1st harmonic), then the 2nd harmonic is 120Hz, the 3rd harmonic is 180Hz, etc.

•Any non-sinusoidal waveform can be created by the addition of harmonics at various amplitudes and phase angles

Page 18: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Electrical Loads and Current Harmonics

18 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Power Source Load Type ?

Line Current Harmonics?

Page 19: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What are Loads That Do Not Have

Current Harmonics?

19 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

• A sinusoidal waveform has no harmonics

• This is an example of a linear load

Voltage Current

Page 20: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What are Loads That Do Not Have

Current Harmonics?

20 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

• A sinusoidal waveform has no harmonics

• This is an example of a linear load

Voltage

Current

Page 21: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Examples of Linear Loads

Induction motors

Incandescent lights

Resistance heaters

Power Factor Correction Caps

Electromagnetic devices

Transformers

non-linear

• During energization

• Over-voltage

21

Page 22: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What are Loads That Have Current

Harmonics?

Rfund.V =...

Rtotal.V =...

0

0

40.00m

40.00m

10.00m

10.00m

20.00m

20.00m

30.00m

30.00m

-150.0 -150.0

150.0

0 0

-100.0 -100.0

-50.0 -50.0

50.0 50.0

100.0 100.0

22

• This is an example of a non - linear load

• A non-sinusoidal waveform contains harmonics

Page 23: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Examples of Non-Linear Loads

Single Phase

Fluorescent lights (ballast)

Incandescent lights with light dimmers

Anything with an ac-dc power supply

Computers (ac-dc PS)

Monitors (ac-dc PS)

TVs (ac-dc PS)

LED lighting

Three Phase

Welders

Arc furnaces

UPS

DC power supplies

DC Drives

Phase control

PWM

AC Drives

6-Step

PWM

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 23

Page 24: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

A Typical AC Drive

24

Power Source AC Drive Motor

Line Current Harmonics

M

How Do Drives Create Harmonics?

Page 25: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What Does it Do?

Converter

AC to DC

Inverter

DC to AC

DC

Bus

Filter

AC Drive

AC

Moto

r Outp

utA

C L

ine I

nput

25 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Input Output

480Vac

60Hz

0-460Vac

0-60Hz

650Vdc

Bus = Fixed Vdc

Page 26: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Let’s Look at Some Voltages and

Current

26 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

AC

Power

Line

LoadVab

Vac

Ia

Vbus

Page 27: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

First Current Pulse

27 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

AC

Power

Line

Load

Into A

Out of B

1

Page 28: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Second Current Pulse

28 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

AC

Power

Line

Load

Into A

Out of C

2

Page 29: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Typical Current Waveform for 6

Diode (Pulse)

Rtotal.V =...

0

0

40.00m

40.00m

10.00m

10.00m

20.00m

20.00m

30.00m

30.00m

-150.0 -150.0

150.0

0 0

-100.0 -100.0

-50.0 -50.0

50.0 50.0

100.0 100.0

29 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Page 30: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Spectrum – 3ph Diode Bridge

0

10

20

30

40

50

60

70

80

90

100

1 3 5 7 9 11 13 15 17 19 21 23 25

30 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Harmonic Number

% A

mp

litude

Page 31: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 31

0

10

20

30

40

50

60

70

80

90

100

1 3 5 7 9 11 13 15 17 19 21 23 25

Why do the line currents

contain 5th and 7th

harmonics?

Harmonic Number

Why 5th and 7th?

Page 32: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Harmonics

32 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

2

4

6

8

10

12

14

16

18

20 NOTE: No even harmonics because each half cycle is identical

Rfund.V =...

Rtotal.V =...

0

0

40.00m

40.00m

10.00m

10.00m

20.00m

20.00m

30.00m

30.00m

-150.0 -150.0

150.0

0 0

-100.0 -100.0

-50.0 -50.0

50.0 50.0

100.0 100.0

1

3

5

7

9

11

13

15

17

19

Page 33: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Harmonics

1

3

5

7

9

11

13

15

17

19

33 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

NOTE: No triplens (multiples of 3)

2

4

6

8

10

12

14

16

18

20

Page 34: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 34

SO WHAT……what do I care

if adjustable speed drives

draw current harmonics

on a power distribution

system?

Page 35: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Issues with Excessive Harmonic Current

35 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Current Harmonics

create

Voltage Distortion

HARMONIC SOURCE

PLC

EQUIPMENT

TELEPHONE

EQUIPMENT

DATA

PROCESSING

CENTER

PCC

IH

Page 36: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Summary of Excessive Harmonic Current Concerns

• Increased Utility current requirement – Inability to expand or utilize

equipment

– Larger wire size needed = increased installation costs

• Component overheating – Distribution transformers,

generators & wires

• Reduced Utility power factor – Increase in utility costs

• Equipment malfunction – Due to voltage distortion with

multiple or loss of zero crossing

– Due to voltage distortion such as flat topping

• Excitation of Power System Resonance's creating over-voltage’s – If PFCC in system

HARMONIC SOURCE

PLC

EQUIPMENT

TELEPHONE

EQUIPMENT

DATA

PROCESSING

CENTER

PCC

IH

PFC PFC

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 36

Page 37: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

When Should You Be Concerned

About Harmonics?

If service Transformer is Loaded near rating 60%

20 % of total Load is Non-Linear electronic load

When PF correction capacitors Used or Planned

When Voltage Distortion exceeds 8%

37 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Page 38: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Example of High Ithd with Low Vthd - 1500kVA, 75hp

38 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Ithd = 37% Vthd = 0.9%

Page 39: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Example of High Ithd with High Vthd - 75kVA, 75hp

39 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Ithd = 29% Vthd = 9.3%

Page 40: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Excessive Harmonic Current

Causing Voltage Flat-Topping

40 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Page 41: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Excessive Harmonic Current

Causing Voltages with High Peaks

Event #397 at 12/23/2009 22:19:59.800

Timed

Ev ent Details/Waveforms

22:19:59.86

12/23/2009

Wednesday

22:19:59.87 22:19:59.88 22:19:59.89

-750

-500

-250

0

250

500

750

Vo

lts

D V A-B V B-C V C-A V

41 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

477VAC RMS

720 volts peak

Page 42: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

IEEE Std 519-2014

42 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

* Provides harmonic current limits for a facility * Provides harmonic voltage limits for the utility connected to facility

Page 43: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What Are the IEEE 519-2014

Standards?

43 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Application Maximum THD (%)

Special Applications - hospitals and airports 3.0%

General System 5.0%

Dedicated System - exclusively converter load 10.0%

Harmonic Voltage LimitsLow-Voltage Systems

Table 10.2

Application Max Notch Depth

Special Applications - hospitals and airports 10%

General System 20%

Dedicated System - exclusively converter load 50%

Harmonic Voltage Limits

Low-Voltage Systems

Rule of Thumb –

Keep notch depth less than 10% if any other equipment will

be connected to that same point of common coupling.

Page 44: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What Are the IEEE 519-2014

Standards?

44 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Table 10.2

Application Max Notch Depth

Special Applications - hospitals and airports 10%

General System 20%

Dedicated System - exclusively converter load 50%

Harmonic Voltage Limits

Low-Voltage Systems

Page 45: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What Are the IEEE 519-2014

Standards?

45 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Table 10.3

Current distortion Limits for General Distribution Systems (120V through 69,000V)

Isc/Iload <11 11<=h<17 17<=h<23 23<=h<35 35<=h TDD (%)

<20 4.0 2.0 1.5 0.6 0.3 5.0

20<50 7.0 3.5 2.5 1.0 0.5 8.0

50<100 10.0 4.5 4.0 1.5 0.7 12.0

100<1000 12.0 5.5 5.0 2.0 1.0 15.0

>1000 15.0 7.0 6.0 2.5 1.4 20.0

Even harmonics are limited to 25% of the odd harmonic limits above

Isc=maximum short circuit current at PCC

Iload=maximum demand load current (fundamental frequency component) at PCC

Maximum Harmonic Current Distortion in Percent of Iload

Table 10.3

Current harmonics create voltage harmonics so there are current harmonic limits

Page 46: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What Is Ithd vs Itdd?

Ithd = Iharm / Ifund at any speed or load level

Itdd (IEEE519) = Iharm / Ifund at max load

Itdd (xfmr) = Iharm / Ifund at rated transformer current

46 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Page 47: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

6-Pulse Buffered Drive Currents

0

10

20

30

40

50

60

70

80

90

100

0 20 40 60 80 100 % Load

TH

D, F

un

d c

urr

ent, a

nd

Ha

rmo

nic

cu

rre

nt %

Iharm

Ifund

ITHD

How Does Motor Load Affect ITHD?

47 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Ifund decreases as load decreases

Iharm decreases as load decreases

(drive is at full speed)

NOTES:

ITHD = Iharm / Ifund

ITHD increases as load decreases

ITDD

Page 48: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Vthd vs Load

48 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

0

5

10

15

20

25

30

35

40

45

50

0 10 20 30 40 50 60 70 80 90 100

% Load

Ithd, %

Iharm, A

Vthd, %

ITDD

100hp drive on 250kVA xfmr, 6%

Max

Vthd

Page 49: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Why Itdd on Table 10.3?

Itdd is called for because that is a worst case

condition.

Please note:

This is not where Ithd is maximum

But, it is where Vthd is maximum because Iharm is

maximum

When Vthd is a maximum, then greatest likelihood of

problems exist

49 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Page 50: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

The Goal of IEEE 519

50 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Thou Shalt Not

Mess Up

Thy

Neighbor’s

Line Voltage

Thou

Shalt Not

Mess Up

Thy

Neighbor’s

Line Voltage

Page 51: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Who Is Your Neighbor?

51 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

transformertransformer

PCC1

2500kVA

5.75%Z

480Vsec

utility

2500kVA

5.75%Z

480Vsec

utility

Other

Customer

Customer

A

Other

Customer

Customer

B

Other

Customer

Customer

C

Iharm A

Iharm B

Iharm C

Ifund A

Ifund B

Ifund C

Iharm

Ifund

I(TDD) is measured at each metering point

Goal is to

keep the V(THD) at

PCC1 <= 5%,

Page 52: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Example

52 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

transformertransformer

PCC1

2500kVA

5.75%Z

480Vsec

utility

2500kVA

5.75%Z

480Vsec

utility

Other

Customer

Customer

A

Other

Customer

Customer

B

Other

Customer

Customer

C

113Arms

101Arms

72Arms

981Arms

926Arms

1053Arms

241Arms

2960Arms

I(TDD) limits are met at each metering point

at PCC1:

V(THD) = 3.6%

300hp 6-p drives

600hp linear load

80hp unbuf drives

700kW linear load

1000hp 12-p drives

Page 53: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What About Within Customer A or B

or C?

113Arms

981Arms

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 53

Meets IEEE 519 at PCC1 and within plant

PCC1

Isc/Iload = 53.3

V(THD) = 2.0%

I(TDD) = 11.5%

V(THD) <= 10%

Customer A

V(THD) <= 8%

300hp 6-P drives

600hp linear loads

V(THD) <= 8%

Page 54: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What About Back-up Generator?

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 54

Meets IEEE 519 within the plant if the generator is sized properly

PCC1

Isc/Iload = 53.3

V(THD) = 2.0%

I(TDD) = 11.5%

V(THD) <= 10%

Customer A

V(THD) <=8%

300hp 6-P drives

600hp linear loads

G V(THD) <8%

Page 55: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Information Needed for Generator

Applications

Generator Issue Information Required

kW Rating Prime Mover / Engine Specifications Generator Reactive Capability Curve

kVAR Lagging Generator Reactive Capability Curve

kVAR Leading Generator Reactive Capability Curve

Voltage Distortion Generator Impedance, Xd”

Voltage Notching Generator Impedance, Xd”

Harmonic Current Regulator Control

Drive Precharge Regulator Control

Table 3 – Generator Issues and Information Required to Understand and Resolve those Issues.

55 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

General Guidelines For 6 pulse drives Generator sized 250% of Drive HP

For 18 pulse drives Generator sized 125% of Drive HP

Page 56: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 56

HARMONIC

Current

Ireact

Ireal

Ifund

Itotal

Iharm

(in phase with

line-to-neutral

voltage, VLN)

REACTIVE

Current

Q

P

S1

S

D

x-axis

y-axis

z-axis

REAL

Current

222 DQPS

What is the Power Factor

of a

Non-Linear load?

Linear Load Power Factor Non-Linear Load Power Factor

No Current Distortion Includes the Effect of Current Distortion

PF = Watts/VA

or phase angle between

voltage and current

What About the Power Factor?

Page 57: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Power Factor

Displacement power factor - PF(disp) PF(disp) = Ireal / Ifund = a number between .01 and 1.0

involves only the fundamental quantities

includes the real and reactive currents

Distortion power factor - PF(dist) PF(dist) = Ifund / Itotal = a number between .01 and 1.0

includes the fundamental and harmonic (distorted) currents

Itotal = fundamental and harmonic currents

57 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Total PF = PF(disp) * PF(dist)

Page 58: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Current Amplitudes

• Itotal = 105.6Arms • Iharm = 33.1Arms

• I5 = 29.3Arms

• I7 = 10.9Arms

• I11 = 7.9Arms

• I13 = 4.5Arms

• ……. • Ifund = 100.3Arms

• Ireal = 98.6Arms

• Ireact = 18.0Arms

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 58

Page 59: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Current Amplitudes

• Itotal = 105.6 Arms

• Iharm = 33.1 Arms

• Ifund = 100.3 Arms

• Ireal = 98.6 Arms

• Ireact = 18.0 Arms

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 59

Page 60: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Current Relationships

Itotal = 105.6Arms

• Iharm = 33.1Arms

• Ifund = 100.3Arms

Ireal = 98.6Arms

Ireact = 18.0Arms

PFdisp = Ireal/Ifund = 0.98

PFdist = Ifund/Itotal = 0.95

PFtotal = PFdisp*PFdist

PFtotal = 0.93

60

Page 61: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 61

How can we reduce

(mitigate) the

harmonic current?

Page 62: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Drive Without DC Link Choke

• Typical ITHD

of 80 to

120%

• Sensitive to

line voltage

transients

• High peak

line currents

La.I = f( ...

150.0m

150.0m

200.0m

200.0m

162.5m

162.5m

175.0m

175.0m

187.5m

187.5m

-400.0 -400.0

400.0

0 0

-200.0 -200.0

200.0 200.0

M

hp

Motor

Load

Transformer

xfmr

% Z

Drive

DC

AC

AC

DC

Common

configuration for

drives < 5hp

NOTE: Ipk about 3x Irms

Page 63: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Line Reactor, Drive w/o DC Link Choke

• Typical ITHD

of 30 to 45%

• Big help for

drives

without DC

link choke

La.I = f(t...

150.0m

150.0m

200.0m

200.0m

162.5m

162.5m

175.0m

175.0m

187.5m

187.5m

-400.0 -400.0

400.0

0 0

-200.0 -200.0

200.0 200.0

Copyright © 2008 Rockwell Automation, Inc. All rights reserved. 63

M

hp

Motor

Load

Transformer

xfmr

% Z

Line Reactor

Drive

DC

AC

AC

DC

Typical values are 3% and

5% impedance

NOTE: shown is 3% LR

Page 64: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Drive With DC Link Choke

• Typical ITHD of

30 to 40%

• Less sensitive

to line transients

La.I = f(t...

150.0m

150.0m

200.0m

200.0m

162.5m

162.5m

175.0m

175.0m

187.5m

187.5m

-400.0 -400.0

400.0

0 0

-200.0 -200.0

200.0 200.0

Copyright © 2008 Rockwell Automation, Inc. All rights reserved. 64

NOTE: Ipk about 1.5x Irms

M

hp

Motor

Load

Transformer

xfmr

% Z

Drive

DC

AC

AC

DC

DC Link

Choke

Page 65: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Line Reactor in Addition to a DC Link

Choke

• Typical ITHD of

20 to 35%

• Big help for

drives w/o DC

link choke

• 0.75 - 0.95 PF

La.I = f(t...

150.0m

150.0m

200.0m

200.0m

162.5m

162.5m

175.0m

175.0m

187.5m

187.5m

-400.0 -400.0

400.0

0 0

-200.0 -200.0

200.0 200.0

M

hp

Motor

Load

Transformer

xfmr

% Z

Line Reactor

Drive

DC

AC

AC

DC

DC Link

Choke

Typical values are 3%

and 5% impedance

NOTE: shown is 3% LR

Page 66: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Passive Harmonic Filter

• Typical ITHD of

4 to 7%

• 0.3 to 1.0 PF

Ia = f( S,...

-25.00m

-25.00m

24.90m

24.90m

0

0

-20.00m

-20.00m

-10.00m

-10.00m

10.00m

10.00m

20.00m

20.00m

-150.0 -150.0

150.0

0 0

-100.0 -100.0

-50.0 -50.0

50.0 50.0

100.0 100.0

M

hp

Motor

Load

Transformer

xfmr

% Z

Passive Filter

Drive

DC

AC

AC

DC

DC Link

Choke

Page 67: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Active Harmonic Filter

• Typical ITHD of 3

to 6%

• 0.9 - 0.99 PF

Ia = f( S,...

-25.00m

-25.00m

24.90m

24.90m

0

0

-20.00m

-20.00m

-10.00m

-10.00m

10.00m

10.00m

20.00m

20.00m

-150.0 -150.0

150.0

0 0

-100.0 -100.0

-50.0 -50.0

50.0 50.0

100.0 100.0

M

Drive

hp

Motor

Load

Transformer

DC

AC

DC Link

Chokexfmr

% Z AC

DC

Ifund Ifund + Iharm

Iharm

Active Filter

AC

DC

Current from Transformer

Page 68: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Multi-Pulse VFD

• 12-Pulse

Typical ITHD of

9 to 12%

• 18-Pulse

Typical ITHD of

4 to 5%

• 0.90 - 0.99

PF

Ia = f( S,...

-25.00m

-25.00m

24.90m

24.90m

0

0

-20.00m

-20.00m

-10.00m

-10.00m

10.00m

10.00m

20.00m

20.00m

-200.0 -200.0

200.0

0 0

-100.0 -100.0

100.0 100.0

M

hp

Motor

Load

Transformer

xfmr

% Z

Multi-Phase

Transformer

Drive

DC

AC

AC

DC

DC Link

Choke

3 9

Multi-Set

6 pulse bridge

Page 69: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Spectrum – 3ph Diode Bridge

0

10

20

30

40

50

60

70

80

90

100

1 3 5 7 9 11 13 15 17 19 21 23 25

69 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Harmonic Number

% A

mp

litude

Page 70: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Spectrum – 12 Pulse Diode Bridge

70 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Harmonic Number

% A

mp

litude

0

10

20

30

40

50

60

70

80

90

100

1 3 5 7 9 11 13 15 17 19 21 23 25

Page 71: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Spectrum – 18 Pulse Diode Bridge

71 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.

Harmonic Number

% A

mp

litude

0

10

20

30

40

50

60

70

80

90

100

1 3 5 7 9 11 13 15 17 19 21 23 25

Page 72: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Active Front-End

• Typical ITHD of 3

to 5%

• Regen

• 0.8 – 1.0 PF

Lx1.I = ...

145.0m

145.0m

195.0m

195.0m

150.0m

150.0m

162.5m

162.5m

175.0m

175.0m

187.5m

187.5m

-200.0 -200.0

200.0

0 0

-100.0 -100.0

100.0 100.0

M

hp

Motor

Load

Transformer

xfmr

% Z

Drive

DC

AC

AC

DC

Notch Filter

Page 73: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

Popular Harmonic Mitigation

Choices

73

• 18-Pulse - widely accepted – Works well – Has become more expensive

• Passive Filters – Suited to lower power ratings <100 hp – Numerous suppliers

• Active Filters – Versatile – used for single drives or multiple drives

• AFE – Increasing in interest and use – Feature of line regeneration capability makes it

attractive

Page 74: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

What Did We Learn?

• What are harmonics? – Distorted waveform, sine

wave element that make up distorted waveform

• How are they measured? – FFT RSS THD TDD PCC

• Why do drives produce line current harmonics?

– Non Linear Load, 6 pulse rectifiers

• How much is too much?

– Voltage distortion greater than 5%

• How do we apply IEEE-519?

– Limits guidelines

• How do harmonics vary with load?

– Voltage distortion increase as Iharm increases as a % of maximum available current

• How can the drive harmonics be reduced?

– DC link choke, Line reactor, Passive filter, active filter, xfmr config, multipulse converter, active front end

• What about Power Factor?

– Disp pf high, total pf is dist pf * disp pf ( lower than disp pf)

• Total pf proportional to Ithd

– Be careful with passive filters and leading pf

• What about gensets ( Generators )?

– Increase in Vthd due to greater impedances,

– Voltage regulation issues when applied to drives

Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 74

HARMONIC SOURCE

PLC

EQUIPMENT

TELEPHONE

EQUIPMENT

DATA

PROCESSING

CENTER

PCC

IH

Page 75: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

PQ02 – Power Quality and Monitoring..

PQ03 – Using Test Eqipment to Detect and Measure PQ Issues

PQ04 – Understanding Power Monitoring

PD02 – Power Quality and Monitoring

MC04 – Installation Considerations for VFD’s

You can find these products in the

Solution Area SA01

Related Content at the Expo

Page 76: Review of Power Control Harmonics, Power Factor, … Expo...Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ02 – Power Quality and Monitoring.. PQ03

PQ01 - Harmonic Solutions for VFD’s

76

Dave Dahl – Rockwell Automation Randy Keranen – Werner Electric Drives, Motors, and PowerMonitor Product Manager [email protected]

Thank You!