revenue meter with advanced power quality capabilities expertmeter - em720
DESCRIPTION
Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720. ExpertMeter – EM720. “All in one” High Performance Meter: Revenue meter Power Quality Analyzer Fault Recorder Transient Recorder. Revenue Meter. IEC 62056-21 protocol support (Infra red) - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/1.jpg)
Revenue Meter with Advanced Power Quality Capabilities
eXpertMeter - EM720
![Page 2: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/2.jpg)
ExpertMeter – EM720
“All in one” High Performance Meter:
Revenue meter
Power Quality Analyzer
Fault Recorder
Transient Recorder
![Page 3: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/3.jpg)
Revenue Meter
IEC 62056-21 protocol support (Infra red)
Accuracy according to IEC 62053-22 Class 0.2S
TOU up to 8 tariffs and 4 seasons
![Page 4: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/4.jpg)
PQ Analyzer
3 Voltage and 4 Current inputs
Voltages and Currents Harmonics and Interharmonics measurement: IEC 61000-4-7 class I
IEC 61000-4-15: Flicker measurement
Complete Power Quality Reports per EN50160 and
IEC 61000-4-30 Class A
![Page 5: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/5.jpg)
Four measured and recorded currents up to 50 A (10In)
Chargeable Back-up battery – 2.5 hours
GPS Time synchronization
Sequence of events with 1 ms accuracy
Fault Recorder
![Page 6: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/6.jpg)
Transient Recorder
Pick-Voltages up to 2000 V
Time 19mcs to 10ms
4 Voltage waveforms captured
3 Phase and neutral to ground
![Page 7: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/7.jpg)
Modules (Hot swap)
Field Replaceable I/O options
Field Replaceable Advanced Communication options
![Page 8: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/8.jpg)
EM720 - Commutations
Communication ports: – Ethernet, – USB,– IR-port – RS232/485,– GSM/GPRS modem
Protocols:– IEC 61850,– Modbus RTU,– ASCII, SMTP, – Web-server
![Page 9: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/9.jpg)
Digital Input Status input / Pulse input
Digital Output Relay / Pulse relay
SATEC DI/DO functions
![Page 10: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/10.jpg)
APPLICATIONS
Utilities Transmission | Distribution | Substations
IndustrialPower Stations | Industrial Plants | Process Control
CommercialBig Commercial Centers
![Page 11: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/11.jpg)
Using the EM720 in “Shaar Hair” building complex project for fault
detection
![Page 12: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/12.jpg)
Detection of PQ failures using EN50160 STD
I II
Samples of using EM720 Revenue Meter
![Page 13: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/13.jpg)
A
B C D
I II
10001000100010001000 630
Public
Substation B Substation A
Device #3
Device #2
Device #1
Supply diagram of the building project
![Page 14: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/14.jpg)
Parameters of devices
Device 1: (EM720T, 0.4 kV)Nominal primary current = 400 ANominal primary voltage = 230 V
Device 2: (EM720T, 22 kV)Nominal primary current = 100 ANominal primary voltage = 22 kV
Device 3: (EM720T, 0.4 kV)Nominal primary current = 1200 ANominal primary voltage = 230 V
![Page 15: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/15.jpg)
Statistics EN50160 – Compliance report
![Page 16: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/16.jpg)
Voltage Dips report :Device-3 (1/02-7/05)
![Page 17: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/17.jpg)
List of dips’ events (30/04-4/05)
![Page 18: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/18.jpg)
Voltage Dip RMS plot V31 (60%Un)
![Page 19: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/19.jpg)
Device #1 (0.4 kV): general voltage dip
![Page 20: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/20.jpg)
Device #2 (22 kV): general voltage dip
![Page 21: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/21.jpg)
Device #3 (0.4 kV): general voltage dip
![Page 22: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/22.jpg)
Device #1 (0.4 kV): Voltage dip before interruption
![Page 23: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/23.jpg)
Device #2 (22 kV): Voltage dip before interruption
![Page 24: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/24.jpg)
Device #3 (0.4 kV): Voltage dip before interruption
![Page 25: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/25.jpg)
Device #1 (0.4 kV): Voltage recovery + Inrush current
![Page 26: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/26.jpg)
Device #2 (22 kV): Voltage recover + Inrush current
![Page 27: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/27.jpg)
Device #2, Phase L1, Inrush current - 570 A=5.7 In
![Page 28: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/28.jpg)
Device #3 - Voltage recovery
![Page 29: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/29.jpg)
Device #3 High even individual harmonics-12.6% during voltage recovery
![Page 30: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/30.jpg)
Device #1 (0.4 kV)Spectrum graph and table – high harmonics Voltage THD = 16%, Current THD = 45.9%
![Page 31: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/31.jpg)
Device #2 (22 kV)Spectrum graph and table – high harmonics Voltage THD = 14.3%, Current THD = 25.1%
![Page 32: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/32.jpg)
Device #3 (0.4 kV) Spectrum graph and table – high harmonics Voltage THD = 13.9%, Current THD = 24%
![Page 33: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/33.jpg)
Comparison of THD (0.2 sec)
Device 1: (EM720T, 0.4 kV)Voltage THD =16%Current THD =45.9%
Device 2: (EM720T, 22 kV)Voltage THD =14.3%Current THD =25.1%
Device 3: (EM720T, 0.4 kV)Voltage THD =13.9%Current THD =24%
![Page 34: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/34.jpg)
Voltage Peaks due to high harmonicsHigh Voltage Amplitude - 380V= Un +18%Un (Phase L3, Device #1)
![Page 35: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/35.jpg)
Comparison - voltage peak value
Device #1 (0.4 kV), High Voltage Amplitude - 380V= Un +18%Un
Device #2 Voltage Amplitude - 33 kV = Un +6.1%Un
Device #3 Voltage Amplitude - 340V= Un +4.5%Un
![Page 36: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/36.jpg)
Device #2 - Real time Current TDD (9.9%)
![Page 37: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/37.jpg)
Device #2 - Current TDD trend (22 kV)
![Page 38: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/38.jpg)
Device #2 THD & TDD compliance
Voltage THD=1.7% - OK
Current TDD=9.9% - NOT OK (Prohibited)
Standard IEEE 519-1992: TDD=5%
![Page 39: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/39.jpg)
Summary and Conclusions
High level dips cause to servers and elevators’ failure of operation
High level short period harmonics cause to increase of voltage amplitude that damaged the elevator controller
Increase of TDD by 9.9% totally damaged the reactive power regulator together with full power shut down in the building
The EM720 allowed the detection of all the root cause of these sever phenomenon
![Page 40: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/40.jpg)
Turbine applicationUsing the SATEC product for failure
detection of turbine operation
![Page 41: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/41.jpg)
Detection of turbine failure – big difference between two identical
turbines of 13.4%
![Page 42: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/42.jpg)
After partial problem fix the difference dropped to 9.5% - less operating cost
![Page 43: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/43.jpg)
Failure detection of pumps operation
Using the basic following formula the SATEC meter can detect pump’s operation problem measuring the pump’s efficiency
Efficiency=(Kw/ton) Efficiency should be constant. If changes during
operation, it shows a problem in the pump’s operation
SATEC meters detects in operational sites such a failure during the pump’s operation.
![Page 44: Revenue Meter with Advanced Power Quality Capabilities eXpertMeter - EM720](https://reader034.vdocuments.site/reader034/viewer/2022051401/56813019550346895d959279/html5/thumbnails/44.jpg)
Thank You