Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors

Upload: others

Post on 23-Apr-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

Retractable Probe Procedure For DumpStar Systems

and 700 Series Retractable Sensors

Page 2: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

Retractable Sensor Part Identification

Page 3: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

Note: Never touch either hex nut on the Primary Seal.

To Install the Sensing Element

Page 4: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Install the Sensing Element

1. Back out the retention screws.

Page 5: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Install the Sensing Element

2. Loosen the packing nut at the slider gland so that the sensing element will slide out easily.

Page 6: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

3. Retract the sensor until the blowout stop (retaining clip) is reached.

To Install the Sensing Element

Page 7: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Install the Sensing Element

4. Thread or Flange the sensing element to the block valve. Minimum valve ID is 7/8” (0.875”).

Page 8: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Install the Sensing Element

5. Tighten the packing nut into the slider gland just enough so that the sensing element will still slide, but tight enough to prevent product leakage from the gland.

Page 9: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Install the Sensing Element

6. Do not stand directly behind the sensor.

7. Crack the blocking valve open.

Page 10: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Install the Sensing Element

8. If product leakage is observed, tighten the packing nut slightly.

Page 11: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Install the Sensing Element

9. Insert the sensing element fully into the vessel, making sure that the retaining groove slides into the packing nut.

Page 12: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Install the Sensing Element

10.Tighten the retention screws snugly into the retaining groove.

Page 13: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

11. Finally, tighten the packing nut again to prevent any leakage.

12. Installation is complete.

To Install the Sensing Element

Page 14: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification
Page 15: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

Retractable Probe Procedure For DumpStar Systems

and 700 Series Retractable Sensors

Page 16: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

Retractable Sensor Part Identification

Page 17: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

Note: Never touch either hex nut on the Primary Seal.

To Retract the Sensing Element

Page 18: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

Note: If necessary remove power wires and wiring to relay terminals.

To Retract the Sensing Element

Page 19: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Retract the Sensing Element

1. Stand clear of the sensing element, back out the retention screws.

Page 20: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Retract the Sensing Element

2. Loosen the packing nut at the slider gland, cautiously.

Page 21: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Retract the Sensing Element

Caution: It is possible that vessel pressure may push the sensor fully out to the blowout stop. This may occur suddenly.

Page 22: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Retract the Sensing Element

3. Withdraw the sensing element until contact is felt with the blowout stop (retaining clip).

Page 23: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

Caution: Flammable liquid can escape at this point. Do not perform this procedure near open flame or any ignition source.

To Retract the Sensing Element

Page 24: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Retract the Sensing Element

4. Close the block valve.

Page 25: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Retract the Sensing Element

5. Remove the ¼” NPT Drain plug to drain any contained liquid.

Page 26: Retractable Probe Procedure - Spartan Controls/media/resources/...Retractable Probe Procedure For DumpStar Systems and 700 Series Retractable Sensors Retractable Sensor Part Identification

To Retract the Sensing Element

5. Remove the sensor from the block valve and withdraw the unit.