residential structural inspector (cas) lesson 3 ... · pdf filetoday we will cover: material...
TRANSCRIPT
Residential Structural Inspector (CAS) Lesson 3
Foundations
(Based on the 2014 ORSC)
of 93 Updated: August 2016 1 Oregon Building Codes, All Rights Reserved
Introduction
Chapter 4 provides the requirements for the design and construction of
foundation systems for buildings regulated by the code. Provisions for seismic
load, flood load and frost protection are contained in this chapter. A foundation
system consists of two interdependent components: the foundation structure
itself and the supporting soil.
This chapter provides prescriptive
requirements for constructing footings
and walls for foundations of wood,
masonry, concrete, and precast concrete.
In addition to a foundations ability to
support the required design loads, this
chapter addresses several other factors that can affect foundation performance.
of 93 2
Today we will cover:
Material requirements for concrete and precast
concrete foundations
Minimum requirements for footings
Minimum requirements for foundation walls
Foundation drainage requirements
Foundation waterproofing and damp proofing
Underfloor area requirements
of 93 3
Foundation requirements
R401.2 Requirements: Foundation construction shall be capable of
accommodating all loads according to Section R301 and of transmitting the
resulting loads to the supporting soil. Where a construction joint is created
between a concrete footing and stem wall, a means of connection shall be
provided to accommodate lateral displacement. The connection shall be made
by the use of a key-way or other method in accordance with accepted foundation
design practices. Fill soils that support footings and foundations shall be
designed, installed and tested in accordance with accepted engineering practice.
of 93 4
Foundation requirements cont.
Foundation tie-in/connection
Where a construction joint is
created between a concrete
footing and stem wall, a means
of connection shall be provided
to accommodate lateral
displacement.
of 93 5
Foundation requirements cont.
of 93 6
Good Compaction
Poor Compaction
Compacted fill requirements
Fill soils that are intended to support a
residential structure are required to be
placed under an engineers direction
and have the appropriate testing (R401.2).
When placed properly, soils will be brought
up in lifts over a compacted original ground
surface.
When placed loosely then
surface compacted the structure can
settle into the un-compacted soils and
cause structural damage to the building.
of 93 7
Foundation requirements cont.
Proper compaction of the support soils for the structure as shown in the cross-
section below will prevent soil slough failure as seen below and the potential for
slab cracking and sinking due to soils settling below the slab.
Compacted or
native soils of 93 8
Site soils
Section R401.4 delineates
the requirements for allowable
soil bearing pressures for
typical residential applications.
On rare occasions the inspector
might encounter soils on site
that do not meet the basic
provisions as outlined in the
table and the sections. In these
cases the developer may need
to provide soils testing and
geotechnical evaluation in
order to assure stability and
safety for the residence.
of 93 9
Foundations on expansive soils
R403.1.10 Foundations on expansive soils: Foundation and floor slabs for
buildings located on expansive soils shall be designed in accordance with Section
1805.8 of the Building Code.
Exception: Slab-on-ground and other foundation systems which have performed
adequately in soil conditions similar to those encountered at the building site are
permitted subject to the approval of the building official.
R403.1.10.1 Expansive soils
Classifications: Soils meeting all four
of the following provisions will be
considered expansive:
1. Plasticity Index (PI) of 15 or greater.
2. More than 10 percent of the soil
particles pass a No.200 sieve.
3. More than 10 percent of the soil
particles are less than 5 micrometers in
size.
4. Expansion Index greater than 20.
of 93 10
Foundations on expansive soils cont.
Potential ways a structure will react to expansive soils
The inspector must be able to recognize potential expansive soils so that appropriate
measures may be taken when encountered in the field. Undetected expansive soils
can lead to severe structural damage in the future.
of 93 11
Surface drainage
R401.3 Drainage: Surface drainage shall
be diverted to a storm sewer conveyance
or other approved point of collection that
does not create a hazard. Lots shall be
graded to drain surface water away from
foundation walls.
The grade shall fall a minimum of
6 inches (152 mm)within the first
10 feet (3048 mm).
of 93 12
Surface drainage cont.
of 93 13
Surface drainage cont.
There will obviously be times when the lot configuration does not lend itself well to
being able to direct drainage 10 feet away from the structure. On these occasions
the code has given the exception which can be accomplished in a variety of
different ways.
of 93 14
Surface drainage cont.
of 93 15
Surface drainage cont.
These conditions are what the code
is trying to avoid when stipulating the
minimum drainage provisions.
of 93 16
Seismic design foundation provisions
R403.1.3 Continuous footing in Seismic Design Categories D1 and D2: The
braced wall panels at exterior walls of buildings located in Seismic Design
Categories D1 and D2 shall be supported by continuous footings. All required
interior braced wall panels in buildings with plan dimensions greater than 50 feet
(15 240 mm) shall also be supported by continuous footings.
The provisions in Section R403.1.3 are reiterated
in Section 602.10 for brace wall support.
of 93 17
Seismic design foundation provisions cont.
R403.1.4 Footing and stem wall reinforcing in Seismic Design Categories D1
and D2: Concrete footings located in Seismic Design Categories D1 and D2, as
established in Table R301.2(1), shall have minimum reinforcement in accordance
with this section and Figure R403.1(1)(A). Reinforcement shall be installed with
support and cover in accordance with Section R403.1.5.3.
Lateral loading from seismic or wind forces also affects the foundations
system. Loads are transmitted to the foundation via brace walls or shear
walls and this loading must be transferred to the supporting soils.
The higher seismic areas require special consideration for the foundations.
of 93 18
Seismic design foundation provisions cont.
Lateral loading from seismic or wind forces also affects the foundations
system. Loads are transmitted to the foundation via brace walls or shear walls
and this loading must be transferred to the supporting soils.
Section R602.10.7 provides the braced wall panel support criteria.
of 93 19
Seismic design foundation provisions cont.
of 93 20
Seismic design foundation provisions cont.
Due to the potential for foundation failure induced by soil movement during a seismic
event Section R403.1.4.1, R403.1.4.2 and R403.1.4.3 provide special reinforcement
requirements in foundations in Seismic Design Category structures in D1 and D2 regions. The details in Figure R403.1(1)(A) give pictorial representations of the
written provisions, below is detailing for a slab floor with turned down footings using
a construction joint at the top of the footing.
of 93 21
Frost protection
R403.1.5 Minimum depth: All exterior footings shall be placed at least 12 inches (305 mm)
below the finished grade on undisturbed ground surface. Where applicable, the depth of
footings shall also conform to Sections R403.1.5.1 through R403.1.5.2.
R403.1.5.1 Frost protection: Except where otherwise protected from frost, foundation walls,
piers and other permanent supports of buildings and structures shall be protected from frost by
one or more of the following methods:
1. Extended below the frost line specified in Table R301.2.(1);
2. Constructing in accordance with Section R403.3;
3. Constructing in accordance with ASCE 32; or
4. Erected on solid rock.
Exceptions:
1. Protection of freestanding accessory structures with an area of 600 square feet
(56m2) or less, of light-frame construction, with an eave height of 10 feet
(3048mm)or less shall not be required.
2. Protection of freestanding accessory structures with an area of 400 square feet
(37 m2) or less, of other than light-frame construction, with an eave height of 10 feet
(3048 mm) or less shall not be required.
3. Decks not supported by a dwelling need not be provided with f