ABSOLUTE INFRARED INSPECTION SERVICES
Sample
Heat Loss Inspection Report
Erie, PA
R
AI
IS
January 2011 I have thermally inspected your house. In this report for your review are photos showing conditions of the areas inspected and a description of findings. The inspection included:
1. Visual Inspection 2. Thermal Diagnostics 3. Thermal images, Real life photos and a description of findings
This infrared inspection is a guide for the building owner to qualify and quantify the presence of heat loss and or cold infiltration. Conducted and or convected heat loss and or cold infiltration can greatly affect heating and cooling costs. Conducted heat loss and or cold infiltration can be addressed by adjusting R values with insulation to reduce the amount of energy needed to heat and or cool an interior space. Convected heat loss and or cold infiltration can be addressed by evaluating leak areas and making corrections as needed. The conditions needed to qualify the presence of heat loss and or cold infiltration are an ideal minimum 40 deg F temperature difference between the inside and outside of the building being inspected to capture conducted heat loss and or cold infiltration. Other conditions such as positive, negative or static pressure of a building from hvac equipment and or weather conditions may reveal convected heat loss and or cold infiltration. These conditions may reveal a significant or insignificant amount of heat loss and or cold infiltration during the inspection however the information gathered is very valuable but may be inconsistent depending pressurization of the building and weather conditions. This report and associated recommendations are based on the conditions at the time of inspection. Both conditions and recommendations will change with time, changes to the building and normal wear and tear. While every effort has been taken to provide accurate interpretation of the anomalies found AIRIS assumes no liability directly or indirectly as a result of this inspection. I am looking forward to working with you in the future regarding any building inspection issues. In the mean time, should you have any questions regarding this report, do not hesitate to call. Craig Casler, CDT Level III Thermographer Level II ASNT Level I Ultrasound
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 68
Exterior Temperature 23
Thermostat Setting N/A
Comments: The heat loss through the attic vent indicates a lack of insulation and or an interior heat source to the attic.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:41:51 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 13
Comments: Exterior overview. The garage does generate heat. It is important to insulate the garage as well.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:14 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 71
Exterior Temperature 30
Comments: The heat loss in this image is likely due to missing or displaced insulation and or an interior heat source.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:41:51 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 13
Comments: Exterior overview.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 68
Exterior Temperature 23
Thermostat Setting N/A
Comments: The heat loss through the attic vent indicates a lack of insulation and or an interior heat source to the attic.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 26
Thermostat Setting N/A
Comments: Exterior Overview
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 26
Thermostat Setting N/A
Comments: The heat loss through the attic vent indicates a lack of insulation and or an interior heat source to the attic.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:14 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 15
Thermostat Setting
Comments: Exterior Overview.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:14 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 18
Thermostat Setting
Comments: The heat loss through the attic vent indicates a lack of insulation and or an interior heat source to the attic.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:41:51 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 13
Comments: Doors and windows are likely causes for cold infiltration. Door adjustments, insulation, caulking and weather stripping may be needed to reduce the amount of cold infiltration around the doors and windows.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:41:51 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 14
Comments: Doors and windows are likely causes for cold infiltration. Door adjustments, insulation, caulking and weather stripping may be needed to reduce the amount of cold infiltration around the doors and windows.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:14 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 15
Thermostat Setting
Comments: The cold and or air infiltration in this image may be missing or displaced insulation.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 68
Exterior Temperature 23
Thermostat Setting N/A
Comments: As the inspection moves to the inside the dark areas are generally cold infiltration. The cold and or air infiltration in this image may be missing or displaced insulation.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 26
Thermostat Setting N/A
Comments: The cold and or air infiltration in this image may be missing or displaced insulation.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 68
Exterior Temperature 23
Thermostat Setting N/A
Comments: The cold and or air infiltration in this image may be missing or displaced insulation.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:14 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 18
Thermostat Setting
Comments: The cold and or air infiltration in this image may be missing or displaced insulation.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 68
Exterior Temperature 23
Thermostat Setting N/A
Comments: The cold and or air infiltration in this image may be missing or displaced insulation.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 68
Exterior Temperature 23
Thermostat Setting N/A
Comments: The cold and or air infiltration in this image may be missing or displaced insulation.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:41:51 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 14
Comments: The cold and or air infiltration in this image may be missing or displaced insulation.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:41:51 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 14
Comments: Cold and or air infiltration.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:41:51 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 14
Comments: The cold and or air infiltration in this image may be missing or displaced insulation.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 26
Thermostat Setting N/A
Comments: Doors and windows are likely causes for cold infiltration. Door adjustments, insulation, caulking and weather stripping may be needed to reduce the amount of cold infiltration around the doors and windows.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:14 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 71
Exterior Temperature 30
Comments: This thermal image of the window indicates the insulated gas may have leaked from the window.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:41:51 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 13
Comments: Doors and windows are likely causes for cold infiltration. Door adjustments, insulation, caulking and weather stripping may be needed to reduce the amount of cold infiltration around the doors and windows.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:41:51 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 13
Comments: Cold infiltration at the bottom of a wall is likely due to the amount of framing, air spaces between framing and a lack of insulation combined.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 68
Exterior Temperature 23
Thermostat Setting N/A
Comments: The cold and or air infiltration in this image may be missing or displaced insulation.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:14 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 66
Exterior Temperature 27
Thermostat Setting
Comments: The cold and or air infiltration in this image may be missing or displaced insulation.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 68
Exterior Temperature 23
Thermostat Setting N/A
Comments: The heat loss in this image is likely due to missing or displaced insulation and or an interior heat source.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Date January 2011
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 68
Exterior Temperature 23
Thermostat Setting N/A
Comments: The heat loss in this image is likely due to missing or displaced insulation and or an interior heat source.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:14 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 18
Thermostat Setting
Comments: The heat loss in this image is likely due to missing or displaced insulation and or an interior heat source.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:14 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 18
Thermostat Setting
Comments: The heat loss in this image is likely due to missing or displaced insulation and or an interior heat source.
ABSOLUTE INFRARED INSPECTION SERVICES PO Box 9594 Erie, PA 16505 814-397-3382
Thermal Diagnostics Report By: Craig Casler Level III Thermographer Level II ASNT
Image Date January 2011
Image Time 7:41:51 AM
Customer
Address
City, State, Zip
Thermal Image Digital Image
Interior Temperature 70
Exterior Temperature 14
Comments: Having a heating and or cooling system in the attic space adds insulation challenges. Containing the heat and cooling within the heating and or cooling system is important for better efficiency of the system and added heat loss issues in the attic environment such as a source of heat loss contributing to ice buildup. Generally the attic floor may be insulated with an R30 between the interior conditioned space and the attic space. The insulation generally used in the heating system may be a lot less adding heat sources in the attic and reducing the efficiency of the heating and cooling system.