1 Sales 800-633-0405 www.productivity2000.com Terminal Block sold separately, (see wiring options on page 5). Warranty: Thirty-day money-back guarantee. Two-year limited replacement. (See www.productivity2000.com for details). 1–9.453V 2 18.23 3 UNDER 4 SPARE 2000 WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from area to area and it is your responsibility to determine which codes should be followed, and to verify that the equipment, installation, and operation are in compliance with the latest revision of these codes. Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guar- antee the products described in this publication are suitable for your particular application, nor do we assume any responsibility for your product design, installation, or operation. If you have any questions concerning the installation or operation of this equipment, or if you need additional information, please call Technical Support at 770-844-4200. This publication is based on information that was available at the time it was printed. At AutomationDirect.com ® we constantly strive to improve our products and services, so we reserve the right to make changes to the products and/or publications at any time without notice and without any obligation. This publication may also discuss features that may not be available in certain revisions of the product. Removable Terminal Block Specifications Part Number P2-RTB P2-RTB-1 Number of positions 18 Screw Terminals 18 Spring Clamp Terminals Wire Range 30 - 16 AWG (0.051 - 1.31 mm²) Solid / Stranded Conductor 3/64 in. (1.2 mm) Insulation Maximum 1/4 in (6 - 7 mm) Strip Length 28-16 AWG (0.081 - 1.31 mm²) Solid / Stranded Conductor 3/64 in (1.2 mm) Insulation Maximum 19/64 in (7 - 8 mm) Strip Length Conductors “USE COPPER CONDUCTORS, 75ºC” or equivalent. Screw Driver Width 1/8 in (3.8 mm) Maximum Screw Size M2 N/A Screw Torque 2.5 lb·in (0.28 N·m) N/A P2-04AD Analog Input The P2-04AD Voltage/Current Analog Input Module provides four channels for receiving ±10VDC, ±5VDC, 0 - 5 VDC and 0 - 20 mA signals for use with the Productivity2000 system. Warning .................................. 1 Removable Terminal Block Specifications. . . . . . . . 1 General Specifications ...................... 2 Input Specifications ......................... 2 Wiring Diagram and Schematic................ 3 Module Installation Procedure ................. 4 QR Code ................................. 4 Hot Swap Information ....................... 4 Wiring Options ............................. 5 Module Configuration ....................... 5 Linear Scaling ............................. 6 Non-Linear Scaling ......................... 6 OLED Panel Display Menus .................. 7

Upload: duongxuyen

Post on 20-Mar-2018

219 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: Removable Terminal Block Specifications - · PDF file · 2018-02-28Terminal Block sold separately, (see wiring options on page 5). ... Full Scale Calibration Error ±0.2% of range

1Sales 800-633-0405 www.productivity2000.com

Terminal Block sold separately, (see wiring options on page 5).Warranty: Thirty-day money-back guarantee. Two-year limited replacement. (See www.productivity2000.com for details).

1–9.453V2 18.233 UNDER4 SPARE

2000WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from area to area and it is your responsibility to determine which codes should be followed, and to verify that the equipment, installation, and operation are in compliance with the latest revision of these codes.Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guar-antee the products described in this publication are suitable for your particular application, nor do we assume any responsibility for your product design, installation, or operation.If you have any questions concerning the installation or operation of this equipment, or if you need additional information, please call Technical Support at 770-844-4200.This publication is based on information that was available at the time it was printed. At AutomationDirect.com® we constantly strive to improve our products and services, so we reserve the right to make changes to the products and/or publications at any time without notice and without any obligation. This publication may also discuss features that may not be available in certain revisions of the product.

Removable Terminal Block SpecificationsPart Number P2-RTB P2-RTB-1

Number of positions 18 Screw Terminals 18 Spring Clamp Terminals

Wire Range

30 - 16 AWG (0.051 - 1.31 mm²)Solid / Stranded Conductor3/64 in. (1.2 mm) Insulation Maximum1/4 in (6 - 7 mm) Strip Length

28-16 AWG (0.081 - 1.31 mm²)Solid / Stranded Conductor3/64 in (1.2 mm) Insulation Maximum19/64 in (7 - 8 mm) Strip Length

Conductors “USE COPPER CONDUCTORS, 75ºC” or equivalent.Screw Driver Width 1/8 in (3.8 mm) Maximum

Screw Size M2 N/A

Screw Torque 2.5 lb·in (0.28 N·m) N/A

P2-04AD Analog InputThe P2-04AD Voltage/Current Analog Input Module provides four channels for receiving ±10VDC, ±5VDC, 0 - 5 VDC and 0 - 20 mA signals for use with the Productivity2000 system.

Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Removable Terminal Block Specifications. . . . . . . . 1General Specifications . . . . . . . . . . . . . . . . . . . . . . 2Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 2Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3Module Installation Procedure . . . . . . . . . . . . . . . . . 4QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Hot Swap Information . . . . . . . . . . . . . . . . . . . . . . . 4Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Module Configuration . . . . . . . . . . . . . . . . . . . . . . . 5Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Non-Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . 6OLED Panel Display Menus . . . . . . . . . . . . . . . . . . 7

Page 2: Removable Terminal Block Specifications - · PDF file · 2018-02-28Terminal Block sold separately, (see wiring options on page 5). ... Full Scale Calibration Error ±0.2% of range

2 Tech Support 770-844-4200www.productivity2000.com

General SpecificationsOperating Temperature 0º to 60ºC (32º to 140ºF)

Storage Temperature -20º to 70ºC (-4º to 158ºF)

Humidity 5 to 95% (non-condensing)

Environmental Air No corrosive gases permitted

Vibration IEC60068-2-6 (Test Fc)

Shock IEC60068-2-27 (Test Ea)

Field to Logic Side Isolation 1800VAC applied for 1 second

Insulation Resistance > 10MΩ @ 500VDC

Heat Dissipation 1.4 W

Enclosure Type Open Equipment

Agency ApprovalsUL508 File E139594, Canada & USACE (EN61131-2*)

Module Keying to Backplane Electronic

Module Location Any I/O slot in a Productivity2000 System

Field Wiring Use ZIPLink Wiring System or removable terminal block (not included). See “Wiring Options” on page 5.

EU DirectiveSee the “EU Directive” topic in the Productivity Suite Help File. Information can also be obtained at: www.productivity2000.com

Connector Type (not included) 18-position removable terminal block

Weight 90g (3.2 oz)

Input SpecificationsInput Channels 4Module Signal Input Ranges ±10 VDC, ±5 VDC, 0-5 VDC, 0-10 VDC, 0-20 mASignal Resolution 16-bit

Resolution Value of LSB (least significant bit)

1 LSB = 1 count ±10 V = 305μV ±5 V = 152μV 0-5 V = 76μV 0-10 V = 152μV 0-20 mA = 0.305μA

Data Range 0-65535 counts unipolar -32768 to +32767 counts bipolar

Maximum Continuous Overload ±31 mA, current input ±100 V, voltage input

Input Impedance 1MΩ±10% voltage input 250Ω±0.1% 1/4 W current input

Hardware Filter Characteristics Low Pass 1st order, -3dB @ 48Hz

Sample Duration Time 2ms per channel (does not include ladder scan time)

All Channel Update Rate 8msOpen Circuit Detection Time Zero reading within 1s (current input only)Conversion Method Successive approximationAccuracy vs. Temperature ±10PPM / ºC maximum

Maximum Inaccuracy 0.1% of range voltage, 0.2% of range current (including temperature drift)

Linearity Error (end to end)±0.01% of range max., ±10 V & ±5 V ±0.015% of range max., 0-10 V, 0-5 V & 0-20 mA Monotonic with no missing codes

Input Stability and Repeatability ±0.035% of range (after 10 min. warmup)Full Scale Calibration Error ±0.2% of range maximumOffset Calibration Error ±0.065% of range maximumMax Crosstalk -96dB, 1 LSB

Recommended Fuse (external) Edison S500-32-R, 0.032A fuse on current inputs only

External DC Power Required 24VDC (-20% / +25%) 35mA

*Meets EMC and Safety requirements. See the D.O.C. for details.

Page 3: Removable Terminal Block Specifications - · PDF file · 2018-02-28Terminal Block sold separately, (see wiring options on page 5). ... Full Scale Calibration Error ±0.2% of range

7Sales 800-633-0405 www.productivity2000.com

Momentarily Press SEL button totoggle throughsecondary displays

Hold SEL button down to cycle through primary screens. Release button to select screen.Power On

Appears initially

These screens will then auto cycle

Fault Messages – Appear in place of data during a fault condition.

Error Messages:An existing error will be inserted into the cycling Status Info screen.

This screen will auto cycle with status information

Input signal is OVER the maximum detectable by the module.Input signal < range minimum. (Voltage only)

PASSEDSELFTEST

P2-04AD Fw. Rev. 1.00

5V, 10V,+/-5V,+/-10V,0-20mA

ChannelsEnabled:4

DISPLAYSETUPINFO

DISPLAYUNITSDECIMALCOUNTS

DISPLAYUNITSHEXCOUNTS

DISPLAYSTATUSINFO

DISPLAYUNITS+/-V,mA,V

1 000002 000003 SPARE4 00000

1 0000H2 0000H3 SPARE4 0000H

1 0.000V2 +0.00V3 SPARE4 00.00

End ofStatusMenuList

MISSINGEXTERNAL24VDC

MISSINGCONFIGDATA

End ofStatusMenuList

SELFTESTFAILREPLACEMODULE

1 OVER2 UNDER34

OLED Panel Display

Page 4: Removable Terminal Block Specifications - · PDF file · 2018-02-28Terminal Block sold separately, (see wiring options on page 5). ... Full Scale Calibration Error ±0.2% of range

6 Tech Support 770-844-4200www.productivity2000.com

0.511.552.2534.556.7570000000

01234566.570000000

Level Transmitter Tank Level

70000000

Select the minimum and maximum values of the raw input signal. These values will relate to the minimum and maximum scaled values.

76543210

1 2 3 4 5 6 7

The Scale (Linear) function can be used to:• Convert analog field input signals from the range which is native to the

analog input module to an application specific range.• Make other linear conversions in ranges appropriate to the application.

The Scale (Non-Linear) function can be used for Non-Linear applications.

Linear Scaling Non-Linear Scaling

Select the Input and Output tags appropriate for the application. Convert raw input signals to engineering units for use in the program, or convert engineering units to output signals for control purposes

max

min

min max

12500

0

65535

220

Level Transmitter Tank Level

Page 5: Removable Terminal Block Specifications - · PDF file · 2018-02-28Terminal Block sold separately, (see wiring options on page 5). ... Full Scale Calibration Error ±0.2% of range

3Sales 800-633-0405 www.productivity2000.com

Voltage Input Circuits

Current Sinking Input CircuitsAn Edison S500-32-R 0.032A fast-acting fuse is recommended for all current loops.

COM

V+

4-Wire VoltageTransmitter

4-Wire Transmitter

Optional TransmitterPower SupplyAC or DC

- +

24 VDC User Supplied Power

+3-Wire VoltageTransmitter

V+

COM

3-Wire Transmitter

.032A2-Wire 4-20 mATransmitter

fuse

fuse

.032Afuse

+

.032A

- +

- +

V+

I+

COM

V+

I+

3-Wire CurrentTransmitter

4-Wire 4-20 mATransmitter

2-Wire Transmitter

3-Wire Transmitter

4-Wire Transmitter

PowerSupply

24VDC User Supplied Power

+

+

+

User SuppliedTransmitter Power AC or DC

V+

I+

COM

COM

V1+I1+V2+I2+V3+I3+

I4+V4+

COMCOM

24VDC-24VDC+- +

24 VDC UserSupplied Power

CH1 ADC

CH2 ADC

CH3 ADC

CH4 ADC

ISOLATEDANALOGCIRCUITPOWER

ISOLATED ANALOGCIRCUIT COMMON

INTERNALMODULE CIRCUITRY

COM

COM 12

34

56

78

910

1112

1813

1415

1617

Wiring Diagram Schematic

Notes: 1. Shield connected to signal source

common.2. If current is chosen, I+ must be

jumped to V+. For example when using 4-20 mA source for Input 3, I3+ must be jumped to V3+.

Page 6: Removable Terminal Block Specifications - · PDF file · 2018-02-28Terminal Block sold separately, (see wiring options on page 5). ... Full Scale Calibration Error ±0.2% of range

4 Tech Support 770-844-4200www.productivity2000.com

QR Code

Use any QR Code reader application to display the module’s product insert.

Important Hot-Swap InformationThe Productivity2000 System supports hot-swap! Individual modules can be taken offline, removed, and replaced while the rest of the system continues con-trolling your process. Before attempting to use the hot-swap feature, be sure to read the hot-swap topic in the programming software’s help file or our online documen-tation at AutomationDirect.com for details on how to plan your installation for use of this powerful feature.

1 Alignwith slot

2 rotateto seatedposition

Module Installation

WARNING: Do not apply field power until the following steps are completed. See hot-swapping procedure for exceptions.

WIRE STRIPLENGTHWIRE STRIPLENGTH

Step One: Align module catch with base slot and rotate module into connector.

Locked Unlocked

Step Two: Pull top locking tab toward module face. Click indi-cates lock is engaged.

Step Three: Attach field wiring using the removable terminal block or ZIPLink wiring system.

Caution: If possible, remove field power prior to proceeding. If not, then EXTREME care MUST be taken to prevent damage to the module, or even personal injury due to a short circuit from the live terminal block.

Page 7: Removable Terminal Block Specifications - · PDF file · 2018-02-28Terminal Block sold separately, (see wiring options on page 5). ... Full Scale Calibration Error ±0.2% of range

5Sales 800-633-0405 www.productivity2000.com

Using the Hardware Configuration tool in the Productivity Suite programming software, drag and drop the P2-04AD module into the base configuration. Select Automatic Module Verification or No Verification and Enable Hot Swap. Select Range type for each input. If desired, assign a User Tagname to each input point (channel) selected and to each Status Bit Item.

Wiring Options 1 ZIPLink Connection System

Cable + ZIPLink Module = Complete SystemZIPLink pre-wired terminal block cables

0.5m (1.6FT) cable1.0m (3.3FT) cable2.0m (6.6FT) cable

ZIPLink Modules

Feed through

ZL-P2-CBL18ZL-P2-CBL18-1ZL-P2-CBL18-2

ZL-RTB20

2 Terminal Block with pigtail cable

1.0m (3.3FT) cable2.0m (6.6FT) cable

ZL-P2-CBL18-1PZL-P2-CBL18-2P

3 Screw Terminal Block onlyP2-RTB(Quantity 1)

4 Spring Clamp Terminal Block onlyP2-RTB-1(Quantity 1)

Module Configuration

Page 8: Removable Terminal Block Specifications - · PDF file · 2018-02-28Terminal Block sold separately, (see wiring options on page 5). ... Full Scale Calibration Error ±0.2% of range

8 Tech Support 770-844-4200www.productivity2000.com

Document Name Edition/Revision DateP2-04AD-DS 1st Ed. Rev A 2/22/2016

Copyright 2016, AutomationDirect.com Incorporated/All Rights Reserved Worldwide