relays

7
 6/ 26/2014 rel ay s - | FaaDoOEngi neers.com ht tp: //w w w.faadooengi neers.com/ threads/ 35620-rel ay s 1/ 7 Types of Relays Types of protection relays are mainly based on their characteristic, logic, on actuating parameter and operation mechanism. Based on operation mechanism protection relay can be categorized as electro magnetic relay, static relay and mechanical relay.  Act ually relay is nothing but a combination of one or more open or closed contact s. Th ese all or s ome specific contact s t he relay change their state when actuating parameters are applied to the relay. That means open contacts become closed and closed contacts become open. In electromagnetic relay these closing and opening of relay contacts are done by electromagnetic action of a solenoid. In mechanical relay these closing and opening of relay contacts are done by mechanical displacement of different gear level system. In static relay it is mainly done by semiconductor switches like thyristor. In digital relay on and off state can be referred as 1 and 0 state. Based on Characteristic the protection relay can be categorized as- 1. Def inite time relays Definite Time Over Current Relay This relay is created by applying intentional time delay after crossing pick up value of the current. A definite time over current relay can be adjusted to issue a trip output at definite amount of time after it picks up. Thus, it has a time setting adjustment and pick up adjustment. 1. Inv erse time relays with definite minimum time(IDMT ) Ideal inverse time characteristics can not be achieved, in an over current relay. As the current in the system increases, the secondary current of the current t ransfo rmer  is increased proportionally. The secondary current is fed to the relay current coil. But when the CT be comes saturated, there would not be further prop ortional increase of CT secondary current with increased syst em curre nt. From this phenomenon it is clear that from trick value to certain range of faulty level, an inverse time relay shows exact inverse characteristic. But after this level of fault, the CT becomes saturated and relay current does not increase further with increasing faulty level of the system. As the relay current is not increased further, there would not be any further reduction in time of operation in the relay. This time is referred as minimum time of operation. Hence, the characteristic is inverse in the initial part, which tends to a definite minimum operating time as the electric current becomes very high. That is why the relay is referred as inverse definite minimum time over current relay or simply IDMT relay. Sponsored Ads

Upload: rajeev-rawat

Post on 04-Nov-2015

6 views

Category:

Documents


0 download

DESCRIPTION

relay

TRANSCRIPT

  • 6/26/2014 relays - | FaaDoOEngineers.com

    http://www.faadooengineers.com/threads/35620-relays 1/7

    Types of Relays

    Types of protection relays are mainly based on their characteristic, logic, on actuating parameter and operation mechanism.

    Based on operation mechanism protection relay can be categorized as electro magnetic relay, static relay and mechanical relay.

    Actually relay is nothing but a combination of one or more open or closed contacts. These all or some specific contacts the relay

    change their state when actuating parameters are applied to the relay. That means open contacts become closed and closed

    contacts become open. In electromagnetic relay these closing and opening of relay contacts are done by electromagnetic action

    of a solenoid.

    In mechanical relay these closing and opening of relay contacts are done by mechanical displacement of different gear level

    system.

    In static relay it is mainly done by semiconductor switches like thyristor.

    In digital relay on and off state can be referred as 1 and 0 state.

    Based on Characteristic the protection relay can be categorized as-

    1. Definite time relays

    Definite Time Over Current Relay

    This relay is created by applying intentional time delay after crossing pick up value of the current. A definite time over current

    relay can be adjusted to issue a trip output at definite amount of time after it picks up. Thus, it has a time setting adjustment

    and pick up adjustment.

    1. Inverse time relays with definite minimum time(IDMT)

    Ideal inverse time characteristics can not be achieved, in an over current relay. As the current in the system increases, the

    secondary current of the current transformer is increased proportionally. The secondary current is fed to the relay current coil.

    But when the CT becomes saturated, there would not be further proportional increase of CT secondary current with increased

    system current.

    From this phenomenon it is clear that from trick value to certain range of faulty level, an inverse time relay shows exact inverse

    characteristic. But after this level of fault, the CT becomes saturated and relay current does not increase further with increasing

    faulty level of the system. As the relay current is not increased further, there would not be any further reduction in time of

    operation in the relay. This time is referred as minimum time of operation.

    Hence, the characteristic is inverse in the initial part, which tends to a definite minimum operating time as the electric current

    becomes very high. That is why the relay is referred as inverse definite minimum time over current relay or simply IDMT

    relay.

    Sponsored Ads

  • 6/26/2014 relays - | FaaDoOEngineers.com

    http://www.faadooengineers.com/threads/35620-relays 2/7

    1. Instantaneous relays.

    Instantaneous over current relay, which operates very fast with no intentional time delay and the operating time of these relay can

    be as low as 0.01sec . These relay operates only when the impedance between the relay and the source zs is very small

    compared to the impedance to the impedance of the protected section zl .

    7. Voltage restraint over current relay.

    The voltage restrained over current protection function(51V) is used to protect generators. The operation set point is adjusted

    according to the voltage to take into account cases of faults close to the generator which cause voltage dips and short circuit

    current. This protection function is three-pole. It picks up if one ,two or three phase currents reach the voltage-adjusted operation

    set point.

    Based on of logic the protection relay can be categorized as-

    1. Differential.

    Principle of Differential Protection scheme is one simple conceptual technique. The differential relay actually compares

    between primary current and secondary current of power transformer, if any unbalance found in between primary and secondary

    currents the relay will actuate and inter trip both the primary and secondary circuit breaker of the transformer.

    [IMG]file:///C:\Users\arptst\AppData\Local\Temp\msohtmlclip1\01\clip_image001.gif[/IMG]

    2. Unbalance.

    3. Neutral displacement.

    4. Directional.

    The over-current protection can be given directional feature by adding directional element in the protection system.

    Directional over-current protection responds to over-currents for a particular direction flow. If power flow is in the

    opposite direction, the directional over-current protection remains un-operative.

    Directional over-current protection comprises over-current relay and power directional relay- in a single relay casing.

    The power directional relay does not measure the power but is arranged to respond to the direction of power flow.

    Directional operation of relay is used where the selectivity can be achieved by directional relaying. The directional

    relay recognizes the direction in which fault occurs, relative to the location of the relay. It is set such that it actuates

    for faults occurring in one direction only. It does not act for faults occurring in the other direction. Consider a feeder

    AC (Fig. 9) passing through sub-section B. The circuit breaker CB3 is provided with a directional

    [IMG]file:///C:\Users\arptst\AppData\Local\Temp\msohtmlclip1\01\clip_image002.emz[/IMG](Fig. 9) Principle of directional

    protection

    Relay `R' which will trip the breaker CB3 if fault power flow in direction C alone. Therefore for faults in feeder AB,

    the circuit breaker CB3 does not trip unnecessarily. However for faults in feeder BC the circuit-breaker CB3 trips

    Because it's protective relaying is set with a directional feature to act in

  • 6/26/2014 relays - | FaaDoOEngineers.com

    http://www.faadooengineers.com/threads/35620-relays 3/7

    direction AC

    Another interesting example of directional protection is that of reverse power protection of generator (Fig. 10). If the

    prime mover fails, the generator continues to run as a motor and takes power from bus-bars.

    [IMG]file:///C:\Users\arptst\AppData\Local\Temp\msohtmlclip1\01\clip_image003.emz[/IMG](Fig. 10) Reverse powers protection

    against motoring action of a generator

    Directional power protection operates in accordance with the direction of power flow.

    Reverse power protection operates when the power direction is reversed in relation to the normal working direction.

    Reverse power relay is different in construction than directional over-current relay.

    In directional over-current relay, the directional element does not measure the magnitude of power. It senses only

    direction of power flow. However, in Reverse Power Relays, the directional element measures magnitude and

    direction of power flow.

    1. Restricted earth fault.

    An external fault in the star side will result in current flowing in the line current transformer of the affected phase and at the same

    time a balancing current flows in the neutral current transformer, hence the resultant electric current in the relay is therefore zero.

    So this REF relay will not be actuated for external earth fault. But during internal fault the neutral current transformer only carries

    the unbalance fault current and operation of Restricted Earth Fault Relay takes place. This scheme of restricted earth fault

    protection is very sensitive for internal earth fault of electrical power transformer. The protection scheme is comparatively

    cheaper than differential protection scheme

    6. Over fluxing.

    7. Distance schemes.

    8. Bus bar protection.

    9. Reverse power relays.

    10.Loss of excitation.

    11.Negative phase sequence relays etc.

    Based on actuating parameter the protection relay can be categorized as-

    1.Current relays.

    2. Voltage relays.

    3. Frequency relays.

    4. Power relays etc.

    Based on application the protection relay can be categorized as-

    1.Primary relay.

    2. Backup relay.

    Primary relay or primary protection relay is the first line of power system protection whereas backup relay is operated only when

    primary relay fails to be operated during fault. Hence backup relay is slower in action than primary relay. Any relay may fail to be

    operated due to any of the following reasons,

    1) The protective relay itself is defective.

    2) DC Trip voltage supply to the relay is unavailable.

    3) Trip lead from relay panel to circuit breaker is disconnected.

    4) Trip coil in the circuit breaker is disconnected or defective.

    5) Current or voltage signals from CT or PT respectively is unavailable.

    As because backup relay operates only when primary relay fails, backup protection relay should not have anything common with

    primary protection relay.

    Some examples of Mechanical Relay are-

    1. Thermal

    (a) OT trip (Oil Temperature Trip)

  • 6/26/2014 relays - | FaaDoOEngineers.com

    http://www.faadooengineers.com/threads/35620-relays 4/7

    (b) WT trip (Winding Temperature Trip)

    (C) Bearing temp trip etc.

    2. Float type

    (a) Buchholz

    (b) OSR

    (c) PRV

    (d) Water level Controls etc.

    3. Pressure Switches.

    4. Mechanical Interlocks.

    5. Pole discrepancy Relay.

    WORKING OF SINGLE-POLE DOUBLE-THROW RELAY

    SPDT relay is an electromagnetic switch consisting of a coil (terminals 85 & 86), 1 common terminal (30), 1 normally closed

    terminal (87a) and a normally open terminal (87).

    [IMG]file:///C:\Users\arptst\AppData\Local\Temp\msohtmlclip1\01\clip_image004.jpg[/IMG]

    Fig1. Poles of a SPDT Relay Switch

    When the coil of the relay is at rest (not energized), the common terminal (30) and the normally closed terminal (87a) have

    continuity.

    [IMG]file:///C:\Users\arptst\AppData\Local\Temp\msohtmlclip1\01\clip_image005.jpg[/IMG]

    Fig2. Un-energized Relay Position

    When the coil is energized, the common terminal (30) and the normally open terminal (87) have continuity.

    [IMG]file:///C:\Users\arptst\AppData\Local\Temp\msohtmlclip1\01\clip_image006.jpg[/IMG]

    Fig3. Energized Relay Position

    Basically, the coil is an electromagnet that causes the arm that is always connected to the common (30) to pivot when

    energized thereby breaking contact with the normally closed terminal (87a) and making it with the normally open terminal (87).

    Below is an example of how the connections are made to a load in a circuit using a SPDT relay switch?

    [IMG]file:///C:\Users\arptst\AppData\Local\Temp\msohtmlclip1\01\clip_image007.jpg[/IMG]

    Fig4. Connection of an SPDT Relay to Load

    When the relay coil is energized, contact is established between the common (COM) and normally-open (NO) terminal thereby

    completing the supply connections to the load. Hence, the load is switched on when the relay is energized. Also check this

    article to understand the working of relays with the help of pictures, here - How Relay works

    Different Types of Relay

    1. Single Pole Single Throw (SPST)- these types of relay comprise of 4 terminals. Two terminals are used as coil points and

    other two can be used to connect or disconnect the circuit (A and B).

    2. Single Pole Double Throw (SPDT)- these types of relay comprise of 5 terminals two for coil one for common terminal(C)

    and rest two can be connected to the common terminal.

    3. Double Pole Single Throw (DPST)- these types of relay comprise of 6 terminal two for coil and other four for connecting and

    disconnecting two device. In other words it contains two SPST relay in one package.

    4.DoublePole Double Throw(SPDT)- these types of relay comprise of 8 terminal two for coil and another two as common point

    and rest for connecting and disconnecting devices. In another words in this two SPDT relay are connected in one package.

    [IMG]file:///C:\Users\arptst\AppData\Local\Temp\msohtmlclip1\01\clip_image008.png[/IMG]

    Comparison of Different Type Relay:

    Characteristic Electro Mechanical

    Relay

    Static Relay Digital Relay Numerical Relay

    Technology

    Standard

    1st generation

    Relays.

    2nd generation

    Relays.

    Present generation Relays. Present generation Relays.

  • 6/26/2014 relays - | FaaDoOEngineers.com

    http://www.faadooengineers.com/threads/35620-relays 5/7

    Operating

    Principle

    They use principle of

    electromagnetic

    principle.

    In this relays

    transistors and ICs

    r been used

    They use Microprocessor. Within built

    software with predefined values

    They use Microprocessor. Within built

    software with predefined values

    Measuring

    elements/

    Hardware

    Induction

    disc,Electromagnets,

    Induction cup,

    Balance Beam

    R, L, C, Transistors,

    Analogue ICs

    comparators

    Microprocessors, Digital ICs, Digital

    Signal Processors

    Microprocessor s,Digital ICs, DigitalSignal

    processors

    Measuring

    method

    Electrical

    Qtysconverted

    intomechanical

    force, torque

    Level

    detects,comparison

    withreference value

    in analogue

    Comparator

    A/D

    conversion,Numericalalgorithmtechniques

    A/D

    conversion,Numericalalgorithmtechniques

    Surrounding

    Environment

    Depend upon

    gravitation and the

    value changes to the

    surrounding

    magnetic fields also.

    There value may

    vary with respect to

    temperature also.

    Relay Size Bulky Small Small Compact

    Speed of

    Response

    Slow Fast Fast Very Fast

    Timing

    function

    Mechanical clock

    works, dashpot

    Static timers Counter Counter

    Time of

    Accuracy

    Temp .Dependant Temp. Dependant Stable Stable

    Reliability High Low High High

    Vibration Proof No Yes Yes Yes

    Characteristics Limited Wide Wide Wide

    Requirement Required Required Not Required Not Required

  • 6/26/2014 relays - | FaaDoOEngineers.com

    http://www.faadooengineers.com/threads/35620-relays 6/7

    of Draw Out

    CT Burden High Low Low Low

    CT Burden 8 to 10 VA 1 VA 20 Pico Farads > 20 Pico Farads

    Deterioration

    due to

    Operation

    Yes No No No

    Relay

    Programming

    No Partially Programmable Programmable

    SCADA

    Compatibility

    No No Possible Yes

    Operational

    value

    indication

    Not Possible Possible Possible Possible

    Visual

    indication

    Flags, targets LEDs LEDs, LCD LEDs, LCD

    Self monitoring No Yes Yes Yes

  • 6/26/2014 relays - | FaaDoOEngineers.com

    http://www.faadooengineers.com/threads/35620-relays 7/7

    Parameter

    setting

    Plug setting, dial

    setting

    Thumb wheel,dual

    in line switches

    Keypad for numeric values,through

    computer

    Keypad for numeric values,through

    computer

    Fault

    Disturbance

    Recording

    Not possible Not possible possible possible