reg 670 app

Upload: johnardnosil9103

Post on 04-Apr-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 REG 670 App.

    1/7

    IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at

    30% of Ir

    IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at

    100% of Ir

    UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at

    5% of Ur

    UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at

    30% of Ur

    UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at

    100% of Ur

    IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir

    IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir

    IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir

    IBase 1 - 99999 A 1 3000 Base setting for current level

    UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level

    Mode L1, L2, L3

    Arone

    Pos Seq

    L1L2

    L2L3

    L3L1

    L1

    L2

    L3

    - - Pos Seq Selection of measured current and

    voltage

    Negative sequence time overcurrent

    protection for machines

    NS2PTOC 2I2> 46I2

    Negative sequence overcurrent protection for machines NS2PTOC is intended

    primarily for the protection of generators against possible overheating of the rotor

    caused by negative sequence component in the stator current.

    The negative sequence currents in a generator may, among others, be caused by:

    Section 3 1MRK 502 030-UEN AIED application

    298

    Application manual

  • 7/30/2019 REG 670 App.

    2/7

    Unbalanced loads

    Line to line faults

    Line to ground faults

    Broken conductors

    Malfunction of one or more poles of a circuit breaker or a disconnector

    NS2PTOC can also be used as a backup protection, that is, to protect the generator

    in the event line protections or circuit breakers fail to perform for unbalanced

    system faults.

    To provide an effective protection for the generator for external unbalanced

    conditions, NS2PTOC is able to directly measure the negative sequence current.

    NS2PTOC also have a time delay characteristic which matches the heating

    characteristic of the generator I22t = K as defined in standard.

    where:

    I2 is negative sequence current expressed in per unit of the rated generator current

    t is operating time in seconds

    K is a constant which depends of the generators size and design

    A wide range of I22t settings is available, which provide the sensitivity and

    capability necessary to detect and trip for negative sequence currents down to the

    continuous capability of a generator.

    A separate output is available as an alarm feature to warn the operator of apotentially dangerous situation.

    Negative-sequence time overcurrent protection NS2PTOC is designed to provide a

    reliable protection for generators of all types and sizes against the effect of

    unbalanced system conditions.

    The following features are available:

    Two steps, independently adjustable, with separate tripping outputs.

    Sensitive protection, capable of detecting and tripping for negative sequence

    currents down to 3% of rated generator current with high accuracy. Two time delay characteristics for step 1:

    Definite time delay

    Inverse time delay

    The inverse time overcurrent characteristic matches

    22I t K= capability curve

    of the generators.

    Wide range of settings for generator capability constant Kis provided, from 1

    to 99 seconds, as this constant may vary greatly with the type of generator.

    1MRK 502 030-UEN A Section 3IED application

    299

    Application manual

  • 7/30/2019 REG 670 App.

    3/7

    Minimum operate time delay for inverse time characteristic, freely settable.

    This setting assures appropriate coordination with, for example, line protections.

    Maximum operate time delay for inverse time characteristic, freely settable.

    Inverse reset characteristic which approximates generator rotor cooling rates

    and provides reduced operate time if an unbalance reoccurs before the

    protection resets.

    Service value that is, measured negative sequence current value, in primary

    Amperes, is available through the local HMI.

    During unbalanced loading, negative sequence current flows in the stator winding.

    Negative sequence current in the stator winding will induce double frequency

    current in the rotor surface and cause heating in almost all parts of the generator rotor.

    When the negative sequence current increases beyond the generators continuous

    unbalance current capability, the rotor temperature will increase. If the generator is

    not tripped, a rotor failure may occur. Therefore, industry standards has been

    established that determine generator continuous and short-time unbalanced current

    capabilities in terms of negative sequence current I2 and rotor heating criteria2

    2I t .

    Typical short-time capability (referred to as unbalanced fault capability) expressed

    in terms of rotor heating criterion2

    2I t K= is shown below in Table 103.

    [ ]2

    2I t K s=

    Salient pole generator 40

    Synchronous condenser 30

    Cylindrical rotor generators: Indirectly cooled 30

    Directly cooled (0 800 MVA) 10

    Directly cooled (801 1600

    MVA)

    See Figure 119

    Fig 119 shows a graphical representation of the relationship between generator

    22I t capability and generator MVA rating for directly cooled (conductor cooled)

    generators. For example, a 500 MVA generator would have K = 10 seconds and a

    1600 MVA generator would have K = 5 seconds. Unbalanced short-time negative

    sequence current I2 is expressed in per unit of rated generator current and time t in

    seconds.

    Section 3 1MRK 502 030-UEN AIED application

    300

    Application manual

  • 7/30/2019 REG 670 App.

    4/7

    en08000358.vsd

    IEC08000358 V1 EN

    Figure 119: Short-time unbalanced current capability of direct cooled generators

    Continuous I2 - capability of generators is also covered by the standard. Table 104

    below (from ANSI standard C50.13) contains the suggested capability:

    Salient Pole

    with damper winding 10

    without damper winding 5

    Cylindrical Rotor

    Indirectly cooled 10

    Directly cooled

    to 960 MVA 8

    961 to 1200 MVA 6

    1201 to 1500 MVA 5

    As it is described in the table above that the continuous negative sequence current

    capability of the generator is in range of 5% to 10% of the rated generator current.

    During an open conductor or open generator breaker pole condition, the negative

    sequence current can be in the range of 10% to 30% of the rated generator current.

    Other generator or system protections will not usually detect this condition and the

    only protection is the negative sequence overcurrent protection.

    Inducing of negative sequence current in a generator can result from any system

    unbalance and these, in turn, may be caused by:

    Unbalanced loads such as

    Single phase railroad load

    Unbalanced system faults such as

    1MRK 502 030-UEN A Section 3IED application

    301

    Application manual

  • 7/30/2019 REG 670 App.

    5/7

    Line to earth faults

    Double line to earth faults

    Line to line faults

    Open conductors, includes Broken line conductors

    Malfunction of one pole of a circuit breaker

    .

    When inverse time overcurrent characteristic is selected, the

    operate time of the stage will be the sum of the inverse time delayand the set definite time delay. Thus, if only the inverse time delay

    is required, it is of utmost importance to set the definite time delay

    for that stage to zero.

    Negative sequence time overcurrent protection for machines NS2PTOC provides

    two operating time delay characteristics for step 1:

    Definite time delay characteristic

    Inverse time delay characteristic

    The desired operate time delay characteristic is selected by setting CurveType1 as

    follows:

    CurveType1 = Definite

    CurveType1 = Inverse

    Step 2 always has a definite time delay characteristic. Definite time delay is

    independent of the magnitude of the negative sequence current once the start value

    is exceeded, while inverse time delay characteristic do depend on the magnitude of

    the negative sequence current.

    This means that inverse time delay is long for a small overcurrent and becomes

    progressively shorter as the magnitude of the negative sequence current increases.

    Inverse time delay characteristic of the NS2PTOC function is represented in the

    equation2

    2I t K= , where the K1 setting is adjustable over the range of1 99

    seconds. A typical inverse time overcurrent curve is shown in Figure 120.

    Section 3 1MRK 502 030-UEN AIED application

    302

    Application manual

  • 7/30/2019 REG 670 App.

    6/7

    Negative sequence inverse time characteristic

    Negative sequence current

    Timedelay

    I2

    tMax

    tMin

    IEC08000355-2-en.vsd

    1

    10

    100

    1000

    10000

    0.01 0.1 1 10 100

    IEC08000355 V2 EN

    Figure 120: Inverse Time Delay characteristic

    The example in figure 120 indicates that the protection function has a set minimum

    operating time t1Min of 5 sec. The setting t1Min is freely settable and is used as a

    security measure. This minimum setting assures appropriate coordination with forexample line protections. It is also possible to set the upper time limit, t1Max.

    The trip start levels Current I2-1> and I2-2> of NS2PTOC are freely settable over

    a range of 3 to 500 % of rated generator current IBase. The wide range of start

    setting is required in order to be able to protect generators of different types and sizes.

    After start, a certain hysteresis is used before resetting NS2PTOC. For both steps

    the reset ratio is 0.97.

    The alarm function is operated by START signal and used to warn the operator for

    an abnormal situation, for example, when generator continuous negative sequence

    current capability is exceeded, thereby allowing corrective action to be taken

    before removing the generator from service. A settable time delay tAlarm is

    provided for the alarm function to avoid false alarms during short-time unbalanced

    conditions.

    1MRK 502 030-UEN A Section 3IED application

    303

    Application manual

  • 7/30/2019 REG 670 App.

    7/7

    Operation Off

    On

    - - Off Operation Off / On

    IBase 1 - 99999 A 1 3000 Rated generator current in primary

    Amperes

    tAlarm 0.00 - 6000.00 s 0.01 3.00 Time delay for Alarm (operated by

    START signal), in sec

    OpStep1 Off

    On

    - - On Enable execution of step 1

    I2-1> 3 - 500 %IB 1 10 Step 1 Neg. Seq. Current pickup level, in

    % of IBase

    CurveType1 Definite

    Inverse

    - - Definite Selection of definite or inverse time-

    characteri. for step 1

    t1 0.00 - 6000.00 s 0.01 10.00 Definite time delay for trip of step 1, in sec

    tResetDef1 0.000 - 60.000 s 0.001 0.000 Time delay for reset of definite timer of

    step 1, in sec

    K1 1.0 - 99.0 s 0.1 10.0 Neg. seq. capability value of generator

    for step 1, in sec

    t1Min 0.000 - 60.000 s 0.001 5.000 Minimum trip time for inverse delay of

    step 1, in sec

    t1Max 0.00 - 6000.00 s 0.01 1000.00 Maximum trip delay for step 1, in sec

    ResetMultip1 0.01 - 20.00 - 0.01 1.00 Reset multiplier for K1, defines reset

    time of inverse curve

    OpStep2 Off

    On

    - - On Enable execution of step 2

    I2-2> 3 - 500 %IB 1 10 Step 2 Neg. Seq. Current pickup level, in

    % of IBase

    CurveType2 Definite

    Inverse

    - - Definite Selection of definite or inverse time-

    characteri. for step 2

    t2 0.00 - 6000.00 s 0.01 10.00 Definite time delay for trip of step 2, in sec

    tResetDef2 0.000 - 60.000 s 0.001 0.000 Time delay for reset of definite timer of

    step 2, in sec

    K2 1.0 - 99.0 s 0.1 10.0 Neg. seq. capability value of generator

    for step 2, in sec

    t2Min 0.000 - 60.000 s 0.001 5.000 Minimum trip time for inverse delay of

    step 2, in sec

    t2Max 0.00 - 6000.00 s 0.01 1000.00 Maximum trip delay for step 2, in sec

    ResetMultip2 0.01 - 20.00 - 0.01 1.00 Reset multiplier for K2, defines reset

    time of inverse curve

    Section 3 1MRK 502 030-UEN AIED application

    304

    Application manual