reg 670 app
TRANSCRIPT
-
7/30/2019 REG 670 App.
1/7
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
100% of Ir
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir
IBase 1 - 99999 A 1 3000 Base setting for current level
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level
Mode L1, L2, L3
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
- - Pos Seq Selection of measured current and
voltage
Negative sequence time overcurrent
protection for machines
NS2PTOC 2I2> 46I2
Negative sequence overcurrent protection for machines NS2PTOC is intended
primarily for the protection of generators against possible overheating of the rotor
caused by negative sequence component in the stator current.
The negative sequence currents in a generator may, among others, be caused by:
Section 3 1MRK 502 030-UEN AIED application
298
Application manual
-
7/30/2019 REG 670 App.
2/7
Unbalanced loads
Line to line faults
Line to ground faults
Broken conductors
Malfunction of one or more poles of a circuit breaker or a disconnector
NS2PTOC can also be used as a backup protection, that is, to protect the generator
in the event line protections or circuit breakers fail to perform for unbalanced
system faults.
To provide an effective protection for the generator for external unbalanced
conditions, NS2PTOC is able to directly measure the negative sequence current.
NS2PTOC also have a time delay characteristic which matches the heating
characteristic of the generator I22t = K as defined in standard.
where:
I2 is negative sequence current expressed in per unit of the rated generator current
t is operating time in seconds
K is a constant which depends of the generators size and design
A wide range of I22t settings is available, which provide the sensitivity and
capability necessary to detect and trip for negative sequence currents down to the
continuous capability of a generator.
A separate output is available as an alarm feature to warn the operator of apotentially dangerous situation.
Negative-sequence time overcurrent protection NS2PTOC is designed to provide a
reliable protection for generators of all types and sizes against the effect of
unbalanced system conditions.
The following features are available:
Two steps, independently adjustable, with separate tripping outputs.
Sensitive protection, capable of detecting and tripping for negative sequence
currents down to 3% of rated generator current with high accuracy. Two time delay characteristics for step 1:
Definite time delay
Inverse time delay
The inverse time overcurrent characteristic matches
22I t K= capability curve
of the generators.
Wide range of settings for generator capability constant Kis provided, from 1
to 99 seconds, as this constant may vary greatly with the type of generator.
1MRK 502 030-UEN A Section 3IED application
299
Application manual
-
7/30/2019 REG 670 App.
3/7
Minimum operate time delay for inverse time characteristic, freely settable.
This setting assures appropriate coordination with, for example, line protections.
Maximum operate time delay for inverse time characteristic, freely settable.
Inverse reset characteristic which approximates generator rotor cooling rates
and provides reduced operate time if an unbalance reoccurs before the
protection resets.
Service value that is, measured negative sequence current value, in primary
Amperes, is available through the local HMI.
During unbalanced loading, negative sequence current flows in the stator winding.
Negative sequence current in the stator winding will induce double frequency
current in the rotor surface and cause heating in almost all parts of the generator rotor.
When the negative sequence current increases beyond the generators continuous
unbalance current capability, the rotor temperature will increase. If the generator is
not tripped, a rotor failure may occur. Therefore, industry standards has been
established that determine generator continuous and short-time unbalanced current
capabilities in terms of negative sequence current I2 and rotor heating criteria2
2I t .
Typical short-time capability (referred to as unbalanced fault capability) expressed
in terms of rotor heating criterion2
2I t K= is shown below in Table 103.
[ ]2
2I t K s=
Salient pole generator 40
Synchronous condenser 30
Cylindrical rotor generators: Indirectly cooled 30
Directly cooled (0 800 MVA) 10
Directly cooled (801 1600
MVA)
See Figure 119
Fig 119 shows a graphical representation of the relationship between generator
22I t capability and generator MVA rating for directly cooled (conductor cooled)
generators. For example, a 500 MVA generator would have K = 10 seconds and a
1600 MVA generator would have K = 5 seconds. Unbalanced short-time negative
sequence current I2 is expressed in per unit of rated generator current and time t in
seconds.
Section 3 1MRK 502 030-UEN AIED application
300
Application manual
-
7/30/2019 REG 670 App.
4/7
en08000358.vsd
IEC08000358 V1 EN
Figure 119: Short-time unbalanced current capability of direct cooled generators
Continuous I2 - capability of generators is also covered by the standard. Table 104
below (from ANSI standard C50.13) contains the suggested capability:
Salient Pole
with damper winding 10
without damper winding 5
Cylindrical Rotor
Indirectly cooled 10
Directly cooled
to 960 MVA 8
961 to 1200 MVA 6
1201 to 1500 MVA 5
As it is described in the table above that the continuous negative sequence current
capability of the generator is in range of 5% to 10% of the rated generator current.
During an open conductor or open generator breaker pole condition, the negative
sequence current can be in the range of 10% to 30% of the rated generator current.
Other generator or system protections will not usually detect this condition and the
only protection is the negative sequence overcurrent protection.
Inducing of negative sequence current in a generator can result from any system
unbalance and these, in turn, may be caused by:
Unbalanced loads such as
Single phase railroad load
Unbalanced system faults such as
1MRK 502 030-UEN A Section 3IED application
301
Application manual
-
7/30/2019 REG 670 App.
5/7
Line to earth faults
Double line to earth faults
Line to line faults
Open conductors, includes Broken line conductors
Malfunction of one pole of a circuit breaker
.
When inverse time overcurrent characteristic is selected, the
operate time of the stage will be the sum of the inverse time delayand the set definite time delay. Thus, if only the inverse time delay
is required, it is of utmost importance to set the definite time delay
for that stage to zero.
Negative sequence time overcurrent protection for machines NS2PTOC provides
two operating time delay characteristics for step 1:
Definite time delay characteristic
Inverse time delay characteristic
The desired operate time delay characteristic is selected by setting CurveType1 as
follows:
CurveType1 = Definite
CurveType1 = Inverse
Step 2 always has a definite time delay characteristic. Definite time delay is
independent of the magnitude of the negative sequence current once the start value
is exceeded, while inverse time delay characteristic do depend on the magnitude of
the negative sequence current.
This means that inverse time delay is long for a small overcurrent and becomes
progressively shorter as the magnitude of the negative sequence current increases.
Inverse time delay characteristic of the NS2PTOC function is represented in the
equation2
2I t K= , where the K1 setting is adjustable over the range of1 99
seconds. A typical inverse time overcurrent curve is shown in Figure 120.
Section 3 1MRK 502 030-UEN AIED application
302
Application manual
-
7/30/2019 REG 670 App.
6/7
Negative sequence inverse time characteristic
Negative sequence current
Timedelay
I2
tMax
tMin
IEC08000355-2-en.vsd
1
10
100
1000
10000
0.01 0.1 1 10 100
IEC08000355 V2 EN
Figure 120: Inverse Time Delay characteristic
The example in figure 120 indicates that the protection function has a set minimum
operating time t1Min of 5 sec. The setting t1Min is freely settable and is used as a
security measure. This minimum setting assures appropriate coordination with forexample line protections. It is also possible to set the upper time limit, t1Max.
The trip start levels Current I2-1> and I2-2> of NS2PTOC are freely settable over
a range of 3 to 500 % of rated generator current IBase. The wide range of start
setting is required in order to be able to protect generators of different types and sizes.
After start, a certain hysteresis is used before resetting NS2PTOC. For both steps
the reset ratio is 0.97.
The alarm function is operated by START signal and used to warn the operator for
an abnormal situation, for example, when generator continuous negative sequence
current capability is exceeded, thereby allowing corrective action to be taken
before removing the generator from service. A settable time delay tAlarm is
provided for the alarm function to avoid false alarms during short-time unbalanced
conditions.
1MRK 502 030-UEN A Section 3IED application
303
Application manual
-
7/30/2019 REG 670 App.
7/7
Operation Off
On
- - Off Operation Off / On
IBase 1 - 99999 A 1 3000 Rated generator current in primary
Amperes
tAlarm 0.00 - 6000.00 s 0.01 3.00 Time delay for Alarm (operated by
START signal), in sec
OpStep1 Off
On
- - On Enable execution of step 1
I2-1> 3 - 500 %IB 1 10 Step 1 Neg. Seq. Current pickup level, in
% of IBase
CurveType1 Definite
Inverse
- - Definite Selection of definite or inverse time-
characteri. for step 1
t1 0.00 - 6000.00 s 0.01 10.00 Definite time delay for trip of step 1, in sec
tResetDef1 0.000 - 60.000 s 0.001 0.000 Time delay for reset of definite timer of
step 1, in sec
K1 1.0 - 99.0 s 0.1 10.0 Neg. seq. capability value of generator
for step 1, in sec
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum trip time for inverse delay of
step 1, in sec
t1Max 0.00 - 6000.00 s 0.01 1000.00 Maximum trip delay for step 1, in sec
ResetMultip1 0.01 - 20.00 - 0.01 1.00 Reset multiplier for K1, defines reset
time of inverse curve
OpStep2 Off
On
- - On Enable execution of step 2
I2-2> 3 - 500 %IB 1 10 Step 2 Neg. Seq. Current pickup level, in
% of IBase
CurveType2 Definite
Inverse
- - Definite Selection of definite or inverse time-
characteri. for step 2
t2 0.00 - 6000.00 s 0.01 10.00 Definite time delay for trip of step 2, in sec
tResetDef2 0.000 - 60.000 s 0.001 0.000 Time delay for reset of definite timer of
step 2, in sec
K2 1.0 - 99.0 s 0.1 10.0 Neg. seq. capability value of generator
for step 2, in sec
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum trip time for inverse delay of
step 2, in sec
t2Max 0.00 - 6000.00 s 0.01 1000.00 Maximum trip delay for step 2, in sec
ResetMultip2 0.01 - 20.00 - 0.01 1.00 Reset multiplier for K2, defines reset
time of inverse curve
Section 3 1MRK 502 030-UEN AIED application
304
Application manual