refrigerator charging unit

Upload: dipak-vinayak-shirbhate

Post on 30-May-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/14/2019 Refrigerator Charging Unit

    1/29

    RefrigeratorCharging Unit

    1. INTRODUCTION

    Refrigeration: refrigeration is defined as any process of heat

    removal. More specially, refrigeration is defined as the branch of science that

    deals with the process of reducing and maintaining the temperature of a space of

    material below the temperature of the surroundings.

    Multipurpose charging set is a single arrangement for charging the

    education and air conditioning unit. This charging set is different than the other

    method. This is a portable device which can be transferred from One place to

    another its construction is simple and decorative one. This set is multipurpose

    device; with charging the unit it can also achieve the vacuum in unit. The weight

    of gas and pressure of gas going to the unit is directly measured at the time of

    charging on this set so it is very useful device for charging the refrigeration and

    air condition unit in laboratories.

    N.P.T.N. Achalpur 1

  • 8/14/2019 Refrigerator Charging Unit

    2/29

    RefrigeratorCharging Unit

    2. PRINCIPLE OF PROJECT

    Evacuation : -

    Removing of fully air present in the refrigeration unit is known as

    evacuation.

    The main purpose of evacuation process is that for charging the

    refrigeration unit. The air should not be present in it. If evacuation is not carried

    out some amount of air is present in the refrigeration unit carried out properly.

    The leakage problems are rising in it.

    Definition of Charging: -

    Charging is the process of filling the gas in the refrigeration and air

    conditioning system.

    Principle of charging set: -

    This is a new method used for the charging of refrigeration unit

    differ than the other method.

    The principle of this charging set is that whenever a charging is

    carried out by this set how many amount of gas is supply to the refrigeration or

    air conditioning unit is calculated with the help of spring balance and also

    determine the pressure of the gas flowing through the charging line with the help

    of compound pressure gauge.

    N.P.T.N. Achalpur 2

  • 8/14/2019 Refrigerator Charging Unit

    3/29

    RefrigeratorCharging Unit

    3. PART LIST

    Sr. no. Part Quantity Material

    1 3 way valve 2 Bronze

    2 2 way valve 1 Bronze

    3 Charging line 3 Rubber

    4Compound

    pressure gauge

    1 -

    5 Spring balance 1 -6 Refrigerant gas 1 kg R-12

    N.P.T.N. Achalpur 3

  • 8/14/2019 Refrigerator Charging Unit

    4/29

    RefrigeratorCharging Unit

    4. REFRIGERANT

    The substance, which carries the heat from low temperature region

    and discharge, the same to the higher temperature region is known as refrigerant.

    Refrigerant removes the heat in the form of sensible heat as in case of air

    refrigeration or in the form of latent heat as in the case of vapour refrigeration.

    The refrigerants, which carry the heat in the form of latent heat and

    also dissipate in the form of latent heat, are more efficient than the refrigerant,

    which carry the heat in the form of sensible heat.

    N.P.T.N. Achalpur 4

  • 8/14/2019 Refrigerator Charging Unit

    5/29

    RefrigeratorCharging UnitREFREGERANT IN COMMON USE.

    1. Ammonia (NH3) :

    Ammonia is one of the oldest refrigerant uses in refrigeration

    system. Its excellence thermal property make it an idea refrigerant for ice plant,

    cold storage etc. Ammonia has the highest refrigerating effect per unit refrigerant

    capacity. It is much less expensive compare with any other refrigerant. Any

    moisture, which may enter the system, will be dissolved in ammonia and it

    attacks many foods, therefore it is not used for domestic refrigerant or where

    there is danger of exposing foods to leaking ammonia. It attack non-ferrous

    metal, brass and bronze, but it is non-corrosive to iron and steel. It is widely used

    in vapour absorption refrigerant system as it soluble in water and easily expelled

    when heated.

    2. Freon 12 or Discholorodifluro methane ( CCL2F2) :

    It is commercially term as F-12 or R-12. It is used for domestic

    refrigerator. It is colorless odorless and non-toxic. Therefore it is best suitable for

    domestic refrigerator. It is used with all types of condenser, air-cooled and water-

    cooled. The boiling point is 29.8

    0

    c at atmospheric pressure make it suitable for

    high, medium and low temperature application with any types of compressor. It

    is soluble in oil; therefore, it is simplifies the problem of lubrication. But its

    N.P.T.N. Achalpur 5

  • 8/14/2019 Refrigerator Charging Unit

    6/29

    RefrigeratorCharging Unitdisadvantage is that it is costly and leak cannot be detected easily. Its leak

    detected with the halides torch.

    3. Freon -22 Difluromonochloro Methane (CHCIF2) :

    It has a boiling Point -40"C at atmospheric pressure. It is used for

    low temperature production. It is also used in packaged air conditioners, where,

    because of space limitations, Relatively small compressor displacement required

    with R-22 water-cooled Condensers are used. When air-cooled condenser is used

    with R-22 is not used. The main advantage of R-22 over R-12 is the smaller

    compressor displacement required for same capacity.

    4. Carbon dioxide (CO2) :

    It is the oldest refrigerant used. Carbon dioxide is Odorless, non-

    toxic, non-flammable, non-explosive and non-corrosive Refrigerant. It used in

    hospitals, theaters, hotels and marine service where safety Is prime

    consideration? Now days its use is limited for production of dry ice. But the

    power required for 002 refrigerants is high.

    5. Sulphur dioxide (S02):

    In olden days it was used in domestic Refrigerator. It is now replaced

    by freon-12. It is colorless and suffocating fluid. In presence of water it forms

    sulphurous acid, it has low refrigerating effect Compared with other refrigerant and it is

    heavy irritating and high toxic in nature.

    N.P.T.N. Achalpur 6

  • 8/14/2019 Refrigerator Charging Unit

    7/29

    RefrigeratorCharging UnitPROPERTY OF IDEAL REFREGERANT

    Therefore, ideal refrigerant should have following properties

    (i) The boiling point should be low.

    (ii) The condensing pressure should not be more.

    (iii) Critical temperature should be high.

    (iv) The latent heat of vaporization should be high.

    (v) Specific heat of liquid should be low.

    (vi) It should not have corrosive action.

    (vii) It should not be flammable and explosive.

    (viii) It should be non-toxic.

    (ix) It should be easily detectable for leaks.

    (x) It should have satisfactory heat transfer coefficient.

    : Should be easily available at low cost.

    N.P.T.N. Achalpur 7

  • 8/14/2019 Refrigerator Charging Unit

    8/29

    RefrigeratorCharging Unit

    5. CONSTRUCTION

    This is a simple arrangement for charging the refrigeration and air

    conditioning unit. The main feature of this charging set is that the whole assembly is

    carried on a rectangular base. This is portable device, which can be transferred from

    one place to another its construction is simple land decorative one. A vacuum pump is

    fitted on the base plate. In front vacuum pump a vertical rectangular angle set is

    attached on which spring balanced is attached and the plywood and valve are attached

    with the help of nut-bolt.

    A vacuum pump is mounted for creating the vacuum in the unit.

    An arrangement of spring balance is to be made for calculating how many

    amount of gas is filled in unit. For calculating the amounting of the gas

    N.P.T.N. Achalpur 8

  • 8/14/2019 Refrigerator Charging Unit

    9/29

    RefrigeratorCharging Unit

    N.P.T.N. Achalpur 9

  • 8/14/2019 Refrigerator Charging Unit

    10/29

    RefrigeratorCharging UnitRefrigerant the refrigerant cylinder is attached tom hook of spring balance with

    the help of into cylinder hanger arrangement.

    On the front side of this charging set a panel board is fixed for

    mounting 2 three way valves and compound pressure gauge. Three charging

    lines are required for this set. One charging line is joined between the vacuum to

    connector disconnect the vacuum pump. The second charging line is connected

    between the cylinder and valve V1 and end of valve V2, which is always open.

    The third charging line is connected between the refrigeration unit

    and common end of valve V2 for the purpose of connect or disconnect the unit

    whenever required. One end of valve V2 is connected to the compound pressure

    gauge with the help of flare nut. These two 3-way valve V1 and V2 are

    connected with the help of copper tube and flare nut.

    So this is a simple arrangement of charging set.

    N.P.T.N. Achalpur 10

  • 8/14/2019 Refrigerator Charging Unit

    11/29

    RefrigeratorCharging Unit

    6. WORKING

    After assembling it is required to charge the system with refrigerant

    gas. Many time charging is necessary after repair and maintenance of the

    system.

    Before charging the system evacuation of system is done. With the

    help of vacuum pump air in the system is removed and vacuum is achieved. For

    this purpose the vacuum pump is joined to the common end of valve V1 and

    connection between cylinder and valve is turned off from cylinder it self. Then

    turn the valve V2 on for the purpose of removing oxygen and nitrogen from the

    unit. The vacuum created in the system should be below 300 mm of Hg.

    N.P.T.N. Achalpur 11

  • 8/14/2019 Refrigerator Charging Unit

    12/29

    RefrigeratorCharging Unit

    N.P.T.N. Achalpur 12

  • 8/14/2019 Refrigerator Charging Unit

    13/29

    RefrigeratorCharging Unit

    After vaccumisation of the system, the vacuum pump is disconnect

    immediately with the help of valve V1 by turning it at off position. In this way at

    the vacuum side connection is off and remaining two connections is on state.

    The hand shut-off valve is used during change of line.

    Before charging the system, calculate the amount of gas required

    for the system. Then place the refrigerate cylinder with the help of cylinder

    hanger arrangement on the spring balance to refrigerant into evacuated system to

    exact quantity required. The purging should be done before admitting the gas

    into system.

    What amount of pressure present in the system is indicated by

    compound pressure gauge. The amount of pressure is required inside the system

    is controlled by valve V2.

    After completing the process, pinch the process tubes and seal it.

    N.P.T.N. Achalpur 13

  • 8/14/2019 Refrigerator Charging Unit

    14/29

    RefrigeratorCharging Unit

    7. ADVANTAGES AND APPLICATION

    Advantages: -

    The weight of gas and pressure of gas going to the unit is directly

    measured at the time of charging.

    It is multipurpose device.

    The connection of vacuum pump to the unit is directly connected with the

    help of valve and charging line. So separate arrangement is not required

    for achieving the vacuum in unit.

    Simple in construction.

    It is portable device, which can be transferred from one place to another.

    Less maintenance.

    Time is saved due to whole accessories are mounted on one table.

    The initial and working cost is less.

    Application: -

    In refrigeration and air-conditioning industries.

    In refrigeration shops and laboratories.

    It is used for charging of ice plant domestic refrigerator etc.

    N.P.T.N. Achalpur 14

  • 8/14/2019 Refrigerator Charging Unit

    15/29

    RefrigeratorCharging Unit

    8. HINTS BEFORE CHARGING

    Use clean & moisture free drums for transfer & charging purpose.

    The system should be evacuated particularly when it is new.

    The charging lines must be purged & it must be made sure that all

    connections are tight air is not drawn in the system with the

    refrigerant.

    The suction pressure may not be allowed to rise above 2 Kg.sq.cm.

    when charging. The pressure may be controlled with the cylinder

    valve.

    The refrigerant in the liquid from should under no circumstances to

    the compressor.

    The charging lines should not be flexible.

    The head pressure must be watched for indications of over charge.

    N.P.T.N. Achalpur 15

  • 8/14/2019 Refrigerator Charging Unit

    16/29

    RefrigeratorCharging Unit

    9. TESTING OF CHARGING SET

    (LEAK DETECTION)

    Before charging the refrigeration unit, the whole system must be

    tested for the purpose of arising leakage problem. If it is not done, the leakage

    problem is created & the charging is not done properly i.e. evacuation is not done

    properly.

    For this test a high-pressure compressed air is drawn through a

    charging set. Before entry of the high-pressure compressed air, a soap bubble are

    placed on v/v port, connection of charging lines & copper tubes & compound

    pressure gauge for the purpose of to detect the leakage. Then a compressed air is

    pass through the system if leakage is find, tight the connection with Teflon tape

    properly. This process is carried out up to the leakage problem is minimized.

    Then the system is ready form charging.

    Method Commonly Used For Leak Detection are: -

    1) Bubble Method

    2) Halide Torch Method

    3) Electronic Leak Detector

    4) Special Method for detection of Ammonia and Sulphur dioxide.

    N.P.T.N. Achalpur 16

  • 8/14/2019 Refrigerator Charging Unit

    17/29

    RefrigeratorCharging Unit1) Bubble Method: -

    This method of leak detection is the oldest one and is Universally

    used with all the refrigerants. A solution of soap or some other leather forming

    liquid detergent is applied with the brush over the subjected area or joint. The

    leaking gas forms bubble, which can be easily been seen. This method of leak

    detection can only be used when the system has positive pressure. If there is

    vacuum present in the system, it will pull in the moisture or stop bubble, which

    will be quite harmful.

    2) Halide Torch Method: -

    A carbon element is heated by methyl alcohol or hydrocarbon

    flame in the halide torch. A rubber tube attached to the refrigerator. A

    refrigerant going on the tube combines with the Flame to cause Perceptible

    change in the Flame Color.

    This method of leak detection is slow and insensitive and in

    brightly lighted area it is almost impossible to locate small leaks.

    3) Electronic Leak Detector: -

    An electronic leak detector is more sensitive and faster responding.

    The electronic detector contains an internal pump, which draws,

    and air leaking gas through a probe and hose as the probe is passed over leaking

    N.P.T.N. Achalpur 17

  • 8/14/2019 Refrigerator Charging Unit

    18/29

    RefrigeratorCharging Unit joints. A leak-detecting lamp Flashes at this moment. By adjusting a knob on

    the Electronic detector the magnitude of the leak can also be found.

    4) Special Method For detection of Ammonia and Sulphur dioxide: -

    Ammonia leak can be detected by bringing a burning candle of

    sulphur near the suspected spot. The candle will give a cloud of white smoke if

    ammonia vapour is present there A solution of hydrochloric acid brought in the

    Vicinity of ammonia leak will also give white smoke. The moistened strip of

    Phenol Phalein Paper turns Pink when faintest trace of ammonia vapour comes in

    contact with it.

    Presence of sulphur dioxide can be detected by bringing aqueous

    ammonia near the suspected area. It will give white smoke in the presence of

    Sulphur dioxide. When no ammonia is available leak may located by the soap

    bubble or oil test.

    N.P.T.N. Achalpur 18

  • 8/14/2019 Refrigerator Charging Unit

    19/29

    RefrigeratorCharging Unit

    10. METHODS OF CHARGING

    By using this set the methods of charging are as follows:

    There are three methods of charging as given below:

    1. Charging thought the suction valve: -

    A small installation, which needs to few kilograms of refrigerant, is

    usually charged through the suction service valve gauge port. For this method of

    charging the system is fully evacuated and charged a follows.

    Charging line is connected to the suction valve gauge port. Attach a

    gauge to the discharge valve and open half turn.

    The other end of the charging lines us connected to a refrigerant cylinder,

    which should be standing up right.

    The cylinder valve is opened slightly and to flare nut is loosened at the

    compressor end.

    N.P.T.N. Achalpur 19

  • 8/14/2019 Refrigerator Charging Unit

    20/29

    RefrigeratorCharging Unit

    N.P.T.N. Achalpur 20

  • 8/14/2019 Refrigerator Charging Unit

    21/29

    RefrigeratorCharging Unit This operation removes air from the line, when the sound of escaping gas

    is heard, the nut is tightened.

    Suction valve is turned into close the suction line, thus drawing the gas

    directly from the cylinder by the compressor.

    Compressor is started drawing the requisite quantity of refrigerant. The

    suction pressure should not be allowed to exceed 2 kg/sq.cm. Gauge.

    The cylinder valve is closed and the compressor is allowed to run

    sufficient time to reduce the pressure in charging time to 0 kg/sq.cm.

    Gauge.

    Compressor is stopped and the suction valve is back seated. The charging

    line is detached and compound gauge attached. The valve is turned in one

    half turn. The system is thus ready for testing and normal operation.

    The refrigerant quantity to be charge is often weighted. In that case

    the cylinder may be on the weighing platform, or suspended from spring scale.

    The tubing should be coiled and long enough to get true weight. The cylinder

    may be kept in warm water to quacked the process of charging.

    2. Charging through discharge valve: -

    The method is used for certain conditions where it is impossible or impracticable

    to add refrigerant by the other methods. This is the least used to the three

    N.P.T.N. Achalpur 21

  • 8/14/2019 Refrigerator Charging Unit

    22/29

    RefrigeratorCharging Unitmethods. The refrigerant is caused to flow by difference in pressure between

    cylinder and high side. The compressor is not operated while the unit is being

    N.P.T.N. Achalpur 22

  • 8/14/2019 Refrigerator Charging Unit

    23/29

    RefrigeratorCharging UnitCharged. In order to save time when charging by this method, it is imperative to

    weight into an empty cylinder the exact amount of charge required by the system.

    If this is known, all contents of cylinder transferred. The system is evacuated

    and following procedure adopted.

    The discharge and suction service value are back-seated. The gauge port

    of each valve is plugged or otherwise kept closed until the valves are wide

    open.

    Compound gauge is attached to the suction valve and the valve is turned

    in one-half turn. A pipe-to-flare adapter is installed to the discharge valve

    port and the charging line is connected to the adapter.

    The other end of the charging line is connected to the cylinder. The air is

    removed from line by loosing flare nut. The nut is tightened. The valve A

    is turned in about half way.

    The cylinder is placed bottom side up since the refrigerant will flow into

    the condenser in liquid form.

    After the refrigerant has flowed into the condenser, the discharge valve is

    back-seated cylinder valve is closed and the charging line is removed.

    The pressure gauge is attached and the valve is ready for testing and

    operation.

    N.P.T.N. Achalpur 23

  • 8/14/2019 Refrigerator Charging Unit

    24/29

  • 8/14/2019 Refrigerator Charging Unit

    25/29

    RefrigeratorCharging Unit

    N.P.T.N. Achalpur 25

  • 8/14/2019 Refrigerator Charging Unit

    26/29

    RefrigeratorCharging Unit

    The cylinder valve is opened slightly and the flare nut is loosened

    at the charging valve to purge the air from the line. When the

    sound of escaping gas is he hard the nut is lightened.

    The cylinder is tipped to ensure liquid at the valve and then

    charging and cylinder valves are opened wide.

    Compressor is started and the system is charged with required

    quinsy. When cylinder becomes empty, frost will form on the

    bottom of the cylinder and the charging line.

    After completing the charging close the cylinder valve and run the

    compressor for sometime to empty the charging line. Then close

    the charging valve C, and remove the line. The charging valve is

    capped to prevent leakage.

    The receiver valve R is opened, the system is ready for testing and

    operation.

    When charging refrigerant into an ammonia plant using the above

    method. It is necessary to lay the cylinders have an internal

    gooseneck which makes this necessary. Charging connections for

    ammonia should be made rigid steel pipe and fittings. For other

    refrigerants use copper tubing Flexible connections, in the authors

    opinion are dangerous.

    N.P.T.N. Achalpur 26

  • 8/14/2019 Refrigerator Charging Unit

    27/29

    RefrigeratorCharging Unit

    11. CONCLUSION AND MODIFICATION

    Conclusion: -

    In the end we concluded that by using this instrument we could

    evacuate and charge the refrigeration and air conditioning system

    simultaneously. This means that we can save a time by connecting and

    disconnecting of the charging line. It is used in the charging of refrigeration and

    air conditioning system in an industries, laboratories etc.

    Modification: -

    1. It is possible to weight a refrigerant, which is supplied to the system.

    2. From the system we can evacuate and charged the refrigeration and air

    conditioning system fastly.

    N.P.T.N. Achalpur 27

  • 8/14/2019 Refrigerator Charging Unit

    28/29

    RefrigeratorCharging Unit

    12. COST ANALYSIS

    Sr. no. Name of material Material Quantity Cost

    1. 3- way valve Bronze 2 360

    2. 2-way valve Bronze 1 180

    3. Copper tube with flare nut Copper 2 80

    4. Compound pressure gauge with

    adaptor

    -- 1 205

    5. Charging line Rubber 3 380

    6. Cylinder with gas R-12 1 kg 690

    7 Angle C.I. 12 kg 210

    8 Vacuum pump -- 1 no. 22009. Spring balance -- 1 no 90

    10. Plywood Plywood 10 sq. ft. 100

    11. Screw C.I. 34 nos. 15

    12 Roller Rubber 4 nos. 80

    13. Welding -- -- 200

    14. Color -- -- 120

    15 Other -- -- 725

    Total Rs.

    5635

    BIBLIOGRAPHY

    1. Refrigeration and air conditioning

    S.C Arora , S. Domculwar

    2. Refrigeration and air conditioning system.

    S.L. Gavhale

    3. Refrigeration and air conditioning system.

    S.T. Ghan, R.M. Naphade.

    N.P.T.N. Achalpur 28

  • 8/14/2019 Refrigerator Charging Unit

    29/29

    RefrigeratorCharging Unit