refrigeration and air conditioning

50
1 Training Session on Energy Training Session on Energy Equipment Equipment Refrigeration & Refrigeration & Air Conditioning Air Conditioning Presentation from the “Energy Efficiency Guide for Industry in Asia” www.energyefficiencyasia.org © UNEP 2006 UNEP 2006 E l e c t r i c a l E q u i p m e n t / R e f r i g e r a t i o n & A C

Upload: vicky123465

Post on 20-Jan-2015

2.446 views

Category:

Business


3 download

DESCRIPTION

 

TRANSCRIPT

Page 1: Refrigeration and air conditioning

1

Training Session on Energy Training Session on Energy EquipmentEquipment

Refrigeration & Air Refrigeration & Air ConditioningConditioning

Presentation from the

“Energy Efficiency Guide for Industry in Asia”

www.energyefficiencyasia.org

©© UNEP 2006 UNEP 2006

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 2: Refrigeration and air conditioning

2

©© UNEP 2006 UNEP 2006

Training Agenda: Refrigeration & Training Agenda: Refrigeration & Air ConditioningAir Conditioning

Introduction

Type of refrigeration

Assessment of refrigeration and AC

Energy efficiency opportunities

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 3: Refrigeration and air conditioning

3

©© UNEP 2006 UNEP 2006

IntroductionIntroduction

How does it work?

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

High Temperature Reservoir

Low Temperature Reservoir

R Work Input

Heat Absorbed

Heat Rejected

Page 4: Refrigeration and air conditioning

4

©© UNEP 2006 UNEP 2006

IntroductionIntroduction

Thermal energy moves from left to right through five loops of heat transfer:

How does it work?El ect ri cal E

quipment /

Ref ri gerat ion &

AC

(Bureau of Energy Efficiency, 2004)

1)

Indoor air loop

2)

Chilled water loop

3)

Refrigerant loop

4)

Condenser water loop

5)

Cooling water loop

Page 5: Refrigeration and air conditioning

5

©© UNEP 2006 UNEP 2006

IntroductionIntroduction

AC options / combinations:

AC SystemsEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

• Air Conditioning (for comfort / machine)

• Split air conditioners

• Fan coil units in a larger system

• Air handling units in a larger system

Page 6: Refrigeration and air conditioning

6

©© UNEP 2006 UNEP 2006

IntroductionIntroduction

• Small capacity modular units of direct expansion type (50 Tons of Refrigeration)

• Centralized chilled water plants with chilled water as a secondary coolant (50 – 250 TR)

• Brine plants with brines as lower temperature, secondary coolant (>250 TR)

Refrigeration systems for industrial processes

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 7: Refrigeration and air conditioning

7

©© UNEP 2006 UNEP 2006

IntroductionIntroduction

• Bank of units off-site with common

• Chilled water pumps

• Condenser water pumps

• Cooling towers

• More levels of refrigeration/AC, e.g.

• Comfort air conditioning (20-25 oC)

• Chilled water system (8 – 10 oC)

• Brine system (< 0 oC)

Refrigeration at large companiesEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 8: Refrigeration and air conditioning

8

©© UNEP 2006 UNEP 2006

Training Agenda: Refrigeration & Training Agenda: Refrigeration & Air ConditioningAir Conditioning

Introduction

Type of refrigeration

Assessment of refrigeration and AC

Energy efficiency opportunities

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 9: Refrigeration and air conditioning

9

©© UNEP 2006 UNEP 2006

Types of RefrigerationTypes of Refrigeration

• Vapour Compression Refrigeration (VCR): uses mechanical energy

• Vapour Absorption Refrigeration (VAR): uses thermal energy

Refrigeration systemsEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 10: Refrigeration and air conditioning

10

©© UNEP 2006 UNEP 2006

Type of RefrigerationType of Refrigeration

Vapour Compression RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

• Highly compressed fluids tend to get colder when allowed to expand

• If pressure high enough

• Compressed air hotter than source of cooling

• Expanded gas cooler than desired cold temperature

Page 11: Refrigeration and air conditioning

11

©© UNEP 2006 UNEP 2006

Type of RefrigerationType of Refrigeration

Vapour Compression RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Two advantages

• Lot of heat can be removed (lot of thermal energy to change liquid to vapour)

• Heat transfer rate remains high (temperature of working fluid much lower than what is being cooled)

Page 12: Refrigeration and air conditioning

12

Type of RefrigerationType of Refrigeration

Vapour Compression RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

©© UNEP 2006 UNEP 2006

Refrigeration cycle

Condenser

Evaporator

High Pressure

Side

Low Pressure

Side

CompressorExpansion Device

1 2

3

4

Page 13: Refrigeration and air conditioning

13

Type of RefrigerationType of Refrigeration

Vapour Compression RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

©© UNEP 2006 UNEP 2006

Refrigeration cycle

Low pressure liquid refrigerant in evaporator absorbs heat and changes to a gas

Condenser

Evaporator

High Pressure

Side

Low Pressure

Side

CompressorExpansion Device

1 2

3

4

Page 14: Refrigeration and air conditioning

14

Type of RefrigerationType of Refrigeration

Vapour Compression RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

©© UNEP 2006 UNEP 2006

Refrigeration cycle

The superheated vapour enters the compressor where its pressure is raised

Condenser

Evaporator

High Pressure

Side

Low Pressure

Side

CompressorExpansion Device

1 2

3

4

Page 15: Refrigeration and air conditioning

15

Type of RefrigerationType of Refrigeration

Vapour Compression RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

©© UNEP 2006 UNEP 2006

Refrigeration cycle

The high pressure superheated gas is cooled in several stages in the condenser

Condenser

Evaporator

High Pressure

Side

Low Pressure

Side

CompressorExpansion Device

1 2

3

4

Page 16: Refrigeration and air conditioning

16

Type of RefrigerationType of Refrigeration

Vapour Compression RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

©© UNEP 2006 UNEP 2006

Refrigeration cycle

Liquid passes through expansion device, which reduces its pressure and controls the flow into the evaporator

Condenser

Evaporator

High Pressure

Side

Low Pressure

Side

CompressorExpansion Device

1 2

3

4

Page 17: Refrigeration and air conditioning

17

©© UNEP 2006 UNEP 2006

Type of RefrigerationType of Refrigeration

Vapour Compression RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Type of refrigerant

• Refrigerant determined by the required cooling temperature

• Chlorinated fluorocarbons (CFCs) or freons: R-11, R-12, R-21, R-22 and R-502

Page 18: Refrigeration and air conditioning

18

©© UNEP 2006 UNEP 2006

Type of RefrigerationType of Refrigeration

Vapour Compression RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Choice of compressor, design of condenser, evaporator determined by

• Refrigerant

• Required cooling

• Load

• Ease of maintenance

• Physical space requirements

• Availability of utilities (water, power)

Page 19: Refrigeration and air conditioning

19

©© UNEP 2006 UNEP 2006

Type of RefrigerationType of Refrigeration

Vapour Absorption RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Condenser Generator

Evaporator

AbsorberCold Side

Hot Side

Page 20: Refrigeration and air conditioning

20

©© UNEP 2006 UNEP 2006

Type of RefrigerationType of Refrigeration

Vapour Absorption RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Evaporator

Page 21: Refrigeration and air conditioning

21

©© UNEP 2006 UNEP 2006

Type of RefrigerationType of Refrigeration

Vapour Absorption RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Absorber

Page 22: Refrigeration and air conditioning

22

©© UNEP 2006 UNEP 2006

Type of RefrigerationType of Refrigeration

Vapour Absorption RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

High pressure generator

Page 23: Refrigeration and air conditioning

23

©© UNEP 2006 UNEP 2006

Type of RefrigerationType of Refrigeration

Vapour Absorption RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Condenser

Page 24: Refrigeration and air conditioning

24

©© UNEP 2006 UNEP 2006

Type of RefrigerationType of Refrigeration

Evaporative CoolingEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

(Adapted from Munters, 2001)

Cold Air

Hot Air

Sprinkling Water

• Air in contact with water to cool it close to ‘wet bulb temperature’

• Advantage: efficient cooling at low cost

• Disadvantage: air is rich in moisture

Page 25: Refrigeration and air conditioning

25

©© UNEP 2006 UNEP 2006

Training Agenda: Refrigeration & Training Agenda: Refrigeration & Air ConditioningAir Conditioning

Introduction

Type of refrigeration

Assessment of refrigeration and AC

Energy efficiency opportunities

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 26: Refrigeration and air conditioning

26

Assessment of Refrigeration and ACAssessment of Refrigeration and AC

• Cooling effect: Tons of Refrigeration

• TR is assessed as:

Assessment of RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

1 TR = 3024 kCal/hr heat rejected

TR = Q xCp x (Ti – To) / 3024

Q = mass flow rate of coolant in kg/hr Cp = is coolant specific heat in kCal /kg deg C Ti = inlet, temperature of coolant to evaporator (chiller) in 0C To = outlet temperature of coolant from evaporator (chiller) in 0C

©© UNEP 2006 UNEP 2006

Page 27: Refrigeration and air conditioning

27

©© UNEP 2006 UNEP 2006

Specific Power Consumption (kW/TR)

• Indicator of refrigeration system’s performance

• kW/TR of centralized chilled water system is sum of• Compressor kW/TR

• Chilled water pump kW/TR

• Condenser water pump kW/TR

• Cooling tower fan kW/TR

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Assessment of Refrigeration and ACAssessment of Refrigeration and AC

Assessment of Refrigeration

Page 28: Refrigeration and air conditioning

28

©© UNEP 2006 UNEP 2006

Coefficient of Performance (COPCarnot)

• Standard measure of refrigeration efficiency

• Depends on evaporator temperature Te and condensing temperature Tc:

• COP in industry calculated for type of compressor:

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

COPCarnot = Te / (Tc - Te)

Cooling effect (kW)COP =

Power input to compressor (kW)

Assessment of Refrigeration and ACAssessment of Refrigeration and AC

Assessment of Refrigeration

Page 29: Refrigeration and air conditioning

29

©© UNEP 2006 UNEP 2006

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

COP increases with rising evaporator temperature

(Te)

COP increases with decreasing condensing

temperature (Tc)

Assessment of Refrigeration and ACAssessment of Refrigeration and AC

Assessment of Refrigeration

Page 30: Refrigeration and air conditioning

30

©© UNEP 2006 UNEP 2006

Measure

• Airflow Q (m3/s) at Fan Coil Units (FCU) or Air Handling Units (AHU): anemometer

• Air density (kg/m3)

• Dry bulb and wet bulb temperature: psychrometer

• Enthalpy (kCal/kg) of inlet air (hin) and outlet air (Hout): psychrometric charts

Calculate TR

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

3024

h h ρ Q TR outin

Assessment of Refrigeration and ACAssessment of Refrigeration and AC

Assessment of Air Conditioning

Page 31: Refrigeration and air conditioning

31

©© UNEP 2006 UNEP 2006

Indicative TR load profile

• Small office cabins : 0.1 TR/m2

• Medium size office (10 – 30 people occupancy) with central A/C: 0.06 TR/m2

• Large multistoried office complexes with central A/C: 0.04 TR/m2

Assessment of Air ConditioningEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Assessment of Refrigeration and ACAssessment of Refrigeration and AC

Page 32: Refrigeration and air conditioning

32

©© UNEP 2006 UNEP 2006

• Accuracy of measurements

• Inlet/outlet temp of chilled and condenser water

• Flow of chilled and condenser water

• Integrated Part Load Value (IPLV)

• kW/TR for 100% load but most equipment operate between 50-75% of full load

• IPLV calculates kW/TR with partial loads

• Four points in cycle: 100%, 75%, 50%, 25%

Considerations for AssessmentEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Assessment of Refrigeration and ACAssessment of Refrigeration and AC

Page 33: Refrigeration and air conditioning

33

©© UNEP 2006 UNEP 2006

Training Agenda: Refrigeration & Training Agenda: Refrigeration & Air ConditioningAir Conditioning

Introduction

Type of refrigeration

Assessment of refrigeration and AC

Energy efficiency opportunities

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 34: Refrigeration and air conditioning

34

©© UNEP 2006 UNEP 2006

1. Optimize process heat exchange

2. Maintain heat exchanger surfaces

3. Multi-staging systems

4. Matching capacity to system load

5. Capacity control of compressors

6. Multi-level refrigeration for plant needs

7. Chilled water storage

8. System design features

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

Page 35: Refrigeration and air conditioning

35

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

High compressor safety margins: energy loss

1. Proper sizing heat transfer areas of heat exchangers and evaporators

•Heat transfer coefficient on refrigerant side: 1400 – 2800 Watt/m2K

•Heat transfer area refrigerant side: >0.5 m2/TR

2. Optimum driving force (difference Te and Tc): 1oC raise in Te = 3% power savings

1. Optimize Process Heat Exchange

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 36: Refrigeration and air conditioning

36

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Evaporator Temperature (0C)

Refrigeration Capacity*(tons)

Specific Power Consumption (kW/TR)

Increase kW/TR (%)

5.0 67.58 0.81 -

0.0 56.07 0.94 16.0

-5.0 45.98 1.08 33.0

-10.0 37.20 1.25 54.0

-20.0 23.12 1.67 106.0

(National Productivity Council)Condenser temperature 40◦C

1. Optimize Process Heat Exchange

Condensing Temperature (0C)

Refrigeration Capacity (tons)

Specific Power Consumption (kW /TR)

Increase kW/TR (%)

26.7 31.5 1.17 -

35.0 21.4 1.27 8.5

40.0 20.0 1.41 20.5

*Reciprocating compressor using R-22 refrigerant. Evaporator temperature.-10◦ C

Page 37: Refrigeration and air conditioning

37

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

3. Selection of condensers

• Options: • Air cooled condensers

• Air-cooled with water spray condensers

• Shell & tube condensers with water-cooling

• Water-cooled shell & tube condenser• Lower discharge pressure

• Higher TR

• Lower power consumption

1. Optimize Process Heat Exchange

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 38: Refrigeration and air conditioning

38

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

• Poor maintenance = increased power consumption

• Maintain condensers and evaporators• Separation of lubricating oil and refrigerant

• Timely defrosting of coils

• Increased velocity of secondary coolant

• Maintain cooling towers• 0.55◦C reduction in returning water from cooling

tower = 3.0 % reduced power

2. Maintain Heat Exchanger Surfaces

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 39: Refrigeration and air conditioning

39

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

Effect of poor maintenance on compressor power consumption

2. Maintain Heat Exchanger SurfacesEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

(National Productivity Council)

ConditionTe (0C)

Tc (0C)

Refrigeration Capacity* (TR)

Specific Power

Consumption (kW/TR)

Increase kW/TR

(%)

Normal 7.2 40.5 17.0 0.69 -

Dirty condenser 7.2 46.1 15.6 0.84 20.4

Dirty evaporator 1.7 40.5 13.8 0.82 18.3

Dirty condenser and evaporator

1.7 46.1 12.7 0.96 38.7

Page 40: Refrigeration and air conditioning

40

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

• Suited for

• Low temp applications with high compression

• Wide temperature range

• Two types for all compressor types

• Compound

• Cascade

3. Multi-Staging SystemsEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 41: Refrigeration and air conditioning

41

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

a. Compound

• Two low compression ratios = 1 high

• First stage compressor meets cooling load

• Second stage compressor meets load evaporator and flash gas

• Single refrigerant

b. Cascade

• Preferred for -46 oC to -101oC

• Two systems with different refrigerants

3. Multi-Stage SystemsEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 42: Refrigeration and air conditioning

42

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

• Most applications have varying loads

• Consequence of part-load operation • COP increases

• but lower efficiency

• Match refrigeration capacity to load requires knowledge of• Compressor performance

• Variations in ambient conditions

• Cooling load

4. Matching Capacity to Load SystemEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 43: Refrigeration and air conditioning

43

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

5. Capacity Control of CompressorsEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

• Cylinder unloading, vanes, valves• Reciprocating compressors: step-by-step

through cylinder unloading:

• Centrifugal compressors: continuous modulation through vane control

• Screw compressors: sliding valves

• Speed control• Reciprocating compressors: ensure

lubrication system is not affected

• Centrifugal compressors: >50% of capacity

Page 44: Refrigeration and air conditioning

44

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

5. Capacity Control of CompressorsEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

• Temperature monitoring• Reciprocating compressors: return water (if

varying loads), water leaving chiller (constant loads)

• Centrifugal compressors: outgoing water temperature

• Screw compressors: outgoing water temperature

• Part load applications: screw compressors more efficient

Page 45: Refrigeration and air conditioning

45

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

Bank of compressors at central plant

• Monitor cooling and chiller load: 1 chiller full load more efficient than 2 chillers at part-load

• Distribution system: individual chillers feed all branch lines; Isolation valves; Valves to isolate sections

• Load individual compressors to full capacity before operating second compressor

• Provide smaller capacity chiller to meet peak demands

6. Multi-Level RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 46: Refrigeration and air conditioning

46

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

Packaged units (instead of central plant)

• Diverse applications with wide temp range and long distance

• Benefits: economical, flexible and reliable

• Disadvantage: central plants use less power

Flow control

• Reduced flow

• Operation at normal flow with shut-off periods

6. Multi-Level RefrigerationEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 47: Refrigeration and air conditioning

47

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

• Chilled water storage facility with insulation

• Suited only if temp variations are acceptable

• Economical because• Chillers operate during low peak demand

hours: reduced peak demand charges

• Chillers operate at nighttime: reduced tariffs and improved COP

7. Chilled Water StorageEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 48: Refrigeration and air conditioning

48

©© UNEP 2006 UNEP 2006

Energy Efficiency OpportunitiesEnergy Efficiency Opportunities

• FRP impellers, film fills, PVC drift eliminators

• Softened water for condensers

• Economic insulation thickness

• Roof coatings and false ceilings

• Energy efficient heat recovery devices

• Variable air volume systems

• Sun film application for heat reflection

• Optimizing lighting loads

8. System Design FeaturesEl ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 49: Refrigeration and air conditioning

49

Training Session on Energy Training Session on Energy EquipmentEquipment

Refrigeration & Air Refrigeration & Air Conditioning SystemsConditioning Systems

THANK YOUTHANK YOU

FOR YOUR ATTENTIONFOR YOUR ATTENTION

©© UNEP 2006 UNEP 2006

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

Page 50: Refrigeration and air conditioning

50

© UNEP 2006© UNEP 2006

Disclaimer and ReferencesDisclaimer and References

El ect ri cal E

quipment /

Ref ri gerat ion &

AC

• This PowerPoint training session was prepared as part of the project “Greenhouse Gas Emission Reduction from Industry in Asia and the Pacific” (GERIAP). While reasonable efforts have been made to ensure that the contents of this publication are factually correct and properly referenced, UNEP does not accept responsibility for the accuracy or completeness of the contents, and shall not be liable for any loss or damage that may be occasioned directly or indirectly through the use of, or reliance on, the contents of this publication. © UNEP, 2006.

• The GERIAP project was funded by the Swedish International Development Cooperation Agency (Sida)

• Full references are included in the textbook chapter that is available on www.energyefficiencyasia.org