Faster Speed Recovers R11 at 100-lb/min liquid and 0.66-lb/min vapor. On transfer tests between two cylinders, LOVAC recovered 500-lbs of R11 to 29 Hg vacuum in just 13-minutes. Noncondensibles? Not an Issue! In the above transfer test, we introduced 32-ft 3 of air to the cylinder being recovered. With the ambient temperature over 100F, recovery only took an extra 1.5 minutes in spite of the heavy contamination. LOVACs compressor works against very high head pressures and the on-board direct expansion unit rapidly condenses and subcools recovered refrigerant to minimize the effects of noncondensibles. High Durability Rugged 2.0-hp open drive compressor stands up to difficult recovery conditions better than vacuum pumps. Refrigerant Compatibility Services all low pressure refrigerants. Switching between R11, R123, & R113 simply involves evacuating the recov- ery unit, changing fluid and replacing two external filters. Easy Operations Evacuating lines and switching from liquid to vapor recovery modes simply involves turning three valves and rerouting one hose. Automatically shuts off upon achieving 29-in Hg vacuum in the cooling system. LOVAC Outpaces Other Recovery Systems, Especially When Refrigerant is contaminated with Moisture, Oil, or Noncondensibles. Refrigerant Recovery Lovac TM Low Pressure Recovery System Other Refrigerant Handling Products from Carrier: TotalVac HandiVac MityVac Evac Commercial Allvac EnviroPurge MiniPurge Electromechanical Model

Upload: others

Post on 21-Jan-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Refrigerant Recovery...Lovac is equipped with full 3/4fl internal piping and valving and a 2.0hp open drive compressor to quickly recover chiller refrigerant. The open drive compressor

Faster Speed Recovers R11 at 100-lb/min liquid and 0.66-lb/min vapor.On transfer tests between two cylinders, LOVAC recovered500-lbs of R11 to 29� Hg vacuum in just 13-minutes.

Noncondensibles? Not an Issue!In the above transfer test, we introduced 32-ft3 of air to thecylinder being recovered. With the ambient temperatureover 100°F, recovery only took an extra 1.5 minutes in spiteof the heavy contamination. LOVAC�s compressor worksagainst very high head pressures and the on-board directexpansion unit rapidly condenses and subcools recoveredrefrigerant to minimize the effects of noncondensibles.

High DurabilityRugged 2.0-hp open drive compressor stands up to difficultrecovery conditions better than vacuum pumps.

Refrigerant CompatibilityServices all low pressure refrigerants. Switching betweenR11, R123, & R113 simply involves evacuating the recov-ery unit, changing fluid and replacing two external filters.

Easy Operations � Evacuating lines and switching from liquid to vapor

recovery modes simply involves turning three valvesand rerouting one hose. Automatically shuts off uponachieving 29-in Hg vacuum in the cooling system.

LOVAC Outpaces Other RecoverySystems, Especially WhenRefrigerant is contaminated withMoisture, Oil, or Noncondensibles.

Refrigerant Recovery

LovacTM

Low Pressure Recovery System

Other Refrigerant Handling Products from Carrier:

TotalVacHandiVacMityVacEvac CommercialAllvacEnviroPurgeMiniPurge

Electromechanical Model

Page 2: Refrigerant Recovery...Lovac is equipped with full 3/4fl internal piping and valving and a 2.0hp open drive compressor to quickly recover chiller refrigerant. The open drive compressor

XXX X XXX XLovac.......................... CRLAir Cooled ............................. AWater Cooled......................... W103-127V,50/60Hz,1Ph,2Hp............ 115220-240V,50/60Hz,1Ph,2Hp............. 240Electromechanical Controls, Open Drive........... E

Included with Purchase:� One power cord� Two each 3/4�-5/8� and 5/8�-1/2� reducing fittings� Electromechanical model includes:

- Two 48-in3 filter drier cores: FD-048-CR- One 3/4 in. x 20 ft. hose: 075-020-HP-FB- Two 3/4 in. x 10 ft. hoses: 075-010-HP-FB

Optional Accessories:� Spare filter driers:

FD-048-CR 48-in3 filter drier cores� Compressor fluid, 1 gal: OIL-POE-1G� 440 lb. & 880 lb. recovery tanks 3/4 in. ports � Tank float safety cables & adapters

SPECIFICATIONS

Lovac is equipped with full 3/4� internal pipingand valving and a 2.0hp open drive compressorto quickly recover chiller refrigerant. The opendrive compressor is highly tolerant of noncon-densibles and makes the unit lighter and moretransportable.

Electromechanical or Microprocessor controlsare available. The unit may also be air or watercooled. Lovac�s high capacity air cooled con-denser has been tested under 140°F ambientconditions with excellent results and providesmore convenient operations.

PART NUMBERS

Gain the Capacity to Quickly Recover Charges From Medium & LargeTonnage Low Pressure Chillers.

Recovery Rates (R11)� Open Drive Model Liquid = 100-lb/min Vapor = 0.66-lb/minFinal Vacuum 29-in HgPower: Recovery Unit 103-127VAC, 1φ, 50/60Hz, 2.0-hp, 10AWeight: 135-lbs (62-kg) Shipping: 245-lbs (112-kg)Connections 3/4-in male flare fittings with ball valvesWarranty 1-year PartsDimensions (LxWxH)

26in (59cm) x 25in (56cm) x 45in (101cm)

Vapormizer lowpressure recoverytanks: 440 & 830 lbcapacities (opt.)

10 ft.x3/4 in.hoses (incl.)

20 ft.x3/4 in.hoses (incl.)

Low pressurechiller

Replacement Components Division � © Carrier Corporation 11/99 Rev. C 03/02Manufacturer reserves the right to make changes to products and specifications. www.totaline.com Literature Number 570-571