SWEET TEA Ft. Gordon, Georgia RECORD SPECIFICATIONS VOLUME 3 DIVISIONS 13-15 FEBRUARY 05, 2010 Hensel Phelps / Kiewit Joint Venture Black & Veatch - Gensler - Ecos Environmental Design CMI - M.C. Dean - Brittingham & Associates Contract Number: W912HN-07-C-0006 Property of the United States Government Copying, Dissemination, or Distribution of this Documents to any Unauthorized person is prohibited UNCLASSIFIED//FOR OFFICIAL USE ONLY

Upload: others

Post on 04-Feb-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

  • SWEET TEA Ft. Gordon, Georgia

    RECORD SPECIFICATIONS

    VOLUME 3 DIVISIONS 13-15

    FEBRUARY 05, 2010

    Hensel Phelps / Kiewit Joint Venture Black & Veatch - Gensler - Ecos Environmental Design

    CMI - M.C. Dean - Brittingham & Associates

    Contract Number: W912HN-07-C-0006

    Property of the United States Government Copying, Dissemination, or Distribution of this Documents

    to any Unauthorized person is prohibited UNCLASSIFIED//FOR OFFICIAL USE ONLY

  • Sweet Tea Property of the United States Government 41695 Fort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    PROJECT TABLE OF CONTENTS

    VOLUME 1 DIVISION 01 - GENERAL REQUIREMENTS

    01010 GENERAL PROJECT DESCRIPTION AND DESIGN REQUIREMENTS 01012 DESIGN AFTER AWARD (DESIGN/BUILD) 01312 QUALITY CONTROL SYSTEM 01320 PROJECT SCHEDULE 01330 SUBMITTAL PROCEDURES 01335 SUSTAINABLE DESIGN AND DEVELOPMENT 01355 ENVIRONMENTAL PROTECTION 01356 STORM WATER POLLUTION PREVENTION MEASURES 01420 SOURCES FOR REFERENCE PUBLICATIONS 01451 CONTRACTOR QUALITY CONTROL 01500 TEMPORARY CONSTRUCTION FACILITIES 01525 SAFETY AND OCCUPATIONAL HEATLH REQUIREMENTS 01572 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT 01670 RECYCLED / RECOVERED MATERIALS 01780 CLOSEOUT SUBMITTALS 01781 OPERATION AND MAINTENANCE DATA 01810 GENERAL COMMISSIONING REQUIREMENTS

    DIVISION 02 - SITE CONSTRUCTION

    02300 EARTHWORK 02360 SOIL TREATMENT FOR SUBTERRANEAN TERMITE CONTROL 02372 FLUID APPLIED GEOMEMBRANE 02510 WATER DISTRIBUTION 02810 UNDERGROUND SPRINKLER SYSTEMS 2921 SEEDING 2922 SODDING 02930 EXTERIOR PLANTS 02935 LANDSCAPE ESTABLISHMENT

    DIVISION 03 - CONCRETE

    03100 STRUCTURAL CONCRETE FORMWORK 03150 EXPANSION JOINTS, CONTRACTION JOINTS, AND WATERSTOPS 03200 CONCRETE REINFORCEMENT 03300 CAST-IN-PLACE STRUCTURAL CONCRETE 03450 PLANT-PRECAST ARCHITECTURAL CONCRETE

    DIVISION 04 - MASONRY

    04200 MASONRY

    VOLUME 2

    DIVISION 05 - METALS

    5090 WELDING, STRUCTURAL 5091 ULTRASONIC INSPECTION OF WELDMENTS 05120 STRUCTURAL STEEL 05310 STEEL DECKS 05400 COLD-FORMED METAL FRAMING 05500 METAL: MISCELLANEOUS AND FABRICATIONS

    Record Specs Property of the United States Government 41695 02/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY

  • Sweet Tea Property of the United States Government 41695 Fort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    PROJECT TABLE OF CONTENTS

    05510 METAL STAIRS 05700 ORNAMENTAL METAL

    DIVISION 06 - WOOD AND PLASTICS

    06100 ROUGH CARPENTRY 06410 LAMINATE CLAD ARCHITECTURAL CASEWORK 06650 SOLID POLYMER (SOLID SURFACING) FABRICATIONS

    DIVISION 07 - THERMAL AND MOISTURE PROTECTION

    07141 ELASTOMERIC SHEET WATERPROOFING 07212 MINERAL FIBER BLANKET (BATT) INSULATION 07220 ROOF AND DECK INSULATION 7412 METAL ROOF PANELS 7413 METAL WALL PANELS 07540 THERMOPLASTIC (TPO) SINGLE-PLY ROOFING 07600 FLASHING AND SHEET METAL 07721 FLOOR HATCHES 07810 SPRAY-APPLIED FIREPROOFING 07840 FIRESTOPPING 07920 JOINT SEALANTS

    DIVISION 08 - DOORS AND WINDOWS

    08110 STEEL DOORS AND FRAMES 08210 WOOD DOORS 8330 OVERHEAD ROLLING DOORS 8331 METAL ROLLING COUNTER DOORS 08390 BLAST RESISTANT DOORS 08630 METAL FRAMED SKYLIGHTS (Blast Resistant Applications) 08710 DOOR HARDWARE 08800 GLAZING 08900 ALUMINUM CURTAIN WALL AND PUNCHED WINDOWS

    DIVISION 09 - FINISHES

    09100 METAL SUPPORT ASSEMBLIES 09250 GYPSUM BOARD 09310 CERAMIC TILE, QUARRY TILE, AND PAVER TILE 09445 RESINOUS TERRAZZO FLOORING 09510 ACOUSTICAL CEILINGS 09650 RESILIENT FLOORING 09670 FLUID-APPLIED FLOORING 09680 CARPET 09720 WALL COVERINGS 09840 ACOUSTICAL WALL TREATMENT 09900 PAINTS AND COATINGS

    DIVISION 10 - SPECIALTIES

    10160 TOILET COMPARTMENTS 10201 METAL LOUVERS 10221 WIRE MESH PARTITIONS 10270 RIGID GRID ACCESS FLOORING 10440 INTERIOR SIGNAGE

    Record Specs Property of the United States Government 41695 02/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY

  • Sweet Tea Property of the United States Government 41695 Fort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    PROJECT TABLE OF CONTENTS

    10500 LOCKERS 10523 FIRE EXTINGUISHERS AND CABINETS 10650 OPERABLE PARTITIONS 10800 TOILET ACCESSORIES

    DIVISION 11 - EQUIPMENT

    11161 DOCK LEVELERS 11243 CHEMICAL TREATMENT OF WATER FOR MECHANICAL SYSTEMS 11400 FOOD SERVICE EQUIPMENT

    DIVISION 12 - FURNISHINGS

    12485 ENTRANCE FLOOR MATS 12490 WINDOW TREATMENT 12610 FIXED SEATING

    VOLUME 3

    DIVISION 13 - SPECIAL CONSTRUCTION

    13080 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT 13100 LIGHTNING PROTECTION SYSTEM 13700 TURNSTILES AND SECURITY GATES 13708 CABLES FOR SECURITY SYSTEMS 13857 FIRE DETECTION, ALARM, AND MASS NOTIFICATION SYSTEM 13858 FIRE DETECTION - AIR SAMPLING SYSTEM 13920 FIRE PUMPS 13930 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION 13945 PREACTION SPRINKLER SYSTEM, FIRE PROTECTION 13965 WET CHEMICAL FIRE EXTINGUISHING SYSTEM

    DIVISION 14 - CONVEYING SYSTEMS

    14240 HYDRAULIC ELEVATORS 14300 COMMERCIAL ESCALATORS

    DIVISION 15 - MECHANICAL

    15070 SEISMIC PROTECTION FOR MECHANICAL EQUIPMENT 15080 THERMAL INSULATION FOR MECHANICAL SYSTEMS 15181 CHILLED AND CONDENSER WATER PIPING SYSTEMS 15400 PLUMBING, GENERAL PURPOSE 15620 LIQUID CHILLERS 15645 COOLING TOWER 15700 UNITARY HEATING AND COOLING EQUIPMENT 15895 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS 15910 DIRECT DIGITAL CONTROL SYSTEMS 15990 TESTING, ADJUSTING, AND BALANCING OF HVAC SYSTEMS 15995 COMMISSIONING OF HVAC SYSTEMS

    VOLUME 4

    DIVISION 16 - ELECTRICAL

    16050 BASIC ELECTRICAL MATERIALS AND METHODS

    Record Specs Property of the United States Government 41695 02/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY

  • Sweet Tea Property of the United States Government 41695 Fort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    PROJECT TABLE OF CONTENTS

    16070 SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT 16081 APPARATUS INSPECTION AND TESTING 16263 DIESEL-GENERATOR SET STATIONARY 100-2800 KW, WITH

    AUXILIARIES 16265 UNINTERRUPTIBLE POWER SUPPLY (UPS) SYSTEM ABOVE 15 KVA

    CAPACITY 16272 THREE-PHASE PAD-MOUNTED TRANSFORMERS 16302 UNDERGROUND ELECTRICAL DISTRIBUTION 16311 MAIN ELECTRIC SUPPLY STATION AND SUBSTATION 16360 SECONDARY UNIT SUBSTATIONS 16402 INTERIOR DISTRIBUTION SYSTEM 16410 AUTOMATIC TRANSFER SWITCH AND BY-PASS/ISOLATION SWITCH 16442 SWITCHBOARDS AND SWITCHGEAR 16475 COORDINATED POWER SYSTEM PROTECTION 16510 INTERIOR LIGHTING 16520 EXTERIOR LIGHTING 16710 BUILDING TELECOMMUNICATIONS CABLING SYSTEM 16711 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)

    -- End of Project Table of Contents --

    Record Specs Property of the United States Government 41695 02/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    SECTION 13080

    SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT

    PART 1 GENERAL

    1.1 REFERENCES

    The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

    AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)

    AISC 325 (2005 e13) Steel Construction Manual

    SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION (SMACNA)

    SMACNA Seismic Restraint Mnl (1998; Addendum 2000, 2nd Ed) Seismic Restraint Manual: Guidelines for Mechanical Systems

    U.S. DEPARTMENT OF DEFENSE (DOD)

    UFC 3-310-03A (2005) Seismic Design for Buildings

    1.2 SYSTEM DESCRIPTION

    1.2.1 General Requirements

    The requirements for seismic protection measures described in this section shall be applied to the mechanical equipment and systems listed below. Structural requirements shall be in accordance with Section 13 48 00 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT.

    1.2.2 Mechanical Equipment

    Mechanical equipment to be seismically protected shall include the following items to the extent required on the drawings or in other sections of these specifications:

    Water Heaters Water PipingExpansion Air Separator Tanks Valves and Fittings for PipingHeat Exchangers Thermal Storage UnitsWater Chiller Units Air and Refrigerant CompressorsCooling Towers Air Handling UnitsRefrigerant Piping DuctsPumps with Motors Unit HeatersStorage Tanks for Water Exhaust and Return Fans

    1.2.3 Mechanical Systems

    The following mechanical systems shall be installed as required on the drawings and other sections of these specifications and shall be seismically protected in accordance with this specification:

    Record Specs Property of the United States Government SECTION 1308002/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 1

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    All Piping Inside the Building Except as Specifically Stated Below Under "Items Not Covered By This Section".Chilled Water Distribution Systems Outside of BuildingsFuel Piping Outside of BuildingsAll Water Supply SystemsStorm and Sanitary Sewer SystemsCondenser Water Piping Outside the BuildingFuel Storage TanksWater Storage Tanks

    1.2.4 Contractor Designed Bracing

    The Contractor shall design the bracing in accordance with UFC 3-310-03A and additional data furnished by the Contracting Officer. Resistance to lateral forces induced by earthquakes shall be accomplished without consideration of friction resulting from gravity loads. UFC 3-310-03A uses parameters for the building, not for the equipment in the building; therefore, corresponding adjustments to the formulas shall be required. Loadings determined using UFC 3-310-03A are based on strength design; therefore, AISC 325 Specifications shall be used for the design. The bracing for the following mechanical equipment and systems shall be developed by the Contractor: .

    1.2.5 Items Not Covered By This Section

    1.2.5.1 Fire Protection Systems

    Seismic protection of piping for fire protection systems shall be installed as specified in Sections 21 30 00 FIRE PUMPS, 21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION, 21 13 17.00 10 DRY PIPE SPRINKLER SYSTEM, FIRE PROTECTION, 21 13 18.00 10 PREACTION AND DELUGE SPRINKLER SYSTEMS, FIRE PROTECTION, and 21 13 24.00 10 AQUEOUS FILM-FORMING FOAM (AFFF) FIRE PROTECTION SYSTEM.

    1.2.5.2 Items Requiring No Seismic Restraints

    Seismic restraints are not required for the following items:

    a. All other piping less than 2-1/2inches inside diameter.

    b. Rectangular air handling ducts less than 6 square feet in cross sectional area.

    c. Round air handling ducts less than 28 inches in diameter.

    d. Piping suspended by individual hangers 12 inches or less in length from the top of pipe to the bottom of the supporting structural member where the hanger is attached, except as noted below.

    e. Ducts suspended by hangers 12 inches or less in length from the top of the duct to the bottom of the supporting structural member, except as noted below.

    In exemptions d. and e. all hangers shall meet the length requirements. If the length requirement is exceeded by one hanger in the run, the entire run shall be braced. Interior piping and ducts not listed above shall be seismically protected in accordance with the provisions of this specification.

    Record Specs Property of the United States Government SECTION 1308002/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 2

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    1.3 EQUIPMENT REQUIREMENTS

    1.3.1 Rigidly Mounted Equipment

    The following specific items of equipment: To be furnished under this contract shall be constructed and assembled to withstand the seismic forces specified in UFC 3-310-03A, Chapter 10. Each item of rigid equipment shall be entirely located and rigidly attached on one side only of a building expansion joint. Piping, duct, electrical conduit, etc., which cross the expansion joint shall be provided with flexible joints that are capable of accommodating displacements equal to the full width of the joint in both orthogonal directions.

    ChillersAir-Handling UnitsCooling Towers

    1.4 SUBMITTALS

    Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

    SD-02 Shop Drawings

    Coupling and Bracing.Flexible Couplings or Joints.Equipment Requirements.Contractor Designed Bracing.

    Detail drawings along with catalog cuts, templates, and erection and installation details, as appropriate, for the items listed. Submittals shall be complete in detail; shall indicate thickness, type, grade, class of metal, and dimensions; and shall show construction details, reinforcement, anchorage, and installation with relation to the building construction.

    SD-03 Product Data

    Coupling and Bracing.Equipment Requirements.

    Copies of the design calculations with the detail drawings. Calculations shall be stamped by a registered engineer and shall verify the capability of structural members to which bracing is attached for carrying the load from the brace.

    Contractor Designed Bracing.

    Copies of the design calculations with the drawings. Calculations shall be approved, certified, stamped and signed by a registered Professional Engineer. Calculations shall verify the capability of structural members to which bracing is attached for carrying the load from the brace.

    SD-07 Certificates

    Record Specs Property of the United States Government SECTION 1308002/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 3

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    Flexible Ball Joints.

    Flexible ball joints shall be certified to be suitable for the service intended by the manufacturer. Information verifying experience at not less than 3 locations of 2 years' satisfactory operation in a similar application shall be submitted.

    PART 2 PRODUCTS

    2.1 FLEXIBLE COUPLINGS

    Flexible couplings shall have same pressure and temperature ratings as adjoining pipe.

    2.2 FLEXIBLE BALL JOINTS

    Flexible ball joints shall have cast or wrought steel casing and ball parts capable of 360-degree rotation with not less than 15-degree angular movement.

    2.3 FLEXIBLE MECHANICAL JOINTS

    a. Mechanical couplings for steel or cast iron pipe shall be of the sleeve type and shall provide a tight flexible joint under all reasonable conditions, such as pipe movement caused by expansion, contraction, slight settling or shifting of the ground, minor variations in trench gradients, and traffic vibrations. Where permitted in other sections of these specifications, joints utilizing split-half couplings with grooved or shouldered pipe ends may be used.

    b. Sleeve-type couplings shall be used for joining plain-end pipe sections. The coupling shall consist of one steel middle ring, two steel followers, two gaskets, and necessary steel bolts and nuts to compress the gaskets.

    2.4 MANUFACTURED BALL JOINTS

    Manufactured ball joints shall be as recommended by the manufacturer for the intended use, and shall be approved by the Contracting Officer before installation.

    2.5 SWAY BRACING MATERIALS

    Sway bracing materials (e.g. rods, plates, rope, angles, etc.) shall be as specified in Section 13 48 00 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT.

    PART 3 EXECUTION

    3.1 COUPLING AND BRACING

    Coupling installation shall conform to the details shown on the drawings. Provisions of this paragraph apply to all piping within a 5 foot line around outside of building unless buried in the ground. Piping grouped for support on trapeze-type hangers shall be braced at the most frequent interval as determined by applying the requirements of this sepcification to each piping run on the common support. Bracing components shall be sized as required for the total load carried by the common supports.

    Record Specs Property of the United States Government SECTION 1308002/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 4

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    Bracing rigidly attached to pipe flanges, or similar, shall not be used where it would interfere with thermal expansion of piping.

    3.2 BUILDING DRIFT

    Joints capable of accommodating seismic displacements shall be provided for vertical piping between floors of the building, where pipes pass through a building seismic or expansion joint, or where rigidly supported pipes connect to equipment with vibration isolators. Horizontal piping across expansion joints shall accommodate the resultant of the drifts of each building unit in each orthogonal direction. For threaded piping, swing joints made of the same piping material shall be provided. For piping with manufactured ball joints the seismic drift shall be [0.015] [_____] feet per foot of height above the base where the seismic separation occurs; this drift value shall be used in place of the expansion given in the manufacturer's selection table.

    3.3 PIPE SLEEVES

    Pipe sleeves in interior non-fire rated walls shall be sized as indicated on the drawings to provide clearances that will permit differential movement of piping without the piping striking the pipe sleeve. Pipe sleeves in fire rated walls shall conform to the requirements in Section 07 84 00 FIRESTOPPING.

    3.4 SPREADERS

    Spreaders shall be provided between adjacent piping runs to prevent contact during seismic activity whenever pipe or insulated pipe surfaces are less than 4 inches apart. Spreaders shall be applied at same interval as sway braces at an equal distance between the sway braces. If rack type hangers are used where the pipes are restrained from contact by mounting to the rack, spreaders are not required for pipes mounted in the rack. Spreaders shall be applied to surface of bare pipe and over insulation on insulated pipes utilizing high-density inserts and pipe protection shields in accordance with the requirements of Section 23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS.

    3.5 SWAY BRACES FOR PIPING

    Sway braces shall be provided to prevent movement of the pipes under seismic loading. Braces shall be provided in both the longitudinal and transverse directions, relative to the axis of the pipe. The bracing shall not interfere with thermal expansion requirements for the pipes as described in other sections of these specifications.

    3.5.1 Transverse Sway Bracing

    Transverse sway bracing for steel and copper pipe shall be provided as specified in Section 13 48 00 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT. All runs (length of pipe between end joints) shall have a minimum of two transverse braces. Transverse sway bracing for pipes of materials other than steel and copper shall be provided at intervals not to exceed the hanger spacing as specified in Section 22 00 00 PLUMBING, GENERAL PURPOSE.

    3.5.2 Longitudinal Sway Bracing

    Longitudinal sway bracing shall be provided at 40 foot intervals unless

    Record Specs Property of the United States Government SECTION 1308002/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 5

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    otherwise indicated. All runs (length of pipe between end joints) shall have one longitudinal brace minimum. Sway braces shall be constructed in accordance with the drawings. Branch lines, walls, or floors shall not be used as sway braces.

    3.5.3 Vertical Runs

    Run is defined as length of pipe between end joints. Vertical runs of piping shall be braced at not more than 10 foot vertical intervals. Braces for vertical runs shall be above the center of gravity of the segment being braced. All sway braces shall be constructed in accordance with the drawings. Sway braces shall attach to the structural system and shall not be connected to branch lines, walls, or floors.

    3.5.4 Clamps and Hangers

    Clamps or hangers on uninsulated pipes shall be applied directly to pipe. Insulated piping shall have clamps or hangers applied over insulation in accordance with Section 23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS.

    3.6 SWAY BRACES FOR DUCTS

    3.6.1 Braced Ducts

    Bracing details and spacing for rectangular and round ducts shall be in accordance with SMACNA Seismic Restraint Mnl, including Appendix E. However, the design seismic loadings for these items shall not be less than loadings obtained using the procedures in UFC 3-310-03A.

    3.6.2 Unbraced Ducts

    Hangers for unbraced ducts shall be attached to the duct within 2 inches of the top of the duct in accordance with SMACNA Seismic Restraint Mnl. Unbraced ducts shall be installed with a 6 inch minimum clearance to vertical ceiling hanger wires.

    -- End of Section --

    Record Specs Property of the United States Government SECTION 1308002/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 6

  • Sweet Tea Property of the United States Government 41695AB Fort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    Record Specs Property of the United States Government SECTION 13100 02/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 1

    SECTION 13100 LIGHTNING PROTECTION SYSTEM

    04/06

    PART 1 GENERAL 1.1 REFERENCES

    The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE) IEEE Std 81 (1983) Guide for Measuring Earth

    Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System (Part 1)Normal Measurements

    NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) NFPA 70 (2007) National Electrical Code - 2008

    Edition NFPA 780 (2007) Standard for the Installation of

    Lightning Protection Systems UNDERWRITERS LABORATORIES (UL) UL 467 (2007) Standard for Grounding and Bonding

    Equipment

    UL 96 (2005) Standard for Lightning Protection

    Components UL 96A (2007) Standard for Installation

    Requirements for Lightning Protection Systems

    UL Electrical Constructn (2007) Electrical Construction Equipment

    Directory 1.2 RELATED REQUIREMENTS

    Section 16050 BASIC ELECTRICAL MATERIALS AND METHODS applies to this section with additions and modifications specified herein. 1.2.1 Verification of Dimensions

    Contractor shall become familiar with all details of work, verify all dimensions in field, and shall advise Contracting Officer of any discrepancy before performing work. No departures shall be made without prior approval of Contracting Officer. 1.2.2 System Requirements

    Materials shall consist of standard products of a manufacturer regularly

  • Sweet Tea Property of the United States Government 41695AB Fort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    Record Specs Property of the United States Government SECTION 13100 02/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 2

    engaged in production of lightning protection systems and shall be manufacturer's latest UL approved design. Lightning protection system shall conform to NFPA 70, NFPA 780, UL 96 and UL 96A. 1.3 SUBMITTALS

    Government approval is required for submittals with a "G" designation;

    submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

    SD-02 Shop Drawings

    Overall lightning protection system; G Each major component; G

    SD-06 Test Reports

    Grounding system test; G Lightning protection system inspection; G

    SD-07 Certificates

    UL listing or label; G

    1.4 QUALITY ASSURANCE

    In each standard referred to herein, consider the advisory provisions to be mandatory, as though the word "shall" has been substituted for "should" wherever it appears. Interpret references in these standards to "authority having jurisdiction," or words of similar meaning, to mean Contracting

    Officer. 1.4.1 Installation Drawings

    a. Submit installation shop drawing for the overall lightning protection system. Drawings shall include physical layout of the equipment, mounting details, relationship to other parts of the work, and wiring diagram. b. Submit detail drawings for each major component to include manufacturer's descriptive and technical literature, catalog cuts, and installation instructions.

    1.4.2 UL Listing or Label

    Submit proof of compliance. Label of or listing in UL Electrical Constructn is acceptable evidence. In lieu of label or listing, submit written certificate from an approved, nationally recognized testing organization equipped to perform such services, stating that items have been tested and conform to requirements and testing methods of Underwriters Laboratories. 1.5 SITE CONDITIONS

    Contractor will become familiar with details of the work, verify dimensions in the field, and advise Contracting Officer of discrepancies before

  • Sweet Tea Property of the United States Government 41695AB Fort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    Record Specs Property of the United States Government SECTION 13100 02/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 3

    performing work. Deviations from contract drawings will not be made without prior approval of Contracting Officer. PART 2 PRODUCTS 2.1 MATERIALS

    Do not use a combination of materials that forms an electrolytic couple of such nature that corrosion is accelerated in presence of moisture unless moisture is permanently excluded from the junction of such metals. Where unusual conditions exist which would cause corrosion of conductors, provide conductors with protective coatings or oversize conductors. Where mechanical hazard is involved, increase conductor size to compensate for hazard or protect conductors by covering them with molding or tubing made of wood or nonmagnetic material. When metallic conduit or tubing is provided, electrically bond conductor to conduit or tubing at the upper and lower ends by clamp type connectors or welds (including exothermic). 2.1.1 Main and Bonding Conductors NFPA 780 and UL 96 Class I, Class II, or Class II modified materials as applicable. 2.1.2 Copper Provide copper conductors on nonmetallic stacks that do not weigh less than 319 pounds per thousand feet, and provide cable such that the size of any strand in the cable is not less than No. 15 AWG. Provide thickness of web or ribbon on stacks that is not less than No. 12 AWG. Provide loop conductors that are comprised of copper conductors not smaller than No. 1/0 AWG. 2.1.3 Aluminum

    Do not allow aluminum to contact the earth and do not use in any other manner that will contribute to rapid deterioration of the metal. Observe appropriate precautions at connections with dissimilar metals in accordance with NFPA 70 Article 110-14. Provide aluminum cable conductors for bonding and interconnecting metallic bodies to main cable that are at least equivalent to strength cross-sectional area of a No. 4 AWG aluminum wire. When perforated strips are provided, use strips that are much wider than solid strips. Use a strip width that is at least twice that of the diameter of the perforations. Use an aluminum strip which has a thickness of not less than the diameter of No. 12 AWG and at least 1 1/2 inches wide for connecting exposed water pipes. 2.2 COMPONENTS 2.2.1 Air Terminals Provide terminals in accordance with UL 96, except provide Class II for Class I and Class II applications. Support air terminals more than 24 inches in length by suitable brace, with guides, not less than one-half the height of the terminal. 2.2.2 Ground Rods Provide ground rods made of copper-clad steel conforming to conform to UL 467. Provide ground rods that are not less than 3/4 inch in diameter and

  • Sweet Tea Property of the United States Government 41695AB Fort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    Record Specs Property of the United States Government SECTION 13100 02/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 4

    10 feet in length. Do not mix ground rods of copper-clad steel, stainless steel, galvanized ferrous, or solid copper on the job. 2.2.3 Connections and Terminations Provide connectors for splicing conductors that conform to UL 96, class as applicable. Conductor connections can be made by clamps or welds

    (including exothermic). Provide style and size connectors required for the installation. 2.2.4 Connector Fittings Provide connector fittings for "end-to-end", "Tee", or "Y" splices that conform to NFPA 780. 2.2.5 Lightning Protection Components Provide bonding plates, air terminal supports, chimney bands, clips, and fasteners that conform to UL 96 classes as applicable. PART 3 EXECUTION 3.1 INTEGRAL SYSTEM Lightning protection system consists of air terminals, roof conductors, down conductors, ground connections, grounding electrodes and ground loop conductor. Electrically interconnect lightning protection system to form the shortest distance to ground. Do not use nonconducting parts of the structure as part of the building's lightning protection system. Expose conductors on the structures except where conductors are required to be in protective sleeves. Interconnect secondary conductors with grounded metallic parts within the building. Make interconnections within side-flash distances at or above the level of the grounded metallic parts.

    3.1.1 Air Terminals Air terminal design and support conforming to NFPA 780. Rigidly connect terminals to, and make electrically continuous with, roof conductors by means of pressure connectors or crimped joints of T-shaped malleable metal. Provide pressure connector or crimped joint with a dowel or threaded fitting to connect ground rod conductor with air terminal. Set air terminals at ends of structures not more than 2 feetfrom ends of ridges and corners of roofs. Do not exceed 25 feet in spacing of 2 foot high air terminals on ridges, parapets, and around perimeter of building with flat roofs. When necessary to exceed this spacing, increase specified height of air terminals not less than 2 inches for each one foot of increase over 25 feet. On large flat, or gently sloping roofs, as defined in NFPA 780, place air terminals at points of the intersection of imaginary lines dividing the surface into rectangles having sides not exceeding 50 feet in length. Secure air terminals against overturning either by attachment to the object to be protected or by means of a substantial tripod or other braces which are permanently and rigidly attached to the building or structure. Metal projections and metal parts of buildings such as smokestacks and other metal objects that are at least 3/16 inch thick and that do not contain hazardous materials, need not be provided with air terminals. However, bond these metal objects to a lightning conductor through a metal conductor of the same unit weight per length as the main conductor. Where metal ventilators are installed, mount air terminals thereon, where practical. Bond air terminals, erected by necessity

  • Sweet Tea Property of the United States Government 41695AB Fort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    Record Specs Property of the United States Government SECTION 13100 02/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 5

    adjacent to a metal ventilator, to the ventilator near the top and bottom. Where nonmetallic spires, steeples, or ventilators are present, mount air terminals to the side. In addition, where spires or steeples project more than 10 feet above the building, continue conductor from air terminal to nearest down conductor securely connect thereto. 3.1.2 Roof Conductors

    Connect roof conductors directly to the roof or ridge roll. Avoid sharp bends or turns in conductors. Do not make turns of less than 8 inches. Preserve horizontal or downward course on conductors. Rigidly fasten conductors every 3 feet along the roof and down the building to the ground. Rigidly connect metal ventilators to the roof conductor at three places. Make connections electrically continuous. Course roof conductors along contours of flat roofs, ridges, parapets, and edges; and where necessary, over flat surfaces, in such a way as to join each air terminal to all the rest. Connect roof conductors surrounding tank tops, decks, flat surfaces, and flat roofs to form a closed loop. 3.1.3 Down Conductors Make down conductors electrically continuous from air terminals and roof conductors to grounding electrodes. Course down conductors over outer extreme portions of the building, such as corners, with consideration given to location of ground connections and air terminals. Provide each building or structure not less than two down conductors located as widely separated as practicable, such as at diagonally opposite corners. Install additional down conductors when necessary to avoid "dead ends" or branch conductors exceeding 16 feet in length, ending at air terminals. Equally and symmetrically spaced down conductors about the perimeter of the structure. Protect conductors where necessary, to prevent physical damage or displacement to the conductor. 3.1.4 Interconnection of Metallic Parts

    Connect metal doors, windows, and gutters directly to ground or down conductors using not smaller than No. 6 copper conductor, or equivalent. Where there is probability of unusual wear, mechanical injury, or corrosion, provide conductors with greater electrical capacity than normal or protect the conductor. Provide mechanical ties or pressure connectors between grounds and metal doors and windows. 3.1.5 Ground Connections Securely connect conductor forming continuations of down conductors from structure to grounding electrode in a manner to ensure electrical continuity between the two. Provide clamp type connections or welds (including exothermic) for continuation. Provide a ground connection for each down conductor. Attach down conductors to ground rods by welding (including exothermic), brazing, or clamping. Provide clamps suitable for direct burial. Protect ground connection from mechanical injury. Bond metal water pipes and other large underground metallic objects together with all grounding mediums. In making ground connections, take advantage of all permanently moist places where practicable, although avoid such places when area is wet with waste water that contains chemical substances, especially those corrosive to metal.

  • Sweet Tea Property of the United States Government 41695AB Fort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    Record Specs Property of the United States Government SECTION 13100 02/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 6

    3.1.6 Grounding Electrodes Provide grounding electrode for each down conductor. Extend driven ground rods into the existing undisturbed earth for a distance of not less 10 feet. Set ground rods not less than 2 feet nor more than 10 feet, from the structure. After the completed installation, measure the total resistance to ground using the fall-of-potential method described in IEEE Std 81.

    Maximum resistance of a driven ground rod shall be 10 ohms, under normally dry conditions when a ground loop is not used. Use a ground loop when two of any three ground rods, driven not less than 10 feet into the ground, a minimum of 10 feet apart, and equally spaced around the perimeter, give a combined value exceeding 50 ohms immediately after having driven. For ground loop, provide continuous No. 1/0 bare stranded copper cable or equivalent material having suitable resistance to corrosion. Lay ground loop around the perimeter of the structure in a trench not less than 30 inches below grade, at a distance not less than 2 feet nor more than 10 feet from the nearest point of the structure. Install a ground loop in earth undisturbed by excavation, not earth fill, and do not locate beneath roof overhang, or wholly under paved areas or roadways where rainfall cannot penetrate to keep soil moist in the vicinity of the cable. Make connections between ground conductors and grounds or ground loop, and between ground loop and grounds electrically continuous. 3.2 APPLICATIONS 3.2.1 Nonmetallic Exterior Walls with Metallic Roof Bond metal roof sections together which are insulated from each other so that they are electrically continuous. Connect air terminals so that they are electrically continuous with the metal roof as well as the roof conductors and down conductors. Bond ridge cables and roof conductors to the roof at upper and lower edges of roof and at intervals not to exceed 100 feet. Bond down conductors to roof conductors and to lower edge of metal roof. Where metal of roof is in small sections, make connections

    between air terminals and down conductors to at least four sections of the metal roof. Make connections electrically continuous and have a surface contact of at least 3 square inches. 3.2.2 Metal Roofs with Metal Walls Bond metal roof and metal walls so that they are electrically continuous and considered as one unit. Connect air terminals to and make them electrically continuous with the metal roof as well as the roof down conductors. Bond all roof conductors and down conductors to metal roof or metal walls at upper and lower edges at intervals not to exceed 100 feet. Make all connections electrically continuous and have surface contact of at least 3 square inches. 3.2.3 Steel Frame Building Make the steel framework of the building electrically continuous. Electrical continuity may be provided by bolting, riveting, or welding unless another specific method is indicated. Connect air terminals to the structural steel framework at the ridge. Provide short runs of conductors to join air terminals to the metal framework so that proper placing of air terminals is maintained. Separate down conductors from air terminals to ground connections are not required. Where water system enters the building, securely connect structural steel framework and water system at point of entrance by a ground connector. Make connections to pipes by

  • Sweet Tea Property of the United States Government 41695AB Fort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    Record Specs Property of the United States Government SECTION 13100 02/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 7

    means of ground clamps with lugs. Make connections to structural framework by means of nut and bolt or welding. Make connections between columns and ground connections at bottom of steel columns. Make ground connections to grounds or ground loop runs from not less than one-half of the columns distributed equally around perimeter of structure. When no water system enter the structure, run ground connections from steel columns distributed equally around the perimeter of the structure. Bond metal doors, windows,

    gutters, and similar metal installation to steel work of the building. Provide a grounding electrode for each ground connection. 3.2.4 Ramps and Covered Passageways Ramps and covered passageways which are in the zone of protection of a lightning protection system, as defined by NFPA 780, need no additional lightning protection. However, ramps and covered passageways which are outside the zone of protection of a lightning protection system shall be provided with a lightning protection conforming to the requirements for lightning protection systems for buildings of similar construction. Place a down conductor and a driven ground at one of the corners where the ramp connects to each building or structure. Connect down conductor and driven ground to the ground loop or nearest ground connection of the building or structure. Where buildings or structures and connecting ramps are clad with metal, connect metal of the buildings or structures and metal of the ramp in a manner to ensure electrical continuity, in order to avoid the possibility of a flash-over or spark due to a difference in potential. Make connections electrically continuous and have a surface contact area of at least 3 square inches. 3.3 INTERFACE WITH OTHER STRUCTURES 3.3.1 Interconnection of Metal Bodies Protect metal bodies when not within the zone of protection of air terminal. Bond metal bodies having an area of 400 square inches or greater

    or a volume of 1000 cubic inches or greater to lightning protection system using main size conductors and a bonding plate having a surface contact area of not less than 3 square inches. Make provisions to guard against the corrosive effect of bonding dissimilar metals. Bond metal bodies at their closest point to the lightning protection system using bonding conductors and fittings. Independently ground any metal body that exceeds 5 feet in any dimension, that is situated wholly within a building, and that does not at any point come within 6 feet of a lightning conductor or metal connected to a lightning protection system. 3.4 FIELD QUALITY CONTROL 3.4.1 Grounding System Test Test the grounding system to ensure continuity and that resistance to ground is not in excess of 3 ohms. Test the ground rod for resistance to ground before making connections to the rod. Tie the grounding system together and test for resistance to ground. Make resistance measurements in dry weather, not earlier than 48 hours after rainfall. Include in the written report: locations of ground rods, resistance, and soil conditions at the time that measurements were made. Submit results of each test to the Contracting Officer.

  • Sweet Tea Property of the United States Government 41695AB Fort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    Record Specs Property of the United States Government SECTION 13100 02/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 8

    3.4.2 Lightning Protection System Inspection Make visual inspections to verify that there are no loose connections which may result in high resistance joints, and that conductors and system

    components are securely fastened to their mounting surfaces and are protected against accidental mechanical displacement. -- End of Section --

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    SECTION 13125

    VEHICLE CANOPIES

    PART 1 GENERAL

    1.1 SUMMARY

    This section includes free-standing, steel-framed, metal vehicle canopies complete with steel frame, roof deck panels, standing-seam fascia panels, gutters and downspouts, trim members, and all necessary brackets and fasteners.

    1.2 REFERENCES

    The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

    ASTM INTERNATIONAL (ASTM)

    ASTM A 325 (2007) Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength

    ASTM A 36/A 36M (2005) Standard Specification for Carbon Structural Steel

    ASTM A 500/A 500M (2007) Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes

    ASTM A 615/A 615M (2008) Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement

    ASTM A 653/A 653M (2007) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

    ASTM C 150 (2007) Standard Specification for Portland Cement

    ASTM C 33 (2007) Standard Specification for Concrete Aggregates

    ASTM F 1554 (2007a)Standard Specification for Anchor Bolts, Steel, 36, 55, and 105-ksi Yield Strength

    ASTM F 436 (2007a) Hardened Steel Washers

    INTERNATIONAL CODE COUNCIL - INTERATIONAL BUILDING CODE (ICC IBC)

    ICC IBC 2006 (2006) International Building Code

    Record Specs Property of the United States Government SECTION 1312502/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 1

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    1.3 SYSTEM DESCRIPTION

    1.3.1 Performance Requirements

    Provide steel framed vehicle canopies that have been manufactured, fabricated, and installed to withstand the environmental loading required by the ICC IBC 2006.

    1.3.2 Design Loads

    Design loads shall be as follows:

    Roof Live Load: 20 psfRoof Dead Load: 3 psfGround Snow Load: 10 psfBasic Wind Speed (3 Second Gust): 100 mph (Exp. "C")

    1.4 SUBMITTALS

    Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. Submit the following in accordance with Section 01330 SUBMITTAL PROCEDURES:

    SD-02 Shop Drawings

    Drawings

    Submit shop drawings showing layout, profiles, and anchorage of all canopy components. Include complete installation details.

    Calculations

    Submit calculations certified by a professional engineer prior to fabrication that indicate that the canopy designs as submitted meet or exceed the structural design requirements.

    SD-04 Samples

    Finish, Color, and Texture

    Submit color samples indicating the Manufacturer's standard colors for the submitted products.

    1.5 QUALITY ASSURANCE

    The canopy manufacturer shall have a minimum of 5 years of experience in the manufacture of canopy systems similar to those proposed for use on this project. The canopy installer shall have 3 years of experience in the installation of similar canopy systems and shall be approved by the manufacturer.

    1.6 DELIVERY, STORAGE, AND HANDLING

    1.6.1 Delivery

    Deliver materials in manufacturer's original, unopened, undamaged containers with identification labels intact.

    Record Specs Property of the United States Government SECTION 1312502/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 2

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    1.6.2 Storage and Protection

    Store materials protected from exposure to harmful weather conditions. Protect stored materials from damage.

    PART 2 PRODUCTS

    2.1 CANOPY COMPONENTS

    2.1.1 Material Requirements

    The structural materials used in the construction of the canopies shall meet the following material requirements.

    a. Anchor Bolts and Rolled Structural Steel Members: ASTM A 36/A 36M.b. Tubular Steel Members: ASTM A 500/A 500M, Grade B.c. Structural Bolts: ASTM A 325.d. Steel Roof Deck: ASTM A 653/A 653M, Grade 50.e. Hardened Steel Washers: ASTM F 436.f. Anchor Bolts: ASTM F 1554.g. Concrete Reinforcing: ASTM A 615/A 615M, Grade 60.h. Concrete Reinforcing Ties and Stirrups: ASTM A 615/A 615M, Grade 40.i. Portland Cement: ASTM C 150.j. Aggregate: ASTM C 33.

    2.2 FINISH REQUIREMENTS

    All panels are to receive a factory-applied polyvinylidene fluoride finish consisting of a baked-on top-coat with a manufacturer's recommended prime coat conforming to the following. Finish shall be applied to both sides of sheet metal components including the roof panels, fascia panels, gutter, and all trim items.

    2.2.1 Metal Preparation

    All metal is to have the surfaces carefully prepared for painting on a continuous process coil coating line by alkali cleaning, hot water rinsing, application of chemical conversion coating, cold water rinsing, sealing with acid rinse, and thorough drying.

    2.2.2 Prime Coating

    A base coat of epoxy paint, specifically formulated to interact with the top-coat, is to be applied to the prepared surfaces by roll coating to a dry film thickness of 0.20 + 0.05 mils. This prime coat must be oven cured prior to application of finish coat.

    2.2.3 Finish Coating

    Apply the finish coating over the primer by roll coating to dry film thickness of 0.80 + 5 mils (3.80 + 0.50 mils for Vinyl Plastisol) for a total dry film thickness of 1.00 + 0.10 mils (4.00 + 0.10 mils for Vinyl Plastisol). This finish coat must be oven-cured.

    2.2.4 Color

    Colors of the finished items will be chosen from the manufacturer's color charts and chips.

    Record Specs Property of the United States Government SECTION 1312502/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 3

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    2.2.5 Repair of Finishes

    Repair paint for color finished metal panels and accessories must be compatible paint of the same formula and color as the specified finish furnished by the metal panel manufacturer.

    2.3 FABRICATION

    Fabricate canopy components to the shapes and profiles required to provide structurally sound and watertight canopies.

    a. Roof deck panels shall be 16 inches wide, fabricated from 20 gauge ASTM A 653/A 653M, Grade 50 sheet steel with 3-inch tall interlocking ribs. Both the top and bottom of the roof deck panels shall be finished as specified in paragraph: FINISH REQUIREMENTS.

    b. Fascia panels shall be 16 inches wide, fabricated from 24 gauge ASTM A 653/A 653M, Grade 50 sheet steel with 1-1/2 inch deep standing seams. Both the front and rear of the fascia panels shall be finished as specified in paragraph: FINISH REQUIREMENTS.

    c. Other components shall be fabricated from galvanized steel to the required shapes and sizes to achieve the final canopy assembly. All components such as gutters and trim members that are exposed in the final construction shall be finished as specified in paragraph: FINISH REQUIREMENTS.

    PART 3 EXECUTION

    3.1 CANOPY ASSEMBLY

    3.1.1 Concrete Footings

    Construct concrete footings below grade to support the canopies using minimum 3000 psi concrete as shown on the approved shop drawings. Install reinforcement and four 1 inch diameter by 3 foot - 0 inch long anchor bolts in each footing.

    3.1.2 Framing System

    Install the canopy framing in accordance with the approved shop drawings. Secure the baseplates of the tubular steel columns to the anchor bolts in the concrete footings. Install grout between the baseplates and the footings. Bolt the roof beams to the tops of the columns and suspend the purlins from the underside of the beams with bolted connections. Encase the column bases in concrete to a height of 3 feet - 0 inches above finished curb height.

    3.1.3 Roof Deck Panels

    Attach the roof deck panels to the underside of the roof purlins with clamps. Connect the panels to each other as recommended by the manufacturer.

    3.1.4 Fascia Panels

    Attach the standing seam fascia panels to the supporting structure using interlocking standing seam clips that are secured to horizontal hat-shaped

    Record Specs Property of the United States Government SECTION 1312502/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 4

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    channels. Attach the hat-shaped channels to channel brackets located at a maximum of 4 feet - 0 inches on center that are attached to the top of the ribs of the roof deck panels.

    3.1.5 Gutters and Trim

    Attach the gutter and trim components in accordance with the approved shop drawings to provide a complete canopy assembly.

    3.1.6 Downspouts

    Install PVC downspouts concealed within the tubular steel columns. Connect to gutters and conceal with painted sheet metal downspout covers.

    3.2 PAINTING

    Finish paint all exposed steel members in accordance with Section 09900 PAINTS AND COATINGS. Touch up paint any factory finished components that have been damaged during construction.

    -- End of Section --

    Record Specs Property of the United States Government SECTION 1312502/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 5

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    SECTION 13202

    FUEL STORAGE SYSTEMS

    PART 1 GENERAL

    1.1 REFERENCES

    The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

    AMERICAN PETROLEUM INSTITUTE (API)

    API Spec 1581 (2002) Specifications and Qualification Procedures for Aviation Jet Fuel Filter/Separators

    API Spec 5L (2004) Line Pipe

    API Spec 6D (2002; Errata 2005) Specification for Pipeline Valves

    API Spec 6FA (1999) Fire Test for Valves

    API Std 1529 (1998) Aviation Fueling Hose

    API Std 1631 (2001) Interior Lining and Periodic Inspection of Underground Storage Tanks

    API Std 594 (1997) Check Valves: Wafer, Wafer-Lug and Double-Flanged Type

    API Std 610(2003) Centrifugal Pumps for Petroleum, Petrochemical, and Natural Gas Industries

    AMERICAN WELDING SOCIETY (AWS)

    AWS A5.1/A5.1M (2004) Carbon Steel Electrodes for Shielded Metal Arc Welding

    AWS A5.4 (1992; R 2000) Stainless Steel Electrodes for Shielded Metal Arc Welding

    ASME INTERNATIONAL (ASME)

    ASME B16.11 (2005) Forged Fittings, Socket-Welding and Threaded

    ASME B16.21 (2005) Nonmetallic Flat Gaskets for Pipe Flanges

    ASME B16.3 (1998) Malleable Iron Threaded Fittings

    ASME B16.34 (2004) Valves Flanged, Threaded, and Welding End

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 1

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    ASME B16.39 (1998) Malleable Iron Threaded Pipe Unions

    ASME B16.5 (2003) Pipe Flanges and Flanged Fittings

    ASME B16.9 (2003) Factory-Made Wrought Steel Buttwelding Fittings

    ASME B31.3 (2004) Process Piping

    ASME B40.100 (2000) Pressure Gauges and Gauge Attachments

    ASME BPVC SEC IX (2004) Boiler and Pressure Vessel Code; Section IX, Welding and Brazing Qualifications

    ASME BPVC SEC VIII D1 (2004) Boiler and Pressure Vessel Code; Section VIII, Pressure Vessels Division 1 - Basic Coverage

    ASTM INTERNATIONAL (ASTM)

    ASTM A 167 (2004) Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip

    ASTM A 181/A 181M (2001) Carbon Steel Forgings, for General-Purpose Piping

    ASTM A 182/A 182M (2005) Forged or Rolled Alloy-Steel Pipe Flanges, Forged Fittings, and Valves and Parts for High-Temperature Service

    ASTM A 193/A 193M (2005) Alloy-Steel and Stainless Steel Bolting Materials for High-Temperature Service

    ASTM A 194/A 194M (2005) Carbon and Alloy Steel Nuts for Bolts for High Pressure or High Temperature Service or Both

    ASTM A 216/A 216M (2004) Steel Castings, Carbon, Suitable for Fusion Welding, for High-Temperature Service

    ASTM A 234/A 234M (2005) Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and High Temperature Service

    ASTM A 27/A 27M (2005) Steel Castings, Carbon, for General Application

    ASTM A 276 (2005) Stainless Steel Bars and Shapes

    ASTM A 307 (2004) Carbon Steel Bolts and Studs, 60 000 PSI Tensile Strength

    ASTM A 356/A 356M (2004) Steel Castings, Carbon, Low Alloy,

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 2

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    and Stainless Steel, Heavy-Walled for Steam Turbines

    ASTM A 36/A 36M (2005) Carbon Structural Steel

    ASTM A 53/A 53M (2004a) Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless

    ASTM A 733 (2003) Welded and Seamless Carbon Steel and Austenitic Stainless Steel Pipe Nipples

    ASTM A 743/A 743M (2003) Castings, Iron-Chromium, Iron-Chromium-Nickel, Corrosion Resistant, for General Application

    ASTM B 687 (1999) Brass, Copper, and Chromium-Plated Pipe Nipples

    ASTM D 229 (2001) Rigid Sheet and Plate Materials Used for Electrical Insulation

    ASTM F 1172 (1988; R 2004) Fuel Oil Meters of the Volumetric Positive Displacement Type

    ASTM F 1199 (1988; R 2004) Cast (All Temperatures and Pressures) and Welded Pipe Line Strainers (150 psig and 150 degrees F Maximum)

    ASTM F 1200 (1988; R 2004) Fabricated (Welded) Pipe Line Strainers (Above 150 psig and 150 degrees F)

    ASTM F 436 (2004) Hardened Steel Washers

    MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS INDUSTRY (MSS)

    MSS SP-58 (2002) Pipe Hangers and Supports - Materials, Design and Manufacture

    MSS SP-69 (2002) Pipe Hangers and Supports - Selection and Application

    NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

    NEMA 250 (2003) Enclosures for Electrical Equipment (1000 Volts Maximum)

    NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

    NFPA 30 (2003) Flammable and Combustible Liquids Code

    NFPA 30A (2003) Code for Motor Fuel Dispensing Facilities and Repair Garages

    NFPA 70 (2005) National Electrical Code

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 3

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)

    SSPC SP 6 (2000; R 2004) Commercial Blast Cleaning

    UNDERWRITERS LABORATORIES (UL)

    UL 142 (2002) Steel Aboveground Tanks for Flammable and Combustible Liquids

    UL 2085 (1997; Rev thru Dec 1999) Protected Aboveground Tanks for Flammable and Combustible Liquids

    UL 567 (2003) emergency Breakaway Fittings, Swivel Connectors and Pipe-Connection Fittings for Petroleum Products and LP-Gas

    UL 913 (2002; Rev thru Dec 2003) Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, and III, Division 1, Hazardous (Classified) Locations

    1.2 SYSTEM DESCRIPTION

    The work shall include the design, fabrication and installation of the entire fuel storage and dispensing type system in conformance with pertinent federal, state, and local code requirements. The completed installation shall conform to NFPA 30 and NFPA 30A as applicable.

    1.3 SUBMITTALS

    Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. The following shall be submitted in accordance with Section 01330 SUBMITTAL PROCEDURES:

    SD-02 Shop Drawings

    Fueling System; G

    Detail drawings of the fueling system including a complete list of equipment and materials, as specified.

    Monitoring Systems; G

    Detail drawings of the monitoring system including a complete list of equipment and materials, as specified.

    SD-03 Product Data

    Fueling System; G

    Manufacturer's standard catalog data, prior to the purchase or installation of the particular component, highlighted to show brand name, model number, size, options, performance charts and curves, etc., in sufficient detail to demonstrate compliance with contract requirements on all parts and equipment.

    Permitting

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 4

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    Three copies of all required federal, state, and local permits.

    Registration

    Required tank registration forms, 30 days after contract award, in order for the Contracting Officer to submit the forms to the regulatory agency.

    Spare Parts Data

    Spare parts data for each different item of equipment specified.

    Installation

    Manufacturer's installation instructions and procedures on all parts and equipment.

    Demonstrations; G

    A letter, at least 14 working days prior to the proposed training date, scheduling a proposed date for conducting the onsite training.

    Welding

    A letter listing the qualifying procedures for each welder. The letter shall include supporting data such as test procedures used, what was tested to, etc., and a list of the names of all qualified welders and their identification symbols.

    Verification of Dimensions

    A letter stating the date the site was visited and a listing of all discrepancies found.

    Fuel Supply

    A letter, at least 60 days prior to fuel delivery, stating the amount of fuel required for testing, flushing, cleaning, or startup of the system. The letter shall define the required dates of each fuel delivery necessary.

    SD-06 Test Reports

    Tests; G

    Six copies of each test containing the information described below in bound letter-size booklets. Individual reports shall be provided for the storage tank tests, the piping tests, the system performance tests, the high level alarm test, and the system leak tests. Drawings shall be folded blue lines, with the title block visible.

    a. The date the tests were performed.

    b. A list of equipment used, with calibration certifications.

    c. A copy of measurements taken.

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 5

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    d. The parameters to be verified.

    e. The condition specified for the parameter.

    f. The inspection results, signed, dated, and certified by the installer. The certification shall state that required procedures were accomplished, that the procedures were conducted in compliance with the plans and specifications.

    g. A description of adjustments performed.

    SD-10 Operation and Maintenance Data

    Operation and Maintenance Manuals

    Six complete copies of operation manuals in bound letter-size booklets listing step-by-step procedures required for system startup, operation, and shutdown at least two weeks prior to the demonstrations. The manuals shall include the manufacturer's name, model number, service manual, a brief description of each piece of equipment, and the basic operating features of each piece of equipment. The manuals shall include procedures necessary for annual tightness testing of the storage tanks and secondary containment piping.

    Six complete copies of maintenance manuals in bound letter-size booklets listing routine maintenance procedures, possible breakdowns and repairs, and a trouble shooting guide at least 2 weeks prior to the demonstrations. The manuals shall include piping, equipment layouts, and simplified wiring and control diagrams of the system as installed.

    1.4 QUALIFICATIONS

    1.4.1 Experience

    Each installation Contractor shall have successfully completed at least 3 projects of the same scope and the same size or larger within the last 6 years. Each installation Contractor shall demonstrate specific installation experience in regard to the specific system installation to be performed. Each installation Contractor shall have taken, if applicable, manufacturer's training courses on the installation of piping, leak detection, and tank management systems and meet the licensing requirements in the state.

    1.4.2 Welding

    Welding shall be in accordance with qualifying procedures using performance qualified welders and welding operators. Welding tests shall be performed at the work site. Procedures and welders shall be qualified in accordance with ASME BPVC SEC IX. Each welder or welding operator shall apply his assigned symbol near each weld he makes as a permanent record. Structural members shall be welded in accordance with Section 05090 WELDING, STRUCTURAL.

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 6

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    1.5 REGULATORY REQUIREMENTS

    1.5.1 Permitting

    Contractor shall obtain necessary permits in conjunction with the installation of belowground storage tanks as required by federal, state, or local authority.

    1.5.2 Registration

    Contractor shall obtain and complete all required tank registration forms required by federal, state, and local authorities.

    1.6 DELIVERY, STORAGE, AND HANDLING

    Stored items shall be protected from the weather and contamination. Proper protection and care of material before, during, and after installation shall be the Contractor's responsibility. Any materials found to be damaged shall be replaced at the Contractor's expense. During installation, piping and similar openings shall be capped to keep out dirt and other foreign matter.

    1.7 PROJECT/SITE CONDITIONS

    1.7.1 Verification of Dimensions

    After becoming familiar with all details of the project, the Contractor shall verify dimensions in the field, and advise the Contracting Officer of any discrepancy before performing any work.

    1.7.2 Fuel Supply

    Fuel required for the flushing, cleaning, and testing of materials, equipment, piping, meters, pumps, instruments, etc., as specified in this section shall be provided by the Contracting Officer. Fuel will be provided by tank trucks. The Contracting Officer will furnish the tank trucks, operators, equipment, and services required for the tank truck operations. The Contractor shall provide the labor, equipment, appliances, and materials required for the flushing, cleaning, and testing operations. Systems shall not be flushed, cleaned, or tested with any fuel or liquid not intended for final system operation. Fuel used in the system shall remain the property of the Government. Fuel shortages not attributable to normal handling losses shall be reimbursed to the Government.

    1.7.3 Safety Requirements

    Exposed moving parts, parts that produce high operating temperatures and pressures, parts which may be electrically energized, and parts that may be a hazard to operating personnel shall be insulated, fully enclosed, guarded, or fitted with other types of safety devices. Safety devices shall be installed so that proper operation of equipment is not impaired.

    1.7.4 Spare Parts Data

    The Contractor shall submit spare parts data for each different item of equipment specified, after approval of detail drawings and not later than three months prior to the date of beneficial occupancy. The data shall include a complete list of parts and supplies, with current unit prices and source of supply, a recommended spare parts list for 1 year of operation,

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 7

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    and a list of the parts recommended by the manufacturer to be replaced on a routine basis.

    1.7.5 Detail Drawings

    1.7.5.1 Fueling System

    The Contractor shall submit detail drawings containing the following:

    a. Complete piping and wiring drawings and schematic diagrams of the overall system.

    b. Equipment layout and anchorage.

    c. Clearances required for maintenance and operation.

    d. Any other details required to demonstrate that the system has been coordinated and will properly function as a unit.

    1.7.5.2 Monitoring Systems

    The Contractor shall submit detail drawings containing the following:

    a. An overview drawing which details the leak detection system operation.

    b. An overview drawing which details the liquid level and setpoint monitoring.

    c. Wiring schematics for each part of the fueling system. The schematics shall indicate each operating device along with their normal ranges of operating values (including pressures, temperatures, voltages, currents, speeds, etc.).

    d. Single line diagrams of the system.

    e. Panel layout along with panel mounting and support details.

    PART 2 PRODUCTS

    2.1 STANDARD PRODUCTS

    Materials and equipment shall be standard products of a manufacturer regularly engaged in the manufacturing of such products, which are of a similar material, design and workmanship. The standard products shall have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2 year use shall include applications of equipment and materials under similar circumstances and of similar size. The 2 years experience shall be satisfactorily completed by a product which has been sold or is offered for sale on the commercial market through advertisements, manufacturer's catalogs, or brochures. Products having less than a 2 year field service record will be acceptable if a certified record of satisfactory field operation, for not less than 6000 hours exclusive of the manufacturer's factory tests, can be shown. Products shall be supported by a service organization. System components shall be environmentally suitable for the indicated locations. The completed installation shall conform to the applicable requirements of NFPA 30 or NFPA 30A, as applicable.

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 8

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    2.2 NAMEPLATES

    Parts and equipment specified herein shall have an attached nameplate to list the manufacturer's name, address, component type or style, model or serial number, catalog number, capacity or size, and the system which is controlled. Plates shall be durable and legible throughout equipment life. Plates shall be fixed in prominent locations with nonferrous screws or bolts.

    2.3 ELECTRICAL WORK

    Electrical equipment, motors, and wiring shall be in accordance with Section 16402 INTERIOR DISTRIBUTION SYSTEM. Electrical bonding of materials shall be performed in accordance with NFPA 70.

    2.4 MATERIALS IN CONTACT WITH FUEL

    Galvanized materials shall not be allowed in direct contact with any fuel.

    2.5 ABOVEGROUND STORAGE TANK

    2.5.1 Secondarily Contained (Steel Vaulted) Tank

    Tank system shall include a primary storage tank and an integral fully-enclosed secondary containment reservoir. Tank system shall be in accordance with NFPA 30 and NFPA 30A. Tank system shall be designed and manufactured for horizontal installation. Primary storage tank shall be constructed of single wall steel in accordance with UL 142. Containment reservoir shall be single-wall steel conforming to UL 142. The interstitial space between the storage tank and the containment reservoir shall be filled with a 2-hour fire rated inhibitor in accordance with UL 2085. Tank system shall bear the UL 2085 label. The volume of the containment reservoir shall be greater than or equal to 110 percent of the primary tank volume. The primary storage tank shall be supported within the containment reservoir with steel tank saddles, or other similar supports, fabricated and attached by the tank manufacturer. Tank system shall be skid mounted and provided with lifting lugs which allow tank system relocation.

    2.5.2 Tank Exterior Protective Coating

    Tank exterior protective coating shall be the manufacturer's standard except as modified herein.

    2.5.3 Tank Interior Protective Coating

    Tank shall be provided with an interior protective coating in accordance with API Std 1631 from the tank bottom up to 3 feet off the bottom.

    2.5.4 Tank Manway

    Tank manway shall be provided with a manway cover and an interior tank ladder. Tank manway shall have an internal diameter of 24 inches. Tank manway shall be provided with a matching flanged watertight manway cover. Manway covers shall be constructed of cast steel in accordance with ASTM A 27/A 27M, grade 60-30 as a minimum. Manhole covers shall be for nontraffic. Interior tank ladder shall be constructed of either fiberglass or steel. If steel, the ladder shall be completely coated in the same fashion as the interior tank bottom coating. The two stringers shall be a

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 9

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    minimum 3/8 inch thick and a minimum 2 inches wide. The rungs shall be a minimum 3/4 inch rod on 12 inch centers. Members of the ladder shall be securely affixed. Ladder shall be of sufficient length to extend from the bottom of the tank to the top surface of the tank. Ladder shall be rigidly connected to the tank bottom in accordance with the tank manufacturer's standard. Ladder shall be connected to the top of the tank with pipe guides or slip bars to accommodate expansion of the two stringers.

    2.5.5 Tank Piping Penetrations

    The number and size of tank piping penetrations shall be provided as indicated. Pipe connections to a tank shall be through welded-in-place double tappered NPT couplings. The termination of fill lines within a tank shall be provided with an antisplash deflector.

    2.5.6 Tank Cleanout and Gauge Connection

    Tank shall be provided with a combination cleanout and gauge connection. The connection shall consist of a 2 inch pipe extending downward through the top of the tank to within 3 inches of the tank bottom. The entire length of pipe inside the tank shall be provided with 1/2 inch wide by 12 inches long slots at alternate locations. The top of the pipe shall be provided with a bronze top-seal type adapter with a corresponding locking type cap. Tank shall have an interior striker/impact plate attached directly under the cleanout and gauge connection. The striker/impact plate shall be a minimum of 1/4 inch in thickness, be larger in diameter than the tank penetration, and fit the curvature of the tank bottom.

    2.5.7 Tank Atmospheric Venting

    Vent pipe shall be in accordance with NFPA 30, NFPA 30A, and UL 142. Vent pipe sizing shall be as indicated.

    2.5.8 Tank Emergency Venting

    Vent shall comply with NFPA 30. There is no vacuum relief requirement but the disc may be subjected to 3 ounces of vacuum. Discs shall be provided with a flanged end connection. Disc holder shall have a nameplate showing design rating.

    2.5.9 Tank Overfill Alarm System

    Tank shall be provided with an overfill alarm system. The system shall include a mechanically-actuated float actuator and an alarm panel. The float actuator shall be field adjustable. The alarm panel shall include an alarm light, an audible alarm, and reset capabilities. The alarm panel shall be mounted adjacent to the fill as indicated. The alarm panel shall initiate a minimum 70 decibel audible alarm when the liquid level within a tank reaches the 90 percent full level. The alarm system shall conform to the requirements of paragraph MONITORING SYSTEM.

    2.6 TANK GAUGES

    2.6.1 Stick Gauge

    Tank shall be provided with 2 stick gauges graduated in feet, inches, and eighths of an inch. Stick gauge shall be of wood and treated after graduating to prevent swelling or damage from the fuel being stored.

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 10

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    2.6.2 Tank Calibration Charts

    Tank shall be furnished with 2 copies of calibrated charts which indicate the liquid contents in gallons for each 1/8 inch of tank depth.

    2.6.3 Tank Gauge

    Each storage tank shall be provided with an automatic reading gauge which is directly mounted to a tank's manway cover. Gauge shall be a level sensing, mechanically actuated device which provides the necessary readout in a sealed glass cap contained in a gauge box. Gauge shall be accurate to plus or minus 1/4 inch and be capable of measuring the liquid level over the full range of a tank's height. Gauge shall have vapor tight seals to prevent condensate from fogging the viewing glass.

    2.6.4 Digital Tank Gauge System

    Gauge shall be electronically actuated and include a sending unit that transmits a digital signal to a liquid level electronic panel. The electronic panel shall be capable of providing a liquid level readout for each tank in terms of inches and gallons. Gauge shall be accurate to plus or minus 1/16 inch and be capable of measuring a tank's liquid level over a tank's full usable liquid level range. Gauge construction shall be compatible with the fuel to be handled. Gauge shall be capable of measuring water accumulation in inchesfrom 3/4 to 5 inches off the bottom of a storage tank. Gauge shall be capable of constantly sensing the fuel level in a storage tank as well as acknowledging 2 programmable liquid level setpoints. The electronic panel shall activate an audible and visual alarm when each setpoint is monitored. The 2 liquid level setpoints to be monitored shall include a tank's 90 percent liquid level (Setpoint 1) and a tank's 95 percent liquid level (Setpoint 2). The panel shall have a means of delineating between the individual setpoints and the individual tanks.

    2.7 ADAPTERS AND COUPLERS

    2.7.1 Tight-Fit Fill Adapter

    Adapter shall be bronze and be fitted with a Buna-N or Viton gasket. Adapter shall be the API standard 4 inch size. Adapter shall be a top seal adapter and provide a tight-fit connection to prevent vapor emissions during filling. The adapter shall be provided with a locking cap. The cap shall mate with the adapter and have a latching mechanism which provides a water tight seal. The cap shall provide some type of locking provision and be easily attachable and removable. The cap shall be attached to the tight-fit vapor recovery adapter by a 12 inch section of brass cable or fuel resistant rope.

    2.7.2 Dry-Break Coupler

    Coupler shall be an API standard and provide a tight-fit connection to prevent vapor emissions during fuel transfer. Coupler shall be compatible with the fuel product being handled and be a female connection. Seals within the coupler shall be Buna-N or Viton. Coupler shall have an internal manually operated shutoff valve. The valve shall have an external operating handle with the valve's position (open or close) clearly labeled. The internal valve shall not be capable of being manually opened unless the coupler is properly connected to a tank truck's tight-fit adapter.

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 11

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    2.8 PUMPS

    Mechanical seals within the pump shall be Buna-N or Viton. Pump casing and bearing housing shall be ductile iron. Impeller shall be aluminum ASTM A 356/A 356M and impeller shaft shall be stainless steel ASTM A 743/A 743M. Pump shaft shall be stainless steel ASTM A 276 Type 410 or 416. Pump baseplate shall be of cast iron construction. Internal pump components in direct contact with the fuel to be handled shall be of compatible construction. Pump assembly shall be statically and dynamically balanced for all flow rates from no flow to 120 percent of design flow. Pump bearings shall be selected to give a minimum L-10 rating life of 25,000 hours in continuous operation. Pump shall be driven by an explosion-proof motor for Class I, Division l, Group D hazardous locations as defined in NFPA 70. Pump shall be accessible for servicing without disturbing connecting piping. Pump control panel shall include on and off indication lights for each pump. The panel shall contain an adjustable control logic for pump operation in accordance with the indicated operation. The panel shall also have a manual override switch for each pump to allow for the activation or deactivation of each pump. Panel, except as modified herein, shall be in accordance with Section 16402 INTERIOR DISTRIBUTION SYSTEM.

    2.8.1 In-Line Centrifugal Pump

    Pump shall be the in-line, split-case, double suction, single stage, self-priming, centrifugal type. Pump motor shall be mounted horizontal to the pump housing and be provided with flanged end connections.

    2.8.2 Submersible Pump

    Pump shall be a multi- stage vertical pump and extend inside the tank to within 6 inches of the striker/impact plate. Pump and motor combination shall operate totally submerged in the product of the storage tank. Pump fuel inlets shall be horizontal. Pump, motor, and column pipe assemble shall mount through a NPT pipe penetration in a tank's manway cover. Pump mounting shall completely support both the weight and vibration of the pump. The unit shall be provided with a steel lifting lug capable of supporting the weight of the entire pump and motor assembly. Pump shall include a vertical solid shaft motor, base mounting flange, horizontal pump discharge, low net positive suction head (NPSH) first stage impellers, dynamic and thrust balancing of impellers, and a stainless steel one piece pump shaft. Pump shall be provided with threaded end piping connections.

    2.9 SUPPLEMENTAL COMPONENTS

    2.9.1 Piping Containment Sump

    Sump shall be constructed of fiberglass reinforced plastic and be chemically compatible with the fuels to be handled. Sump shall not be connected in any way to the street manway cover or concrete above. The top of a containment sump shall be capped with a friction fit access cover. Cover shall be constructed of the same material as the sump. Cover shall have a minimum diameter of 22 inches. Cover shall be easily removable through the street manway above. Rainfall drainage from the street manhole above shall not drain into a sump. Sump shall be capable of withstanding underground burial loads to be encountered. The sides of a containment sump shall allow the penetration of carrier pipes, exterior containment pipes, conduits, and vapor pipes as required. Penetrations in the containment sump sides shall be booted or sealed to ensure that liquid will

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 12

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    not escape from the sump in the event that the liquid level within the sump rises above the pipe penetration. Boots and seals used shall be compatible with the fuel to be handled. Boots and seals shall be water resistant to the influx of ground water. Boots and seals shall be designed and installed to accommodate the anticipated amount of thermal expansion and contraction in the piping system.

    2.9.2 Fuel Oil Meter

    Meter shall be the volumetric positive displacement type in accordance with ASTM F 1172, except as modified herein. Meter shall indicate the fuel oil flow rate in gpm. Meter shall be provided with overspeed protection and a water escape hole. If meter is not mounted in-line with the piping, then the Contractor shall provide an appropriate pedestal for mounting. Meter installation shall be in accordance with manufacturer's recommendations.

    2.9.3 Electrically Isolating Flanges

    Flanges shall be provided with an electrical insulating material of 1000 ohms minimum resistance conforming to ASTM D 229. The material shall be resistant to the effects of the type of fuel to be handled. Gaskets shall be full face and be provided between flanges. Flanges shall have full surface 0.03 inch thick, spiral-wound mylar insulating sleeves between the bolts and the holes in the flanges. Bolts may have reduced shanks of a diameter not less than the diameter at the root of the threads. High-strength 1/8 inch thick phenolic insulating washers shall be provided next to the flanges with flat circular stainless steel washers over the insulating washers. Bolts shall be long enough to compensate for the insulating gaskets and stainless steel washers.

    2.9.4 Electrically Isolating Union

    Union shall be provided with an electrical insulating material of 1000 ohms minimum resistance conforming to ASTM D 229. The material shall be resistant to the effects of the type of fuel to be handled.

    2.9.5 Concrete Anchor Bolts

    Concrete anchor bolts shall be group II, Type A, class 2 in accordance with ASTM A 307.

    2.9.6 Bolts

    Bolts shall be in accordance with ASTM A 193/A 193M, Grade B8.

    2.9.7 Nuts

    Nuts shall be in accordance with ASTM A 194/A 194M, Grade 8.

    2.9.8 Washers

    Washers shall be in accordance with ASTM F 436, flat circular stainless steel. Washers shall be provided under each bolt head and nut.

    2.9.9 Exterior Coating of Miscellaneous Items

    Steel surfaces to be externally coated or painted shall be cleaned to a commercial grade blast cleaning finish in accordance with SSPC SP 6 prior to the application of the coating. Exterior surfaces, other than stainless

    Record Specs Property of the United States Government SECTION 1320202/05/10 UNCLASSIFIED // FOR OFFICIAL USE ONLY Page 13

  • Sweet Tea Property of the United States Government 41695ABFort Gordon UNCLASSIFIED // FOR OFFICIAL USE ONLY

    steel pipe and flexible connectors, which are not otherwise painted and do not require the application of an exterior coating, as well as all items supplied without factory-applied finish paint, not including primer only items, shall be painted as specified in Section 09900 PAINTS AND COATINGS.

    2.9.10 Buried Utility Tape

    Detectable aluminum foil plastic-backed tape or detectable magnetic plastic tape shall be provided for warning and identification of buried piping. Tape shall be detectable by an electronic detection instrument. Tape shall be provided in minimum 3 inch width rolls, color coded for the utility involved, with warning identification imprinted in bold black letters continuously and repeatedly over entire tape length. Permanent code and letter coloring shall be used which is unaffected by moisture and other substances contained in trench backfill material.

    2.10 BULK FUELING

    2.10.1 Fueling Hose

    Hose shall be in accordance with API Std 1529, Grade 3, Type A or C, semi-hardwall. Hose shall be compatible with the specified fuel and withstand a working pressure of 300 psig. Hose shall be constructed of braided synthetic cord surrounded by an interior rubber tube and an exterior rubber cover. Each fueling hose shall be provided with a stainless steel hose tray. The hose tray shall provide support for the entire length of the fueling hose, allow for draining of rainwater, support the fueling hose at the height indicated, protect the hose from the sun's ultraviolet rays, and allow for easy insertion and removal of the fueling hose

    2.10.2 Fuel Meter For Truck Fill Stand

    Meter shall be of the continuous duty, positive displacement, straight-through flow type, designed for outdoor installation. Meter shall be capable of handling diesel fuel, at a flow rate of 300 gpm. Meter shall be constructed of either