990-1427A 07/2003
®®®®
Receiving & Unpacking Guide
Symmetra PX 80 kW 208/400 V
1 System Components
Symmetra® PX
10 - 40 kW, 200 V
Basic Opera
tion Guide
DOCUMENT STORAGE
?
5.2”/132 mm
27.5”/700 mm19”/483 mm
82”/2080 mm
36”/915 mm
24”/610 mm
UPS (Empty)650 lb./295 kg
Power Module60 lb./26 kg
2 Important Safety InstructionsSAVE THESE INSTRUCTIONSThis guide contains important instructions that should be followed when handling the Symmetra PX UPS, Battery Enclosures, and Batteries.
Symbols used in this Guide
Weight Symbols
3 Receiving UPS Frame & Modules/Removal of Plastic & Corner Protection
Indicates important information.
Indicates a heavy load that should not be lifted without assistance.
Indicates that more information is available on this subject in a different section of this manual.
Do not lift heavy loads without assistance.
<40 lb.<18 kg
40 - 70 lb.18 - 32 kg
70 - 120 lb.32 - 54 kg
>120 lb.>54 kg
Inspect shipment and verify that labeled boxes match purchase order.
If any shipping damage has been detected, contact APC (see Customer Support in this guide).
Shipping materials are recyclable. Please re-use or dispose of appropriately.
Symmetra PX 10-80 kW Receiving & Unpacking
4 Moving to Installation SiteDoorway Clearance (for UPS on pallet)
Symmetra TM
PXQuick-Start User Guide
Symmetra TM
PXQuick-Start User Guide
Ramp
If UPS height exceeds doorway height, remove from pallet and wheel through door (see Removing from Pallet Section).
47 in. (1200 mm)
91” (2300 mm)
Symmetra PX 10-80 kW Receiving & Unpacking Guide
5 Removing from Pallet
Symmetra PXQuick-Start User Guide
Use 13/14 mm wrench (shipped with unit) for the removal of ship-ping brackets and adjustment of stabilizing feet
Place ramp as shown, aligning strips on ramp with strip on front edge of pallet
Remove card-board cover and bag
Remove 13 mm hex bolts (4 brackets)
VelcroStrips
VelcroStrips
1
2
3
Two people to rollUPS from pallet
4
Doorway Clearance for UPS
6 Operating Space
>82” / 2080 mm
>24” >610 mm Center of Gravity
(UPS Emty)
The UPS is heavy: 1166 lb/529 kg in maximum configuration. Ensure that the floor can support the total weight of the configuration when concentrated on the stabilizing feet.
Proceed to the Electrical Installation Guide. If you have purchased any optional equipment, refer to applicable guides.
UPS
24” / 610 mm
36” / 915 mm (208 V) 700 mm (400 V)
36” / 915 mm
36” / 915 mm (208 V) 700 mm (400 V)
MinimumFront Clearance
MinimumRear Clearance
Stabilizing Feet
Symmetra PX 10-80 kW Receiving & Unpacking
Operating Environment
7 Customer Support
Install the UPS in an Indoor, Controlled Environment
TemperatureRange:
32°-104°F/0°-40° C
Keep Ventilated
Front-to-RearAirflow
RelativeHumidity: <95%Non-condensing
No Conductive Dust or
Corrosive Fumes
Max. Elevation:
0-10,000 ft./0-3,000 m
Full Load Loss at Nominal Mains: 23,743 BTU/hr (6,957 Watts)
Country Customer Support Country Customer
Support
AustriaBelgiumCzech RepublicDenmarkFinlandFranceGermanyGreeceHungaryIrelandIsraelItalyLuxemburgNetherlandsNorway
0800 99967000800 0272 04790800 10206300800 0272 04799800 11530800800 0272 047900800 0272 047900800 1259240640 20026200800 0272 04791800 945220600800 0272 04790800 2209100800 0272 047900800 0272 0479
PolandPortugalRussiaSlovak RepublicSouth AfricaSpainSwedenSwitzerlandTurkeyUKUkraineUSA & North AmericaOther CountriesFaxeSupport
0801 34591700800 0272 04798800 20027220800 1720630861 27287700800 0272 047900800 0272 04790800 1114690800 261213500800 0272 04790800 50272201 877 537 0607353 91 702055353 91 755275http://www.apcc.com/support